18-Addendum No.4.pdf

PDF 1 MB Posted

Attached to
General Contractor Services for Precinct 2 Justice Facility in Gregg County, Texas
Solicitation number
2025-21
Issued by
Gregg County, Texas

About this file

This document is an Addendum to Construction Documents for Gregg County, specifically for the 800 Gilmer Rd. Precinct 2 project, prepared by EMA Engineering & Consulting, Inc. The addendum, dated August 07, 2025, modifies the original Construction Documents from 05/01/2025 and provides updates to electrical specifications and drawings. The project involves electrical system modifications, including changes to electrical site plans, floor plans, and panel schedules for the Gregg County facility.

The addendum includes specific technical modifications such as removing section 1.7 in 26 09 23 regarding additional materials, relocating disconnect switches, adding unistrut rack with ATS and main disconnect switch, and updating electrical panel configurations. The electrical plans cover details for various building areas including office spaces, courtrooms, breakrooms, and exterior lighting. The document provides comprehensive electrical load calculations, panel schedules, and technical specifications, with all electrical work conforming to the 2017 National Electrical Code (NEC). The project appears to be a renovation or upgrade of the existing Gregg County Precinct 2 facility's electrical infrastructure.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ES7

GENERATOR

ES10

ES9

ES8

ZFH

Z3H

Z4H

ES11

ES4

BL

BL

ZFP

ZFP

ZFP

L1-15,17

L1-15,17

L1-15,17

L2-17

BLBLBL

L2-19

ES13

ES15

ES2

ES16

ES14

L1- 51

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Matthew A. Hensley

108637TX

REVIEW ONLY

8/7/2025 1:47:06 PM

ES1.1

ELECTRICAL SITE

PLAN

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

ARJ

06-06-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

ELECTRICAL SITE PLAN GENERAL NOTES

1. CONTRACTORS AND SUBCONTRACTORS SHALL VERIFY LOCATION,

CONDUCT TEST AND INSPECTIONS, COORDINATE WITH UTILITIES,

OWNER'S REPRESENTATIVES, AND CHECK FOR ALL UNDERGROUND

UTILITIES AND LINES BEFORE DITCHING TAKES PLACE.

CONTRACTOR AND SUBCONTRACTORS PERFORMING THESE DUTIES

SHALL BE RESPONSIBLE FOR ANY REPAIRS OF CUT OR DAMAGED

LINES AND UTILITIES NOT SHOWN ON PLANS.

2. PROVIDE SEPARATE CONTACTORS FOR INDEPENDENT CONTROL OF

EXTERIOR LIGHTING GROUPS PER LIGHTING CONTROL DETAIL.

ELECTRICAL SITE PLAN NOTES

ES2 PROVIDE AND ROUTE UNDERGROUND SERVICE CONDUCTORS

FROM UTILITY TRANSFORMER LOAD SIDE TO MAIN SERVICE

DISCONNECT. PROVIDE AND ROUTE UNDERGROUND SERVICE

CONDUCTORS FROM SECONDARY ENCLOSURE TO ELECTRICAL

SERVICE DISCONNECT(S). REFER TO RISER DIAGRAM FOR MORE

INFORMATION.

ES4 FLAG POLE. REFER TO FLAG POLE DETAIL. COORDINATE EXACT

LOCATION WITH ARCHITECT.

ES7 APPROXIMATE LOCATION OF EXISTING OVERHEAD UTILITY

POWER. VERYIFY EXACT LOCATION WITH UTILITY PROVIDER IF

NEEDED AND REFER TO RISER DIAGRAM FOR MORE

INFORMATION.

ES8 APPROXIMATE LOCATION OF EXISTING UNDERGROUND UTILITY

POWER.

ES9 APPROXIMATE LOCATION OF EXISTING UTILITY METER.

ES10 APPROXIMATE LOCATION OF NEW GENERATOR. REFER TO

GENERATOR DETAIL FOR MORE INFORMATION.

ES11 PROVIDE AND RUN UNDERGROUND CONDUITS FROM

GENERATOR TO ATS. SEE RISER DIAGRAM FOR MORE

INFORMATION.

ES13 POLE TO BE INSTALLED IN EXISTING FLOOD LIGHT LOCATION.

REUSE EXISTING PATHWAY.

ES14 PROVIDE A UNISTRUT RACK TO FILL ALL NEW ELECTRICAL

EQUIPMENT INCLUDING TRANSSOCKET METER, GFCI

WEATHERPROOF MAINTENANCE OUTLET, AND MAIN DISCONNECT

SWITCH. COORDINATE WITH OWNER FOR EXACT LOCATION AND

DIMENSIONS OF UNISTRUT RACK.

ES15 APPPROXIMATE LOCATION OF SERVICE DISCONNECT SWITCH.

PROVIDE 400A DISCONNECT WITH 400A FUSES. REFER TO RISER

DIAGRAM FOR MORE INFORMATION.

ES16 APPROXIMATE LOCATION OF ATS. ATS SHALL HAVE NEMA 3R

ENCLOSURE. PROVIDE AND ROUTE UNDERGROUND

CONDUCTORS FROM GENERATOR TO LOAD SIDE OF ATS. REFER

TO RISER DIAGRAM FOR MORE INFORMATION.

1" = 20'-0"

1 ELECTRICAL SITE PLAN

07-23-2025 Addendum 2

08-07-2025 Addendum 3

08-07-2025

EF

EF

M

J

M

M

J

J

J

J

J

J

J

J

J

JJ

J

J

J

J

J

J

P

JJ

J

J

J

EF

EF

EF

J

E3

E2

E2

E5

T6

E17

E6

E6

E17

T1

T6

T1 T6

E6

T6

T6

E2

T1

E5

T1

E6

E2

E2E2

T1

MDP

AHAC

L2L1

T1

T1

T1

T1

T1

T1

T1

T1

T1

T1

T1 T1

T1

T6

J

J

E5

E5

E2 E2

E13

E5

E5

T6

E25E2 E2E2

T6

E2

E2

E2

E2

E5

E20

CONFERENCE

OPEN OFFICE

BREAKROOM

COURT ROOM

130 TIM

SUPER OFF.

HALL

MENS

JAN

ENTRY

100 WAITING

TAX CLERKS

ELEC

WORKROOM

STRG

STRG

ROGER

JP WAITING

IT

STRG

DRIVE THRU

WEB DEAL

SUPER OFF.

MICHELLE

STRG

STRG

UNISEX

WMNS

RAY

SERVICE AREA

RR

STRG

STRG

L2- 2

L1- 13

L1- 45

L1- 16

L2- 43 L2- 46L2- 45

L1- 21

L1- 21

L2- 41

E6

L1-11

L1-29

L1- 21

L1- 21

L1- 21

L1- 21

L1- 3

L1- 38

L2- 20

L2- 18

L1- 2

L1- 36

L2- 3

L1- 42

L1- 46

L2- 29

L1- 10

L1- 39

L2- 14

L2- 26

L2- 24

L2- 8

L1- 11

L1- 4

L1- 31

L1- 30

L1- 18

L1- 12

L1- 10

L1- 33

L1- 48

L1- 37

L1- 44

L1- 14 L1- 27

L1- 40

L1- 28

L2- 6

L1- 22

L1- 24

L1- 34

L1- 7

L2- 4

L2- 44

L2- 42

E24

L2- 47

L1- 26 L1- 35 L2- 47 L1- 35

L2- 30

L2- 23 L2- 25

L2- 10

L1- 5

L2- 16

L2- 32

L1- 23

L2- 21

L2- 15

L2- 9

L2- 27 L2- 33

L1- 6

L1- 29

L1- 25

L1- 25

L1- 25

L1- 25

L1- 25

L1- 25 L1- 25

L1- 1

L1- 1

L1- 1

L1- 1

L1- 1

L1- 1

L1- 1

L1- 1

L1- 1

E27E28

L2- 35

L2- 31

T1

T1

L1- 25 L1- 25

T1

L1- 25

L1- 25

T1

L1- 1

T1 L1- 1

E2

L1- 26

T6

L2- 28

E22

E22

L2- 36

L1- 47

E13E13

L2- 12

E30

L1- 8

L1- 10

L1- 10

L1- 43

L1- 21

L1- 41

MS-AH-1T

#117

L2- 34

L1- 9

L1- 20

L1- 19

L1- 32 E31

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Matthew A. Hensley

108637TX

REVIEW ONLY

8/7/2025 1:47:11 PM

EP1.1

ELECTRICAL FLOOR

PLAN

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

ARJ

06-06-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

ELECTRICAL GENERAL NOTES

1. SEE SHEET EP7.1 FOR GENERAL NOTES APPLICABLE

TO THE ENTIRE DRAWING SET.

ELECTRICAL PLAN NOTES

E2 OUTLET INSTALLED 6" ABOVE MILLWORK SPLASH.

VERIFY EXACT LOCATION WITH ARCHITECTURAL

DRAWINGS.

E3 EWC OUTLET INSTALLED 20" A.F.F. - ON GFCI

BREAKER.

E5 WEATHERPROOF GFCI MAINTENANCE OUTLET

INSTALLED 18" A.F.F.

E6 GFCI OUTLET INSTALLED 44" A.F.F.

E13 MILLWORK RECEPTACLES - PROVIDE A 1" CONDUIT

FROM ACCESSIBLE ATTIC SPACE, RUN DOWN

INSIDE NEAREST WALL AND UNDER SLAB TO

J-BOXES. RUN CONDUIT CONCEALED IN

MILLWORK TO OUTLETS SHOWN. DO NOT INSTALL

OUTLET FACEPLATE FACING UP IN MILLWORK.

VERIFY EXACT LOCATION OF J-BOX PRIOR TO

CONCRETE POUR WITH FURNITURE INSTALLER.

E17 FLOOR BOXES TO BE UNDER FURNITURE.

COORDINATE LOCATION OF FLOOR BOXES WITH

FURNITURE SUPPLIER BEFORE ROUGH IN FOR

EXACT LOCATION. SAW-CUT EXISTING SLAB.

E20 PROVIDE SINGLE-POLE MOTOR RATED SWITCH

FOR DRIVE THRU TUBING SYSTEM (TELLER

TERMINAL & CUSTOMER TERMINAL). COORDINATE

EXACT SWITCH LOCATION WITH ARCHITECT

BEFORE INSTALLATIONL.

E22 PROVIDE POWER TO AIR HANDLER FROM

CONDENSOR. REFER TO MECHANICAL

SCHEUDLES FOR MORE INFORMATION.

E24 GFCI OUTLET INSTALLED 24" A.F.F.

E25 GFCI OUTLET INSTALLED 66" A.F.F.

E27 DISCONNECT TO PROVIDE POWER TO ELECTRIC

WATER HEATER.

E28 RECEPTACLE TO POWER CIRCULATION PUMP.

COORDINATE EXACT LOCATION OF PUMP WITH

PLUMBING BEFORE ROUGH-IN.

E30 SWITCH FOR DISPOSAL TO BE MOUNTED 6" ABOVE

MILLWORK SPLASH.

E31 APPROXIMATE LOCATION FOR IRRIGATION

CONTROLLER. COORDINATE EXACT LOCATION

WITH ARCHITECT PRIOR TO INSTALLATION.

True

PROJECT

NORTH

3/16" = 1'-0"

1 ELECTRICAL FLOOR PLAN

ELECTRICAL TECHNOLOGY PLAN NOTES

T1 POWER ABOVE CEILING FOR ELECTRIC DOOR

RELEASE HARDWARE FOR CONNECTION TO BUILDING

ACCESS SYSTEM.

T6 PROVIDE AND INSTALL OUTLET AT THIS

APPROXIMATE LOCATION FOR POWER TO FLAT

SCREEN TV. COORDINATE EXACT INSTALLATION

HEIGHT WITH TECHNOLOGY.

06-06-2025 City Comments

07-23-2025 Addendum 2

08-07-2025 Addendum 3

ALL ELECTRICAL WORK TO

CONFORM TO 2017 NEC.

NOT FOR REGULATORY

APPROVAL, PERMITTING,

OR CONSTRUCTION

Engineer:

Date:

License No.:License State:

Tyler | Austin | Houston | El Paso

Texas Firm Registration No. F-893

Louisiana Firm Registration No. EF-5818 www.EMAengineer.com

EMA Engineering & Consulting, Inc.

DFW | San Antonio | Shreveport

SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE

CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB

CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING

AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND

WORKING SYSTEM.

HLH DESIGN BUILD, INC. RESERVES PROPRIETARY

RIGHTS, INCLUDING COPYRIGHTS, TO THIS

DRAWING AND THE DATA SHOWN THEREON. SAID

DRAWINGS AND/OR DATA ARE EXCLUSIVE

PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL

NOT BE USED OR REPRODUCED FOR ANY OTHER

PROJECT WITHOUT THE EXPRESS WRITTEN

APPROVAL AND PARTICIPATION OF HLH DESIGN

BUILD, INC. @2025 HLH DESIGN BUILDING, INC.

TBAE# BR3A65

P R

O

JE

C T:

O W

N E

R

A D

D R

E S

S

DATE REVISIONS

BY:

DATE:

c COPYRIGHT1 292 1403 001

Matthew A. Hensley

108637TX

REVIEW ONLY

8/7/2025 1:47:11 PM

EP8.1

ELECTRICAL PANEL

SCHEDULES

G R

E G

G C

O U

N T

Y

G R

E G

G C

O U

N T

Y P

R E

C

IN

C T

ARJ

06-06-2025

G

IL

M

E R

R D

L O

N G

V

IE

W

T X

[1

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

Water Heating 125.00% 6250 VA 5000 VA

Receptacles 65.79% 20835 VA 31671 VA

Power 100.00% 7441 VA 7441 VA Total Est. Demand: 289 A

NonLinear Tech 90.72% 14425 VA 15900 VA Total Conn.: 306 A

Motor 100.00% 3615 VA 3615 VA Total Est. Demand: 120060 VA

Lighting 125.00% 18909 VA 15127 VA Total Conn. Load: 127398 VA

HVAC 100.00% 49351 VA 49351 VA

Load Classification Demand Factor Estimated Demand Connected Load Panel Totals

Legend: Phase A,B,C values are in Amps.

41 SPACE 1 -- -- 0 A / 0 A -- -- 1 - 42

39 SPACE 1 -- -- 0 A / 0 A -- -- 1 - 40

37 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPD 38

35 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 36

33 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 34

31 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 32

29 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 30

27 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 28

25 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 26

23 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 24

21 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 22

19 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 20

17 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 18

15 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 16

13 -- -- -- -- 144 A / 0 A -- -- 1 SPARE 14

11 Panel L1 - w/Main CB 2 225 A #4/0 145 A / 0 A 12

9 SPARE 1 -- -- 0 A / 0 A 10

7 SPARE 1 -- -- 0 A / 174 A -- -- -- -- 8

5 -- -- -- -- 131 A / 234 A #4/0 225 A 2 Panel L2 - w/Main CB 6

3 -- -- -- -- 154 A / 0 A -- -- 1 SPARE 4

1 Panel AHAC - w/Main CB 3 225 A #4/0 127 A / 0 A -- -- 1 SPARE 2

# Load Name P Bkr Wire A B C Wire Bkr P Load Name #

% Imbalance - 70Notes:, ** See Riser Diagram for feeder info. **

Total Demand Load - 289 A

Fed From - UTIL TX Service - 120/240 3ph 4w Branch AIC - 18,000 AIC

Mount - Surface Mnt / NEMA 1Panel - MDP Bus - 400 A / MCB - 400 A In Room - ELEC 117

Total Est. Demand: 119 A

Total Conn.: 119 A

Total Est. Demand: 49351 VA

Total Conn. Load: 49351 VA

HVAC 100.00% 49351 VA 49351 VA

Load Classification Demand Factor Estimated Demand Connected Load Panel Totals

Legend: Phase A,B,C values are in Amps.

41 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 42

39 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 40

37 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 38

35 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 36

33 SPACE 1 -- -- 0 A / 0 A -- -- 1 SPACE 34

31 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 32

29 -- -- -- -- 12 A / 0 A -- -- 1 SPARE 30

27 AC-2T 30A DISC. & 20A FUSES 2 20 A #12 12 A / 0 A -- -- 1 SPARE 28

25 SPARE 1 -- -- 0 A / 0 A -- -- 1 SPARE 26

23 SPARE 1 -- -- 0 A / 15 A -- -- -- -- 24

21 -- -- -- -- 15 A / 15 A #12 20 A 2 RTU-2T #107 30A DISC. & 25A FUSES 22

19 RTU-2T #121 30 A DISC. & 30A FUSES 2 20 A #12 15 A / 0 A -- -- 1 SPARE 20

17 -- -- -- -- 18 A / 0 A -- -- 1 SPARE 18

15 -- -- -- -- 18 A / 8 A -- -- -- -- 16

13 RTU-3T #130 30A DISC. & 25A FUSES 3 20 A #12 18 A / 8 A #12 20 A 2 AC-1T 30A DISC. & 15A FUSES 14

11 -- -- -- -- 21 A / 26 A -- -- -- -- 12

9 -- -- -- -- 21 A / 26 A -- -- -- -- 10

7 RTU-4T #103 30A DISC. & 30A FUSES 3 30 A #10 21 A / 26 A #10 30 A 3 RTU-5T #118 60A DISC. & 40A FUSES 8

5 -- -- -- -- 18 A / 21 A -- -- -- -- 6

3 -- -- -- -- 18 A / 21 A -- -- -- -- 4

1 RTU-3T #128 30A DISC. & 25A FUSES 3 20 A #12 18 A / 21 A #10 30 A 3 RTU-4T #115 30A DISC. & 30A FUSES 2

# Load Name P Bkr Wire A B C Wire Bkr P Load Name #

% Imbalance - 18Notes:, ** See Riser Diagram for feeder info. **

Total Demand Load - 119 A

Fed From - MDP Service - 120/240 3ph 4w Branch AIC - 18,000 AIC

Mount - Surface Mnt / NEMA 1Panel - AHAC Bus - 225 A / MCB - 225 A In Room - ELEC 117

Water Heating 125.00% 6250 VA 5000 VA

Receptacles 94.11% 10668 VA 11336 VA Total Est. Demand: 198 A

Power 100.00% 4521 VA 4521 VA Total Conn.: 181 A

NonLinear Tech 100.00% 6000 VA 6000 VA Total Est. Demand: 47597 VA

Motor 100.00% 2535 VA 2535 VA Total Conn. Load: 43430 VA

Lighting 125.00% 18290 VA 14632 VA

Load Classification Demand Factor Estimated Demand Connected Load Panel Totals

Legend: Phase A,B,C values are in Amps.

53 GENERATOR BLOCK HEATER(FOR FUTURE) 1 20 A #12 2 A / ... -- -- 1 SPACE 54

51 WEATHERPROOF GP OUTLET(FOR FUTURE) 1 20 A #12 2 A / ... -- -- 1 SPACE 52

49 GENERATOR BATTERY CHARGER(FOR FUTURE) 1 20 A #12 2 A / 0 A -- -- 1 SPACE 50

47 GFCI OUTLET - BREAKROOM #127 1 20 A #12 3 A / 0 A -- -- 1 SPACE 48

45 UNDERCOUNTER ICE MACHINE - BREAKROOM #117 (ON GF... 1 20 A #12 11 A /... #12 20 A 1 REFRIGERATOR - BREAKROOM #127 (ON GFCI BREAKER) 46

43 REFRIGERATOR - BREAKROOM #127 (ON GFCI BREAKER) 1 20 A #12 10 A /... #12 20 A 1 DISPOSAL - BREAKROOM #127 (ON GFCI BREAKER) 44

41 DRINKING FOUNTAIN - BREAKROOM #127 (ON GFCI BREAKER) 1 20 A #12 7 A / ... #12 20 A 1 DISHWASHER - BREAKROOM #127 (ON GFCI BREAKER) 42

39 LIGHTING 1 20 A #12 11 A / 11 A #10 20 A 1 EXTERIOR SIGNAGE 40

37 EXTERIOR SIGNAGE 1 20 A #12 11 A / 11 A #12 20 A 1 EXTERIOR SIGNAGE 38

35 WATER HEATER W/ 60A DISC. & 50A FUSES 1 50 A #6 38 A / 2 A #12 20 A 1 GP OUTLETS - JANITOR #126 36

33 GP OUTLETS - OPEN OFFICE #119 1 20 A #12 6 A / 9 A #10 20 A 1 GP OUTLETS - SUPER OFF. #131 34

31 CIRCULATION PUMP & GP OUTLET 1 20 A #12 4 A / 8 A #12 20 A 1 FLOOR BOXES - COURTROOM #130 32

29 GP OUTLETS - MICHELLE #110 1 20 A #12 8 A / 3 A #12 20 A 1 GP OUTLETS - BREAKROOM #127 30

27 GP OUTLETS - OPEN OFFICE #119 1 20 A #12 5 A / 4 A #12 20 A 1 TV - COURTROOM #130 (FUTURE) 28

25 TV - BREAKROOM #127 1 20 A #12 4 A / 3 A #12 20 A 1 GP OUTLETS - STRG #106 26

23 GP OUTLETS - BREAKROOM #127 1 20 A #12 2 A / 5 A #12 20 A 1 GP OUTLETS - CORRIDOR 24

21 COPIER - OPEN OFFICE #119 1 20 A #8 13 A / 0 A #12 20 A 1 EXTERIOR CANOPY LIGHTING THRU CONTACTOR 22

19 EXTERIOR LIGHTING THRU CONTACTOR 1 20 A #12 7 A / 6 A #12 20 A 1 GP OUTLETS - RAY #104 20

17 EXTERIOR LIGHTING THRU CONTACTOR 1 20 A #12 0 A / 4 A #12 20 A 1 TV - RAY #104 18

15 GP OUTLETS - OPEN OFFICE #119 1 20 A #12 6 A / 3 A #12 20 A 1 GP OUTLETS - JUDGES STAND 16

13 EXTERIOR CANOPY LIGHTING THRU CONTACTOR 1 20 A #12 4 A / 4 A #12 20 A 1 TV - WAITING #103 14

11 EXTERIOR CANOPY LIGHTING THRU CONTACTOR 1 20 A #12 4 A / 8 A #12 20 A 1 GP OUTLETS - WAITING #103 12

9 TV - OPEN OFFICE #119 1 20 A #12 4 A / 4 A #12 20 A 1 TV - TIM #128 10

7 LIGHTING 1 20 A #12 4 A / 13 A #12 20 A 1 COPIER - WORKROOM #109 8

5 LIGHTING 1 60 A #4 42 A / 3 A #12 20 A 1 GP OUTLETS - CORRIDOR 6

3 GP OUTLETS - JP WAITING #118 1 20 A #12 5 A / 8 A #12 20 A 1 GP OUTLETS - TIM #128 4

1 LIGHTING 1 80 A #1 61 A / 2 A #12 20 A 1 GP OUTLETS - MENS RR #125 2

# Load Name P Bkr Wire A B C Wire Bkr P Load Name #

% Imbalance - 100Notes:, ** See Riser Diagram for feeder info. **

Total Demand Load - 198 A

Fed From - MDP Service - 120/240 1ph 3w Branch AIC - 18,000 AIC

Mount - Surface Mnt / NEMA 1Panel - L2 Bus - 225 A / MCB - 225 A In Room - ELEC 117

Receptacles 74.59% 15168 VA 20335 VA Total Est. Demand: 124 A

Power 100.00% 1675 VA 1675 VA Total Conn.: 145 A

NonLinear Tech 100.00% 9900 VA 9900 VA Total Est. Demand: 29656 VA

Motor 100.00% 2355 VA 2355 VA Total Conn. Load: 34700 VA

Lighting 125.00% 619 VA 495 VA

Load Classification Demand Factor Estimated Demand Connected Load Panel Totals

Legend: Phase A,B,C values are in Amps.

53 SPACE 1 -- -- 0 A / ... -- -- 1 SPACE 54

51 WEATHERPROOF OUTLET 1 20 A #12 2 A / ... -- -- 1 SPACE 52

49 DRIVE-THRU TUBING SYSTEM 1 20 A #12 15 A / 0 A -- -- 1 SPACE 50

47 GFCI OUTLETS - RR #102 1 20 A #12 2 A / 9 A #12 20 A 1 GP OUTLETS - TAX CLERKS #111 48

45 IT RACK 1 20 A #10 15 A /... #12 20 A 1 GP OUTLETS - ELEC ROOM #117 46

43 GP OUTLETS - TAX CLERKS #111 1 20 A #12 8 A / ... #12 20 A 1 GP OUTLETS - TAX CLERKS #111 44

41 GP OUTLETS - TAX CLERKS #111 1 20 A #12 8 A / ... #12 20 A 1 TV - JP WAITING #118 42

39 GP OUTLETS - SUPER OFF. #115 1 20 A #12 8 A / 13 A #12 20 A 1 PRINTER - DRIVE THRU #114 40

37 GP OUTLETS - TAX CLERKS #111 1 20 A #12 8 A / 3 A #12 20 A 1 DRIVE-THRU DEAL DRAWER 38

35 GFCI OUTLET - BREAKROOM #127 1 20 A #12 3 A / 4 A #12 20 A 1 TV - ROGER #107 36

33 GP OUTLETS - SERVICE AREA #116 1 20 A #12 5 A / 3 A #12 20 A 1 GP OUTLETS - CORRIDOR 34

31 GP OUTLET - WORKROOM #109 1 20 A #12 2 A / 3 A #12 20 A 1 IRRIGATION CONTROLLER - ELEC #117 32

29 GP OUTLETS - ENTRY #101 1 20 A #12 5 A / 2 A #12 20 A 1 GP OUTLET - WORKROOM #109 30

27 GP OUTLETS - TAX CLERKS #111 1 20 A #12 3 A / 3 A #12 20 A 1 GP OUTLETS - DRIVE THRU #114 28

25 DOOR ACCESS CONTROL 1 20 A #12 0 A / 3 A #12 20 A 1 GFCI OUTLET - BREAKROOM #127 26

23 GP OUTLETS - HALLWAY #120 / STORAGE #132 1 20 A #12 6 A / 5 A #12 20 A 1 GP OUTLETS - DRIVE THRU #114 24

21 WEATHERPROOF MAINTENCE OUTLET - EXTERIOR 1 20 A #10 11 A / 3 A #12 20 A 1 GP OUTLETS - DRIVE THRU #114 22

19 GP OUTLETS - IT #124 1 20 A #12 8 A / 8 A #12 20 A 1 FLOOR BOXES - CONFERENCE #121 20

17 -- -- -- -- 2 A / 4 A #12 20 A 1 TV - CONFERENCE ROOM #121 18

15 PARKING LOT LIGHTS THRU CONTACTOR 2 20 A #12 2 A / 15 A #10 20 A 1 IT RACK 16

13 GFCI OUTLETRS - UNISEX #122 1 20 A #12 6 A / 13 A #12 20 A 1 COPIER - TAX CLERKS #111 14

11 UNDERCOUNTER REFRIGERATOR WORKROOM #109 (ON... 1 20 A #12 10 A / 8 A #12 20 A 1 GP OUTLETS - CONFERENCE #121 12

9 GP OUTLETS - OPEN OFFICE #119 1 20 A #12 6 A / 11 A #12 20 A 1 GP OUTLET - STRG #113 10

7 GFCI OUTLETS - WMNS #123 1 20 A #12 7 A / 10 A #12 20 A 1 ERRS PANEL 8

5 GP OUTLETS - COURTROOM #130 1 20 A #12 8 A / 5 A #12 20 A 1 GP OUTLETS - WAITING #103 6

3 FANS-PATIO 1 20 A #12 1 A / 2 A #12 20 A 1 GP OUTLET - WORKROOM #109 4

1 DOOR ACCESS CONTROL 1 20 A #12 0 A / 8 A #12 20 A 1 GP OUTLETS - ROGER #107 2

# Load Name P Bkr Wire A B C Wire Bkr P Load Name #

% Imbalance - 100Notes:, ** See Riser Diagram for feeder info. **

Total Demand Load - 124 A

Fed From - MDP Service - 120/240 1ph 3w Branch AIC - 18,000 AIC

Mount - Surface Mnt / NEMA 1Panel - L1 Bus - 225 A / MCB - 225 A In Room - ELEC 117

07-23-2025 Addendum 2

08-07-2025 Addendum 3

GREGG COUNTY PRECINCT 2 - ELECTRICAL- IFP - 8-7-2025 - ADD 3.pdf
Sheets
EP1.1 - ELECTRICAL FLOOR PLAN
EP8.1 - ELECTRICAL PANEL SCHEDULES
ES1.1 - ELECTRICAL SITE PLAN

File details come from the government source that posted it. Updated .