This document is an Amendment (A00004) to Solicitation 75H70125R00016 for the Blackfeet Hospital CT Room Renovation project. The amendment extends the proposal due date from May 30, 2025, to June 17, 2025, at 2:00 PM PT, and includes responses to submitted questions and an addendum to the project drawings. The solicitation is a 100% Indian Small Business Economic Enterprise (ISBEE) set-aside under NAICS code 236220 for Commercial and Institutional Building Construction, with a project budget between $500,000 and $1,000,000.
The renovation involves creating an adequate space for a new 128-slice CT scan unit at the Blackfeet Hospital in Browning, Montana, including upgrades to the CT room's infrastructure, HVAC, and electrical systems, as well as improvements to the existing security room. The project has a 180-calendar-day performance period, and the Indian Health Service (IHS) intends to award a Firm Fixed Price (FFP) contract using Lowest Price Technically Acceptable (LPTA) evaluation criteria. The amendment provides clarifications on various technical aspects, equipment specifications, and project requirements, addressing contractor questions about construction methods, materials, and project scope.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
SF30 CONTINUATION OF BLOCK NARRATIVE
SUMMARY OF CHANGES
Solicitation Number 75H70125R00016 is hereby amended to address the following:
1. Extend the proposal due date from 30 May 2025 at 2:00PM PT to 17 June 2025 at 2:00PM PT (2 pages)
i. See revised SF1442
2. Provide responses to submitted questions. (17 Pages)
3. Provide an addendum to the drawings. See the following attachments:
i. BFSU Addendum 01 Drawings
ii. BFSU Addendum 01 Specs
NOTICE TO OFFERORS: Offerors must acknowledge receipt of any and all amendments by number and date on their cover letter in their offer or by submitting a signed copy of the SF30. All other terms and conditions remain unchanged.
END OF SUMMARY OF CHANGES
(See ).
SOLICITATION, OFFER,
AND AWARD
(Construction, Alteration, or Repair)
IMPORTANT - The "offer" section on the reverse must be fully completed by offeror.
9. FOR
INFORMATION CALL:
NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid and "bidder".
SOLICITATION
1. SOLICITATION NUMBER
5. REQUISITION/PURCHASE REQUEST NUMBER
CODE
6. PROJECT NUMBER
8. ADDRESS OFFER TO
4. CONTRACT NUMBER
7. ISSUED BY
10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS (Title, identifying number, date)
11. The contractor shall begin performance within
12a. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE AND PAYMENT BONDS?
(If "YES", indicate within how many calendar days after award in Item 12b.)
13. ADDITIONAL SOLICITATION REQUIREMENTS:
a. Sealed offers in original and
b. An offer guarantee
c. All offers are subject to the (1) work requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.
d. Offers providing less than
STANDARD FORM 1442 (REV. 12/2022)
Prescribed by GSA - FAR (48 CFR) 53.236-1(d) calendar days for Government acceptance after the date offers are due will not be considered and will be rejected.
is, is not required.
containing offers shall be marked to show the offeror's name and address, the solicitation number, and the date and time offers are due.
(date). If this is a sealed bid solicitation, offers will be publicly opened at that time. Sealed envelopes copies to perform the work required are due at the place specified in Item 8 by (hour) award, YES NO notice to proceed. This performance period is mandatory negotiable.
calendar days and complete it within calendar days after receiving
a. NAME b. TELEPHONE NUMBER (Include area code) (NO COLLECT CALLS)
12b. CALENDAR DAYS
2. TYPE OF SOLICITATION
SEALED BID (IFB)
INVITATION FOR BID
NEGOTIATED (RFP)
REQUEST FOR PROPOSAL
3. DATE ISSUED PAGE OF PAGES
75H70125R00016
Indian Health Service Division of Engineering Services (DES) - Seattle 701 5th Ave, Suite 1600 Seattle, WA 98104
Project: BI22BF400H08, Blackfeet Hospital CT Room Renovation
Location: 760 Blackweasel Rd, Browning, MT 59417
See Section L for Proposal Submittal Instructions and Site Visit Information.
This project will be procured as a 100% Indian Small Business Economic Enterprise (ISBEE) set-aside under North American Industry Classification System (NAICS) code 236220 Commercial and Institutional Building Construction. The associated size standard for this procurement is $45 million.
CONSTRUCTION MAGNITUDE: The magnitude of this construction project is anticipated to be between $500,000 and $1,000,000 in accordance with FAR 36.204(f).
Indian Health Service Division of Engineering Services (DES) - Seattle Attn: Taylor Kanthack 701 5th Ave Seattle, WA 98104
Taylor Kanthack taylor.kanthack@ihs.gov 240-478-1501
BI22BF400H08
1 5802/03/2025 local time 6/17/2025
2:00PM PT
10 Days after award
F.2 FAR 52.211-10
AWARD (To be completed by Government)
17. The offeror agrees to perform the work required at the prices specified below in strict accordance with the terms of this solicitation, if this offer is accepted calendar days after the date offers are due. (Insert any number equal to or greater than the minimum requirement by the Government in writing within stated in Item 13d. Failure to insert any number means the offeror accepts the minimum in Item 13d.)
OFFER (Must be fully completed by offeror)
AMOUNTS
18. The offeror agrees to furnish any required performance and payment bonds.
19. ACKNOWLEDGMENT OF AMENDMENTS
(The offeror acknowledges receipt of amendments to the solicitation -- give number and date of each)
AMENDMENT
NUMBER
DATE
CONTRACTING OFFICER WILL COMPLETE ITEM 28 OR 29 AS APPLICABLE
14. NAME AND ADDRESS OF OFFEROR (Include ZIP Code)
CODE FACILITY CODE
15. TELEPHONE NUMBER (Include area code)
16. REMITTANCE ADDRESS (Include only if different than Item 14.)
20a. NAME AND TITLE OF PERSON AUTHORIZED TO SIGN OFFER (Type or print)
21. ITEMS ACCEPTED:
22. AMOUNT
26. ADMINISTERED BY
30a. NAME AND TITLE OF CONTRACTOR OR PERSON AUTHORIZED TO SIGN (Type or print)
31c. DATE
STANDARD FORM 1442 (REV. 12/2022) BACK
31b. UNITED STATES OF AMERICA
BY
31a. NAME OF CONTRACTING OFFICER (Type or print)
29. AWARD (Contractor is not required to sign this document.) Your offer on this solicitation is hereby accepted as to the items listed. This award consummates the contract, which consists of (a) the Government solicitation and your offer, and (b) this contract award. No further contractual document is necessary.
30b. SIGNATURE 30c. DATE
28. NEGOTIATED AGREEMENT (Contractor is required to sign this document and return and deliver all items or perform all work requirements identified on this form and any continuation sheets for the consideration stated in this contract. The rights and obligations of the parties to this contract shall be governed by (a) this contract award, (b) the solicitation, and (c) the clauses, representations, certifications, and specifications incorporated by reference in or attached to this contract.
copies to issuing office.) Contractor agrees to furnish
24. SUBMIT INVOICES TO ADDRESS SHOWN IN
(4 copies unless otherwise specified)
23. ACCOUNTING AND APPROPRIATION DATA
ITEM
25. OTHER THAN FULL AND OPEN COMPETITION PURSUANT TO THE UNITED STATES
CODE AT
27. PAYMENT WILL BE MADE BY
10 U.S.C. 3204(a) ( ) 41 U.S.C. 3304(a) ( )
20b. SIGNATURE 20c. OFFER DATE
B.3
Indian Health Service, DES - Seattle 701 5th Ave, Suite 1600 Seattle, WA 98104
Indian Health Service - Billings Area Office 2900 4th Ave North Billings, MT 59101
Taylor M. Kanthack
LUMP SUM TOTAL $______________________
Questions and Answers
75H70125R00016
Blackfeet CT Room Reno
A00001 Item Question Answer 1 Could you verify that the Lead based Sheetrock is to be removed and mitigated using full containment protocols for Hazardous Waste materials? The product is throughout the intended renovation Area and will have a material effect on the cost of the project.
Lead based sheetrock removal is minimal per the plans. Refer to page AD101.1. demolition plan and notes. Note 14 states:
“REMOVE LEAD LINING AND GYPSUM BOARD AS NEEDED TO
PREPARE FOR NEW FINISHES AND NEW WORK.” Containment and HEPA filtration would be required, at a minimum, during the demolition phase.
2 Is this slab on grade construction throughout the entire proposed work site?
Page AD101.1 shows the location/boundary of the slab on grade vs.
the crawlspace. The CT Room 1556 and Waiting 1557 are the rooms to be renovated and are on the slab on grade. The CT room will require concrete cutting and patch work.
Security Room 1565 is located on Slab on Grade, no concrete work will be required in this room.
A00002 3 Can you provide any pictures of Panels NB or NBB? At this time we are not available to provide pictures.
4 Could you tell me where room 1057 is in the building?
North of the CT scan room.
5 Sheet GC101.1 – First Floor Infection Control Plan - Phasing
Overview comment - “COORDINATE WITH COR ON TIMING
AND DURATION OF MOBIL CT UNIT. CONTRACTOR IS TO
COMPLETE, AT A MINIMUM THE CT SCAN ROOM, CONTROL
ROOM AND CHANGING ROOM WHILE MOBIL CT UNIT IS ON
SITE. THIS IS TO INCLUDE A MINIMUM OF TWO WEEKS TO USE
THE MOBIL UNIT PRIOR TO DEMOLTION/ REMOVAL OF
EXISTING CT AND A MINIMUM OF THREE WEEKS PRIOR
TEMPORARY MOBILE CT UNIT BEING REMOVED.”
a. Can you provide clarity for the three weeks indicated above.
b. Would this be a notification 3 weeks prior to our completion of the CT Area?
The IHS intention is to procure the mobile unit in Parallel with the construction award. The rental duration is 6 months.
The intent of the three-week timeline to allow the facility to operate the new CT unit prior to the mobile unit leaving the site.
6 Sheet GC101.1 – First Floor Infection Control Plan - Phasing Overview comment - “ONCE RELEASED, CONTRACTOR IS TO
COORDINATE CT UNIT REMOVAL. ENSURE ALL PATIENT DATA
IS SCRUBBED FROM THE UNIT PRIOR TO POWER REMOVAL.”
a. Will the facility or CT Vender provide the removal of patient data?
IHS and the CT removal company are obligated to verify the removal of patient data prior to CT removal.
Sheet GC101.1 – First Floor Infection Control Plan - Phasing Overview comment - “PROVIDE TEMPORARY HEAT DETECTION
ONCE CEILINGS ARE REMOVED”
a. Please provide the location and type of the required equipment ie strobes, sensors etc. for temporary heat detection.
Fire alarm contractor is to verify the temporary heat detection coverage that supports the areas of work. At a minimum, one temporary heat detector should be provided in rooms 1556 and 1557 for the duration of when existing fire alarm devices are decommissioned until they are reactivated. For corridor and security work, contractors are to work with HIS on their ILSM (Interim Life Safety Measures) Plan.
8 Sheet GC101.1 – First Floor Infection Control Plan - Phasing Overview comment - “CONTRACTOR SHALL PROVIDE A
EXPEDITED SCHEDULE TO COMPLETE THE CORRIDOR WORK
TO MINIMIZE IMPACTS TO EGRESS AND ACCESS TO HELIPAD
ELEVATOR.”
Is there a defined required time frame duration for the corridor work?
Contractor is responsible to identify the sequence of work and its duration for review with IHS prior to work commencing. The intent is to always provide and maintain access to the helipad elevator.
IHS understands there will be impact the elevator access during corridor work that will require continuous communication by the contractor.
9 Sheet GC101.1 – First Floor Infection Control Plan – General Construction Notes – “13) IN ALL CONSTRUCTION ZONES AND
AREAS. CONTRACTOR RESPONSIBLE FOR MAINTAINING AN
ACTIVE STROBE SPEAKER SYSTEM AT ALL TIMES TYPICAL FOR
ALL CONSTRUCTION ZONES FOR ALL BUILDINGS.”
a. Please provide locations and product type for the Strobe speaker systems.
b. Are we utilizing the existing equipment?
The contractor is responsible to provide a safe work environment and maintain systems. The fire alarm contractor is responsible to either reuse existing devices or provide temporary devices that will work with existing system.
10 Sheet AD101.1 – First Floor Demolition Plan – Note on plan sheet “NOTE SLAB IS NOT MONOLITIC AS ASHPHALT WAS
HERE PRIOR”
a. Can you provide the area represented in the comment
b. Can you provide an existing cross section of existing conditions
Disregard the note as written. The area that the arrow was pointing to was the area of the crawlspace coverage. Existing slab thickness to field verified. As-builts indicate concrete slab on metal deck supported by steel bar joists.
c. Will there be concrete / asphalt removed and replaced in this area
11 Sheet AD101.1 – First Floor Demolition Plan – Note 10 “THE
AWARDED CT VENDOR WILL DISASSEMBLE AND REMOVE THE
EXISTING CT EQUIPMENT AND ASSOCIATED EQUIPMENT
(GANTRY, CONSOLT DESK, PATIENT TABLE, POWER
DISTRIBUTION UNIT, SERVICE CABINET, PARTIAL UPS, REAR
CABLE COVER).”
a. Please clarify the work above is not included in our scope of work.
b. If the CT vender is already awarded would you be able to provide their contact information.
A. IHS verified that the new CT vendor will salvage the existing equipment.
B. New equipment has been procured by IHS. The contact information will be provided to the awarded contractor.
12 Sheet AD101.1 – First Floor Demolition Plan – Note 3
“REMOVE & SALVAGE EXISTING DOORS(S), FRAME(S),
HARDWARE, ETC FOR REINSTALLATION.”
a. Can you provide the door location were note 3 is referencing as it is not indicated on the plan.
Disregard. Note three was prior approach not used.
13 Sheet AD101.1 – First Floor Demolition Plan – General notes
a. Is there a designated area in the hospital for the items identified to be removed and salvaged?
b. Can you provide the location?
Final location to be determined with the awarded contractor.
14 General Note – Was there an asbestos study performed in the remodeled areas.?
a. Would you Please provide the asbestos report in the bidding documents.
No asbestos survey completed in design, as it was assumed all clear. Contractors should be aware that hazardous materials may be present, if identified, provide awareness to the COR.
15 Sheet A001.1 – Wall Type – H6
a. The wall type H6 identified is not indicted in the plans
This wall type indicates a one-sided gypsum wall board replacement – same wall type as H4. Do not use.
b. Can you provide the wall type H6 location on the plans.
16 Sheet A001.1 – Wall Type – 2E
a. The wall type 2E identified is not indicted in the plans
b. Can you provide the wall type 2E location on the plans.
2E is indicated in corridor 1559.
17 Sheet A101.1 – First Floor Plan – Equipment Schedule – A – Contractor installed items that are owner supplied.
a. Can you provide the shop drawings / Product data for the installation of these products?
CLK1 – NO ADDITIONAL PRODUCT DATA IS AVAILABLE. GOVT WILL
HAVE TO ORDER PRIOR TO INSTALLATION – DATA SHEETS WILL BE
PROVIDED PRIOR TO INSTALL.
GLB1 - NO ADDITIONAL PRODUCT DATA IS AVAILABLE. GOVT WILL
HAVE TO ORDER PRIOR TO INSTALLATION – DATA SHEETS WILL BE
PROVIDED PRIOR TO INSTALL.
HS1 - NO ADDITIONAL PRODUCT DATA IS AVAILABLE. GOVT WILL
HAVE TO ORDER PRIOR TO INSTALLATION – DATA SHEETS WILL BE
PROVIDED PRIOR TO INSTALL.
PTD1 - NO ADDITIONAL PRODUCT DATA IS AVAILABLE. GOVT WILL
HAVE TO ORDER PRIOR TO INSTALLATION – DATA SHEETS WILL BE
PROVIDED PRIOR TO INSTALL.
SD1 - NO ADDITIONAL PRODUCT DATA IS AVAILABLE. GOVT WILL
HAVE TO ORDER PRIOR TO INSTALLATION – DATA SHEETS WILL BE
PROVIDED PRIOR TO INSTALL.
SH1 - NO ADDITIONAL PRODUCT DATA IS AVAILABLE. GOVT WILL
HAVE TO ORDER PRIOR TO INSTALLATION – DATA SHEETS WILL BE
PROVIDED PRIOR TO INSTALL.
ST1 – CT DOES NOT HAVE A DEDICATED STRETCHER, MODEL WILL
VARY
18 Sheet A101.1 – First Floor Plan – Equipment Schedule – A – Contractor to supply Apron Rack, Mirror, Patient Transfer Board, Robe Hook.
a. The specifications do not include the material specifications.
Apron Rack – Phillips Safety Product: RAR P4 Mirror – Bobrick B-1658 Series Patient Transfer Board Hanger – Philips Safety Transfer Device Storage Rack.Product: PTB-7799R Robe Hook – Bobrick B-7672 Double Hook
b. Would you be able to add the specifications for these products?
19 Sheet A101.1 – First Floor Plan – General Notes – 12 12.
WHERE FIRE RATED SEPARATIONS ARE SHOWN IN CODE
PLANS PROVIDE STENCILING EVERY 20'-0'' HORIZONTALLY
WITHIN THE CEILING PLENUM SPACE WITH THE FOLLOWING”
a. The specifications do not indicate the wording required stenciling.
b. Can you provide the required wording for the stencil.
A. Letting not less than 3 inches in height with a minimum 3/8-inch stroke in a contrasting color. Located within 15 feet of the end of each wall and at intervals not excedding 30 feet measured horizontally along the wall or partition.
B. Incorporating the suggested wording, “Fire and/or smoke barrier
– protect all openings”. Label as noted on the code compliance plan such as 1-hour or smoke, etc.
20 Sheet A101.1 – First Floor Plan – Control Room Opening
a. There does not appear to be an opening for the Control Room in the plan.
b. The hardware schedule is referencing opening 102
c. Is the control room opening have a door?
d. If it’s an opening please provide the required opening size
A. See detail 05/A420.1 B. No Hardware C. No door it is a cased opening D. Wall opening to be a minimum of 3’-0” by 8’-0” wide.
21 Sheet A420.1 – Interior Elevations & Door Schedule
a. There appears to be two copies of this sheet in the plans ie detail 16 appears to be different between sheets.
b. Can you reissue appropriate sheet A420.1
Utilize 2025 04 15 drawings “2024 04 15 IHS BFSU Project A CT – Issued for BD Drawings R1”
22 Sheet A420.1 – Interior Elevations & Door Schedule
a. Door 101A indicates owner to provide door.
b. Can you provide the shop drawings and Product data for door 101A
b. Product Data CoreClad 1/16” LL Wood Door 4070x1-3/4” with 60PP rating 1/16” LL (Type 1) HM Door Frame 4070 x 9’1/12” JD (8-1/2” throat) welded
c. Door is prepared for push/pull hardware
c. Can you also confirm door is prepared for hardware set 01 including operators and only push pull devices identified in the door schedule.
23 Sheet A420.1 – Interior Elevations & Door Schedule Room
a. The Plan Detail descriptions are different from the floor plan
b. Corridor 105 should be corridor 1559 as per floor plan.
c. CT Scan 101 should be CT Scan 1556 as per floor plan.
d. Locker Room 104 should be Changing Room 1556B as per floor plan.
e. Control Room 102 should be Control Room 1556A as per floor plan.
f. Security Room 106 should be Security 1565 as per floor plan.
g. Can you confirm and provide the correct room numbers to match the floor plan
Follow the room numbers listed on the plan
24 Sheet P500.1 – Plumbing Details and Schedules
a. Detail 2 indicates water heater under sink. As referenced on sheet A520.1 detail 02 the casework only shows a cover.
b. Can you provide the location of the water heater to mounted?
Mount on back wall under the sink USS1 shown on sheet P201.1.
Locate to make accessible for replacement and not obstructing under sink plumbing or storage.
25 Sheet E500.1
a. Can you provide the requirements for the card reader and electric strikes on doors
ED DOOR HAS MAG LOCKS WITH PUNCH CODE LOCK MECHANISM.
26 Several Sections are not included in the project specifications as referenced in 1.02 RELATED REQUIREMENTS identified in other sections included below. Please provide missing required sections.
a. Section 012100 - Allowances
b. Section 014000 - Quality Requirements
c. Section 016000 – Product Requirements
The following sections do not apply to this project:
Section 090600 – Schedule for Finishes Section 09300 – Tiling Section 097200 – Wall Coverings Section 099113 – Exterior Painting
d. Section 016116 - Volatile Organic Compound (VOC) Content Restrictions.
e. Section 017000 – Execution and Closeout Requirements
f. Section 019113 - General Commissioning Requirements
g. Section 054000 - Cold-Formed Metal Framing:
h. Section 055000 - Metal Fabrications
i. Section 061000 - Rough Carpentry
j. Section 061643 - Gypsum Sheathing:
k. Section 072100 - Thermal Insulation
l. Section 079200 - Joint Sealants:
m. Section 08 14 00 - Interior Wood Doors
n. Section 083100 - Access Doors and Panels.
o. Section 083473 – Sound Control Assemblies
p. Section 090600 - Schedule For Finishes.
q. Section 093000 - Tiling:
r. Section 097200 - Wall Coverings:
s. Section 099113 - Exterior Painting
t. Section 220516 - Expansion Fittings and Loops for Plumbing Piping.
u. Section 220548 - Vibration and Seismic Controls for Plumbing Piping and Equipment.
v. Section 230513 - Common Motor Requirements for HVAC Equipment
w. Section 231123 - Facility Natural-Gas Piping
x. Section 231126 - Facility Liquefied-Petroleum Gas Piping.
y. Section 233600 – Air Terminal Units
z. Section 262100 - Low-Voltage Electrical Service Entrance
aa. Section 262200 - Low-Voltage Transformers:
bb. Section 264300 - Surge Protective Devices
cc. Section 265600 - Exterior Lighting
dd. Section 312323 – Fill
ee. Section 330110.58 - Disinfection of Water Utility Piping Systems.
27 Table of Contents See revised addendum.
a. Section 260553 - Identification for Electrical Systems was not identified
28 3. Specification Section 011000 – SUMMARY – 1.03 DESCRIPTION OF ALTERATIONS WORK – Owner will remove the following items before start of work:
a. Please provide a list of the items the owner intends to remove
COR WILL DISCUSS AND PROVIDE A WALKTHROUGH DURING THE
PRECONSTRUCTION MEETING. ITEMS WILL BE IDENTIFIED DURING
THAT TIME.
29 Specification Section 011000 – SUMMARY – 1.04 WORK BY OWNER – Item B,C,D,E owner provided items.
a. Please provide a list of the items the owner intends to install
b. Please provide a list of the items (NIC) not in this contract
A. Reference equipment schedule on sheet A101.1.
30 Specification Section 011000 – SUMMARY – 1.06 CONTRACTOR USE OF SITE AND PREMISES - C. Provide access to and from site as required by law and by Owner:
a. Can you provide contractor egress route to exterior including corridor and exist doors?
The preferred route to egress and contractor exterior storage is approx. 250 feet from the construction area. A closer route may be available and will be verified during the preconstruction meeting.
31 Specification Section 011000 – SUMMARY – 1.06 CONTRACTOR USE OF SITE AND PREMISES - I. Noise, Vibration, Dust, and Odors: Coordinate operations that may result in high levels of noise and vibration, dust, odors, or other disruption to Owner occupancy with Owner.
a. Is there restricted access hours were we are not able to work after the normal construction times?
Depending on the activity, restrictions will be discussed with the awarded contractor during the sequencing of the work.
32 Specification Section 013526 – SAFETY REQUIREMENTS FOR
MAJOR PROJECTS - .10 “SITE SAFETY AND HEALTH OFFICER”
(SSHO) AND “COMPETENT PERSON” (CP):
a. Can the superintendent perform dual hat responsibility’s for SSHO and Superintendent at the same time.?
The superintendent will perform dual services.
33 Specification Section 015000 – TEMPORARY FACILITIES AND CONTROLS - 1.04 TEMPORARY UTILITIES as referenced in items A and B below
A. Owner will provide the following:
1. Electrical power and metering, consisting of connection to existing facilities.
2. Water supply, consisting of connection to existing facilities.
B. Provide and pay for all electrical power, lighting, water, heating and cooling, and ventilation required for construction purposes.
a. Item A and Item B conflict with each other.
b. Confirm the electrical power and water to be provided by owner and the utilization of existing HVAC system will be used for temporary heat and cooling.
The requirement for the contractor to pay fore electrical power and water has been removed with Addendum 01.
34 Specification Section 015000 – TEMPORARY FACILITIES AND
CONTROLS - 1.06 FENCING –
a. Please provide a staging area location and defined area for temporary trailer, dumpster, construction vehicles and storage.
This location will be determined with the awarded contractor.
35 Specification Section 030516 - UNDERSLAB VAPOR BARRIER – STEGO - 3.02 INSTALLATION - B. Install vapor barrier under interior slabs on grade; lap sheet over footings and seal to foundation walls.
a. Please provide location where this would be required.
b. In reference to detail 14 on sheet A420.1 indicating the existing concrete at trench for the new CT scanner only extends to a depth of 3 ½” and the existing slab is indicated at
Note for lapping vapor barrier over footings will be removed with Addendum 01.
Vapor barrier to be provided under the new slab will be included with Addendum 01.
See reissued Underslab Vapor Barrier with Addendum 01.
5 ½”. From the design this area would not require vapor barrier.
c. Please confirm the requirement for stego wrap?
36 Specification Section 033000 - CAST-IN-PLACE CONCRETE -
1.01 SECTION INCLUDES – A Floors and Slabs on Grade.
a. Provide clarification any new concrete would be at the new trench duct only.
b. Would there be any other areas for new concrete.
The trench duct and new floor drain is the only anticipated area that would require new concrete.
37 Specification Section 033000 - CAST-IN-PLACE CONCRETE -
1.01 SECTION INCLUDES - C. Miscellaneous concrete elements, including equipment pads, equipment pits, light pole bases, flagpole bases, thrust blocks, and manholes.
a. The items Indicated in item C above are not defined in the scope of work.
b. Please provide clarification and location of items.
c. Can you define the locations of any equipment pads?
No equipment pads, equipment pits, light pole bases, flagpole bases, thrust blocks or manholes are included in this project. This text will be removed with Addendum 01.
38 Specification Section 081113 - HOLLOW METAL DOORS AND FRAMES - 2.05 FINISHES - B. Factory Finish: Complying with ANSI/SDI A250.3, manufacturer's standard coating.
a. In Section 2.03 and 2.04 the door and frame finishes are specified as a field finish
b. Can you provide confirmation that the HM doors and frames are field finished.
Door finish is to be factory finished, this will be addressed in Addendum 01.
39 Specification Section 081416 - FLUSH WOOD DOORS - 2.05 FINISHES - WOOD VENEER DOORS - Finish work in accordance with WDMA I.S. 1A for grade specified and as follows:
Door finish work to be finished with a transparent TR-6 catalyzed polyurethane, satin sh
a. The section does not define the finish work
b. Can you provide requirements for finishes on wood doors?
40 Specification Section 084418 – GLAZED STEEL CURTAIN WALLS
a. From the plans it does not appear Glazed Curtain Walls are part of the scope of work.
b. Can you provide the location and details of the required Glazed Curtain walls on the plans.
Correct. No glazed steel curtain walls are to be provided.
41 Specification Section 087100 - DOOR HARDWARE – 1.01 SUMMARY B. Item 5 Overhead Doors
a. From the plans an overhead door is not identified in the opening schedule or plans
b. Please provide the location and appropriate specifications for overhead doors
Correct. No overhead doors included.
42 Specification Section 087100 - DOOR HARDWARE – 1.01
SUMMARY C.
a. Item 1 Division 01 Section “Alternates” – Please define any alternates
b. Item 2 Division 06 Section “Rough Carpentry” – Please add required specification section
c. Item 3 Division 06 Section “Finish Carpentry” – Please add required specification section
See updated Addendum 01.
43 Specification Section 087100 - DOOR HARDWARE – Hardware Group CO-01 for use on door 102
a. The door schedule on sheet A4201.1 does not indicate door
This is not a door, it is an 8’-0” cased opening – no hardware required.
b. Can you provide the opening size and details for door 102
44 Specification Section 117311 - PATIENT LIFTS - 2.01
MANUFACTURERS –
a. Can you provide basis of design product information for the patient lift system
Final drawings will be coordinated once the equipment is procured by IHS and coordinated with the awarded contractor. As indicated on the equipment schedule, Guldmann system Type A was coordinated in the drawings. A similar product would also be acceptable by IHS by Arjo.
45 Specification Section 123600 - COUNTERTOPS – 1.02 RELATED
REQUIREMENTS –
a. Section 064100 – Architectural Wood Casework Section is not included in Bid Documents
b. Clarify if it should be section 064116 Plastic-Laminate-Faced Architectural Cabinets
Section 064116 Plastic Laminate – Faced Architectural Cabinets is correct related requirement. 064100 Architectural Wood casework is not included.
46 Specification Section 134900 – RADIATION PROTECTION 3.01
MATERIALS.
a. This section identifies several materials that are not identified in the plans work including Lead Lined Concrete Masonry Units, Lead Lined Gypsum Lath, Lead Lined Plywood Panels:
b. Can you provide the locations of the above required materials that will be incorporated
c. The lead lined window is not indicated in this specification section
d. Please provide specifications requirements for Lead Lined Window
Addendum 01 reissued 134900 specification section revised the materials.
47 Specification Section 134900 – RADIATION PROTECTION 3.01
MATERIALS.
Drawings A420.1 includes the lead lined window specification notes.
a. The lead lined window identified in the plans for the control room is not indicated in this specification section
b. Can you please provide the required specifications and product details for Lead Lined Window
48 Specification Section - FIRE SUPPRESSION SPRINKLER SYSTEM
3.02 INTERFACE WITH OTHER PRODUCTS
a. Provide existing Fire Alarm System manufacture and service provider
JCI is the existing fire alarm system manufacturer.
49 Specification Section – 220553 IDENTIFICATION FOR
PLUMBING PIPING AND EQUIPMENT – 1.02 RELATED
REQUIREMENTS A. Section 099123 - Interior Painting:
Identification painting.
a. The 099123 section does not identify the requirements for this work
b. Can you provide requirements for the identification painting
Painting of plumbing equipment or piping is not required.
50 Specification Section – 220719 PLUMBING PIPING INSULATION
– 1.02 RELATED REQUIREMENTS C. Section 099123 - Interior Painting: Painting insulation jacket.
a. The 099123 section does not identify requirements provide requirements for painting
Painting the insulation jacket is not required.
51 Specification Section – 221006 PLUMBING PIPING SPECIALTIES
– 1.02 RELATED REQUIREMENTS. A. Section 011000 - Summary: Product requirements for Owner furnished kitchen equipment.
a. In Section 011000 provide any required owner furnished equipment schedule
There is no kitchen in scope.
52 Specification Section – 221006 PLUMBING PIPING SPECIALTIES
– 2.02 DRAINS A. Shower Channel Drain (TD-1): Factory fabricated channel and grate with built in outlet pipe.
a. Shower drain channels are not indicted in the plans please provide location
Initially we intended to include shower channel drains, however, this was changed per the plans with standard drains.
53 Specification Section – 221006 PLUMBING PIPING SPECIALTIES
– 2.03 CLEANOUTS
a. Can you provide the Cleanout’s locations as they are not identified in the plans
Provide cleanouts at each new elbow installed
54 Specification Section – 2213000 PLUMBING EQUIPMENT –
2.01 WATER HEATERS A. Manufacturers:
a. As identified in the plans on sheet P500.1 in the schedule it identifies a Bosch manufacture.
b. The specifications do not indicate Bosch as a manufacture.
Bosch is an acceptable manufacturer for water heaters.
55 Specification Section – 224000 PLUMBING FIXTURES – 1.02 RELATED REQUIREMENTS. A. Section 011000 - Summary:
Owner-furnished fixtures.
a. Can you provide the list of owner provided fixtures and the product details
See drawing A101.1, Equipment Schedule
56 Specification Section – 230593 TESTING, ADJUSTING, AND
BALANCING FOR HVAC – 1.03 PRICE AND PAYMENT
PROCEDURES
A. Cash Allowance: See Section 012100 for additional requirements.
B. Allowance includes testing, adjusting, and balancing of mechanical systems.
a. Please provide the 012100 section as it was not included in the bidding documents
The specifications were not meant to include a cash allowance for T&B.
Cash allowance are not apart of this specification.
b. Can you provide any allowances to be incorporated into scope of work
57 Section 233700 AIR OUTLETS AND INLETS - 2.05 DOOR GRILLES and 2.06 LOUVERS
a. The plans do not indicate any locations of door grilles can you provide the locations and specifications
b. The plans do not indicate any locations for louvers can you provide the locations and specifications
There are no door grills or louvers included on tis project. The specification for these was included a potential add for a door grill or louver.
58 Section 260539 UNDERFLOOR RACEWAYS FOR ELECTRICAL
SYSTEMS - 2.02 FLUSH INFLOOR DUCT
a. Can you provide basis of design product?
Basis of design – Manufacture: Legend Product: Trench Feeder Systems. Specify product in accordance with arch drawings.
59 Section 260923 LIGHTING CONTROL DEVICES - 2.05 OUTDOOR
PHOTO CONTROLS
a. The plans do not indicate a location of exterior photo controls can you please provide the location and specifications for photo cells.
There is no exterior lighting controls for this project, disregard specs section.
60 Section 263353 STATIC UNINTERRUPTIBLE POWER SUPPLY -
2.02 UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEMS
a. Please provide the basis of design product for the UPS system
Basis of Design – For Partial UPS system (called out on drawings):
One (1) Liebert EXS, Model EXS15KN, 15KVA Capacity, 3 phase UPS
One (1) Wall-Mount Maintenance Bypass, Model WMBC208- EXS15K3BTK, 15kVA Capacity, Nominal 208 VAC 3ph/4W/G
For Full UPS system:
1.0 Vertiv APM2 Modular Three Phase VAC UPS System consisting o the following: Quantity One (1) model 56O120PNN4. Capacity rating 12kVA.
61 Are the equipment/panels supplied with the CT equipment? CT equipment vendor will provide the main disconnect panel for installation in the CT room by the electrical contractor.
62 Do they have any documentation on the temporary CT machine and the new equipment that we will be installing?
- Are we responsible for receiving that equipment storing and setting or will that all be by others?
It is anticipated that the existing temporary connection will support this. No work will be required for the contractor for this.
| ADPAA4.tmp |
| END OF SUMMARY OF CHANGES |
| SECTION C – DESCRIPTION/SPECIFICATIONS/STATEMENT OF WORK |
| 1. Project Description |
| 3. Submittals |
| 4. Schedule/Meetings |
| 5. Miscellaneous |
| a. |
| b. |
| c. |
| d. |
| e. |
| f. |
| 6. Payments to the Contractor |
| 7. IHS Personnel |
| 8. Invoice Format |
| 9. Closeout Documents |
| SECTION F – DELIVERIES OR PERFORMANCE |
| ADP6CB2.tmp |
| END OF SUMMARY OF CHANGES |
| ADP7CF3.tmp |
| END OF SUMMARY OF CHANGES |
| ADP5930.tmp |
| END OF SUMMARY OF CHANGES |
| SECTION I – CONTRACT CLAUSES |
| SECTION K – REPRESENTATIONS, CERTIFICATIONS, AND OTHER STATEMENTS OF OFFERORS |
| SECTION L – INSTRUCTIONS, CONDITIONS, & NOTICES TO OFFERORS |
| ADP60E8.tmp |
| END OF SUMMARY OF CHANGES |
| SECTION I – CONTRACT CLAUSES |
| SECTION K – REPRESENTATIONS, CERTIFICATIONS, AND OTHER STATEMENTS OF OFFERORS |
| SECTION L – INSTRUCTIONS, CONDITIONS, & NOTICES TO OFFERORS |
| ADP7948.tmp |
| END OF SUMMARY OF CHANGES |
| SECTION I – CONTRACT CLAUSES |
| ADPBBC0.tmp |
| END OF SUMMARY OF CHANGES |
| SECTION I – CONTRACT CLAUSES |
| ADP3F0A.tmp |
| END OF SUMMARY OF CHANGES |
| ADP994.tmp |
| END OF SUMMARY OF CHANGES |
| ADPF11C.tmp |
| END OF SUMMARY OF CHANGES |
| ADPFC8.tmp |
| END OF SUMMARY OF CHANGES |
| ADPA10E.tmp |
| END OF SUMMARY OF CHANGES |
| topmostSubform[0]: |
| Page1[0]: |
| AmendmentNo[0]: A00004 |
| Code[0]: |
| Code[1]: |
| AccountingData[0]: |
| A13[0]: |
| C13[0]: |
| D13[0]: |
| NameandTitleSigner[0]: |
| NameandTitleOfficer[0]: Taylor M. Kanthack |
| Description[0]: |
Please see continuation page.
| FacilityCode[0]: |
| Code[2]: |
| IssuedBy[0]: Indian Health Service (IHS) |
Division of Engineering Services (DES) - Seattle 701 5th Ave, Suite 1650 Seattle, WA 98104
| NameandAddress[0]: |
| AdministeredBy[0]: See item 6 |
| ContractIDCode[0]: |
| ReqNumber[0]: |
| AmendmentNo[1]: 75H70125R00016 |
| ProjectNo[0]: |
| Page[0]: 1 |
| Pages[0]: 21 |
| EffectiveDate[0]: 5/22/2025 |
| Dated9B[0]: 2/3/2025 |
| Dated10B[0]: |
| CheckBox9[0]: 1 |
| CheckBox10[0]: Off |
| CheckBox11[0]: 1 |
| CheckBox13A[0]: Off |
| CheckBox13B[0]: Off |
| CheckBox13C[0]: Off |
| CheckBox13D[0]: Off |
| IsNot[0]: Off |
| Is[0]: Off |
| Extended[0]: 1 |
| NotExtended[0]: Off |
| DateSigned[0]: |
| DateSigned[1]: |
| Copies[0]: |
| CopiesReturned[0]: |
File details come from the government source that posted it. Updated .