Attachment 3 Water Quality Testing Requirements.pdf
PDF 69 KB Posted
- Attached to
- S. DeGoede Well (COW)
- Solicitation number
- 75H7012
About this file
This document is a technical specification table establishing water quality testing requirements based on Washington Administrative Code (WAC) Section 246-291-171.
The document specifies Maximum Contaminant Limits (MCLs) for inorganic chemicals and physical characteristics that must be tested in water samples, along with a required bacterial test. For inorganic chemicals, primary MCLs are established for 15 substances including antimony (0.006 mg/L), arsenic (0.01 mg/L), barium (2.0 mg/L), beryllium (0.004 mg/L), cadmium (0.005 mg/L), chromium (0.1 mg/L), cyanide (0.2 mg/L), fluoride (4.0 mg/L), mercury (0.002 mg/L), nickel (0.1 mg/L), nitrate as N (10.0 mg/L), nitrite as N (1.0 mg/L), selenium (0.05 mg/L), and thallium (0.002 mg/L). Sodium is also required for monitoring despite lacking an established MCL due to public health significance. Secondary MCLs are established for nine additional substances including chloride (250.0 mg/L), copper (1.3 mg/L), fluoride (2.0 mg/L), iron (0.3 mg/L), lead (0.015 mg/L), manganese (0.05 mg/L), silver (0.1 mg/L), sulfate (250.0 mg/L), and zinc (5.0 mg/L). For physical characteristics, turbidity has a primary MCL of 1.0 NTU, while secondary MCLs include color (15 Color Units), specific conductivity (700 umhos/cm), total dissolved solids (500 mg/L), and pH (6.5–8.5). Note that copper and lead MCLs are designated as Maximum Contaminant Level Goals (MCLGs) per the Washington State Department of Health Lead and Copper Rule.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 75H70126Q00030-A00002.pdf | ||
| Attachment 2 Pump Test Field Data Recording Form.pdf | ||
| 75H70126Q00030-A00001.pdf | ||
| Attachment 1 Local Well Logs.pdf | ||
| 2-Technical Specifications.pdf | ||
| 1-Statement of Work.docx | DOCX document | |
| 4-Site Plan DeGoede.pdf | ||
| 3-Aerial View DeGoede.pdf | ||
| 6-US DOL WA20260051 Dated 5-18-2026.pdf | ||
| B01 75H70126Q00030.pdf | ||
| A11 Pre-Solicitation SAM Notice.pdf | ||
| 5-Measurement and Payment.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Chemicals required to be tested and corresponding Maximum Contaminant Limits (MCLs), modified from the Washington Administrative Code (WAC) Section 246-291-171. Note: A bacterial test is also required.
Table 1
INORGANIC CHEMICAL CHARACTERISTICS
Substance Primary MCLs (mg/L)
Antimony 0.006 Arsenic 0.01 Barium 2.0 Beryllium 0.004 Cadmium 0.005 Chromium 0.1 Cyanide 0.2 Fluoride 4.0 Mercury 0.002 Nickel 0.1 Nitrate (as N) 10.0 Nitrite (as N) 1.0 Selenium (Se) 0.05 Sodium (Na) * Thallium 0.002
Substance Secondary MCLs (mg/L)
250.0
2.0 0.3
0.05 0.1 250.0
Chloride (Cl) Copper (Cu)** Fluoride (F) Iron (Fe) Lead (Pb)** Manganese (Mn) Silver (Ag) Sulfate (SO4) Zinc (Zn) 5.0
*Although there is not an established MCL for sodium, there is enough public health significance connected with sodium levels to require inclusion in inorganic chemical and physical monitoring.
**MCLG (Maximum Contaminant Level Goal), as set by the Washington State Department of Health Lead and Copper Rule.
1.3
0.015
Table 2
PHYSICAL CHARACTERISTICS
Substance Primary MCL Turbidity 1.0 NTU
Substance Secondary MCLs Color Hardness Specific Conductivity Total Dissolved Solids (TDS)
15 Color Units None established 700 umhos/cm 500 mg/L pH
Alkalinity (as CaCO3)
6.5 – 8.5 None established
| Table 1 |
| Table 2 |
File details come from the government source that posted it. Updated .