This document is an Installation Facilities Standards (IFS) Lighting Requirements specification for Nellis and Creech Air Force Bases dated 22 January 2019. The document provides comprehensive technical requirements for interior and exterior lighting fixtures, mandating the exclusive use of solid-state LED luminaires with specific performance characteristics. Key requirements include LED fixtures with color temperatures between 4000K-4500K, minimum 10-year luminaire and 5-year driver warranties, 50,000-hour rated life, and operation in ambient temperatures from 0-120 degrees Fahrenheit.
The specification details lighting control requirements across various facility types, emphasizing energy efficiency and security. All interior and exterior lighting must be controlled by motion detectors, with exceptions requiring Contracting Officer approval. Specific guidelines are provided for different lighting applications, including interior fixtures, high bay fixtures, street and parking lot lighting, wall pack and walkway fixtures, area and security lighting, and airfield/apron lighting. The document also mandates compatibility with CCTV and night vision equipment, and requires lighting design approvals from base Security Forces and Antiterrorism Force Protection (ATFP) offices for certain applications.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NELLIS AND CREECH AFB
INSTALLATION FACILITIES STANDARDS (IFS)
LIGHTING REQUIREMENTS
22 JAN 2019
This document is an appendix to Nellis & Creech Air Force Bases IFS which is located here:
https://www.wbdg.org/ffc/af-afcec/installation-facilities-standards-ifs/nellis-creech-afb-ifs
1. Codes and Standards: All design and construction shall be in compliance with the most recent versions of the following:
Nellis & Creech Air Force Bases Installation Facilities Standards (IFS) Unified Facilities Criteria (UFC) 3-530-01 Design: Interior, Exterior Lighting and
Controls Unified Facilities Guide Specification (UFGS) 26 51 00.00 40 for interior lighting UFGS 26 56 00 for exterior lighting UFGS 26 56 19.00 40 for roadway lighting UFGS 26 56 23.00 40 for area lighting UFGS 26 56 36 00 40 for flood lighting UFGS 26 56 20.00 10 for airfield and heliport lighting AFI 31-101 Integrated Defense for security applications
2. All interior and exterior lighting fixtures shall comply with the following:
2.1 Fixtures shall be solid-state LED luminaires designed specifically for LED technologies (typically flat to compliment the directional characteristics of LEDs) with integrated controls and remote lighting level adjustment/dimming capabilities.
2.2 Fixtures shall have a color temperature in KELVIN of between 4000K and 4500K.
Fixtures shall have appropriate illumination volume (foot candle/lumen) output to meet work surface UFC guidelines per fixture/space photometric analysis (using typical manufacturer software).
2.3 LED Luminaires shall have a minimum warranty of 10 years.
2.4 LED Drivers shall have a minimum warranty of 5 years.
2.5 Ballasts and lamps shall have a minimum rated life of 50,000 hours.
2.6 Fixtures shall be rated to operate at ambient temperatures between 0 degrees F and
120 degrees F or higher. This requirement does not apply to Interior Recessed, Downlight, and Wall Wash Fixtures.
2.7 T-8, T-5, Induction, and High Intensity Discharge fixtures are prohibited.
https://www.wbdg.org/ffc/af-afcec/installation-facilities-standards-ifs/nellis-creech-afb-ifs
2.8 All interior (and all practicable exterior) facility lighting fixtures shall be controlled by motion detectors. Any exceptions shall be requested by Contractor for approval by the Contracting Officer. No exceptions will be made for restroom and conference room fixtures. Wall switches shall be installed to turn sensors/lights on and off as needed (i.e. lights off in a conference room in order to view wall screens). Sensors shall be placed in a location not affected by movement outside of open doorways.
Daylighting wall switches shall be installed to allow dimming/turn-off of fixtures located nearest to windows, hangar/truck doors or similar daylighting sources. This may also be accomplished with photocell controls for automatic dimming/turn-off.
3. Interior Fixtures located 20 feet or less above finished floor:
3.1 Luminaires shall be solid-state LED Luminaires (preferably flat plate as opposed to
Silver Bowl, recessed, or light scattering fixtures) with full remote dimming controls.
3.2 LED linear replacements for existing fluorescent fixtures may be used provided that the following conditions are met:
3.2.1 The existing ballast shall be replaced with LED Driver or electronic ballast specifically for LED applications.
3.2.2 Fixtures shall have a color temperature as indicated in 2.2. Other color temperatures may be considered in housing applications, hospitality applications, and in maintenance facilities. See UFC 3-530-01 for additional information.
3.3 Provide wire guards for all open LED linear replacements.
4. Interior High Bay Fixtures located higher than 20 feet above work surface:
Each fixture shall have on/off motion sensors (with partial shutoff delay before full off), and be remotely adjustable (infrared or Bluetooth) light output/on-off control.
5. Exterior Street and Parking Lot Fixtures:
5.1 All street and parking lot light fixtures shall include appropriate controls for dusk till dawn photocells (one photocell per fixture). Parking area fixtures shall have automatic dimming for late-night to dawn operation to increase energy savings when parking lots are typically vacant.
5.2 Glass fixture lens are preferred.
6. Exterior Wall Pack and Walkway Fixtures:
6.1 All wall pack lighting fixtures shall include dusk till dawn photocells; wall-packs away from ingress/egress points and not illuminating Air Force assets (mechanical and electrical equipment, trash enclosures, etc.) shall also have motion sensor controls to eliminate energy waste and night sky pollution.
6.2 All walkway lighting fixtures shall include dusk till dawn photocells.
6.3 Glass fixture lens are preferred.
6.4 Light bollards shall be full cutoff type and vandal resistant. Bollards shall not have exposed vertical plastic/acrylic lens. Electrical service shall be 208v maximum with 120v to ground.
7. Exterior Area, Flood, Canopy, and Security Lighting Fixtures:
7.1 As appropriate, Contractor shall obtain lighting design approval from base Security
Forces and/or base Antiterrorism Force Protection (ATFP) office.
7.2 Fixtures shall be compatible with CCTV, and night vision goggles.
7.3 Fixtures shall meet appropriate illumination requirements for security and ATFP.
7.4 Certain large area security lighting applications may employ individual fixture motion sensor on-controls to identify intrusion points with lighting where otherwise fixtures remain off, saving energy.
7.5 Automatic dimming/on-off and motion sensors shall be used to allow energy savings during low use times while maintaining some illumination for adequate security when dimmed.
8. Exterior Airfield / Apron Lighting Fixtures:
8.1 As appropriate, Contractor shall obtain lighting design approval from Airfield
Operations office, base Security Forces, and/or base ATFP office.
8.1.1 Fixtures shall be compatible with CCTV, and night vision goggles.
8.1.2 Fixtures shall meet appropriate illumination requirements for aircraft and equipment operations and ATFP/security.
8.2 Glass fixture lens are preferred.
8.3 Automatic Bi-level dimming with occupancy sensors shall be explored to allow energy savings when lights are used infrequently, or when instant-on LED capabilities enhance security achievement. Certain locations (i.e. personnel/vehicle doors or gates) shall have motion sensors that only dim lighting to maintain access point illumination.
9. Reference separate Nellis-Creech IFS appendix document for non-lighting Electrical
Requirements.
END OF LIGHTING REQUIREMENTS