8-Exhibit H PLUMBING - IFP - 5-1-2025 REV 1 (1).pdf

PDF 3 MB Posted

Attached to
General Contractor Services for Precinct 2 Justice Facility in Gregg County, Texas
Solicitation number
2025-21
Issued by
Gregg County, Texas

About this file

These are plumbing construction documents for the Gregg County Precinct 2 facility located at 800 Gilmer Road in Longview, Texas, prepared by EMA Engineering & Consulting, Inc. The documents are 100% construction documents dated May 29, 2025, covering plumbing demolition, site plans, floor plans, roof plans, details, and fixture schedules for a county government building renovation project. The plans specify comprehensive plumbing system modifications including new sanitary sewer lines, domestic water systems, gas lines, condensate drains, and fixtures, with all plumbing work to conform to 2012 International Fuel Gas Code (IFGC) and 2012 International Plumbing Code (IPC).

The project includes installing various plumbing fixtures such as wall-mounted lavatories, water closets, urinals, a mop sink, breakroom sink, exterior hose bibb, bottle filling station, and a 40-gallon electric water heater. The documents outline detailed specifications for gas regulators, pipe supports, wall and floor penetrations, and require careful coordination with mechanical and electrical contractors. Key technical considerations include maintaining proper slope for condensate drains, installing trap primers, coordinating utility connections, and ensuring compliance with accessibility standards. The design emphasizes precise installation requirements, including specific mounting heights, valve placements, and fire-rated penetration details.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P35

P35

P35

P35

P35

P35

P35

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Ty J. Cobb

144952TX

REVIEW ONLY

5/29/2025 10:11:40 AM

PD1.1

PLUMBING

DEMOLITION FLOOR

PLAN

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

KS

05-29-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

3/16" = 1'-0"

1 PLUMBING DEMOLITION FLOOR PLAN

PLUMBING DEMOLITION GENERAL NOTES

1. CONTRACTOR TO VISIT SITE AND BE FAMILIAR WITH BUILDING

MECHANICAL AND ELECTRICAL LAYOUTS.

2. ALL MATERIAL, EQUIPMENT, DUCTS, PIPE, ETC. TO BE REMOVED

SHALL BE DISPOSED OF OFF SITE IN A LEGAL AND LAWFUL

MANNER.

3. CAP ANY UNUSED PIPE AT FLOOR, WALL, OR CEILING. REMOVE

MATERIAL NOT BEING REUSED.

4. IF ASBESTOS IS FOUND, CONTACT OWNER IMMEDIATELY. DO NOT

WORK IN ANY AREA SUSPECTED TO CONTAIN ASBESTOS.

5. ALL EXISTING EQUIPMENT SHOWN IN APPROXIMATE LOCATION.

ALL EXISTING CONCEALED PIPING SHOWN IS BASED ON THE MOST

RECENT EXISTING M.E.P. AND CIVIL DRAWINGS AVAILABLE. FIELD

VERIFY.

6. TAKE CARE NOT TO DESTROY INSULATION VALUE TO ANY WATER

PIPING BEING REUSED. REPAIR AS NECESSARY.

7. CONTRACTOR TO VERIFY LOCATION OF ALL UTILITIES AND

RELOCATE AS REQUIRED BY NEW CONSTRUCTION.

PLUMBING DEMOLITION PLAN NOTES

P35 REMOVE EXISTING PLUMBING FIXTURE, FAUCET, SUPPLIES,

CARRIER, FLOOR DRAIN, ETC. CAP SERVICE LINES IN A

CONCEALED LOCATION.

06-02-2025

06-02-2025

06-06-2025

06-06-2025

05-01-2025

APPROXIMATE LOCATION

FOR FUTURE GENERATOR

NEW GAS METER

APPROXIMATE LOCATION

PS3

PS1

PS4

PS2

1" G

1" G

1 1/4" G

3" G

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Ty J. Cobb

144952TX

REVIEW ONLY

5/29/2025 10:11:42 AM

PS1.1

PLUMBING SITE PLAN

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

KS

05-29-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

PLUMBING SITE GENERAL NOTES

1. CONTRACTOR AND SUBCONTRACTORS SHALL VERIFY LOCATION,

CONDUCT TEST AND INSPECTIONS, COORDINATE WITH UTILITIES,

OWNER'S REPRESENTATIVES, AND CHECK FOR ALL UNDERGROUND

UTILITIES AND LINES BEFORE DITCHING TAKES PLACE.

CONTRACTOR AND SUBCONTRACTORS PERFORMING THESE

DUTIES SHALL BE RESPONSIBLE FOR ANY REPAIRS OF CUT OR

DAMAGED LINES AND UTILITIES. THERE ARE LINES AND UTILITIES

NOT SHOWN ON PLANS.

2. ALL INSTALLATIONS SHALL BE PER THE AUTHORITY OF HAVING

JURISDICTION. THE CONTRACTOR IS RESPONSIBLE FOR

COORDINATING WITH THE CITY FOR ALL OF THE NECESSARY TAPS

REQUIRED, MANHOLES, WATER METERS, BACK-FLOW

PREVENTERS, DETECTOR CHECKS, ETC. AS REQUIRED.

3. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE

WITH THE AUTHORITY HAVING JURISDICTION ANY REQUIRED

STREET BORINGS (WET OR DRY) FOR NEW UTILITY TIE-INS.

4. IT IS THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR TO

COORDINATE ALL UTILITY CONNECTIONS WITH UTILITY

CONTRACTOR PRIOR TO CONSTRUCTION.

PLUMBING SITE PLAN NOTES

PS1 2-1/2" DOMESTIC WATER STUB-OUT. EXTEND TO CONNECTION.

REFER TO CIVIL PLANS FOR WATER METER AND BACK-FLOW

PREVENTER LOCATIONS.

PS2 SAW-CUT EXISTING SLAB FOR INSTALLATION OF NEW GAS

PIPING. PATCH TO MATCH EXISTING AS NECESSARY.

PS3 4" SANITARY SEWER STUB-OUT 46" B.F.F. EXTEND TO

CONNECTION. REFER TO CIVIL PLANS FOR CONTINUATION.

PS4 1-1/4" MEDIUM PRESSURE GAS LINE SLEEVED UNDER CONCRETE.

1" = 20'-0"

1 PLUMBING SITE PLAN

GAS REGULATOR SCHEDULE

MARK MANUFACTURER C.F.H. IN OUT

1 ITRON SERIES B 3076 1 1/4" 3"

2 ITRON SERIES B 175 1" 1 1/4"

GAS LOAD BREAKDOWN

PLUMBING CONTRACTOR TO COORDINATE

WITH GAS REGULATOR MANUFACTURER ALL

ORIFICE AND SPRING SIZES, AS REQUIRED, T...

TYPE C.F.H.

EMERGENCY

GENERATOR

HVAC UNITS 175

TOTAL CONNECTED GAS

LOAD

SAW-CUT EXISTING SLAB FOR

INSTALLATION OF NEW GAS

PIPING. PATCH TO MATCH

EXISTING AS NECESSARY.

800 GILMER RD PRECINCT 2

06-02-2025

06-02-2025

06-06-2025

06-06-2025

B2

A1 C1

D1

E1

G2M1

G1

F1 J1

A1

A1 C1

D1

B2

A2

A2

A2

B2

B2

D1

D1

D1

A1

B1

MICHELLE

DRIVE THRU

TAX CLERKS

SERVICE AREA

ELEC

ENTRY

WAITING

STRG

SUPER OFF.

WEB DEAL

STRG

IT

CONFERENCE

WORKROOM

BREAKROOM

STRG

JAN

MENS

BREAKROOM

TIM

COURT ROOM

WMNS

UNISEX

SUPER OFF.

OPEN OFFICE

STRG

HALL

JP WAITING

RAY

RR

STRG

STRG

STRG

ROGER

REFER TO SHEET PS1.1

FOR CONTINUATION

REFER TO SHEET PS1.1

FOR CONTINUATION

P8

TIE-IN TO EXISTING SANITARY SEWER.

(FIELD VERIFY EXACT LOCATION)

P3

P3

P3

P3

P3

1/2" CW

1/2" HW

2" SS

2 1/2" CW 3/4" HW 3/4" HW

3/4" HW

3/4" HW

2 1/2" CW

2 1/2" CW

PL8.1

PL8.1

PL8.1

4" SS

4" SS

3/4" HW

2 1/2" CW

3/4" HW

3/4" HW

3/4" CW

3/4" HW

4" SS

P5

P4

P4

P4

P4

P4

P5

P4

P4

P5

P4

P5

P4

P4

P4

H1

H1

H1

P54

P53

P1

1/2" CW

1/2" CW

1/2" CW

P16

P17

P30

P4

P32

P20

2 1/2" CW

4" SS

P2

1/2" CW 4" SS

4" SS

4" SS

REFER TO SHEET PS1.1

FOR CONTINUATION

P4

P10

P10

R1 P6

1" COND

1" COND

1" COND

1" COND

1" COND

1" COND

1" COND

1" COND1" COND

1" COND

1" COND

P19

1" COND

P19

1" COND

NO PIPING ABOVE

IT ROOM

NO PIPING ABOVE

ELECTRICAL ROOM

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Ty J. Cobb

144952TX

REVIEW ONLY

5/29/2025 10:11:44 AM

PL1.1

PLUMBING FLOOR

PLAN

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

KS

05-29-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

ALL DOMESTIC HOT WATER SHALL MEET 2015 IECC HOT WATER

REQUIREMENTS.

AT LOCATIONS OF HOT WATER LOOP PIPING GOING DOWN IN

WALL AND BACK UP, PROVIDE 1/2" HOT WATER TO CONNECT

TO EACH HAND SINK/LAVATORY. HOT WATER LOOP PIPING

SHALL BE WITHIN 2'-0" OF THE CONNECTION TO THE FIXTURE,

PER 2015 IECC. PROVIDE 3/4" TO CONNECT TO EACH LAVATORY

STATION.

PRIOR TO ANY SAWCUTTING, VERIFY THAT SLAB IS NOT A 2-

WAY SLAB. IF SLAB IS 2-WAY, THEN CONTACT STRUCTURAL

ENGINEER FOR FURTHER GUIDANCE BEFORE ANY

SAWCUTTING.

PLUMBING CONTRACTOR IS RESPONSIBLE FOR REPLACING

ANY EXISTING CEILING TILES DAMAGED DURING INSTALLATION

OF NEW PLUMBING PIPING ABOVE EXISTING CEILINGS.

PLUMBING GENERAL NOTES

1. SEE SHEET PL7.1 FOR GENERAL NOTES APPLICABLE TO THE

ENTIRE DRAWING SET.

PLUMBING PLAN NOTES

P1 TWO-WAY CLEANOUT

P2 ONE-WAY CLEANOUT

P3 WALL CLEANOUT

P4 DOWN IN WALL/CHASE

P5 HOT WATER LOOP DOWN IN WALL/CHASE TO WITHIN

2'-0" OF LAVATORY PER IECC, THEN BACK UP TO

ABOVE CEILING.

P6 CONTRACTOR TO CONNECT DISHWASHER TO SINK

P8 UP FROM BELOW SLAB

P10 3" VENT UP TO ROOF.

P16 CONDENSATE DRAIN DOWN IN WALL, TIE-IN TO P-TRAP

AT SINK WITH TAILPIECE

P17 CONDENSATE DRAIN DOWN TO MOP SINK/FLOOR

SINK/HUB DRAIN

P19 CONDENSATE DRAIN FROM WALL UNIT. LINE

PRESSURIZED FROM INTERNAL CONDENSATE PUMP.

(ROUTE SEPARATELY FROM GRAVITY SYSTEMS OR

TIE INTO TOP OF GRAVITY PIPE)

P20 DOWN TO CONNECTION

P30 BLANK

P32 HOT WATER RETURN

P53 DOWN TO LOWER LEVEL CEILING SPACE

P54 UP TO HIGHER LEVEL CEILING SPACE

True

PROJECT

NORTH

3/16" = 1'-0"

1 PLUMBING FLOOR PLAN

SAW-CUT EXISTING SLAB FOR

INSTALLATION OF NEW SANITARY

SEWER PIPING. PATCH TO MATCH

EXISTING AS NECESSARY.

06-02-2025

06-02-2025

06-06-2025

06-06-2025

12' - 5"

P14

3" V.T.R.

P30

P22

P31

P50

P50

1" COND

1" COND

1" COND

1" COND

1" COND

1" COND

1" COND

P14

P14

P14

P14

P14

P14

1" G 1" G

1" G

1" G

1" COND

1" COND

1 1/4" G

1" G

1 1/4" G1 1/4" G

1 1/4" G

1 1/4" G

1" G

1" COND

1" COND

1" COND

1" COND

1" COND

1" COND

1" G

1 1/4" G

1" G

1 1/4" G

1 1/4" G

1" G

2" V.T.R.

2" V.T.R.

2" V.T.R.

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Ty J. Cobb

144952TX

REVIEW ONLY

6/6/2025 11:06:13 AM

PL6.1

PLUMBING ROOF

PLAN

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

KS

06-06-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

PLUMBING ROOF GENERAL NOTES

1. FURNISH AND INSTALL CUTOFF VALVES UPSTREAM OF EACH GAS

REGULATOR. FURNISH AND INSTALL CUTOFF VALVES AT EACH

EQUIPMENT TIE-IN AND VERTICAL RISERS.

2. REFER TO HOODED ROOF PENETRATION DETAIL FOR PROPER

ROOF PENETRATION.

3. ALL CUTOFF VALVES AND REGULATOR VENTS IN HORIZONTAL

POSITION SHALL BE INSTALLED AT 3 OR 9 O'CLOCK POSITION.

4. REFER TO DETAILS FOR GAS REGULATOR DETAIL.

5. THIS DESIGN UTILIZES A CONVERSION FACTOR OF 1000 B.T.U.H.

PER C.F.H.

6. MAINTAIN A MINIMUM OF 10'-0" FROM GAS REGULATORS AND ALL

OUTDOOR AIR INTAKES.

ALL CONDENSATE PIPE CONNECTIONS SHALL BE 1" NOMINAL PIPE SIZE.

CONNECT TO EACH ROOFTOP UNIT WITH P-TRAP.

PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL GAS COCK VALVES

PRIOR TO CONNECTION TO EACH UNIT.

ALL EQUIPMENT GAS PIPE CONNECTIONS SHALL BE 1" NOMINAL PIPE SIZE

UNLESS OTHERWISE NOTED.

ROOF PIPE SUPPORTS SHALL BE FURNISHED AND INSTALLED AT

REQUIRED SPACING.

PLUMBING GENERAL NOTES

1. SEE SHEET PL7.1 FOR GENERAL NOTES APPLICABLE TO THE

ENTIRE DRAWING SET.

PLUMBING PLAN NOTES

P14 CONDENSATE TIE-IN TO UNIT/AIR HANDLER WITH P-TRAP

P22 GAS UP AND OVER

P30 BLANK

P31 CONDENSATE UP AND OVER

P50 DOWN TO LEVEL BELOW

1/8" = 1'-0"

1 PLUMBING ROOF PLAN

GAS REGULATOR SCHEDULE

MARK MANUFACTURER C.F.H. IN OUT

1 ITRON SERIES B 3076 1 1/4" 3"

2 ITRON SERIES B 175 1" 1 1/4"

GAS LOAD BREAKDOWN

PLUMBING CONTRACTOR TO COORDINATE

WITH GAS REGULATOR MANUFACTURER ALL

ORIFICE AND SPRING SIZES, AS REQUIRED, T...

TYPE C.F.H.

EMERGENCY

GENERATOR

HVAC UNITS 175

TOTAL CONNECTED GAS

LOAD

ALL PLUMBING PIPING

TO CONFORM WITH 2012

IFGC AND 2012 IPC.

06-06-2025 City Comments

06-06-2025

06-06-2025

2.

1.

NOTES:

3.

ELECTRIC WATER HEATER SUSPENDED WITH CIRCULATOR

TEMPERED & COLD SUPPLY LAVATORY DETAIL

ROOF PIPING SUPPORT

N.T.S.

N.T.S. (PER IECC 2015 C404)

N.T.S.

PIPING

(COLD) CHROME

PLATED TUBING SUPPLY

(COLD)

ANGLE STOP

P-TRAP

8"

8"

(HOT)

ANGLE

STOP

(HOT) CHROME PLATED

TUBING SUPPLY

(TEMPERED/COLD) lAVATORY/FAUCET

FINISHED FLOOR

(MAX.18")

(TEMPERED) STAINLESS

STEEL BRAIDED SUPPLY

H

C

ROUTE BEHIND BASIN

BOWL TO HIDE

THERMOSTATIC

MIXING VALVE

RUBBER BLOCK

SPACER

WALL

BRAIDED SUPPLY

THERMOSTATIC MIXING VALVE WITH BRACKET

WALL SCREW

AND ANCHOR

THERMOSTATIC MIXING VALVE MUST HAVE BRACKET FOR MOUNTING TO WALL.

NOTES:

PROVIDE RUBBER SPACER BETWEEN WALL AND TMV.

WALL ANCHOR SYSTEM MUST BE USED.

STAINLESS STEEL SUPPLY LINES MUST BE KEPT TO MINIMUM LENGTH.

(MAX.12")

(COLD) STAINLESS

STEEL BRAIDED SUPPLY

LONG SWEEPING

ELBOW

RETURN

WATER HEATER

(W/ DISCONNECT)

2" DEEP ROUND GALVANIZED

STEEL DRAIN PAN

ROUTE TEMPERATURE AND

PRESSURE RELIEF DRAIN TO

FLOOR DRAIN/ FLOOR SINK OR

MOP SINK.

TEMPERATURE AND PRESSURE

RELIEF VALVE. DO NOT REDUCE

VALVE / PIPE SIZE.

PROVIDE DI-ELECTRIC CONNECTIONS AT

ALL WATER HEATER CONNECTIONS

UNION

(TYPICAL)

HOT WATER

CHECK VALVE

DRAIN DOWN

IF PIPING IS RUN IN WALLS, THEN STUB-OUT

FROM WALL WITH CHROME ESCUTCHEON.

PIPING INSULATION TO COVER ALL UNIONS,

VALVE BONNETS, AND FITTINGS. MITER ALL

TERMINATION POINTS OF INSULATION. GLUE

AND MASTIC ALL INSULATION JOINTS. ALL

A.S.M.E. WATER HEATERS SHALL BE INSTALLED

WITH A.S.M.E. EXPANSION TANKS.

UNION

HOT WATER SUPPLY

THERMOMETER

THERMOMETER WELL

ROUTE DRAIN LINE TO

FLOOR DRAIN/ FLOOR

SINK OR MOP SINK

CHECK VALVECOLD WATER SUPPLY

STRAP TO WALL OR

SUSPEND FROM ABOVE

EXPANSION TANK

[A.S.M.E. AS

REQUIRED BY LOCAL

CODES]

UNION

FULL PORT

QUARTER TURN

BALL VALVE

HEAT

TRAP

HEAT

TRAP

DOUBLE NUT

UNI-STRUT HARNESS

1/2" ALL THREAD

DOUBLE NUTJOIST

ANGLE SUPPORT BOLTED

TO TOP CHORD OF JOIST

(SIZE BASED ON SPAN AND

WATER HEATER SIZE)

A Q

AQUASTAT '_m at chpr op '_m at chpr op

THE CIRCULATION PUMP WITH INTEGRAL PRESSURE

SENSOR AND AQUASTAT TO BE PROVIDED UNDER J1 DESIGNATION

IN THE PLUMBING SCHEDULE

CIRCULATION

PUMP WITH

INTEGRAL

PRESSURE

SENSOR

PRESSURE SENSOR ON

PUMP AND AQUASTAT TO BE

CONNECTED TO PUMP IN

PARALLEL.

PIPE SUPPORT (ADJUSTABLE)

1/2" TRAFBLOC - SCRAPE ROOF

AND ATTACH WITH MASTIC

ALL PIPE SUPPORTS TO BE SELECTED BASED

ON THE MANUFACTURERS REQUIREMENTS

FOR VARIES PIPE SIZES AND FOR SYSTEM

TYPE THE PIPE IS SERVING

NOTE: "E-(ABBRIVATION)" = EXISTING PIPING

NOTE: NOT ALL SYMBOLS ARE USED

PLUMBING SYMBOLS

ACID LINEA

COMPRESSED AIR LINECA

CONDENSATE LINECOND

CRAWLSPACE DRAIN LINECRAWL

DOMESTIC COLD WATER LINECW

DOMESTIC HOT WATER LINEHW

DOMESTIC FILTERED WATER LINEFW

FIRE PROTECTION LINEFP

FIRE PROTECTION DRY LINEFP-D

FIRE PROTECTION OTHER LINEFP-O

FIRE PROTECTION PRE-ACTION LINEFP-PA

GAS LINEG

GREASE LINEGL

PUMP DISCHARGE LINESP

ROOF DRAIN - OVERFLOW LINEORD

ROOF DRAIN - PRIMARY LINERD

SAND/OIL WASTE LINES/O

SOLIDS WASTE LINESW

SANITARY SEWER LINESS

STORM DRAINAGE LINESD

SUB-SOIL DRAIN LINESSD

VENT LINEV

SPRINKLER LINEF

INDICATES SAWCUT SLAB AND

PATCH TO MATCH AFTERWARDS

V.T.R. VENT THROUGH ROOF

GAS COCK (VALVE)

WATER METER

PLUMBING RISER

P

FLOOR SINK/O.S.D.

GAS METER

DRAIN

CAP

HOSE BIBB

CUT-OFF VALVE

PRIMARY/OVERFLOW ROOF DRAIN

CUT-OFF VALVE

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Ty J. Cobb

144952TX

REVIEW ONLY

6/6/2025 11:06:13 AM

PL7.1

PLUMBING SYMBOLS,

DETAILS & GENERAL

NOTES

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

KS

06-06-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

PLUMBING GENERAL NOTES

1. PLUMBING CONTRACTOR SHALL REFER TO ARCHITECTURAL

PLANS FOR A.D.A. PLUMBING FIXTURE AND STANDARD MOUNTING

HEIGHTS.

2. PLUMBING CONTRACTOR TO COORDINATE ALL PIPING ROUTING

ABOVE WITH MECHANICAL AND ELECTRICAL CONTRACTORS

BEFORE INSTALLING.

3. ALL VALVES SHALL BE INSTALLED NO HIGHER THAN 2'-0" ABOVE

THE CEILING. ACCESS DOORS TO BE INSTALLED AT ALL HARD

CEILING LOCATIONS.

4. ALL PIPING PENETRATIONS SHALL BE SLEEVED. COMPLETELY

GROUT AROUND OUTSIDE OF SLEEVE AND FILL SLEEVE VOID

AROUND PIPE WITH FIBERFRAX FYRE-PUTTY.

5. AT ALL DISSIMILAR METAL CONNECTIONS, PROVIDE AND INSTALL

DIELECTRIC UNIONS IMMEDIATELY TO MINIMIZE USE OF

GALVANIZED PIPE MATERIAL.

6. PLUMBING CONTRACTOR SHALL COORDINATE WITH THE

MECHANICAL CONTRACTOR MOUNTING HEIGHTS OF ALL AIR

HANDLERS TO GUARANTEE POSITIVE DRAINAGE OF ALL

CONDENSATE DRAINS (1/8" PER FT. SLOPE - MINIMUM).

7. MECHANICAL CONTRACTOR TO PROVIDE TO THE PLUMBING

CONTRACTOR THE RECOMMENDED AC MANUFACTURERS' DATA

FOR CONDENSATE TRAPS PER EACH TYPE OF UNIT.

8. DO NOT INSTALL PLUMBING VENTS WITHIN 10'-0" OF ANY

ROOFTOP UNITS OR FRESH AIR UNITS / INTAKES. COORDINATE

WITH MECHANICAL CONTRACTOR.

9. PLUMBING CONTRACTOR TO PROVIDE TRAP PRIMERS/GUARDS TO

ALL FLOOR DRAINS, SHOWER DRAINS, OPEN SITE DRAINS AND

FLOOR SINKS.

10. MOUNT A.D.A. FLUSH CONTROLS TO WIDE SIDE OF STALL.

11. PLUMBING CONTRACTOR TO PROVIDE A CLEAN-OUT FOR EACH

URINAL.

ALL PLUMBING PIPING

TO CONFORM WITH 2012

IFGC AND 2012 IPC.

06-06-2025 City Comments

06-06-2025

06-06-2025

TYPICAL GAS REGULATOR INSTALLATION

GENERATOR REGULATOR INSTALLATION

EXTERIOR CLEANOUT DETAIL

CONDENSATE DRAIN DETAIL

WALL CLEANOUT

EXTERIOR WALL PIPE PENETRATION

PIPE SUPPORT DETAIL

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

5 MED. PRESSURE

GAS LINE SUPPORT ROOF

9 O'CLOCK

UNION

GAS LINE

GAS LINE

UNION

GAS REGULATOR

3 O'CLOCK

1/2" IRON BODY STOP WITH 1/2" PLUG

LOW PRESSURE

CUT-OFF

VALVE

GAS - MANUAL

(TYPICAL)

CUT-OFF

VALVE

GAS - MANUAL

1/2" IRON BODY STOP WITH 1/2" PLUG

GAS COCK AND REGULATOR VENT

TO BE INSTALLED IN 3 O'CLOCK OR

9 O'CLOCK POSITION ONLY.

> 10 PIPE DIAMETERS

MED. PRESSURE

GAS LINE SUPPORT ROOF/FLOOR/GRADE

9 O'CLOCK

UNION

GAS LINE

GAS LINE

UNION

GAS REGULATOR

3 O'CLOCK

1/2" IRON BODY STOP WITH 1/2" PLUG

LOW PRESSURE GAS LINE DIAMETER TWO TIMES REQUIRED LINE SIZE

CUT-OFF

VALVE

GAS - MANUAL

(TYPICAL)

CUT-OFF

VALVE

GAS - MANUAL

1/2" IRON BODY STOP WITH 1/2" PLUG

GAS COCK AND REGULATOR VENT

TO BE INSTALLED IN 3 O'CLOCK OR

9 O'CLOCK POSITION ONLY.

9 O'CLOCK 3 O'CLOCK

10'-0" MINIMUM

GAS LINE

CUT-OFF

VALVE

DRIP LEG

BOILER OR GENERATOR

GENERAL NOTES:

1. OUTLET OF GAS REGULATOR TO BE NO LESS THAN 10'-0" (STRAIGHT RUN) FROM GAS TIE-IN.

2. MAJORITY OF THE MINIMUM 10'-0" OF STRAIGHT RUN TO BE TWICE THE SIZE, IN DIAMETER, AS THE GAS LINE TO TIE-IN.

UNION

GAS LINE

END OF LINE TWO WAY IN-LINE

TWO WAY CLEANOUT FITTINGS NOT ALLOWED

LONG

SWEEP

FITTING

14"X14"X5" PAD

14"X14"X5" PAD

CAST IRON FERRULE WITH COUNTER SUNK

BRASS CLEANOUT PLUG-TYPICAL

GRADE

V A

R

IE

S

FITTING

SWEEP

LONG

14"X14"X5" PAD

FITTING

SWEEP

LONG

NOTE: ALL PADS TO BE CONCRETE WITH CHAMFERED EDGES

14"X14"X5" PAD

ELBOW

SWEEP

LONG

COORDINATE P-TRAP CONSTRUCTION

UNIT MANUFACTURER

AND INSTALLATION WITH H.V.A.C.

DRAW-THROUGH COIL

BLOW-THROUGH COIL

ADAPTER

COIL DRAIN PAN

ADAPTER

1/8"/FT. SLOPE

UNIT MANUFACTURER

AND INSTALLATION WITH H.V.A.C.

COORDINATE P-TRAP CONSTRUCTION

UNION PLUG

REFER TO ROOF PENETRATION

DETAIL FOR CONDENSATE DRAIN

LINE DOWN THROUGH ROOF

P-TRAP

UNION PLUG

UNION

LINE DOWN THROUGH ROOF

DETAIL FOR CONDENSATE DRAIN

REFER TO ROOF PENETRATION

1.75" MIN.

DRAW THROUGH SYSTEMS

DOWNSTREAM SIDE

VENT REQUIRED ON

1/8"/FT. SLOPE

2" MINIMUM

2" MINIMUM

(6" MINIMUM FOR MEDIUM

PRESSURE AIR HANDLER UNITS)

COIL DRAIN PAN

PROVIDE CLEANOUT AT FIRST CONNECTION, AT INCREASE IN PIPE SIZE, EVERY 100'-0", AND EVERY CHANGE IN

DIRECTION, WHETHER SHOWN ON PLAN OR NOT.

NOTES:

2.75" MIN.

4.5" MIN.

(NO-HUB WITH

ACCESS COVER AND FRAME

FINISHED WALL SURFACE

THREADED CLEANOUT PLUG

(BRASS PLUG WITH MACHINE

FLOOR

TEST TEE

WALL CLEANOUT

(PAINT ORANGE)

DO NOT LOCATE

ACCESS COVER) BEHIND STUDS

8" MAX

SCREW REQUIRED)

VENT

SEALED

PER SPECS

PENETRATION

HANGER

HANGER ROD

1'-0"

SADDLE

(SEE SPEC.)

SHEET METAL

PIPE OR

CONDUIT

FILL ANNULAR SPACE WITH

NON-SHRINKING CAULK

THAN PIPE PENETRATING WALL

WALL

PIPE SLEEVE 2 PIPE SIZES LARGER

PIPE INSULATION

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Ty J. Cobb

144952TX

REVIEW ONLY

5/29/2025 10:11:55 AM

PL7.2

PLUMBING DETAILS

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

KS

05-29-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

06-02-2025

06-02-2025

06-06-2025

06-06-2025

ONE AND TWO HOUR WALL PENETRATION DETAIL FOR INSULATED PIPE

TWO HOUR WALL PENETRATION FOR INSULATED PIPE

TWO HOUR FLOOR PENETRATION DETAIL FOR P.V.C. PIPE TWO HOUR FLOOR PENETRATION DETAIL FOR P.V.C. PIPE

TWO HOUR FLOOR PENETRATION DETAIL FOR INSULATED PIPE

ONE AND TWO HOUR WALL PENETRATION DETAIL FOR P.V.C. PIPEPIPE ROUTING AT FOOTINGS

IMPERVIOUS BARRIER

CONDENSATE CLEANOUT DETAIL

IN-LINE CONDENSATE CLEANOUT DETAIL

VERTICAL CONDENSATE CLEANOUT DETAIL

GAS TIE-IN TO GAS-FIRED EQUIPMENT

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

N.T.S.

BELOW FOOTING.

ROUTE PIPE

FINISHED FLOOR

FOOTING

BOTTOM OF

STRUCTURAL FOOTING

3'-0"

6"

TOPSOIL

IMPERVIOUS BARRIER

OR CALICHE ROCK

PIPE OR

CONDUIT

12"

DITCH DEPTH MINUS

6" FOR TOPSOIL

INSTALL 12" THICK IMPERVIOUS

BARRIER AT BUILDING LINE AND

15'-0" OUT FROM BUILDING ON

ALL LINES WHICH TRAVEL UNDER

BUILDING GRADE BEAM (SEWER,

STORM, WATER, ELECT, ETC).

STEEL SLEEVE

PIPE INSULATION

PIPE

CP 25WB+ CAULK

3M FIRE BARRIER

ASSEMBLY

GYPSUM WALLBOARD

1 OR 2 HOUR

PACKING MATERIAL

BACKER ROD

OF UL 1479 AND ASTM E 814

MUST MEET THE REQUIREMENTS

STEEL PIPE

PIPE INSULATION

CP 25WB+ CAULK

3M FIRE BARRIER

WALLBOARD ASSEMBLY

2 HOUR GYPSUM

OF UL 1479 AND ASTM E 814

MUST MEET THE REQUIREMENTS

PLASTIC PIPE/CONDUIT

SOLID CONCRETE FLOOR

3M FIRE BARRIER

3M FIRE BARRIER

FS-195+ WRAP/STRIP

RC-1 RESTRICTING COLLAR OR PPD

OF UL 1479 AND ASTM E 814

MUST MEET THE REQUIREMENTS

FIRE RATED CONCRETE

FLOOR SLAB

CS-195+

STEEL HOSE CLAMP

3M FIRE BARRIER

RC-1 RESTRICTING

COMPOSITE SHEET

3M FIRE BARRIER

COLLAR.

FS-195+ WRAP/STRIP

3M FIRE BARRIER

P.V.C. PIPE

FLUTED STEEL DECK

OF UL 1479 AND ASTM E 814

MUST MEET THE REQUIREMENTS

PIPE INSULATION

CP 25WB+ CAULK

3M FIRE BARRIER

FIRE RATED

FLOOR SLAB

CONCRETE

3M FIRE BARRIER

FS-195+ WRAP/STRIP

PIPE

STEEL SLEEVE

OF UL 1479 AND ASTM E 814

MUST MEET THE REQUIREMENTS

PIPE/CONDUIT

PLASTIC

3M FIRE BARRIER

RC-1 RESTRICTING

COLLAR OR PPD

3M FIRE BARRIER

GYPSUM WALLBOARD

1 OR 2 HOUR FIRE RATED

FS-195+ WRAP/STRIP

OF UL 1479 AND ASTM E 814

MUST MEET THE REQUIREMENTS

ALL THREAD ROD

AND CLEVIS

HANGER

CLEANOUT COVER

SUPPORT CABLE

CLOSED CELL

INSULATION

CLEANOUT

COVER

FIBERGLASS

INSULATION

AND CONDENSATE

DRAIN

RIGID INSULATION

UNDER CLEVIS

HANGER

ALL THREAD ROD

AND CLEVIS

HANGER

CLEANOUT

COVER

CLOSED CELL

INSULATION

CLEANOUT

COVER

FIBERGLASS

INSULATION

AND CONDENSATE

DRAIN

RIGID INSULATION

UNDER CLEVIS

HANGER

SUPPORT

CABLE

6" M

IN

IM

U M

6" M

IN

IM

U M

ALL THREAD ROD

AND CLEVIS

HANGER

COVER

CLOSED CELL

INSULATION

CLEANOUT

COVER

FIBERGLASS

INSULATION AND

CONDENSATE

DRAIN

RIGID INSULATION

UNDER CLEVIS

HANGER

SUPPORT

CABLE

6" M

IN

IM

U M

ROOF

FLOOR/

3" MINIMUM

EQUIPMENT

GAS FIRED

6" MINIMUM

UNION

GAS PIPING ON

ROOF (VERIFY SIZE)

CAP FOR

DRIP LEG

GAS COCK

3'-0" MAXIMUM

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Ty J. Cobb

144952TX

REVIEW ONLY

5/29/2025 10:11:55 AM

PL7.3

PLUMBING DETAILS

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

KS

05-29-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

06-02-2025

06-02-2025

06-06-2025

06-06-2025

DESCRIPTIONMARK

PLUMBING FIXTURE SCHEDULE

SUPPLYMANUFACTURER & NO. ELEC. DATA ACCESSORIES

TRAP PRIMER WITH ACCESS DOOR

N.T.S.

REMARKSWASTE

2"

2"

3"

4"

VENT

1-1/4"

2"

1-1/2"

2"

1-1/4"

3"

2"

3"

1-1/2"

1-1/2"

H.W.

3"

3/4"

C.W.

1"

1-1/4"

3"

1-1/2"

1-1/4"

3"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

TRAP SIZE

SIPHON JET TYPE W/MAX. 0.5 GAL. FLUSH

FLUSH VALVE WITH MAX. 1.28 GALLON FLUSH

ALL FLOOR DRAINS TO HAVE TRAP PRIMERS

WALL HUNG OR FLOOR TYPE

MINIMUM FIXTURE CONNECTION SCHEDULE

FLOOR DRAIN

ELEC. WATER COOLER

JANITOR SINK

COUNTER SINK

WATER CLOSET

NAME OF FIXTURE

LAVATORY

URINAL

NOTE: ALL THE ABOVE FIXTURES ARE NOT NECESSARILY USED.

B1

WALL MOUNT (ADULT)

LAVATORY - A.D.A.

AMERICAN STANDARD

TEMP/COLD DELTA NICOLI 25749 LF-SS STAINLESS FAUCET (4" CENTERS), 0.5 GPM, P-TRAP, GRID DRAIN, SUPPLIES W/

STOPS, WATTS WCA-411 CARRIER, TRUEBRO LAV-GUARD, BRADLEY S59-4000A TMV

C1

WALL MOUNT (ADULT)

URINAL

ZURN

Z5738

SLOAN 186-0.5 FLUSH VALVE (3/4" TOP SPUD), 0.5 GPF, WADE 402 CARRIER

D1

FLOOR DRAIN WADE

1103G6

6" TOP SIZE, 3" DISCHARGE, TRAP PRIMER TAP

A1

FLOOR MOUNT

WATER CLOSET - A.D.A.

KOHLER

K-96057-0

SLOAN 111-1.28 FLUSH VALVE (1 1/2" TOP SPUD), 1.28 GPF,

WHITE OPEN-FRONT SEAT, BOLT CAPS (2), REFER TO ARCH PLANS FOR MOUNTING HEIGHT

G1

MOP SINK MUSTEE

63M

HOT/COLD T-10-VB FAUCET, T-35 HOSE AND WALL BRACKET, T-40 MOP HANGER,

STAINLESS STEEL BACKSPLASH & SIDESPLASH

A2

FLOOR MOUNT

WATER CLOSET

KOHLER

K-96057-0

SLOAN 3780046 FLUSH VALVE (1 1/2" TOP SPUD), 1.28 GPF,

WHITE OPEN-FRONT SEAT, BOLT CAPS (2)

B2

COUNTERTOP (ADULT)

LAVATORY - A.D.A.

AMERICAN STANDARD

AQUALYN

TEMP/COLD DELTA NICOLI 25749 LF-SS STAINLESS FAUCET (6" CENTERS), 1.5 GPM, P-TRAP, GRID DRAIN, SUPPLIES W/

STOPS, TRUEBRO LAV-GUARD, BRADLEY S59-4000A TMV

J1

CIRCULATING

PUMP

BELL & GOSSETT

ECOCIRC 20-18

120 V.

1/11 H.P.

STAINLESS STEEL BODY, FLANGED,

PROVIDE WITH JOHNSON CONTROLS A19 AQUASTAT

G2

BREAKROOM

SINK

ELKAY

LRAD 25225

TEMP/COLD 9" DEEP BASIN, DELTA MONROVIA 9191-AR-PR-DST LUMICOAT ARCTIC STAINLESS FAUCET, P-TRAP, SUPPLIES W/ STOPS, DUO-STRAINER,TMV EQUAL TO LEONARD 270 LF

M1

ICE MACHINE UTILITY BOX

AND RPZ

GUY GRAY

MIB1HAAB

MOUNT CONTROLS AT A.D.A. HEIGHT, PROVIDE WATTS LF-009 RPZ ON SUPPLY LINE

H1

EXTERIOR

HOSE BIBB

WOODFORD

B67

COLD VACUUM BREAKER, RECESSED IN LOCK BOX, VERIFY WALL THICKNESS, FREEZE RESISTANT, TAMPER

RESISTANT

E1

IN WALL BOTTLE

FILLING STATION

ELKAY

EZH20

120 V. ARCHITECT TO SELECT FINISH, NO CFC REFRIGERANTS, VANDAL RESISTANT,

WADE 403-BFS CARRIER, REFER TO ARCHITECTURAL PLANS FOR MOUNTING HEIGHT

F1

40 GALLON ELECTRIC

WATER HEATER

LOCHINVAR

LDS-40PK

240 V., 3 PH.

4500 W.

TEMPERATURE AND PRESSURE RELIEF VALVE, DUAL ELEMENT, WATTS EXPANSION TANK,

NON-SIMULTANEOUS OPERATION, LOW BOY HEIGHT

R1

SINK DISPOSER IN-SINK-ERATOR

BADGER 5

120 V., 1 PH.

1/2 HP

TRAP PRIMER

CHASE

WALL

ACCESS DOORWATER LINE(S) DOWN TO BELOW

SLAB WITH PROTECTIVE LINER

UNIONSHUTOFF

VALVE

DISTRIBUTION

SYSTEM

(AS REQUIRED)

TAP INTO TOP OF COLD WATER LINE

OF 1 1/2" OR SMALLER IN RESTROOM

CHASE. WATER LINE MUST BE

SUPPLYING AT LEAST 1 WATER

CLOSET DOWNSTREAM.

DO NOT INSTALL TRAP PRIMERS UNTIL AFTER

THE DOMESTIC WATER PIPING HYDROSTATIC

PRESSURE TEST IS SUCCESSFULLY

COMPLETED.

ACCESS DOORS TO BE INSTALLED TO ALLOW DOOR

TO FULLY OPEN. ANY ACCESS DOOR INSTALLED

WHICH CANNOT OPEN TO PROVIDE ADEQUATE

ACCESS TO TRAP PRIMER, DISTRIBUTION UNIT, ETC.

WILL BE REMOVED, WALL PATCHED TO MATCH

ADJACENT WALL, AND RELOCATED.

TRAP PRIMER TO BE

LOCATED WITHIN 4"

OF ACCESS DOOR.

*PLUMBING CONTRACTOR SHALL PROVIDE AN OFFSET VACUUM BREAKER TUBE WHERE THE HEIGHT OF THE GRAB BAR CREATES A CONFLICT WITH THE FLUSH VALVE.

1 1/4" CW

2 1/2" CW

2 1/2" CW

1 1/4" CW

3/4" HW

1/2" CW

1/2" CW

3/4" HW

3/4" HW

2 1/2" CW

2 1/2" CW

1 1/2" SS

4" SS

4" SS4" SS

4" SS

4" SS

4" SS

3" SS

1/2" CW

1/2" CW

2" V 2" V

1 1/4" V

2" V2" V

2" V

2" V.T.R

1/2" CW

3/4" HW

3/4" HW

3/4" HW

1/2" CW

1 1/2" SS

1 1/2" SS

4" SS

3" SS

4" SS

3" SS

4" SS

4" SS

4" SS

4" SS

4" SS

1" CW

1 1/4" CW

1" CW

2" CW

1 1/4" CW 1 1/4" CW

1 1/4" CW

1 1/4" CW

1 1/4" CW

2" CW 2" CW

2" CW

2" CW

3/4" HW

3/4" HW

1/2" CW

1/2" CW

3/4" HW

1/2" CW

4" SS

2" SS

1 1/2" SS

3" SS

4" SS

2" CW

4" SS

4" SS

4" SS

4" SS

4" SS

4" SS

3" SS

3" SS

4" SS

4" SS

4" SS

4" SS

3" SS

3/4" HW

3/4" HW

3/4" HW

1 1/4" CW

2" V 1 1/4" V

1 1/4" V

2" V

2" V

2" V

2" V.T.R 3" V.T.R

3" V

2" V

2" V

2" V

2" V

2" V

2" V

2" V

2" V

2" V

2" V

2" V

3" V

2" V

1 1/4" V

1 1/4" V 2" V

1 1/4" V

3/4" HW

3/4" CW

3/4" HW

4" SS3" SS

4" SS

4" SS

1" COND

2" V

1/2" CW

1/2" CW

1" COND

2" V

3/4" CW

3/4" HW

3/4" HW

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Ty J. Cobb

144952TX

REVIEW ONLY

6/6/2025 11:06:15 AM

PL8.1

PLUMBING

SCHEDULE AND

RISERS

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

KS

06-06-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

1 RISER 1

2 RISER 2 3 RISER 3

ALL PLUMBING PIPING

TO CONFORM WITH 2012

IFGC AND 2012 IPC.

06-06-2025 City Comments

06-06-2025

06-06-2025

Sheets
PD1.1 - PLUMBING DEMOLITION FLOOR PLAN
PL1.1 - PLUMBING FLOOR PLAN
PL6.1 - PLUMBING ROOF PLAN
PL7.1 - PLUMBING SYMBOLS, DETAILS & GENERAL NOTES
PL7.2 - PLUMBING DETAILS
PL7.3 - PLUMBING DETAILS
PL8.1 - PLUMBING SCHEDULE AND RISERS
PS1.1 - PLUMBING SITE PLAN

File details come from the government source that posted it. Updated .