18-Addendum No.4.pdf
PDF 1 MB Posted
- Solicitation number
- 2025-21
- Issued by
- Gregg County, Texas
About this file
This document is an Addendum to Construction Documents for Gregg County, specifically for the 800 Gilmer Rd. Precinct 2 project, prepared by EMA Engineering & Consulting, Inc. The addendum, dated August 07, 2025, modifies the original Construction Documents from 05/01/2025 and provides updates to electrical specifications and drawings. The project involves electrical system modifications, including changes to electrical site plans, floor plans, and panel schedules for the Gregg County facility.
The addendum includes specific technical modifications such as removing section 1.7 in 26 09 23 regarding additional materials, relocating disconnect switches, adding unistrut rack with ATS and main disconnect switch, and updating electrical panel configurations. The electrical plans cover details for various building areas including office spaces, courtrooms, breakrooms, and exterior lighting. The document provides comprehensive electrical load calculations, panel schedules, and technical specifications, with all electrical work conforming to the 2017 National Electrical Code (NEC). The project appears to be a renovation or upgrade of the existing Gregg County Precinct 2 facility's electrical infrastructure.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ES7
GENERATOR
ES10
ES9
ES8
ZFH
Z3H
Z4H
ES11
ES4
BL
BL
ZFP
ZFP
ZFP
L1-15,17
L1-15,17
L1-15,17
L2-17
BLBLBL
L2-19
ES13
ES15
ES2
ES16
ES14
L1- 51
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Matthew A. Hensley
108637TX
REVIEW ONLY
8/7/2025 1:47:06 PM
ES1.1
ELECTRICAL SITE
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
ARJ
06-06-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
ELECTRICAL SITE PLAN GENERAL NOTES
1. CONTRACTORS AND SUBCONTRACTORS SHALL VERIFY LOCATION,
CONDUCT TEST AND INSPECTIONS, COORDINATE WITH UTILITIES,
OWNER'S REPRESENTATIVES, AND CHECK FOR ALL UNDERGROUND
UTILITIES AND LINES BEFORE DITCHING TAKES PLACE.
CONTRACTOR AND SUBCONTRACTORS PERFORMING THESE DUTIES
SHALL BE RESPONSIBLE FOR ANY REPAIRS OF CUT OR DAMAGED
LINES AND UTILITIES NOT SHOWN ON PLANS.
2. PROVIDE SEPARATE CONTACTORS FOR INDEPENDENT CONTROL OF
EXTERIOR LIGHTING GROUPS PER LIGHTING CONTROL DETAIL.
ELECTRICAL SITE PLAN NOTES
ES2 PROVIDE AND ROUTE UNDERGROUND SERVICE CONDUCTORS
FROM UTILITY TRANSFORMER LOAD SIDE TO MAIN SERVICE
DISCONNECT. PROVIDE AND ROUTE UNDERGROUND SERVICE
CONDUCTORS FROM SECONDARY ENCLOSURE TO ELECTRICAL
SERVICE DISCONNECT(S). REFER TO RISER DIAGRAM FOR MORE
INFORMATION.
ES4 FLAG POLE. REFER TO FLAG POLE DETAIL. COORDINATE EXACT
LOCATION WITH ARCHITECT.
ES7 APPROXIMATE LOCATION OF EXISTING OVERHEAD UTILITY
POWER. VERYIFY EXACT LOCATION WITH UTILITY PROVIDER IF
NEEDED AND REFER TO RISER DIAGRAM FOR MORE
INFORMATION.
ES8 APPROXIMATE LOCATION OF EXISTING UNDERGROUND UTILITY
POWER.
ES9 APPROXIMATE LOCATION OF EXISTING UTILITY METER.
ES10 APPROXIMATE LOCATION OF NEW GENERATOR. REFER TO
GENERATOR DETAIL FOR MORE INFORMATION.
ES11 PROVIDE AND RUN UNDERGROUND CONDUITS FROM
GENERATOR TO ATS. SEE RISER DIAGRAM FOR MORE
INFORMATION.
ES13 POLE TO BE INSTALLED IN EXISTING FLOOD LIGHT LOCATION.
REUSE EXISTING PATHWAY.
ES14 PROVIDE A UNISTRUT RACK TO FILL ALL NEW ELECTRICAL
EQUIPMENT INCLUDING TRANSSOCKET METER, GFCI
WEATHERPROOF MAINTENANCE OUTLET, AND MAIN DISCONNECT
SWITCH. COORDINATE WITH OWNER FOR EXACT LOCATION AND
DIMENSIONS OF UNISTRUT RACK.
ES15 APPPROXIMATE LOCATION OF SERVICE DISCONNECT SWITCH.
PROVIDE 400A DISCONNECT WITH 400A FUSES. REFER TO RISER
DIAGRAM FOR MORE INFORMATION.
ES16 APPROXIMATE LOCATION OF ATS. ATS SHALL HAVE NEMA 3R
ENCLOSURE. PROVIDE AND ROUTE UNDERGROUND
CONDUCTORS FROM GENERATOR TO LOAD SIDE OF ATS. REFER
TO RISER DIAGRAM FOR MORE INFORMATION.
1" = 20'-0"
1 ELECTRICAL SITE PLAN
07-23-2025 Addendum 2
08-07-2025 Addendum 3
08-07-2025
EF
EF
M
J
M
M
J
J
J
J
J
J
J
J
J
JJ
J
J
J
J
J
J
P
JJ
J
J
J
EF
EF
EF
J
E3
E2
E2
E5
T6
E17
E6
E6
E17
T1
T6
T1 T6
E6
T6
T6
E2
T1
E5
T1
E6
E2
E2E2
T1
MDP
AHAC
L2L1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1 T1
T1
T6
J
J
E5
E5
E2 E2
E13
E5
E5
T6
E25E2 E2E2
T6
E2
E2
E2
E2
E5
E20
CONFERENCE
OPEN OFFICE
BREAKROOM
COURT ROOM
130 TIM
SUPER OFF.
HALL
MENS
JAN
ENTRY
100 WAITING
TAX CLERKS
ELEC
WORKROOM
STRG
STRG
ROGER
JP WAITING
IT
STRG
DRIVE THRU
WEB DEAL
SUPER OFF.
MICHELLE
STRG
STRG
UNISEX
WMNS
RAY
SERVICE AREA
RR
STRG
STRG
L2- 2
L1- 13
L1- 45
L1- 16
L2- 43 L2- 46L2- 45
L1- 21
L1- 21
L2- 41
E6
L1-11
L1-29
L1- 21
L1- 21
L1- 21
L1- 21
L1- 3
L1- 38
L2- 20
L2- 18
L1- 2
L1- 36
L2- 3
L1- 42
L1- 46
L2- 29
L1- 10
L1- 39
L2- 14
L2- 26
L2- 24
L2- 8
L1- 11
L1- 4
L1- 31
L1- 30
L1- 18
L1- 12
L1- 10
L1- 33
L1- 48
L1- 37
L1- 44
L1- 14 L1- 27
L1- 40
L1- 28
L2- 6
L1- 22
L1- 24
L1- 34
L1- 7
L2- 4
L2- 44
L2- 42
E24
L2- 47
L1- 26 L1- 35 L2- 47 L1- 35
L2- 30
L2- 23 L2- 25
L2- 10
L1- 5
L2- 16
L2- 32
L1- 23
L2- 21
L2- 15
L2- 9
L2- 27 L2- 33
L1- 6
L1- 29
L1- 25
L1- 25
L1- 25
L1- 25
L1- 25
L1- 25 L1- 25
L1- 1
L1- 1
L1- 1
L1- 1
L1- 1
L1- 1
L1- 1
L1- 1
L1- 1
E27E28
L2- 35
L2- 31
T1
T1
L1- 25 L1- 25
T1
L1- 25
L1- 25
T1
L1- 1
T1 L1- 1
E2
L1- 26
T6
L2- 28
E22
E22
L2- 36
L1- 47
E13E13
L2- 12
E30
L1- 8
L1- 10
L1- 10
L1- 43
L1- 21
L1- 41
MS-AH-1T
#117
L2- 34
L1- 9
L1- 20
L1- 19
L1- 32 E31
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Matthew A. Hensley
108637TX
REVIEW ONLY
8/7/2025 1:47:11 PM
EP1.1
ELECTRICAL FLOOR
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
ARJ
06-06-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
ELECTRICAL GENERAL NOTES
1. SEE SHEET EP7.1 FOR GENERAL NOTES APPLICABLE
TO THE ENTIRE DRAWING SET.
ELECTRICAL PLAN NOTES
E2 OUTLET INSTALLED 6" ABOVE MILLWORK SPLASH.
VERIFY EXACT LOCATION WITH ARCHITECTURAL
DRAWINGS.
E3 EWC OUTLET INSTALLED 20" A.F.F. - ON GFCI
BREAKER.
E5 WEATHERPROOF GFCI MAINTENANCE OUTLET
INSTALLED 18" A.F.F.
E6 GFCI OUTLET INSTALLED 44" A.F.F.
E13 MILLWORK RECEPTACLES - PROVIDE A 1" CONDUIT
FROM ACCESSIBLE ATTIC SPACE, RUN DOWN
INSIDE NEAREST WALL AND UNDER SLAB TO
J-BOXES. RUN CONDUIT CONCEALED IN
MILLWORK TO OUTLETS SHOWN. DO NOT INSTALL
OUTLET FACEPLATE FACING UP IN MILLWORK.
VERIFY EXACT LOCATION OF J-BOX PRIOR TO
CONCRETE POUR WITH FURNITURE INSTALLER.
E17 FLOOR BOXES TO BE UNDER FURNITURE.
COORDINATE LOCATION OF FLOOR BOXES WITH
FURNITURE SUPPLIER BEFORE ROUGH IN FOR
EXACT LOCATION. SAW-CUT EXISTING SLAB.
E20 PROVIDE SINGLE-POLE MOTOR RATED SWITCH
FOR DRIVE THRU TUBING SYSTEM (TELLER
TERMINAL & CUSTOMER TERMINAL). COORDINATE
EXACT SWITCH LOCATION WITH ARCHITECT
BEFORE INSTALLATIONL.
E22 PROVIDE POWER TO AIR HANDLER FROM
CONDENSOR. REFER TO MECHANICAL
SCHEUDLES FOR MORE INFORMATION.
E24 GFCI OUTLET INSTALLED 24" A.F.F.
E25 GFCI OUTLET INSTALLED 66" A.F.F.
E27 DISCONNECT TO PROVIDE POWER TO ELECTRIC
WATER HEATER.
E28 RECEPTACLE TO POWER CIRCULATION PUMP.
COORDINATE EXACT LOCATION OF PUMP WITH
PLUMBING BEFORE ROUGH-IN.
E30 SWITCH FOR DISPOSAL TO BE MOUNTED 6" ABOVE
MILLWORK SPLASH.
E31 APPROXIMATE LOCATION FOR IRRIGATION
CONTROLLER. COORDINATE EXACT LOCATION
WITH ARCHITECT PRIOR TO INSTALLATION.
True
PROJECT
NORTH
3/16" = 1'-0"
1 ELECTRICAL FLOOR PLAN
ELECTRICAL TECHNOLOGY PLAN NOTES
T1 POWER ABOVE CEILING FOR ELECTRIC DOOR
RELEASE HARDWARE FOR CONNECTION TO BUILDING
ACCESS SYSTEM.
T6 PROVIDE AND INSTALL OUTLET AT THIS
APPROXIMATE LOCATION FOR POWER TO FLAT
SCREEN TV. COORDINATE EXACT INSTALLATION
HEIGHT WITH TECHNOLOGY.
06-06-2025 City Comments
07-23-2025 Addendum 2
08-07-2025 Addendum 3
ALL ELECTRICAL WORK TO
CONFORM TO 2017 NEC.
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Matthew A. Hensley
108637TX
REVIEW ONLY
8/7/2025 1:47:11 PM
EP8.1
ELECTRICAL PANEL
SCHEDULES
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
ARJ
06-06-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
Water Heating 125.00% 6250 VA 5000 VA
Receptacles 65.79% 20835 VA 31671 VA
Power 100.00% 7441 VA 7441 VA Total Est. Demand: 289 A
NonLinear Tech 90.72% 14425 VA 15900 VA Total Conn.: 306 A
Motor 100.00% 3615 VA 3615 VA Total Est. Demand: 120060 VA
Lighting 125.00% 18909 VA 15127 VA Total Conn. Load: 127398 VA
HVAC 100.00% 49351 VA 49351 VA
Load Classification Demand Factor Estimated Demand Connected Load Panel Totals
Legend: Phase A,B,C values are in Amps.
41 SPACE 1 -- -- 0 A / 0 A -- -- 1 - 42
39 SPACE 1 -- -- 0 A / 0 A -- -- 1 - 40
37 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPD 38
35 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 36
33 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 34
31 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 32
29 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 30
27 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 28
25 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 26
23 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 24
21 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 22
19 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 20
17 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 18
15 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 16
13 -- -- -- -- 144 A / 0 A -- -- 1 SPARE 14
11 Panel L1 - w/Main CB 2 225 A #4/0 145 A / 0 A 12
9 SPARE 1 -- -- 0 A / 0 A 10
7 SPARE 1 -- -- 0 A / 174 A -- -- -- -- 8
5 -- -- -- -- 131 A / 234 A #4/0 225 A 2 Panel L2 - w/Main CB 6
3 -- -- -- -- 154 A / 0 A -- -- 1 SPARE 4
1 Panel AHAC - w/Main CB 3 225 A #4/0 127 A / 0 A -- -- 1 SPARE 2
# Load Name P Bkr Wire A B C Wire Bkr P Load Name #
% Imbalance - 70Notes:, ** See Riser Diagram for feeder info. **
Total Demand Load - 289 A
Fed From - UTIL TX Service - 120/240 3ph 4w Branch AIC - 18,000 AIC
Mount - Surface Mnt / NEMA 1Panel - MDP Bus - 400 A / MCB - 400 A In Room - ELEC 117
Total Est. Demand: 119 A
Total Conn.: 119 A
Total Est. Demand: 49351 VA
Total Conn. Load: 49351 VA
HVAC 100.00% 49351 VA 49351 VA
Load Classification Demand Factor Estimated Demand Connected Load Panel Totals
Legend: Phase A,B,C values are in Amps.
41 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 42
39 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 40
37 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 38
35 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 36
33 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 34
31 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 32
29 -- -- -- -- 12 A / 0 A -- -- 1 SPARE 30
27 AC-2T 30A DISC. & 20A FUSES 2 20 A #12 12 A / 0 A -- -- 1 SPARE 28
25 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 26
23 SPARE 1 -- -- 0 A / 15 A -- -- -- -- 24
21 -- -- -- -- 15 A / 15 A #12 20 A 2 RTU-2T #107 30A DISC. & 25A FUSES 22
19 RTU-2T #121 30 A DISC. & 30A FUSES 2 20 A #12 15 A / 0 A -- -- 1 SPARE 20
17 -- -- -- -- 18 A / 0 A -- -- 1 SPARE 18
15 -- -- -- -- 18 A / 8 A -- -- -- -- 16
13 RTU-3T #130 30A DISC. & 25A FUSES 3 20 A #12 18 A / 8 A #12 20 A 2 AC-1T 30A DISC. & 15A FUSES 14
11 -- -- -- -- 21 A / 26 A -- -- -- -- 12
9 -- -- -- -- 21 A / 26 A -- -- -- -- 10
7 RTU-4T #103 30A DISC. & 30A FUSES 3 30 A #10 21 A / 26 A #10 30 A 3 RTU-5T #118 60A DISC. & 40A FUSES 8
5 -- -- -- -- 18 A / 21 A -- -- -- -- 6
3 -- -- -- -- 18 A / 21 A -- -- -- -- 4
1 RTU-3T #128 30A DISC. & 25A FUSES 3 20 A #12 18 A / 21 A #10 30 A 3 RTU-4T #115 30A DISC. & 30A FUSES 2
# Load Name P Bkr Wire A B C Wire Bkr P Load Name #
% Imbalance - 18Notes:, ** See Riser Diagram for feeder info. **
Total Demand Load - 119 A
Fed From - MDP Service - 120/240 3ph 4w Branch AIC - 18,000 AIC
Mount - Surface Mnt / NEMA 1Panel - AHAC Bus - 225 A / MCB - 225 A In Room - ELEC 117
Water Heating 125.00% 6250 VA 5000 VA
Receptacles 94.11% 10668 VA 11336 VA Total Est. Demand: 198 A
Power 100.00% 4521 VA 4521 VA Total Conn.: 181 A
NonLinear Tech 100.00% 6000 VA 6000 VA Total Est. Demand: 47597 VA
Motor 100.00% 2535 VA 2535 VA Total Conn. Load: 43430 VA
Lighting 125.00% 18290 VA 14632 VA
Load Classification Demand Factor Estimated Demand Connected Load Panel Totals
Legend: Phase A,B,C values are in Amps.
53 GENERATOR BLOCK HEATER(FOR FUTURE) 1 20 A #12 2 A / ... -- -- 1 SPACE 54
51 WEATHERPROOF GP OUTLET(FOR FUTURE) 1 20 A #12 2 A / ... -- -- 1 SPACE 52
49 GENERATOR BATTERY CHARGER(FOR FUTURE) 1 20 A #12 2 A / 0 A -- -- 1 SPACE 50
47 GFCI OUTLET - BREAKROOM #127 1 20 A #12 3 A / 0 A -- -- 1 SPACE 48
45 UNDERCOUNTER ICE MACHINE - BREAKROOM #117 (ON GF... 1 20 A #12 11 A /... #12 20 A 1 REFRIGERATOR - BREAKROOM #127 (ON GFCI BREAKER) 46
43 REFRIGERATOR - BREAKROOM #127 (ON GFCI BREAKER) 1 20 A #12 10 A /... #12 20 A 1 DISPOSAL - BREAKROOM #127 (ON GFCI BREAKER) 44
41 DRINKING FOUNTAIN - BREAKROOM #127 (ON GFCI BREAKER) 1 20 A #12 7 A / ... #12 20 A 1 DISHWASHER - BREAKROOM #127 (ON GFCI BREAKER) 42
39 LIGHTING 1 20 A #12 11 A / 11 A #10 20 A 1 EXTERIOR SIGNAGE 40
37 EXTERIOR SIGNAGE 1 20 A #12 11 A / 11 A #12 20 A 1 EXTERIOR SIGNAGE 38
35 WATER HEATER W/ 60A DISC. & 50A FUSES 1 50 A #6 38 A / 2 A #12 20 A 1 GP OUTLETS - JANITOR #126 36
33 GP OUTLETS - OPEN OFFICE #119 1 20 A #12 6 A / 9 A #10 20 A 1 GP OUTLETS - SUPER OFF. #131 34
31 CIRCULATION PUMP & GP OUTLET 1 20 A #12 4 A / 8 A #12 20 A 1 FLOOR BOXES - COURTROOM #130 32
29 GP OUTLETS - MICHELLE #110 1 20 A #12 8 A / 3 A #12 20 A 1 GP OUTLETS - BREAKROOM #127 30
27 GP OUTLETS - OPEN OFFICE #119 1 20 A #12 5 A / 4 A #12 20 A 1 TV - COURTROOM #130 (FUTURE) 28
25 TV - BREAKROOM #127 1 20 A #12 4 A / 3 A #12 20 A 1 GP OUTLETS - STRG #106 26
23 GP OUTLETS - BREAKROOM #127 1 20 A #12 2 A / 5 A #12 20 A 1 GP OUTLETS - CORRIDOR 24
21 COPIER - OPEN OFFICE #119 1 20 A #8 13 A / 0 A #12 20 A 1 EXTERIOR CANOPY LIGHTING THRU CONTACTOR 22
19 EXTERIOR LIGHTING THRU CONTACTOR 1 20 A #12 7 A / 6 A #12 20 A 1 GP OUTLETS - RAY #104 20
17 EXTERIOR LIGHTING THRU CONTACTOR 1 20 A #12 0 A / 4 A #12 20 A 1 TV - RAY #104 18
15 GP OUTLETS - OPEN OFFICE #119 1 20 A #12 6 A / 3 A #12 20 A 1 GP OUTLETS - JUDGES STAND 16
13 EXTERIOR CANOPY LIGHTING THRU CONTACTOR 1 20 A #12 4 A / 4 A #12 20 A 1 TV - WAITING #103 14
11 EXTERIOR CANOPY LIGHTING THRU CONTACTOR 1 20 A #12 4 A / 8 A #12 20 A 1 GP OUTLETS - WAITING #103 12
9 TV - OPEN OFFICE #119 1 20 A #12 4 A / 4 A #12 20 A 1 TV - TIM #128 10
7 LIGHTING 1 20 A #12 4 A / 13 A #12 20 A 1 COPIER - WORKROOM #109 8
5 LIGHTING 1 60 A #4 42 A / 3 A #12 20 A 1 GP OUTLETS - CORRIDOR 6
3 GP OUTLETS - JP WAITING #118 1 20 A #12 5 A / 8 A #12 20 A 1 GP OUTLETS - TIM #128 4
1 LIGHTING 1 80 A #1 61 A / 2 A #12 20 A 1 GP OUTLETS - MENS RR #125 2
# Load Name P Bkr Wire A B C Wire Bkr P Load Name #
% Imbalance - 100Notes:, ** See Riser Diagram for feeder info. **
Total Demand Load - 198 A
Fed From - MDP Service - 120/240 1ph 3w Branch AIC - 18,000 AIC
Mount - Surface Mnt / NEMA 1Panel - L2 Bus - 225 A / MCB - 225 A In Room - ELEC 117
Receptacles 74.59% 15168 VA 20335 VA Total Est. Demand: 124 A
Power 100.00% 1675 VA 1675 VA Total Conn.: 145 A
NonLinear Tech 100.00% 9900 VA 9900 VA Total Est. Demand: 29656 VA
Motor 100.00% 2355 VA 2355 VA Total Conn. Load: 34700 VA
Lighting 125.00% 619 VA 495 VA
Load Classification Demand Factor Estimated Demand Connected Load Panel Totals
Legend: Phase A,B,C values are in Amps.
53 SPACE 1 -- -- 0 A / ... -- -- 1 SPACE 54
51 WEATHERPROOF OUTLET 1 20 A #12 2 A / ... -- -- 1 SPACE 52
49 DRIVE-THRU TUBING SYSTEM 1 20 A #12 15 A / 0 A -- -- 1 SPACE 50
47 GFCI OUTLETS - RR #102 1 20 A #12 2 A / 9 A #12 20 A 1 GP OUTLETS - TAX CLERKS #111 48
45 IT RACK 1 20 A #10 15 A /... #12 20 A 1 GP OUTLETS - ELEC ROOM #117 46
43 GP OUTLETS - TAX CLERKS #111 1 20 A #12 8 A / ... #12 20 A 1 GP OUTLETS - TAX CLERKS #111 44
41 GP OUTLETS - TAX CLERKS #111 1 20 A #12 8 A / ... #12 20 A 1 TV - JP WAITING #118 42
39 GP OUTLETS - SUPER OFF. #115 1 20 A #12 8 A / 13 A #12 20 A 1 PRINTER - DRIVE THRU #114 40
37 GP OUTLETS - TAX CLERKS #111 1 20 A #12 8 A / 3 A #12 20 A 1 DRIVE-THRU DEAL DRAWER 38
35 GFCI OUTLET - BREAKROOM #127 1 20 A #12 3 A / 4 A #12 20 A 1 TV - ROGER #107 36
33 GP OUTLETS - SERVICE AREA #116 1 20 A #12 5 A / 3 A #12 20 A 1 GP OUTLETS - CORRIDOR 34
31 GP OUTLET - WORKROOM #109 1 20 A #12 2 A / 3 A #12 20 A 1 IRRIGATION CONTROLLER - ELEC #117 32
29 GP OUTLETS - ENTRY #101 1 20 A #12 5 A / 2 A #12 20 A 1 GP OUTLET - WORKROOM #109 30
27 GP OUTLETS - TAX CLERKS #111 1 20 A #12 3 A / 3 A #12 20 A 1 GP OUTLETS - DRIVE THRU #114 28
25 DOOR ACCESS CONTROL 1 20 A #12 0 A / 3 A #12 20 A 1 GFCI OUTLET - BREAKROOM #127 26
23 GP OUTLETS - HALLWAY #120 / STORAGE #132 1 20 A #12 6 A / 5 A #12 20 A 1 GP OUTLETS - DRIVE THRU #114 24
21 WEATHERPROOF MAINTENCE OUTLET - EXTERIOR 1 20 A #10 11 A / 3 A #12 20 A 1 GP OUTLETS - DRIVE THRU #114 22
19 GP OUTLETS - IT #124 1 20 A #12 8 A / 8 A #12 20 A 1 FLOOR BOXES - CONFERENCE #121 20
17 -- -- -- -- 2 A / 4 A #12 20 A 1 TV - CONFERENCE ROOM #121 18
15 PARKING LOT LIGHTS THRU CONTACTOR 2 20 A #12 2 A / 15 A #10 20 A 1 IT RACK 16
13 GFCI OUTLETRS - UNISEX #122 1 20 A #12 6 A / 13 A #12 20 A 1 COPIER - TAX CLERKS #111 14
11 UNDERCOUNTER REFRIGERATOR WORKROOM #109 (ON... 1 20 A #12 10 A / 8 A #12 20 A 1 GP OUTLETS - CONFERENCE #121 12
9 GP OUTLETS - OPEN OFFICE #119 1 20 A #12 6 A / 11 A #12 20 A 1 GP OUTLET - STRG #113 10
7 GFCI OUTLETS - WMNS #123 1 20 A #12 7 A / 10 A #12 20 A 1 ERRS PANEL 8
5 GP OUTLETS - COURTROOM #130 1 20 A #12 8 A / 5 A #12 20 A 1 GP OUTLETS - WAITING #103 6
3 FANS-PATIO 1 20 A #12 1 A / 2 A #12 20 A 1 GP OUTLET - WORKROOM #109 4
1 DOOR ACCESS CONTROL 1 20 A #12 0 A / 8 A #12 20 A 1 GP OUTLETS - ROGER #107 2
# Load Name P Bkr Wire A B C Wire Bkr P Load Name #
% Imbalance - 100Notes:, ** See Riser Diagram for feeder info. **
Total Demand Load - 124 A
Fed From - MDP Service - 120/240 1ph 3w Branch AIC - 18,000 AIC
Mount - Surface Mnt / NEMA 1Panel - L1 Bus - 225 A / MCB - 225 A In Room - ELEC 117
07-23-2025 Addendum 2
08-07-2025 Addendum 3
| GREGG COUNTY PRECINCT 2 - ELECTRICAL- IFP - 8-7-2025 - ADD 3.pdf |
| Sheets |
| EP1.1 - ELECTRICAL FLOOR PLAN |
| EP8.1 - ELECTRICAL PANEL SCHEDULES |
| ES1.1 - ELECTRICAL SITE PLAN |
File details come from the government source that posted it. Updated .