75H70122R00045-A00004.pdf

PDF 465 KB Posted

Attached to
Shitike Creek Water Main Crossing - Warm Springs, OR
Solicitation number
75H70122R00045
Issued by

About this file

This solicitation is for the Shitike Creek Water Main Crossing construction project for the Indian Health Service. Key details include:

  • The project scope involves construction of approximately 1,000 linear feet of 16-inch ductile iron water main, including a bridge crossing over Shitike Creek.

  • The location is at the intersection of Wolford Canyon Road and Hollywood Boulevard in Warm Springs, Oregon. The period of performance is 150 calendar days from notice to proceed.

  • The estimated value is between $1-5 million. The contract type will be firm-fixed price.

  • The solicitation is set aside 100% for small businesses, with preference given to Indian Economic Enterprise firms. The NAICS code is 237110.

  • Proposals are due by June 22, 2022. The pre-bid site visit was held on June 7, 2022. All work is subject to the Tribal Employment Rights Ordinance of the Confederated Tribes of Warm Springs. Registration in SAM is required for consideration for award.

View the file

Other files

File Type Posted
J09 Section B Price Schedule (OFFEROR FILL-IN) (REVISED as of A00006).xlsx XLSX spreadsheet
J04 WD OR20220069 dated 07082022.pdf PDF
75H70122R00045-A00006.pdf PDF
RFP 75H70122R00045 as of A00005.pdf PDF
75H70122R00045-A00005.pdf PDF
J09 Section B Price Schedule (OFFEROR FILL-IN).xlsx XLSX spreadsheet
J01 Technical Specifications - Shitike Creek Crossing (REVISED as of A00003).pdf PDF
75H70122R00045-A00003.pdf PDF
75H70122R00045-A00002.pdf PDF
J02a Plans - Bridge Water Main Crossing.pdf PDF
75H70122R00045-A00001.pdf PDF
Exhibit 3 - Warm Springs Interdisciplinary Team - Small Project Approval Resolution.pdf PDF
J06 Company Specialized Experience Form.docx DOCX document
J08 IHS IEE Representation Form.pdf PDF
Exhibit 1 - Geotechnical Evaluation and Utility Research Report.pdf PDF
J05 Self Performed Calculation Sheet (Construction).docx DOCX document
J02 Plans - Shitike Creek Crossing.pdf PDF
J04 WD OR20220069 04012022.pdf PDF
J03 Submittal and Testing Log.xlsx XLSX spreadsheet
J09 Section B Price Schedule (OFFEROR FILL-IN).xlsx XLSX spreadsheet
Exhibit 2 - Shitike Creek Crossing PP and Detail Sheets from As-builts.pdf PDF
J07 PPQ.docx DOCX document
J01 Technical Specifications - Shitike Creek Crossing.pdf PDF
RFP 75H70122R00045.pdf PDF
Exhibit 6 - Shitike Creek Cable Relocation Cost Estimate.pdf PDF
Exhibit 5 - Lumen Cable Relocation Special Construction Proposal.pdf PDF
Exhibit 4 - Example BIA Control Plan.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE OF PAGES

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

Previous edition unusable

A00004

TOBY HAYDEN

75H70122R00045 Shitike Creek Water Main Crossing

The purpose of Amendment A00004 is to answer additional questions, update attachment J09, and extend the proposal due date. All other terms and conditions remain unchanged. See continuation page for details.

Indian Health Service - DES Seattle 701 5th Avenue, Suite 1600 Seattle, WA 98104

75H70122R00045

PO-20-M97

1 4

06/15/2022

05/20/2022

6/15/2022

SF 30 Continuation Page

75H70122R00045-A00004 Page 2 of 4

Amendment A00004 – SF 30, Block 14 (Cont’d)

The purpose of this amendment is as follows:

1. Additional questions (20 - 26) have been received and answered in response to this solicitation:

QUESTION ANSWER

I don't see any details for the bridge crossing. Are there drawings for this section that I am not seeing?

See attachment J02a Plans - Bridge Water Main

Crossing

The DI pipe will take about 150 day lead time from order. Do you have a provision for this regarding completion time?

The period of performance (POP) for this effort is 150 days from NTP; NTP is anticipated to be issued 10 days after award. For long lead time items, the contractor is expected to order approved materials as soon as possible in order to accommodate this POP.

Extensions to the POP will be considered for unusually long lead time items.

Requesting alternate equipment/material: Fusible

C900 pipe

Fusible PVC C900 is not an approved substitute for

Class 350 ductile iron water main.

Do you have any more detail on the bridge crossing? I do not see any information on it in the bid documents.

See answer to Q1

Is there a maximum length for the required 2 pipe sections after the welded-outlet for the blow-off assembly?

A full 20’ pipe section is allowable, as long as there are

2 connections with a minimum length of 2’ per connection.

We have had long delays in receiving ductile iron water main (~150-180 days), how will this affect the period of performance?

See answer to Q2

What is the nearest waste disposal location? There is a transfer station located in Madras, OR. The

Confederated Tribes of Warm Springs operates a landfill within Warm Springs, but its availability hasn’t been verified. Excess rock and spoil can be dumped at the nearby Warm Springs Wastewater Treatment Plant.

Are the tests (e.g. compactions tests) and special inspections the responsibility of the contractor?

Testing and special inspections as outlined in the specifications are the responsibility of the contractor.

The identity of the independent testing entities is required as a submittal.

Does the TERO office have traffic flaggers available for hire?

Yes, the TERO contact number is 541-615-0853, and website: wstero.com

What are the rush-hour times for traffic along

Hollywood Boulevard?

7:45-8:30am and 4:30-5:30pm.

What type of connections should be used for the tee that will connect to the existing system?

Welded flanges are preferred for the tee connecting to the existing system. The rest of the connections are as listed in the technical specifications.

Is there a preference on the order of installation for the water main?

In order to minimize downtime of the system, the

Utility prefers making the connections to the existing water main with the isolation valves, then to proceed with the rest of the water main installation.

What is the purpose of the shear pin in the bridge crossing supports?

The shear pin provides resistance to shear forces between the concrete curb and girder from the pipe weight.

75H70122R00045-A00004 Page 3 of 4

Is a flexible expansion joint required for the bridge crossing?

A flexible expansion joint is not included in the design.

The TR Flex restrained joints specified provide adequate movement to allow for expansion.

Is there a side view of the pipe support for the bridge crossing?

Side views are not available. Standard dimensions of the ASTM A36 steel members are available online however.

Are pipe saddles required for the pipe insulation on the bridge crossing?

Pipe saddle supports are required at the bridge at the bridge supports. Pipe insulation will be jacketed around pipe with aluminum sheeting, which will be secured with stainless steel strapping, per the specifications

(Section 33 14 13, pg 10; sheets CP-02 and CP-03).

Is there an escalation clause for long lead times on material?

No

Is there a waiver on Buy American clauses? If so, does it apply to this project?

There are currently no waivers for the acquisition. The requirements of contract clause FAR 52.225-9 Buy

American – Construction Materials (NOV 2021) and

FAR 52.225-10 Notice of Buy American Requirement

– Construction Materials (MAY 2014) are applicable to this solicitation and resulting contract.

Offerors may request a determination of inapplicability of the Buy American statute by submitting a request to the Contracting Officer in accordance with FAR

52.225-10 paragraph (b)

Do you guys have a contact list for all job walk attendees on 6/7/22?

The companies in attendance were as follows:

Doyon

York Bros

McDonalds Excavating

Mckernan

NWCP

Bridge Masters Inc.

Spec section 33 14 13, 1.8 calls for a test pressure of 440 psi on the bridge and buried pipe crossing.

The gasket material which determines the maximum pressure for the pipe is only 350 psi for the flange gaskets and TR Flex gaskets (assuming a Flange Tyte gasket from US Pipe). The butterfly valves are only rated to 150 psi for a

Class 150B. This material is not designed for these pressures. Do you want a different pipe/valve material or will a lower test pressure be acceptable?

A test pressure of 350 psi will be acceptable. For the butterfly valve please see the revised specifications section 33 14 13. The valve must meet the AWWA

C504 standard for Class 250B valves, but exceed the standard's requirement for working pressure to meet

350 psi.

I did not see a test or working pressure for the balance of the 16” ductile iron water line. Is it as high as the bridge crossing?

The specified working pressure for the remainder of the ductile iron water main is the same as the bridge-crossing at 350 psi.

I did not find any requirements for Buy

America(n) or BABA in the specifications. Will any of these be required on this project?

See answer to Q18

Is the 16” bridge crossing pipe connected to the rest of the 16” in schedule A?

Yes, the 16" water main will be connected with the bridge crossing water main. The bridge crossing design was done by a separate designer, hence the apparent disconnect.

The Price Schedule for CLIN 0001- SCHEDULE

A calls for 1” DI Butterfly Valve on item 10 shouldn’t this be 16”?

Yes, this is a typo. The butterfly valve should be 16" diameter. (See revised attachment J09)

75H70122R00045-A00004 Page 4 of 4

Specification section 33 14 13, 2.3, C, 1 & 8 sound as if you do not want mechanical joint fittings is that the case?

For the 16" ductile iron water main that is the case. The piping type is included in Section 33 14 13, 1.8

The blow off detail on plan sheet C502 shows a

4” x 2” eccentric reducer. That isn’t made in a TR

Flex fitting. We could do a MJ 4” cap that is tapped for 2” galvanized pipe would that work for you?

This would be acceptable provided the MJ 4" cap is restrained.

2. Section J Attachment J09 Section B Price Schedule (OFFEROR FILL-IN) is revised to correct the description of Item 10:

FROM: D.I. Butterfly Valve, 1" Diameter

TO: D.I. Butterfly Valve, 16" Diameter

3. The proposal due date is extended to Wednesday, June 22, 2022 at 2:00 PM PT.

4. All other terms and conditions remain unchanged.

Offerors are reminded to acknowledge all amendments on the SF1442 when submitting a proposal in accordance with the RFP requirements.

2022-06-15T16:29:16-0700
Toby M. Hayden -S

File details come from the government source that posted it. Updated .