9-Addendum 2 RFP 3809 Variable Frequency Drive (VFD) over 100HP Attachment B.pdf

PDF 132 KB Posted

Attached to
RFP-WM-3809 - VARIABLE FREQUENCY DRIVES (VFD) OVER 100HP
Solicitation number
RFP-WM-3809
Issued by
Riverside County, California

About this file

This document is Addendum #2 - Attachment B for RFP 3809, a Variable Frequency Drive (VFD) project issued by Eastern Municipal Water District (EMWD) involving six different VFD replacements across three regional water reclamation facilities: San Jacinto, Moreno Valley, and Perris Valley. The project involves replacing existing VFDs for various pumps with specifications ranging from 100 to 300 horsepower, manufactured between 1994 and 2012, and currently using brands like ABB and Toshiba.

The equipment details reveal consistent electrical specifications across the sites, with all units operating at 480 volts, 3-phase power. The VFDs have varying current output requirements from 127.65 to 340.4 amps, with most designated as ULH (Ultra Low Harmonic) units, except for one 6 Pulse unit. Motor usages include vertical turbine, centrifugal, submersible centrifugal chopper, and other pump types. The age of the existing equipment suggests this is a modernization and replacement project to upgrade aging infrastructure across EMWD's water reclamation facilities, ensuring continued reliable operation of critical water management infrastructure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFP 3809 Variable Frequency Drive (VFD) - Over 100 HP Project 2

ADDENDUM #2 - Attachment B

RFP 3809 Page 1 of 3

1. San Jacinto Regional Water Reclamation Facility (SJRWRF)

Equipment Name T3100 TEPS UTILITY WATER

PERRIS VALLEY EFFLUENT

PUMP 3 VFD

Manufacturer Date 2012 Horsepower 100 Volts 480 Phase 3 Current Brand ABB Part Number ACS800-U4-550-5+E210+P901 Serial Number Unknown Motor Usage Vertical Turbine Motor Nameplate HP 100 Motor Nameplate AMPs 111 Motor Nameplate SF 1.15 Minimum VFD Current Output Required

127.65

ULH or Non-ULH ULH

2. Moreno Valley Regional Water Reclamation Facility (MVRWRF)

Equipment Name T3200 IPS PUMP 1 VFD

Manufacturer Date 2006 Horsepower 100 Volts 480 Phase 3 Current Brand Toshiba Part Number VF-AS1-4750PL-HN Serial Number 9227 05131421 0043 Motor Usage Centrifugal Pump Motor Nameplate HP 100 Motor Nameplate AMPs 122 Motor Nameplate SF 1.15 Minimum VFD Current Output Required

140.3

RFP 3809 Page 2 of 3

3. Moreno Valley Regional Water Reclamation Facility (MVRWRF)

Equipment Name T3200 TEPS PUMP 4 VFD Manufacturer Date 2009 Horsepower 150 Volts 480 Phase 3 Current Brand ABB Part Number ACS800 Serial Number 2102000957 Motor Usage Vertical Turbine – 4 Stage Motor Nameplate HP 250 Motor Nameplate AMPs 273 Motor Nameplate SF 1 Minimum VFD Current Output Required

4. Perris Valley Regional Water Reclamation Facility (PVRWRF)

Equipment Name T3500 TEPS U/W PUMP 4 VFD

Manufacturer Date 2005 Horsepower 150 Volts 480 Phase 3 Current Brand Toshiba Part Number W7 Serial Number 060805743 Motor Usage Unknown Motor Nameplate HP 150 Motor Nameplate AMPs 168 Motor Nameplate SF 1.15 Minimum VFD Current Output Required

193.2

RFP 3809 Page 3 of 3

5. Moreno Valley Regional Water Reclamation Facility (MVRWRF)

Equipment Name T3200 IPS PUMP 3 VFD

Manufacturer Date 2010 Horsepower 200 Volts 480 Phase 3 Current Brand ABB Part Number ACS800 Serial Number 2102001084 Motor Usage Centrifugal Pump Motor Nameplate HP 218 Motor Nameplate AMPs 264 Motor Nameplate SF 1.25 Minimum VFD Current Output Required

6. Perris Valley Regional Water Reclamation Facility (PVRWRF)

Equipment Name T3500 IPS PUMP 3 VFD

Manufacturer Date 1994 Horsepower 300 Volts 480 Phase 3 Current Brand Toshiba Part Number H7 Serial Number A060304717 Motor Usage Submersible Centrifugal Chopper

Pump Motor Nameplate HP 250 Motor Nameplate AMPs 296 Motor Nameplate SF 1.15 Minimum VFD Current Output Required

340.4

ULH or Non-ULH 6 Pulse

File details come from the government source that posted it. Updated .