These mechanical design documents are for the Gregg County Precinct 2 facility located at 800 Gilmer Road in Longview, Texas, prepared by EMA Engineering & Consulting, Inc. The project involves a comprehensive mechanical system renovation, including demolition and replacement of existing HVAC infrastructure. The documents detail the removal and replacement of multiple rooftop units (RTUs), exhaust fans, and air handling systems, with specific equipment including Lennox packaged roof top units ranging from 2 to 5 tons, split system units, and various exhaust and supply fans. The mechanical plans are 100% construction documents dated June 6, 2025, with engineering review completed on May 29, 2025.
The project specifications include detailed requirements for equipment installation, with specific emphasis on energy efficiency, ventilation standards, and code compliance using the 2012 International Mechanical Code. The proposed equipment features high-efficiency units with SEER ratings between 13.4 and 21, ECM motors, two-stage compressors, and advanced features like air ionizers, economizers, and BAS terminal strips. The mechanical design incorporates comprehensive notes on installation practices, including requirements for roof curb placement, refrigerant line routing, electrical connections, and coordination with other trades. The project appears to be fully funded and is part of a planned facility upgrade for Gregg County, with all mechanical systems being replaced to improve overall building performance and efficiency.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EF-
#2
EF-
#1
EF-
#3
CONTRACTOR TO DEMO ALL SUPPLY
AND RETURN DUCTWORK. CONTRACTOR
TO FIELD VERIFY EXACT LOCATIONS AND
QUANTITIES.
CONTRACTOR TO DEMO ALL SUPPLY
AND RETURN DIFFUSERS.
CONTRACTOR TO FIELD VERIFY EXACT
LOCATION, SIZE AND QUANTITY.
CONTRACTOR TO DEMO ALL EXHAUST
FANS AND EXHAUST RELIEF/LOUVERS.
CONTRACTOR TO PATCH OPENING AS
REQUIRED TO MATCH EXISTING
WALL/ROOF FINISHES. CONTRACTOR TO
FIELD VERIFY EXACT LOCATION, SIZE
AND QUANTITY.
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Javier Garcia
118760TX
REVIEW ONLY
5/29/2025 8:12:59 AM
MD1.1
MECHANICAL
DEMOLITION FLOOR
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
JM
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
MECHANICAL GENERAL NOTES
SEE SHEET MH7.1 FOR ALL GENERAL NOTES APPLICABLE TO ENTIRE
DRAWING SET
1/4" = 1'-0"
1 MECHANICAL DEMOLITION FLOOR PLAN
06-06-2025
06-02-2025
06-06-2025
06-06-2025
05-01-2025
RTU-3T
#1
RTU-5T
#2
RTU-3T
#3
MD1
MD1
MD1
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Javier Garcia
118760TX
REVIEW ONLY
5/29/2025 8:12:59 AM
MD1.6
MECHANICAL
DEMOLITION ROOF
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
JM
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
MECHANICAL GENERAL NOTES
SEE SHEET MH7.1 FOR ALL GENERAL NOTES APPLICABLE TO ENTIRE
DRAWING SET
1/4" = 1'-0"
1 MECHANICAL DEMOLITION ROOF PLAN
MECHANICAL DEMOLITION PLAN NOTES
MD1 REMOVE AND DISCARD EXISTING RTU AND ROOF CURB. PATCH
OVER OPENING ON ROOF FROM RTU.
06-02-2025
06-02-2025
06-06-2025
06-06-2025
CF-75
#102
CF-75
#125
CF-75
#126
CF-75
#122
RAY
ROGER
WAITING
ENTRY
SERVICE AREA
TAX CLERKS
ELEC
DRIVE THRU
WEB DEAL
SUPER OFF.
WORKROOM
CONFERENCE
JP WAITING
MICHELLE
JAN
MENS
IT
OPEN OFFICE
HALL
STRG
SUPER OFF.
TIM
BREAKROOM
COURT ROOM
WMNS
UNISEX
130 CFM
A-08
130 CFM
A-08
140 CFM
A-08
(TYP. 2)
140 CFM
A-08
(TYP. 2)
B-24/24
110 CFM
A-08
(TYP. 2)
110 CFM
A-08
(TYP. 2)
B-24/24
160 CFM
A-08
80 CFM
A-08
75 CFM
A-08
150 CFM
A-08
120 CFM
A-08
B-24/24
170 CFM
A-08
(TYP. 2)
B-24/24
185 CFM
A-08
200 CFM
A-08
140 CFM
A-08
220 CFM
A-08
(TYP. 2)
B-24/24
B-24/24
B-24/24
230 CFM
A-08
(TYP. 4)
B-24/24
B-24/24
275 CFM
A-10
(TYP. 4)
200 CFM
A-08
100 CFM
A-08
B-24/24
130 CFM
A-08
(TYP. 3)
B-24/24
B-24/24
8"ø
8"ø 8"ø
8"ø
B-24/24
8"ø
8"ø
18"x12" 10"ø
10"ø
12"x12"
125 CFM
A-10
(TYP. 2)
8"ø
B-24/24 10"ø
18"x12"
18"x12"
M5
8"ø 8"ø
14"x12"12"x12"12"ø10"ø
B-24/24
12"x12"
240 CFM
A-08
60 CFM
A-06
IF-300
#123
6"ø
200 CFM
A-08
8"ø
60 CFM
A-06
60 CFM
A-08
6"ø
6"ø
8"ø
200 CFM
A-08
8"ø
12"ø
12"x10"
M6
M6
14"x12"
75 CFM
A-06B-12/12
8"ø
B-24/24
8"ø
M6
M6
M6
140 CFM
A-08
150 CFM
A-08
B-24/24
8"ø
8"ø
20"x14"
250 CFM
A-08
8"ø
8"ø
8"ø
6"ø
B-24/24
B-24/24
8"ø
8"ø 10"ø
8"ø
8"ø
8"ø
8"ø
8"ø
8"ø
8"ø
8"ø10"ø
8"ø
10"ø
MS-AH-2T
#124
MS-AH-1T
#117
200 CFM
A-10
200 CFM
A-10
M6 20"x14" 24"x14"18"x12"
20"x14" B-24/24
B-24/24
M7
M7
B-24/24
M8
60 CFM
A-08
10"ø12"ø
10"ø
B-24/24 8"ø
6"ø
E-08
E-12
6"ø
M9
RTU-4T
#103
10"ø
RTU-4T
#115
RTU-2T
#121
RTU-3T
#128
RTU-5T
#118
RTU-3T
#130
12"ø 10"ø
PATIO FAN-1
PATIO FAN-2
16"x12"
S
S
RTU-2T
#107
6"ø
400 CFM
CA-8/4
DA-8/4
200 CFM
CA-8/4
8"ø
DA-8/4
8"ø 10"ø
B-24/24
8"ø
180 CFM
CA-8/4
180 CFM
CA-8/4
DA-8/4
T
T
T
T
T
T
T
CONTRACTOR TO COORDINATE WITH OWNER
ON EXACT THERMOSTAT AND FAN SWITCH
LOCATIONS.
8"ø
10"ø
10"ø
8"ø
8"ø 10"ø
10"ø
8"ø
18"x14"
14"x12"
20"x14"
16"x12"16"x12"
18"x14"
8"ø12"x12"
14"x12"
12"ø
10"ø
10"ø 6"ø
12"ø
8"ø
B-24/24 8"ø
6"ø
8"ø
12"x12"
B-24/24
M10
12"x12"
8"ø
12"ø
8"ø
10"ø
16"x12"
8"ø
B-24/24
M7
T
ROUTE DUCTWORK AS HIGH AND TIGHT TO
STRUCTURE AS POSSIBLE.
20"x14"
8"ø
M11
8"ø T
12"ø
ALL MECHANICAL WORK TO CONFORM WITH
2012 IMC SECTION 106.3.1.
M12
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Javier Garcia
118760TX
REVIEW ONLY
6/6/2025 11:03:54 AM
MH1.1
MECHANICAL FLOOR
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
JM
06-06-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
MECHANICAL GENERAL NOTES
SEE SHEET MH7.1 FOR ALL GENERAL NOTES APPLICABLE TO ENTIRE
DRAWING SET
MECHANICAL PLAN NOTES
M5 10"Ø DUCT DOWN TO RETURN GRILLE
M6 8"Ø DUCT DOWN TO SUPPLY DIFFUSER.
M7 8"Ø DUCT DOWN TO RETURN GRILLE
M8 12"Ø EXHAUST DUCT UP TO EXHAUST RELIEF ON ROOF.
M9 8"Ø EXHAUST DUCT UP TO EXHAUST RELIEF ON ROOF.
M10 6"Ø RETURN DUCT DOWN TO RETURN DIFFUSER.
M11 ADD ISOLATION CURB FOR RTU #130
M12 DUCT TO BE INTERNALLY LINED.
True
PROJECT
NORTH
3/16" = 1'-0"
1 MECHANICAL FLOOR PLAN
06-06-2025 City Comments
06-06-2025
06-06-2025
12' - 5"
RTU-4T
#103
RTU-4T
#115
RTU-2T
#121
RTU-2T
#107
RTU-3T
#130
RTU-5T
#118
RTU-3T
#128
MS-AC-1T
#117
MS-AC-2T
#124
E-12
E-08
M4
M4
M11
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Javier Garcia
118760TX
REVIEW ONLY
5/29/2025 8:13:03 AM
MH6.1
MECHANICAL ROOF
PLAN
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
JM
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
MECHANICAL GENERAL NOTES
SEE SHEET MH7.1 FOR ALL GENERAL NOTES APPLICABLE TO ENTIRE
DRAWING SET
MECHANICAL PLAN NOTES
M4 HOODED ROOF PENETRATION FOR REFRIGERANT LINES DOWN.
M11 ADD ISOLATION CURB FOR RTU #130
3/16" = 1'-0"
1 MECHANICAL ROOF PLAN
06-02-2025
06-02-2025
06-06-2025
06-06-2025
N.T.S.
ROOM SENSOR INSULATION
SENSOR MOUNTING
RTU with GAS PIPE, CONDENSATE, AND ELEC. WIRING
EXISTING CURB CAP
MINI-SPLIT CONDENSING UNIT SUPPORT
INSTALLATION CLEARANCES AROUND ELECTRICAL EQUIPMENT
N.T.S.
N.T.S.
N.T.S.
N.T.S.
N.T.S.
4'-0" MIN.
DEDICATED SPACE
WORK SPACE
ELECTRICAL
AREA
COORDINATE WITH
ELECTRICAL CONTRACTOR
STUFF FIBERGLASS
INSULATION IN THE
BACK BOX OF THE
ROOM SENSOR
ROOM
SENSOR
2 X 4 ELECTRICAL
J-BOX
GASKET ON
BACK OF SENSOR
44"
12" MIN.
FINISHED FLOOR
1/2" CONDUIT
TO ACCESSIBLE
FINISHED
CEILING LINE
LONG SWEEP
RADIUS BENDS
CONTROL WIRING
TO HVAC UNIT.
T
12"
AT LOCATIONS SIMILAR TO THIS ARRANGEMENT
ON MECHANICAL AND ELECTRICAL DRAWINGS,
PROVIDE TEMPERATURE SENSOR.
PROVIDE TEMPERATURE AND CO2 SENSORS.
ON MECHANICAL AND ELECTRICAL DRAWINGS,
AT LOCATIONS SIMILAR TO THIS ARRANGEMENT
ELECTRICAL DRAWINGS, PROVIDE
ARRANGEMENTS ON MECHANICAL AND
AT LOCATIONS SIMILAR TO THESE
TEMPERATURE/HUMIDITY AND CO2 SENSORS.
NOTES:
ELECTRICAL, MECHANICAL AND CONTROLS CONTRACTORS
MUST COORDINATE ALL REQUIREMENTS.
ALL CONDUIT AND BACKBOXES ARE FURNISHED AND
INSTALLED BY ELECTRICAL CONTRACTOR
ALL SENSORS, CONTROL WIRING AND ASSOCIATED DEVICES
ARE FURNISHED AND INSTALLED BY CONTROLS CONTRACTOR.
TEMPERATURE/HUMIDITY
CO2
1.
2.
3.
SENSOR
COORDINATE BACK
BOX QUANTITY AND
ORIENTATION WITH
EMCS AND HVAC
CONTRACTORS
SENSOR
ATTIC SPACE
30"
OPTIONAL MOUNTING ARRANGEMENT
ONLY WHEN THERE IS A DEVICE
CONFLICT ISSUE.
VERIFY WITH OWNER AND ENGINEER.
44"
C2 TH TH
C2
T
C2
H
T
C2
TH
C2
T
CO2
H
TO ACCESS PANEL.
JUNCTION BOX. DO NOT MOUNT
CONDUIT AND NEW WIRE TO
SWITCH WITH FUSES, NEW
PROVIDE NEW FUSED DISCONNECT
UNION
DIELECTRIC
6" MIN.
TO POWER SUPPLY
MAKE-UP WIRING
J-BOX SHEETMETAL
CONTROL WIRING MOUNTED
4"x4" JUNCTION BOX FOR
WIRE (#18 GA MIN) TO THERMOSTAT
BELOW ROOF - RUN NEW CONTROL
IN CONDUIT
VENT
BOX UP THROUGH CURB
TO NEW DISCONNECT ON
6" MIN.
PLUG
CONDENSATE
DRAIN
THIS LINE 1" LOWER
THAN OUTLET OF UNIT
CONDENSATE
LINE SUPPORT
THREADED
POWER SUPPLY WIRING -
ROOFTOP UNIT TO JUNCTION
GAS CUT-OFF VALVE
ROOFTOP CURB (FLASHING
BY ROOFING CONTRACTOR)
COMPRESSOR SECTION
ROOFTOP UNIT
GAS LINE SUPPORT
GAS LINE
(BELOW ROOF)
EXISTING JOISTS TO REMAIN
EXISTING CURB TO REMAIN
3/4" PLYWOOD 3/4" PLYWOOD
16 GA CONT RUNNER
15# FELT
15# FELT
MECHANICAL UNIT
CONT. CLEAT
4'-0" ± FIELD VERIFY
SECTION A
2 1/2" BATT INSULATION
2X4 FRAME, TOENAILED
INTO EXISTING CURB
CONTINUOUS 24 GA. GALV.
SHEET METAL CAP
NOTE:
SPUD BACK EXG. GRAVEL & REMOVE
TOP LAYER OF EXG. ROOF MEMBRANE
2'-0" BACK FROM OPENING, PATCH BACK
ROOF MEMBRANE TO MATCH EXISTING.
A
C.U.
ROOF DECK
NEOPRENE STRIP
ROOFING MATERIAL
WRAPPING NAILER CURB
SHEET METAL CAP
WOOD BLOCK
PROVIDE SEALANT
AROUND BOLT
HOODED ROOF
PENETRATION
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Javier Garcia
118760TX
REVIEW ONLY
5/29/2025 8:13:03 AM
MH7.1
MECHANICAL
DETAILS, NOTES,
AND SYMBOLS
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
JM
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
MECHANICAL GENERAL NOTES
1. MECHANICAL CONTRACTOR TO PROVIDE TO THE PLUMBING
CONTRACTOR THE RECOMMENDED AC MANUFACTURER'S DATA FOR
CONDENSATE TRAPS PER EACH TYPE OF UNIT.
2. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
REMOVAL OR ADJUSTMENT OF ALL HOLD DOWN BOLTS ON
COMPRESSORS AT HVAC EQUIPMENT TO ALLOW FOR PROPER
VIBRATION ISOLATION.
3. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
REMOVAL OF ALL ABANDONED SCREWS, PIPING, TAPE, PAPERS,
PACKING PRODUCTS, ETC.
4. ALL EQUIPMENT SHALL BE PROPERLY LABELED PER
SPECIFICATIONS.
5. CLOSE ALL OUTSIDE AIR DAMPERS UPON INSTALLATION AND KEEP
ALL OUTSIDE AIR DAMPERS CLOSED UNTIL THE "TEST AND BALANCE"
IS PERFORMED.
6. PROVIDE AND INSTALL MANUAL VOLUME CONTROL DAMPERS ON
SUPPLY AND RETURN BRANCH DUCT SERVING A DIFFUSER OR
REGISTER. ALL MANUAL DAMPERS INSTALLED ABOVE HARD CEILINGS
OR AT OTHER INACCESSIBLE AREAS SHALL BE SUPPLIED WITH A
CABLE OPERATED DAMPER EQUAL TO "YOUNG REGULATOR MODEL
830A-CC".
7. DUCT MOUNTED SMOKE DETECTORS SHALL BE FURNISHED BY THE
FIRE ALARM CONTRACTOR, INSTALLED BY THE MECHANICAL
CONTRACTOR, AND FINAL TIE-IN BY THE FIRE ALARM CONTRACTOR.
8. DUCT MOUNTED SMOKE DETECTORS SHALL BE FURNISHED BY THE
FIRE ALARM CONTRACTOR, INSTALLED BY THE MECHANICAL
CONTRACTOR, AND FINAL TIE-IN BY THE FIRE ALARM CONTRACTOR.
9. SEAL WITH FIRE RETARDING SEALANT AROUND PIPE THROUGH ANY
PENETRATION OF FIRE WALLS. REFER TO ARCHITECTURAL SHEETS
FOR FIRE WALLS.
10. ALL GRILLES ARE SHOWN IN APPROXIMATE LOCATION. FIELD VERIFY
PLACEMENT WITH CEILING GRID.
11. ALL DIFFUSERS/FLEX CONNECTIONS SHALL HAVE A RIGID METAL
ELBOW UNLESS COMING DIRECTLY DOWN FROM A UNIT OR HEIGHT
OF CEILING IS EXTREME. ALL FLEX DUCT TO HAVE AT LEAST ONE
SUPPORT STRAP.
12. THE SPACE AROUND DUCTS AND PENETRATING ITEMS OF SMOKE
PARTITION WALLS SHALL BE FILLED WITH AN IBC APPROVED
MATERIAL LIMITING THE FREE PASSAGE OF SMOKE.
13. ALL FAN CURBS TO BE INSTALLED LEVEL. PROVIDE SEAL BETWEEN
CURB AND ROOF.
14. COORDINATE WITH THE PLUMBING CONTRACTOR LOCATION OF ALL
SUPPLY FANS WITH PLUMBING VENTS. MAINTAIN 10'-0" MINIMUM
SEPARATION.
15. NO MECHANICAL EQUIPMENT THAT REQUIRES SERVICE (i.e. FANS, ROOFTOP UNITS, CONDENSERS, ETC.) ON ROOF SHALL BE CLOSER
THAN 10'-6" TO EDGE OF BUILDING.
16. THE MECHANICAL CONTRACTOR SHALL NOT INSTALL ANY ROOF
EQUIPMENT CLOSER THAN 5'-0" TO ANY ADJACENT WALLS,
EXPANSION JOINTS, AND/OR PARAPETS.
17. COORDINATE WITH THE PLUMBING CONTRACTOR LOCATION OF ALL
ROOFTOP UNITS WITH ALL PLUMBING VENTS. MAINTAIN 10'-0"
MINIMUM SEPARATION.
18. COORDINATE ALL UNITS, DUCTWORK, GRILLES, REFRIGERANT LINES
WITH ALL TRADES BEFORE INSTALLING.
19. MECHANICAL CONTRACTOR SHALL COORDINATE WITH THE ROOFING
CONTRACTOR ALL COUNTER FLASHING REQUIRED AT ROOF CURBS.
20. MECHANICAL CONTRACTOR SHALL COORDINATE WITH THE STEEL
ERECTOR AND ROOFING CONTRACTOR THE INSTALLATION OF ALL
ROOF MOUNTED EQUIPMENT.
21. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING
SLOPE OF STRUCTURAL STEEL TO ALLOW ROOF CURBS TO BE
INSTALLED LEVEL.
22. ALL ROOFTOP UNITS AND CURBS TO BE INSTALLED LEVEL. ROOFTOP
UNIT MFG. TO PROVIDE SEAL BETWEEN UNIT AND CURB.
23. MECHANICAL CONTRACTOR SHALL SUBMIT TO ARCHITECT /
ENGINEER REFRIGERANT LINE SET DESIGN AND ROUTING PER
MANUFACTURER FOR REVIEW BEFORE INSTALLATION BEGINS.
24. THE MECHANICAL CONTRACTOR SHALL APPLY ULTRA-VIOLET
PROTECTIVE COATING OVER REFRIGERANT INSULATION PER
MANUFACTURER.
THERMOSTAT/SENSOR (PER SPEC.)
CO2 SENSOR
HUMIDISTAT
THERMOSTAT/HUMIDISTAT
CFM (CUBIC FT. PER MIN.)
GRILLE TYPE
DUCT TYPE TAG
DENOTATION
RETURN AIR GRILLE
SUPPLY GRILLE
DUCT DETECTOR WITH CONTROL RELAY
FIRE DAMPER/SMOKE
FIRE DAMPER
MANUAL VOLUME DAMPER
SPIRAL DUCT
MOTORIZED DAMPER
MEDIUM PRESSURE DUCT
FLEX DUCT
MECHANICAL SYMBOLS
C2
T
H
TH
XX
D
M
FD SFD
ROUND
RECTANGULAR
RECTANGULAR
FLAT OVAL
ROUND
XX" x XX"
XX"/XX"
XX"Ø
FD SFD
NOTE: SOME SYMBOLS MAY NOT BE USED.
*BALANCING DAMPER SHALL BE NAILER SERIES 1021
OR EQUAL FOR AIR BALANCING
BALANCING DAMPER* BAL
CAP
MECHANICAL DEMOLITION GENERAL NOTES
1. CONTRACTOR TO VISIT SITE AND BE FAMILIAR WITH BUILDING
MECHANICAL AND ELECTRICAL LAYOUTS.
2. IF ASBESTOS IS FOUND CONTACT OWNER IMMEDIATELY. DO NOT
WORK IN ANY AREA SUSPECTED TO CONTAIN ASBESTOS.
3. ALL EXISTING EQUIPMENT SHOWN IN APPROXIMATE LOCATION.
FIELD VERIFY.
4. DO NOT RELEASE ANY REFRIGERANT TO ATMOSPHERE. DISPOSE OF
IN A LAWFUL MANNER.
5. ALL REUSED EXISTING MECHANICAL EQUIPMENT SHALL BE
INSPECTED AND CLEANED FOR PROPER OPERATION. CHANGE ALL
BELTS.
6. PROVIDE AND INSTALL A FIRE DAMPER WHERE NEW DUCTWORK
CROSSES AN EXISTING FIRE RATED WALL. IF ANY EXISTING
DUCTWORK CROSSES A NEW FIRE RATED WALL A FIRE DAMPER IS
TO BE PROVIDED AND INSTALLED.
7. ALL MATERIAL, EQUIPMENT, DUCTS, PIPE, ETC. TO BE REMOVED
SHALL BE DISPOSED OF OFF SITE IN A LEGAL AND LAWFUL MANNER.
8. ALL EXISTING FIRE DAMPERS OR SMOKE DAMPERS BEING REUSED
SHALL REMAIN IN PLACE AND OPERATIONAL.
9. IF EXISTING CEILING ARE TO REMAIN, REMOVE ONLY CEILING TILE
NECESSARY TO ACCOMPLISH DEMOLITION AND NEW WORK.
REMOVE AND REINSTALL ELECTRICAL, LIGHTING FIXTURES, FIRE
ALARM DEVICES, SPEAKERS, ETC. REPLACE ALL BROKEN TILES WITH
NEW TILES TO MATCH EXISTING WHERE REQUIRED. REUSE EXISTING
TILES.
10. CAP ANY UNUSED PIPE AT FLOOR, WALL, CEILING. REMOVE
MATERIAL NOT BEING REUSED.
11. WHERE REMOVING HVAC AND PIPING, PATCH ALL WALLS WITH 5/8
SHEET ROCK ON EACH SIDE OF WALL, PAINT TO MATCH.
12. LEAVE ANY DOMESTIC WATER HEATER IN PLACE AND OPERATIONAL.
13. LEAVE ALL EXISTING EXHAUST FANS IN PLACE AND OPERATIONAL
UNLESS DRAWINGS SHOW TO REPLACE OR ADD EXHAUST FANS.
14. LEAVE ALL GAS TO EXISTING RTU THAT HAVE GAS IN PLACE AND
OPERATIONAL UNLESS REPLACING UNIT.
15. REMOVE ALL CONDENSATE DRAIN PIPING FROM UNITS THAT ARE TO
BE REPLACED. EACH ROOFTOP UNIT HAS CONDENSATE PIPING.
16. AIR HANDLER(S) BEING REINSTALLED MUST MAINTAIN FILTER
ACCESS. COORDINATE FILTER ACCESS DOORS WITH STRUCTURE,
PIPING, ETC.
06-02-2025
06-02-2025
06-06-2025
06-06-2025
4'-0"
4'-O" MINIMUM ON ALL SIDES
(10'-0" TO ADJ. FLUES
AND PLUMBING VENTS)
4'-0"
4'-0"
DUCT TAKEOFF
SUPPLY DIFFUSER
OUTSIDE AIR BALANCING - ONE INTAKE BRANCH
CEILING EXHAUST FAN ROOF EXHAUST RELIEF ROOF UPBLAST EXHAUST FAN
FLASHING FOR ROOFTOP CURBSCLEARANCES FOR ROOFTOP UNITS
ROOFTOP UNIT SYSTEM
REFRIGERANT LINES IN WALL
REFRIGERANT LINE ABOVE CEILING SUPPORT
HOODED ROOF PENETRATION
N.T.S.
N.T.S.
N.T.S.
N.T.S. (NON RATED CEILING)
N.T.S.
N.T.S. (NOT FOR USE WITH KITCHEN HOOD)
N.T.S.
N.T.S
N.T.S.
N.T.S.
N.T.S.
N.T.S.
RECTANGULAR OR
RECTANGULAR DUCT
NOTCH
DUCTWORK
SHOE-TAP
SQUARE
PROFILE
BELL MOUTH
ROUND DUCT
VARIES
RECTANGULAR OR SQUARE
DUCTWORK
SPIN IN
VOLUME DAMPER
VOLUME DAMPER 1.
MANUAL DAMPER
ELBOW
7'-0" MAXIMUM
FLEX DUCT
CEILING DIFFUSER
T-BAR
SYSTEM
INSULATION BLANKET
OVER DIFFUSER
FLEX DUCT NOTES
2. INSTALL STRAIGHT.
FLEX DUCT 30 DEG. MAXIMUM.
HORIZONTAL DEFLECTION OF REDUCER
INSULATION BLANKET
OVER DIFFUSER
SYSTEM
T-BAR
REDUCER
FLEX DUCT
ADD SUPPORT AS REQUIRED TO
KEEP WEIGHT OFF CEILING GRID
SYSTEM, WITH A MINIMUM OF
3.
FLEX DUCT
7'-0" MAXIMUM
ONE HANGER EVERY 3'-0".
MAXIMUM ANGLE30°
ALL GRILLES ARE TO HAVE AN ELBOW
UNLESS CEILING IS TO HIGH OR DUCT-
4.
WORK DROPS DIRECTLY FROM A UNIT.
CEILING DIFFUSER
MANUAL DAMPER
MIN.
2'-0"
OUTSIDE AIR DUCT
RETURN
MANUAL BALANCING DAMPER
NO OPPOSED BLADE DAMPERS
WILL BE ALLOWED IN RETURN AIR GRILLE
2'-0"
MIN.
MOTORIZED DAMPERM1
M2
EXHAUST FAN
PROVIDE FLANGE ON FLEX
CONNECTOR TO BOLT TO
FAN BOX
CEILING
BOLT GRILLE, CEILING,
AND DUCT EXTENSION
FLANGE TOGETHER
DUCT EXTENSION WITH
MOUNTING FLANGE
FLEX
CONNECTION
ROUND EXHAUST DUCT
TO EXHAUST RELIEF
ON ROOF
SQUARE TO
ROUND TRANSITION
STRUCTURAL
SUPPORT FAN FROM
SPEED CONTROL
VIBRATION ISOLATORS
FROM FAN MANUFACTURER.
LOCATE ON SUPPORT PER
MANUFACTURE'S INSTRUCTIONS.
ROOF PLIES UNDER CURB
EXHAUST RELIEF
BACK DRAFT DAMPER
ROOF INSULATION
STEEL DECK
AND CONTINUATION
SEE PLANS FOR DUCT SIZES
JOIST
PLENUM
ROOF PLIES UNDER CURB
EXHAUST FAN
BACK DRAFT DAMPER
ROOF INSULATION
STEEL DECK
AND CONTINUATION
SEE PLANS FOR DUCT SIZES
JOIST
PLENUM
ROOFTOP UNIT BASE BOTTOM
INSULATION - ON ROOFTOP UNIT
18" ROOF CURB BY UNIT MFG.
RIGID INSULATION
BY ROOFING CONTRACTOR
ROOFTOP UNIT PANEL
NAILER STRIP
WITH CURB
COUNTER FLASHING
BY ROOFING
CONTRACTOR
CANT STRIP
BY ROOFING
CONTRACTOR
ROOFING MATERIAL
BY ROOFING
CONTRACTOR
OPENING IN ROOF
TO BE SIZE OF
DUCT PENETRATION
SEAL AROUND DUCT.
SOUND INSULATING MATERIAL
TO BE INSIDE CURB
12" MINIMUM
COORDINATE WITH
GENERAL CONTRACTOR
VARIES
TOP OF CURB LEVEL (ALL SHIMS ON BOTTOM)
SHIM HERE AS
REQUIRED
COORDINATE WITH
GENERAL CONTRACTOR
ROOFTOP UNIT
CONTRACTOR RESPONSIBLE FOR INCREASING
EQUIPMENT CLEARANCE AS NEEDED TO COMPLY WITH
MANUFACTURER RECOMMENDATIONS
SUPPLY
DUCT
CEILING
CONNECTORS
FLEX
RETURN
DUCT
GASKET BY
FIELD SUPPLIED
COUNTER FLASHING
MIN.
12"
DRAIN PAN
NAIL
ROOFTOP
UNIT
ROOFTOP UNIT
DUCT
CONTR.
MECH.
BOTTOM, NO SHIMS
ON TOP OF CURB
REMOVE ROOF DECK
ONLY AT SUPPLY
AND RETURN DUCT
PENETRATIONS
LEVEL CURBS FROMROOF CURB
12" MIN. FROM THE TOP OF
THE CURB TO THE TOP OF
THE ROOF. THIS DOES NOT
ACCOUNT FOR THE ROOF
DECKING AND INSULATION.
BOTTOM OF CURB TO BE
PLACED ON STEEL STRUCTURE
MIN.
2'-0"
PENETRATIONS IN ROOF
MEMBRANE TO BE EQUAL TO SIZE
OF DUCTWORK. ROOF
PENETRATIONS EQUAL TO THE SIZE
OF THE ROOF CURB ARE NOT
ALLOWED.
CONTRACTOR TO INSTALL
INTERNAL DUCT LINER FROM
THE BOTTOM OF THE DECK
FOR THE FIRST 2'-0" OF DUCT
FROM THE ROOFTOP UNIT.
SHEETROCK
FROM PENETRATING LINES
HORIZONTAL SECTION
OF STUD TO PREVENT
SHEETROCK SCREWS
STUDS (INSTALL
3 - 2'-0" O.C.)
LINES
REFRIGERANT
SECTION OF METAL
STUD SPANNING TWO INTERIOR
STUD
WALL
HANGER ROD
PIPE HANGER
TEFLON TY-WRAP
(TAPE WILL NOT BE
ALLOWED)
LIQUID LINE
INSULATED
SUCTION LINE
PVC SLEEVE SIZED
TO FIT HANGER
AND ACCEPT REFRIG.
LINES
6"
CAP TO BE WELDED
ROOF PENETRATIONS SHALL BE SIZED
IN 8" INCREMENTS WITH SEPARATE
COMPARTMENTS EVERY 8" INCHES.
TRATION.
OF HOODED ROOF PENE-
TO 1/2" BEYOND EXTERIOR
SLEEVE TO CONTINUE
METAL BASE OUT 6"
STRUCTURE
SUPPORT
NOTE:
FROM SHEET-METAL
PITCH PAN.
8"
6"
1'-0"
GROUT
NON-SHRINK
REMOVABLE
ATTACHMENT
BOLTS
POURABLE
SEALANT
FLANGE
CAP STOP
WATER TIGHT
45° TURN DOWN
AT END OF CAP CAP WITH SLOPE 1/4" PER FOOT
REMOVABLE 24 GAGE
ALL SEAMS FOR
ROOFING INSULATION
SECURE PIPES TO STRUCTURE BELOW
6" MIN. FROM THE TOP OF
THE CURB TO THE TOP OF
THE ROOF. THIS DOES NOT
ACCOUNT FOR THE ROOF
DECKING AND INSULATION.
BOTTOM OF CURB TO BE
PLACED ON STEEL STRUCTURE
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Javier Garcia
118760TX
REVIEW ONLY
5/29/2025 8:13:03 AM
MH7.2
MECHANICAL
DETAILS
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
JM
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
06-02-2025
06-02-2025
06-06-2025
06-06-2025 ventilation#IMC2012Comm_Ch04_Sec403.3 more than 10 percent air recirculated from these spaces (see Section 403.2.1, Items
2 and 4).
h. For nail salons, each nail station shall be provided with a source capture system capable of exhausting not less than 50 cfm per station.
ventilation#IMC2012Comm_Ch04_Sec403.3
Copyright © 2025 International Code Council, Inc., or its licensors (ALL RIGHTS RESERVED).
Accessed by Vincent LaTour on 05/27/2025 pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a violation of the federal copyright, and subject to civil and criminal penalties thereunder.
PDF from: http://codes.iccsafe.org/content/IMC2012Comm/chapter-4-ventilation#IMC2012Comm_Ch04_Sec403.3
Copyright © 2025 International Code Council, Inc., or its licensors (ALL RIGHTS RESERVED).
Accessed by Vincent LaTour on 05/27/2025 pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a violation of the federal copyright, and subject to civil and criminal penalties thereunder.
PDF from: http://codes.iccsafe.org/content/IMC2012Comm/chapter-4-ventilation#IMC2012Comm_Ch04_Sec403.3
Copyright © 2025 International Code Council, Inc., or its licensors (ALL RIGHTS RESERVED).
Accessed by Vincent LaTour on 05/27/2025 pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a violation of the federal copyright, and subject to civil and criminal penalties thereunder.
PDF from: http://codes.iccsafe.org/content/IMC2012Comm/chapter-4-
Copyright © 2025 International Code Council, Inc., or its licensors (ALL RIGHTS RESERVED).
Accessed by Vincent LaTour on 05/27/2025 pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Any Unauthorized reproduction or distribution is a violation of the federal copyright, and subject to civil and criminal penalties thereunder.
PDF from: http://codes.iccsafe.org/content/IMC2012Comm/chapter-4-
For SI: 1 cubic foot per minute = 0.0004719 m /s, 1 ton = 908 kg, 1 cubic foot per minute per square foot = 0.00508 m /(s · m ), °C = [(°F) -32]/1.8, 1 square foot = 0.0929 m .
a. Based upon net occupiable floor area.
b. Mechanical exhaust required and the recirculation of air from such spaces is prohibited (see Section 403.2.1, Item 3).
c. Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous.
d. Ventilation systems in enclosed parking garages shall comply with Section 404.
e. Rates are per water closet or urinal. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while occupied.
f. Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is designed to operate intermittently. The lower rate shall be permitted only where the exhaust system is designed to operate continuously while occupied.
g. Mechanical exhaust is required and recirculation is prohibited except that recirculation shall be permitted where the resulting supply airstream consists of not
Supermarkets 8 7.5 0.06 —
Sports and amusement
Disco/dance floors 100 20 0.06 —
Bowling alleys (seating areas) 40 10 0.12 —
Game arcades 20 7.5 0.18 —
Ice arenas without combustion engines — — 0.30 0.5
Gym, stadium, arena (play area) — — 0.30 —
Spectator areas 150 7.5 0.06 —
Swimming pools (pool and deck area) — — 0.48 —
Health club/aerobics room 40 20 0.06 —
Health club/weight room 10 20 0.06 —
Storage
Repair garages, enclosed parking garagesb, d — — — 0.75
Warehouses — — 0.06 —
Theaters
Auditoriums (see education) — — — —
Lobbies 150 5 0.06 —
Stages, studios 70 10 0.06 —
Ticket booths 60 5 0.06 —
Transportation
Platforms 100 7.5 0.06 —
Transportation waiting 100 7.5 0.06 —
Workrooms
Bank vaults/safe deposit 5 5 0.06 —
Darkrooms — — — 1.0
Copy, printing rooms 4 5 0.06 0.5
Meat processingc 10 15 — —
Pharmacy (prep. area) 10 5 0.18 —
Photo studios 10 5 0.12 —
Computer (without printing) 4 5 0.06 —
3 2 2
Physical therapy 20 15 — —
Recovery and ICU 20 15 — —
Hotels, motels, resorts and dormitories
Multipurpose assembly 5 0.06 —
Bathrooms/toilet—privateg — — 25/50f
Bedroom/living room 5 0.06 —
Conference/meeting 5 0.06 —
Dormitory sleeping areas 5 0.06 —
Gambling casinos 7.5 0.18 —
Lobbies/prefunction 7.5 0.06 —
Offices
Conference rooms 50 5 0.06 —
Office spaces 5 5 0.06 —
Reception areas 30 5 0.06 —
Telephone/data entry 60 5 0.06 —
Main entry lobbies 10 5 0.06 —
Private dwellings, single and multiple
Garages, common for multiple unitsb — — — 0.75
Garages, separate for each dwellingb — — — 100 cfm per car
Kitchensb — — — 25/100f
Living areasc
Based upon number of bedrooms. First bedroom, 2; each additional bedroom, 1
0.35 ACH but not
less than 15 cfm/person
Toilet rooms and bathroomsg — — — 20/50f
Public spaces
Corridors — — 0.06 —
Elevator car — — — 1.0
Shower room (per shower head) g — — — 50/20f
Smoking loungesb 70 60 — —
Toilet rooms — publicg — — — 50/70e
Places of religious worship 120 5 0.06 —
Courtrooms 70 5 0.06 —
Legislative chambers 50 5 0.06 —
Libraries 10 5 0.12 —
Museums (children’s) 40 7.5 0.12 —
Museums/galleries 40 7.5 0.06 —
Retail stores, sales floors and showroom floors
Sales (except as below) 15 7.5 0.12 —
Dressing rooms — — — 0.25
Mall common areas 40 7.5 0.06 —
Shipping and receiving — — 0.12 —
Smoking loungesb 70 60 — —
Storage rooms — — 0.12 —
Warehouses (see storage) — — — —
Specialty shops
Automotive motor-fuel dispensing stationsb
— — — 1.5
Barber 25 7.5 0.06 0.5
Beauty salonsb 25 20 0.12 0.6
Nail salons b, h 25 20 0.12 0.6
Embalming roomb — — — 2.0
Pet shops (animal areas) b 10 7.5 0.18 0.9
2012 IMC Code and Commentary (Mechanical)
CHAPTER 4: VENTILATION
TABLE 403.3
MINIMUM VENTILATION RATES
OCCUPANCY CLASSIFICATION
OCCUPANT
DENSITY
#/1000 FT2 a
PEOPLE
OUTDOOR
AIRFLOW RATE IN
BREATHING
ZONE,
Rp CFM/PERSON
AREA OUTDOOR
AIRFLOW RATE IN
BREATHING
ZONE,
Ra CFM/FT 2 a
EXHAUST
AIRFLOW RATE
CFM/FT2 a
Correctional facilities
Cells without plumbing fixtures 25 5 0.12 — with plumbing fixturesg 25 5 0.12 1.0
Dining halls
(see food and beverage service)
Guard stations 15 5 0.06 —
Day room 30 5 0.06 —
Booking/waiting 50 7.5 0.06 —
Dry cleaners, laundries
Coin-operated dry cleaner 20 15 — —
Coin-operated laundries 20 7.5 0.06 —
Commercial dry cleaner 30 30 — —
Commercial laundry 10 25 — —
Storage, pick up 30 7.5 0.12 —
Education
Auditoriums 150 5 0.06 —
Corridors (see public spaces) — — — —
Media center 25 10 0.12 —
Sports locker roomsg — — — 0.5
Music/theater/dance 35 10 0.06 —
Smoking loungesb 70 60 —
Day care (through age 4) 25 10 0.18 —
Classrooms (ages 5-8) 25 10 0.12 —
Classrooms (age 9 plus) 35 10 0.12 —
Lecture classroom 65 7.5 0.06 —
Lecture hall (fixed seats) 150 7.5 0.06 —
Art classroomg 20 10 0.18 0.7
Science laboratoriesg 25 10 0.18 1.0
Wood/metal shopsg 20 10 0.18 0.5
Computer lab 25 10 0.12 —
Multiuse assembly 100 7.5 0.06 —
Locker/dressing roomsg — — — 0.25
Food and beverage service
Bars, cocktail lounges 100 7.5 0.18 —
Cafeteria, fast food 100 7.5 0.18 —
Dining rooms 70 7.5 0.18 —
Kitchens (cooking) b — — — 0.7
Hospitals, nursing and convalescent homes
Autopsy roomsb — — — 0.5
Medical procedure rooms 20 15 — —
Operating rooms 20 30 — —
Patient rooms 10 25 — —
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Javier Garcia
118760TX
REVIEW ONLY
6/6/2025 11:03:54 AM
MH7.3
MECHANICAL
DETAILS
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
JM
06-06-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
06-06-2025 City Comments
06-06-2025
06-06-2025
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
Date:
License No.:License State:
Tyler | Austin | Houston | El Paso
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818 www.EMAengineer.com
EMA Engineering & Consulting, Inc.
DFW | San Antonio | Shreveport
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
HLH DESIGN BUILD, INC. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWINGS AND/OR DATA ARE EXCLUSIVE
PROPERTY OF HLH DESIGN BUILD, INC. AND SHALL
NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF HLH DESIGN
BUILD, INC. @2025 HLH DESIGN BUILDING, INC.
TBAE# BR3A65
P R
O
JE
C T:
O W
N E
R
A D
D R
E S
S
DATE REVISIONS
BY:
DATE:
c COPYRIGHT1 292 1403 001
Javier Garcia
118760TX
REVIEW ONLY
5/29/2025 8:13:04 AM
MH8.1
MECHANICAL
SCHEDULES
G R
E G
G C
O U
N T
Y
G R
E G
G C
O U
N T
Y P
R E
C
IN
C T
JM
05-29-2025
G
IL
M
E R
R D
L O
N G
V
IE
W
T X
[1
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
DESIGN
MANUFACTURER
AIR IONIZER SCHEDULE
MODEL
MINIMUM
CFM
MAXIMUM
CFM REMARKS | PROVIDE
PHENOMENAL
AIRE
C6 0 6,000 UL 2998 CERTIFIED, SELF CLEANING, 24V POWER
RTU REMARKS | PROVIDE
1. 2" FILTER RACK WITH MERV 8 FILTERS
2. ROOF CURB
3. HAIL COIL GUARD
4. MOTORIZED MODULATING OUTSIDE AIR DAMPER
5. CRANKCASE HEATER
6. FREEZE THERMOSTAT
7. A2L REFRIGERANT
8. TWO STAGE COMPRESSOR
9. MULTIPLE COMPRESSORS
10. ECM OR VFD ON SUPPLY FAN
11. HINGED ACCESS DOORS
12. FUSED DISCONNECT BY EC
13. BAS TERMINAL STRIP
14. AIR IONIZER
15. ECONOMIZER WITH F.D.D.
16. BAROMETRIC RELIEF
17. HOT GAS REHEAT
18. CONVIENCE OUTLET POWERED BY EC
FAN REMARKS | PROVIDE
1. EC MOTOR WITH MOUNTED SPEED CONTROLLER FOR BALANCING ONLY 5. BACKDRAFT DAMPER
7. WHITE ALUMINUM GRILLE
6. HANGING ISOLATOR KIT 10. 18" HIGH ROOF CURB
9. BIRD SCREEN
4. FACTORY MOUNTED NON-FUSED DISCONNECT
2. EC MOTOR FOR CONNECTION TO EMCS (CONTROLLER & TRANSFORMER BY CONTROLS CONTRACTOR)
8. BOLTED ACCESS PANELS
13. ACID RESISTANT
11. 24" HIGH VENTED ROOF CURB
14. SOFT STARTER OR VFD FOR MOTOR
3. EC MOTOR FOR CONNECTION TO HOOD (CONTROLLER & TRANSFORMER BY KITCHEN CONTRACTOR)
12. GREASE CAPTURE AND CONTAINMENT
DX COOLING / GAS HEATING
PACKAGED ROOF TOP UNIT SCHEDULE
RTU MARKS
DESIGN
MANUFACTURER MODEL TONS
SEER2 |
IEER
E.S.P.
(IN.
W.C.)
FAN CFM
OUTSIDE
AIR CFM
DX COOLING HEAT
INPUT
(MBTUH)
ELECTRICAL UNIT
WEIGHT
(LBS) REMARKS | PROVIDE RTU TAGS
HIGH
SPEED
LOW
SPEED
TOTAL
(MBTUH)
SENSIBLE
(MBTUH) VOLT. PHASE MCA MOCP
RTU-2T LENNOX LGX024S5E 2T 13.4 0.5 800 600 100 24 15 65 240 V 1 19 A 25 A 800 1, 2, 3, 4, 5, 6, 7, 8, 10, 11, 12, 13, 14,16 107, 121
RTU-3T LENNOX LGT036H5E 3T 17.5 0.5 1,200 800 150 36 21 65 240 V 3 19 A 25 A 800 1, 2, 3, 4, 5, 6, 7, 8, 10, 11, 12, 13, 14,16 128, 130
RTU-4T LENNOX LGT048H5E 4T 17.3 0.5 1,600 1,000 200 49 29 65 240 V 3 23 A 30 A 800 1, 2, 3, 4, 5, 6, 7, 8, 10, 11, 12, 13, 14,16 103, 115
RTU-5T LENNOX LGT060H5E 5T 16.4 0.5 1,990 1,300 200 60 37 65 240 V 3 28 A 40 A 800 1, 2, 3, 4, 5, 6, 7, 8, 10, 11, 12, 13, 14,16 118
FAN SCHEDULE
FAN MARKS
DESIGN
MANUFACTURER MODEL
E.S.P.
(IN.
W.C.) FAN CFM
ELECTRICAL
SONES
WEIGHT
(LBS)
FAN
CONTROL
FAN SYSTEM
TYPE REMARKS | PROVIDE M_TAGSVOLT. PHASE
HP |
WATTS
CF-75 COOK GCVF-100 0.25 75 120 V 1 7.28 W 1.5 25 LIGHTS EXHAUST 1, 5, 6, 7 102, 122, 125, 126
IF-300 COOK 100SQN17DH (VF) 0.5 300 120 V 1 1/8 HP 6.6 65 LIGHTS EXHAUST 2, 4, 5, 6, 8 123
SMALL CAPACITY SPLIT SYSTEM SCHEDULE
MS MARKS
DESIGN
MANUFACTURER MODEL TONS SEER EER
FAN CFM COOLING
CAPACITY
(MBTUH)
ELECTRICAL UNIT
WEIGHT
(LBS) REMARKS | PROVIDE MS TAGS
HIGH
SPEED
LOW
SPEED VOLT. PHASE MCA MOCP
MS-AH-1T LG KNSAC121A 1 20 12.3 450 200 24 V 1 25
POWERED FROM AC UNIT, WALL UNIT, CONDENSATE PUMP, WIRED
SENSOR
MS-AC-1T LG KUSAC121A 1 11 240 V 1 10 A 15 A 75 HAIL COIL GUARD, MAX REF. PIPE LENGTH 49'-0", MAX ELEVATION 23'-0" 117
MS-AH-2T LG KNSAC241A 2 20 12.3 650 370 24 V 1 30
POWERED FROM AC UNIT, WALL UNIT, CONDENSATE PUMP, WIRED
SENSOR
MS-AC-2T LG KUSAC241A 2 21 240 V 1 15 A 20 A 100 HAIL COIL GUARD, MAX REF. PIPE LENGTH 65'-0", MAX ELEVATION 33'-0" 124
GRILLE SCHEDULE
GRILLE
MARKS
DESIGN
MANUFACTURE MODEL DESCRIPTION MATERIAL FINISH MODULE SIZE NECK SIZE REMARKS | PROVIDE
A-06 PRICE SCD
CEILING SUPPLY
DIFFUSER
STEEL WHITE 12" x 12" 06" Ø CONCEALED FASTENERS
A-08 PRICE SCD
CEILING SUPPLY
DIFFUSER
STEEL WHITE 24" x 24" 08" Ø
A-10 PRICE SCD
CEILING SUPPLY
DIFFUSER
STEEL WHITE 24" x 24" 10" Ø
B-12/12 PRICE 80
CEILING RETURN
GRILLE
ALUMINUM WHITE 12" x 12" PER PLANS PROVIDE ROUND ADAPTER AS NECESSARY,CONCEALED FASTENERS
B-24/24 PRICE 80
CEILING RETURN
GRILLE
ALUMINUM WHITE 24" x 24" PER PLANS PROVIDE ROUND ADAPTER AS NECESSARY
CA-8/4 PRICE 620L
SIDEWALL SUPPLY
GRILLE
ALUMINUM WHITE 8" x 4" 8" x 4"
HORIZONTAL FRONT BLADES, COORDINATE EXACT MOUNTING
HEIGHT WITH ARCHITECT, CONCEALED FASTENERS
DA-8/4 PRICE 630L
SIDEWALL RETURN
GRILLE
ALUMINUM WHITE 8" x 4" 8" x 4"
HORIZONTAL FRONT BLADES, COORDINATE THE EXACT MOUNTING
HEIGHT WITH ARCHITECT,CONCEALED FASTENERS
E-08 COOK PR-08
EXHAUST RELIEF | OA
INTAKE
ALUMINUM - 08 8" x 8" ROOF CURB, BACKDRAFT DAMPER
E-12 COOK PR-12
EXHAUST RELIEF | OA
INTAKE
ALUMINUM - 12 12" x 12" ROOF CURB, BACKDRAFT DAMPER
CEILING FAN SCHEDULE
MANUFACTURER
MODEL REMARKS | PROVIDE
PATIO FAN-1,
PATIO FAN-2
50W COLOR BY ARCH, MOUNTING KIT
TAGS
MOTOR
HP/W
VOLTAGE/
PHASE
CONTROL
SWITCHVISUAL COMFORT
& CO.
5LD044BZ
120/1
06-02-2025
06-02-2025
06-06-2025
06-06-2025
| Sheets |
| MD1.1 - MECHANICAL DEMOLITION FLOOR PLAN |
| MD1.6 - MECHANICAL DEMOLITION ROOF PLAN |