BFSU Addendum 01 Drawings.pdf

PDF 2 MB Posted

Attached to
BLACKFEET HOSPITAL CT ROOM RENOVATION
Solicitation number
75H70125R00016
Issued by

About this file

These are architectural and engineering design drawings for the Blackfeet Hospital CT Room Renovation project, dated February 16, 2024 with an Addendum on April 22, 2025. The comprehensive set of technical drawings includes detailed plans for renovating an existing CT scan room and adjacent spaces, covering architectural, mechanical, plumbing, electrical, and power system modifications. The drawings specify comprehensive changes including demolition of existing walls and finishes, installation of new lead-lined walls, reconfiguration of HVAC and medical gas systems, new electrical and power infrastructure, and specialized equipment placement for a new 128-slice CT scanner.

The renovation focuses on creating an appropriately sized and equipped CT scan room that meets 2018 Facility Guidelines Institute (FGI) standards and manufacturer recommendations. Key design elements include lead shielding, specialized electrical and mechanical systems, new floor trench ducts, medical gas connections, and integration of equipment like a wall-mounted air conditioner, humidifier, and medical equipment. The drawings provide precise technical specifications for contractors, including detailed schedules for grilles, registers, diffusers, electrical equipment, and mechanical components, ensuring a comprehensive approach to the medical facility upgrade.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CODE COMPLIANCE LEGEND

1-HOUR FIRE RATED PARTITION - UL DES U419

2-HOUR FIRE RATED BARRIER - UL DES U419

SMOKE BARRIER - NFPA 101 - 8.3

ROOM NAME

XXX SF

ROOM NAME

ROOM NUMBER

ROOM AREA

CODE ROOM TAG INFORMATION

PATH OF EGRESS

EXIT

OCCUPANT LOAD PER EXIT

OCCUPANT LOAD

EGRESS CORRIDOR

ROOM OCCUPANT LOADXX

AREA NOT IN SCOPE

1/2 HOUR FIRE RESISTIVE WALL

519 SF

CT SCAN

92 SF

SECURITY

58 SF

1556B

CHANGING

83 SF

1556A

CONTROL ROOM

114 SF

FAMILY CONSULT

AREA NOT IN SCOPE

CODES & REGULATIONS

AUTHORITY

HAVING

JURISDICTION

CODES AND REGULATIONS

• INTERNATIONAL BUILDING CODE - 2021 EDITION

• NFPA 10, STANDARD FOR THE PORTABLE FIRE

EXTINGUISHERS - 2022 EDITION

• NFPA 13, STANDARD FOR THE INSTALLATION OF

SPRINKLER SYSTEMS - 2022 EDITION

• NFPA 70, NATIONAL ELECTRIC CODE - 2020

EDITION

• NFPA 72, NATIONAL FIRE ALARM CODE - 2022

EDITION

• NFPA 80, STANDARD FOR FIRE DOORS AND OTHER

OPENING PROTECTIVES - 2022 EDITION

• NFPA 101, LIFE SAFETY CODE - 2021 EDITION

• NFPA 90A, STANDARD FOR THE INSTALLATION OF

AIR-CONDITIONING AND VENTILATING SYSTEMS -

2021 EDITION

• NFPA 99, HEALTH CARE FACILITIES CODE - 2021

EDITION

• NFPA 220, STANDARD ON TYPES OF BUILDING

CONSTRUCTION - 2021 EDITION

GENERAL BUILDING LIMITATIONS

CODE/REGULATED

ITEM

IBC

OCCUPANCY

CONSTRUCTION

TYPE

AUTOMATIC FIRE

SPRINKLER

NFPA 101

I-2, B

II

YES YES

ACTUAL

BUILDING HEIGHT

15' 4" EXISTING NO CHANGE

1 STORY NO CHANGESTORIES

DEAD END

CORRIDOR

COMMON PATH

OF TRAVEL

100' 18.2.5.3

EXISTING

HEALTHCARE, BUSINESS

LIFE SAFETY CODE ANALYSIS

GENERAL PROJECT DESCRIPTION

1. THE PROJECT SCOPE CONSISTS OF UPGRADING CURRENT

ROOM FINISHES AND EQUIPMENT

INTERNATIONAL BUILDING CODE - 2021

OCCUPANCY CLASSIFICATION

1. EXISTING HEALTHCARE AREA, EXISTING BUSINESS

ALLOWABLE HEIGHT

1. TABULAR HEIGHT - UNLIMITED [TABLE 504.3]

2. TABULAR NUMBER OF STORIES - UNLIMITED [TABLE 504.4]

ALLOWABLE AREA

1. TABULAR AREA - UNLIMITED [TABLE 506.2]

STRUCTURAL FIRE RESISTIVE

RATING OF BUILDING ELEMENTS

1. REQUIRED FIRE RESISTANCE RATINGS STRUCTURAL

ELEMENTS BASED ON

IBC TYPE IA CONSTRUCTION [TABLE 601 & TABLE 602]

STRUCTURAL ELEMENT FIRE RESISTANCE

RATING (HOURS)

BEARING WALLS EXTERIOR 3

INTERIOR 3

FIRE BARRIERS EXIT STAIRWAYS CONNECTING

FEWER THAN FOUR STORIES

EXIT STAIRWAYS CONNECTING

FOUR OR MORE STORIES

SHAFTS (OTHER THAN EXITS) AND

ELEVATOR HOISTWAY

NON-LOAD

BEARING

WALLS

EXTERIOR ( < 30 FT. SEPARATION) 1

0 ( ≥ 30 FT. SEPARATION)

INTERIOR 0

PRIMARY STRUCTURAL MEMBERS 3

FLOOR CONSTRUCTION (INCLUDING BEAMS) 2

ROOF

CONSTRUCTION

(INCLUDING BEAMS,

TRUSSES, ARCHES

AND ROOF DECK)

LESS THAN 20 FT. IN HEIGHT

TO LOWEST MEMBER

1-1/2

20 FT. OR MORE IN HEIGHT

TO LOWEST MEMBER

a, b c c a

NOT LESS THAN THE FIRE SEPARATION DISTANCE (IBC TABLE 602)

b

NOT LESS THAN FIRE RESISTANCE RATING OF THE WALL SUPPORTED

c

RATING MAY BE REDUCED BY 1-HOUR IF SUPPORTING ROOF ONLY

NFPA 101, LIFE SAFETY CODE - 2021

OCCUPANT USE LOAD FACTORS [TABLE 7.3.1.2]

1. ASSEMBLY USE (LESS CONCENTRATED): 15 SF/PERSON

2. BUSINESS USE: 100 SF/PERSON

3. BUSINESS USE (CONCENTRATED): 50 SF/PERSON

TRAVEL DISTANCE WITH AUTOMATIC

FIRE SPRINKLER PROTECTION

1. MAXIMUM TRAVEL DISTANCE

1.1. NEW BUSINESS: 300 FT. [§38.2.6.3]

1.2. EXISTING BUSINESS: 300 FT. [§39.2.6.3]

2. MAXIMUM COMMON PATH OF TRAVEL

2.1. NEW BUSINESS: 100 FT. [§38.2.5.3.1]

2.2. EXISTING BUSINESS: 100 FT. [§39.2.5.3.1]

3. MAXIMUM DEAD END CORRIDOR DISTANCE

3.1. NEW BUSINESS: 50 FT. [§38.2.5.2.1]

3.2. EXISTING BUSINESS: 50 FT. [§39.2.5.2.1]

OCCUPANCY SEPARATION

1. SEPARATED OCCUPANCY (BUSINESS AND HEALTHCARE)

1.1. EACH PART OF THE BUILDING COMPRISING OF A DISTINCT

OCCUPANCY SHALL BE COMPLETELY SEPARATED FROM OTHER

OCCUPANCIES BY FIRE-RESISTIVE CONSTRUCTION [§6.1.14.4.1]

HAZARDOUS AREA PROTECTION

1. PROTECTION FROM ANY AREA HAVING A DEGREE OF HAZARD

GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF THE

BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE

FOLLOWING MEANS [§8.7.1.1]

1.1. 1-HOUR FIRE BARRIER

1.2. AUTOMATIC SPRINKLER SYSTEM

1.3. APPLYING BOTH WHEN HAZARD IS SEVERE

2. IN NEW CONSTRUCTION, WHERE PROTECTION IS PROVIDED WITH

AUTOMATIC SPRINKLERS WITHOUT FIRE-RESISTIVE SEPARATION, THE

SPACE SHALL BE ENCLOSED WITH SMOKE PARTITIONS [§8.7.1.2]

3. SMOKE PARTITION - CONTINUOUS MEMBRANE THAT IS DESIGNED TO

FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE. IT IS NOT

REQUIRED TO HAVE A FIRE RESISTANCE RATING [§3.3.256]

4. NO SEVERE HAZARDS ARE ANTICIPATED WITHIN THE SCOPE OF THE

PROJECT

FIRE RESISTANCE RATED SEPARATION

1. CORRIDOR WALL

1.1. 0-HOUR [ §38.3.6.1, §39.3.6.1]

2. HAZARDOUS AREA (GENERAL STORAGE, BOILER, FURNACE ROOM)

2.1. NEW BUSINESS: SMOKE PARTITION [§38.3.2.1, §8.7.1.2]

2.2. EXISTING BUSINESS: 0-HOUR [ §39.3.2.1, §8.7.1.2]

3. HIGH HAZARD CONTENTS

3.1. 1-HOUR [§38.3.2.1, §39.3.2.1, §8.7.1.1]

OPENING PROTECTIVE

1. BARRIER WALLS - 1-HOUR

1.1. 3/4-HOUR [TABLE 8.3.4.2]

2. BARRIER WALLS - 2-HOUR

2.1. 1 1/2-HOUR [TABLE 8.3.4.2]

3. SMOKE PARTITIONS - 1/2-HOUR

3.1. 1/3-HOUR [TABLE 8.3.4.2]

REQUIRED FIRE RESISTANCE RATING

1. ENCLOSURES CONNECTING ≥ 4 STORIES

1.1. 2-HOUR

2. OTHER ENCLOSURES

1.2. 1-HOUR

INTERIOR FINISH WITH AUTOMATIC

SPRINKLER PROTECTION

1. EXIT ACCESS CORRIDORS AND OTHER EXIT WAYS

1.1. EXISTING HEALTHCARE: CLASS A or B [§19.3.3.2]

1.2. EXISTING BUSINESS: CLASS C [§39.3.3.2.1]

2. ROOMS AND ENCLOSED SPACES

2.1. EXISTING HEALTHCARE:

2.2. EXISTING BUSINESS: CLASS C [§39.3.3.2.2]

3. FLOOR FINISH

3.1. EXISTING HEALTHCARE: CLASS II [§38.3.3.3.2]

3.2. EXISTING BUSINESS: CLASS II [§39.3.3.3.2]

FIRE AND SMOKE DAMPERS

1. FIRE DAMPERS

1.1. FIRE DAMPERS SHALL BE PROVIDED WHERE DUCTS PENETRATE

OR TERMINATE AT OPENINGS IN WALLS OR PARTITIONS REQUIRED

TO HAVE A FIRRESISTANCE RATING OF 2-HOURS OR MORE [NFPA

90A §5.3.1.1]

1.2. FIRE DAMPERS SHALL BE INSTALLED AT EACH DIRECT OR

DUCTED OPENING INTO AND OUT OF SHAFT ENCLOSURES [NFPA

90A §5.3.4.6]

2. SMOKE DAMPERS

2.1. SMOKE DAMPERS SHALL BE INSTALLED IN SYSTEMS WITH

CAPACITY GREATER THAN 15,000 CFM TO ISOLATE THE AIR-

HANDLING EQUIPMENT FROM THE REMAINDER OF THE SYSTEM

ON BOTH THE BUILDING SUPPLY SIDE AND THE RETURN SIDE

[NFPA 90A §4.3.10.2]

MEANS OF EGRESS COMPONENTS

1. DOORS

1.1. MINIMUM CLEAR WIDTH: 32 INCHES [§7.2.1.2.4]

1.2. SWING IN THE DIRECTION OF EGRESS WHEN SERVING AN

OCCUPANT LOAD GREATER THAN 50 OCCUPANTS [§7.2.1.4.2]

1.3. SWING IN DIRECTION OF EGRESS TRAVEL WHEN USED IN AN

EXIT ENCLOSURE OR WHERE SERVING A HIGH HAZARD

CONTENTS AREA [§7.2.1.4.2]

2. MARKING OF MEANS OF EGRESS

2.1. EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY

VISIBLE FROM ANY DIRECTION OF EXIT ACCESS [§7.10.1.2.1]

2.2. SIGN PLACEMENT SHALL BE SUCH THAT NO POINT IN AN EXIT

ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING

DISTANCE OR 100 FT, WHICHEVER IS LESS, FROM THE NEAREST

SIGN [§7.10.1.5.2]

2.3. A DIRECTIONAL SIGN READING "EXIT" WITH A DIRECTIONAL

INDICATOR (CHEVRON STYLE) SHOWING THE DIRECTION OF

TRAVEL SHALL BE PLACED IN EVERY LOCATION WHERE THE

DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT IS NOT

APPARENT [§7.10.2.1/7.10.3.1]

2.4. NEW SIGN PLACEMENT SHALL BE SUCH THAT NO POINT IN

AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE RATED

VIEWING DISTANCE OR 100 FT. TO THENEAREST SIGN [§

7.10.1.5.2]

3. EXIT SIGN ILLUMINATION

3.1. EVERY EXIT SIGN SHALL BE SUITABLY ILLUMINATED BY A

RELIABLE LIGHT

SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS

SHALL BE LEGIBLE IN BOTH THE NORMAL AND EMERGENCY

LIGHTING MODE [§7.10.5.1]

3.2. THE ILLUMINATION SHALL BE FOR 90 MINUTES IN THE CASE OF

PRIMARY POWER LOSS [§7.9.2.1]

3.3. EXIT SIGNS THAT ARE EXTERNALLY ILLUMINATED SHALL HAVE

AN INTENSITY NOT LESS THAN 5 FT-CANDLES [§7.10.6.3]

4. NUMBER AND ARRANGEMENT OF MEANS OF EGRESS

4.2. OCCUPANT LOAD OF 501 - 1,000: 3 EXITS [§7.4.1.2]

4.3. OCCUPANT LOAD OF MORE THAN 1,000: 4 EXITS [§7.4.1.2]

5. ARRANGEMENT OF EXITS

5.1. WHERE TWO OR MORE EXITS ARE REQUIRED, THEY MUST BE

SPACED APART A MINIMUM OF 1/3 THE LENGTH OF THE MAXIMUM

DIAGONAL OF THE BUILDING OR AREA BEING SERVED [§7.5.1.3.3]

4.1. OCCUPANT LOAD OF 1 - 500: 2 EXITS [§7.4.1.1]

4. HEALTH CARE USE (INPATIENT TREATMENT): 240 SF/PERSON

5. HEALTH CARE USE AMBULATORY): 150 SF/PERSON

6. STORAGE, MECH. AND ELEC. AREAS: 500 SF/PERSON

30' 18.2.5.3

BUILDING AREA EXISTING BLDG

MAIN LEVEL = 90,000 S.F.

CLASS A or B [§19.3.3.2]

SEISMIC

SEISMIC RISK CATEGORY: III

0 8' 16' 32'

600 E. Michigan Ave., Suite B

Kalamazoo, MI 49007

P: 269.927.0144 www.7GenAE.com

ARCHITECTURE + ENGINEERING

SEVEN

GENERATIONS

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

KEYPLAN

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

G201.1

FIRST FLOOR CODE

COMPLIANCE PLAN

BID DOCUMENTS02/16/24

PROJECT A

NORTH

SCALE: 1/16" = 1'-0"

FIRST FLOOR CODE

COMPLIANCE PLAN

04/22/25 ADDENDUM 01

A1

DEMOLITION KEY NOTES

REMOVE EXISTING WALL CONSTRUCTION

COMPLETE AS SHOWN. INCLUDING WALL

PROTECTION, WALL BASE, AND ALL ITEMS ATTACHED

TO THE WALLS (NOT ALL ITEMS ATTACHED TO THE

WALLS ARE SHOWN ON THIS PLAN). PATCH &

REPAIR ADJACENT SURFACES TO REMAIN AS

NECESSARY TO PREPARE FOR NEW CONSTRUCTION

AND / OR NEW FINISHES.

REMOVE EXISTING WALL CONSTRUCTION AND LEAD

LINED GYPSUM BOARD AS SHOWN. PATCH &

REPAIR ADJACENT SURFACES TO REMAIN AS

NECESSARY TO PREPARE FOR NEW CONSTRUCTION

AND/OR NEW FINISHES.

REMOVE & SALVAGE EXISTING DOORS(S), FRAME(S),

HARDWARE, ETC. TURN OVER TO COR. AND NOTIFY

COR UNLESS DIRECTED OTHERWISE.

REMOVE & SALVAGE EXISTING DOORS(S), FRAME(S),

HARDWARE, ETC FOR REINSTALLATION.

REMOVE WINDOW FRAME AND LEADED GLASS.

REMOVE EXISTING WALL FINISHES, WALL BASE, AND

ALL ITEMS ATTACHED TO WALLS. PATCH & REPAIR

EXPOSED SURFACES TO REMAIN AS REQUIRED FOR

NEW CONSTRUCTION AND/OR NEW FINISHES.

REMOVE EXISTING FLOORING AND FLOOR FINISHES

INCLUDING ALL ADHESIVES, SETTING MATERIALS

DOWN TO EXISTING SUBSTRATE. PREPARE CONCRETE

FLOORS AS REQUIRED TO PROVIDE A SMOOTH AND

UNIFORM SURFACE FOR NEW FINISHES.

REMOVE EXISTING CEILING TILE AND GRID SYSTEM.

REMOVE EXISTING CEILING MOUNTED LIGHT

FIXTURES (UNLESS NOTED IN CONJUNCTION),

SPEAKERS CAMERAS, FIRE ALARMS, MECHANICAL

DEVICES, SMOKE DETECTORS, SENSORS, WIRELESS

ACCESS POINT, EXIT SIGNAGE, SAFETY MIRRORS,

ETC. TURN OVER TO THE COR. OR SALVAGE TILE FOR

RECYCLING UNLESS DIRECTED OTHERWISE.

REMOVE EXISTING CASEWORK & COUNTERTOP

WITH WALL MOUNTED EQUIPMENT. SALVAGE

EQUIPMENT & TURN OVER TO COR. UNLESS

DIRECTED OTHERWISE. PATCH & REPAIR EXPOSED

SURFACES TO REMAIN AS REQUIRED TO RECEIVE

NEW CONSTRUCTION AND FINISHES.

REMOVE EXISTING MECHANICAL, PLUMBING &

ELECTRICAL ITEMS - REFER TO MECHANICAL,

PLUMBING & ELECTRICAL DEMOLITION PLANS FOR

FURTHER INFORMATION. PATCH AND REPAIR

EXPOSED SURFACES TO REMAIN AS REQUIRED TO

RECEIVE NEW CONSTRUCTION AND FINISHES.

THE CT VENDOR WILL DISASSEMBLE AND REMOVE

THE EXISTING CT EQUIPMENT AND ASSOCIATED

EQUIPMENT (GANTRY, CONSULT DESK, PATIENT

TABLE, POWER DISTRIBUTION UNIT, SERVICE

CABINET, PARTIAL UPS, REAR CABLE COVER).

REMOVE EPOXY PAD, CUT AND GRIND THE EXISTING

ANCHORS FLUSH WITH THE EXISTING FLOOR.

REMOVE EXISTING ISOLATION PODS. SALVAGE

EQUIPMENT & TURN OVER TO COR. REFER TO

MECHANICAL AND ELECTRICAL DEMOLITION

PLANS.

EXISTING WALL FRAMING TO REMAIN. REMOVE

GYPSUM BOARD AND PREPARE FOR NEW FINISHES.

EXISTING WALL FRAMING TO REMAIN. REMOVE

LEAD LINING AND GYPSUM BOARD LAYERS AS

NEEDED TO PREPARE FOR NEW FINISHES AND NEW

WORK. CONTRACTOR TO ASSUME EXISTING LEAD

SHIELDING EXTENDS ABOVE 7'-0" ABOVE FINISH

FLOOR AND IS ALSO CONTINUOUSLY LAMINATED

TO UNDERSIDE OF BAR JOIST. CONTRACTOR TO

PATCH AND INFILL ALL WALL AND CEILING LEAD

LINING INCLUDING AT UNDERSIDE OF EXISTING

STRUCTURE ABOVE.

REMOVE EXISTING HANDRAILS. PROVIDE BLOCKING

AS NEEDED FOR NEW HANDRAILS.

REMOVE AND SALVAGE INJECTOR, HEAD END

MONITOR, CONTROL ARM AND BRACING.

CONTRACTOR IS TO SALVAGE FOR REINSTALLATION

IN NEW LAYOUT, INCLUDING CABLING.

REMOVE ALL WALL MOUNTED ITEMS (SUCH AS PIN

BOARDS, HAND SANITIZERS, TVS, CLOCKS ETC.) TURN

OVER ALL ITEMS TO THE COR. PATCH AND REPAIR

EXPOSED SURFACES TO REMAIN AS REQUIRED TO

RECEIVE NEW CONSTRUCTION AND FINISHES.

REMOVE ALL LOOSE AND WALL MOUNTED

FURNITURE. TURN OVER ALL ITEMS TO COR. PATCH &

REPAIR ADJACENT SURFACES TO REMAIN AS

NECESSARY TO PREPARE FOR NEW CONSTRUCTION

AND/OR NEW FINISHES.

SAWCUT AND REMOVE A PORTION OF EXISTING

CONCRETE SLAB AND GRADE BASE IN PREPARATION

FOR NEW ELECTRICAL CONDUIT TRENCH.

SAWCUT AND REMOVE A PORTION OF EXISTING

CONCRETE SLAB AND GRADE BASE IN PREPARATION

FOR NEW FLOOR DRAIN AND SANITARY

LINE/CONNECTIONS. EXACT LOCATION TO BE

DETERMINED IN FIELD, THROUGH GROUND-

PENETRATING RADAR OR OTHER METHODS.

AREA NOT IN SCOPE

LINE OF EXISITING FOUNDATION WALLS

1A

WAITING

SECURITY

1556A

CONTROL 1556

CT SCAN

ORTHO

CORRIDOR

CORRIDOR

CORRIDOR

1A

1A

6 7

PORTION OF CEILING

TO BE REMOVED

AND REPLACED.

EXTENT OF CEILING

DEMOLITION ABOVE

TRENCH

1'-2" 2'-0"

/2

/2

/8

8'-9 1/4"

1'-2" VERIFY W/ CT MANUFACTURER

2'-7 1/2" VERIFY W/ CT MANUFACTURER

EXACT DIMENSIONS TO BE COORDINATED IN FIELD W/ CT VENDOR

30'-10 5/8" +/-

/4

14 13

6 76

ED.7D.2D

8 8

REMOVE DECORATIVE

COLUMN

REMOVE GLASS

BLOCK WALL

REMOVE COAT

HANGER ON BACK

OF DOOR, DOOR TO

REMAIN

REMOVE

ROOM SIGN

17 18

17 18

REMOVE ROOM

SIGN & ACCESS

BUTTON

/8

EXISTING MED GAS TO REMAIN.

CONTRACTOR TO REMOVE COVER

PLATES (STORE FOR REINSTALLATION)

TO FACILITATE GYP BOARD

DEMOLITION.

SLAB ON GRADE

EXISTING CRAWLSPACE

SLAB ON GRADE EXISTING CRAWLSPACE

SLAB ON GRADE

EXISTING CRAWLSPACE

EXISTING CEILING TO REMAIN

REWORK EXISTING GRID AND

TILES AS REQUIRED TO

ACCOMODATE NEW CEILING

REMOVE EXISTING

WALL PAPER BORDER

REMOVE "X-RAY

IN USE" LIGHT

PROTECT EXISTING ADJACENT

WALL TILE TO REMAIN

REMOVE EXISTING COILING

SECURITY WINDOW COMPLE TE

INCLUDING ALL TRACKS,

BRACKETS, WALL SUPPORT AND

HEADER

A1

A1

GENERAL DEMO NOTES

1. ALL DEMOLITION WORK REQUIRED IS NOT NECESSARILY LIMITED

TO WHAT IS SHOWN ON THE DEMOLITION PLANS. THE INTENT IS

TO REMOVE ALL MATERIALS AND ITEMS AS REQUIRED TO

FACILITATE NEW CONSTRUCTION.

2. CONTRACTORS ARE TO VERIFY FIELD CONDITIONS, IF

CONDITIONS DO NOT REFLECT WHAT IS NOTED IN THE

CONTRACT DOCUMENTS, THE CONTRACTOR IS TO NOTIFY THE

ARCHITECT.

3. THIS PLAN IS TO BE USED IN CONJUNCTION WITH THE ENTIRE SET

OF CONSTRUCTION DOCUMENTS. DO NOT REMOVE ANY ITEMS

WITHOUT VERIFYING AND COORDINATING WITH ALL GENERAL

TRADES AS TO HOW THEY RELATE TO THE OVERALL PROJECT.

4. CONTRACTOR IS RESPONSIBLE FOR PROVIDING DUMPSTERS.

LOCATION OF DUMPSTERS TO BE DETERMINED BY COR. WITH

CONTRACTORS INPUT.

5. CONTRACTOR SHALL REMOVE AND DISPOSE OF ALL

DEMOLISHED MATERIALS. DO NOT ALLOW MATERIALS AND

DEBRIS GENERATED BY DEMOLITION ACTIVITIES TO

ACCUMULATE ON THE JOBSITE. REMOVE DAILY AND DISPOSE

OF IN A LEGAL MANNER. NO ONSITE SALE OR BURNING OF

REMOVED ITEMS IS PERMITTED.

6. THE CONTRACTOR MUST TAKE ALL NECESSARY PRECAUTIONS

TO ENSURE THE SAFETY OF THE PUBLIC AND/OR WORKMEN ON

THE SITE TO PREVENT ACCIDENTS OR INJURY TO ANY PERSON

ON, ABOUT OR ADJACENT TO THE PREMISES. THE CONTRACTOR

SHALL COMPLY WITH ALL LAWS, ORDINANCES, CODES AND

REGULATIONS PERTAINING TO SAFETY AND THE PREVENTION OF

ACCIDENTS.

7. THE CONTRACTOR MUST MAINTAIN ADEQUATE SUPPORT,

INSULATION, WATERPROOFING, EMERGENCY LIGHTING,

SECURITY, ALARMS, ETC. FOR ALL OR PART OF ITEMS WHICH

ARE TO REMAIN.

8. THE COR. RESERVES THE RIGHTS TO ANY REMOVED MATERIALS

OR ITEMS. CONTRACTOR TO COORDINATE WITH COR.

9. DO NOT CUT AND/OR PATCH STRUCTURAL ELEMENTS IN A

MANNER THAT COULD CHANGE THEIR LOAD-CARRYING

CAPACITY OR LOAD-DEFLECTION RATIO.

10. PATCH/REPAIR OR REPLACE ALL AREAS DAMAGED BY

DEMOLITION, REWORK AS REQUIRED, PREPARE FOR NEW

CONSTRUCTION AS REQUIRED. BRICK OR BLOCK PATCHING

SHALL BE TOOTHED-IN TO MATCH EXISTING COURSING

PATTERN.

11. WHERE WALLS & CEILINGS ARE TO BE REMOVED, ALL ITEMS

THAT FALL WITH THE WALLS &/OR CEILINGS ARE TO BE

REMOVED OR REROUTED. REFER TO MECHANICAL, ELECTRICAL,

AND PLUMBING PLANS FOR ADDITIONAL DEMOLITION NOT

SHOWN ON THIS SHEET.

12. CONSTRUCTION AREAS TO BE COMPLETELY SEPARATED FROM

OCCUPIED AREAS WITH A ONE-HOUR FIRE RATED ASSEMBLY,

AND WITH SUITABLE DUST BARRIER. TEMPORARILY SEAL OFF ALL

RETURN & SUPPLY AIR DIFFUSERS IN CONSTRUCTION AREA.

PROVIDE RECIRCULATING HEPA FILTER IN CONSTRUCTION

AREA. ALL DEMOLISHED MATERIAL IS TO BE REMOVED FROM

SITE IN A COVERED CONTAINER. NEGATIVE AIR PRESSURE TO BE

MAINTAINED WITHIN CONSTRUCTION ZONE.

13. IF HAZARDOUS MATERIALS ARE ENCOUNTERED DURING

DEMOLITION, CONTRACTOR SHALL CONTACT COR. FOR

ABATEMENT. (LEAD GYP. BACKING IS TO BE REMOVED BY

CONTRACTOR AND DOES NOT REQUIRE COR. ABATEMENT).

14. REMOVE, REPLACE, PATCH, AND REPAIR MATERIALS AND

SURFACES CUT OR DAMAGED DURING DEMOLITION, BY

METHODS AND WITH MATERIALS SO AS NOT TO VOID EXISTING

WARRANTIES.

15. CLEAN AREAS AND SPACES WHERE CUTTING AND PATCHING

ARE PERFORMED.

16. CONTRACTOR SHALL PATCH, REPAIR, AND INFILL ALL APPLIED

FIREPROOFING MATERIAL IN AREAS LEFT UNPROTECTED DUE TO

REMOVAL OF EXISTING ELEMENTS OR AREAS DAMAGED

DURING NEW WORK AND DEMOLITION. MATCH EXISTING

FIREPROOFING MATERIAL TYPE AND THICKNESS TO MAINTAIN

REQUIRED LEVEL OF PROTECTION.

0 2' 4' 8'

600 E. Michigan Ave., Suite B

Kalamazoo, MI 49007

P: 269.927.0144 www.7GenAE.com

ARCHITECTURE + ENGINEERING

SEVEN

GENERATIONS

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

KEYPLAN

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

AD101.1

FIRST FLOOR DEMOLITION

PLAN

BID DOCUMENTS02/16/24

04/22/25 ADDENDUM 01

PROJECT A

NORTH

SCALE: 1/4" = 1'-0"

FIRST FLOOR DEMOLITION PLAN

04/22/25 ADDENDUM 01

SECURITY

13'-4"

FAMILY CONSULT

1556A

CONTROL ROOM

1556B

CHANGING

CT SCAN

/8

/2

LE

A

D G

L A

S S

/8

50'-5 15/16" +/-

A420.101

101A

104A420.1

A420.1

CORRIDOR

AREA NOT IN SCOPE

9'-0"

D4

E6

C4

A6

A4

A4

C4

10'-0"

A420.1

A420.1

A420.1 08

A420.1

A4

G6

F12

E6

G4

G4

ELEVATOR

ED.7D.2D

E6

A

B

A420.1

F12

D4

09 11

H4H4

H4

H4

H4 H4

H4

H4

EXSITING WALL FRAMING TO REMAIN

PROVIDE NEW FINISHES ON BOTH SIDES OF

WALL FRAMING. NEW FINISHES TOBE

CONSISTENT WITH WALL TAGS ON EITHER SIDE

1'-4" lOCATION FOR FUTURE SECURITY MONITORS

B6

9'-6"

CLEAR

3'-0"

A1

A1

A1

A420.1

A420.1

SIM

FLOOR PLAN LEGEND

EXISTING WALL

NE WALL

EXISTING DOOR

NEW DOOR

1-HOUR FIRE RATED PARTITION - UL DES U419

2-HOUR FIRE RATED BARRIER - UL DES U419

1-HOUR SMOKE BARRIER - NFPA 101 - 8.3

NEW CONCRETE SLAB, DEPTH TO MATCH

EXISTING, WITH WELDED WIRE FABRIC ON

NEW VAPOR BARRIER ON COMPACTED

GRANULAR FILL ON COMPACTED

SUBGRADE. REFER TO PLUMBING DRAWINGS.

ABBREVIATIONS:

A = ARCHITECT

C = CONTRACTOR

G = GOVERNMENT

O = OWNER

V = VENDOR

X = ITEM TO BE INCLUDED WITH ASSOCIATED EQUIPMENT

A420.101

A420.1

A420.1

04 19

A420.1

A420.1 0807

ED.7D.2

CT TABLE

CEILING MOUNTED

INJECTOR

BENCHMIR

RH1UPS

PTD1

SD1

PDU1

MDC1

FAMILY CONSULT

1556A

CONTROL ROOM

1556B

CHANGING

CT SCAN

50'-5 15/16" +/-

IN USE LIGHT

IN USE LIGHT

AR1

HS1

ST1

CLK1

SH1

GLB1

ISO POINT

9'-0 5/8"

BW

HS1

PB1

CB

LKR LKR

/2

PP PP

CG1

CG1

CG1

CG1

CG1

A420.1

CT FLOOR RACEWAY

SYSTEM NOTES

WALL RACEWAY FROM FLOOR TO ABOVE CEILING.

WALL RACEWAY SHALL CONNECT TO CEILING

RACEWAY AND FLOOR TRENCH DUCT. RACEWAY SHALL

BE SIZED BY CT MANUFACTURER WITH (1) DIVIDERS.

FLOOR TRENCH DUCT 3-1/2"H X 10"W WITH (1) DIVIDERS,

REMOVABLE COVERS AND MOISTURE GASKETS.

A

B

GENERAL NOTES

1. INTERSECTION BETWEEN ALL RATED WALL SYSTEM AND

DECK SYSTEM TO BE SEALED WITH APPROVED UL FIRE SPRAY

MATERIAL.

2. REFER TO CODE COMPLIANCE FOR RATED WALL LOCTIONS.

3. PROVIDE UL RATED WALLS WHERE SHOWN. REFER TO WALL

TYPES FOR WALL CONSTRUCTION.

4. ALL COUNTERTOP OUTSIDE CORNERS TO BE 2" RADIUS

UNLESS NOTED OTHERWISE.

5. PROVIDE METAL BLOCKING WITHIN WALL CAVITY AS

REQUIRED FOR WALL MOUNTED EQUIPMENT AS SHOWN ON

ENLARGED PLANS AND ON INTERIOR ELEVATIONS.

COORDINATE FINAL LOCATIONS WITH OWNER.

6. ALL WALL BOARD CARRYING CERAMIC TILE SHALL BE

CEMENT BOARD - REFER TO FINISH SCHEDULE.

7. ALL WALLS CARRYING PLUMBING FIXTURES SHALL BE 5/8"

MOISTURE RESISTANT FIRECORE GYP BOARD UNLESS NOTED

OTHERWISE.

8. CONTRACTOR SHALL PATCH, REPAIR, AND INFILL ALL

APPLIED FIREPROOFING MATERIAL IN AREAS LEFT

UNPROTECTED DUE TO REMOVAL OF EXISTING ELEMENTS

OR AREAS DAMAGED DURING NEW WORK AND

DEMOLITION. MATCH EXISTING FIREPROOFING MATERIAL

TYPE AND THICKNESS TO MAINTAIN REQUIRED LEVEL OR

PROTECTION.

9. CONTRACTOR TO INSTALL 1/16" LEAD EQUIVALENT

BACKING ON ALL VOIDS AND PENTRATIONS IN THE WALL

SHIELDING.

10. ALL INTERIOR DIMENSIONS ARE TO FACE OF DRYWALL.

REFER TO WALL TYPES ON A001 FOR ADDITIONAL WALL

INFORMATION.

11. THE CONCRETE FLOOR MUST BE LEVEL WITHIN 3/8"

MAXIMUM DEVIATION IN THE AREA AROUND THE BASE OF

THE GANTRY AND THE BASE OF THE PATIENT TABLE. PROVIDE

CEMENTITIOUS FLOOR LEVELER AS REQUIRED.

12. WHERE FIRE RATED SEPARATIONS ARE SHOWN IN CODE

PLANS PROVIDE STENCILING EVERY 20'-0'' HORIZONTALLY

WITHIN THE CEILING PLENUM SPACE WITH THE FOLLOWING

13. PROVICE GYP BOARD CONTROL JOINTS ON BOTH SIDES OF

THE DOOR. TYPICAL AT ALL NEW DOORS.

0 2' 4' 8'

600 E. Michigan Ave., Suite B

Kalamazoo, MI 49007

P: 269.927.0144 www.7GenAE.com

ARCHITECTURE + ENGINEERING

SEVEN

GENERATIONS

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

KEYPLAN

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

A101.1

FIRST FLOOR PLAN

BID DOCUMENTS02/16/24

PROJECT A

NORTH

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN - CT ROOM

RENOVATION

EQUIPMENT SCHEDULE - A

ABBREV. EQUIPMENT DESCRIPTION S

P

E C

IF

IE

D B

Y

S U

P P

L

IE

D B

Y

IN

S T A

L L E D

B Y

E L E C

D A

T A

C A

B L E T

V

B L O

C K

IN

G

W A

T E R

D R

A

IN

BASIS OF DESIGN -

MANUFACTURER

BASIS OF DESIGN -

MODEL REMARKS

AR1 APRON RACK A C C X PHILLIPS SAFETY 7 APRON PEG RACK

BW BLANKET WARMER G G G X MAC MEDICAL MODEL DWC243074T

CB CODE BLUE CALL BUTTON A C C X REFER TO LOW VOLTAGE DRAWINGS

CG1 CORNER GUARD A C C CONSTRUCTION SPECIALTIES REFER TO FINISH KEY

CL1 BARIATRIC PATIENT CEILING LIFT A C C X X ARJO / GULDMANN

CLK1 CLOCK G G C X X X

GLB1 GLOVE BOX G G C X BOBRICK

HS1 HAND SANITIZER G G C X PURELL

MDC1 MAIN DISCONNECT CONTROL G C C GE

MIR MIRROR: 24"x60" A C C X BOBRICK B-167 SERIES

PB1 PATIENT TRANSFER BOARD A C C X GE

PDU1 POWER DISTRIBUTION UNIT G C C X X GE PROVIDED BY CT EQUIPMENT

SUPPLIER

PP BARRIER FREE PUSH PLATE A C C X REFER TO DOOR HARDWARE

PTD1 PAPER TOWEL DISPENSER G G C X

RH1 ROBE HOOK A C C X BRADLEY CORPORATION 9B1-110200 DOUBLE HOOK

SD1 SOAP DISPENSER G G C X

SH1 SHARPS CONTAINER G G C X BOBRICK 305017

ST1 STRETCHER G G G

NORTH

SCALE: 1/4" = 1'-0"

FIRST FLOOR EQUIPMENT PLAN

AR1

PDU1

PTD1 SD1GLB1

MDC1

A520.1

A520.1

A701.1

A701.1

A520.1

6'-0"

F.E.P.

1'-3"

F.E.P.

1'-6" 2'-1"

W P

-1

S E E S

C H

E D

U

LE

SCHD.

SEE

S E E S

C H

E D

U

LE

S E E S

C H

E D

U

LE

SCHD.

SEE

SCHD.

SEE

2"

SCHD.

SEE 2"

S E E S

C H

E D

U

LE

A B C D1

DOOR TYPES

SCALE: 1/4" = 1'-0"

FRAME TYPES

SCALE: 1/4" = 1'-0"

6" 4"

6'-0"

LEAD GLAZING

FLOOR

LINE

6"6"

SCHD.

SEE

S E E S

C H

E D

U

LE

MIRMIR

A520.1

A520.1

FILLER

1' - 0"

F.E.P.

1' - 0"

F.E.P.

1' - 11"

1'-6" 2'-0"

11 1/8" 6'-0"

HS1

LEAD GLAZING AND

LEAD LINED HOLLOW

METAL FRAME

A420.1

CL1

W P

-1

CG1

OAV

A701.1

A701.1 20

A420.1

F.E.P.

3'-0"FILLER

CG1

A520.1

BW

CG1

S2

LEAD BACKED GYP. BD. INSTALLED

CONTINUOUS FROM FLOOR TO 7'-0"

ABOVE FINISH FLOOR.

RADIATION

ROOM SIDE

CONTROL

ROOM SIDE

16 GA. STEEL FRAME, 2 PIECE

TELESCOPIC WINDOW FRAME AND

STOP, W/ MITER CORNERS.

2"

1/16" LEAD SHIELDING AT INSIDE

OF FRAME INCLUDING PROFILE

LEAD LINED GLASS, 1/16"

LEAD EQUIVALENT

FACTORY SET STOPS

3/8"

SPECIFICATION NOTES:

1. THE LEAD SHIELDING VALUE TO BE THE SAME

AS THE SURROUNDING WALL, PARTITION OR

CEILING. (SEE PLANS OR PHYSICIST RADIATION

SHIELDING REPORT FOR LEAD THICKNESS

VALUES).

2. ALL SHEET LEAD IS 99.9% PURE MEETING

FEDERAL SPC QQ-L-201F GRADE C AND ASTM

B749 TYPE L51121 AND ALL APPLICABLE NCRP

REPORTS.

3. ENSURE IF LEAD IS PENETRATED IT SHALL HAVE

A CONTINUOUS LEAD SHIELDING WRAP

CL1

PB1

SH1

CG1

HS1

OAV

W P

-1

A701.1

A701.1

MDC1

CL1

C4

CB

CG1

PDU1

A520.1

RAKKS BRACKET; 3'-0" O.C. TYP. FINAL

LOCATION TO BE COORDINATED WITH OWNER.

COUNTERTOP W.

GROMMET; COORD.

LOCATION W. OWNER 2

FILLER 2'-6"

F.E.P.

2'-6"

A520.1

A520.1

FILLER 2'-6"

F.E.P.

2'-6"

W P

-1

S1

BG-1; BUMPER GUARD

HR-1; HANDRAIL

S1

A701.1

A701.1

W P

-1

CG1

HR-1; HANDRAIL

BG-1; BUMPER GUARD

A701.1

A701.1

W P

-1

CG1

S1 HR-1; HANDRAIL

BG-1; BUMPER GAURD

A701.1

A701.1

A420.1

/2

8'-3 5/8"

LEAD GLAZING AND

LEAD LINED HOLLOW

METAL FRAME

A520.1

RAKKS BRACKET;

36" O.C. MAX

PAINTED WRAP-AROUND HOLLOW

METAL DRYWALL FRAME. LEAD

LINED HOLLOW METAL FRAME AT

LEAD LINED DOORS.

OPTIONAL SECURITY ANCHOR AT

HEAD FOR FRAMES WIDER THAN 3'-0"

SEALANT CONTINUOUS @

PERIMETER (BOTH SIDES)

LT. GA. METAL BOX HEADER

CLOSER AS REQ'D - (SEE SCHED.)

PAINTED WRAP-AROUND

HOLLOW

METAL DRYWALL FRAME. LEAD

LINED HOLLOW METAL FRAME

AT LEAD LINED DOORS.

JAMB ANCHORS (2 PER JAMB-

& ADJ. BASE ANCHORS - TYP.)

DOUBLE METAL STUD

@ EA. JAMB

SEALANT CONTINUOUS @

PERIMETER (BOTH SIDES)

ADJACENT WALL

(WHERE OCCURS)

CG1CG1

HR-1; HANDRAIL BG-1; BUMPER GUARD

W P

-1

S2 S2 S2

A701.1

A701.1

/2

V.I.F. 10" V.I.F.

EXISTING 5" CONC. SLAB. PATCH

AND REPAIR TO ALLOW A

UNIFORM TRANSITION TO THE

NEW TRENCH

ELECTRICAL TRENCH DUCT.

REFER TO ELECTRICAL AND

CT EQUIPMENT SUPPLIER

NEW CONCRETE

VAPOR BARRIER

COMPACTED GRANULAR FILL

ON COMPACTED SUBGRADE

#4 DOWEL (4" @ 1'-6" O.C.)

A520.1

RAKKS BRACKET; 3'-0" O.C. TYP.

FINAL LOCATION TO BE

COORDINATED WITH OWNER.

WELDED WIRE FABRIC

#4 DOWEL (4" @ 1'-6" O.C.)

NEW CONCRETE

VAPOR BARRIER

COMPACTED GRANUAL FILL

(NEW PLUMBING NOT SHOWN)

600 E. Michigan Ave., Suite B

Kalamazoo, MI 49007

P: 269.927.0144 www.7GenAE.com

ARCHITECTURE + ENGINEERING

SEVEN

GENERATIONS

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

KEYPLAN

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

A420.1

INTERIOR ELEVATIONS

AND DOOR SCHEDULE

BID DOCUMENTS02/16/24

04/17/25 ADDENDUM 01

PROJECT A

DOOR AND FRAME SCHEDULE BP1

DOOR

NUMBER SIZE

DOOR FRAME FIRE RATING

(MIN.) HARDWARE SET REMARKSTYPE MATERIAL TYPE MATERIAL

101 (2) 3'-0" D HM 1 HM 90 MIN. 04 LEAD LINED FRAME AND DOOR, AUTO OPERATOR, PANIC BARS.

101A 4'-0" X 7'-0" A 1 HM 01 OWNER PROVIDED LEAD LINED DOOR.CONTRACTOR INSTALLED.

103 3'-0" X 7'-0" B WD 1 HM 20 MIN. 02

104 3'-0" X 7'-0" A WD 1 HM 20 MIN. 03

105 (2) 3'-0" x 7'-0" B WD 1 HM 20 MIN. 05 AUTO OPERATOR, PANIC BARS, CARD READER ON CORRIDOR 1559 SIDE.

SCALE: 1/4" = 1'-0"A420.1

CT SCAN - 10101

SCALE: 1/4" = 1'-0"A420.1

LOCKER ROOM 10406

SCALE: 1/4" = 1'-0"A420.1

CT SCAN - 10103

SCALE: 1/4" = 1'-0"A420.1

CT SCAN - 10105

SCALE: 1 1/2" = 1'-0"A420.1

WINDOW FRAME DETAIL19

SCALE: 1/4" = 1'-0"A420.1

CT SCAN - 10102

SCALE: 1/4" = 1'-0"A420.1

CT SCAN - 10104

SCALE: 1/4" = 1'-0"A420.1

SECURITY ROOM 10610

SCALE: 1/4" = 1'-0"A420.1

CONTROL ROOM 10208

SCALE: 1/4" = 1'-0"A420.1

CORRIDOR 10515

SCALE: 1/4" = 1'-0"A420.1

CORRIDOR 10514

SCALE: 1/4" = 1'-0"A420.1

CORRIDOR 10512

SCALE: 1/4" = 1'-0"A420.1

CONTROL ROOM 10207

SCALE: 1 1/2" = 1'-0"A420.1

DOOR HEAD DETAIL17

SCALE: 1 1/2" = 1'-0"A420.1

DOOR JAMB DETAIL18

SCALE: 1/4" = 1'-0"A420.1

CORRIDOR 10513

SCALE: 1 1/2" = 1'-0"A420.1

TRENCH DETAIL16

SCALE: 1/4" = 1'-0"A420.1

SECURITY ROOM 10609

SCALE: 1/4" = 1'-0"A420.1

SECURITY ROOM 10611

04/22/25 ADDENDUM 01

A1

A1

SCALE: 1 1/2" = 1'-0"A420.1

SLAB INFILL DETAIL20

AREA NOT IN SCOPE

USS1

CONTROL RM

1556A

FAMILY CONSULT

SECURITY

CORRIDOR

CORRIDOR

Space

TREADMILL

2" FD-3

2" SS

1 1/2" V

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

P101.1

FIRST FLOOR SANITARY

AND VENT PLAN

BID DOCUMENTS02/16/24

PROJECT A

KEYNOTES

1 CONNECT NEW SANITARY PIPING TO EXISTING SANITARY

PIPING. 2" MINIMUM. FIELD VERIFY CONDITIONS.

2 CONNECT NEW VENT PIPING TO EXISTING VENT PIPING. 2"

MINIMUM. FIELD VERIFY CONDITIONS.

3 ROUTE DRAIN LINE FROM HUMIDIFER IN WALL DOWN TO

FLOOR DRAIN. TERMINATE DRAIN PIPE AT FLOOR DRAIN WITH

AIR GAP. ROUTE 2" DRAIN LINE FROM FLOOR DRAIN TO

NEAREST EXISTING SANITARY LINE.

PLUMBING NOTES

1 THIS PLAN IS DIAGRAMMATIC IN NATURE AND SHALL NOT BE

SCALED TO DETERMINE THE LOCATION OR DIMENSION OF THE

WORK. CONTRACTOR SHALL VERIFY EXACT LOCATION OF

PIPING AND PENETRATIONS.

2 CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THE

STRUCTURAL MEMBERS IS PROHIBITED.

3 WALL-MOUNTED ACCESS PANELS SHALL BE LOCKABLE TYPE.

4 CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE LOCATION

OF EXISTING BELOW GRADE WASTE PIPING AND REFLECT ANY

DEVIATION GREATER THAN 1'-0" FROM THIS PLAN ON THE

AS-BUILT DRAWINGS.

SANITARY & VENT NOTES

1 ALL SANITARY DRAINAGE (SS) PIPING IS LOCATED BELOW SLAB,

UNLESS OTHERWISE NOTED.

2 ROUTE ALL PIPING INTENDED FOR ABOVE CEILING LEVEL

INSTALLATION AS HIGH AS POSSIBLE. COORDINATE ROUTING

WITH OTHER TRADES. SLOPED PIPING ELEVATIONS TAKE PRIORITY

OVER ALL OTHER SYSTEMS AND TRADES.

3 PROVIDE SLEEVED AND WATERTIGHT PENETRATIONS AT ALL PIPE

PENETRATIONS THROUGH: LOWER LEVEL FLOOR SLAB, UPPER

LEVEL FLOOR SLAB, MECHANICAL PENTHOUSE FLOOR SLAB,

ROOF STRUCTURES AND, PERIMETER WALLS BELOW GRADE.

4 PROVIDE WATERTIGHT INSTALLATIONS OF ALL FLOOR EMBEDDED

DEVICES INCLUDING BUT NOT LIMITED TO: FLOOR DRAINS,

FLOOR SINKS, SHOWER DRAINS, HUB DRAINS, FLOOR RECESSED

CLEANOUTS AND, FLUSH TO FLOOR ACCESS HOUSINGS.

5 COORDINATE WITH ARCHITECT TO MAINTAIN THE WATERTIGHT

INTEGRITY OF THE BUILDING ENVELOPE AND FLOOR SLABS.

NORTH

SCALE: 1/4" = 1'-0"

BP1 - FIRST FLOOR WASTE & VENT PLAN

USS11

CONTROL RM

1556A

FAMILY CONSULT

SECURITY

CORRIDOR

CORRIDOR

Space

TREADMILL

EWH-01 1/2" CW

KE-31

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

P201.1

FIRST FLOOR DOMESTIC

WATER AND GAS PLAN

BID DOCUMENTS02/16/24

PROJECT A

KEYNOTES

1 CONNECT COLD WATER TO EXISTING COLD WATER PIPING.

1/2" MINIMUM. FIELD VERIFY CONDITIONS.

2 CONNECT EXISTING HOT WATER TO UNDER COUNTER WATER

HEATER INPUT. ROUTE WATER HEATER OUTPUT TO EXTERNAL

ASSE 1070 COMPLIANT THERMOSTATIC MIXING VALVE.

3 CONNECT OXYGEN, MEDICAL AIR, AND MEDICAL VACUUM

TO NEW HEADWALL.

4 CONNECT UNDERFLOOR 1/2" COLD WATER LINE UP TO HM-01

HUMIDIFIER. PROVIDE WALL MOUNTED VALVE BOX.

PLUMBING NOTES

1 THIS PLAN IS DIAGRAMMATIC IN NATURE AND SHALL NOT BE

SCALED TO DETERMINE THE LOCATION OR DIMENSION OF THE

WORK. CONTRACTOR SHALL VERIFY EXACT LOCATION OF

PIPING AND PENETRATIONS.

2 CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THE

STRUCTURAL MEMBERS IS PROHIBITED.

3 WALL-MOUNTED ACCESS PANELS SHALL BE LOCKABLE TYPE.

4 CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE LOCATION

OF EXISTING BELOW GRADE WASTE PIPING AND REFLECT ANY

DEVIATION GREATER THAN 1'-0" FROM THIS PLAN ON THE

AS-BUILT DRAWINGS.

DOMESTIC WATER NOTES

1 PROVIDE SLEEVED AND WATERTIGHT PENETRATIONS AT ALL PIPE

PENETRATIONS THROUGH: LOWER LEVEL FLOOR SLAB AND,

PERIMETER WALLS BELOW GRADE.

2 PROVIDE WATERTIGHT INSTALLATIONS OF ALL FLOOR EMBEDDED

DEVICES INCLUDING BUT NOT LIMITED TO: FLOOR DRAINS,

FLOOR RECESSED CLEANOUTS.

3 COORDINATE WITH ARCHITECT TO MAINTAIN THE WATERTIGHT

INTEGRITY OF THE BUILDING ENVELOPE AND FLOOR SLABS.

4 PROVIDE BALL VALVE FOR ISOLATION OF ALL DOMESTIC WATER

BRANCH LINES. TYPICAL UNLESS OTHERWISE NOTED.

NORTH

SCALE: 1/4" = 1'-0"

BP1 - FIRST FLOOR DOMESTIC WATER PLAN

04/22/25 ADDENDUM 01

BradenCox Callout at what elevation?

PIPE

HIGH DENSITY

INSULATION

INSERT, REFER TO

THE

SPECIFICATIONS

CLEVIS HANGER

INSULATION

PIPE RING HANGER

GALVANIZED

STEEL SHIELD

HOT WATER

TO FAUCET

1/2" HOT WATER

SHUT-OFF VALVE

COLD WATER

TO FAUCET

INSTANTANEOUS ELECTRIC WATER HEATER. MOUNT

ON BACK WALL UNDER SINK. LOCATE TO MAKE

ACCESSIBLE FOR REPLACEMENT AND NOT

OBSTRUCTING UNDER SINK PLUMBING OF STORAGE.

LAVATORY OR SINK

THERMOSTATIC

MIXING VALVE

1/2" COLD WATER

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

P500.1

PLUMBING DETAILS AND

SCHEDULES

BID DOCUMENTS02/16/24

PROJECT A

SCALE: NTSP500.1

INSULATED PIPE AT HANGER DETAIL1

PLUMBING FIXTURE SCHEDULE

MARK DESCRIPTION MANUFACTURER MODEL NO.

MATERIAL

DESCRIPTION FINISH

TRIM FLOW FIXTURE FLUSH FIXTURE

WASTE

ROUGH-IN

PIPE SIZE

INDIRECT

WASTE

PIPE SIZE

VENT

PIPE

SIZE

COLD WATER

ROUGH-IN

PIPE SIZE

HOT WATER

ROUGH-IN

PIPE SIZE DESCRIPTION NOTESMANUFACTURER MODEL NO. TYPE

MOTION

SENSOR

CONTROL WATER FLOW

MAX.

MWT

VOL. PER

FLUSH

MIN. VOL.

PER FLUSH

KE-31 OUTLET BOX SIOUX CHIEF 696-RG1010MF ABS PLASTIC WHITE No 0.5 GPM 105 °F 1/2" GALVANIZED METAL CONSTRUCTION-NO PLASTIC BOXES ALLOWED

USS1 UNDERMOUNT SOLID

SURFACE SINGLE BOWL SINK

WILSONART AK2015 SOLID SURFACE

SS-3

SOLID

SURFACE

ELKAY LK406GN04T4 MANUAL No 1.5 GPM 105 °F 2" 1 1/2" 1/2" 1/2" SINGLE BOWL, UNDER COUNTER MOUNTED, SOLID SURFACE. SINGLE LEVER SWIVEL FAUCET WITH AN EXTERNAL ASSE 1070 COMPLIANT THERMOSTATIC MIXING VALVE. ONE ELKAY MODEL NO. LK35 BASKET STRAINER, P-TRAP, TAILPIECES, SUPPLIES AND STOPS. REFER TO FINISH PLANS FOR FURTHER

SINK AND COUNTERTOP INFORMATION. REFER TO FINISH KEY IN ARCHITECT PLANS FOR

ADDITIONAL MATERIAL INFORMATION. INSTALL WITH INCLUDED 1.5 GPM AERATOR.

ELECTRIC WATER HEATER SCHEDULE

MARK MANUFACTURER MODEL NO. TYPE

ELECTRIC HEAT EXCHANGER

EF

UNIT

WEIGHT FLA MOCP VOLT PH NOTES

HEATING

CAPACITY

FLOW ENTERING

WATER

TEMPERATURE

LEAVING

WATER

TEMPERATURE

MAXIMUM

TEMPERATURE

RISEDESIGN MIN MAX

EWH-01 BOSCH TR4000C-6 TANKLESS 6.5 kW 1.3 GPM 0.5 GPM 1.5 GPM 70 °F 105 °F 35 °F 0.96 4 lb 30 A 40 A 208 V 1

SCALE: NTSP500.1

INSTANTANEOUS ELECTRIC BOOSTER WATER HEATER2

SCHEDULE NOTES:

1. INSULATE THE SUPPLY AND DRAIN PIPING WITH A WHITE INSULATION DEVICE EQUAL TO McGUIRE MODEL NO. PW-2150-WC AND PROVIDE A THERMOSTATIC MIXING VALVE ON THE SUPPLIES EQUAL TO WATTS MODEL NO. USG-B.

FLOOR DRAIN SCHEDULE

MARK DESCRIPTION MANUFACTURER MODEL NO.

MATERIAL

DESCRIPTION WASTE VENT

DESCRIPTION NOTESDRAIN BODY PIPE SIZE PIPE SIZE

FD-3 FLOOR DRAIN ZURN Z415S EPOXY COATED

CAST IRON

2" 1 1/2" DURA COATED CAST IRON FLOOR DRAIN WITH ANCHOR FLANGE, INVERTIBLE MEMBRANE CLAMP, TRAP PROTECTION INSERT, AND ADJUSTABLE COLLAR WITH SEEPAGE SLOTS, ADJUSTABLE HEAVY

DUTY SQUARE HEEL PROOF NICKEL BRONZE STRAINER, AND NO HUB OUTLET.

FPVAV-10.4

CC-1

VAV-XX

S6L1

S10L1

"x

S /A 8"Ø S/A8"Ø S/A

S16L1

S16L1

S12L1

"x

R /A

10"Ø S-O/A

20"x20" S/A16"Ø S/A

16"Ø S/A

S8L1

8"x8" S/A

R14L1

R14L1

(E) O/A

8"Ø S/A (E)

R8L1

R10L1

E R/A

14"Ø R/A

14"Ø R/A

8"Ø R/A

B

9 9

CORRIDOR

SECURITY

CORRIDOR

FAMILY CONSULT

CHANGING

1556B

CT SCAN

CT SCAN

CONTROL RM

1556A 18"x14" R/A10"Ø S-O/A

12"Ø S/A

20"x20" S/A

10"Ø R/A

12"Ø R/A

AC-1

CU-1

HM-01

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

M101.1

FIRST FLOOR

MECHANICAL PLAN

BID DOCUMENTS02/16/24

PROJECT A

KEYNOTES

1 REBALANCE EXISTING RETURN GRILLE TO 190 CFM.

2 RELOCATE EXISTING FAN COIL UNIT (FPVAV-10.4) AND

COOLING COIL (CC-1) AS SHOWN.

3 NEW LOCATION FOR THE RELOCATED SECONDARY DRAIN

PAN UNDER COOLING COIL. INSTALL WITH MOISTURE SENSOR

INTERLOCKED WITH FPVAV-10.4 TO SHUT-DOWN OPERATION

UPON DETECTION OF MOISTURE.

4 DUCT CONTINUES AND CONNECTS TO BRANCH DUCTWORK

FROM AHU-6.

5 CONNECT NEW DIFFUSERS AND DUCTWORK TO EXISTING

RETURN BRANCH DUCTWORK APPROXIMATELY 15 FEET.

6 PLACE FABRIC BLADE BACKDRAFT DAMPER IN VERTICAL

EXHAUST DUCTWORK AND TRANSITION DUCTWORK FROM

42x42 TO 18x18.

7 CONNECT NEW TO EXISTING AND REBALANCE TO 500 CFM.

BALANCING DAMPER LOCATED ON TAKE-OFF FROM MAIN

BRANCH.

8 REBALANCE EXISTING VAV-XX TO PRE-BALANCING REPORT

AIRFLOW.

9 INSTALL FILTERS AT RETURN GRILLES FOR MAINTAINABILITY.

10 REFRIGERANT LINE SET ROUTED DOWN TO CONDENSING UNIT

IN CRAWLSPACE. FIELD VERIFY ROUTE AND CONNECTIONS.

11 CONDENSING UNIT LOCATED IN CRAWLSPACE BENEATH THE

CT SCAN ROOM AND STRUCTURALLY MOUNTED ABOVE

GRADE. REFRIGERANT LINE SET ROUTED TO THE INDOOR COIL,

FIELD VERIFY THE ROUTE.

MECHANICAL SHEET METAL NOTES

1 THE INSTALLATION OF ALL DUCTWORK SHALL BE CLOSELY

COORDINATED WITH NEW PLUMBING, ELECTRICAL, AND

STRUCTURAL CONDITIONS. NOT ALL REQUIRED OFFSETS AND

FITTINGS ARE INDICATED ON DRAWINGS, BUT SHALL BE

PROVIDED. REFER TO ARCHITECTURAL AND STRUCTURAL PLANS

FOR CLEARANCES. ALTERNATE DUCT ROUTING SHALL BE

APPROVED BY ARCHITECT/ENGINEER BEFORE PROCEEDING IN

ORDER TO ENSURE THAT THE AVAILABLE STATIC PRESSURE

REMAINS ADEQUATE. DUCTWORK LOCATION SHALL TAKE

PRECEDENCE OVER HVAC AND FIRE PROTECTION PIPING AND

ELECTRICAL CONDUIT AND CABLE TRAY.

2 LOCATE MECHANICAL EQUIPMENT SUCH THAT THERE IS

UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS

AND VALVING.

3 INSTALL, SUPPORT AND BRACE NEW DUCTWORK AND

ACCESSORIES PER SMACNA GUIDELINES.

4 UNLESS OTHERWISE NOTED, ALL DUCTWORK ABOVE CEILING OR

EXPOSED IS OVERHEAD AND AS HIGH AS POSSIBLE TO THE

UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION

WHERE REQUIRED.

5 DUCTS CONNECTED TO EQUIPMENT SHALL EQUAL EQUIPMENT

CONNECTION SIZE UNLESS NOTED OTHERWISE.

6 PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS

CONNECTED TO MECHANICAL EQUIPMENT THAT REQUIRE

VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE

PROVIDED AT THE POINT OF CONNECTION TO THE EQUIPMENT

UNLESS OTHERWISE NOTED.

7 REFER TO DUCT TAKEOFF DETAILS. SPIN-IN TYPE WITH SCOOPS

SHALL NOT BE ACCEPTED. A MINIMUM OF 2 FEET SHALL BE

PROVIDED BETWEEN RUNOUT TAKEOFFS FROM TRUNK DUCTS.

8 MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 5'-0",

9 RUNOUT BALANCING DAMPERS SHALL BE MOUNTED AS CLOSE

TO MAIN DUCT AS POSSIBLE.

10 ROUND DUCT ELBOWS SHALL BE LONG RADIUS ELBOWS, UNLESS

SHOWN OTHERWISE.

11 PROVIDE FLAT BLADE MANUAL VOLUME DAMPERS AT ALL

TERMINAL DUCT BRANCHES AND AS INDICATED.

12 TERMINAL UNITS SHALL BE MOUNTED TO NOT IMPAIR ACCESS TO

FILTERS, COILS AND CONTROLS.

14 TRANSFER DUCTWORK SHALL BE INTERNALLY LINED WITH A

MINIMUM 1/2" ACOUSTIC LINING.

MECHANICAL NOTES

1 CONTRACTOR SHALL PROVIDE A COMPLETE AND WORKING

SYSTEM.

2 INSTALL EQUIPMENT PER MANUFACTURER'S

RECOMMENDATIONS. ROOF MOUNTED EQUIPMENT SHALL BE

LOCATED A MINIMUM OF 10'-0" FROM THE ROOF EDGE.

3 COORDINATE ALL EXTERIOR PENETRATIONS INCLUDING ROOF

PENETRATIONS WITH OTHER TRADES TO PROVIDE A COMPLETE

AND FULLY WEATHER-PROOF INSTALLATION.

4 PRIMARY CONDENSATE DRAIN PIPING SHALL BE INSULATED AND

SHALL INCLUDE A VAPOR RETARDANT INSULATION JACKET.

SEAL ALL JOINTS AND PENETRATIONS.

5 CONTRACTOR SHALL ENGAGE A TESTING AND BALANCING

FIRM CERTIFIED BY AABC OR NEBB TO PERFORM TESTING AND

BALANCING PROCEDURES ON EACH SYSTEM ACCORDING TO

THE PROCEDURES CONTAINED IN AABC'S OR NEBB'S

STANDARDS FOR TESTING AND BALANCING HEATING,

VENTILATION, AND AIR CONDITIONING SYSTEMS.

6 THIS DRAWING IS DIAGRAMMATIC IN NATURE AND SHALL NOT

BE SCALED.

A CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE A

COMPLETE AND WORKING SYSTEM.

7 THIS DRAWING IS BASED ON VISUALLY OBSERVABLE EXISTING

CONDITIONS AS OF THE TIME OF DESIGN. CONTRACTOR SHALL

BE RESPONSIBLE TO FULLY VERIFY ALL EXISTING CONDITIONS,

COMPONENTS, ETC. PRIOR TO THE START OF THE WORK. ANY

DEVIATION FROM THIS DRAWING IN KIND, OR IN LOCATION

EXCEEDING 1'-0", SHALL BE BROUGHT TO THE ATTENTION OF THE

ENGINEER.

8 HVAC SYSTEMS IN PENTHOUSE #4 CONDITION THIS SPACE.

SYSTEM AC4B(1) SUPPLIES VENTILATION THROUGH THE

CRAWLSPACE DUCTWORK, CV BOXES WITH REHEAT, THEN UP

INTO THE ROOMS THROUGH THE ATU'S SELECTED CV'S ALSO

HAVE HUMIDIFIERS. SYSTEM AC4B(3) PROVIDES TEMPERATURE

CONTROL OVERHEAD THROUGH THE CEILING BY VAV BOXES

WITHOUT REHEAT. THE TWO SYSTEMS WORKED TOGETHER FOR

SPACE CONDITIONING. ONE THERMOSTAT CONTROLS BOTH THE

CRAWL SPACE VENTILATION SUPPLY AND ABOVE CEILING 4B(3)

VAV BOXES. BOTH AC4B(1) AND AC4B(3) HAVE A COMMON

PLENUM FOR RETURN.

NORTH

SCALE: 1/4" = 1'-0"

BP1 - FIRST FLOOR HVAC PLAN

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

M600.1

MECHANICAL SCHEDULES

BID DOCUMENTS02/16/24

PROJECT A

GRILLES, REGISTERS AND DIFFUSERS SCHEDULE

MARK DESCRIPTION MANUFACTURER MODEL

FACE

SIZE

MAX

AIRFLOW

CFM

TOTAL

PRESSURE

NECK THROW

DISTANCE

(A) NC (B) FINISH NOTESSIZE

R8L1 LAY-IN EGG-CRATE, ROUND-NECK

RETURN GRILLE

TITUS 50F 24x24 200 CFM 0.08 in-wg 8" 0" 0 WHITE ENAMEL 1

R10L1 LAY-IN EGG-CRATE, ROUND-NECK

RETURN GRILLE

TITUS 50F 24x24 200 CFM 0.06 in-wg 10" 0" 0 WHITE ENAMEL 1

R14L1 LAY-IN EGG-CRATE, ROUND-NECK

RETURN GRILLE

TITUS 50F 24x24 815 CFM 0.06 in-wg 14" 0" 0 WHITE ENAMEL 1

S6L1 LAY-IN LOUVERED FACE,

ROUND-NECK SUPPLY DIFFUSER

TITUS TDC-AA 24x24 100 CFM 0.08 in-wg 6" 4' - 0" 18 WHITE ENAMEL

S8L1 LAY-IN LOUVERED FACE,

ROUND-NECK SUPPLY DIFFUSER

TITUS TDC-AA 24x24 200 CFM 0.08 in-wg 8" 6' - 0" 21 WHITE ENAMEL

S10L1 LAY-IN LOUVERED FACE,

ROUND-NECK SUPPLY DIFFUSER

TITUS TDC-AA 24x24 200 CFM 0.09 in-wg 10" 7' - 0" 21 WHITE ENAMEL

S12L1 LAY-IN LOUVERED FACE,

ROUND-NECK SUPPLY DIFFUSER

TITUS TDC-AA 24x24 430 CFM 0.09 in-wg 12" 8' - 0" 22 WHITE ENAMEL

S16L1 LAY-IN LOUVERED FACE,

ROUND-NECK SUPPLY DIFFUSER

TITUS TDC-AA 24x24 850 CFM 0.09 in-wg 16" 8' - 0" 20 WHITE ENAMEL

GENERAL NOTES:

A. THROW AT 50 FEET PER MINUTE VELOCITY.

B. "-" NC RATING IS LOW ENOUGH TO NOT REGISTER IN THE MANUFACTURER'S DATA.

SCHEDULE NOTES:

1. FULL 24"x24" EGG CRATE FACE.

WALL MOUNTED AIR CONDITIONER SCHEDULE

MARK

BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL

NO. TYPE

FAN COOLING COIL

UNIT

WEIGHT MCA MOCP VOLT PH

INTERLOCK

ACCESSORIES NOTES

DESIGN

AIRFLOW

MOTOR NOMINAL

CAP

CAP

MARKQTY POWER ECM TOTAL

AC-1 BLUERIDGE ZKFN-90-8-1 WALL AC UNIT 500 CFM 1 0.13 hp No 4 ton 48000 Btu/h 88 lb 2 A 15 A 208 V 1 CU-1 CP 1

SPLIT SYSTEM OUTDOOR UNIT SCHEDULE

MARK DESCRIPTION MANUFACTURER MODEL NO. TYPE

COOLING

CAPACITY

COMPRESSOR

TYPE

REFRIGERANT

TYPE

LOW

AMBIENT

KIT

SUMMER

AMBIENT

DBT

WINTER

AMBIENT

DBT

EFFICIENCY

UNIT

WEIGHT MCA MOCP VOLT PH ACCESSORIES NOTESSEER2 EER2

CU-1 CONDENSING UNIT BLUERIDGE KTQ420D1UMU OUTDOOR 4.00 ton ROTARY R-410A Yes 75.0 °F 70.0 °F 18.9 9.3 219 lb 37 A 50 A 208 V 1 LA, T 1-3

ACCESSORIES:

CP - ASPEN CONDENSATE PUMP

SCHEDULE NOTES:

1. UNIT TO BE MOUNTED 7' ABOVE FINISHED FLOOR.

ACCESSORIES:

LA - LOW AMBIENT KIT

T - THERMOSTATIC INTERFACE CONNECTED TO EXISTING JOHNSON CONTROLS

SCHEDULE NOTES:

1. MANUFACTURER SUBMITTALS MUST INCLUDE REFRIGERANT PIPING DIAGRAM WITH PIPE DIAMETERS, LENGTHS, AND REFRIGERANT VOLUME.

2. SUBSTITUE MANUFACTER SHALL BE RESPONSIBLE FOR ADDITIONAL PIPING AND REFRIGERANT.

3. PROVIDE INSULATION ON REFRIGERANT PIPING.

ELECTRIC HUMIDIFIER SCHEDULE

MARK

LOCATION

BASIS OF DESIGN

MANUFACTURER

BASIS OF

DESIGN MODEL

NO. TYPE ARRANGEMENT

HEATING ELEMENT HUMIDIFIER

OUTPUT

(LBS/HR)

UNIT

WEIGHT FLA MCA MOCP VOLT PH NOTESNAME NO. QTY TYPE POWER SCR

HM-01 CT SCAN 1556 CONDAIR EL-010 ELECTRODE WALL-MOUNT 1 ELEC 4 kW Yes 55 lb 18 A 18 A 25 A 208 V 1 N/A

GENERAL NOTES:

1. PROVIDE WITH DUAL CHANNEL FACTORY CONTROL.

2. PROVIDE WITH DUCT MOUNTED STEAM DISTRIBUTOR ASD 18.

10.0

J

48"

J

48"

J 4

J

J4

J4 "J 9

J9

J

96"

CLNG

J

J

48"

4D A

C A

C 2D

A C

A C2D

84"

TP

TP

TPTP

TP

TP

TP

TP

A

C TP

TP

TP

TP

J

J

96"

TP

84" 1D

2D

4D

2D

2D

S

2D

J

48"

CLNG

J

M

CR

R

M L

ML

60" 60"

S

CLNG

J

J J

AREA NOT IN SCOPE

2 1

CHANGING

1556B

CT SCAN

CT SCAN

CONTROL RM

1556A

FAMILY CONSULT

SECURITY

Space

CORRIDOR

CORRIDOR

CT MDP

CT UPS

PDU

AC-1

E500.1

HM-01

GENERAL POWER NOTES

1 WHERE CONNECTED TO A 20 AMP BRANCH CIRCUIT

SUPPLYING AN INDIVIDUAL (SIMPLEX OR DUPLEX), THE

RECEPTACLE SHALL BE RATED AT 20 AMPS.

2 REFER TO SECTION 26 0519 FOR MINIMUM CONDUCTOR SIZE

ADJUSTMENTS FOR VOLTAGE DROP.

3 WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN.

PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE

CIRCUIT AND SWITCHING CONNECTIONS SHOWN.

4 CIRCUIT WIRING IS NOT SHOWN EXCEPT FOR SWITCHING

INTENT OF FIXTURES AND CONTROL OF DEVICES.

5 PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE

CIRCUITING AND SWITCHING SHOWN.

6 SINGLE PHASE BRANCH CIRCUITS SHALL NOT SHARE

NEUTRALS.

7 THE CONTRACTOR SHALL PROVIDE THE DATA CONDUITS,

BOXES, AND DATA CABLING AS SHOWN.

8 THE CONTRACTOR SHALL FIELD VERIFY THE ROUGH-IN

DIMENSIONS OF ALL DATA OUTLETS, TV OUTLETS AND PRIOR

TO ANY INSTALLATION. ANY CHANGE OF LOCATION OF A

BOX THAT WAS NOT VERIFIED WITH THE OWNER PRIOR TO

INSTALLATION SHALL BE RELOCATED, TO THE OWNER’S

SATISFACTION. AT THE CONTRACTOR’S EXPENSE.

9 PROVIDE THE REQUIRED POWER FOR ALL MECHANICAL OR

PLUMBING EQUIPMENT SPECIFIED IN THE CONTRACT

DOCUMENTS, EVEN IF NOT SHOWN ON THE POWER PLANS.

10 THE CONTRACTOR SHALL FIELD VERIFY THE POWER

REQUIREMENTS OF ALL MECHANICAL AND PLUMBING

EQUIPMENT, WITH THE EQUIPMENT SUPPLIERS, PRIOR TO

PREPARING SUBMITTALS OR ORDERING ANY SWITCHGEAR

OR EQUIPMENT. SUPPLIED PLUMBING AND/OR MECHANICAL

EQUIPMENT MAY VARY FROM EQUIPMENT SPECIFIED IN THE

PLANS.

11 FOR EACH THERMOSTAT, TEMPERATURE SENSOR OR WALL

MOUNTED HVAC CONTROL DEVICE PROVIDE A JUNCTION

BOX, WITH A SINGLE GANG MUD RING, AT 48” ABOVE THE

FINISH FLOOR WITH A ¾” CONDUIT (WITH A PULL STRING) TO

ABOVE THE CEILING FOR THE HVAC CONTROLS. HVAC

CONTROLS WIRING AND DEVICES INSTALLED BY

MECHANICAL CONTROLS CONTRACTOR.

12 ALL PENETRATIONS MUST BE BACKED WITH SHEET LEAD OF THE

SAME THICKNESS (OR GREATER) AS REQUIRED FOR THE WALL

OR PARTITION THAT PENETRATION OCCURS IN.

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

259 E. Michigan Ave., Suite 407

Kalamazoo, MI 49007

P: 269.585.2255 steelheadengineeringco.com

THE REPRODUCTION, COPYING OR OTHER USE OF THIS

DRAWING WITHOUT WRITTEN AUTHORIZATION IS PROHIBITED.

c SEVEN GENERATIONS ARCHITECTURE & ENGINEERING, LLC

SHEET NO.

SHEET TITLE

JOB NUMBER:

ISSUE DATES:

BID DOCUMENTS

222112

IH

S B

F S U

M U

LT

IP

LE

P

R O

J E C

T D

E S

IG

N

IH

S B

LA

C

K F E E T

S E R

V

IC

E U

N

IT

B

LA

C K

W E A

S E L

R O

A D

B R

O W

N

IN

G M

O N

TA

N

A

E201.1

FIRST FLOOR POWER PLAN

BID DOCUMENTS02/16/24

04/22/25 ADDENDUM 01

PROJECT A

KEYNOTES

1 JUNCTION BOX AT 48" ABOVE THE FINISH FLOOR FOR THE

POWERED DOOR OPERATOR PUSH BUTTON. PROVIDE A 3/4"

CONDUIT TO THE JUNCTION BOX OVER THE DOOR.

2 JUNCTION BOX ABOVE THE CEILING OVER THE DOOR FOR THE

POWERED DOOR POWER CONNECTION, FIELD VERIFY THE

CONNECTION REQUIREMENTS WITH THE EQUIPMENT SUPPLIER.

3 JUNCTION BOX AT 48" ABOVE THE FINISH FLOOR, FOR THE

CODE BLUE BUTTON, WITH A 3/4" CONDUIT TO ABOVE THE

CEILING.

4 JUNCTION BOX IN THE CEILING FOR THE POWER CONNECTION

TO THE PATIENT LIFT, CONNECT NEW DEVICES TO EXISTING

HOMERUN CIRCUITRY FROM DEMOLISHED FIXTURES. WHERE

NEEDED ROUTE AND PROVIDE NEW CIRCUITRY FROM PANELS

NB OR NBB IN ROOM 1057 TO ACHIEVE APPROXIMATE

LAYOUT SHOWN. FIELD VERIFY THE REQUIREMENTS WITH THE

EQUIPMENT SUPPLIER.

5 JUNCTION BOX ABOVE DOOR TO PROVIDE POWER FOR

X-RAY. 'IN-USE' SIGNAGE PROVIDED BY OWNER, FIELD VERIFY

THE CONNECTION REQUIREMENTS.

6 SWITCH FOR CONTROL OF XRAY IN-USE LIGHTS.

7 TWIST LOCK EMERGENCY POWER OFF BUTTON FOR CT

SCANNER. CONNECT TO POWER DISTRIBUTION UNIT. FIELD

VERIFY THE CONNECTION REQUIREMENTS WITH THE

EQUIPMENT SUPPLIER.

8 SEE CT RISER DIAGRAM FOR ADDITIONAL CONNECTION

DETAIL ON SHEET E500.1.

9 EXISTING RECEPTACLE AND ASSOCIATED BRANCH CIRCUITRY

TO REMAIN.

10 CONNECT NEW DEVICES TO EXISTING HOMERUN CIRCUITRY

FROM DEMOLISHED FIXTURES. WHERE NEEDED ROUTE AND

PROVIDE NEW CIRCUITRY TO ACHIEVE APPROXIMATE LAYOUT

SHOWN. ROUTE ANY NEW HOMERUN CIRCUITRY FROM SPARE

BREAKERS IN PANEL NBB OR PANEL NB IN ROOM 1057. FIELD

VERIFY EXISTING CONDITIONS AND CONNECTION

REQUIREMENTS.

11 PROVIDE DEDICATED 20-AMP 1-POLE BREAKER IN PANEL NB

OR PANEL NBB IN ROOM 1057. ROUTE #12 COPPER

CONDUCTORS TO THE NEW BLANKET WARMER RECEPTACLE.

FIELD VERIFY THE CIRCUIT LOCATION DUE TO PANEL SPACE

AND AVAILABLE AMPACITY CONSTRAINTS.

12 COORDINATE SPEAKER WITH CT MANUFACTURER, PROVIDE

SPEAKER WIRING FROM CT TO SPEAKER PER MANUFACTURER'S

REQUIREMENTS.

13 NEW LOCATION FOR STAFF NURSE CALL IN CONTROL ROOM,

CONNECT TO EXISTING NURSE CALL SYSTEM, EXTEND AND

MODIFY CIRCUITRY AS REQUIRED.

14 APPROXIMATE LOCATION OF NEW UNDERFLOOR RACEWAY,

REFER TO ARCHITECTURAL FLOOR PLAN FOR MORE

INFORMATION.

15 ROUTE NEW FEEDER FOR GANTRY POWER FROM CT MDP TO

CT GANTRY VIA FLOOR TRENCH DUCT AND CONNECT PER

MANUFACTURER SPECIFICATIONS.

16 APPROXIMATE FLOOR TO CEILING RACEWAY LOCATION

REFER TO ARCHITECTURAL FLOOR PLAN FOR MORE

INFORMATION.

17 CONNECT NEW CT MAIN DISTRIBUTION PANEL TO NEW

FEEDERS FROM EXISTING CT DISCONNECT LOCATED IN THE

CRAWL SPACE. PROVIDE COMPATIBLE VERTICAL TRENCH

RACEWAY SECTION TO ROUTE THE CONDUCTORS FED

THROUGH THE FLOOR TRENCH UP TO THE CT MDP FOR

TERMINATION, PROVIDE COVERS AND OPENINGS FOR

TRENCH AS REQUIRED. SEE CT RISER DIAGRAM ON FOR

ADDITONAL DETAILS.

18 NEW 40-AMP 208V 1-PHASE BREAKER WITH #8 COPPER

CONDUCTORS FOR WATER HEATER FROM PANEL NB OR NBB,

FIELD VERIFY CONNECTION REQUIREMENTS.

19 DISCONNECT, EXTEND AND RECONNECT THE POWER

CIRCUITRY FOR RELOCATED VAV BOX.

20 JUNCTION BOX FOR CT INJECTOR CONTROL CONSOLE,

COORDINATE AND FIELD VERIFY MANUFACTURER

REQUIREMENTS PRIOR TO INSTALLATION.

21 CT MAIN DISTRIBUTION PANEL SHALL PROVIDE POWER FOR CT

INJECTOR. COORDINATE AND FIELD VERIFY MANUFACTURER

REQUIREMENTS PRIOR TO INSTALLATION.

22 AC UNIT POWERED BY CONDENSING UNIT PER

MANUFACTURER SPECIFICATIONS. PROVIDE 3-POLE MOTOR

SWITCH AS DISCONNECTING MEANS FOR INDOOR AC UNIT.

SEE MECHANICAL DRAWINGS.

23 PROVIDE 50A 2-POLE CIRCUIT BREAKER IN PANEL NBB OR NB

FOR CONNECTION TO NEW AC CONDENSING UNIT. PROVIDE

2 POLE, 50 AMP FUSED DISCONNECT AS DISCONNECTING

MEANS IN CRAWLSPACE. FIELD VERIFY ROUTE AND

CONNECTIONS. SEE MECHANICAL DRAWINGS.

24 PROVIDE POWER FOR DOOR ACCESS CARD READER AND

AUTOMATIC SWING OPERATOR, ROUTE NEW 20A SPARE

BREAKER AND ASSOCIATED BRANCH CIRCUITRY FROM PANEL

NBB OR NB IN ROOM 1057, FIELD VERIFY CONNECTION

REQUIREMENTS.

25 ROUTE NEW FEEDER FOR OPERATOR CONSOLE FROM CT MDP

THROUGH FLOOR TRENCH DUCT AND CONNECT PER

MANUFACTURER SPECIFICATIONS.

26 NEW 25-AMP 208V 1-PHASE BREAKER WITH #10 COPPER

CONDUCTORS FOR HUMIDIFER FROM PANEL NB OR NBB.

PROVIDE 2 POLE, 30-AMP DISCONNECT IN ACCESSIBLE

CEILING WITHIN 6 FT. OF EQUIPMENT. FIELD VERIFY

CONNECTION REQUIREMENTS AND COORDINATE WITH

MECHANICAL…