These are plumbing construction documents for the Gregg County Precinct 2 facility located at 800 Gilmer Road in Longview, Texas, prepared by EMA Engineering & Consulting, Inc. The documents are 100% construction documents dated May 29, 2025, covering plumbing demolition, site plans, floor plans, roof plans, details, and fixture schedules for a county government building renovation project. The plans specify comprehensive plumbing system modifications including new sanitary sewer lines, domestic water systems, gas lines, condensate drains, and fixtures, with all plumbing work to conform to 2012 International Fuel Gas Code (IFGC) and 2012 International Plumbing Code (IPC).
The project includes installing various plumbing fixtures such as wall-mounted lavatories, water closets, urinals, a mop sink, breakroom sink, exterior hose bibb, bottle filling station, and a 40-gallon electric water heater. The documents outline detailed specifications for gas regulators, pipe supports, wall and floor penetrations, and require careful coordination with mechanical and electrical contractors. Key technical considerations include maintaining proper slope for condensate drains, installing trap primers, coordinating utility connections, and ensuring compliance with accessibility standards. The design emphasizes precise installation requirements, including specific mounting heights, valve placements, and fire-rated penetration details.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P35
P35
P35
P35
P35
P35
P35
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Ty J. Cobb
144952TX
REVIEW ONLY
5/29/2025 10:11:40 AM
PD1.1
PLUMBING
DEMOLITION FLOOR
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
KS
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
3/16" = 1'-0"
1 PLUMBING DEMOLITION FLOOR PLAN
PLUMBING DEMOLITION GENERAL NOTES
1. CONTRACTOR TO VISIT SITE AND BE FAMILIAR WITH BUILDING
MECHANICAL AND ELECTRICAL LAYOUTS.
2. ALL MATERIAL, EQUIPMENT, DUCTS, PIPE, ETC. TO BE REMOVED
SHALL BE DISPOSED OF OFF SITE IN A LEGAL AND LAWFUL
MANNER.
3. CAP ANY UNUSED PIPE AT FLOOR, WALL, OR CEILING. REMOVE
MATERIAL NOT BEING REUSED.
4. IF ASBESTOS IS FOUND, CONTACT OWNER IMMEDIATELY. DO NOT
WORK IN ANY AREA SUSPECTED TO CONTAIN ASBESTOS.
5. ALL EXISTING EQUIPMENT SHOWN IN APPROXIMATE LOCATION.
ALL EXISTING CONCEALED PIPING SHOWN IS BASED ON THE MOST
RECENT EXISTING M.E.P. AND CIVIL DRAWINGS AVAILABLE. FIELD
VERIFY.
6. TAKE CARE NOT TO DESTROY INSULATION VALUE TO ANY WATER
PIPING BEING REUSED. REPAIR AS NECESSARY.
7. CONTRACTOR TO VERIFY LOCATION OF ALL UTILITIES AND
RELOCATE AS REQUIRED BY NEW CONSTRUCTION.
PLUMBING DEMOLITION PLAN NOTES
P35 REMOVE EXISTING PLUMBING FIXTURE, FAUCET, SUPPLIES,
CARRIER, FLOOR DRAIN, ETC. CAP SERVICE LINES IN A
CONCEALED LOCATION.
06-02-2025
06-02-2025
06-06-2025
06-06-2025
05-01-2025
APPROXIMATE LOCATION
FOR FUTURE GENERATOR
NEW GAS METER
APPROXIMATE LOCATION
PS3
PS1
PS4
PS2
1" G
1" G
1 1/4" G
3" G
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Ty J. Cobb
144952TX
REVIEW ONLY
5/29/2025 10:11:42 AM
PS1.1
PLUMBING SITE PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
KS
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
PLUMBING SITE GENERAL NOTES
1. CONTRACTOR AND SUBCONTRACTORS SHALL VERIFY LOCATION,
CONDUCT TEST AND INSPECTIONS, COORDINATE WITH UTILITIES,
OWNER'S REPRESENTATIVES, AND CHECK FOR ALL UNDERGROUND
UTILITIES AND LINES BEFORE DITCHING TAKES PLACE.
CONTRACTOR AND SUBCONTRACTORS PERFORMING THESE
DUTIES SHALL BE RESPONSIBLE FOR ANY REPAIRS OF CUT OR
DAMAGED LINES AND UTILITIES. THERE ARE LINES AND UTILITIES
NOT SHOWN ON PLANS.
2. ALL INSTALLATIONS SHALL BE PER THE AUTHORITY OF HAVING
JURISDICTION. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING WITH THE CITY FOR ALL OF THE NECESSARY TAPS
REQUIRED, MANHOLES, WATER METERS, BACK-FLOW
PREVENTERS, DETECTOR CHECKS, ETC. AS REQUIRED.
3. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE
WITH THE AUTHORITY HAVING JURISDICTION ANY REQUIRED
STREET BORINGS (WET OR DRY) FOR NEW UTILITY TIE-INS.
4. IT IS THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR TO
COORDINATE ALL UTILITY CONNECTIONS WITH UTILITY
CONTRACTOR PRIOR TO CONSTRUCTION.
PLUMBING SITE PLAN NOTES
PS1 2-1/2" DOMESTIC WATER STUB-OUT. EXTEND TO CONNECTION.
REFER TO CIVIL PLANS FOR WATER METER AND BACK-FLOW
PREVENTER LOCATIONS.
PS2 SAW-CUT EXISTING SLAB FOR INSTALLATION OF NEW GAS
PIPING. PATCH TO MATCH EXISTING AS NECESSARY.
PS3 4" SANITARY SEWER STUB-OUT 46" B.F.F. EXTEND TO
CONNECTION. REFER TO CIVIL PLANS FOR CONTINUATION.
PS4 1-1/4" MEDIUM PRESSURE GAS LINE SLEEVED UNDER CONCRETE.
1" = 20'-0"
1 PLUMBING SITE PLAN
GAS REGULATOR SCHEDULE
MARK MANUFACTURER C.F.H. IN OUT
1 ITRON SERIES B 3076 1 1/4" 3"
2 ITRON SERIES B 175 1" 1 1/4"
GAS LOAD BREAKDOWN
PLUMBING CONTRACTOR TO COORDINATE
WITH GAS REGULATOR MANUFACTURER ALL
ORIFICE AND SPRING SIZES, AS REQUIRED, T...
TYPE C.F.H.
EMERGENCY
GENERATOR
HVAC UNITS 175
TOTAL CONNECTED GAS
LOAD
SAW-CUT EXISTING SLAB FOR
INSTALLATION OF NEW GAS
PIPING. PATCH TO MATCH
EXISTING AS NECESSARY.
800 GILMER RD PRECINCT 2
06-02-2025
06-02-2025
06-06-2025
06-06-2025
B2
A1 C1
D1
E1
G2M1
G1
F1 J1
A1
A1 C1
D1
B2
A2
A2
A2
B2
B2
D1
D1
D1
A1
B1
MICHELLE
DRIVE THRU
TAX CLERKS
SERVICE AREA
ELEC
ENTRY
WAITING
STRG
SUPER OFF.
WEB DEAL
STRG
IT
CONFERENCE
WORKROOM
BREAKROOM
STRG
JAN
MENS
BREAKROOM
TIM
COURT ROOM
WMNS
UNISEX
SUPER OFF.
OPEN OFFICE
STRG
HALL
JP WAITING
RAY
RR
STRG
STRG
STRG
ROGER
REFER TO SHEET PS1.1
FOR CONTINUATION
REFER TO SHEET PS1.1
FOR CONTINUATION
P8
TIE-IN TO EXISTING SANITARY SEWER.
(FIELD VERIFY EXACT LOCATION)
P3
P3
P3
P3
P3
1/2" CW
1/2" HW
2" SS
2 1/2" CW 3/4" HW 3/4" HW
3/4" HW
3/4" HW
2 1/2" CW
2 1/2" CW
PL8.1
PL8.1
PL8.1
4" SS
4" SS
3/4" HW
2 1/2" CW
3/4" HW
3/4" HW
3/4" CW
3/4" HW
4" SS
P5
P4
P4
P4
P4
P4
P5
P4
P4
P5
P4
P5
P4
P4
P4
H1
H1
H1
P54
P53
P1
1/2" CW
1/2" CW
1/2" CW
P16
P17
P30
P4
P32
P20
2 1/2" CW
4" SS
P2
1/2" CW 4" SS
4" SS
4" SS
REFER TO SHEET PS1.1
FOR CONTINUATION
P4
P10
P10
R1 P6
1" COND
1" COND
1" COND
1" COND
1" COND
1" COND
1" COND
1" COND1" COND
1" COND
1" COND
P19
1" COND
P19
1" COND
NO PIPING ABOVE
IT ROOM
NO PIPING ABOVE
ELECTRICAL ROOM
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Ty J. Cobb
144952TX
REVIEW ONLY
5/29/2025 10:11:44 AM
PL1.1
PLUMBING FLOOR
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
KS
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
ALL DOMESTIC HOT WATER SHALL MEET 2015 IECC HOT WATER
REQUIREMENTS.
AT LOCATIONS OF HOT WATER LOOP PIPING GOING DOWN IN
WALL AND BACK UP, PROVIDE 1/2" HOT WATER TO CONNECT
TO EACH HAND SINK/LAVATORY. HOT WATER LOOP PIPING
SHALL BE WITHIN 2'-0" OF THE CONNECTION TO THE FIXTURE,
PER 2015 IECC. PROVIDE 3/4" TO CONNECT TO EACH LAVATORY
STATION.
PRIOR TO ANY SAWCUTTING, VERIFY THAT SLAB IS NOT A 2-
WAY SLAB. IF SLAB IS 2-WAY, THEN CONTACT STRUCTURAL
ENGINEER FOR FURTHER GUIDANCE BEFORE ANY
SAWCUTTING.
PLUMBING CONTRACTOR IS RESPONSIBLE FOR REPLACING
ANY EXISTING CEILING TILES DAMAGED DURING INSTALLATION
OF NEW PLUMBING PIPING ABOVE EXISTING CEILINGS.
PLUMBING GENERAL NOTES
1. SEE SHEET PL7.1 FOR GENERAL NOTES APPLICABLE TO THE
ENTIRE DRAWING SET.
PLUMBING PLAN NOTES
P1 TWO-WAY CLEANOUT
P2 ONE-WAY CLEANOUT
P3 WALL CLEANOUT
P4 DOWN IN WALL/CHASE
P5 HOT WATER LOOP DOWN IN WALL/CHASE TO WITHIN
2'-0" OF LAVATORY PER IECC, THEN BACK UP TO
ABOVE CEILING.
P6 CONTRACTOR TO CONNECT DISHWASHER TO SINK
P8 UP FROM BELOW SLAB
P10 3" VENT UP TO ROOF.
P16 CONDENSATE DRAIN DOWN IN WALL, TIE-IN TO P-TRAP
AT SINK WITH TAILPIECE
P17 CONDENSATE DRAIN DOWN TO MOP SINK/FLOOR
SINK/HUB DRAIN
P19 CONDENSATE DRAIN FROM WALL UNIT. LINE
PRESSURIZED FROM INTERNAL CONDENSATE PUMP.
(ROUTE SEPARATELY FROM GRAVITY SYSTEMS OR
TIE INTO TOP OF GRAVITY PIPE)
P20 DOWN TO CONNECTION
P30 BLANK
P32 HOT WATER RETURN
P53 DOWN TO LOWER LEVEL CEILING SPACE
P54 UP TO HIGHER LEVEL CEILING SPACE
True
PROJECT
NORTH
3/16" = 1'-0"
1 PLUMBING FLOOR PLAN
SAW-CUT EXISTING SLAB FOR
INSTALLATION OF NEW SANITARY
SEWER PIPING. PATCH TO MATCH
EXISTING AS NECESSARY.
06-02-2025
06-02-2025
06-06-2025
06-06-2025
12' - 5"
P14
3" V.T.R.
P30
P22
P31
P50
P50
1" COND
1" COND
1" COND
1" COND
1" COND
1" COND
1" COND
P14
P14
P14
P14
P14
P14
1" G 1" G
1" G
1" G
1" COND
1" COND
1 1/4" G
1" G
1 1/4" G1 1/4" G
1 1/4" G
1 1/4" G
1" G
1" COND
1" COND
1" COND
1" COND
1" COND
1" COND
1" G
1 1/4" G
1" G
1 1/4" G
1 1/4" G
1" G
2" V.T.R.
2" V.T.R.
2" V.T.R.
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Ty J. Cobb
144952TX
REVIEW ONLY
6/6/2025 11:06:13 AM
PL6.1
PLUMBING ROOF
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
KS
06-06-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
PLUMBING ROOF GENERAL NOTES
1. FURNISH AND INSTALL CUTOFF VALVES UPSTREAM OF EACH GAS
REGULATOR. FURNISH AND INSTALL CUTOFF VALVES AT EACH
EQUIPMENT TIE-IN AND VERTICAL RISERS.
2. REFER TO HOODED ROOF PENETRATION DETAIL FOR PROPER
ROOF PENETRATION.
3. ALL CUTOFF VALVES AND REGULATOR VENTS IN HORIZONTAL
POSITION SHALL BE INSTALLED AT 3 OR 9 O'CLOCK POSITION.
4. REFER TO DETAILS FOR GAS REGULATOR DETAIL.
5. THIS DESIGN UTILIZES A CONVERSION FACTOR OF 1000 B.T.U.H.
PER C.F.H.
6. MAINTAIN A MINIMUM OF 10'-0" FROM GAS REGULATORS AND ALL
OUTDOOR AIR INTAKES.
ALL CONDENSATE PIPE CONNECTIONS SHALL BE 1" NOMINAL PIPE SIZE.
CONNECT TO EACH ROOFTOP UNIT WITH P-TRAP.
PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL GAS COCK VALVES
PRIOR TO CONNECTION TO EACH UNIT.
ALL EQUIPMENT GAS PIPE CONNECTIONS SHALL BE 1" NOMINAL PIPE SIZE
UNLESS OTHERWISE NOTED.
ROOF PIPE SUPPORTS SHALL BE FURNISHED AND INSTALLED AT
REQUIRED SPACING.
PLUMBING GENERAL NOTES
1. SEE SHEET PL7.1 FOR GENERAL NOTES APPLICABLE TO THE
ENTIRE DRAWING SET.
PLUMBING PLAN NOTES
P14 CONDENSATE TIE-IN TO UNIT/AIR HANDLER WITH P-TRAP
P22 GAS UP AND OVER
P30 BLANK
P31 CONDENSATE UP AND OVER
P50 DOWN TO LEVEL BELOW
1/8" = 1'-0"
1 PLUMBING ROOF PLAN
GAS REGULATOR SCHEDULE
MARK MANUFACTURER C.F.H. IN OUT
1 ITRON SERIES B 3076 1 1/4" 3"
2 ITRON SERIES B 175 1" 1 1/4"
GAS LOAD BREAKDOWN
PLUMBING CONTRACTOR TO COORDINATE
WITH GAS REGULATOR MANUFACTURER ALL
ORIFICE AND SPRING SIZES, AS REQUIRED, T...
TYPE C.F.H.
EMERGENCY
GENERATOR
HVAC UNITS 175
TOTAL CONNECTED GAS
LOAD
ALL PLUMBING PIPING
TO CONFORM WITH 2012
IFGC AND 2012 IPC.
06-06-2025 City Comments
06-06-2025
06-06-2025
2.
1.
NOTES:
3.
ELECTRIC WATER HEATER SUSPENDED WITH CIRCULATOR
TEMPERED & COLD SUPPLY LAVATORY DETAIL
ROOF PIPING SUPPORT
N.T.S.
N.T.S. (PER IECC 2015 C404)
N.T.S.
PIPING
(COLD) CHROME
PLATED TUBING SUPPLY
(COLD)
ANGLE STOP
P-TRAP
8"
8"
(HOT)
ANGLE
STOP
(HOT) CHROME PLATED
TUBING SUPPLY
(TEMPERED/COLD) lAVATORY/FAUCET
FINISHED FLOOR
(MAX.18")
(TEMPERED) STAINLESS
STEEL BRAIDED SUPPLY
H
C
ROUTE BEHIND BASIN
BOWL TO HIDE
THERMOSTATIC
MIXING VALVE
RUBBER BLOCK
SPACER
WALL
BRAIDED SUPPLY
THERMOSTATIC MIXING VALVE WITH BRACKET
WALL SCREW
AND ANCHOR
THERMOSTATIC MIXING VALVE MUST HAVE BRACKET FOR MOUNTING TO WALL.
NOTES:
PROVIDE RUBBER SPACER BETWEEN WALL AND TMV.
WALL ANCHOR SYSTEM MUST BE USED.
STAINLESS STEEL SUPPLY LINES MUST BE KEPT TO MINIMUM LENGTH.
(MAX.12")
(COLD) STAINLESS
STEEL BRAIDED SUPPLY
LONG SWEEPING
ELBOW
RETURN
WATER HEATER
(W/ DISCONNECT)
2" DEEP ROUND GALVANIZED
STEEL DRAIN PAN
ROUTE TEMPERATURE AND
PRESSURE RELIEF DRAIN TO
FLOOR DRAIN/ FLOOR SINK OR
MOP SINK.
TEMPERATURE AND PRESSURE
RELIEF VALVE. DO NOT REDUCE
VALVE / PIPE SIZE.
PROVIDE DI-ELECTRIC CONNECTIONS AT
ALL WATER HEATER CONNECTIONS
UNION
(TYPICAL)
HOT WATER
CHECK VALVE
DRAIN DOWN
IF PIPING IS RUN IN WALLS, THEN STUB-OUT
FROM WALL WITH CHROME ESCUTCHEON.
PIPING INSULATION TO COVER ALL UNIONS,
VALVE BONNETS, AND FITTINGS. MITER ALL
TERMINATION POINTS OF INSULATION. GLUE
AND MASTIC ALL INSULATION JOINTS. ALL
A.S.M.E. WATER HEATERS SHALL BE INSTALLED
WITH A.S.M.E. EXPANSION TANKS.
UNION
HOT WATER SUPPLY
THERMOMETER
THERMOMETER WELL
ROUTE DRAIN LINE TO
FLOOR DRAIN/ FLOOR
SINK OR MOP SINK
CHECK VALVECOLD WATER SUPPLY
STRAP TO WALL OR
SUSPEND FROM ABOVE
EXPANSION TANK
[A.S.M.E. AS
REQUIRED BY LOCAL
CODES]
UNION
FULL PORT
QUARTER TURN
BALL VALVE
HEAT
TRAP
HEAT
TRAP
DOUBLE NUT
UNI-STRUT HARNESS
1/2" ALL THREAD
DOUBLE NUTJOIST
ANGLE SUPPORT BOLTED
TO TOP CHORD OF JOIST
(SIZE BASED ON SPAN AND
WATER HEATER SIZE)
A Q
AQUASTAT '_m at chpr op '_m at chpr op
THE CIRCULATION PUMP WITH INTEGRAL PRESSURE
SENSOR AND AQUASTAT TO BE PROVIDED UNDER J1 DESIGNATION
IN THE PLUMBING SCHEDULE
CIRCULATION
PUMP WITH
INTEGRAL
PRESSURE
SENSOR
PRESSURE SENSOR ON
PUMP AND AQUASTAT TO BE
CONNECTED TO PUMP IN
PARALLEL.
PIPE SUPPORT (ADJUSTABLE)
1/2" TRAFBLOC - SCRAPE ROOF
AND ATTACH WITH MASTIC
ALL PIPE SUPPORTS TO BE SELECTED BASED
ON THE MANUFACTURERS REQUIREMENTS
FOR VARIES PIPE SIZES AND FOR SYSTEM
TYPE THE PIPE IS SERVING
NOTE: "E-(ABBRIVATION)" = EXISTING PIPING
NOTE: NOT ALL SYMBOLS ARE USED
PLUMBING SYMBOLS
ACID LINEA
COMPRESSED AIR LINECA
CONDENSATE LINECOND
CRAWLSPACE DRAIN LINECRAWL
DOMESTIC COLD WATER LINECW
DOMESTIC HOT WATER LINEHW
DOMESTIC FILTERED WATER LINEFW
FIRE PROTECTION LINEFP
FIRE PROTECTION DRY LINEFP-D
FIRE PROTECTION OTHER LINEFP-O
FIRE PROTECTION PRE-ACTION LINEFP-PA
GAS LINEG
GREASE LINEGL
PUMP DISCHARGE LINESP
ROOF DRAIN - OVERFLOW LINEORD
ROOF DRAIN - PRIMARY LINERD
SAND/OIL WASTE LINES/O
SOLIDS WASTE LINESW
SANITARY SEWER LINESS
STORM DRAINAGE LINESD
SUB-SOIL DRAIN LINESSD
VENT LINEV
SPRINKLER LINEF
INDICATES SAWCUT SLAB AND
PATCH TO MATCH AFTERWARDS
V.T.R. VENT THROUGH ROOF
GAS COCK (VALVE)
WATER METER
PLUMBING RISER
P
FLOOR SINK/O.S.D.
GAS METER
DRAIN
CAP
HOSE BIBB
CUT-OFF VALVE
PRIMARY/OVERFLOW ROOF DRAIN
CUT-OFF VALVE
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Ty J. Cobb
144952TX
REVIEW ONLY
6/6/2025 11:06:13 AM
PL7.1
PLUMBING SYMBOLS,
DETAILS & GENERAL
NOTES
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
KS
06-06-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
PLUMBING GENERAL NOTES
1. PLUMBING CONTRACTOR SHALL REFER TO ARCHITECTURAL
PLANS FOR A.D.A. PLUMBING FIXTURE AND STANDARD MOUNTING
HEIGHTS.
2. PLUMBING CONTRACTOR TO COORDINATE ALL PIPING ROUTING
ABOVE WITH MECHANICAL AND ELECTRICAL CONTRACTORS
BEFORE INSTALLING.
3. ALL VALVES SHALL BE INSTALLED NO HIGHER THAN 2'-0" ABOVE
THE CEILING. ACCESS DOORS TO BE INSTALLED AT ALL HARD
CEILING LOCATIONS.
4. ALL PIPING PENETRATIONS SHALL BE SLEEVED. COMPLETELY
GROUT AROUND OUTSIDE OF SLEEVE AND FILL SLEEVE VOID
AROUND PIPE WITH FIBERFRAX FYRE-PUTTY.
5. AT ALL DISSIMILAR METAL CONNECTIONS, PROVIDE AND INSTALL
DIELECTRIC UNIONS IMMEDIATELY TO MINIMIZE USE OF
GALVANIZED PIPE MATERIAL.
6. PLUMBING CONTRACTOR SHALL COORDINATE WITH THE
MECHANICAL CONTRACTOR MOUNTING HEIGHTS OF ALL AIR
HANDLERS TO GUARANTEE POSITIVE DRAINAGE OF ALL
CONDENSATE DRAINS (1/8" PER FT. SLOPE - MINIMUM).
7. MECHANICAL CONTRACTOR TO PROVIDE TO THE PLUMBING
CONTRACTOR THE RECOMMENDED AC MANUFACTURERS' DATA
FOR CONDENSATE TRAPS PER EACH TYPE OF UNIT.
8. DO NOT INSTALL PLUMBING VENTS WITHIN 10'-0" OF ANY
ROOFTOP UNITS OR FRESH AIR UNITS / INTAKES. COORDINATE
WITH MECHANICAL CONTRACTOR.
9. PLUMBING CONTRACTOR TO PROVIDE TRAP PRIMERS/GUARDS TO
ALL FLOOR DRAINS, SHOWER DRAINS, OPEN SITE DRAINS AND
FLOOR SINKS.
10. MOUNT A.D.A. FLUSH CONTROLS TO WIDE SIDE OF STALL.
11. PLUMBING CONTRACTOR TO PROVIDE A CLEAN-OUT FOR EACH
URINAL.
ALL PLUMBING PIPING
TO CONFORM WITH 2012
IFGC AND 2012 IPC.
06-06-2025 City Comments
06-06-2025
06-06-2025
TYPICAL GAS REGULATOR INSTALLATION
GENERATOR REGULATOR INSTALLATION
EXTERIOR CLEANOUT DETAIL
CONDENSATE DRAIN DETAIL
WALL CLEANOUT
EXTERIOR WALL PIPE PENETRATION
PIPE SUPPORT DETAIL
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
5 MED. PRESSURE
GAS LINE SUPPORT ROOF
9 O'CLOCK
UNION
GAS LINE
GAS LINE
UNION
GAS REGULATOR
3 O'CLOCK
1/2" IRON BODY STOP WITH 1/2" PLUG
LOW PRESSURE
CUT-OFF
VALVE
GAS - MANUAL
(TYPICAL)
CUT-OFF
VALVE
GAS - MANUAL
1/2" IRON BODY STOP WITH 1/2" PLUG
GAS COCK AND REGULATOR VENT
TO BE INSTALLED IN 3 O'CLOCK OR
9 O'CLOCK POSITION ONLY.
> 10 PIPE DIAMETERS
MED. PRESSURE
GAS LINE SUPPORT ROOF/FLOOR/GRADE
9 O'CLOCK
UNION
GAS LINE
GAS LINE
UNION
GAS REGULATOR
3 O'CLOCK
1/2" IRON BODY STOP WITH 1/2" PLUG
LOW PRESSURE GAS LINE DIAMETER TWO TIMES REQUIRED LINE SIZE
CUT-OFF
VALVE
GAS - MANUAL
(TYPICAL)
CUT-OFF
VALVE
GAS - MANUAL
1/2" IRON BODY STOP WITH 1/2" PLUG
GAS COCK AND REGULATOR VENT
TO BE INSTALLED IN 3 O'CLOCK OR
9 O'CLOCK POSITION ONLY.
9 O'CLOCK 3 O'CLOCK
10'-0" MINIMUM
GAS LINE
CUT-OFF
VALVE
DRIP LEG
BOILER OR GENERATOR
GENERAL NOTES:
1. OUTLET OF GAS REGULATOR TO BE NO LESS THAN 10'-0" (STRAIGHT RUN) FROM GAS TIE-IN.
2. MAJORITY OF THE MINIMUM 10'-0" OF STRAIGHT RUN TO BE TWICE THE SIZE, IN DIAMETER, AS THE GAS LINE TO TIE-IN.
UNION
GAS LINE
END OF LINE TWO WAY IN-LINE
TWO WAY CLEANOUT FITTINGS NOT ALLOWED
LONG
SWEEP
FITTING
14"X14"X5" PAD
14"X14"X5" PAD
CAST IRON FERRULE WITH COUNTER SUNK
BRASS CLEANOUT PLUG-TYPICAL
GRADE
V A
R
IE
S
FITTING
SWEEP
LONG
14"X14"X5" PAD
FITTING
SWEEP
LONG
NOTE: ALL PADS TO BE CONCRETE WITH CHAMFERED EDGES
14"X14"X5" PAD
ELBOW
SWEEP
LONG
COORDINATE P-TRAP CONSTRUCTION
UNIT MANUFACTURER
AND INSTALLATION WITH H.V.A.C.
DRAW-THROUGH COIL
BLOW-THROUGH COIL
ADAPTER
COIL DRAIN PAN
ADAPTER
1/8"/FT. SLOPE
UNIT MANUFACTURER
AND INSTALLATION WITH H.V.A.C.
COORDINATE P-TRAP CONSTRUCTION
UNION PLUG
REFER TO ROOF PENETRATION
DETAIL FOR CONDENSATE DRAIN
LINE DOWN THROUGH ROOF
P-TRAP
UNION PLUG
UNION
LINE DOWN THROUGH ROOF
DETAIL FOR CONDENSATE DRAIN
REFER TO ROOF PENETRATION
1.75" MIN.
DRAW THROUGH SYSTEMS
DOWNSTREAM SIDE
VENT REQUIRED ON
1/8"/FT. SLOPE
2" MINIMUM
2" MINIMUM
(6" MINIMUM FOR MEDIUM
PRESSURE AIR HANDLER UNITS)
COIL DRAIN PAN
PROVIDE CLEANOUT AT FIRST CONNECTION, AT INCREASE IN PIPE SIZE, EVERY 100'-0", AND EVERY CHANGE IN
DIRECTION, WHETHER SHOWN ON PLAN OR NOT.
NOTES:
2.75" MIN.
4.5" MIN.
(NO-HUB WITH
ACCESS COVER AND FRAME
FINISHED WALL SURFACE
THREADED CLEANOUT PLUG
(BRASS PLUG WITH MACHINE
FLOOR
TEST TEE
WALL CLEANOUT
(PAINT ORANGE)
DO NOT LOCATE
ACCESS COVER) BEHIND STUDS
8" MAX
SCREW REQUIRED)
VENT
SEALED
PER SPECS
PENETRATION
HANGER
HANGER ROD
1'-0"
SADDLE
(SEE SPEC.)
SHEET METAL
PIPE OR
CONDUIT
FILL ANNULAR SPACE WITH
NON-SHRINKING CAULK
THAN PIPE PENETRATING WALL
WALL
PIPE SLEEVE 2 PIPE SIZES LARGER
PIPE INSULATION
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Ty J. Cobb
144952TX
REVIEW ONLY
5/29/2025 10:11:55 AM
PL7.2
PLUMBING DETAILS
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
KS
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
06-02-2025
06-02-2025
06-06-2025
06-06-2025
ONE AND TWO HOUR WALL PENETRATION DETAIL FOR INSULATED PIPE
TWO HOUR WALL PENETRATION FOR INSULATED PIPE
TWO HOUR FLOOR PENETRATION DETAIL FOR P.V.C. PIPE TWO HOUR FLOOR PENETRATION DETAIL FOR P.V.C. PIPE
TWO HOUR FLOOR PENETRATION DETAIL FOR INSULATED PIPE
ONE AND TWO HOUR WALL PENETRATION DETAIL FOR P.V.C. PIPEPIPE ROUTING AT FOOTINGS
IMPERVIOUS BARRIER
CONDENSATE CLEANOUT DETAIL
IN-LINE CONDENSATE CLEANOUT DETAIL
VERTICAL CONDENSATE CLEANOUT DETAIL
GAS TIE-IN TO GAS-FIRED EQUIPMENT
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
BELOW FOOTING.
ROUTE PIPE
FINISHED FLOOR
FOOTING
BOTTOM OF
STRUCTURAL FOOTING
3'-0"
6"
TOPSOIL
IMPERVIOUS BARRIER
OR CALICHE ROCK
PIPE OR
CONDUIT
12"
DITCH DEPTH MINUS
6" FOR TOPSOIL
INSTALL 12" THICK IMPERVIOUS
BARRIER AT BUILDING LINE AND
15'-0" OUT FROM BUILDING ON
ALL LINES WHICH TRAVEL UNDER
BUILDING GRADE BEAM (SEWER,
STORM, WATER, ELECT, ETC).
STEEL SLEEVE
PIPE INSULATION
PIPE
CP 25WB+ CAULK
3M FIRE BARRIER
ASSEMBLY
GYPSUM WALLBOARD
1 OR 2 HOUR
PACKING MATERIAL
BACKER ROD
OF UL 1479 AND ASTM E 814
MUST MEET THE REQUIREMENTS
STEEL PIPE
PIPE INSULATION
CP 25WB+ CAULK
3M FIRE BARRIER
WALLBOARD ASSEMBLY
2 HOUR GYPSUM
OF UL 1479 AND ASTM E 814
MUST MEET THE REQUIREMENTS
PLASTIC PIPE/CONDUIT
SOLID CONCRETE FLOOR
3M FIRE BARRIER
3M FIRE BARRIER
FS-195+ WRAP/STRIP
RC-1 RESTRICTING COLLAR OR PPD
OF UL 1479 AND ASTM E 814
MUST MEET THE REQUIREMENTS
FIRE RATED CONCRETE
FLOOR SLAB
CS-195+
STEEL HOSE CLAMP
3M FIRE BARRIER
RC-1 RESTRICTING
COMPOSITE SHEET
3M FIRE BARRIER
COLLAR.
FS-195+ WRAP/STRIP
3M FIRE BARRIER
P.V.C. PIPE
FLUTED STEEL DECK
OF UL 1479 AND ASTM E 814
MUST MEET THE REQUIREMENTS
PIPE INSULATION
CP 25WB+ CAULK
3M FIRE BARRIER
FIRE RATED
FLOOR SLAB
CONCRETE
3M FIRE BARRIER
FS-195+ WRAP/STRIP
PIPE
STEEL SLEEVE
OF UL 1479 AND ASTM E 814
MUST MEET THE REQUIREMENTS
PIPE/CONDUIT
PLASTIC
3M FIRE BARRIER
RC-1 RESTRICTING
COLLAR OR PPD
3M FIRE BARRIER
GYPSUM WALLBOARD
1 OR 2 HOUR FIRE RATED
FS-195+ WRAP/STRIP
OF UL 1479 AND ASTM E 814
MUST MEET THE REQUIREMENTS
ALL THREAD ROD
AND CLEVIS
HANGER
CLEANOUT COVER
SUPPORT CABLE
CLOSED CELL
INSULATION
CLEANOUT
COVER
FIBERGLASS
INSULATION
AND CONDENSATE
DRAIN
RIGID INSULATION
UNDER CLEVIS
HANGER
ALL THREAD ROD
AND CLEVIS
HANGER
CLEANOUT
COVER
CLOSED CELL
INSULATION
CLEANOUT
COVER
FIBERGLASS
INSULATION
AND CONDENSATE
DRAIN
RIGID INSULATION
UNDER CLEVIS
HANGER
SUPPORT
CABLE
6" M
IN
IM
U M
6" M
IN
IM
U M
ALL THREAD ROD
AND CLEVIS
HANGER
COVER
CLOSED CELL
INSULATION
CLEANOUT
COVER
FIBERGLASS
INSULATION AND
CONDENSATE
DRAIN
RIGID INSULATION
UNDER CLEVIS
HANGER
SUPPORT
CABLE
6" M
IN
IM
U M
ROOF
FLOOR/
3" MINIMUM
EQUIPMENT
GAS FIRED
6" MINIMUM
UNION
GAS PIPING ON
ROOF (VERIFY SIZE)
CAP FOR
DRIP LEG
GAS COCK
3'-0" MAXIMUM
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Ty J. Cobb
144952TX
REVIEW ONLY
5/29/2025 10:11:55 AM
PL7.3
PLUMBING DETAILS
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
KS
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
06-02-2025
06-02-2025
06-06-2025
06-06-2025
DESCRIPTIONMARK
PLUMBING FIXTURE SCHEDULE
SUPPLYMANUFACTURER & NO. ELEC. DATA ACCESSORIES
TRAP PRIMER WITH ACCESS DOOR
N.T.S.
REMARKSWASTE
2"
2"
3"
4"
VENT
1-1/4"
2"
1-1/2"
2"
1-1/4"
3"
2"
3"
1-1/2"
1-1/2"
H.W.
3"
3/4"
C.W.
1"
1-1/4"
3"
1-1/2"
1-1/4"
3"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
TRAP SIZE
SIPHON JET TYPE W/MAX. 0.5 GAL. FLUSH
FLUSH VALVE WITH MAX. 1.28 GALLON FLUSH
ALL FLOOR DRAINS TO HAVE TRAP PRIMERS
WALL HUNG OR FLOOR TYPE
MINIMUM FIXTURE CONNECTION SCHEDULE
FLOOR DRAIN
ELEC. WATER COOLER
JANITOR SINK
COUNTER SINK
WATER CLOSET
NAME OF FIXTURE
LAVATORY
URINAL
NOTE: ALL THE ABOVE FIXTURES ARE NOT NECESSARILY USED.
B1
WALL MOUNT (ADULT)
LAVATORY - A.D.A.
AMERICAN STANDARD
TEMP/COLD DELTA NICOLI 25749 LF-SS STAINLESS FAUCET (4" CENTERS), 0.5 GPM, P-TRAP, GRID DRAIN, SUPPLIES W/
STOPS, WATTS WCA-411 CARRIER, TRUEBRO LAV-GUARD, BRADLEY S59-4000A TMV
C1
WALL MOUNT (ADULT)
URINAL
ZURN
Z5738
SLOAN 186-0.5 FLUSH VALVE (3/4" TOP SPUD), 0.5 GPF, WADE 402 CARRIER
D1
FLOOR DRAIN WADE
1103G6
6" TOP SIZE, 3" DISCHARGE, TRAP PRIMER TAP
A1
FLOOR MOUNT
WATER CLOSET - A.D.A.
KOHLER
K-96057-0
SLOAN 111-1.28 FLUSH VALVE (1 1/2" TOP SPUD), 1.28 GPF,
WHITE OPEN-FRONT SEAT, BOLT CAPS (2), REFER TO ARCH PLANS FOR MOUNTING HEIGHT
G1
MOP SINK MUSTEE
63M
HOT/COLD T-10-VB FAUCET, T-35 HOSE AND WALL BRACKET, T-40 MOP HANGER,
STAINLESS STEEL BACKSPLASH & SIDESPLASH
A2
FLOOR MOUNT
WATER CLOSET
KOHLER
K-96057-0
SLOAN 3780046 FLUSH VALVE (1 1/2" TOP SPUD), 1.28 GPF,
WHITE OPEN-FRONT SEAT, BOLT CAPS (2)
B2
COUNTERTOP (ADULT)
LAVATORY - A.D.A.
AMERICAN STANDARD
AQUALYN
TEMP/COLD DELTA NICOLI 25749 LF-SS STAINLESS FAUCET (6" CENTERS), 1.5 GPM, P-TRAP, GRID DRAIN, SUPPLIES W/
STOPS, TRUEBRO LAV-GUARD, BRADLEY S59-4000A TMV
J1
CIRCULATING
PUMP
BELL & GOSSETT
ECOCIRC 20-18
120 V.
1/11 H.P.
STAINLESS STEEL BODY, FLANGED,
PROVIDE WITH JOHNSON CONTROLS A19 AQUASTAT
G2
BREAKROOM
SINK
ELKAY
LRAD 25225
TEMP/COLD 9" DEEP BASIN, DELTA MONROVIA 9191-AR-PR-DST LUMICOAT ARCTIC STAINLESS FAUCET, P-TRAP, SUPPLIES W/ STOPS, DUO-STRAINER,TMV EQUAL TO LEONARD 270 LF
M1
ICE MACHINE UTILITY BOX
AND RPZ
GUY GRAY
MIB1HAAB
MOUNT CONTROLS AT A.D.A. HEIGHT, PROVIDE WATTS LF-009 RPZ ON SUPPLY LINE
H1
EXTERIOR
HOSE BIBB
WOODFORD
B67
COLD VACUUM BREAKER, RECESSED IN LOCK BOX, VERIFY WALL THICKNESS, FREEZE RESISTANT, TAMPER
RESISTANT
E1
IN WALL BOTTLE
FILLING STATION
ELKAY
EZH20
120 V. ARCHITECT TO SELECT FINISH, NO CFC REFRIGERANTS, VANDAL RESISTANT,
WADE 403-BFS CARRIER, REFER TO ARCHITECTURAL PLANS FOR MOUNTING HEIGHT
F1
40 GALLON ELECTRIC
WATER HEATER
LOCHINVAR
LDS-40PK
240 V., 3 PH.
4500 W.
TEMPERATURE AND PRESSURE RELIEF VALVE, DUAL ELEMENT, WATTS EXPANSION TANK,
NON-SIMULTANEOUS OPERATION, LOW BOY HEIGHT
R1
SINK DISPOSER IN-SINK-ERATOR
BADGER 5
120 V., 1 PH.
1/2 HP
TRAP PRIMER
CHASE
WALL
ACCESS DOORWATER LINE(S) DOWN TO BELOW
SLAB WITH PROTECTIVE LINER
UNIONSHUTOFF
VALVE
DISTRIBUTION
SYSTEM
(AS REQUIRED)
TAP INTO TOP OF COLD WATER LINE
OF 1 1/2" OR SMALLER IN RESTROOM
CHASE. WATER LINE MUST BE
SUPPLYING AT LEAST 1 WATER
CLOSET DOWNSTREAM.
DO NOT INSTALL TRAP PRIMERS UNTIL AFTER
THE DOMESTIC WATER PIPING HYDROSTATIC
PRESSURE TEST IS SUCCESSFULLY
COMPLETED.
ACCESS DOORS TO BE INSTALLED TO ALLOW DOOR
TO FULLY OPEN. ANY ACCESS DOOR INSTALLED
WHICH CANNOT OPEN TO PROVIDE ADEQUATE
ACCESS TO TRAP PRIMER, DISTRIBUTION UNIT, ETC.
WILL BE REMOVED, WALL PATCHED TO MATCH
ADJACENT WALL, AND RELOCATED.
TRAP PRIMER TO BE
LOCATED WITHIN 4"
OF ACCESS DOOR.
*PLUMBING CONTRACTOR SHALL PROVIDE AN OFFSET VACUUM BREAKER TUBE WHERE THE HEIGHT OF THE GRAB BAR CREATES A CONFLICT WITH THE FLUSH VALVE.
1 1/4" CW
2 1/2" CW
2 1/2" CW
1 1/4" CW
3/4" HW
1/2" CW
1/2" CW
3/4" HW
3/4" HW
2 1/2" CW
2 1/2" CW
1 1/2" SS
4" SS
4" SS4" SS
4" SS
4" SS
4" SS
3" SS
1/2" CW
1/2" CW
2" V 2" V
1 1/4" V
2" V2" V
2" V
2" V.T.R
1/2" CW
3/4" HW
3/4" HW
3/4" HW
1/2" CW
1 1/2" SS
1 1/2" SS
4" SS
3" SS
4" SS
3" SS
4" SS
4" SS
4" SS
4" SS
4" SS
1" CW
1 1/4" CW
1" CW
2" CW
1 1/4" CW 1 1/4" CW
1 1/4" CW
1 1/4" CW
1 1/4" CW
2" CW 2" CW
2" CW
2" CW
3/4" HW
3/4" HW
1/2" CW
1/2" CW
3/4" HW
1/2" CW
4" SS
2" SS
1 1/2" SS
3" SS
4" SS
2" CW
4" SS
4" SS
4" SS
4" SS
4" SS
4" SS
3" SS
3" SS
4" SS
4" SS
4" SS
4" SS
3" SS
3/4" HW
3/4" HW
3/4" HW
1 1/4" CW
2" V 1 1/4" V
1 1/4" V
2" V
2" V
2" V
2" V.T.R 3" V.T.R
3" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
2" V
3" V
2" V
1 1/4" V
1 1/4" V 2" V
1 1/4" V
3/4" HW
3/4" CW
3/4" HW
4" SS3" SS
4" SS
4" SS
1" COND
2" V
1/2" CW
1/2" CW
1" COND
2" V
3/4" CW
3/4" HW
3/4" HW
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Ty J. Cobb
144952TX
REVIEW ONLY
6/6/2025 11:06:15 AM
PL8.1
PLUMBING
SCHEDULE AND
RISERS
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
KS
06-06-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
1 RISER 1
2 RISER 2 3 RISER 3
ALL PLUMBING PIPING
TO CONFORM WITH 2012
IFGC AND 2012 IPC.
06-06-2025 City Comments
06-06-2025
06-06-2025
| Sheets |
| PD1.1 - PLUMBING DEMOLITION FLOOR PLAN |
| PL1.1 - PLUMBING FLOOR PLAN |
| PL6.1 - PLUMBING ROOF PLAN |
| PL7.1 - PLUMBING SYMBOLS, DETAILS & GENERAL NOTES |
| PL7.2 - PLUMBING DETAILS |
| PL7.3 - PLUMBING DETAILS |
| PL8.1 - PLUMBING SCHEDULE AND RISERS |
| PS1.1 - PLUMBING SITE PLAN |
File details come from the government source that posted it. Updated .