9-COUNTRY CLUB WATER TANK DRAWINGS.pdf
PDF 10 MB Posted
- Attached to
- IFB - COUNTRY CLUB WATER TANK
- Solicitation number
- 26-276
- Issued by
- Washington County, Utah
About this file
This is a set of construction drawings and design documents prepared by Jones & DeMille Engineering, Inc. for the City of St. George, Utah, detailing the specifications for a 2.5 million-gallon (MG) concrete water tank to be constructed at the Country Club site in St. George. The project encompasses site preparation, excavation, water main installation, and associated infrastructure including a 150-foot-diameter concrete storage tank with finished floor elevation at 2,750 feet. The design includes 425 feet of 16-inch PVC water outflow line, 425 feet of 14-inch PVC water inflow line, 242.25 feet of 18-inch PVC drain pipe, overflow systems, a 15.5-foot by 13.5-foot concrete water vault, access roads, erosion control measures, power infrastructure, and a 6-foot-diameter concrete manhole. The drawings indicate total earthwork requirements of approximately 27,000 cubic yards of cut and 1,900 cubic yards of fill, with construction to conform to the 2017 APWA Utah Chapter specifications, International Building Code (IBC), and City of St. George standards. The project is for bidding only, with all work requiring coordination with the City of St. George Water Department, utilities locating, and adherence to geotechnical recommendations based on a May 23, 2023 site investigation by Landmark Testing & Engineering.
The City of St. George requires that all bids be accompanied by a bid bond in the amount of 5 percent of the total bid amount, issued by a surety company licensed in Utah and acceptable to the city. A 100 percent performance bond covering labor and materials is mandatory upon project award. The design documents specify that all waterline works must be installed by a contractor pre-qualified by the City of St. George Water Department and that all construction shall conform to the city's Standard Specifications for Design and Construction, the International Plumbing Code, and the Uniform Building Code. Structural design is based on ACI 318-19 and ACI 350-20 standards with a design bearing pressure of 5,000 pounds per square foot on sandstone bedrock. The city reserves the right to reject any or all submissions or waive any formality or technicality in its interest. All special inspections, materials testing, geotechnical observation during construction, and quality assurance inspections are required, with costs to be borne by the contractor.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Map data (c) OpenStreetMap contributors, Microsoft, Facebook, Google, Esri Community Maps contributors, Map layer by Esri Powered by Esri
CITY OF ST. GEORGE
COUNTRY CLUB 2.5 MG TANK
ST. GEORGE, UTAH
h:
\2
7-
6\ dw g\ de si gn _2
7-
VICINITY MAP
Jones & DeMille Engineering, Inc.
1.800.748.5275 www.jonesanddemille.com
GIS - ENVIRONMENTAL - MATERIALS TESTING
CIVIL & STRUCTURAL ENGINEERING - SURVEYING
- shaping the quality of life -
PROJECT LOCATION APPROVAL
RECOMMENDED FOR APPROVAL:
DATE
APPROVED:
DATECLIENT
2207-026 G-001
SHEET NO.PROJECT NO.
SUBMITTAL: FOR BIDDING ONLY
IDAHO
C O
LO
R
AD
O
ARIZONA
N
EV
AD
A
WASHINGTON KANE
SAN JUAN
GARFIELDIRON
BEAVER PIUTE WAYNE
GRANDEMERY
ST. GEORGE
SEVIER
MILLARD
SANPETE
CARBON
UINTAH
DUCHESNE
UTAH
WASATCH
SALT LAKE
JUAB
TOOELE
BOX ELDER
DAVIS
SUMMIT
MORGAN
WEBER
DAGGETT
RICH
CACHE
WYOMING
INDEX TO SHEETS
SHEET NO. SHEET TITLE
G-001 COVER SHEET
G-002 LEGEND & NOTES
C-101 SITE PLAN
C-102 TANK PLAN & PROFILE
C-401 EROSION CONTROL PLAN
C-501 CIVIL DETAILS
S-101 STRUCTURAL NOTES, PLANS, & SECTIONS
S-501 STRUCTURAL DETAILS
S-701 STRUCTURAL DETAILS & SCHEDULES
PROFESSIONA L ENGINEER
STATE OF UTAH
No. 12440204
CHAD
COFFEY
02/13/2026
G-002
CO
UN
TR
Y
CL
UB
.5
M G
T
AN
K
LE
G
EN
D
NO
TE
S
-0
2/
/2
_1 st nd rd
-ir
.c tb
-0
D
ES
IG
N
_2
7-
R
EV
IS
IO
N S
N O
D
AT
E
R
EV
. B Y
D
ES
IG
N
R
EM
AR
KS
O R
IG
IN
AL
S
U
BM
IS
SI
O N
F O
R A
U
TH
O R
IZ
AT
IO
N
SC
AL
E:
SH
T
SE
T:
PE
N
T
BL
PL
O
TT
ED
U
PD
AT
ED
SU
BM
IT
TA
L:
COUNTY
SHEET NO.
D W
G C
R
EA
TE
D
D
W G
N
AM
E:
G
IS
EN
VI
R
O N
M
EN
TA
L
- M
AT
ER
IA
LS
T
ES
TI
N G
1.
0.
8.
w w .jo ne sa nd de m ille
.c om
Jo ne s
D eM ille E ng in ee rin g, In c.
C
IV
IL
S
TR
U
C
TU
R
AL
E N
G
IN
EE
R
IN
G
SU
R
VE
YI
N
G
ST
AM
P:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
PR
O
JE
C
T N
U M
BE
R
2/
/2
N O
N E
WASHINGTON
ST
. G
EO
RG
E
CI
TY
FO
R
B
ID
D
IN
G O
N
LY
LEGEND
EDGE OF ASPHALT
EDGE OF CONCRETE
EDGE OF GRAVEL SURFACING
EDGE OF DIRT SURFACING
EDGE OF ASPHALT SURFACING
TOP BACK OF CURB
LIP OF CURB
TOP OF SIDEWALK
TOP OF CONCRETE
TOP OF GRATE
EDGE OF ASPHALT
FLOW LINE OF GUTTER
FLOW LINE OF CULVERT
SIDEWALK
FINISHED GROUND
TOP OF ASPHALT
CONCRETE SURFACING
ASPHALT SURFACING
STREET SIGN
TBC
LOC
TSW
TOC
TOG
EOA
FLG
FLC
SW
FG
TOA
SANITARY SEWER LINE
CULINARY WATER LINE
BURIED POWER LINE
FENCE LINE (BARBED OR STOCKTIGHT)
DRAINAGE CULVERT
FLOW LINE OF DITCH
BURIED TELEPHONE LINE
NATURAL GAS LINE
BURIED CABLE TV LINE
CULINARY WATER VALVE
SANITARY SEWER MANHOLE
TREE
CONCRETE SURFACING
DELINEATOR POST
PROPERTY LINE
IRRIGATION LINE
EXISTING RIGHT OF WAY LINE
SANITARY SEWER MANHOLE
CULINARY WATER VALVE
DRAINAGE CULVERT
CULINARY WATER LINE
SANITARY SEWER LINE
SECTION LINE
PROPOSED RIGHT-OF-WAY LINE
SUBDIVISION BOUNDARY LINE
LOT LINES
QUARTER SECTION LINE
(P.U.E.) PUBLIC UTILITY EASEMENT
DEED LINE
FIRE HYDRANT
FIRE HYDRANT
STRUCTURE
DELINEATOR POST
STREET SIGN
TOP OF CUT LIMITS
TOE OF FILL LIMITS
CULINARY WATER METER
WATER METER
POWER POLE & GUY WIRE
G.W.
STORM DRAIN
SANITARY SEWER SERVICE
POWER POLE
EXISTING FEATURES PROPOSED FEATURESMISC. FEATURES
(SIDEWALK, CURB, GUTTER, ETC.)
FENCE LINE (CHAIN LINK)
M
M
TELEPHONE PEDESTAL
OVERHEAD CABLE TV LINE
OVERHEAD POWER LINE
OVERHEAD TELEPHONE LINE
BURIED POWER LINE
OVERHEAD POWER LINE
BURIED TELEPHONE LINE
OVERHEAD TELEPHONE LINE
BURIED CABLE TV LINE
OVERHEAD CABLE TV LINE
NATURAL GAS LINE
IRRIGATION LINE
STORM DRAIN
FENCE LINE (BARBED OR STOCKTIGHT)
FENCE LINE (CHAIN LINK)
FIBER OPTIC LINE
FIBER OPTIC LINE
MAILBOX
MAILBOX
ABBREVIATIONS
POWER POLE
COMMUNICATION MANHOLE
RIGHT-OF-WAY
SEWER MANHOLE
LEFT
RIGHT
EPP
CMH
R/W
SMH
L / LT
R / RT
TEMPORARY T.C.E.
PUBLIC UTILITY EASEMENTP.U.E.
CONSTRUCTION EASEMENT
STATIONSTA
EXISTING CITY BLOCK LINES
BLOCK LINE
EXISTING N/A LINE
EPP
SMH SMH
EPP
WMH WATER MANHOLE
LIGHT POLE
LIGHT POLE
SCO
M GAS METER
GAS METERM
UTILITY NOTES
1. COORDINATE UTILITY CONNECTIONS AND SERVICES BEFORE STARTING CONSTRUCTION. STAGE CONSTRUCTION TO AVOID DELAYS IN SERVICES AND
PERMITTING.
2. PROVIDE UTILITY PIPING AND APPURTENANCES ACCORDING TO PROJECT SPECIFICATIONS AND IN LINE WITH APPROPRIATE JURISDICTIONAL SPECIFICATIONS
AND DETAILS.
3. SUBMIT TO THE ENGINEER FOR REVIEW AND ACCEPTANCE FOR BEDDING, BACKFILL, PIPE, METERS, BOXES, VALVES, FIRE HYDRANTS, BLOWOFFS, VAULTS, MANHOLES, INLET BOXES, ETC. ENSURE SUBMITTALS CONTAIN ENOUGH INFORMATION TO SHOW THAT PROPOSED PRODUCTS AND MATERIALS CONFORM TO
OWNER'S STANDARDS AND SPECIFICATIONS.
4. VERIFY RIM AND INVERT ELEVATIONS BEFORE FABRICATING MANHOLES, VAULTS, AND INLET BOXES.
5. ADJUST UTILITY MANHOLES, VALVE BOXES, AND OTHER BOXES AND CONSTRUCT CONCRETE COLLAR PER APWA OR OWNER SPECIFICATIONS WHEN WITHIN
PAVED OR OTHER IMPROVED AREAS.
6. PROVIDE TESTING RESULTS AS REQUIRED PER OWNER SPECIFICATION SUCH AS PRESSURE TESTING, DEFLECTION TESTING, AIR TESTING AND VIDEO
INSPECTIONS.
7. CLEAN UTILITY LINES TO REMOVE DIRT AND DEBRIS BEFORE BEING PUT INTO SERVICE. PROTECT DOWN-GRADE LINES FROM WASH-WATER DURING THE
CLEANING PROCESS TO AVOID CONTAMINATION AND COMPROMISING OUTFALL CLEANLINESS.
8. ENSURE ALL UTILITY PIPES, APPURTENANCES, AND STRUCTURES ARE OF NEW MATERIAL. REUSED MATERIAL MAY BE PERMITTED AS INDICATED ON PLANS.
9. PROVIDE THRUST BLOCKS AND/OR JOINT RESTRAINTS AS REQUIRED BY CITY OF ST. GEORGE STANDARDS AND SPECIFICATIONS. INSTALL JOINT RESTRAINTS ON MECHANICAL JOINT FITTINGS AND ON PIPE JOINTS FOR THE REQUIRED LENGTH SPECIFIED FOR EACH JOINT CONDITION.
EROSION CONTROL NOTES
1. PREPARE AND SUBMIT STORM WATER POLLUTION PREVENTION PLAN (SWPPP). FILE NOTICE OF INTENT (NOI) PRIOR TO STARTING CONSTRUCTION AND FILE
NOTICE OF TERMINATION (NOT) AT END OF CONSTRUCTION.
2. ADHERE TO UTAH POLLUTION DISCHARGE ELIMINATION SYSTEM (UPDES) REGULATIONS DURING CONSTRUCTION WORK.
3. PREVENT AND CONTROL EROSION DUE TO WIND AND WATER DURING CONSTRUCTION. FOLLOW PROCEDURES AND BEST MANAGEMENT PRACTICES IN SWPPP AND INSTALL EROSION CONTROL MEASURES AS INDICATED IN SWPPP. MAINTAIN A COPY OF THE SWPPP ON SITE AT ALL TIMES.
4. PROVIDE ADDITIONAL EROSION CONTROL MEASURES WHEN UNFORESEEN PROBLEMS OCCUR OR IF SWPPP DOES NOT FUNCTION AS INTENDED. ADJUST EROSION CONTROL MEASURES (SILT FENCES, STRAW BALES, ETC.) AS NEEDED DUE TO GRADE CHANGES DURING CONSTRUCTION. BE AWARE THAT OWNER
MAY REQUIRE ADDITIONAL CONTROL DEVICES UPON INSPECTION OF PROPOSED FACILITIES.
5. KEEP STREETS CLEAN AND FREE FROM SOIL AND DEBRIS DURING CONSTRUCTION.
6. PROTECT STORM DRAIN FACILITIES ON SITE AND ADJACENT TO SITE FROM SITE RUNOFF. INSTALL INLET PROTECTION DEVICES IMMEDIATELY WHEN
INDIVIDUAL INLETS BECOME FUNCTIONAL.
7. SEED AREAS DISTURBED DURING CONSTRUCTION WITH APPROPRIATE NATIVE SEED MIX OR PLACE LANDSCAPING TO MATCH EXISTING.
8. DISPOSE OF WASH WATER (CONCRETE TRUCKS, VEHICLE CLEANING, ETC.) IN A MANNER THAT PREVENTS CONTACT WITH STORM WATER DISCHARGES FROM
SITE.
9. STABILIZE CONSTRUCTION AREAS AT END OF EACH WORKING DAY. INCLUDE BACKFILLING OF TRENCHES FOR UTILITY CONSTRUCTION AND PLACEMENT OF
PAVING FOR ROAD CONSTRUCTION.
10.MAINTAIN MEASURES IN SWPPP IN FULLY FUNCTIONAL CONDITION UNTIL FINAL STABILIZATION OF SITE. CHECK EROSION AND SEDIMENTATION CONTROL MEASURES BY QUALIFIED PERSON AT LEAST ONCE EVERY SEVEN CALENDAR DAYS AND WITHIN 24 HOURS OF END OF RAINFALL EVENT. COMPLETE ANY NEEDED CLEANING AND REPAIRS WITHIN TIME FRAMES SPECIFIED IN SWPPP AND/OR UPDES GENERAL PERMIT.
11.POWER WASH EXCAVATION EQUIPMENT BEFORE ENTERING DIFFERENT VEGETATION MATRIX.
12.REMOVE INLET PROTECTION DEVICES AFTER N.O.T. AND FINAL ACCEPTANCE BY OWNER.
13.APPLY WATER FOR FUGITIVE DUST CONTROL BY MEANS OF TRUCKS, HOSES AND/OR SPRINKLERS AT SUFFICIENT FREQUENCY AND QUANTITY ACCORDINGLY:
13.1. PRIOR TO, CONCURRENTLY AND AFTER EARTHMOVING ACTIVITIES
13.2. TO DEPTH OF PROPOSED CUTS OR EQUIPMENT PENETRATIONS
13.3. PRIOR TO EXPECTED WIND EVENTS
13.4. TO DEVELOP A SURFACE CRUST FOR ALL INACTIVE SITES
14.MINIMIZE FUGITIVE DUST WITH APPROPRIATE VEHICLE HANDLING AND LOADING OPERATIONS.
15.INSTALL FENCE BARRIER AND/OR “NO TRESPASSING” SIGNS TO PREVENT ACCESS AND DISTURBANCE OF INACTIVE AREAS.
SURVEY NOTES
1. SUBJECT SITE WAS FIELD SURVEYED 01/05/2023 BY JONES AND DEMILLE ENGINEERING.
2. UNLESS OTHERWISE NOTED, ANY BOUNDARY LINES SHOWN ARE TO BE CONSIDERED DEED RECORD LINES. JDE HAS NOT PERFORMED AN OFFICIAL BOUNDARY
SURVEY AND NO RECORD OF SURVEY WILL BE FILED.
3. ANY COORDINATES AND ELEVATIONS, IF SHOWN, ARE LOCAL COORDINATES UNLESS OTHERWISE INDICATED.
4. DISTANCES REFLECT GROUND MEASUREMENTS.
5. NOTIFY ENGINEER IF CONTROL POINTS VARY MORE THAN 0.07-FEET.
CONSTRUCTION NOTES
1. NOTIFY OWNER AT LEAST TWO BUSINESS DAYS PRIOR TO BEGINNING CONSTRUCTION.
2. SCHEDULE AND ATTEND PRE-CONSTRUCTION MEETING PRIOR TO STARTING CONSTRUCTION ACTIVITIES THROUGH OWNER OR OWNER'S REPRESENTATIVE.
3. PROVIDE CONSTRUCTION SCHEDULE TO ENGINEER AND OWNER.
4. FIELD VERIFY EXISTING CONDITIONS. QUANTITIES, LENGTHS, VOLUMES, AND AREAS INDICATED ARE APPROXIMATE AND ARE PROVIDED TO ASSIST
CONTRACTOR. VERIFY QUANTITIES AND DETERMINE MEASUREMENTS AS NECESSARY.
5. VERIFY DIMENSIONS BEFORE STARTING WORK AND IMMEDIATELY NOTIFY ENGINEER OF ANY DISCREPANCIES.
6. OBTAIN APPROVAL FROM OWNER PRIOR TO CONSTRUCTION FOR USE OF STAGING AREAS (IF ANY) NOT SHOWN ON DRAWINGS. COORDINATE WITH OWNER TO IDENTIFY POTENTIAL USABLE STAGING AREAS. RESTORE STAGING AREA TO PRECONSTRUCTION CONDITION.
7. PROTECT EXISTING IMPROVEMENTS DURING CONSTRUCTION AND REPLACE OR RESTORE IMPROVEMENTS DAMAGED AS RESULT OF CONSTRUCTION ACTIVITY.
RESTORE IMPROVEMENTS TO AS-GOOD-AS OR BETTER-THAN CONDITION THAT EXISTED PRIOR TO CONSTRUCTION. REPAIR IRRIGATION/SPRINKLERS WITHIN
24 HOURS FOLLOWING PLACEMENT OF IMPROVEMENTS.
8. PROPERLY BACKFILL, COMPACT, AND RESTORE PAVEMENT WITHIN STREET RIGHT-OF-WAY.
9. DISPOSE WASTE OFF SITE AT LANDFILL OR OTHER LEGAL DISPOSAL FACILITY.
10.REMOVE SURPLUS EXCAVATION FROM SITE. USE TOPSOIL OR OTHER NATIVE MATERIAL IN LANDSCAPE OR NATIVE GRADING. STOCKPILE TOPSOIL SEPARATELY FROM OTHER EXCAVATED MATERIALS. PLACE TOPSOIL IN LANDSCAPED AREAS IN 4 INCHES THICK MINIMUM AND GRADE TO DRAIN.
11.PERFORM CONSTRUCTION QUALITY CONTROL TESTING, INCLUDING SOILS, BACKFILL CONCRETE, UTILITIES, ETC.
12.A GEOTECHNICAL REPORT OF THE SITE WAS PERFORMED BY LANDMARK TESTING & ENGINEERING ON MAY 23, 2023 AND SERVED AS THE BASIS FOR DESIGN.
1. UNDERSTAND ALL RECOMMENDATIONS FROM THE GEOTECHCNICAL ENGINEER AND NOTIFY THE DESIGN ENGINEER OF ANY DEVIATIONS IN DESIGN.
2. PERFORM ALL EXCAVATION, GRADING, AND OPERATIONS WITHIN THE BUILDING AREA UNDER OBSERVATION OF THE GEOTECHNICAL ENGINEER. ENSURE THE GEOTECHNICAL ENGINEER VERIFIES SUB-SOIL CONDITIONS, DETERMINES THE ADEQUACY OF SITE PREPARATION, ASSESSES THE SUITABILITY OF FILL, AND
CONFIRMS COMPLIANCE WITH COMPACTION REQUIREMENTS.
3. PROVIDE A GRADING COMPLETION REPORT BY THE GEOTECHNICAL ENGINEER TO CONFIRM THE WORK HAS BEEN PERFORMED ACCORDING TO THE
GEOTECHNICAL ENGINEER'S RECOMMENDATIONS.
13.PERFORM MATERIALS TESTING AND SUBMIT COPIES OF TEST RESULTS TO ENGINEER AND/OR OWNER AS REQUIRED PER SPECIFICATIONS. COORDINATE TESTING WITH INSPECTORS AND/OR ENGINEER. PERFORM DENSITY TESTING ON TRENCH BACKFILL, GRANULAR BORROW, AND UNTREATED BASE COURSE PLACEMENT FOR ROADWAY AND PRIOR TO ANY CONCRETE PLACEMENT WHERE NECESSARY. SEE SPECIFICATIONS FOR TESTING FREQUENCY.
14.PROVIDE SITE DUST CONTROL AND SUPPRESSION FOR DURATION OF PROJECT, INCLUDING WEEKENDS.
15.PROVIDE AND MAINTAIN ANY AND ALL TEMPORARY UTILITIES DURING CONSTRUCTION.
16.PROVIDE PAVEMENT MARKINGS, STRIPING AND SIGNAGE PER THE REQUIREMENTS OF THE LATEST EDITION OF THE MANUAL OF UNIFORM TRAFFIC CONTROL
DEVICES (MUTCD).
GENERAL NOTES
1. REQUEST ACCEPTANCE FROM ENGINEER PRIOR TO MAKING MODIFICATIONS TO DRAWINGS, SPECIFICATIONS, OR CONSTRUCTION SCHEDULE.
2. PERFORM CONSTRUCTION IN ACCORDANCE WITH LATEST VERSION (2017) OF APWA UTAH CHAPTER MANUAL OF STANDARD SPECIFICATIONS AND MANUAL OF STANDARD PLANS, INCLUDING AMENDMENTS, DDW RULES, INTERNATIONAL BUILDING CODE (IBC), INTERNATIONAL PLUMBING CODE (IPC), INTERNATIONAL FIRE CODE (IFC), INTERNATIONAL RESIDENTIAL CODE (IRC), APPLICABLE AUTHORITY HAVING JURISDICTION (AHJ) AND/OR OWNER STANDARDS AND SPECIFICATIONS.
3. IN CASE OF CONFLICT BETWEEN CODES, REFERENCE STANDARDS, STATE RULES, DRAWINGS AND SPECIFICATIONS, ADHERE TO MOST STRINGENT
REQUIREMENTS.
4. EXISTING UTILITIES ARE SHOWN IN APPROXIMATE LOCATIONS ONLY AND ARE BASED ON UTILITY MAPS AND FIELD SURVEY OF SURFACE EVIDENCE.
5. LOCATE AND PROTECT EXISTING UTILITIES AND ANY OBSTRUCTIONS DURING COURSE OF CONSTRUCTION. NOTIFY BLUE STAKES (811) AT LEAST 48 HOURS IN ADVANCE OF ANY CONSTRUCTION ACTIVITIES ON SITE. RESTORE UTILITIES DAMAGED DURING CONSTRUCTION TO CONDITION EQUAL TO OR BETTER THAN
EXISTING CONDITION PRIOR TO CONSTRUCTION.
6. NOTIFY ENGINEER OR PROJECT REPRESENTATIVE OF ANY CONFLICTS BETWEEN EXISTING FEATURES AND NEW CONSTRUCTION.
7. UNLESS DETAILED, SPECIFIED OR INDICATED OTHERWISE, CONSTRUCTION SHALL BE AS INDICATED IN APPLICABLE TYPICAL DETAILS AND GENERAL NOTES.
8. THE CONTRACTOR IS RESPONSIBLE FOR ALL ASPECTS OF SAFETY INCLUDING, BUT NOT LIMITED TO, EXCAVATION, TRENCHING, SHORING, TRAFFIC CONTROL
AND SECURITY.
9. MEET UTAH DEPARTMENT OF ENVIRONMENTAL QUALITY AND U.S. EPA REQUIREMENTS, RULES, AND REGULATIONS.
10.OBTAIN REQUIRED APPROVALS AND PERMITS AND PAY REQUIRED FEES PRIOR TO BEGINNING CONSTRUCTION.
11.FOR MATERIALS USED AND WORK PERFORMED IN UTAH DEPARTMENT OF TRANSPORTATION (UDOT) RIGHT-OF-WAY, CONFORM TO UDOT STANDARDS AND
SPECIFICATIONS.
12.CONDUCT CONSTRUCTION OPERATIONS WITH NECESSARY SIGNS, BARRICADES, AND FLASHERS PLACED TO COMPLY WITH OSHA, UTAH STATE INDUSTRIAL COMMISSION, LOCAL SAFETY STANDARDS, AND THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES.
13.NO FULL ROAD CLOSURES WILL BE PERMITTED WITHOUT PRIOR APPROVAL OF THE OWNER. MAINTAIN TRAFFIC IN TWO DIRECTIONS AT ALL TIMES FOR ROADS AND ROAD CROSSINGS, UNLESS EXTENUATING CIRCUMSTANCES PROHIBIT. MAKE ROAD CLOSURE REQUESTS 1 WEEK BEFORE NEEDING TO CLOSE ROAD.
14.PROVIDE WRITTEN NOTIFICATION INCLUDING CONTACT INFORMATION TO RESIDENTS AND BUSINESSES IMPACTED BY CONSTRUCTION. PROVIDE NOTICE MINIMUM OF 48 HOURS IN ADVANCE OF WORK BEING PERFORMED. MAINTAIN DRIVEWAY ACCESS TO RESIDENCES AND BUSINESSES AT ALL TIMES UNLESS PARKING ARRANGEMENTS HAVE BEEN MADE WITH RESIDENTS AND BUSINESSES WHILE WORK IS COMPLETED ADJACENT TO OR ON THEIR PROPERTIES.
15.WORK WITH INDIVIDUAL PROPERTY OWNERS OR BUSINESS FOR ACCESS AND PERMISSION TO CONNECT TO UTILITY SERVICE AT PROPERTIES.
16.SECURE RIGHT OF INGRESS AND EGRESS IF WORK OR PERSONNEL NEED TO VENTURE ONTO PRIVATE PROPERTY NOT INCLUDED IN OWNER ACQUIRED
RIGHTS-OF-WAY AND EASEMENTS.
17.ACQUIRE A COUNTY PERMIT PRIOR TO STARTING CONSTRUCTION FOR WORK LOCATED WITHIN 30 FEET OF A GOVERNMENT SURVEY MONUMENT OR PUBLIC
LAND SURVEY GOVERNMENT CORNER.
STORM WATER NOTES
1. FOLLOW IRC R401.3 FOR SITE DRAINAGE:
1. DIVERT SURFACE DRAINAGE TO STORM SEWER OR APPROVED POINT OF COLLECTION THAT DOES NOT CREATE HAZARD.
2. GRADE PROPERTY TO DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS.
3. GRADE 6 INCHES OF FALL WITHIN FIRST 10 FEET OF FOUNDATION PERIMETER.
4. WHERE PROPERTY LINES, SLOPES OR PHYSICAL BARRIERS PREVENT 6 INCHES OF FALL, CONSTRUCT DRAINAGE SWALES TO ENSURE DRAINAGE AWAY FROM
STRUCTURE.
5. SLOPE IMPERVIOUS SURFACES WITHIN 10 FEET OF BUILDING FOUNDATION MINIMUM OF 2% AWAY FROM BUILDING.
2. USE NON-SHRINK GROUT WHEREVER GROUT IS REQUIRED FOR STORM DRAIN FACILITIES.
3. CUT PIPES OFF FLUSH WITH INSIDE WALL OF BOX OR MANHOLE AND APPLY GROUT AT CONNECTION OF PIPE TO PROVIDE SMOOTH FINISH. REMOVE JAGGED
OR SHARP EDGES AT PIPE CONNECTIONS AND APPLY GROUT TO PROVIDE SMOOTH FINISH.
4. APPLY GROUT BETWEEN GRADE RINGS. FOR EACH INLET BOX THAT IS LOCATED NEXT TO CURB, REMOVE PROTRUDING, JAGGED OR SHARP CONCRETE EDGES AND APPLY GROUT BETWEEN BOTTOM OF INLET LID FRAME AND TOP OF CONCRETE BOX. FINISH GROUT TO CREATE SMOOTH, BEVELED TRANSITION AT EDGES IN CLEANOUT AND INLET BOXES. APPLY GROUT AROUND ALL EDGES OF RESTRICTIVE ORIFICE PLATE.
5. REMOVE SNAP TIES, NAILS, REBAR AND OTHER PROTRUSIONS FROM BOX OR PIPE INSIDE SURFACE, AND FROM FORM WORK, PLASTIC AND CARDBOARD.
6. REMOVE SILT AND DEBRIS FROM INLET BOXES, COMBO BOXES, JUNCTION BOXES, AND PIPE. MAINTAIN BOXES AND PIPES IN CLEAN CONDITION UNTIL FINAL
ACCEPTANCE BY OWNER.
7. CLEAN MANHOLE LIDS AND INLET GRATES TO REMOVE ASPHALT, CONCRETE, TAR OR OTHER ADHESIVES TO ALLOW ACCESS.
8. PLACE INLET, COMBINATION AND JUNCTION BOXES ON 12-INCH MINIMUM COMPACTED STABILIZATION MATERIAL.
9. REMOVE SILT AND DEBRIS FROM INLET BOXES, COMBO BOXES, JUNCTION BOXES, AND PIPE. MAINTAIN BOXES AND PIPES IN CLEAN CONDITION UNTIL FINAL
ACCEPTANCE BY OWNER.
CITY OF ST. GEORGE WATER NOTES
1. ALL WATERLINE WORKS MUST BE INSTALLED BY A CONTRACTOR THAT HAS BEEN RE-QUALIFIED BY THE CITY OF ST. GEORGE
WATER DEPARTMENT.
2. ALL CONSTRUCTION SHALL CONFORM TO THE “CITY OF ST. GEORGE STANDARD SPECIFICATIONS FOR DESIGN AND
CONSTRUCTION”, “THE INTERNATIONAL PLUMBING CODE”, AND THE “UNIFORM BUILDING CODE” LATEST EDITION AS
ADMINISTERED BY THE CITY OF ST. GEORGE.
3. CONTRACTOR SHALL POTHOLE ALL PIPELINES AND VERIFY LOCATION AND DEPTH PRIOR TO PROCEEDING WITH ANY BUILDING OR PIPELINE CONSTRUCTION. IF THE IN-FIELD CONDITION VARIES FROM DESIGN THE CONTRACTOR IS RESPONSIBLE FOR COSTS DUE TO CHANGES IN CONDITION. CITY MAPS ARE “BEST KNOWLEDGE” AND APPROXIMATE.
4. THE POTABLE WATER SUPPLY TO LAWN IRRIGATION SYSTEMS SHALL BE PROCTECTED AGAINST BACKFLOW PER THE “INTERNATIONAL PLUMBING CODE (IPC)” SECTION 608.16.5 AND FIRE SPRINKLER SYSTEMS PER (IPC) 608.16.4.
5. ALL BACKFLOW ASSSEMBLY INSTALLATION AND TEST REQUIREMENTS SHALL BE IN ACCORDANCE WITH THE CITY OF ST.
GEORGE BACKFLOW ORDINANCE 9-1-1997-5-6-5.
6. 14 GAUGE WIRE SHALL BE TAPED TO ALL WATER LINES FOR LOCATING PURPOSES. THE WIRE SHALL ALSO BE BROUGHT UP AT
EACH VALVE BOX AND HYDRANT.
7. THRUST RESTRAINT ON THE NEW PIPELINE WILL BE AS SHOWN ON THE DETAILS. USE MEGA-LUG ON THE FITTINGS AND FIELD
LOCK GASKETS ON THE REQUIRED LENGTH OF RESTRAINED PIPE.
8. ASPHALT REPLACED OVER THE PIPE TRENCHING IS TO MATCH EXISTING PAVEMENT DEPTHS WITH A 6” OVER CUT FROM EDGE
OF THE TRENCH ON EACH SIDE OF THE TRENCH.
9. CONTRACTORS SHALL CUT OFF AND CAP (BACK AT THE WATER MAIN), ALL EXISTING SERVICE LINES OR UNUSED STUB LINES
THAT WILL BE ABANDONED.
10. ANY CHANGES MADE IN THE FIELD MUST BE FIRST APPROVED AND DOCUMENTED BY THE CITY OF ST. GEORGE WATER
SERVICES REPRESENTATIVE.
11. ALL NEW FIRE HYDRANTS SHALL BE INSTALLED AT THE CORRECT HEIGHT. RISERS WILL NOT BE ALLOWED.
12. IRRIGATION WATER WORKS MAY REQUIRE ADDITIONAL APPROVALS FROM RESPECTIVE IRRIGATION COMPANIES.
ST. GEORGE ENERGY SERVICES POWER NOTES
1. PRIMARY POWER FROM SWITCH TO SWITCH SHALL BE 750 WIRE IN 3” CONDUIT.
2. PRIMARY POWER FROM VAULT TO TRANSFORMER SHALL BE 1/0 WIRE IN 3” CONDUIT UNLESS OTHERWISE NOTED. ALL WIRE
SHALL HAVE A TEMPERATURE RATING OF 90°C
3. SECONDARY POWER FROM TRANSFORMER TO METER (90°C TEMP. RATING):
A. FOR RESIDENTIAL LOTS – WHERE LENGTH IS LESS THAN OR EQUAL TO 200-FT
• 100 – 150 AMPS = 1/0 IN 2” CONDUIT
• 200 AMPS = 4/0 IN 2” CONDUIT
• 400 AMPS = 350 MCM IN 3”CONDUIT
• 600 AMPS = 500 MCM IN 3”CONDUIT
• CONTACT SGES FOR LENGTHS > 200-FT IF NOT SPECIFIED PERPLAN.
B. FOR C.T. CONNECTIONS (SERVICES > 400 AMPS) – SECONDARY CONDUIT AND WIRE SHALL BE SIZED BY BUILDING
ELECTRICAL ENGINEER.
C. FOR COMMERCIAL AND/OR APARTMENT COMPLEX ≤ 400 AMPS, OR > 400 AMPS WITH GANG PACK
INDIVIDUAL METERS – SIZED BY SGES BASED ON LOAD CALC’S.
4. CONTRACTOR TO FOLLOW ALL BLUE STAKES PROTOCOLS.
5. THE POWER DESIGN ON THIS UTILITY PLAN IS CONSIDERED BY ST. GEORGE ENERGY SERVICES (SGES) AS PRELIMINARY AND
NON-BIDABLE UNTIL ACCOMPANIED BY A JUC APPROVAL STAMP.
6. ALL PRIMARY UNDERGROUND POWER WORK/INSTALLATION MUST BE COMPLETED BY A CONTRACTOR THAT HAS BEEN
PREQUALIFIED BY SGES AND MEET ALL SGES STANDARDS. ALL OVERHEAD WORK/INSTALLATION MUST BE COMPLETED BY
SGES.
7. ALL WORK DONE BY SGES WILL BE PREPAID BY THE DEVELOPER.
8. IT IS THE RESPONSIBILITY OF THE DESIGN ENGINEER TO PROVIDE LOCATION AND ELEVATION OF ALL EXISTING AND DESIGN
UNDERGROUND/OVERHEAD UTILITIES AND STRUCTURES THAT WILL IMPACT THE SGES POWER DESIGN.
9. ALL JUC TRENCHES WILL BE BACKFILLED AND COMPACTED IN 6” TO 8” LIFTS TO A COMPACTION OF 95% IN
ROADWAYS/SIDEWALKS AND 90% BEHIND SIDEWALK. TESTING IS TO BE DONE AT MIDDLE AND TOP OF TRENCH.
10. ALL CHANGES TO EXISTING GRADES NEAR EXISTING POWER UTILITIES MUST BE APPROVED BY SGES PRIOR TO
CONSTRUCTION.
11. ANY IN-FIELD CHANGES TO THE JUC APPROVED POWER DESIGN WILL BE AT THE DEVELOPER’S EXPENSE AND MUST BE
PRE-APPROVED AND DOCUMENTED BY SGES PRIOR TO INSTALLATION.
MATERIALS NOTES
1. ALL MATERIALS WILL CONFORM WITH AUTHORITY(IES) HAVING JURISDICTION (AHJ) SPECIFICATIONS AND STANDARDS UNLESS
OTHERWISE INDICATED.
2. WHERE INDICATED, SUBMIT PRODUCT DATA AND MATERIALS TESTING TO ENGINEER OR OWNER AS CONSTRUCTION RECORD.
SUBMIT ALL CONSTRUCTION DOCUMENTS TO AHJ FOR ALL WORK DONE WITH PUBLIC RIGHT-OF-WAY, INCLUDING FIELD AND LAB TEST REPORTS. ALL SUBMITTALS MUST BE COMPLETED AND SUBMITTED TO ENGINEER PRIOR TO PROJECT TERMINATION.
3. EARTHWORK
3.1 EARTHWORK VOLUMES SHOWN ARE THE DIFFERENCE BETWEEN EXISTING GROUND AND PROPOSED FINISHED GRADE DIGITAL TERRAIN MODELS, AND ACCOUNTS FOR CONCRETE MATERIAL DEPTH FOR THE PROPOSED TANK. THE VOLUMES SHOWN DO NOT ACCOUNT FOR COMPACTION, CONSOLIDATION, OR OTHER MATERIAL DEPTHS. EARTHWORK QUANTITIES SHOWN ARE FOR PLANNING AND PERMITTING PURPOSES ONLY. VERIFY IMPORT AND EXPORT QUANTITIES PRIOR TO CONSTRUCTION AND NOTIFY ENGINEER OR PROJECT REPRESENTATIVE OF ANY CONFLICTS BETWEEN EXISTING FEATURES
AND NEW CONSTRUCTION.
TOTAL CUT VOLUME = 27,000 CUBIC YARDS (ALL CUT IS EXPECTED TO BE ROCK EXCAVATION)
TOTAL FILL VOLUME = 1,900 CUBIC YARDS
PROFESSIONA L ENGINEER
STATE OF UTAH
No. 12440204
CHAD
.00
320.35'
EXISTING 14" WATER LINE
EXISTING 14" WATER LINE
EXISTING 8" WATER LINE
EXISTING 12" WATER LINE
220.00'
0.0
0'
R150.00'
17.50'
C-101
CO
UN
TR
Y
CL
UB
.5
M G
T
AN
K
SI
TE
P
LA
N
-0
2/
/2
_1 st nd rd
-ir
.c tb
-0
D
ES
IG
N
_2
7-
R
EV
IS
IO
N S
N O
D
AT
E
R
EV
. B Y
D
ES
IG
N
R
EM
AR
KS
O R
IG
IN
AL
S
U
BM
IS
SI
O N
F O
R A
U
TH
O R
IZ
AT
IO
N
SC
AL
E:
SH
T
SE
T:
PE
N
T
BL
PL
O
TT
ED
U
PD
AT
ED
SU
BM
IT
TA
L:
COUNTY
SHEET NO.
D W
G C
R
EA
TE
D
D
W G
N
AM
E:
G
IS
EN
VI
R
O N
M
EN
TA
L
- M
AT
ER
IA
LS
T
ES
TI
N G
1.
0.
8.
w .jo ne sa nd de m ille
.c om
Jo ne s
D eM ille E ng in ee rin g, In c.
C
IV
IL
S
TR
U
C
TU
R
AL
E N
G
IN
EE
R
IN
G
SU
R
VE
YI
N
G
ST
AM
P:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
PR
O
JE
C
T N
U M
BE
R
2/
/2
1" =4
0' 4-
-2
WASHINGTON
ST
. G
EO
RG
E
CI
TY
FO
R
B
ID
D
IN
G O
N
LY
PROJECT INFORMATION
EASMENT AREA
EXISTING TANK EASEMENT 14,445.87 SF / 0.33 AC
CONSTRUCTION LIMITS EASEMENT 212,337.19 SF / 4.87 AC
NEW TANK EASMENT 48,400 SF / 1.11 AC
PIPE LINE & LOWER ACCESS ROAD
EASEMENT
10,943.04 SF / 0.25 AC
UPPER ACCESS ROAD EASEMENT 9,796.12 SF / 0.22 AC
EARTHWORK CALCULATION OF TANK
EXCAVATION
35,209.38 SF / 0.81 AC
CUT / FILL 24,063.84 CY CUT / 1,850.78 CY FILL
150' DIA.WATER TANK
FFE: 2750.00
LIMITS OF
CONSTRUCTION
LIMITS OF
CONSTRUCTION
LIMITS OF
CONSTRUCTION
PROPOSED 20 FOOT
LOWER ACCESS ROAD
SEE DETAIL 'K9', SHEET C-501
FOR TYP. SECTION
PROPOSED 20 FOOT
UPPER ACCESS
ROAD EASEMENT
LIMITS OF CONSTRUCTION
EXISTING TANK EASEMENT
TO BE VACATED
EXISTING TANK
TO BE REMOVED
PROPOSED WATER
TANK EASEMENT
PROPOSED WATER
TANK EASEMENT
STAGING & STOCKPILE AREA
SIR MONTE DRIVE
W
IN
DS
OR
D
RI
VE
CA
NT
ER
BU
RY
DR
IV
E
EXISTING 12" WATER LINE
EXISTING 12" DRAIN LINE
TO BE REPLACED
EXISTING EASEMENT LINE
242.25' OF 18" SDR-18 C900 PVC
DRAIN PIPE @ -0.50%
18" PVC DRAIN PIPE TO
EXISTING DRAINAGE BOX
GRATE = 2713.29
INVERT IN = 2708.25'
15.50'x13.50'
CONCRETE WATER VAULT,
SEE DETAIL ON SHEET C-102
399' OF 14" SDR-18 C900 PVC PIPE
402' OF 16" SDR-18 C900 PVC PIPE
POWER CONDUIT TO
CONNECT TO EXISTING
SECONDARY BOX
6' DIA CONCRETE MANHOLE
GRATE = 2744.34
INVERT OUT = 2736.34
SEE DETAIL 'D1', SHEET C-501
203 LF (1) 2" CONDUIT W/ 4/0 TRIPLEX
(SECONDARY BOX TO METER PANEL)
OVERHEAD POWER LINES
EXISTING POWER CONDUIT
TO BE REMOVED
ST. GEORGE CITY WATER TANK
893 SIR MONTE DRIVE
ST. GEORGE, UTAH
KADE BRINGHURST, P.E.
435-627-4854
Feet 0 40 80
5' OF 18" D.I. OVERFLOW DRAIN PIPE
MEASURED FROM CENTER OF WALL,
SEE DETAIL 'A1', SHEET S-501
18" D.I. TO
18" PVC PIPE
WITH MJ CONNECTION
DOUBLE-SWING CHAIN LINK GATE
DOUBLE-SWING CHAIN LINK GATE
DOUBLE-SWING CHAIN LINK GATE
POWER METER & 100 AMP MAIN
W/ DISCONNECT MOUNTED ON
UNISTRUT TYPE PEDESTAL
CHAIN LINK FENCE,
SEE DETAIL 'G9', SHEET C-501
CHAIN LINK FENCE,
APPROXIMATE LOCATIONS SHOWN
FIELD VERIFY WITH CITY,
SEE DETAIL 'G9', SHEET C-501
402' 16" WATER LINE
400' 14" WATER LINE
400' (2) 2" PVC CONDUITS FOR POWER/SCADA
DRAINAGE SWALE,
GRADE TO DRAIN
CONCRETE HEADWALL
SEE DETAIL 'D9', SHEET C-501
122' of 18" SDR-18 C900 PVC PIPE @ -18.54%
176.77' of 18" SDR-18 C900 PVC PIPE @ -2.41%
EXISTING POWER
POLE W/ POLE MOUNT
TRANSFORMER
(PROTECT IN PLACE)
EXISTING 2" CONDUIT W/ 40/ WIRE
(POLE TO SECONDARY BOX)
(PROTECT IN PLACE)
16" BUTTERFLY VALVE
60' of 18" SDR-18 C900
PVC PIPE @ -2.11%
SCADA PANEL(S) BY OTHERS
4" FOUNDATION DRAIN PIPE,
GRADE TO DRAIN
4" FOUNDATION DRAIN PIPE,
TEE AND DRAIN TO MANHOLE
EXISTING ACCESS ROAD,
SEE DETAIL 'K9', SHEET C-501
LOWER ACCESS ROAD,
SEE DETAIL 'K9', SHEET C-501
UPPER ACCESS ROAD,
SEE DETAIL 'K9', SHEET C-501
4" FOUNDATION DRAIN PIPE,
GRADE TO DRAIN
90° BEND
45° BEND
22.5° BEND
EXISTING FENCE
TO BE REMOVED
EXISTING PIPES
ABANDON IN PLACE
EXISTING VAULTS
PROTECT IN PLACE
EXISTING AC PIPE
PROTECT IN PLACE
EXISTING DRAIN PIPE
ABANDON IN PLACE
CONNECT NEW WATER LINES
TO EXISTING AC PIPE
51' OF 8" SDR-18 C900 TANK DRAIN PIPE @ 0.50%,
WITH WYE INTO 18" OVERFLOW DRAIN PIPE
11.25° BEND
16x8 TEE
5' OF 14" D.I. INLET PIPE
MEASURED FROM
CENTER OF WALL, SEE
DETAIL 'D9', SHEET S-5015' OF 16" D.I. OUTLET PIPE
MEASURED FROM
CENTER OF WALL, SEE
DETAIL 'D13', SHEET S-501
14" D.I. TO
14" PVC PIPE
WITH MJ CONNECTION
16" D.I. TO
16" PVC PIPE
WITH MJ CONNECTION
TURN UP AND CAP CONDUITS.
CONNECTION BY OTHERS
ROUTE CONDUIT TO
TRANSDUCER ENCLOSURE,
SEE DETAIL ON SHEET S-501
8" GATE VALVE
PROFESSIONA L ENGINEER
STATE OF UTAH
No. 12440204
CHAD
.0
0'
320.35'
25 27
30 27 35 27
40 27 45 27
50 27 55 27
70 27
220.00'
0.
-3.0:1
-1 2.
1:
-9.1:1
1:3
1:3
-2.7:1
-2 .0
:1
0+
1+
2+
3+
4+
5+
6+
R1
.0 0'
17.50'
2743 27
60 27
50 2751
27182715
-3.0:1
-7.7%
R1
.2 9'
-0.
3%
-4.7%
-2.4%
TOW:2749.02
BOW:2743.34
TOW:2746.00
BOW:2743.34
TOW:2746.26
BOW:2743.34
-4.0:1 -1
0.
2%
0+00
.1
.2
1+00
.1
.5
.8
.8
2+00
.9
.9
.5
.3
3+00
.1
.0
.7
.5
4+00
.4
.0
.6
.0
5+00
.1
.0
.2
.3
6+00
150' DIA. WATER TANK
FFE: 2750.00
EXISTING GROUND
3:1
1:
5.25%
FINISH GRADE
6' DIA CONCRETE MANHOLE
GRATE = 2744.34
FINISH GROUND = 2743.34
INVERT OUT = 2736.34
176.77' of 18" PVC PIPE @ -2.41%
FINISH GRADE
425' of 16" SDR-18 C900 PVC TANK OUTFLOW WATER LINE
425' of 14" SDR-18 C900 PVC TANK INFLOW WATER LINE
14" WATER INFLOW LINE
16" WATER OUTFLOW LINE
CONNECT WATER LINES
TO EXISTING 14" AC WATER MAIN
CONCRETE
WATER
VAULT
FINISH GRADE
FINISH GRADE
122' of 18" PVC PIPE @ -18.54%
18" OVERFLOW DRAIN LINE
DRAIN PIPE
WITH 90° TURNDOWN
INVERT OUT = 2745.34
4" PERFORATED FOUNDATION
DRAIN, GRADE TO DRAIN,
SEE DETAIL 'K13', SHEET S-501
STRUCTURAL FILL UNDER SLAB REQUIRED.
FOOTINGS TO BE ESTABLISHED ON CLEAN
SANDSTONE BEDROCK.
SEE STRUCTURAL DRAWINGS
EXTEND EXCAVATION
A MAXIMUM OF 10'
FROM FOUNDATION
EDGE AS NEEDED
FOR CONSTRUCTION
C-102
CO
UN
TR
Y
CL
UB
.5
M G
T
AN
K
TA
NK
P
LA
N
PR
O
FI
LE
-0
2/
/2
_1 st nd rd
-ir
.c tb
-0
D
ES
IG
N
_2
7-
R
EV
IS
IO
N S
N O
D
AT
E
R
EV
. B Y
D
ES
IG
N
R
EM
AR
KS
O R
IG
IN
AL
S
U
BM
IS
SI
O N
F O
R A
U
TH
O R
IZ
AT
IO
N
SC
AL
E:
SH
T
SE
T:
PE
N
T
BL
PL
O
TT
ED
U
PD
AT
ED
SU
BM
IT
TA
L:
COUNTY
SHEET NO.
D W
G C
R
EA
TE
D
D
W G
N
AM
E:
G
IS
EN
VI
R
O N
M
EN
TA
L
- M
AT
ER
IA
LS
T
ES
TI
N G
1.
0.
8.
w .jo ne sa nd de m ille
.c om
Jo ne s
D eM ille E ng in ee rin g, In c.
C
IV
IL
S
TR
U
C
TU
R
AL
E N
G
IN
EE
R
IN
G
SU
R
VE
YI
N
G
ST
AM
P:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
PR
O
JE
C
T N
U M
BE
R
2/
/2
1" =2
0' 4-
-2
WASHINGTON
ST
. G
EO
RG
E
CI
TY
FO
R
B
ID
D
IN
G O
N
LY
150' DIA. WATER TANK
FF ELEV: 2750.00
EXISTING 12" WATER LINE
EXISTING 12" DRAIN LINE
TO BE REPLACED
EXISTING EASEMENT LINE
PROPOSED 30-FOOT
PIPELINE & LOWER
ACCESS ROAD EASEMENT
LIMITS OF
CONSTRUCTION
PROPOSED WATER
TANK EASEMENT
PROPOSED WATER
TANK EASEMENT
LIMITS OF
CONSTRUCTION
LIMITS OF
CONSTRUCTION
LIMITS OF
CONSTRUCTION
LIMITS OF
CONSTRUCTION
LIMITS OF
CONSTRUCTION
PROPOSED 20 FOOT
UPPER ACCESS
ROAD EASEMENT
16" WATER LINE
14" WATER LINE
CONDUITS FOR POWER/SCADA
122' of 18" SDR-18 C900 PVC PIPE @ -18.54%
176.77' of 18" SDR-18 C900 PVC PIPE @ -2.41%
242.25' OF 18" SDR-18 C900 PVC DRAIN PIPE @ -0.50%
18" PVC DRAIN PIPE TO
EXISTING DRAINAGE BOX
INVERT IN = 2708.25'
15.50'x13.50' CONCRETE WATER VAULT, SEE DETAIL 'A3', SHEET C-501
399' OF 14" SDR-18 C900
PVC PIPE
402 OF 16" SDR-18 C900
PVC PIPE
Feet 0 20 40
POWER CONDUIT TO
CONNECT TO EXISTING
SECONDARY BOX
6' DIA CONCRETE MANHOLE
GRATE = 2744.34
INVERT OUT = 2736.34
5' OF 18" D.I. PIPE
WRAPPED WITH V-BIO POLY
45' OF 18" SDR-18 C900 PVC
OVERFLOW DRAIN PIPE @ -2.00%
5' OF 18" D.I. OVERFLOW DRAIN PIPE
WRAPPED WITH V-BIO POLY
18" D.I. TO 18" PVC PIPE
WITH MJ CONNECTION
DOUBLE-SWING
CHAIN LINK GATE
DOUBLE-SWING
CHAIN LINK GATE
DOUBLE-SWING
CHAIN LINK GATE
DRAINAGE SWALE
AT TOP OF SLOPE,
GRADE TO DRAIN
DRAINAGE SWALE
AT TOE OF SLOPE,
GRADE TO DRAIN
DRAINAGE SWALE
AT TOE OF SLOPE,
GRADE TO DRAIN
DRAINAGE SWALE
AT TOP OF SLOPE,
GRADE TO DRAIN
CHAIN LINK FENCE,
SEE DETAIL 'G9', SHEET C-501
CHAIN LINK FENCE,
SEE DETAIL 'G9', SHEET C-501
CHAIN LINK FENCE,
SEE DETAIL 'G9', SHEET C-501
(1) 2" CONDUIT W/ 4/0 TRIPLEX
(SECONDARY BOX TO VAULT)
POWER METER & 100 AMP MAIN
W/ DISCONNECT MOUNTED ON
UNISTRUT TYPE PEDESTAL
CONNECT 8" TANK DRAIN PIPE TO 16" WATER
LINE 16x8 TEE AND 8" GATE VALVE
51' OF 8" SDR-18 C900 TANK DRAIN PIPE @ 0.50%,
WITH WYE INTO 18" OVERFLOW DRAIN PIPE
70' OF 8" SDR-18 C900 TANK DRAIN PIPE @ 1.71%,
WITH WYE INTO 18" OVERFLOW DRAIN PIPE
51' OF 18" SDR-18 C900 PVC
OVERFLOW DRAIN PIPE @ -2.00%
DRAINAGE SWALE
AT TOE OF SLOPE,
GRADE TO DRAIN
DRAINAGE SWALE
AT TOP OF SLOPE,
GRADE TO DRAIN
EXISTING ACCESS ROAD,
SEE DETAIL 'K9', SHEET C-501
LOWER ACCESS ROAD,
SEE DETAIL 'K9', SHEET C-501
UPPER ACCESS ROAD,
SEE DETAIL 'K9', SHEET C-501
4" FOUNDATION DRAIN PIPE,
GRADE TO DRAIN
4" FOUNDATION DRAIN PIPE,
TEE AND DRAIN TO MANHOLE
4" FOUNDATION DRAIN PIPE,
GRADE TO DRAIN
90° BEND
11.25° BEND
45° BEND
22.5° BEND
CONNECT NEW
WATER LINES
TO EXISTING
AC PIPE
16x8 TEE
CONNECT 8" TANK DRAIN PIPE
TO 16" WATER LINE
51' OF 8" SDR-18 C900 TANK DRAIN PIPE @ 0.50%,
WITH WYE INTO 18" OVERFLOW DRAIN PIPE
EQUIPMENT HATCH
EQUIPMENT HATCH
16" BUTTERFLY VALVE
PROFESSIONA L ENGINEER
STATE OF UTAH
No. 12440204
CHAD
60 2765 27
70 2775 27
90 2795
2755 27
95 2800 28
0+
1+
2+
3+
4+
5+
6+
6+
74 27
75 27 76 27
-21.1%
271527
271527
-7.7%
-0.3%
-4.7%
-2 .4
-10.2%
C-401
CO
UN
TR
Y
CL
UB
.5
M G
T
AN
K
ER
O
SI
O N
CO
NT
RO
L
PL
AN
-0
2/
/2
_1 st nd rd
-ir
.c tb
-0
D
ES
IG
N
_2
7-
R
EV
IS
IO
N S
N O
D
AT
E
R
EV
. B Y
D
ES
IG
N
R
EM
AR
KS
O R
IG
IN
AL
S
U
BM
IS
SI
O N
F O
R A
U
TH
O R
IZ
AT
IO
N
SC
AL
E:
SH
T
SE
T:
PE
N
T
BL
PL
O
TT
ED
U
PD
AT
ED
SU
BM
IT
TA
L:
COUNTY
SHEET NO.
D W
G C
R
EA
TE
D
D
W G
N
AM
E:
G
IS
EN
VI
R
O N
M
EN
TA
L
- M
AT
ER
IA
LS
T
ES
TI
N G
1.
0.
8.
w .jo ne sa nd de m ille
.c om
Jo ne s
D eM ille E ng in ee rin g, In c.
C
IV
IL
S
TR
U
C
TU
R
AL
E N
G
IN
EE
R
IN
G
SU
R
VE
YI
N
G
ST
AM
P:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
PR
O
JE
C
T N
U M
BE
R
2/
/2
1" =4
0' 4-
-2
WASHINGTON
ST
. G
EO
RG
E
CI
TY
FO
R
B
ID
D
IN
G O
N
LY
PROJECT INFORMATION
MC AREA
EXISTING TANK EASEMENT 14,445.87 SF / 0.33 AC
CONSTRUCTION LIMITS EASEMENT 212,337.19 SF / 4.87 AC
NEW TANK EASMENT 48,400 SF / 1.11 AC
PIPE LINE & LOWER ACCESS ROAD
EASEMENT
10,943.04 SF / 0.25 AC
UPPER ACCESS ROAD EASEMENT 9,796.12 SF / 0.22 AC
EARTHWORK CALCULATION OF TANK
EXCAVATION
35,209.38 SF / 0.81 AC
CUT / FILL 24,063.84 CY CUT / 1,850.78 CY FILL
150' DIA.WATER TANK
FFE: 2750.00
LIMITS OF
CONSTRUCTION
LIMITS OF
CONSTRUCTION
LIMITS OF
CONSTRUCTION
LIMITS OF CONSTRUCTION
EXISTING TANK EASEMENT
TO BE VACATED
EXISTING TANK
TO BE REMOVED
PROPOSED WATER
TANK EASEMENT
PROPOSED WATER
TANK EASEMENT
STAGING & STOCKPILE AREA
WITH CONCRETE WASHOUT
SIR MONTE DRIVE
W
IN
DS
OR
D
RI
VE
CA
NT
ER
BU
RY
DR
IV
E
EXISTING EASEMENT LINE
OVERHEAD POWER LINES
ST. GEORGE CITY WATER TANK
893 SIR MONTE DRIVE
ST. GEORGE, UTAH
KADE BRINGHURST, P.E.
435-627-4854
Feet 0 40 80
DRAINAGE SWALE,
GRADE TO DRAIN
EXISTING FENCE
TO BE REMOVED
EXISTING PIPES
ABANDON IN PLACE
EXISTING VAULTS
PROTECT IN PLACE
SILT FENCE
NOTES
1. ALL EROSION CONTROL MEASURES PER ST. GEORGE CITY STANDARDS AND
APWA STANDARDS.
STABILIZED
CONSTRUCTION
ENTRANCE
STABILIZED
CONSTRUCTION
ENTRANCE
CONSTRUCTION PHASE SWPPP BEST MANAGEMENT PRACTICES
ITEM BMP LOCATION INSTALL PRECEDING REMOVE PROCEEDING
A BERMS AND TEMPORARY DIVERSION DITCHES PER CONTRACTOR SITE GRUBBING/DEMOLITION SITE IMPROVEMENTS COMPLETION
B DUST CONTROL PER CONTRACTOR SITE GRUBBING/DEMOLITION SITE IMPROVEMENTS COMPLETION
C PRESERVE NATURAL VEGETATION PER CONTRACTOR SITE GRUBBING/DEMOLITION N/A
D SILT FENCE AS SHOWN SITE GRUBBING/DEMOLITION FINAL STABILIZATION
E STABILIZED CONSTRUCTION ENTRANCE AS SHOWN SITE GRUBBING/DEMOLITION PERMANENT ACCESS CONSTRUCTION
F STRAW WATTLE FILTER BERM OR CHECK DAM PER CONTRACTOR/ AS SHOWN SITE GRUBBING/DEMOLITION FINAL STABILIZATION
G STORM DRAIN INLET PROTECTION AS SHOWN EXISTING INLETS - SITE GRUBBING/DEMOLITION
NEW INLETS - AFTER INSTALLATION FINAL STABILIZATION
H CONCRETE WASHOUT PER CONTRACTOR/ AS SHOWN SITE CONSTRUCTION SITE IMPROVEMENTS COMPLETION
I MATERIAL DELIVERY, STORAGE AND
CONTAINMENT PER CONTRACTOR SITE CONSTRUCTION SITE IMPROVEMENTS COMPLETION
J SOLID WASTE MANAGEMENT PER CONTRACTOR SITE CONSTRUCTION SITE IMPROVEMENTS COMPLETION
K TEMPORARY SANITATION FACILITIES PER CONTRACTOR SITE CONSTRUCTION SITE IMPROVEMENTS COMPLETION
L SEDIMENT TRACKING CLEANUP PER CONTRACTOR AS NECESSARY AS NECESSARY
M SPILL PREVENTION FOR FUELING AND
MAINTENANCE PER CONTRACTOR AS NECESSARY AS NECESSARY
N VEHICLE WASH DOWN PER CONTRACTOR AS NECESSARY AS NECESSARY
O PERMANENT SEEDING PER CONTRACTOR SITE IMPROVEMENTS COMPLETION N/A
INLET PROTECTION
INLET PROTECTION
PROFESSIONA L ENGINEER
STATE OF UTAH
No. 12440204
CHAD
1'
PIPE
O.D. 1'
6"
PI
PE
O
.D
1'
VA
R
IE
S
4' -0
" M
IN
. F O
R F
O R
C E
M
AI
N
MAXIMUM ALLOWABLE WATER
LEVEL DURING CONSTRUCTION
3/4" MINUS BEDDING MATERIAL
COMPACTED TO 96% IN 6" LIFTS.
WARNING TAPE
(2' ABOVE PIPE)
FULL DEPTH GRANULAR BORROW
BACKFILL COMPACTED TO 96%
SEE NOTE 4.
GROUND SURFACE
SHAPE AND GRADE EXISTING TANK ACCESS RD.
20.00' UPPER ROAD & 12.00' LOWER ROAD
2.00% SLOPE
4:1 SLOPE
3:1 SLOPE
EXISTING GROUND
EXISTING GROUND
6" COMPACTED ROAD BASE
3" CORNER POST
2" LINE POST
INSTALL EXTENSION ARMS &
3 STRANDS BARBED WIRE
4" GATE POST TOP RAIL
6' -0
2" MAX
12"
16'-0"±
(2) 8'-0" GATES)
10'-0"10'-0"10'-0"
12"8"12" 8"
TENSION WIRE,
7 GAUGE
2500 psi CONC., TYP.
3' -6
TY
P.
9 GAUGE CHAIN
LINK FABRIC, TYP.
SEE PLAN FOR LOCATIONS
GRANULAR BEDDING REQ'D (1/4" MIN TO
1" MAX. WELL GRADED AGGREGATE)
PRECAST CONCRETE BASE
6" M
IN
PRECAST REINFORCED CONCRETE
MANHOLE SECTION WITH STEPS
RUBBER BOOT COUPLER
ALL MANHOLES SHALL BE WATERTIGHT
USE GASKET JOINTS. STEPS REQ'D 12" C.C.
6'
GRADE RINGS AS REQ'D. JOINTS TO
BE SEALED WATERTIGHT
#4 MESH NONCORRODIBLE
SCREEN ON PIPE.
ATTACHED WITH SET
SCREW COLLAR.
FINISHED GRADE
12"
TYP
TY
P
GRATE
FROM TANK
SLOPED TO DRAIN
18" PVC 90° TURNDOWN
18" PVC DRAIN LINE FROM TANK
TO STORM DRAIN
SLOPED TO DRAIN
18" PVC DRAIN LINE
FINISHED GRADE
CONCRETE HEADWALL
SEE DETAILS 'A1' & 'A5', THIS SHEET
8' -6
1.
FROM FOUNDATION DRAIN
SLOPED TO DRAIN
4" FOUNDATION DRAIN LINE FROM TANK
NOTE:
1. SCH. 40 GALV. PIPE AND FITTINGS TO
MATCH AIR-VAC OR COMBINATION AIR
RELEASE VALVE SIZE. SEE PLAN AND
PROFILE SHEETS FOR LOCATION AND
SIZE.
2. RELATED SPEC SECTION 33 14 12.
3. TRACER WIRE TO BE BROUGHT UP
WITHIN 2 FEET OF LID.FULL BODY TAP SADDLE (PVC OR D.I. PIPE)
12" DEPTH CRUSHED ROCK OR OTHER
ACCEPTED FREE DRAINING MATERIAL
12" TYP
COMBINATION AIR RELEASE
VALVE REQUIRED
1/16" Ø WEEP HOLE REQ'D
THREADED UNION REQ'D
BALL VALVE
(MATCH VALVE SIZE)
6" TYP5'
-0
" M
IN
1' -0
CONCRETE BOLLARD
EMBED IN CONCRETE
3' -0
BACKFILL LINE
36" Ø CORRUGATED HDPE BARREL
ATTACH PIPE TO STEEL POST
w/ STAINLESS WORM SCREW HOSE
CLAMP @ 3 PLACES
SCH 40 GALV. PIPING
(SIZE TO MATCH VALVE SIZE)
D&L A-1540 RING & LID COVER,
OR AN EQUAL
4" PILLOW INSULATION REQ'D
#14 MESH NON-CORRODIBLE
SCREEN PROTECTED BY #4
RODENT STAINLESS STEEL
SCREEN ATTACHED WITH
SET SCREW COLLAR
SCH 40 GALV PIPING w/ FITTINGS AS NECESSARY
EXISTING
GROUND
3' -0
LOOP TRACER WIRE
CONCRETE VAULT
15.50'
.5
0'
16" WATER LINE
14" WATER LINE
EXISTING 14" AC WATER LINE
TO TANK
FROM TANK
14"x10"x14" TEE
14" BUTTERFLY VALVE
14"x10"x14" TEE
10" ELECTRONIC ACTUATED
VALVE SINGER MODEL
106-2SC-PCO WITH SPI-MV
10" GATE VALVE
COMBINATION VALVE
2" COMBINATION VALVE
COMBINATION
VALVE RISER
COMBINATION
VALVE RISER
PLAN VIEW
ADJUSTABLE PIPE
STANDS, SEE NOTES
ADJUSTABLE PIPE
STANDS, SEE NOTES
16"x10"
REDUCER
14"x10"
REDUCER
10" SPOOL
10" SPOOL
14" SPOOL
ADJUSTABLE PIPE
STANDS, SEE NOTES
PROFILE VIEW
NOTES:
1. (3) ADJUSTABLE METAL PIPE SADDLE SUPPORTS, EVENLY SPACED, REQ'D. ON 16" PIPING.
2. (2) ADJUSTABLE METAL PIPE SADDLE SUPPORTS, EVENLY SPACED, REQ'D. ON 14" PIPING.
3. AFTER PLACEMENT OF VAULT IF WATER DOES NOT DRAIN TO DRAINS CUT HOLE IN
PRECAST BOX (AND PLACE GRATES) SUCH THAT PONDING DOES NOT OCCUR.
4. ALL MATERIALS IN CONTACT WITH WATER MUST BE NSF 61 COMPLIANT.
5. PAINT PIPING, FITTINGS, VALVES, AND APERTURES LOCATED INSIDE VAULT.
6. PROVIDE HAND WHEELS ON GATE VALVES LOCATED INSIDE VAULT.
4.
2.
(SEE PLAN VIEW FOR PIPING)
LOCATE LIFTING EYES
ABOVE ISOLATION VALVES
ADJUSTABLE PIPE
STANDS, SEE NOTES
GROUT OR
RUBBER BOOT
AROUND PIPE, TYP.
1.
CRUSHED ROCK
CONCRETE VAULT,
SEE VAULT
STRUCTURAL DETAILS
HEAVY DUTY MANHOLE FRAME AND COVER
TYPICALLY VENTED UNLESS OTHERWISE
NOTED ON PLANS
D&L A 1180 OR
EQUAL LABELED AS
"WATER"
CONCRETE
COLLAR
SET FRAME FLUSH WITH FINISH
GRADE. GRADE RINGS AS NEEDED
STEPS @ 12" OC
3" DRAIN HOLES
W/ GRATE
EXISTING 14"
AC WATER LINE 14" & 16"
WATER LINE
2" CONDUIT
TO SECONDARY
POWER BOX,
SEE SITE PLAN
SHEET C-101
VAPOR PROOF
SEALED LED
LIGHTS
POWER
OUTLET
FAN
AIR VENT WITH COVER AND
#14 MESH NON-CORRODIBLE SCREEN
PROTECTED BY
#4 RODENT STAINLESS STEEL SCREEN
ATTACHED WITH SET SCREW COLLAR
SUMP
CONCRETE WALL
#5 @ 12" OC VERT REINF
#4 @ 12" OC VERT REINF
#4 @ 12" OC HORIZ REINF
# 5@ 12" OC LONG REINF
# 5@ 12" OC TRANS REINF
CONCRETE FOOTING
DOWEL TO MATCH VERT REINF
1.00' 7.00'
1.
5.
1.00'
6.
0'
4.0' 4.0'
6' OF 16" PVC PIPE
TO BEND
#4 MESH
NON CORRODIBLE
SCREEN ON PIPE.
NOTES:
1. SEE DETAIL A5, SHEET S-502 FOR
ADDITIONAL DETAILS.
135°
TO STORM DRAIN
SLOPED TO DRAIN
FROM TANK
SLOPED TO DRAIN
FL
O
W
FL
O W
CONCRETE
HEADWALL
CONCRETE FOOTING
C-501
CO
UN
TR
Y
CL
UB
.5
M G
T
AN
K
DE
TA
IL
S
-0
2/
/2
_1 st nd rd
-ir
.c tb
##D
ET
AI
LS
R
EV
IS
IO
N S
N O
D
AT
E
R
EV
. B Y
D
ES
IG
N
R
EM
AR
KS
O R
IG
IN
AL
S
U
BM
IS
SI
O N
F O
R A
U
TH
O R
IZ
AT
IO
N
SC
AL
E:
SH
T
SE
T:
PE
N
T
BL
PL
O
TT
ED
U
PD
AT
ED
SU
BM
IT
TA
L:
COUNTY
SHEET NO.
D W
G C
R
EA
TE
D
D
W G
N
AM
E:
G
IS
EN
VI
R
O N
M
EN
TA
L
- M
AT
ER
IA
LS
T
ES
TI
N G
1.
0.
8.
w .jo ne sa nd de m ille
.c om
Jo ne s
D eM ille E ng in ee rin g, In c.
C
IV
IL
S
TR
U
C
TU
R
AL
E N
G
IN
EE
R
IN
G
SU
R
VE
YI
N
G
ST
AM
P:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
PR
O
JE
C
T N
U M
BE
R
2/
/2
SC
AL
E C
R _D
AT
E
SCALE
K1
SCALE
K5 TRENCH DETAIL
SCALE
K9 TYPICAL ROAD SECTION
SCALE
G9
SCALE
D1
SCALE
D9
SCALE
D13
SCALE
A1
SCALE
A5
SCALE
A9
WASHINGTON
ST
. G
EO
RG
E
CI
TY
FO
R
B
ID
D
IN
G O
N
LY
CHAIN LINK FENCE DETAIL
6' DIA. CONCRETE MANHOLE TANK DRAIN DETAIL AIR VAC DETAIL
CONCRETE HEADWALL DETAIL CONCRETE WATER VAULT DETAIL
NTS
NTS NTS
NTS
NTS
NTSNTS
CONCRETE HEADWALL DETAIL
AIR VENT WITH COVER AND
#14 MESH NON-CORRODIBLE SCREEN
PROTECTED BY
#4 RODENT STAINLESS STEEL SCREEN
ATTACHED WITH SET SCREW COLLAR
PROFESSIONA L ENGINEER
STATE OF UTAH
No. 12440204
CHAD
N
D1
S-101
D1
S-101
PIPE FOOTING
475'-0" LONG x 9" WIDE CONTINUOUS
RIBBED PVC. WATER STOP,
(GREENSTREAK MODEL #646 OR
EQUAL) RATED FOR 125' OF PRESSURE
HEAD MINIMUM. PROVIDE WELDED
BUTT JOINT AT ENDS. PLACE AT WALL
CENTER & PROVIDE 3" MIN.
EMBEDMENT INTO FOOTING.
2'
4"
O .D
TY
P.
1'
2" W
AL
L
0'
0"
I.
D
25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0"
D CE
G A
BOF ELEV = 2749.40
BOF ELEV = 2749.07 BOF ELEV = 2749.19
CS-1
CF-2 CF-2
CF-2CF-2
CF-1CW-1
150' - 0"
BOF ELEV = 2749.40
CC-1 CC-1
CC-1CC-1
0°
FOUNDATION DRAIN PER
TYPICAL STRUCTURAL DETAIL
BF
CF-2
BOF ELEV = 2749.19
CC-1
CF-2
BOF ELEV = 2749.25
CC-1
CF-2
BOF ELEV = 2749.19
CC-1
CF-2
BOF ELEV = 2749.19
CC-1
CF-2
BOF ELEV = 2749.50
CC-1
CF-2
BOF ELEV = 2749.19
CC-1
CF-2
BOF ELEV = 2749.25
CC-1
CF-2
BOF ELEV = 2749.50
CC-1
CF-2
BOF ELEV = 2749.75
CC-1
CF-2
BOF ELEV = 2749.45
CC-1
CF-2
BOF ELEV = 2749.22
CC-1
CF-2
BOF ELEV = 2749.11
CC-1
CF-2
BOF ELEV = 2749.19
CC-1
CF-2
BOF ELEV = 2748.77
CC-1
CF-2
BOF ELEV = 2748.93
CC-1
CF-2
BOF ELEV = 2749.02
CC-1
CF-2
BOF ELEV = 2749.05
CC-1
8°
MANWAY
DOOR
S-501 D5
236°
INLET
PIPE FOOTING
OULET
A1
S-501
OVERFLOW
9'
0"
ACCESS LADDER
10" DIA. ROOF VENT
SEE DETAIL
10" DIA. ROOF VENT
SEE DETAIL
10" DIA. ROOF VENT
SEE DETAIL
10" DIA. ROOF VENT
SEE DETAIL
D1
S-101
D1
S-101
CONCRETE WALL
ROOF DROP
PANEL
0'
0"
ID
150' - 0"
2'
4"
O D
D CE
G A
BOP ELEV = 2770.50 BOP ELEV = 2770.50
BOP ELEV = 2770.50 BOP ELEV = 2770.50
CS-2
TYP
5' - 0" SQUARE
25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0"
BF
0°
BOP ELEV = 2770.00
BOP ELEV = 2770.00
BOP ELEV = 2770.00 BOP ELEV = 2770.00 BOP ELEV = 2770.00
BOP ELEV = 2770.50 BOP ELEV = 2771.00
BOP ELEV = 2770.00 BOP ELEV = 2770.00
BOP ELEV = 2770.50
BOP ELEV = 2770.00 BOP ELEV = 2770.50
BOP ELEV = 2770.00
BOP ELEV = 2770.00 BOP ELEV = 2770.00 BOP ELEV = 2770.00
BOP ELEV = 2770.50
CC-1 CC-1
CC-1CC-1
CC-1 CC-1 CC-1
CC-1 CC-1 CC-1
CC-1 CC-1 CC-1 CC-1 CC-1
CC-1CC-1CC-1
CC-1 CC-1 CC-1
EQUIPMENT
HATCH
S-501 G1
K9
S-501
PRESSURE TRANSDUCER
ENCLOSURE
ACCESS HATCH
S-501 G1
N
FOOTINGS TO BE ESTABLISHED ON
CLEAN SANDSTONE BEDROCK
FINISHED GRADE
SEE CIVIL SHEETS
1.
2.
3.
4.
NOTE:
CAST-IN-PLACE ROOF SHOWN
REINFORCING STEEL NOT SHOWN
ROOF VENTS NOT SHOWN.
FOUNDATION DRAIN NOT SHOWN.
WALL
1' - 2"
150' - 0" I.D. WALL
1' - 2"
152' - 4" O.D.
CONCRETE
FOOTING
CAST-IN-PLACE
CONCRETE
ROOF SLAB
CONCRETE
FLOOR SLAB
ROOF DROP PANEL
CONCRETE FOOTING
CONCRETE WALL
ELEV = 2772.27
OVERFLOW ELEV = 2769.00
1'-0" FREEBOARD
D CEG A
CONCRETE COLUMN
CONCRETE FOOTING
SLOPE
S-101 G13
ELEV = 2770.75
FINISHED GRADE
SEE CIVIL SHEETS
CONCRETE WALL
S-101 A1
BF
ELEV = 2750.00
SLOPE
UNTREATED BASE COURSE, ST GEORGE
CITY SPEC ROADBASE IS SUITABLE
CONCRETE FOOTING
LONG REINF FOOTING WIDTH
9" WATERSTOP, SET ON TOP OF
FOOTING REINF. (NOT REQ'D TO
BE CENTERED @ JOINT)
NO KEY REQ'D. ROUGHEN SURFACE;
1/4" MIN. AMPLITUDE REQ'D
BEND FLOOR REINF AT
FTG. AS REQ'D
CONCRETE FOOTING
TRANS REINF
#6 HOOK @ 6" OC EF
CONCRETE WALL
CONCRETE WALL VERT REINF
4' -0
1'-2"
EXTEND SLAB REINF TO
EDGE OF FOOTING
ROOF SLAB REINFORCEMENT
NOT SHOWN
TH
IC
K
FO
O
TI
N
G
CONCRETE WALL HORIZ REINF
S-501 A13
SLOPE FROM
TANK CENTER
CONCRETE ROOF SLAB
CONCRETE ROOF SLAB
TOP MAT REINF
CHAMFER EDGE ON
DROP PANEL.
CONCRETE ROOF
SLAB BOT MAT REINF
ROOF DROP PANEL
DOWELS TO MATCH
CONCRETE COLUMN VERTICAL
REINF, PLACED RADIALLY
(8) ADDITIONAL #5 12'-0" LONG
EACH WAY CENTERED AT COLUMN
CONCRETE COLUMN
CONCRETE COLUMN VERT REINF
CONCRETE COLUMN TIES
1 1/2 EXTRA TURNS OF SPIRAL
BAR @ EACH END
DOWELS TO MATCH CONCRETE
COLUMN VERTICAL REINF
CONCRETE FOOTING REINF
CONCRETE FLOOR SLAB REINF
1.
2.
3.
NOTE:
ORIENT ROOF AND FLOOR BARS TO BE PARALLEL
TO COLUMN CENTERLINES.
SEE STRUCTURAL SCHEDULES FOR ADDITIONAL
THICKNESS AND REINFORCEMENT REQUIREMENTS
SEE EARTHWORK NOTES FOR FOOTING AND SLAB
PREPARATION
4' -0
4'-0"
1'-0"
6' -0
CONCRETE FLOOR SLAB
FOOTING WIDTH
2" CLR TYP
SEE WATER TANK ROOF PLAN
DROP PANEL WIDTH
6" M
IN
FO
O
TI
N
G
TH
IC
K
DESIGN CRITERIA
BUILDING CODE: 2021 IBC, ACI 318-19, ACI 350-20
CLASSIFICATION: RISK CATEGORY IV
LIVE LOADING
ROOF: 20 PSF
DEAD LOADING
ROOF: 112.5 PSF
SNOW LOADING (BASED ON 2018 UTAH GROUND SNOW LOAD MAP)
ELEVATION: 2,700 FT (APPROX.)
GROUND SNOW LOAD: Pg = 21 PSF EXPOSURE FACTOR: Ce = 0.9 SNOW IMPORTANCE FACTOR: Is = 1.2 THERMAL FACTOR: Ct = 1.0 CALCULATED SNOW LOAD: Pf = 15.875 PSF DESIGN SNOW LOAD: Pf = 24 PSF SLOPE FACTOR: Cs = 1.0
SEISMIC LOADING
LOCATION: 37.06553° LAT., -113.60152° LON.
SEISMIC IMPORTANCE FACTOR: Ie = 1.5 MAPPED SPECTRAL RESPONSE ACCELERATIONS: SS = 0.500g S1 = 0.163g
SITE CLASS: B
SPECTRAL RESPONSE COEFFICIENTS: SDS = 0.333g SD1 = 0.109g
SEISMIC DESIGN CATEGORY: B
SOILS
SOIL BEARING PRESSURE: 5,000 PSF
PROJECT GEOTECHNICAL INVESTIGATION: LANDMARK ENGINEERING
PROJECT NO. 230029 EARTHWORK
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
A.
B.
C.
D.
E.
F.
12.
13.
ENGINEER SHALL VERIFY CONDITION AND/OR ADEQUACY OF ALL SUBGRADES,
FILLS, AND BACK FILLS, ETC.
SHORE AND BRACE AS REQUIRED.
DE-WATER AS REQUIRED TO REMOVE STANDING WATER FROM
EXCAVATIONS.
FOUNDATIONS ARE SHOWN AND DIMENSIONED AS BEING FORMED. INCREASE
FOOTING WIDTHS BY 2" FOR FOOTINGS PLACED IN NEAT EXCAVATIONS.
CLEAN ALL DEBRIS FROM EXCAVATIONS.
NOTIFY ENGINEER 48 HOURS IN ADVANCE OF PLACING CONCRETE.
PROVIDE 12" MINIMUM FOOTING EMBEDMENT FROM FINISH GRADE FOR
FROST PROTECTION AT EXTERIOR FOOTINGS.
EXCAVATE SANDSTONE BEDROCK FOR FOOTINGS TO BEAR DIRECTLY ON.
FOOTING BEARING SURFACE SHOULD BE RELATIVELY SMOOTH, WITH
FRACTURED AND JAGGED UNDULATION BEING REMOVED. FILL VOIDS WITH
LEAN CONCRETE FILL. ANY VOIDS LARGER THAN 3" IN WIDTH AND 18" IN
DEPTH SHOULD BE FILLED WITH CEMENTITIOUS GROUT. GEOTECHNICAL
ENGINEER SHALL OBSERVE EXCAVATION PRIOR TO STRUCTURE PLACEMENT.
PROVIDE AT LEAST 4" OF UNTREATED BASE COURSE BENEATH FLOOR SLABS.
BACKFILL WALLS WITH ENGINEERED FILL.
ENGINEERED FILL USED FOR BACKFILL OF WALLS:
WELL-GRADED
NON-EXPANSIVE
MAXIMUM PARTICLE SIZE: 1-1/2"
FREE OF ORGANICS AND ALL DELETERIOUS MATERIALS
PERCENT PASSING NO. 200 SIEVE: 10% MAX
PLASTICITY INDEX: 9 OR LESS
COMPACT FILL AGAINST WALLS TO 95% OF MAXIMUM DRY DENSITY
DETERMINED BY ASTM D1557 WITH 2% OF OPTIMUM MOISTURE CONTENT.
PLACE ENGINEERED FILL IN MAXIMUM EIGHT-INCH THICK LOOSE LIFTS TO
ACHIEVE ADEQUATE COMPACTION.
ABBREVIATIONS
ADDNL ADDITIONAL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
BLDG BUILDING
BLKG BLOCKING
BN BOUNDARY NAILING
BOP BOTTOM OF PANEL
BRG BEARING
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONT CONTINUOUS
CTR CENTER
CTRD CENTERED
DBL DOUBLE
DF DOUGLAS FIR
DIA DIAMETER
EF EACH FACE
ELEV ELEVATION
EN EDGE NAILING
EW EACH WAY
EXIST EXISTING
FN FIELD NAILING
FND FOUNDATION
FT(') FOOT/FEET
FTG FOOTING
GA GAUGE
GYP BD GYPSUM BOARD
HORIZ HORIZONTAL
HSS HOLLOW STEEL SECTION
IN (") INCH
K KING STUD
LAT LATITUDE
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LVL LAMINATED VENEER
LUMBER
MECH MECHANICAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OPPOSITE HAND
PAF POWDER ACTUATED
FASTENER
PERP PERPENDICULAR
PL PLATE
PSF POUNDS PER SQUARE
FOOT
PSI POUNDS PER SQUARE
INCH
PSL PARALLAM BEAM
REINF REINFORCING
REQ'D REQUIRED
SIM SIMILAR
STRUC STRUCTURAL
T TRIMMER
TOF TOP OF FOOTING
TOS TOP OF SLAB
TOW TOP OF WALL
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED
OTHERWISE
VERT VERTICAL
QA PLAN
1.
2.
3.
4.
A.
B.
C.
D.
E.
F.
A.
B.
C.
D.
A.
1.
2.
3.
4.
5.
1.
2.
QUALITY ASSURANCE AGENCY (QAA) REQUIREMENTS:
THE OWNER OR REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
CHARGE ACTING AS THE OWNER'S AGENT SHALL ENGAGE A QUALIFIED
QUALITY ASSURANCE AGENCY TO PROVIDE ALL SPECIAL INSPECTION AND
QUALITY ASSURANCE TESTING FOR THE PROJECT. ALL QUALITY ASSURANCE
PERSONNEL ASSIGNED TO THE PROJECT SHALL PROVIDE WRITTEN
DOCUMENTATION TO THE BUILDING OFFICIAL DEMONSTRATING HIS OR HER
COMPETENCE AND RELEVANT EXPERIENCE OR TRAINING.
PRIOR TO CONSTRUCTION, THE QAA SHALL PREPARE A WRITTEN QUALITY
ASSURANCE IMPLEMENTATION PLAN FOR THE PROJECT. THE PLAN SHALL
INCLUDE A LIST OF PERSONNEL ASSIGNED TO THE PROJECT INCLUDING
MANAGEMENT PERSONNEL, INSPECTION PROCEDURES AND FREQUENCY,
PROPOSED TESTING METHODS AND FREQUENCY OF TESTING, AND
REPORTING PROCEDURES. THE PLAN SHALL ALSO OUTLINE METHODS OF
DOCUMENTING DEFICIENCIES AND REPORTING CORRECTIONS. A COPY OF
THE PLAN SHALL BE GIVEN TO THE CONTRACTOR FOR REVIEW AND
COORDINATION WITH SUBCONTRACTORS.
THE SPECIAL INSPECTOR SHALL INSPECT THE WORK PER CHAPTER 17 OF
THE IBC FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS. THE
SPECIAL INSPECTOR SHALL SEND REPORT TO THE OWNER, BUILDING
OFFICIAL, ENGINEER, AND CONTRACTOR. ALL NOTED DEFICIENCIES SHALL
BE NOTED IN THE REPORT AND SHALL BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE CONTRACTOR FOR CORRECTION. THE QAA SHALL
SUBMIT A FINAL SIGNED REPORT STATING THAT THE SPECIAL INSPECTION
WORK WAS, TO THE BEST OF THEIR KNOWLEDGE, IN CONFORMANCE WITH
THE PLANS, SPECIFICATIONS AND APPLICABLE WORKMANSHIP PROVISIONS
OF THE IBC.
CONTRACTOR IS ADVISED THAT ADDITIONAL SPECIAL INSPECTIONS AND
TESTING MAY BE REQUIRED BY THE AUTHORITY HAVING JURISDICTION.
SPECIAL INSPECTION: SPECIAL INSPECTION SHALL BE PROVIDED FOR THE
FOLLOWING ITEMS PER IBC 1704 AND 1707.
1. SOILS: SITE SOIL CONDITIONS, FILL PLACEMENT AND LOAD-BEARING
REQUIREMENTS SHALL BE INSPECTED AS REQUIRED BY IBC 1705.6, THE
APPROVED GEOTECHNICAL REPORT, AND THE CONSTRUCTION DOCUMENTS
PREPARED BY THE REGISTERED DESIGN PROFESSIONALS. SPECIAL INSPECTION
OF SOILS SHALL INCLUDE THE FOLLOWING:
VERIFY MATERIALS BELOW SHALLOW FOUNDATION ARE ADEQUATE TO
ACHIEVE THE DESIGN BEARING CAPACITY.
VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE
REACHED PROPER MATERIAL.
PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL
MATERIALS.
VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESS
DURING PLACEMENT AND COMPACTION OF COMPACTED FILL.
PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE SUBGRADE AND
VERIFY THAT SITE HAS BEEN PREPARED PROPERLY.
SOILS SHALL RECEIVE CONTINUOUS SPECIAL INSPECTION DURING
PLACEMENT OF MATERIALS TO VERIFY PROPER MATERIALS, DENSITIES,
AND LIFT THICKNESS.
2. CONCRETE AND EMBEDDED ITEMS IN CONCRETE SHALL BE SPECIAL
INSPECTED PRIOR TO AND DURING PLACEMENT OF CONCRETE. SPECIAL
INSPECTION OF CONCRETE SHALL INCLUDE THE FOLLOWING:
REINFORCING STEEL GRADE, SIZE AND PLACEMENT.
SURFACE PREPARATION AT COLD JOINTS INCLUDING PLACEMENT OF
KEYWAYS.
BOLT AND EMBED SIZE, CONFIGURATION AND PLACEMENT.
CONCRETE SHALL RECEIVE CONTINUOUS SPECIAL INSPECTION DURING
PLACEMENT, AND PERIODIC INSPECTION AFTER PLACEMENT TO
ENSURE PROPER CURING AND WEATHER PROTECTION PROCEDURES.
3. POST-INSTALLED ANCHORS, INCLUDING BUT NOT LIMITED TO EXPANSION
ANCHORS, ADHESIVE ANCHORS AND REBAR DOWELS, AND LOW VELOCITY
FASTENERS, SHALL RECEIVE SPECIAL INSPECTION PER THE CODE EVALUATION
REPORTS FOR THE ANCHORS.
CONTINUOUS SPECIAL INSPECTION IS REQUIRED DURING THE
INSTALLATION OF ALL ADHESIVE ANCHORS AND REBAR DOWELS.
SPECIAL INSPECTOR SHALL VERIFY THE FOLLOWING:
ANCHOR SIZE AND STEEL GRADE.
HOLE DIAMETER, LOCATION AND TYPE OF DRILL BIT.
CLEANLINESS OF HOLE AND ANCHOR.
ADHESIVE APPLICATION.
ANCHOR EMBEDMENT.
STRUCTURAL TESTING: THE FOLLOWING MATERIALS SHALL BE TESTED PER IBC
1705. THE OWNER RESERVES THE RIGHT TO TEST ANY AND ALL MATERIALS
USING ANY APPROPRIATE NON-DESTRUCTIVE PROCEDURE. ANY ITEMS FOUND TO
BE DEFICIENT SHALL BE CORRECTED AND RETESTED AT NO ADDITIONAL COST TO
THE OWNER.
EARTHWORK: ALL COMPACTED STRUCTURAL FILL SHALL BE TESTED
TO VERIFY SOIL GRADATION, LIFT THICKNESS, AND COMPACTION
REQUIREMENTS. SEE THE PROJECT SPECIFICATIONS FOR TESTING
FREQUENCY AND ACCEPTABILITY CRITERIA.
CONCRETE STRENGTH VERIFICATION AND TESTING. ALL CONCRETE
SHALL BE TESTED TO VERIFY STRENGTH, SLUMP, UNIT WEIGHT, AIR
CONTENT, AND TEMPERATURE. SEE THE PROJECT SPECIFICATIONS
FOR TESTING CRITERIA, TESTING FREQUENCY AND ACCEPTABILITY
CRITERIA.
SPLICE LENGTH (IN.) FOR F'c = 5,000 PSI
LOCATION
REINFORCEMENT SIZE
#11
TOP
OTHER
#10
#9
#8
#7
#6
#5
#4
#3
CONCRETE REINFORCEMENT
LAP SPLICES
1.
2.
3.
4.
5.
6.
TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE LENGTHS ARE
BASED ON ACI 318-19, SECTIONS 25.4.2 AND 25.5.2 RESPECTIVELY.
TABULATED VALUES FOR BEAMS OR COLUMNS ARE BASED ON TRANSVERSE
REINFORCEMENT AND CONCRETE COVER MEETING MINIMUM CODE
REQUIREMENTS.
LAP SPLICE LENGTHS SHOWN ARE FOR CLASS B AND CASE 1.
TOP REINFORCEMENT IS HORIZONTAL REINFORCEMENT THAT HAS MORE
THAN TWELVE INCHES OF FRESH CONCRETE CAST BELOW IT. THIS
INCLUDES HORIZONTAL REINFORCEMENT IN WALLS. ALL VERTICAL BARS
ARE CONSIDERED AS "OTHER".
FOR LIGHTWEIGHT CONCRETE AGGREGATE CONCRETE, MULTIPLY
TABUL…