This document is a detailed product submittal for an ASCO Power Technologies automatic transfer switch (ATS) for Pilkington Construction. The submittal provides comprehensive technical specifications for a Series 300 Transfer Switch, model D03ATSA30230NG0C, featuring 230 amps, 3-pole configuration, 480V/60Hz service voltage, and an open transition type. Key technical details include a Type 1 enclosure, solid neutral configuration, front accessible design, and compatibility with UL 1008 standards.
The document extensively covers the transfer switch's features, including advanced Group G controller capabilities with multiple configurable time delays, remote monitoring options via the 72EE Connectivity Module, and optional accessories like load current metering, engine exerciser, and communication interfaces. The submittal also includes a 24-month limited warranty with optional extended warranty coverage up to 5 years, emphasizing the product's reliability across various industries such as telecommunications, agriculture, retail, and municipal services. The technical documentation provides detailed performance ratings, dimensional specifications, and comprehensive electrical and operational characteristics.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lara Kirkland ASCO Power Technologies
4891 Independence St.
Suite 210
Wheat Ridge CO 80033 United States
Tel # (720) 638-2696 Lara.Kirkland@ascopower.com
October 6, 2020 www.ascopower.com | customercare@ascopower.com 800.800.ASCO | 160 Park Avenue, Florham Park NJ 07932
PILKINGTON CONSTRUCTION
TRANSFER SWITCH SUBMITTAL
REVISION 00
FOR INFORMATIONAL PURPOSES ONLY
mailto:Kevin.Chmielewski@ascopower.com http://www.ascopower.com/ mailto:customercare@ascopower.com
PILKINGTON CONSTRUCTION
Bill of Materials
Reference Quote: K2-20-353420-1-1
Sales Order: N/A
ATS Withstand and Closing Ratings
NOTES:
1) All WCR values indicated are tested in accordance with the requirements of UL 1008, 7th Edition.
2) Application requirements may permit higher WCR for certain switch sizes.
3) Short Time ratings are provided for applications involving circuit breakers that utilize trip delay settings for system selective coordination
ATS
NAME
QTY
AMPS/
POLES
BYPASS
TRANSITION
TYPE
CATALOG
NUMBER
ACCESSORIES
OUTLINE
DRAWING
WIRING
DIAGRAM
BOM NUMBER
- 1 230 / 3 NO OPEN D 3ATS A3 230 NGC STANDARD 978723-001 978741 1007108
300, 4000 & 7000 Series 300, 4000 & 7000 Series 7000 Series
ATS NAME FRAME
SIZE
Switch Rating (Amps) Current Limiting Fuses Specific Breaker Time Based Short Time Ratings3 (sec)
Transfer
Switches Bypass Switches
480V Max. 600V Max.
480V
Max.
600V
Max.
Max Size, A Class 240V
Max.
480V
Max.
600V
Max.
Time
(sec)
240V
Max.
480V
Max.
600V
Max. .13 .2 .3 .5 .1 .13 .3 .5
- D 230 - 100kA - 300 J 65kA 25kA - 0.025 10kA 10kA - - -
FOR INFORMATIONAL PURPOSES ONLY
Transfer Switch Details
ATS AMPS: 0230 QTY: 1
Product : Series 300 Transfer Switches Catalog Number : D03ATSA30230NG0C
Service Voltage / Hz : 480V/60Hz Optional Accessories :
Bypass Isolation : Not Applicable Product Description :
300 Series, Automatic Open Transition Transfer Switch
Switched Poles : 3 Neutral Configuration : Solid [A]
Withstand Rating :
Please refer to WCR chart
Frame = D, Switch Rating = 0230
Cables and Lug Sizes : 1, #14 to 4/0 AWG
Enclosure : 1(C) Type 1 Enclosure Service : Three Phase, 4-wire
Extended Warranty : Not Included Markings :
ASCO
ASCO
®FOR INFORMATIONAL PURPOSES ONLY
DENNIS
Text Box
D03ATSA30230NG0C
ASCO
ENGINE CONTROL CONTACTS
LOAD DISCONNECT FEATURE
COMMON ALARM & NOT IN AUTO SIGNALING FEATURES
INPHASE TRANSFER FEATURE FOR LOAD TRANSFER
SOURCE AVAILABILITY SIGNALS
EXTERNAL POWER SUPPLY COMPATIBILITY
LOAD CURRENT METERING
NON-AUTOMATIC (MANUAL) OPERATION
REMOTE CONTROL FEATURES
ADVANCED-FUNCTION SOFTWARE BUNDLE
FOR INFORMATIONAL PURPOSES ONLY
DENNIS
Text Box
D03ATSA30230NG0C
Publication 3223 3-28-17
Limited Warranty
Series 150, 200, 300 and 4000 Series Power Transfer Switches
This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser's business.
General:
ASCO Power Technologies, LP products and systems are in our opinion the finest available. We take pride in our products and are pleased you have chosen them. Under certain circumstances we offer with our products the following Twenty Four Month Limited Warranty Against Defects in Material and Workmanship.
Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain performance under this Warranty.
TWENTY FOUR MONTH LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP ASCO PRODUCTS COVERED:
Product Description Series Catalog Code
150, 200 1ATS, 2ATS
Automatic Transfer Switch 300 3ATS, 3ADTS
4000 4ATS, 4ADTS, 4ACTS
Non Automatic Transfer Switch (Electrically Operated)
300 3NTS, 3NDTS
4000 4NTS, 4NDTS, 4NCTS
Manual Transfer Switch 300 3MTS
Service Entrance Transfer Switch (SEATS) 300 3AUS, 3ADUS, 3APS, 3ARS
Power Transfer Load Center (PTLC) 300 300L
Quick Contact Panels 300 3QC
LIMITED WARRANTY:
ASCO warrants that the ATS will be free from defects in material and workmanship and will conform to ASCO’s standard specifications for the ATS for a period of twenty four (24) months from date of product shipment from ASCO (the “Warranty Period”). This Limited Warranty does not extend to subsequent owners of the structure during the Warranty Period.
Terms of Warranty:
The foregoing Limited Warranty is conditioned upon User’s compliance with the following:
1. The ASCO Power Transfer Switch is installed in accordance with ASCO specifications and state and local codes and standards by an electrician licensed in the state of installation.
2. The ASCO Power Transfer Switch is maintained in accordance with ASCO instructions and used under normal conditions for the purposes intended by ASCO.
All warranty field-related repairs, replacements or adjustments must be made by ASCO Services Inc. or its duly authorized representative.
Optional Available Extended Warranty
Optional extended warranty coverage may be purchased from ASCO for a specified fee at the time of the original sale. If purchased, warranty period shall be extended up to an additional thirty - six (36) months beyond the standard twenty - four (24) months to provide up to five (5) year coverage applicable to the above referenced products, except for 3AUS, 3APS, and 3ARS products where the warranty period for the circuit breaker shall be limited to 24 months from date of shipment from ASCO. The length of optional extended coverage shall be reflected on the ASCO invoice and/or order acknowledgement document.
Warranty Extends to First Purchaser for Use, Non-transferable:
This Warranty is extended to the first person, firm, association or corporation for whom the ASCO product specified herein is originally installed for use (the "User") in the fifty United States or Canada. This Warranty is not transferable or assignable without the prior written permission of ASCO.
Assignment of Warranties:
ASCO assigns to User any warranties which are made by manufacturers and suppliers of components of, or accessories to, the ASCO product and which are assignable, but ASCO makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to such components or accessories.
Drawings, Descriptions:
ASCO warrants for the period and on the terms of the Warranty set forth herein that the ASCO product will conform to the descriptions contained in the certified drawings, if any, applicable thereto, to ASCO's final invoices, and to applicable ASCO product brochures and manuals current as of the date of product shipment (“Descriptions”). ASCO does not control the use of any ASCO product. Accordingly, it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A
PARTICULAR PURPOSE.
Warranty Claims Procedure:
Within a reasonable time, but in no case to exceed thirty (30) days, after User's discovery of a defect, User shall contact ascopowerwarranty@ascopower.com. Subject to the limitations specified herein, an ASCO Services field service representative will repair the non-conforming ASCO product warranted hereunder, without charge for parts, labor, or travel expenses. Warranty coverage will apply only after ASCO's inspection discloses the claimed defect and shows no signs of treatment or use that would void the coverage of this Warranty .
All defective products and component parts replaced under this warranty become the property of mailto:ascopowerwarranty@emerson.com
ASCO.
Warranty Performance of Component Manufacturers:
It is ASCO's practice, consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible, to cooperate with and utilize the services of component manufacturers and their authorized representatives in the performance of work to correct defects in the product components. Accordingly, ASCO may utilize third parties in the performance of Warranty work, including repair or replacement hereunder, where, in ASCO's opinion, such work can be performed in less time, with less expense, or in closer proximity to the ASCO product.
Items Not Covered By Warranty:
THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or connection, negligence, inappropriate on site operating conditions, repair by non-ASCO designated personnel, accident in transit, tampering, alterations, a change in location or operating use, exposure to the elements, water, or other corrosive liquids or gases, Acts of God, theft or installation contrary to ASCO's recommendations or specifications, or in any event if the ASCO serial number has been altered, defaced, or removed.
THIS WARRANTY DOES NOT COVER shipping costs, installation costs, external circuit breaker resetting or maintenance or service items and further, except as may be provided herein, does NOT include labor costs or transportation charges arising from the replacement of the ASCO product or any part thereof or charges to remove or reinstall same at any premises of User.
REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES
NOT EXTEND THE ORIGINAL WARRANTY PERIOD.
THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT FOR USE IN THE
CONTROL AREA OR ANY REACTOR CONNECTED OR SAFETY APPLICATIONS OR
WITHIN THE CONTAINMENT AREA OF A NUCLEAR FACILITY OR FOR
INTEGRATION INTO MEDICAL DEVICES.
Limitations:
THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE.
USER'S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE ASCO
PRODUCT AS SET FORTH HEREIN.
IF USER'S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A
COURT OF COMPETENT JURISDICTION, ASCO'S RESPONSIBILITY FOR PROPERTY
LOSS OR DAMAGE SHALL NOT EXCEED THE NET PRODUCT PURCHASE PRICE.
IN NO EVENT SHALL ASCO ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL,
INCIDENTAL, CONSEQUENTIAL OR EXEMPLARY DAMAGES OF ANY KIND
WHATSOEVER, INCLUDING WITHOUT LIMITATION LOST PROFITS, BUSINESS
INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED UPON
THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT, OR
OTHERWISE.
Miscellaneous:
NO SALESPERSON, EMPLOYEE OR AGENT OF ASCO IS AUTHORIZED TO ADD TO
OR VARY THE TERMS OF THIS
WARRANTY. Warranty terms may be modified, if at all, only in writing signed by an ASCO officer.
ASCO obligations under this Warranty are conditioned upon ASCO timely receipt of full payment of the product purchase price and any other amounts due. ASCO reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others.
In the event that any provision of this Warranty should be or becomes invalid and/or unenforceable during the warranty period, the remaining terms and provisions shall continue in full force and effect.
This Warranty shall be governed by, and construed under, the laws of the State of New Jersey, without reference to the conflict of laws principles thereof.
This Warranty represents the entire agreement between ASCO and User with respect to the subject matter herein and supersedes all prior or contemporaneous oral or written communications, representations, understandings or agreements relating to this subject.
ASCO SERIES 300
Power Transfer Switches ascopower.com
Where would you be without a constant flow of electrical power? We often take for granted that power will always be around when we need it.
In reality, power failures are common, and when the power goes out, your business suffers. Power failures are unpredictable. They can occur at any time and for any number of reasons — a bolt of lightning, a power surge, a blackout, an accident or even equipment failure. They come without warning and often at the most inconvenient times.
It’s for this reason that many businesses and other entities have invested in emergency power backup systems. Typically, the system consists of an engine generator and an automatic transfer switch (ATS) that transfers the load from the utility to the generator.
An ATS with built-in control logic monitors your normal power supply and senses interruptions and unacceptable abnormalities. When the utility power fails, the ATS automatically starts the engine generator and transfers the load after the generator has reached proper voltage and frequency. This happens in a matter of seconds after the power failure occurs. When the utility power has been restored, the ATS will automatically switch the load back and, after a time delay, shut down the engine generator. With an ATS, you are protected 24 hours a day, seven days a week.
ASCO SERIES 300 Power Transfer Switches for Power Outage Protection
24-hour protection, no matter when trouble strikes
In the telecommunication industry, providing a high level of service and dependability is crucial. Lost power means an interruption in service for your customers and lost business for your company. For instance, with cell sites scattered across a wide geographical region and in many remote areas, the chances of an interruption in power are increased, making an ATS valuable resource at each location.
To maintain dependable service, each cell site must be monitored 24 hours a day. This can be very difficult without some type of remote monitoring and testing capability. The SerieS 300 Transfer Switch, combined with ASCO’s monitoring and control management system, is a cost-effective, packaged solution that can achieve both of these challenging objectives without a major investment at each cell site.
With ASCO’s connectivity solutions, you can remotely monitor and control numerous sites from around the corner or across the world.
Maintaining electrical power is vital to an agriculture operation. If the flow of power is interrupted, your operation will be at risk unless the backup generator is quickly activated. A prolonged power outage can affect numerous aspects of the operation, from housing and feeding livestock to processing and producing the end product.
With an ASCO SerieS 300 Transfer Switch, power will automatically be transferred over to your backup generator, eliminating the need to manually switch from utility to generator. When power is restored, the ASCO SerieS 300 Transfer Switch will, after an adjustable time delay to allow for utility stabilization, automatically switch the load back to the utility service.
The retail industry is very competitive. An electrical power failure can have a dramatic impact on a retailer’s bottom line. If power is interrupted during peak shopping times, the effect can be extremely damagin to present and future business.
A power interruption will not only suspend shopping, it can also create safety problems, result in lost transaction data, lost account information and possible damage to data collection equipment. In addition, retailers who rely on controlled climates to protect valuable inventory could suffer even greater losses, especially if the power failure occurs at a time when no one is available to rectify the situa-tion. To avoid any of these power outage problems, simply install a backup generator with an ASCO SerieS 300 Transfer Switch, and your power outage concerns will be a thing of the past.
The ASCO SerieS 300 Transfer Switch can be a critical component of a municipal government’s emergency power backup system.
Residentsof townships, cities and counties rely on police, fire, ambulance/first aid and other critical public sector services.
An interruption in power can affect the ability of emergency services to effectively respond to the needs of the community. When time is a critical factor, such as when responding to a fire alarm or an emergency call, an ASCO SerieS 300 Transfer Switch can be a lifesaver, by automatically switching to power from the backup generator. While not all municipal services are a matter of life and death, they are always expected to be there.
TELECOM
TYPICAL APPLICATIONS
AGRICULTURE
COMMERCIAL/RETAIL, LIGHT INDUSTRIAL
MUNICIPAL
• Restriction of Hazardous Substances (RoHS) compliant controller.
• 30 through 3000 amperes in a compact design.
• Switch operating temperature range of
0 to +40o C.
• Available to 600 VAC, single or three phase.
• True double-throw operation: The single solenoid design is inherently inter-locked and prevents connections to both sources at the same time.
• No danger of the SerieS 300 ATS transferring loads to a dead source because the unique ASCO single-solenoid operator derives power to operate from the source to which the load is being transferred.
• Easy-to-navigate 128x64 graphical LCD display with keypad provides LED indicators for switch position, source availability, not in auto mode, and alert condition.
• Integrated multilingual user interface for configuration and monitoring.
• Delayed transition operation is now available (Dual Operator Configuration).
• Non-automatic operation can be selected using the key pad without opening enclosure door.
• Relay expansion module with extra relays for acces-sory outputs (optional).
• Includes soft keys for test function and time delay bypass as standard features.
• Emergency source failure alert indication.
• Historical event log (optional).
• Statistical ATS system monitoring information.
• Diagnostic functions.
• Password protection to prevent unauthorized tam-pering of settings.
• Adjustable time-delay feature prevents switch from being activated due to momentary utility power out-ages and generator dips.
• Auxiliary contacts to indicate position of main con-tacts. Two (2) for normal and two (2) emergency position
• Supplied with solid neutral termination.
• Optional switched neutral pole available.
• Field modification accessory kits available.
• Available for immediate delivery.
MAXIMUM RELIABILITY & EXCELLENT VALUE
With a SerieS 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually every major technological advance in the Transfer Switch industry.
The ASCO SerieS 300 was designed for one purpose–to automatically transfer critical loads in the event of a power outage. Each and every standard component was designed by ASCO engineers for this purpose.
The SerieS 300 incorporates the Group G controller with enhanced capabilities for dependable operation in any environment. A user-friendly control interface with a 128x64 graphical LCD display and intuitive symbols allow for ease of operation while visual LED indicators display the transfer switch status. Operating parameters and feature settings can be adjusted without opening the enclosure door.
The rugged construction and proven performance of the ASCO SerieS 300 assure the user of many years of complete reliability. The SerieS 300 is even designed to handle the extraordinary demands placed on the switch when switching stalled motors and high inrush loads.
ASCO’s SerieS 300 modular, compact design makes it easy to install, inspect and maintain. All parts are accessible from the front so switch contacts can be easily inspected.
FEATURES
• The SerieS 300 is listed to UL 1008 standard for total system loads for automatic transfer switches.
• Meets NFPA 110 for Emergency and Standby Power Systems and the
National Electrical Code (NEC) Articles 700, 701 and 702.
Fig. 1: ASCO Power Transfer Switch rated 200 Amps
Notes:
1. All WCR values indicated are tested in accordance with the requirements of UL 1008, 7th Edition. See ASCO Pub. 1128 for more WCR information.
2. Application requirements may permit higher WCR for certain switch sizes.
3. Front connected only.
4. J150, 200, 230 Amperes available in 3ADTS and 3NDTS only.
UL 1008 WITHSTAND AND CLOSE-ON RATINGS FOR
ASCO Series 300 GROUP G PRODUCTS 1,2
(RMS Symmetrical Amperes)
Series 300 POWER TRANSFER SWITCHES
FRAME
SWITCH
RATINGS
(AMPERES)
CURRENT LIMITING FUSES SPECIFIC BREAKER
TRANSFER
SWITCHES
480V
MAX.
600V
MAX.
MAX.
SIZE, A
CLASS
240V
MAX.
480V
MAX.
600V
MAX.
D 30 100kA - 60 J 22kA 22kA 10kA
D 70-104 35kA 35kA 200 RK1
42kA 22kA 10kA 200kA 35kA 200 J
D 150 35kA 35kA 200 RK1
65kA 25kA 10kA 200kA 35kA 200 J
D 200 200kA - 200 J 65kA 25kA 10kA
D 230 100kA - 300 J 65kA 25kA 10kA
J 1504, 2004, 2304, 260, 200kA 200kA 600 J 50kA 50kA 42kA
J 600 200kA 200kA 800 L 50kA 50kA 42kA
H 800-1200 200kA 200kA 1600 L 65kA3 65kA 65kA
G 1600-20003 200kA 200kA 2500 L 85kA 85kA3 85kA3
G 2600-3000 200kA 200kA 4000 L 100kA 100kA 100kA
DESIGNED TO FIT ANYWHERE
The ASCO SerieS 300 product line represents the most compact design of automatic power transfer switches in the industry. With space in electrical closets being at a premium, the use of wall- or floor-mounted ASCO Power Transfer Switches assure designers optimum utilization of space.
All transfer switches through 2000 amperes are designed to be completely front accessible. This permits the enclosures to be installed flush against the wall and still allow installation of all power cabling and connections from the front of the switch. Cable entrance plates are also standard on the 1600 and 2000 amperes units to install optional side-mounted pull boxes for additional cable bending space. Fig. 2: ASCO Power Transfer Switch rated 200 Amps
Fig. 3: ASCO Power Transfer Switch rated 400 Amps
Fig. 5: ASCO Power Transfer Switch rated 1000 Amps
Fig. 6: ASCO Power Transfer Switch rated 2000 Amps shown in Type 3R enclosure
Fig. 7: ASCO Power Transfer Switch rated 3000 Amps
Fig. 4: ASCO Power Transfer Switch rated 600 Amps
Series 300 POWER TRANSFER SWITCHES
Fig. 8: ASCO SerieS 300 Group G Controller
The Series 300 incorporates the group “G” controller with enhanced capabilities for dependable operation in any environment.
Controller/TS Interface Plug
Battery to Maintain Engine Exerciser
Clock Settings
Dip Switches for Voltage/Frequency and Feature Functions
Customer Control Interface
2) SE and ER Relay
Performance Features 600 volt spacing per UL and CSA standards.
Meets or exceeds the requirements for Electromagnetic Compatibility (EMC).
IEEE C37.90
IEC 61000 – 4 - 2 Electrostatic Discharge Immunity
IEC 61000 – 4 - 3 Radiated RF Field Immunity
IEC 61000 – 4 - 4 Electrical Fast Transient/Burst Immunity
IEC 61000 – 4 - 5 Surge Immunity
IEC 61000 – 4 - 6 Conducted RF Immunity
CISPR 11 – Conducted RF Emissions and Radiated RF Emissions
Control Power Transformers
Mounting Location for Accessory Dongle
NR Relay
Mounting Location for Current Sensing Card
RS 485 Port (Optional) Enabled with Feature
Bundle 11BE
CAN Bus Port
485 Configuration Dip Switches
Power Supply Jumper Card
SERIES 300 GROUP G CONTROLLER
TIME DELAYS
• Engine start time delay – delays engine starting signal to over-ride momentary normal source outages, adjustable from 0 to 6 seconds (Feature 1C).
• Emergency source stabilization time delay to ignore momentary transients during initial generator set loading, adjustable from 0 to 4 seconds (Feature 1F).
• Re-transfer to normal time delay with two settings (Feature 3A).
• Power failure mode – 0 to 60 minutes
• Test mode – 0 to 10 hours
• Unloaded running time delay for engine cooldown, adjustable from 0 to 60 minutes (Feature 2E).
• Pre- and post-signal time delay for selective load disconnect with a programmable bypass on source failures, adjustable from 0 to 5 minutes (specify ASCO optional accessory 31Z).
• Optional fully programmable engine exerciser with seven inde-pendent routines to exercise the engine generator, with or with-out loads, on a daily, weekly, bi-weekly or monthly basis (specify ASCO optional accessory feature bundle 11BE).
• Delayed transition load disconnect time delay, adjusable from 0 to 5 mi-nutes (3ADTS/3NDTS configuration only).
STANDARD SELECTABLE FEATURES
• Inphase monitor to transfer motor loads, without any intentional off time, to prevent inrush currents from exceeding normal starting levels.
• Engine exerciser to automatically test backup generator each week, with or without load 20 minutes not adjustable.
• Commit to transfer.
• Selective load disconnect circuit to provide a pre-transfer and/ or post-transfer signal when transferring from emergency to normal and/or normal to emergency.
• Re-transfer to normal through soft keys on user interface permits selection of “manual” or “automatic” operation.
• 60Hz or 50Hz selectable switch. Three-/single- phase select-able switch.
REMOTE CONTROL FEATURES
• External inputs for connecting:
• Remote test switch.
• Remote contact for test or peak shaving applications. If emer-gency source fails, switch will automatically transfer back to normal source if acceptable.
• Inhibit transfer to emergency.
• Remote time delay bypass switch emergency to normal.
CONTROL AND DISPLAY PANEL
• Easy-to-navigate 128x64 graphical LCD display with keypad provides LED indicators for switch position, source availability, not in auto mode, and alert condition. It also includes test and time delay bypass soft keys.
VOLTAGE, FREQUENCY & CURRENT
SENSING
• 3-phase under and over voltage settings on normal and single phase sensing on emergency source.
• Under and over frequency settings on normal and emergency.
• True RMS voltage sensing with +/-1% accuracy.
• Frequency sensing accuracy is +/- 0.1Hz.
• Voltage and frequency parameters adjustable in 1% incre-ments.
• Selecting settings: single or threephase voltage sensing on normal, and single phase sensing on emergency; 50 or 60Hz.
3-phase voltage unbalance on normal.
• Load current sensing card (optional).
Fig. 9: Door-Mounted Control & Display Panel
LED Source Availability and Switch Position Indicators Transfer / Time Delay Override control push-button
Escape Key
5 Enter Key
Scroll, Up/Down Arrows
Common Alarm
Not In Auto Indicator
Main Menu/ Settings
Settings/ Engine Exerciser
Settings/General/ Communications
Settings/General/ Common Alarms
Control Status Source Status Alarm Status Controller Information
Main Menu/ Event Logging
Main Menu/ Statistics
Main Menu/ Factory/Diagnostics
Main Menu/ About
SERIES 300 GROUP G OFFERS SOPHISTICATED FUNCTIONALITY
The new Group G controller offers an intuitive, easy-to-navigate 128*64 graphical LCD display with soft keypad and provides six (6) LED indicators.
• Switch Position (green for normal, red for emergency LED)
• S.ource Availability (green for normal, red for emergency LED)
• “Not In Auto” (amber LED)
• Common Alarm (amber LED)
The ASCO group “G” controller is self-contained with an integrated display (no other components are required for efficient operation).
The controller allows for open or delayed transition transfer opertion (both automatic, and non-automatic configurations).
An integrated multilingual user interface for configuration and monitoring (this design approach allowsgreater application flexibility).
Multiple source-sensing capabilities of voltage, frequency (under frequency sensing on normal and emergency sources), and optional current card, single and three phase (does not require an external metering device).
Fig. 10: Strip Heater Kit (Accessory 44G)
ACCESSORY 1UP
UPS back up power to allow controller to run with LCD display for 30 seconds without AC power.
ACCESSORY 11BE FEATURE BUNDLE
A fully programmable engine exerciser with seven independent routines to exercise the engine generator with or without loads, on a daily, weekly, bi-weekly or monthly basis. Engine exerciser setting can be displayed and changed from the user interface keypad.
Event Log display shows the event number, time and date of event, event type, and event reason (if applicable).
A maximum of 300 events can be stored. RS 485 Communications Port Enabled Common Alarm Output Contact
ACCESSORY 18RX
Relay expansion module (REX) provides for some commonly used accessory relays, includes one form C contact for source availability of normal (18G), and one form C contact for availability of emergency (18B) (contact rating 5 amperes @ 30Vdc or @125 VAC resistive) (100 ma, 5Vdc min). Additional output relay is provided, the default is to indicate a common alarm. (See operator’s manual for configurable options.)
ACCESSORY 23GA1 (SINGLE PHASE) AND 23GB (THREE
PHASE)
Load current metering card measures either single or three phase load current.
Note 1: This feature is not available with a Power Meter Option (135L).
ACCESSORY 44A
Strip Heater with thermostat for extremely cold areas to prevent condensation and freezing of this condensation. External 120 volt power source required.
ACCESSORY 44G
Strip Heater with thermostat, wired to load terminals:
208-240, 360-380, 460-480, 550-600 volts. Contains wiring harnesses for all transfer switch sizes.
ACCESSORY 72EE
Connectivity Module enabling remote monitoring and control capabilities includes accessory 11BE featured bundle (pages 12-14).
FIELD CONVERSION KITS FOR Series 300
TRANSFER SWITCHES
ACCESSORY 73
Surge Suppressor (TVSS) Rated 65kA.
ACCESSORY 62W
Audible alarm with silencing feature to signal each time switch transfers to emergency (may require oversize enclosure depending on accessory combination for "D" frame only).
ACCESSORY 37B
6' Extension harness for units shipped open type to accommodate customer mounting of controls and switch.
ACCESSORY 37C
9' Extension harness for units shipped open type to accommodate customer mounting of controls and switch.
ACCESSORY 135L2
Power Meter on load side (includes shorting block and CTs)Note 2: This feature is not available with Load Current Metering Option (23GA or 23GB).
ACCESSORY 30A3
Shedding circuit initiated by opening of a customer-supplied contact.
ACCESSORY 30B*3
Load-shedding circuit initiated by removal of customer-supplied voltage. (*Specify Voltage)
ACCESSORY 30AA3
Load-shedding circuit initiated by opening of a customer-supplied contact.
ACCESSORY 30BA*3
Load-shedding circuit initiated by removal of customer-supplied voltage. (*Specify Voltage)
Note 3: Accessory 30A and 30B* are only available for 3ATS only;
accessory 30AA and 30BA* are only available for 3ADTS.
Fig. 11: Relay Expansion Module (Accessory 18RX)
Fig. 12: Load Current Card (Accessory 23GA/GB)
Fig. 14: Accessory 1UP UPS Backup Power
Fig. 13: Programmable Engine Exerciser
SERIES 300 ATS OPTIONAL ACCESSORIES
KIT NO. DESCRIPTION
935147 Feature Bundle Includes Engine Exerciser/Event Log/RS 485/ Common Alarm Output Contact (Acc. 11BE) Dongle
935148 REX Module with Source Availability Contacts (Acc. 18RX)
935149 UPS to allow controller to run for 30 seconds minimum without AC Power (Acc. 1UP)
935150 1/3 Phase load current sensing card only (Acc. 23GA/GB)
K613127- 001 Strip Heater (125 watt) 120 volt (Acc. 44A)
K613127- 002 Strip Heater (125 watt) 208-480 volt (Acc. 44G)
948551 Quad-Ethernet Module (Acc. 72EE)
K609027 Cable Pull Box (1600-2000 amperes)
Series 300 NON-AUTOMATIC TRANSFER SWITCHING (3NTS) ASCO non-automatic transfer switches are generally used in applications in which operating personnel are available and the load is not an emergency type requiring automatic transfer of power. They can also be arranged for remote control via ASCO’s connectivity products.
Fig. 15: ASCO 3NTS 400 Amps Type 1 Enclosure
3ADTS/3NDTS FEATURES
• Sizes from 150 through 3000 amperes.
• Reliable field proven dual solenoid operating mechanisms.
• Mechanical interlocks to prevent direct connection of both sources.
• Adjustable time delay for load disconnect (0 to 5 minutes).
• Available in manual operation configuration (3NDTS).
• Available with optional load shed feature for (3ADTS).
Series 300 DELAYED TRANSITION TRANSFER
SWITCHING
(3ADTS/3NDTS)
ASCO Delayed Transition Transfer Switches are designed to provide transfer of loads between power sources with a timed load disconnect position for an adjustable period of time.
Fig. 16: ASCO 3ADTS/3NDTS 400 Amps
Type 1 Enclosure
3NTS FEATURES
• ASCO Non-Automatic Transfer Switches are manually initiated via soft keys on the user interface panel.
• Sizes range from 30 through 3000 amperes.
• Group G controller provides for addition of optional accessories.
• Controller prevents inadvertent operation under low voltage condi-tion.
• Source acceptability lights inform operator if sources are available to accept load.
• Source inphase monitor to transfer motor loads between live sources.
• Two auxiliary contacts closed when transfer switch is connected to normal and two closed on emergency standard feature 14AA/14BA.
SERIES 300 POWER TRANSFER SWITCHES
EXTENDED WARRANTIES FOR Series 300 TRANSFER SWITCHES (3ATS/3NTS/3ADTS/3NDTS)
Series 300 EXTERNAL POWER CONNECTIONS Size UL-Listed Solderless Screw-Type Terminals
Notes:
1. All SerieS 300 switches are furnished with a solid neutral plate (unless switched neutral configuration is specified) and terminal lugs.
2. 200 and 230 amperes rated switches for use with copper cable only. Refer to paragraph
310.15 of the NEC for additional information.
3. Use wire rated 75oC minimum for all power connections.
* 150 for DTS only
To order an ASCO series 300 Power Transfer Switch, complete the following catalog number:
Notes:
1. Standard warranty is (24) months, 2 years from date of shipment, extended warranty is in addition to the two years, for a total of, 3, 4, or 5 years.
2. Refer to Publication 3223 for warranty terms and conditions.
SERIES 300 TRANSFER SWITCH ORDERING INFORMATION
Notes:
J 03ATS A 3 0600 N GX C
Frame Transition Type Neutral Code Phase
Poles Amperes
Voltage
Code
Group
Code Enclosure
Open Transition D = 30A - 230A
Open/Delayed Transition J = 150A - 600A H = 800A - 1200A G = 1600A - 3000A
Automatic 03ATS Open Transition
3ADTS Delayed Transition
Non Automatic 03NTS Open Transition
3NDTS Delayed Transition
A = Solid Neutral
B = Switched Neutral
00301
00701
01041
01501, 5
02001, 3, 4
02301, 3, 4
02601, 4
04001, 4
06001, 4
08004
10004
12004, 5
16004, 5
20004, 5
26004, 5
30004, 5
A3 = 115
B3 = 120
C = 208
D = 220
E = 230
F = 240
H = 380
J = 400
K = 415
L = 440
M = 460
N = 480
P = 550
Q = 575
R = 600
G0 No Optional Accessories
GX
Optional Accessories
0 = Open Type (zero)
C = Type 1 Enclosure
F = Type 3R1 Enclosure
G = Type 41 Enclosure
H = Type 4X1 Enclosure (304 Stainless Steel)
L = Type 121 Enclosure
M = Type 3R3 Secure Double Door Enclosure
N = Type 4 Secure Double Door Enclosure
Q = Type 12 Secure Double Door Enclosure
R = Type 3RX7,8 Secure Double Door Enclosure (304 Stainless Steel)
1. Switch sizes 30-600 amperes supplied in non-secure enclosures as standard.
2. 115-120 volt available for 30-400 amperes only. For other voltages contact ASCO.
3. 200 and 230 amperes rated switches for use with copper cable only.
4. Switch sizes 800-3000 amperes, and 150-400 amperes 3ADTS/3NDTS provided in secure type outdoor enclosures when required.
5. Use Type 3R secure for 1200, 2000, 2600, and 3000.
6. Type 304 stainless steel is standard. Suitable for indoor or outdoor use where there may be caustic or alkali chemicals in use. To provide an improved reduction in corrosion of salt and some chemicals, optional type 316 stainless steel is recommended. This is the preferred choice for marine environments.
7. Available on switches rated 1200, 2000, 2600, and 3000 amperes.
8. When temperatures below 32oF can be experienced, special precautions should be taken, such as the inclusion of strip heaters, to prevent condensation and freezing of this condensation. This is particularly important when environmental (Type 3R, 4) are ordered for installation outdoors.
9. Type 3R enclosures are not suitable for installations subject to wind blown rain or snow. Use type 4 enclosures where available or install supplemental shelter protection around the 3R enclosure.
SWITCH RATING
(AMPERES)
RANGES OF AL-CU WIRE SIZES
(UNLESS SPECIFIED COPPER ONLY)
30-2302 ATS and NTS only One #14 to 4/0 AWG
150*, 260, 400 Two 1/0 AWG to 250 MCM or One #4 AWG to
600 MCM
600 Two 2/0 AWG to 600 MCM
800, 1000, 1200 Four 1/0 to 600 MCM
1600, 2000 Six 1/0 to 600 MCM
2600, 3000 Twelve 1/0 to 750 MCM
DESCRIPTION
1 Year Extension (Total of 3 Years)
2 Year Extension (Total of 4 Years)
3 Year Extension (Total of 5 Years)
UL TYPE 3R, 4 OR 12 ENCLOSURE1,2,3,4
Notes:
1. When climate conditions at installation site present condensation risk, special precautions should be taken, such as the inclusion of space heaters, to prevent interior condensation and freezing of this condensation.
2. Dimensions for 30-200 amperes when furnished with a power meter 18"W - 48"H
- 13"D
3. 30-1000 amperes switches are available in secure type enclosures, contact ASCO for details.
4. Dimensional data is approximate and subject to change. Certified dimensions available upon request.
UL TYPE 1 ENCLOSURE1,2,3,4
Notes:
1. Unit is designed for top cable entry of emergency and load, and bottom entry of normal. A cable pull box is also available for all top or bottom cable access when required (optional accessory kit #K609027). Not required for type 3R, 4X and 12 enclosures where available.
2. Enclosures for 2600, 3000 amperes are free-standing with removable top, sides and back.
3. Dimensions for 30-200 amperes when furnished with accessory 135L power meter, 18"W - 41"H - 13"D
4. Dimensional data is approximate and subject to change. Certified dimensions available upon request.
SERIES 300 Transfer Switch Dimensions and Shipping Weights
SWITCH
RATING
AMPS
PHASE
POLES
NEUTRAL
CODE
DIMENSIONS, IN. (MM)
APPROX. SHIPPING
WEIGHT LB. (KG)WIDTH HEIGHT DEPTH
303,703,1043
1503, 2003
2 A 18 (457) 31 (787) 13 (330) 69 (32) 2 B 18 (457) 31 (787) 13 (330) 72 (33) 3 A 18 (457) 31 (787) 13 (330) 72 (33) 3 B 18 (457) 31 (787) 13 (330) 75 (34)
2 A 18 (457) 48 (1219) 13 (330) 117 (53) 2 B 18 (457) 48 (1219) 13 (330) 125 (57) 3 A 18 (457) 48 (1219) 13 (330) 125 (57) 3 B 18 (457) 48 (1219) 13 (330) 133 (61)
260, 400
2 A 24 (610) 56 (1422) 14 (356) 250 (113) 2 B 24 (610) 56 (1422) 14 (356) 260 (118) 3 A 24 (610) 56 (1422) 14 (356) 260 (118) 3 B 24 (610) 56 (1422) 14 (356) 270 (123)
150, 200, 230 SerieS
3ADTS/3NTS only
2 A 24 (610) 56 (1422) 14 (356) 250 (113) 2 B 24 (610) 56 (1422) 14 (356) 260 (118) 3 A 24 (610) 56 (1422) 14 (356) 260 (118) 3 B 24 (610) 56 (1422) 14 (356) 270 (123)
2 A 24 (610) 63 (1600) 17 (432) 300 (137) 2 B 24 (610) 63 (1600) 17 (432) 320 (146) 3 A 24 (610) 63 (1600) 17 (432) 320 (146) 3 B 24 (610) 63 (1600) 17 (432) 320 (151)
800, 1000
2 A 34 (864) 72 (1829) 20 (508) 431 (196) 2 B 34 (864) 72 (1829) 20 (508) 460 (209) 3 A 34 (864) 72 (1829) 20 (508) 460 (209) 3 B 34 (864) 72 (1829) 20 (508) 489 (222)
2 A 38 (965) 87 (2210) 23 (584) 581 (264) 2 B 38 (965) 87 (2210) 23 (584) 611 (277) 3 A 38 (965) 87 (2210) 23 (584) 611 (277) 3 B 38 (965) 87 (2210) 23 (584) 639 (290)
1600, 2000 3 A 38 (965) 87 (2210) 23 (584) 1160 (525) 3 B 38 (965) 87 (2210) 23 (584) 1160 (525)
2600, 3000 3 A 38 (965) 91 (2311) 72 (1829) 1430 (649) 3 B 38 (965) 91 (2311) 72 (1829) 1495 (679)
SWITCH
RATING
AMPS
PHASE
POLES
NEUTRAL
CODE
DIMENSIONS, IN. (MM)
APPROX. SHIPPING
WEIGHT LB. (KG)WIDTH HEIGHT DEPTH
302,702,1042
1502, 2002
(Non-Secure Enclosure)
2 A 17.5 (445) 35 (886) 11.625 (295)
84 (38)
2 B 17.5 (445) 35 (886) 11.625 (295)
87 (40)
3 A 17.5 (445) 35 (886) 11.625 (295)
87 (40)
3 B 17.5 (445) 35 (886) 11.625 (295)
90 (41)
(Non-Secure Enclosure)
2 A 18 (458) 50.5 (1284) 14.33 (364) 90 (41) 2 B3 or C 18 (458) 50.5 (1284) 14.33 (364) 132 (60) 3 A 18 (458) 50.5 (1284) 14.33 (364) 140 (63) 3 B3 or C 18 (458) 50.5 (1284) 14.33 (364) 148 (67)
260, 400
2 A 24 (610) 63 (1600) 18.2 (462) 320 (146) 2 B 24 (610) 63 (1600) 18.2 (462) 340 (155) 3 A 24 (610) 63 (1600) 18.2 (462) 340 (155) 3 B 24 (610) 63 (1600) 18.2 (462) 350 (160)
150, 200, 230 SerieS
3ADTS/3NTS only (Non-Secure Enclosure)
2 A 24 (610) 63 (1600) 18.2 (462) 320 (146) 2 B 24 (610) 63 (1600) 18.2 (462) 340 (155) 3 A 24 (610) 63 (1600) 18.2 (462) 340 (155) 3 B 24 (610) 63 (1600) 18.2 (462) 350 (160)
(Non-Secure Enclosure)
2 A 24 (610) 63 (1600) 18.2 (462) 320 (146) 2 B 24 (610) 63 (1600) 18.2 (462) 340 (155) 3 A 24 (610) 63 (1600) 18.2 (462) 340 (155) 3 B 24 (610) 63 (1600) 18.2 (462) 350 (160)
800, 1000
2 A 34 (859) 72 (1821) 20 (508) 519 (236) 2 B 34 (859) 72 (1821) 20 (506) 543 (246) 3 A 34 (859) 72 (1821) 20 (506) 543 (246) 3 B 34 (859) 72 (1821) 20 (506) 565 (257)
(Secure Enclosure)
2 A 41 (1037) 95.5 (2415) 33.5 (848) 1131 (513) 2 B 41 (1037) 95.5 (2415) 33.5 (848) 1160 (526) 3 A 41 (1037) 95.5 (2415) 33.5 (848) 1160 (526) 3 B 41 (1037) 95.5 (2415) 33.5 (848) 1189 (539)
1600, 2000 (Secure Enclosure)
3 A 42.5 (1074) 95.5 (2529) 47 (1189) 1705 (775) 3 B 42.5 (1074) 95.5 (2529) 47 (1189) 1830 (832)
2600, 3000 (Secure Enclosure)
3 A 41 (1037) 95.5 (2529) 74 (1872) 2150 (976) 3 B 41 (1037) 95.5 (2529) 74 (1872) 2230 (1012)
300 ATS with 72EE
Engine Generator
Utility Facility
WiFi
Tablet
Mobile Device
Desktop
72EE enables basic local or remote monitoring for ASCO Series 300 Transfer Switches.
ASCO 5700
CPMS
72EE FEATURES
CONTROL FEATURES
• ATS Transfer/Re-transfer
• ATS Timer Bypass
• Generator Start
• Generator Test
CONNECTIVITY FEATURES
• Modbus TCP/IP (over Ethernet or Serial)
SNMP Protocol
• AES 128 Bit Encryption
• Four Port Ethernet Switch
72EE ALSO ENABLES ENHANCED POWERQUEST CPMS FUNCTIONALITY
• 5310 Series Single Channel Annunciator
• 5350 Series Eight Channel Annunciator
• 5700 Critical Power Management Systems
• 5705 8-Device Annunciator
Sample drawing for demonstration purposes only.
Consult ASCO for exact connection specifications.
MONITORING FEATURES
• ATS and Generator Stats
• Alarms
• Voltage and Frequency
• Statistics and Activity
• Email Notifications
• Event Log (300 Events)
• Optional Monitoring Features
— Energy Consumption, Acc 135L
Required
— Power Demand, Acc 135L Required
SERIES 300 72EE MONITORING AND CONTROL
Content-rich monitoring screens enable real-time information for power metering, event logs, volt-ages, time delays and alerts. The 72EE also allows for remote switch transfer.
SERIES 300 72EE MONITORING SCREENS
Dashboard Power Metering
Events
About
Configuration
ADDITIONAL OPTIONAL POWERQUEST COMPONENTS
5310, 5350 Annunciators
5210, 5220 Power Manager
5710, 5750, 5790 Display Terminals
ASCO 5210 (Left) and 5220 (Right) Power Meters measure, displays and provides single- or 3-phase Energy and Power information
5700 Critical Power Management Systems (5790 Shown)pro-vide various levels of monitoring, control and management ca-pability of power equipment. It seamlessly monitors ASCO trans-fer switches as well as generators, breakers, paralleling busses, panel boards and other power equipment via a 5221 PMU. It consists of servers and touch-screen interfaces.
ASCO 5310 (Left) and 5350 (Right) ATS Remote Annunciators provide distributed monitoring of transfer switch position and source availability as well as transfer test and re-transfer control.
ASCO 5221
Power Manager Unit
ASCO 5221 Power Manager Unit (PMU) enables power measurement, discrete inputs for status and output relays for control of generators, break-ers and other power equipment via 5700 Series CPMS solutions.
Connectivity Module
ASCO 5160 Remote Connectivity Unit (RCU) provides 10 Ethernet and Dual-Fiber Optic connections in a NEMA 3R enclosure.
The ASCO 72EE Connectivity Module offers remote monitoring for SerieS 300 ATSs and 5210 Power Meter. For the ATS, the op-tional accessory 72EE provides remote ATS and generator control, monitoring and connectivity features via integrated web page dashboards. Once connected to an Ethernet, WiFi or cellular connection, the dashboards can easily be pulled up by any mobile or desktop device on the network by multiple users.
CONTROL
The control capabilities allows remote transfer and retransfer of the ATS while allowing you to view time delays and bypass functions.
The generators can also be called to start and stop for emergency situations as well as for testing and maintenance. Running the generator periodically ensures that the battery is charged for power anomalies and increases reliability. Generator pick-up and drop-out set points are also viewable for comprehensive understanding of control events.
MONITORING
Monitor transfer switch and generator health, system state, metering and review calculated transfer statistics and activity. Active control timer information allows the operator to anticipate an automated control action such as generator start or ATS transfer. The device can also interface with an email server to keep users up-to-date on alarms and critical power events with alerts. In addition the 72EE can interface to an optional 5210 Power Meter, (stand-alone or with the ATS Acc. 135L) for enhanced monitoring features such as power metering, demand and energy usage.
CONNECTIVITY
Connect and extract ATS and metering data using industry-standard open protocols such as Modbus and SNMP. An integrated four-port Ethernet switch maximizes connectivity options and flexibility. Embedded pass-word protection will only allow access to appropriate users while utilizing AES 128-bit encryption for enhanced data security per National Institute of Standards and Technology (NIST).
Fig. 22: Accessory
72EE
SERIES 300 72EE CONNECTIVITY MODULE
FULFILL YOUR NEED
Drill down for a closer look - Each transfer switch, generator, breaker and any other power equipment has its own dedicated screens.
The PowerQuest® family is the most comprehensive communication, monitoring and control solution ever offered by ASCO Power Technologies. It empowers you. It provides the ability to test, manage loads, optimize the bus bar, remotely monitor and be aware of the status of your facility's utility source and on-site power. It provides reports for events, tests, energy use or settings, and gets data directly from generators and transfer switches.
Whether users require standard monitoring and control or a comprehensive Critical Power Management System, PowerQuest can satisfy your needs.
Hardware. Software. Installation and testing.
Service. And upgrades and technology refreshes. A truly complete solution for all your communication, monitoring and control needs.
This web-enabled management system is based on open protocols. As communications among equipment improve, so does the performance of critical power systems.
ASCO POWERQUEST® POWER MONITORING AND CONTROL SYSTEMS
PowerQuest provides monitoring, alarming and control of Critical Power Management Systems, which comprise transfer switches, paralleling control switchgear, gensets, circuit breakers, UPSs, load banks, distribution and other gear. It also integrates with building management systems.
BE EMPOWERED POWERQUEST CAN ENABLE YOU TO:
• Monitor and control power transfer switches, paralleling control switchgear, gensets, breakers, UPS, bus bars and other equipment.
• Monitor normal and emergency voltages and frequency and their settings.
• Know transfer switch position and source availability.
• Transfer and re-transfer loads for system testing.
• View and adjust transfer switch time-delay settings.
• Receive automatic alerts or selected system alarms on system operation via email or pager.
• View transfer switch event log and know the transfer switch test schedule.
• Generate reports for alarms, energy consumption,settings, historical logs and code-mandated tests.
*For more PowerQuest product information see publication 3245
Static Transfer Switches
Transfer Switches
Paralleling Control Switchgear
GeneratorsCPMS Display Terminal
HVAC
Critical Power Management System (CPMS)
Security
Fire Alarm Monitoring
Internet Remote Display Terminal
Building Management System (BMS)
UPS
ASCO Power Technologies - Global Headquarters 160 Park Avenue Florham Park, NJ 07932 Tel: 800 800 ASCO www.ascopower.com customercare@ascopower.com
© 2019 ASCO Power Technologies. All Rights Reserved. Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
Publication 1195. Printed in the U.S.A.
| 1 - Cover Page |