7440851 DrawingsAsOne.pdf
PDF 8 MB Posted
- Attached to
- REPLACE CHILLER & COOLING TOWER, BLDG 4225
- Solicitation number
- N400857440851
About this file
Summary: Construction Drawing Set for Building 4225 Chiller and Cooling Tower Replacement
This document is a comprehensive set of construction drawings for the replacement of chillers and cooling tower systems at Building 4225, Marine Corps Air Station Cherry Point, North Carolina. The project, designated Work Order No. 7440851, is managed by Naval Facilities Engineering Systems Command (NAVFAC) Mid-Atlantic, with Summer Consultants Incorporated serving as the design firm. The contract number is referenced as 12939345, with individual drawing numbers ranging from 12939346 to 12939383. The project involves demolition of existing equipment and installation of new air-cooled chillers, with a design date of May 4, 2026.
The drawing set includes civil, structural, mechanical, and electrical components. Civil work encompasses demolition plans, site layout with 8-foot chain-link security fencing, and concrete pads with 1.04% slope for drainage. Structural designs specify concrete foundations (3000 psi strength), steel framing with AISC LRFD specifications, anchor bolt details, and equipment support systems. Mechanical systems include two rotary screw chillers (300-ton capacity each), expansion tanks, end-suction pumps with variable frequency drives, control valves, and piping schedules with heat tracing for exterior applications. Electrical work provides for power distribution from existing switchboards, variable frequency drive installations, motor control centers, panel schedules, and temporary chiller connections. The project must be executed while the building remains occupied with scheduled weekend outages for critical work, requiring temporary 250-ton and 80-ton chiller provisions during construction. All existing hazardous materials assessments indicate no asbestos-containing materials or elevated lead-based paint requiring abatement.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 7440851 Amendment 0004.pdf | ||
| 7440851 Amendment 0003.pdf | ||
| 7440851 Amendment 0002.pdf | ||
| 7440851 Amendment 0001.pdf | ||
| 7440851 SpecsAsOne.pdf | ||
| RFP_7440851.pdf | ||
| Master PPI Form.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION
MAIN GATE PASS AND
ID OFFICE
ROOSEVELT BLVD.
PROJECT LOCATION
BUILDING 4225
SLOCUM GATE
BUILDING
BUILDING
BEAUFORT RD.
E STREET
ROOSEVELT BLVD
2ND AVE.
E STREET
PROJECT LOCATION - B4225
A STREET
CUNNINGHAM BOULEVARD
ROOSEVELT BOULEVARD
FI
LE
N
AM
E:
OU
R
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :23
:55 P
M
1.0
1.0
G
-0
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
G-001 12939345
CO
VE
R
SH
EE
T
ZAC ZAC WAN
SHEET
NUMBER SHEET TITLE NAVFAC
DWG NO.
G-001 COVER SHEET 12939345
CD201 CIVIL DEMOLITION PLAN 12939346
CS301 CIVIL SITE PLAN 12939347
S-001 STRUCTURAL NOTES 12939348
S-002 STRUCTURAL NOTES 12939349
S-100 FOUNDATION DEMO PLAN 12939350
S-101 FOUNDATION PLAN 12939351
S-102 FRAMING PLAN 12939352
M-001 SYMBOLS & ABBREVIATIONS 12939353
M-002 PHASING PLAN 12939354
MD101 OVERALL PLAN - DEMOLITION 12939355
MD102 CONTROL VALVE PLAN - DEMOLITION 12939356
MD401 MECHANICAL ROOM PLAN - DEMOLITION 12939357
MD402 YARD PLAN - DEMOLITION 12939358
M-101 OVERALL PLAN 12939359
M-102 CONTROL VALVE PLAN 12939360
M-401 MECHANICAL ROOM PLAN 12939361
M-402 YARD PLAN 12939362
M-403 ROOF PLAN 12939363
M-501 DETAILS 12939364
M-601 SCHEDULES 12939365
M-701 CONTROLS COVER 12939366
M-702 CONTROLS 12939367
M-703 CONTROLS 12939368
E-001 SYMBOLS AND ABBREVIATIONS 12939369
ED101 OVERALL PLAN - DEMOLITION 12939370
ED401 MECHANICAL ROOM PLAN - DEMOLITION 12939371
ED402 ELECTRICAL ROOM PLAN - DEMOLITION 12939372
ED403 MECHANICAL YARD PLAN - DEMOLITION 12939373
SHEET
NUMBER SHEET TITLE NAVFAC
DWG NO.
E-101 OVERALL PLAN 12939374
E-401 MECHANICAL ROOM PLAN 12939375
E-402 ELECTRICAL ROOM PLAN 12939376
E-403 MECHANICAL YARD PLAN 12939377
E-601 SCHEDULES 12939378
E-602 PANEL SCHEDULES 12939379
E-603 PANEL SCHEDULES 12939380
E-604 PANEL SCHEDULES 12939381
E-605 PANEL SCHEDULES 12939382
E-606 PARTIAL POWER RISER DIAGRAM 12939383
CHERRY POINT, NORTH CAROLINA
WORK ORDER NO.
VICINITY MAPLOCATION MAP
MARINE CORPS AIR STATION
N N
DRAWING INDEX
CONSTRUCTION CONTRACT NO.
REPLACE CHILLERS & COOLING TOWER
CHERRY POINT, NORTH CAROLINA
WORK ORDER NO.
BUILDING 4225
MARINE CORPS AIR STATION
7440851
HAZMAT SUMMARY
NO ASBESTOS CONTAINING MATERIALS HAVE BEEN IDENTIFIED
IN THE CHILLER PLANT AREA
NO LEAD BASED PAINT WITH LEAD GREATER THAN OR EQUAL
TO 1.0 MG/CM2 HAVE BEEN IDENTIFIED IN THE CHILLER PLANT
AREA.
PAINT MUST BE CONSIDERED LEAD CONTAINING AT
CONCENTRATIONS LESS THAN 1.0 MG/CM2.
PERFORM WORK IN ACCORDANCE WITH SPECIFICATIONS, OSHA
STANDARDS AND GUIDELINES, INCLUDING 29 CFR 1926.62, LEAD
EXPOSURE IN CONSTRUCTION STANDARDS.
05/04/2026
CT-1 CT-2
SCALE: 1" = 10' 0 5' 30'20'10'A1 CIVIL DEMOLITION PLAN PLAN
NORTH
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
WE WE CR
KEY PLAN
N.T.S.
N
GENERAL SHEET NOTES
1. THIS SHEET IS PART OF A MULTI-SHEET SET OF CONSTRUCTION
PLANS AND MUST BE READ WITH THE FULL SET TO BEST ENSURE
PROPER INTERPRETATION.
2. ANY WORK/CUTOVERS/INTERRUPTIONS ON EXISTING UTILITIES
MUST BE SCHEDULED THROUGH THE BASE AT LEAST 14 DAYS IN
ADVANCE.
3. BACKGROUND INFORMATION HAS BEEN PROVIDED BY SUMMER
CONSULTANTS. NO SURVEY HAS BEEN PERFORMED.
CONTRACTOR MUST VERIFY ALL EXISTING CONDITIONS PRIOR
TO DEMOLITION AND CONSTRUCTION.
LEGEND:
DEMOLITION AREA
ITEM DEMOLITION/ / / / / / / / / / / / / /
SHEET KEYNOTES
1. DEMO THIS PART OF EXISTING CHAIN-LINK FENCE.
2. DEMO MECHANICAL EQUIPMENTS AND CONCRETE INSIDE THIS
AREA - REFER TO MECHANICAL DRAWINGS SHEET (MD402) AND
STRUCTURAL DRAWINGS SHEET (S-100).
3. EXISTING CHAIN-LINK FENCE TO REMAIN.
4. EXISTING GATE TO REMAIN.
5. EXISTING SIDEWALK.
6. TEMPORARY CONSTRUCTION FENCE - SEE DETAIL (D1), SHEET
(CD201)
CI
VI
L D
EM
OL
IT
IO
N
PL
AN
3 3
43.29'
.6
7'
27.14'
D1 TEMPORARY CONSTRUCTION FENCE DETAIL
NTS
TEMPORARY CONSTRUCTION FENCE
66.66'
RAYMOND1035 GREEN ST.
SUITE A
CONYERS, GA
30012
CD201
12939346
X
X
X
X
X
X X X X X X
X X
X X
SCALE: 1" = 10' 0 5' 30'20'10'A1 CIVIL SITE PLAN PLAN
NORTH
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
WE WE CR
KEY PLAN
N.T.S.
N
D3 8 FT CHAIN LINK SECURITY FENCE DETAIL
NTS
1. PROPOSED 8 FT CHAIN-LINK SECURITY FENCE TO MATCH
EXISTING FENCE (8 FT HEIGHT WITHOUT THE TOP
BARBED-WIRE HEIGHT) - SEE DETAIL (D3), SHEET (CS301).
2. MECHANICAL EQUIPMENT INSIDE THIS AREA - REFER TO
MECHANICAL DRAWINGS , SHEET (M-402)
3. EXISTING CHAIN-LINK FENCE.
4. EXISTING GATE.
5. EXISTING SIDEWALK.
6. PROVIDE CONCRETE PAD FLUSH TO GRADE - SEE
STRUCTURAL DRAWINGS FOR MORE DETAILS.
7. AFTER TEMPORARY CHILLER HAS BEEN DE-MOBILIZED, EXTEND
CONCRETE PAD FOR TEMPORARY CHILLER LAYDOWN AREA. PAD MUST
FLUSH TO GRADE - SEE STRUCTURAL PLANS SHEET (S-101)
FOR MORE DETAILS.
8. 2' x 2' LOCKABLE ACCESS DOOR - SEE DETAIL (D2), SHEET
(CS301).
9. TEMPORARY CONSTRUCTION FENCE - SEE DETAIL (D1),
SHEET (CD201)
# SHEET KEYNOTES
CI
VI
L S
IT
E
PL
AN
43.78'
.4
8'
16.77'
2'
61.51' 6.14'
57.71'
40.31'
30.32'
6.
RAYMOND1035 GREEN ST.
SUITE A
CONYERS, GA
30012
47'
44.04'
LEGEND:
PROPOSED FENCEX
PROPOSED CONCRETE PAD
TEMPORARY CONSTRUCTION FENCE
CONCRETE PAD
D2 2'x2' FENCE LOCKABLE ACCESS DOOR DETAIL
NTS
CS301
12939347
GENERAL SHEET NOTES
1. THIS SHEET IS PART OF A MULTI-SHEET SET OF CONSTRUCTION
PLANS AND MUST BE READ WITH THE FULL SET TO BEST ENSURE
PROPER INTERPRETATION.
2. ANY WORK/CUTOVERS/INTERRUPTIONS ON EXISTING UTILITIES
MUST BE SCHEDULED THROUGH THE BASE AT LEAST 14 DAYS IN
ADVANCE.
3. BACKGROUND INFORMATION HAS BEEN PROVIDED BY SUMMER
CONSULTANTS. NO SURVEY HAS BEEN PERFORMED.
CONTRACTOR MUST VERIFY ALL EXISTING CONDITIONS PRIOR
TO DEMOLITION AND CONSTRUCTION.
4. CONTRACTOR MUST PROVIDED FOR POSITIVE DRAINAGE AWAY
FROM THE MECHANICAL EQUIPMENT PAD AND PREVENT ANY
STANDING WATER.
5. CONCRETE MECHANICAL EQUIPMENT PAD MUST HAVE A 1.04%
AWAY FROM THE BUILDING.
6. CONCRETE PAD MUST HAVE BETWEEN 5-6% AIR ENTRAINMENT.
7. CONCRETE PADS MUST HAVE BROOM FINISH.
8.71'
1.04% slope
1.04% slope
GENERAL STRUCTURAL NOTES:
1. THE CONTRACTOR MUST REVIEW ALL SUBMITTALS BEFORE THEY ARE PROVIDED TO THE
CONTRACTING OFFICER. THE CONTRACTOR’S REVIEW MUST BE DOCUMENTED WITHIN THE
SUBMITTAL. THE CONTRACTING OFFICER RESERVE THE RIGHT TO REJECT SUBMITTALS THAT HAVE
NOT BEEN FIRST REVIEWED BY THE CONTRACTOR. THE ACCURACY AND COMPLETENESS OF THE
SUBMITTALS IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR, INCLUDING ALL ERRORS AND OMISSIONS. IN ADDITION, THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL MEANS, METHODS, AND SEQUENCING OF CONSTRUCTION.
2. THE CONTRACTOR MUST BE EXPERIENCED AND QUALIFIED TO PERFORM THE TYPE OF
CONSTRUCTION REQUIRED TO COMPLETE THE WORK PRESCRIBED BY THE CONTRACT
DOCUMENTS. THE CONTRACT DOCUMENTS WERE PREPARED AS A COMPLETE SET OF PROJECT
DRAWINGS AND SPECIFICATIONS. IT IS THE CONTRACTOR’S RESPONSIBILITY TO COORDINATE ALL INFORMATION PROVIDED IN THE ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR MUST NOTIFY THE CONTRACTING OFFICER IMMEDIATELY OF
ANY CONFLICTS, OMISSIONS, OR DISCREPANCIES. THIS COORDINATION MUST BE PERFORMED
BEFORE THE PROCUREMENT OF MATERIALS AND/OR FABRICATION OF ANY PROJECT
COMPONENTS.
3. WHERE SECTION IS SHOWN AND DETAILED, OTHER SECTIONS OF SIMILAR CONDITION MUST BE
DETAILED THE SAME OR OPPOSITE HAND, WHETHER SPECIFICALLY NOTED OR NOT.
4. CONTRACTOR MUST VERIFY EXISTING DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE
BEGINNING CONSTRUCTION. NOTIFY ENGINEER OF RECORD OF ANY DISCREPANCIES.
5. COORDINATE SIZES AND LOCATIONS OF ALL FLOOR AND ROOF PENETRATIONS WITH PLUMBING, MECHANICAL, AND ARCHITECTURAL REQUIREMENTS.
6. CONTRACTING OFFICER'S APPROVAL MUST BE SECURED FOR ALL SUBSTITUTIONS. SUCH
APPROVAL MAY ALSO BE WITHHELD AT THE SOLE DISCRETION OF THE CONTRACTING OFFICER.
7. THE STRUCTURES HAVE BEEN DESIGNED IN ACCORDANCE WITH THE PROVISIONS OF THE
FOLLOWING:
a. INTERNATIONAL BUILDING CODE, 2021 EDITION (IBC 2021).
b. AMERICAN SOCIETY OF CIVIL ENGINEERS, "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES," 2022 EDITION (ASCE 7-22).
c. UNIFIED FACILITIES CRITERIA (UFC) 3-301-01, "STRUCTURAL ENGINEERING," DATED 3 JUNE 2025
8. THE CONTRACTOR MUST PROVIDE TEMPORARY SHORING AND BRACING REQUIRED TO ERECT AND
HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL PERMANENT SUPPORTS AND LATERAL
BRACING ARE IN PLACE.
9. DO NOT SCALE DRAWINGS, USE DIMENSIONS.
10. DESIGN LOADS USED IN THE DESIGN OF THE STRUCTURAL SYSTEMS IN THIS PROJECT ARE AS
FOLLOWS:
a. RISK CATEGORY II
b. LIVE LOAD:
PIPE RACK LOAD 100 psf
c. ROOF SNOW LOAD:
GROUND SNOW LOAD, pg 31 psf SNOW EXPOSURE FACTOR, Ce 0.9 IMPORTANCE FACTOR, Is 1.0 THERMAL FACTOR, Ct 1.0 FLAT ROOF SNOW LOAD, pf 26 psf
d. WIND DESIGN CRITERIA:
EXPOSURE CATEGORY B
BASIC WIND SPEED, V 137 mph (FACTORED, ULTIMATE LOAD)
e. SEISMIC DESIGN CRITERIA:
SPECTRAL RESPONSE ACCELERATION:
Ss (SHORT PERIOD (0.2 SECOND)) 0.14 g S1 (LONG PERIOD (1.0 SECOND)) 0.052 g SDS (SHORT PERIOD (0.2 SECOND)) 0.12 g SD1 (LONG PERIOD (1.0 SECOND)) 0.074 g
SITE CLASS CLASS D
SEISMIC DESIGN CATEGORY B
LATERAL FORCE RESISTING SYSTEM STEEL SYSTEM NOT SPECIFICALLY DEISGNED
FOR SEISMIC RESISTANCE
IMPORTANCE FACTOR, Ie 1.0
RESPONSE MODIFICATION COEFFICIENT, R 3.0
SEISMIC RESPONSE COEFFICIENT, Cs 0.025
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
SEISMIC BASE SHEAR, V 130 LBS
11. ALL VERTICAL ELEVATIONS ARE BASED ON THE CONTROL ELEVATION FROM SURVEY BY OTHERS.
FOUNDATION
1. FOUNDATIONS FOR THIS STRUCTURE HAVE BEEN DESIGNED IN ACCORDANCE WITH PRESUMPTIVE
LOAD BEARING VALUES PER THE INTERNATIONAL BUILDING CODE(IBC) TABLE 1806.2.
2. FOUNDATIONS AND EARTH RETAINING STRUCTURES HAVE BEEN DESIGNED FOR A MAXIMUM
ALLOWABLE SOIL BEARING PRESSURE OF 1500 PSF.
3. PRIOR TO PLACING FOUNDATION CONCRETE, AND AFTER COMPACTION OF SUBGRADE, ALL
FOUNDATION EXCAVATIONS MUST BE INSPECTED AND TESTED BY A QUALIFIED GEOTECHNICAL
TECHNICIAN. TESTING MUST INCLUDE IN PLACE DENSITY TESTING, WHICH WILL REQUIRE
ESTABLISHING THE OPTIMUM MOISTURE CONTENT OF THE SUBGRADE. IF THE SUBGRADE HAS
LESS THAN THE STATED ALLOWABLE BEARING CAPACITY (NOTE 2 ABOVE) THE WEAK SUBGRADE
MUST BE REMOVED, RECOMPACTED & RETESTED UNTIL IT IS SATISFACTORY AT NO ADDITIONAL
COST TO THE OWNER. CONCRETE PLACEMENT MUST NOT PROCEED UNTIL THE SUBGRADE HAS
BEEN COMPACTED TO A MINIMUM OF 98% MAX DRY DENSITY.
4. NO UNBALANCED BACKFILLING MUST BE DONE AGAINST CONCRETE OR MASONRY WALLS UNLESS
WALLS ARE SECURELY BRACED AGAINST OVERTURNING, EITHER BY TEMPORARY CONSTRUCTION
BRACING OR BY PERMANENT CONSTRUCTION.
ADHESIVE ANCHORS
1. ADHESIVE ANCHORS INTO CONCRETE OR SOLID GROUTED CMU MUST BE THREADED ANCHORS
DRILLED AND GROUTED USING EPOXY OR ACRYLIC ADHESIVES BASED ON THE DIAMETER AND
EMBEDMENT DEPTH SHOWN ON THE DESIGN DRAWINGS. ANY CONTRACTOR REQUEST FOR
ALTERNATES MUST BE PRE-APPROVED IN WRITING BY THE CONTRACTING OFFICER.
2. ADHESIVE ANCHORS INTO HOLLOW CMU MUST BE THREADED ANCHORS DRILLED AND GROUTED
USING EPOXY OR ACRYLIC. ADHESIVES BASED ON THE DIAMETER AND EMBEDMENT DEPTH SHWON
ON THE DESIGN DRAWINGS. ANCHORS MUST USE A PLASTIC OR METALIC MESH SCREEN IN THE
CMU VOIDS. ANY CONTRACTOR REQUEST FOR ALTERNATES MUST BE PRE-APPROVED IN WRITING
BY THE CONTRACTING OFFICER.
3. ANCHORS MUST HAVE A MINIMUM Fy = 36 ksi.
4. ANCHOR INSTALLATION MUST BE IN STRICT CONFORMANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
STRUCTURAL STEEL
1. STRUCTURAL STEEL FOR THIS PROJECT HAS BEEN DESIGNED IN ACCORDANCE WITH THE
FIFTEENTH EDITION OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) "STEEL
CONSTRUCTION MANUAL", USING LOAD AND RESISTANCE FACTOR DESIGN(LRFD).
2. STRUCTURAL STEEL MUST COMPLY WITH THE FOLLOWING SPECIFICATIONS:
a. STRUCTURAL STEEL WIDE FLANGE SHAPES - ASTM A992, Fy = 50 ksi
b. OTHER STRUCTURAL STEEL SHAPES, PLATES, AND BARS - ASTM A36, Fy = 36 ksi
c. COLD-FORMED STRUCTURAL STEEL TUBING - ASTM A500, GRADE B, Fy = 42 ksi
d. STEEL PIPE - ASTM A53, GRADE B, TYPE E OR S, Fy = 35 ksi
e. ANCHOR RODS - ASTM F1554, Fy = 36 ksi
3. WELDING MUST BE IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY(AWS) D.1,
"STRUCTURAL WELDING CODE - STEEL", LATEST EDITION. WELD ELECTRODES MUST BE E70XX.
PROVIDE 3/16" CONTINUOUS FILLET WELDS UNLESS NOTED OTHERWISE.
4. EXPOSED EXTERIOR METAL INCLUDING ALL EXTERIOR METAL FABRICATIONS MUST BE HOT DIPPED
GALVANIZED.
5. UNLESS NOTED OTHERWISE, ALL BEAM SHEAR CONNECTIONS MUST BE MADE USING 3/4"∅ A325 BOLTS, BEARING TYPE WITH THREADS EXCLUDED. ALL GRAVITY ONLY BEAMS MUST HAVE SIMPLE SHEAR CONNECTIONS DESIGNED TO SUPPORT 1/2 THE TOTAL FACTORED UNIFORM LOAD FOR THE
SUPPORTED BEAM, ITS SPAN, AND ITS GRADE OF STEEL AS SPECIFIED IN AISC LRFD.
I N C O R P O R A T E D
SUMMER
CONSULTANTS
SUMMER
CONSULTANTS
N
KEY PLAN
N.T.S.
M C
A S
C H
E R
R Y
P O
IN
T
N
C C
H E
R R
Y P
O
IN
T N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C A
S C
H E
R R
Y P
O
IN
T
C H
E R
R Y
P O
IN
T
N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
B U
IL
D
IN
G
R
E P
LA
C
E C
H
IL
LE
R
S
C O
O
LI
N G
T O
W E
R
AS NOTED
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
ACTIVITY
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
CHK
SATISFACTORY TO DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
4 5
NEVER INCLUDE
SEAL
A/E INFO
F ile
P a th
X
F
Y \1
\0
.C
A D
B
IM
\0 .0
.B
IM
P lo t D a te
/2
/2
:3
:4
P
M
S-001
RMM RMM JJS
S T
R U
C T
U R
A L N
O T
E S
12939348
CAST-IN-PLACE CONCRETE
1. CAST-IN-PLACE CONCRETE FOR THIS PROJECT MUST COMPLY WITH THE AMERICAN CONCRETE INSTITUTE (ACI) "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND COMMENTARY"
ACI 318-19 AND ACI 318R-19.
2. REFERENCE PROJECT SPECIFICATION SECTION 03 30 00 "CAST-IN-PLACE CONCRETE".
3. CONCRETE MUST HAVE THE FOLLOWING PROPERTIES:
AREA WEIGHT STRENGTH @ AIR MAX. W/C NOMINAL MAX.
28 DAYS CONTENT RATIO AGG. SIZE
FOUNDATIONS 145 pcf 3000 psi 5% 0.55 1" PAVING 145 pcf 3000 psi 5% N/A 3/4"
THE EXPOSURE CLASSES FOR THE CONCRETE AREAS ARE AS FOLLOWS:
AREA FREEZING & SULFATES CONTACT W/ CORROSION
THAWING (F) (S) WATER (W) PROTECTION (C)
FOUNDATIONS F1 S0 W1 C0
(SEE SPECIFICATION SECTION 03 30 00 FOR ADDITIONAL REQUIREMENTS)
4. AN INTENTIONALLY ROUGHENED SURFACE MAY BE USED INSTEAD OF A CONTINUOUS SHEAR KEY AT
ALL HORIZONTAL CONSTRUCTION JOINTS.
5. ALL EXPOSED CONCRETE EDGES MUST HAVE 3/4" CHAMFER, WHETHER SPECIFICALLY NOTED OR NOT.
6. TYPICAL SLAB FINISH MUST BE BROOM FINISH FOR EXTERIOR SLABS AND STEEL TROWEL FINISH FOR
INTERIOR SLABS.
7. ALL ANCHOR RODS MUST BE BLACK AS NOTED ON DESIGN DRAWINGS.
8. CONCRETE FORM WORK MUST COMPLY WITH ACI 347, LATEST EDITION. CONTRACTOR MUST BE
RESPONSIBLE FOR THE DESIGN OF ALL FORMWORK.
9. DURING AND IMMEDIATELY AFTER PLACING, CONCRETE MUST BE THOROUGHLY COMPACTED BY
SPADING OR MECHANICAL VIBRATING TO PROVIDE DENSE CONCRETE FREE OF HONEY COMBING.
10. DIRECTLY AFTER FORMS HAVE BEEN REMOVED, ALL EXPOSED TIE WIRES AND STAPLED ENDS MUST
BE REMOVED FROM CONCRETE SURFACES TO BE EXPOSED. CUT TIES FLUSH WITH FINISHED
SURFACES FOR ALL OTHER CONCRETE. RUB SMOOTH OR CUT OFF FINS AND ROUGH PLACES. REMOVE ALL LOOSE CONCRETE AND OTHER IRREGULARITIES. PATCH AND FILL VOIDS WITH BONDING AGENT AS
REQUIRED.
CONCRETE REINFORCEMENT:
1. REINFORCING STEEL MUST CONFORM TO ASTM A615 SUPPLEMENT SI, GRADE 60, OF DOMESTIC
MANUFACTURER.
2. WELDED WIRE REINFORCEMENT MUST CONFORM TO ASTM A185. WELDED WIRE REINFORCEMENT MUST
BE SUPPLIED IN FLAT SHEETS ONLY. LAP 9" MINIMUM.
3. REINFORCEMENT MUST BE FABRICATED TO SHAPES AND DIMENSIONS SHOWN AND MUST CONFORM TO THE REQUIREMENTS OF CONCRETE REINFORCING STEEL INSTITUTE(CRSI) AND ACI 318. REINFORCEMENT MUST BE COLD BENT UNLESS OTHERWISE AUTHORIZED. BENDING MAY BE ACCOMPLISHED IN THE FIELD
OR AT THE MILL. BARS MUST NOT BE BENT AFTER EMBEDDED IN CONCRETE.
4. REINFORCEMENT MUST BE FREE FROM LOOSE RUST AND SCALE, DIRT, OIL, OR OTHER DELETERIOUS
COATING THAT COULD REDUCE BOND WITH THE CONCRETE.
5. NO SPLICES OF REINFORCEMENT MUST BE PERMITTED EXCEPT AS DETAILED OR AUTHORIZED. MAKE BARS CONTINUOUS AROUND CORNERS WITH CORNER BARS. WHERE PERMITTED, SPLICES MADE BY
CONTACT LAPS MUST BE CLASS "B" TENSION LAPS.
6. TENSION AND COMPRESSION REINFORCEMENT SPLICES IN CONCRETE MUST BE MADE AS FOLLOWS:
3000 PSI CONC 3500 PSI CONC 4000 PSI CONC 4500 PSI CONC
#4 BARS - 37" #4 BARS - 35" #4 BARS - 33" #4 BARS - 31"
#5 BARS - 46" #5 BARS - 43" #5 BARS - 41" #5 BARS - 38"
#6 BARS - 56" #6 BARS - 52" #6 BARS - 49" #6 BARS - 46"
#7 BARS - 81" #7 BARS - 75" #7 BARS - 71" #7 BARS - 67"
7. WHERE HOOKS ARE SHOWN, PROVIDE STANDARD 90° HOOKS IN ACCORDANCE WITH CRSI AND ACI 318, UNLESS NOTED OTHERWISE.
8. WHERE REQUIRED, PROVIDE DOWELS TO MATCH SIZE AND SPACING OF VERTICAL REINFORCING FROM
FOUNDATION. DOWELS MUST HAVE STANDARD 90° HOOKS.
CAST-IN-PLACE
9. MINIMUM CONCRETE REINFORCING COVER REQUIREMENTS: CONCRETE COVER
a. CONCRETE CAST AGAINST EARTH: 3"
b. FORMED CONCRETE EXPOSED TO EARTH OR WEATHER:
WALLS, SLABS:
#6 BAR AND LARGER 2"
#5 BAR AND SMALLER 1½"
c. FORMED CONCRETE NOT EXPOSED TO WEATHER OR IN
CONTACT WITH GROUND:
WALLS, SLABS:
#11 BAR AND SMALLER ¾"
10. ALL REINFORCING STEEL AND EMBEDDED ITEMS SUCH AS ANCHOR RODS AND WELD PLATES MUST BE
PLACED TO PREVENT DISPLACEMENT BEYOND PERMITTED TOLERANCES.
11. DETAIL BARS IN ACCORDANCE WITH "ACI DETAILING MANUAL-2004", PUBLICATION SP-66, ACI 318, AND
ACI 315, OR LATEST EDITIONS.
12. PROVIDE ACCESSORIES NECESSARY TO PROPERLY SUPPORT REINFORCING AT POSITIONS SHOWN ON
PLANS
ABBREVIATION KEY
AT
ARCHITECTURAL
BUILDING
BEAM
BOTTOM
CENTERLINE
CAST-IN-PLACE
CONTROL JOINT
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS
DEAD LOAD
DRAWING
DOWEL
EACH END
EACH FACE
ENGINEER OF RECORD
EDGE OF SLAB
EACH SIDE
EACH WAY
EXPANSION
FLOOR DRAIN
FOUNDATION
FLOOR PENETRATION
FINISH FLOOR
FAR SIDE
FOOTING
HOOK
HORIZONTAL
HEADED STUD
HEIGHT
HEAVY
INCH
INTERIOR
1,000 POUNDS PER SQUARE INCH
EXTERIOR
FEET
DIAMETER
ELEVATION
CLEAR
POUNDS
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
MAXIMUM
MANUFACTURER
MINIMUM
MILES PER HOUR
NOT APPLICABLE
NOT IN CONTRACT
NEAR SIDE
OUT TO OUT
ON CENTER
OPENING
OPPOSITE
PLATE
PROJECTION
POST-TENSION BEAM
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
REINFORCED CONCRETE BEAM
REQUIRED
SELF-DRILLING, SELF-TAPPING
SHEET METAL SCREWS
SQUARE FOOT
SIMILAR
STANDARD
STEEL
SELF-WEIGHT
TOP AND BOTTOM
TOP OF
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
WITH
WATER TO CEMENT
WIDE FLANGE
WIND LOAD
WORKING POINT
WEIGHT
WELDED WIRE REINFORCEMENT
SQUARE
THREADED
PRE-MOLDED JOINT FILLER
REINFORCEMENT
NOT TO SCALE
ARCH
BLDG
BM
BTM.
C.L.
CIP
CJ
CLR.
CMU
COL.
CONC.
CONST.
CONT.
DIA.
D.L.
DWG.
DWL.
E.E.
E.F.
ELEV.
E.O.R.
E.O.S.
E.S.
E.W.
EXP.
EXT.
FD
FDN.
F.P.
F.F.
F.S.
FT.
FTG
HK.
HOR.
H.S.
HT.
HVY.
IN.
INT.
ksi lb
L.L.
LLH
LLV
MAX.
MFR.
MIN.
mph
N/A
N.I.C.
N.S.
N.T.S.
O/O
O.C.
OPN'G
OPP.
PL.
PJF
PROJ.
PTB
psf psi
RCB
REINF.
REQ'D
SDSTSMS
S.F.
SIM.
SQ.
STD.
STL.
S.W.
T&B
T/
THRD'D
TYP.
U.N.O.
VERT.
w/
W/C
WF
W.L.
W.P.
WT.
WWR
KIPSK
EQUALEQ.
EXISTINGEXIST.
BOTTOM OFB/
DEGREEDEG.
ELECTRICALELEC.
HOLLOW STRUCTURAL SECTIONHSS
MECHANICALMECH.
PRE-ENGINEERED METAL
BUILDING SYSTEM
PEMB
TOP OF STEELTOS
I N C O R P O R A T E D
SUMMER
CONSULTANTS
SUMMER
CONSULTANTS
N
KEY PLAN
N.T.S.
M C
A S
C H
E R
R Y
P O
IN
T
N
C C
H E
R R
Y P
O
IN
T N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C A
S C
H E
R R
Y P
O
IN
T
C H
E R
R Y
P O
IN
T
N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
B U
IL
D
IN
G
R
E P
LA
C
E C
H
IL
LE
R
S
C O
O
LI
N G
T O
W E
R
AS NOTED
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
ACTIVITY
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
CHK
SATISFACTORY TO DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
4 5
NEVER INCLUDE
SEAL
A/E INFO
F ile
P a th
X
F
Y \1
\0
.C
A D
B
IM
\0 .0
.B
IM
P lo t D a te
/2
/2
:3
:4
P
M
S-002
RMM RMM JJS
S T
R U
C T
U R
A L N
O T
E S
12939349
D
D.4
3.5 4 4.5 5
S E
E A
R C
H S
E E
A R
C H
S E
E A
R C
H
VERIFY IN FIELD
EXISTING OPENING TO REMAIN EXISTING
EXTERIOR WALL,
TYP
EXISTING COLUMN,
TYP
EXISTING CHAIN
LINK FENCE, TYP
VERIFY IN FIELD
EXISTING MECHANICAL
EQUIPMENT, TYP.
VERIFY IN FIELD
VERIFY IN FIELD
18'-6"
VERIFY IN FIELD
18'-6"
VERIFY IN FIELD
18'-6"
VERIFY IN FIELD
18'-6"
EXISTING EQUIPMENT PADS
MUST BE DEMOLISHED.
CONTRACTOR MUST CHIP OUT
EXISTING PAD AND REPAIR THE
FLOOR WITH A SELF-LEVELING
CONCRETE TOPPING MATERIAL.
EXISTING EXTERIOR CONCRETE EQUIPMENT
PAD AND STRUCTURAL STEEL PLATFORM. DEMO
AND REMOVE ALL. DEMO EXTERIOR SLAB IN
AFFECTED AREA
SEE MECHANICAL
S E
E M
E C
H A
N
IC
A L
VERIFY IN FIELD
EXISTING CMU ENCLOSURE WALL MUST BE
DEMOLISHED AND REMOVED. EXISTING SPREAD
FOOTINGS MUST BE DEMOLISHED AND REMOVED
TO INSTALL NEW FOUNDATIONS, TYP
EXISTING CMU PILASTER MUST BE DEMOLISHED
AND REMOVED. EXISTING SPREAD FOOTINGS
MUST BE DEMOLISHED AND REMOVED TO
INSTALL NEW FOUNDATIONS, TYP
V E
R
IF
Y I N
F
IE
L D
EXISTING
EXTERIOR SLAB
VERIFY W/ MECHANICAL AND ARCH
NEW OPENING
MECHANICAL PIPES, VERIFY W/ MECHANICAL
DEMO EXISTING WALL TO
INSTALL NEW LINTEL. SEE
PLAN FOR LINTEL SIZE
EXISTING CMU WALL,
VERIFY IN FIELD
CONTRACTOR TO SHORE EXISTING WALL AND
ANY STRUCTURE BEARING ON EXISTING WALL
PRIOR TO DEMO OF WALL AND REINSTALL OF
NEW LINTEL
NOTES:
1. SEE FOR LOCATION. VERIFY & COORDINATE WITH MECHANICAL/A1 S-102
CMU ABOVE OPENING MUST NOT BE
DEMOED
I N C O R P O R A T E D
SUMMER
CONSULTANTS
SUMMER
CONSULTANTS
N
KEY PLAN
N.T.S.
M C
A S
C H
E R
R Y
P O
IN
T
N
C C
H E
R R
Y P
O
IN
T N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C A
S C
H E
R R
Y P
O
IN
T
C H
E R
R Y
P O
IN
T
N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
B U
IL
D
IN
G
R
E P
LA
C
E C
H
IL
LE
R
S
C O
O
LI
N G
T O
W E
R
AS NOTED
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
ACTIVITY
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
CHK
SATISFACTORY TO DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
4 5
NEVER INCLUDE
SEAL
A/E INFO
F ile
P a th
X
F
Y \1
\0
.C
A D
B
IM
\0 .0
.B
IM
P lo t D a te
/2
/2
:3
:4
P
M
S-100
RMM RMM JJS
F O
U N
D A
T
IO
N D
E M
O P
L A
N
1/8" = 1'-0"A1
FOUNDATION DEMO PLAN
3/4" = 1'-0"C3
NEW LINTEL IN EXISTING WALL DETAIL
12939350
FOUNDATION PLAN NOTES:
1. SEE S-001 FOR STRUCTURAL GENERAL NOTES
2. F# DENOTES SPREAD FOOTING TYPE. SEE SCHEDULE FOR SIZE AND REINFORCING.
D
D.4
3.5 4 4.5
S E
E A
R C
H S
E E
A R
C H
S E
E A
R C
H
VERIFY IN FIELD
EXISTING OPENING TO REMAIN
C1
S-101
TYP
VERIFY SIZE W/ MECH
39'-2" MIN
V E
R
IF
Y S
IZ
E
W M
E C
H
M
IN
VERIFY SIZE W/ MECH
39'-2" MIN
V E
R
IF
Y S
IZ
E
W M
E C
H
M
IN
EXISTING
EXTERIOR WALL,
TYP
EXISTING COLUMN,
TYP
5'-9"
NEW INTERIOR EQUIPMENT
PAD. VERIFY LOCATION & SIZE
REQUIREMENTS W/
MECHANICAL
C1
S-101
TYP
C2
S-101
V E
R
IF
Y W
M
E C
H A
N
IC
A L
V E
R
IF
Y W
M
E C
H A
N
IC
A L
NEW EXTERIOR EQUIPMENT
PADS. (2) LOCATIONS TYP
MECHANICAL UNIT. VERIFY W/
MECHANICAL, TYPEXISTING
CHAIN LINK
FENCE, VERIFY
IN FIELD
NEW CHAIN
LINK FENCE,
SEE CIVIL
TYP
C2
S-101
TYP
2'-5"
EXISTING MECHANICAL
EQUIPMENT, TYP.
VERIFY IN FIELD
VERIFY IN FIELD
18'-6"
VERIFY IN FIELD
18'-6"
VERIFY IN FIELD
18'-6"
VERIFY IN FIELD
18'-6"
F3.11 x 2.0
A3
S-101
TYP
HSS4X4X5/16 COLUMN
HATCHED PORTION OUTSIDE THE FENCE LINE
MUST BE 1'-4" THICK TO SUPPORT TEMPORARY
EXTERIOR MECHANICAL UNIT. SIMILAR TO
AND SEE MECHANICAL
DENOTES PAD
EXTENSION FOR PIPE
SUPPORT. SEE /B4 S-102
NEW 4" EXTERIOR PAVING PER
VERIFY EXTENTS OF EXISTING EXTERIOR SLAB IN THE FIELD
& PROVIDE CONSTRUCTION JOINTS PER
WHERE NEW SLAB MEETS EXISTING SLAB.
PROVIDE MAX CONTROL JOINT SPACING OF 8'-0" x 8'-0"
PER
/B1 S-101
/D4 S-101
/C4 S-101
TYP EA SIDE
1'-6" MIN,
9"
E Q
E
Q
TYP
9"
F3.11 x 2.0 F4.5x2.0
F4.5x2.0
F5.5x2.25
TYP
1'-6"
T Y
P
F5.5x2.25
F2.5
2'-5"
TYP
2'-5" 11'-2"
/2
/2
13'-6" 15'-6"
, TYP
T Y
P
0' - 0"
T/PAD=
0' - 4"
T/PAD =
0' - 4"
T/PAD =
EXISTING SIDEWALK,
VERIFY IN FIELD
/C2 S-101
PROVIDE BLOOMED
SURFACE AND 1/8" / FT
SLOPE, TYP
EXISTING CONCRETE SLAB
6" CONCRETE PAD
ADHESIVE ANCHOR WITH 3" EMBED -
COORDINATE, SIZE, QUANTITY, &
LOCATIONS WITH MANUFACTURER'S
REQUIREMENTS
#3 DOWEL @ 12" O.C. w/ 3"
EMBED. DRILL & GROUT
USING EPOXY ADHESIVE
#3 @ 12" O.C. MAX
3/4" CHAMFER @ EXPOSED
CORNERS, TYP
ROUGHEN & CLEAN CONC.
2" CLR, TYP
VERIFY W/ MECHANICAL
EXISTING COMPACTED SUBGRADE
6" MIN. ALL AROUND
MECHANICAL UNIT - SEE
MECHANICAL DWGS FOR SIZE,
TYPE AND LOCATION
ROUGHEN
& CLEAN
CONCRETE
#5 @ 10" O.C. MAX,
EA WAY
T/GRADE =
VERIFY IN FIELD
MECHANICAL UNIT - SEE
MECHANICAL DWGS FOR
SIZE, TYPE AND LOCATION
NEW CONCRETE PAD
ADHESIVE ANCHOR WITH
4" EMBED - COORDINATE,
SIZE, QUANTITY, &
LOCATIONS WITH
MANUFACTURER'S
REQUIREMENTS
3" CLR3" CLR
C L R
6" MIN. ALL AROUND
VERIFY W/ MECHANICAL
EXISTING COMPACTED
SUBGRADE
3/4" CHAMFER ALL AROUND
CUT AND DEMO EXISTING
EXTERIOR CONCRETE SLAB
AS REQUIRED TO INSTALL
NEW EQUIPMENT PAD, TYP
1/2" PRE-MOLDED JOINT
FILLER W/ SEALANT, TYP
DIAMETER
/1
E M
B E
D M
E N
T
A N
C H
O R
R O
D
/2
P
R O
J
T H
R 'D
HEAVY HEX NUT &
WASHER
T/CONC. EL.
ASTM F1554, GR. 36
THREADED ROD
HEAVY HEX NUT
TACK WELD 2
PLACES
PER PLAN
ANCHOR
ROD DIAM.
SQUARE WASHER SCHEDULE
SIZE (INCH)
BASEPLATE
HOLE SIZE
THICKNESS
23/4" Ø
1" Ø 3
1 1/4" Ø
1 1/2" Ø
1 3/4" Ø
2" Ø
3 1/2
7/8" Ø
1 1/8" Ø
1 3/8" Ø
1 5/8" Ø
1 7/8" Ø
2 1/8" Ø
1/4"
3/8"
1/2"
1/2"
5/8"
3/4"
1 1/2" NONSHRINK,
NON METALLIC
GROUT
0'-10" SQ x 3/4" THICK
BASEPLATE W/ (4) 3/4" Ø
ANCHOR BOLTS W/ 9" EMBED
COLUMN, PER PLAN
E M
B E
D
P E
R S
C H
E D
U L E
T H
IC
K
N E
S S
PER SCHEDULE, TYP
WIDTH
3" , TYP
C O
V E
R
FOOTING PER PLAN
SEE SCHEDULE FOR REINF.
DETAILS. PROVIDE STD HOOKED
BARS TOP & BOT, TYP
SECTION A-A
A A
CL
CL
/2
T
Y P
E Q
E
Q
EQ. EQ.
10"
T/FTG =
EXISTING GRADE=
VERIFY IN FIELD
M
IN
6'' TRIMABLE COMPACTABLE GRANULAR
FILL (CRUSHER RUN OR EQUAL)
EACH SIDE OF JOINT WITH 1/8" RADIUS
NOTES:
1. CONTROL JOINTS MAY REPLACE CONSTRUCTION JOINTS SEE
2. WHERE THE CONSTRUCTION JOINT OCCURS BETWEEN THE NEW EXTERIOR SLAB AND EXISTING
EXTERIOR SLAB, PROVIDE 1/2" PREMOLDED JOINT FILLER W/ SEALANT, TYP
COMPACTED
SUBGRADE
/C4 S-101 S
E E
P L A
N
V A
R
IE
S
6'' TRIMABLE
COMPACTABLE GRANULAR
FILL (CRUSHER RUN OR
EQUAL)
COMPACTED
SUBGRADE
6'' TRIMABLE COMPACTABLE GRANULAR
FILL (CRUSHER RUN OR EQUAL)
COMPACTED
SUBGRADE
1/8'' x (SLAB THICKNESS X 1/4'')
SAW CUT JOINT AND INSTALL
JOINT FILLER
S E
E P
L A
N S
V A
R
IE
S
NOTES:
1. SLAB MUST BE SAWN AS SOON AS THE CONCRETE WILL SAFELY SUPPORT MEN AND EQUIPMENT.
2. FILL JOINT WITH SEALANT AFTER SLAB HAS BEEN CURED.
3. CONSTRUCTION JOINT MAY REPLACE CONTROL JOINT SEE /D4 S-101
I N C O R P O R A T E D
SUMMER
CONSULTANTS
SUMMER
CONSULTANTS
N
KEY PLAN
N.T.S.
M C
A S
C H
E R
R Y
P O
IN
T
N
C C
H E
R R
Y P
O
IN
T N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C A
S C
H E
R R
Y P
O
IN
T
C H
E R
R Y
P O
IN
T
N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
B U
IL
D
IN
G
R
E P
LA
C
E C
H
IL
LE
R
S
C O
O
LI
N G
T O
W E
R
AS NOTED
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
ACTIVITY
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
CHK
SATISFACTORY TO DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
4 5
NEVER INCLUDE
SEAL
A/E INFO
F ile
P a th
X
F
Y \1
\0
.C
A D
B
IM
\0 .0
.B
IM
P lo t D a te
/2
/2
:3
:4
P
M
S-101
RMM RMM JJS
F O
U N
D A
T
IO
N P
L A
N
Spread Footing Schedule
Type Mark Thickness Length Width Reinforcement Details Notes
F2.5 2' - 0" 2' - 6" 2' - 6" (3) #6 EA DIRECTION T&B
F3.11 x 2.0 2' - 0" 2' - 0" 3' - 11" #6 @ 12" O.C. MAX EA WAY T&B
F4.5 x 2.0 2' - 0" 2' - 0" 4' - 5" #6 @ 12" O.C. MAX EA WAY T&B
F5.5x2.25 2' - 0" 2' - 3" 5' - 5" #6 @ 12" O.C. MAX EA WAY T&B
1/8" = 1'-0"A1
FOUNDATION PLAN
3/4" = 1'-0"C1
INTERIOR EQUIPMENT PAD DETAIL
3/4" = 1'-0"C2
EXTERIOR EQUIPMENT PAD DETAIL
3/4" = 1'-0"B4
ANCHOR BOLT DETAIL
3/4" = 1'-0"A3
TYPICAL COLUMN ON FOOTING DETAIL
3/4" = 1'-0"D4
TYPICAL CONSTRUCTION JOINT DETAIL
3/4" = 1'-0"B1
TYPICAL EXTERIOR PAVING DETAIL
3/4" = 1'-0"C4
TYPICAL CONTROL JOINT DETAIL
12939351
D.4
3.5 4 4.5
EXISTING
EXTERIOR WALL,
TYP
EXISTING COLUMN,
TYP
VERIFY IN FIELD
EXISTING OPENING TO REMAIN
MECHANICAL UNIT. VERIFY W/
MECHANICAL, TYP
MECHANICAL PIPES.
VERIFY W/ MECH,
TYP
2'-5"11'-2"
2'-5"
/2
E Q
E
Q
E Q
E Q
E
Q
E Q
5'-4" 5'-4"
7' - 8"T/STL =
TYP
C2
S-102
SIM
C1
S-102
________________________________________________ TYP
C1
S-102
SIM
M C
X
M C
X
W10X26, TYP
MC12X31
MC12X31
MC12X31
M C
X
CANTILEVER BEAM OVER
COLUMN OVER PER
DENOTES BRACE PER
TYP
/C2 S-102
DENOTES BRACE PER
TYP
/C1 S-102
C3
S-102
TYP
C3
S-102
TYP
NEW L-1
4'-5"
13'-6"
SEE MECHANICAL FOR PIPE
SUPPORT REQUIREMENTS,
LOCATIONS, AND SPACING, TYP
15'-6"
SEE
(4) PIPE SUPPORT LOCATIONS
/B4 S-102
MC12X31
MC12X31
EQ.
EQ. EQ.
T Y
P
EQ. EQ. EQ.
W X
1' - 7"T/STL =
@ LO BEAMS
1' - 7"T/STL =
1' - 7"T/STL =
TYP
TYP
C2
S-102
T Y
P
NEW L-1
NOTE: W10x26 INFILL BEAMS SHALL BE MOVED TO ACCOMODATE PIPE SUPPORTS. VERYIFY LOCATIONS WITH MECHANICAL. IF A BEAM IS MORE THAN 2'-0" AWAY FROM REQUIRED PIPE SUPPORT, A NEW W10x26 BEAM SHALL BE ADDED TO ACCOMODATE THAT REQUIRED PIPE SUPPORT.
T/STL
PER PLAN
3/16" CAP PLATE W/
1/8" FILLET WELD ALL
AROUND, TYP
BEAM BEYOND,
SEE PLAN
CL CL
SEE PLAN
WP, TYP
PROVIDE (2) 3/4" Ø
THRU BOLT, TYP
L3x3 x1
/4
COL, SEE
FOR SIZE
TYP
1/2" MAX,
T Y
P
/2
1/4
1/4
TYP
BEAM, PER PLAN
9" x 4" x 1/4" KNIFE
PLATE W/ (3) 3/4"
Ø A325 BOLTS
T Y P
1 1/2" T Y P
3"
/A1 S-101
T/STL
PER PLAN
1/4" CAP PLATE, TYP
BEAM BEYOND,
SEE PLAN
CL
WP, TYP
PROVIDE 3/4" Ø
THRU BOLT, TYP
L3x3x1/4
COL, SEE
FOR SIZE
1/4
1/4
TYP
BEAM, PER PLAN
9" x 4" x 1/4" KNIFE
PLATE W/ (3) 3/4"
Ø A325 BOLTS
4'-3"
1/4" GUSSET PLATE
W/ (2) 3/4" Ø A325
BOLT
1 1/2"
3"
/A1 S-101
CANTILEVER, PER PLAN
T/STL
PER PLAN
CL
BEAM, PER PLAN
COL, PER
1'-0" x 0'-4" x 5/8" THICK CAP PLATE 1/4
1/4
1/4
/A1 S-101
T/STL
PER PLAN
MAX
1/2"
/2
T Y
P
BEAM, PER PLAN
PROVIDE 9" x 4" x 1/4" KNIFE
PLATE W/ (3) 3/4" Ø A325 BOLTS @
MC12 CONNECTIONS
PROVIDE 6" x 4" x 1/4" KNIFE
PLATE W/ (2) 3/4" Ø A325 BOLTS @
C8 CONNECTIONS
2" 2"
STEEL LINTEL SCHEDULE
MARK
L-1
BEAM SIZE
(2) C8x11.5
NOTE:
1. LINTEL MUST EXTEND 12" EACH SIDE
2. SEE FOR DEMO
REQUIREMENTS
3. INSTALL BRICK FACADE AFTER NEW
LINTEL HAS COMPLETELY BEEN
INSTALLED
EXISTING CMU
5/8" CONT. PL LENGTH
OF LINTEL
4" BRICK FACADE,
MATCH EXISTING
MASONRY ANCHOR
@ 16" O.C.
INSULATION
1/2" MAX
STEEL LINTEL,
PER SCHD
THICKNESS
VERIFY IN FIELD
WALL ASSEMBLY
VERIFY IN FIELD
/C3 S-100
VERIFY W/ MECHANICAL AND ARCH
NEW OPENING
MECHANICAL PIPES, VERIFY W/ MECHANICAL
EXISTING CMU WALL,
VERIFY IN FIELD
SEE
FOR DEMO
REQUIREMENTS
/C3 S-100
NEW STEEL LINTEL
SEE PLAN AND SCHEDULE
EXTEND MINIMUM 12" PAST OPENING ON EACH SIDE
3/16 2-12
3/16 2-12
3/4" Ø THRU BOLTS @ 8" O.C.
MIN
1'-0"
MIN
1'-0"
NOTE: INSTALL
LINTEL PRIOR TO
REMOVING CMU
FRAMING PLAN NOTES:
1. SEE S-001 FOR STRUCTURAL GENERAL NOTES
2. L-# DENOTES LINTEL. SEE LINTEL SCHEDULE.
M A
N U
F A
C T
U R
E R
V E
R
IF
Y
W M
E C
H
VERIFY ANCHORAGE &
ATTACHMENT W/ MECH
MANUFACTURER
EQUIPMENT PAD
EXTENSION OR FOOTING.
@ PAD EXTENSION
PROVIDE TOP REINF. TO
MATCH BOT REINF. PER
ALSO PROVIDE
STANDARD HOOKED
BARS TOP & BOT
PIPE SUPPORT PER
MECHANICAL
PER PLAN PER PLAN
D E
P T
H O
F P
A D
/C2 S-101
A A
/2
T Y
P
TYP
7 1/2"
TYP
7 1/2"
1 1/2" BASEPLATE W/ (8)
3/4" Ø EPOXY ANCHORS
W/ MIN 8" EMBED
1'-6"
SECTION A-A
MAX
10" SQ.
DOWEL INTO EXIST
FOOTING AS REQ'D
I N C O R P O R A T E D
SUMMER
CONSULTANTS
SUMMER
CONSULTANTS
N
KEY PLAN
N.T.S.
M C
A S
C H
E R
R Y
P O
IN
T
N
C C
H E
R R
Y P
O
IN
T N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C A
S C
H E
R R
Y P
O
IN
T
C H
E R
R Y
P O
IN
T
N
C
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
B U
IL
D
IN
G
R
E P
LA
C
E C
H
IL
LE
R
S
C O
O
LI
N G
T O
W E
R
AS NOTED
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
ACTIVITY
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
CHK
SATISFACTORY TO DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
4 5
NEVER INCLUDE
SEAL
A/E INFO
F ile
P a th
X
F
Y \1
\0
.C
A D
B
IM
\0 .0
.B
IM
P lo t D a te
/2
/2
:3
:4
P
M
S-102
RMM RMM JJS
F R
A M
IN
G
P L
A N
1/8" = 1'-0"A1
PIPE SUPPORT FRAMING PLAN
3/4" = 1'-0"C1
BRACE DETAIL
3/4" = 1'-0"C2
BRACE DETAIL
3/4" = 1'-0"C3
BEAM OVER COLUMN DETAIL
3/4" = 1'-0"C4
TYPICAL BEAM TO BEAM DETAIL
3/4" = 1'-0"A3
TYPICAL STEEL LINTEL DETAIL
3/4" = 1'-0"B4
TYPICAL PIPE SUPPORT DETAIL
12939352
(E)
SYMBOLS GENERAL SYMBOLSABBREVIATIONS
SYMBOLS
PIPE TURN UP
PIPE TURN DOWN
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
DIRECTION OF FLOW
PIPE CAP
PIPE CLEANOUT
WALL PIPE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
C.O.
W.C.O.
F.C.O.
FL.D.
DOUBLE LINE PIPE TURN UP
DOUBLE LINE PIPE TURN DOWN
FORGED BRANCH PIPE FITTING
PROVIDE FULL LUG BUTTERFLY
ISOLATION VALVES
PROVIDE MOTORIZED, FULL LUG
BUTTERFLY ISOLATION VALVES
PIPE CAP
PROVIDE OS&Y
ISOLATION VALVES
GATE VALVE
GLOBE VALVE
SWING CHECK VALVE
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
STRAINER
UNION
PRESSURE REDUCING VALVE
SAFETY RELIEF VALVE
O.S.&Y VALVE
MOTORIZED O.S.&Y VALVE
FLOW MEASURING VALVE
COMBINATION FLOW MEASURING
AND BALANCING VALVE
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
MOTORIZED BUTTERFLY VALVE
BACKFLOW PREVENTER
MANUAL AIR VENT 3/8" BALL VALVEM.A.V.
THERMOMETER AND WELL
PRESSURE GAUGE
RETURN AIR SYMBOL
NUMBER INDICATES CFM
THERMOSTAT
NORTH ARROW
COLUMN BUBBLE
DESIGNATION
REVISION CLOUD WITH REVISION
NUMBER DESIGNATION
BREAKLINE
MATCHLINE DESIGNATIONM A T C H L I N E A-A
DEMOLITION LINETYPE
CENTERLINE
EXISTING
POINT OF CONNECTION TO EXISTING
POINT OF TERMINATION OF REMOVAL
NOTE NUMBER
EXHAUST DUCT UP
EXHAUST DUCT DOWN
T
M
M
M
A.D. ACCESS DOOR
A.F.F. ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CFM CUBIC FEET PER MINUTE
C.O. CLEANOUT
CW DOMESTIC COLD WATER
CWP CHILLED WATER PUMP
D.B. DRY BULB
db DECIBEL
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DN. DOWN
(E) EXISTING
EFF. EFFICIENCY
ELEV. ELEVATION/ELEVATOR
E.S.P. EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
°F DEGREES FAHRENHEIT
FLA FULL LOAD AMPS
FL.D. FLOOR DRAIN
FT. FEET
GAL. GALLON
GPM GALLONS PER MINUTE
HP HORSEPOWER
HWP HEATING WATER PUMP
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
Hz HERTZ
IN. INCHES
LBS. POUNDS
MER MECHANICAL EQUIPMENT ROOM
MIN. MINIMUM
M.O.D. MOTOR OPERATED DAMPER
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
N.I.C. NOT IN CONTRACT
N.O. NORMALLY OPEN
O.A. OUTSIDE AIR
O.C. ON CENTER
P.D. PRESSURE DROP
PH PHASE
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
RLA RUNNING LOAD AMPS
RPZ REDUCED PRESSURE ZONE
RTU ROOFTOP UNIT
TYP. TYPICAL
UH UNIT HEATER
V VOLTS
ARROW INDICATES
TRUE NORTH AND/OR
PROJECT NORTH
N
M101
N
8'0 1/8"=1'-0"
UNIQUE PLAN OR
DETAIL NUMBER
ON THIS DRAWING NORTH ARROW
NAME OF PLAN OR DETAIL
ALL DRAWINGS WHERE
DETAIL IS REFERENCED
GRAPHIC SCALE OF
PLAN OR DETAIL
SECTION IDENTIFICATION
INDICATES DIRECTION
OF CUTTING PLANE
NUMBER INDICATES SECTION
SHEET NUMBER WHERE
SECTION IS DRAWN
2-PART REFERENCE DETAIL IDENTIFICATION:
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
FLOOR PLAN
M101, M1022
FLOOR PLAN AND DETAIL TITLES:
M101
ROOM NUMBER DESIGNATION.1234
CWS
C CONDENSER WATER SUPPLY
CONDENSER WATER RETURNCR
DOMESTIC COLD WATERCW
CWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAIND
HWR HEATING WATER RETURN
HEATING WATER SUPPLYHWS
MAKE-UP WATERMU
PC PUMPED CONDENSATE
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :20
:40 P
M
1.0
1.0
M
-0
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M-001 12939353
SY
MB
OL
S
AB
BR
EV
IA
TI
ON
S
ZAC ZAC WAN
3 3.5 4 4.5
D.4
3 3.5 4 4.5
D
D.4
MECH
MECH
SEE MD402 FOR
CONTINUATION
TEMPORARY
8"CWS&R
TEMPORARY
8"CWS&R
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :20
:49 P
M
1.0
1.0
M
-0
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
KEY PLAN
N.T.S.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
N
M-002 12939354
SE
QU
EN
CI
NG
P
LA
N
ZAC ZAC WAN
N
8'0 4' 1/4"=1'-0"
PHASING PLAN - NEW WORK2
N
8'0 4' 1/4"=1'-0"
PHASING PLAN - DEMO1
SEQUENCING NOTES
NOTES
1. OVER A WEEKEND OUTAGE REMOVE 8"CWS&R COMPLETE TO
POINTS INDICATED.
2. OVER A WEEKEND OUTAGE, CUT IN AND PROVIDE PERMANENTLY
MOUNTED 8" TEMPORARY CHILLER CONNECTIONS.
3. PRIOR TO CONSTRUCTION, OBTAIN BASELINE OPERATING DATA
FOR THE EXISTING CHILLED WATER SYSTEM, INCLUDING
SECONDARY PUMP DIFFERENTIAL HEAD AND TOTAL BUILDING
CHILLED WATER FLOW. OBTAIN OPERATING DATA WITH ALL
CHILLED WATER COIL CONTROL VALVES AT 100%, 80%, & 60%
OPEN. EXISTING EQUIPMENT CHILLED WATER FLOW RATES ARE
PROVIDED FOR REFERENCE ONLY.
4. ROUTE TEMPORARY 8"CWS&R PIPING THROUGH EXISTING
DOORWAY. PROVIDE TEMPORARY PLYWOOD WEATHER BARRIER
TO MAINTAIN WEATHER TIGHTNESS.
1. THE PROJECT MUST BE BUILT WHILE THE BUILDING REMAINS IN
SERVICE AND OCCUPIED, AND MUST REMAIN IN SERVICE, EXCEPT
FOR SCHEDULED OUTAGES.
2. GOVERNMENT WILL PROVIDE TEMPORARY CHILLER PRIOR TO
START OF CONSTRUCTION. PROVIDE SKID MOUNTED CHILLED
WATER PUMP. PUMP MUST BE TIED INTO THE EXISTING BUILDING
SYSTEMS OVER A WEEKEND OUTAGE.
3. PROVIDE ALL NECESSARY VALVES, ACCESSORIES, TEMPORARY
PIPING AND APPURTENANCES NECESSARY TO OPERATE
TEMPORARY CHILLER. PROVIDE ISOLATION VALVES NECESSARY
TO ISOLATE ACTIVE ZONES OF THE CHILLED WATER DISTRIBUTION
SYSTEM FROM THE AREA OF WORK.
4. AFTER INSTALLATION OF PERMANENT CHILLER EQUIPMENT,
START-UP AND SWITCHOVER WILL OCCUR WITH PRIOR APPROVAL
FROM THE CONTRACTING OFFICER, AT LEAST 2 WEEKS IN
ADVANCE. FOR START-UP, PROVIDE ISOLATION VALVES AT THE
TEMPORARY EQUIPMENT FOR SWITCHOVER WITHOUT THE NEED
FOR DE-COUPLING OR DRAIN DOWN.
(E) EQUIPMENT
SCHEDULE
UNIT NO. GPM NOTES
RTU-1 23.6
RTU-2 4.8
RTU-3 26.9
RTU-4 12.5
RTU-5 4.3
RTU-7 18.8
RTU-8 58.1
RTU-9 13
RTU-10 20.6
RTU-14 4.1
AHU-1 10.5
AHU-2 5.9
AHU-4 88.2
AHU-22-301 63.2
AHU-22-303 -
AHU-22-304 -
AHU-22-306 -
NOTES
A
A. OBTAIN PRE-TAB CHILLED WATER COIL FLOW
MEASUREMENT PRIOR TO CONSTRUCTION.
B. PROVIDED FOR REFERENCE ONLY.
A A
B
MD401
MD402
(E)TEMPORARY CHILLER
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :20
:57 P
M
1.0
1.0
M
D1
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
KEY PLAN
N.T.S.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
N
MD101
12939355
OV
ER
AL
L P
LA
N
- D
EM
OL
IT
IO
N
ZAC ZAC WAN
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. NOT USED.
N
8'0 16' 1/8"=1'-0"
OVERALL PLAN - DEMOLITION1
B.2
B.3
(E)AIR HANDLING
UNIT
(E)AHU-1
(E)1-1/2"CWS&R
7.5 8 8.5 9
A
A.3
(E)RTU-10
(E)RTU-5
(E)EXHAUST
FAN
(E)1-1/2"CWS&R
(E)1"CWS&R
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :21
:03 P
M
1.0
1.0
M
D1
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
MD102
12939356
CO
NT
RO
L V
AL
VE
P
LA
N
- D
EM
OL
IT
IO
N
ZAC ZAC WAN
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
1. OVER A WEEKEND OUTAGE, REMOVE EXISTING THREE-WAY
CONTROL VALVE AND ASSOCIATED BYPASS PIPING AND PROVIDE
TWO WAY CONTROL VALVE. BALANCE NEW VALVE PER SCHEDULE
ON M-601.
NOTES
N
8'0 4' 1/4"=1'-0"
(E)AHU-1 CONTROL VALVE - DEMOLITION2 KEY PLAN
N.T.S.
N
N
8'0 4' 1/4"=1'-0"
(E)RTU-5&10 CONTROL VALVES - DEMOLITION1 KEY PLAN
N.T.S.
N
D.4
(E)3"CW
(E)3"CW
2"CW
(E)2"CW (BELOW GRADE)
(E)10"C (BELOW GRADE)6
(E)EXHAUST FAN
(E)10"CR (BELOW GRADE) 6
(E)EXHAUST FAN
ON ROOF ABOVE
CHEM SHOT FEEDER7
(E)28x28
(E)AIR SEPARATOR
(E)LPS
(E)6"HWS
(E)6"HWR
(E)2"HWS
(E)2"HWR
(E)3" PC
(E)2" PC
(E)6"HWS
CWP
CWP
(E)HWP
(E)HWP
(E)3/4"CW
1"CWR81"CWS8
CWP
CWP
(E)6" HWR
(E)6"HWS
8"PCWS 3
10"CWR3
8" PCWR
(E)DDC PANELS
(E)10"CWS
(E)10"CWR
10"CR 3
10"CWS
10"C3
(E)28x28 UP
(E)EXPANSION TANK
(E)AIR COMPRESSOR
(E)FIRE PROTECTION
EQUIPMENT
(E)BACKFLOW PREVENTER
(E)SPRINKLER PIPE
(E)3"CW
(E)STORM
(E)SPRINKLER PIPE
(E)SPRINKLER PIPE
(E)SPRINKLER PIPE
(E)HEAT EXCHANGER
10"CWS3
12 12
3"CW12
2"CW12
(E)3"CW
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :21
:11 P
M
1.0
1.0
M
D4
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
KEY PLAN
N.T.S.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
N
MD401
12939357
ME
CH
AN
IC
AL
R
OO
M
PL
AN
DE
MO
LIT
IO
N
ZAC ZAC WAN
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. REMOVE CHILLER AND ALL ASSOCIATED PIPING, SUPPORTS,
CONTROLS, AND APPURTENANCES COMPLETE. CAPTURE AND
DISPOSE OF REFRIGERANT PER SPECIFICATIONS.
2. REMOVE REFRIGERANT MONITORING SYSTEM AND ALL
ASSOCIATED CONTROLS INCLUDING CONTROLLER, SENSOR,
ALARM, LIGHT, WIRING, TUBE FOR AIR SAMPLING, AND HORNS.
ASSOCIATED EXHAUST FAN TO REMAIN FOR REUSE.
3. REMOVE PIPING AND ALL ASSOCIATED INSULATION, SUPPORTS,
AND APPURTENANCES COMPLETE TO POINTS INDICATED.
4. REMOVE END SUCTION PUMP AND ALL ASSOCIATED SUPPORTS,
CONTROLS, PIPING AND APPURTENANCES COMPLETE.
5. REMOVE EQUIPMENT PAD COMPLETE. REPAIR FLOOR BELOW TO
MATCH ADJACENT.
6. FILL AND ABANDON PIPE BELOW GRADE.
7. REMOVE CHEMICAL FEEDER AND ALL ASSOCIATED SUPPORTS AND
APPURTENANCES COMPLETE.
8. REMOVE PIPING, AND ALL ASSOCIATED INSULATION, SUPPORTS,
AND APPURTENANCES COMPLETE.
9. REMOVE PIPING AND ALL ASSOCIATED INSULATION, SUPPORTS,
AND APPURTENANCES TO 6" BELOW FINISHED FLOOR, FILL AND
CAP. PATCH CONCRETE SLAB TO MATCH EXISTING CONDITIONS.
10. REMOVE EXPANSION TANK AND ALL ASSOCIATED SUPPORTS AND
APPURTENANCES COMPLETE.
11. REMOVE REFRIGERANT RELIEF PIPING COMPLETE TO ROOF
PENETRATION. CAP AND ABANDON PIPE AT ROOF PENETRATION.
12. REMOVE BACKFLOW PREVENTER AND ALL ASSOCIATED DRAIN AND
MAKE UP WATER PIPING COMPLETE TO POINTS INDICATED.
13. REMOVE AIR SEPARATOR AND ALL ASSOCIATED SUPPORTS AND
APPURTENANCES COMPLETE.
N
8'0 4' 1/4"=1'-0"
MECHANICAL ROOM PLAN - DEMOLITION1
D.4
8"C 10
10" CR 2
8" CR 2
8" CR2
2" CW2
COOLING
TOWER
1 1
PUMP11
PUMP11
10" C2
(E)2"CW (BELOW GRADE)3
(E)10"C (BELOW GRADE)3
(E)10"CR (BELOW GRADE) 3
(E)AHU-4
ABANDONED PUMP11
ENCLOSURE WALL5
CHAIN LINK FENCE7
(E)CHAIN LINK FENCE
(E)SIDEWALK
(E)CHAIN LINK FENCE
3 3.5 4 4.5
TEMPORARY CHILLED
WATER PUMP AREA
SEE M-002 FOR
CONTINUATION
(E)TEMPORARY CHILLER
TEMPORARY
8"CWS&R
COOLING
TOWER
8"C 10
(E)PROCESS EQUIPMENT
(E)PROCESS EQUIPMENT
(E)PROCESS EQUIPMENT
CONCRETE PAD
(E)3"CWS&R
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :21
:21 P
M
1.0
1.0
M
D4
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
KEY PLAN
N.T.S.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
N
MD402
12939358
YA
RD
P
LA
N
- D
EM
OL
IT
IO
N
ZAC ZAC WAN
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
1. REMOVE COOLING TOWER AND ALL ASSOCIATED CONTROLS,
EQUALIZING AND BYPASS PIPING, APPURTENANCES, AND DRAIN
PIPING COMPLETE.
2. REMOVE PIPING, AND ALL ASSOCIATED INSULATION, SUPPORTS,
AND APPURTENANCES TO 6" BELOW GRADE, FILL AND CAP. PATCH
CONCRETE SLAB TO MATCH EXISTING CONDITIONS.
3. FILL AND ABANDON PIPE BELOW GRADE.
4. REMOVE EQUIPMENT PAD COMPLETE. REPAIR FLOOR BELOW TO
MATCH ADJACENT.
5. REMOVE CMU ENCLOSURE WALL COMPLETE. ENCLOSURE WALL IS
APPROXIMATELY 17' TALL. SEE STRUCTURAL DRAWINGS FOR MORE
REQUIREMENTS.
6. REMOVE COOLING TOWER EQUIPMENT CONCRETE SUPPORTS
COMPLETE. SEE STRUCTURAL DRAWINGS FOR MORE
REQUIREMENTS.
7. REMOVE CHAIN LINK FENCE COMPLETE TO POINTS INDICATED. SEE
CIVIL DRAWINGS FOR MORE REQUIREMENTS.
8. ROUTE TEMPORARY 8"CWS&R PIPING THROUGH EXISTING
DOORWAY. PROVIDE TEMPORARY PLYWOOD WEATHER BARRIER
TO MAINTAIN WEATHER TIGHTNESS.
9. REUSE EXISTING FENCE PIPE CUT-OUTS FOR TEMPORARY CHILLER
CONNECTION DURING CONSTRUCTION.
10. REMOVE PIPING, AND ALL ASSOCIATED INSULATION, SUPPORTS,
AND APPURTENANCES COMPLETE.
11. REMOVE END SUCTION PUMP AND ALL ASSOCIATED SUPPORTS,
CONTROLS, PIPING AND APPURTENANCES COMPLETE.
12. REMOVE CONCRETE ENCLOSURE PAD COMPLETE TO POINTS
INDICATED.
13. OVER A WEEKEND OUTAGE, REMOVE EXISTING THREE-WAY
CONTROL VALVE AND ASSOCIATED BYPASS PIPING AND PROVIDE
TWO WAY CONTROL VALVE. BALANCE NEW VALVE PER SCHEDULE
ON M-601.
NOTES
N
8'0 4' 1/4"=1'-0"
YARD PLAN - DEMOLITION1
M-401
M-403
M-402
CONCRETE PAD2
CONCRETE PAD1
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :21
:29 P
M
1.0
1.0
M
-1
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
KEY PLAN
N.T.S.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
N
M-101 12939359
OV
ER
AL
L P
LA
N
ZAC ZAC WAN
GENERAL NOTES
NOTES
1. PROVIDE CONCRETE PAD FLUSH TO GRADE. SEE STRUCTURAL
DRAWINGS FOR MORE DETAILS.
2. AFTER TEMPORARY CHILLER HAS BEEN DE-MOBILIZED, PROVIDE
CONCRETE PAD FOR TEMPORARY CHILLER LAYDOWN AREA. PAD
MUST FLUSH TO GRADE. SEE STRUCTURAL DRAWINGS FOR MORE
DETAILS.
N
8'0 16' 1/8"=1'-0"
OVERALL PLAN1
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
B.2
B.3
(E)AIR HANDLING
UNIT
(E)AHU-1
(E)1-1/2"CWS&R
V-AHU-1 1
7.5 8 8.5 9
A
A.3
(E)RTU-10
(E)RTU-5
(E)EXHAUST
FAN
(E)1-1/2"CWS&R V-RTU-10 1
(E)1"CWS&R V-RTU-5 1
FI
LE
N
RE
F:
PL
OT
D
AT
E:
4/3
0/2
6 2 :21
:36 P
M
1.0
1.0
M
-1
.D W
G
A
B
C
D
1 2 3 4 5
1 2 3
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
CHK
SATISFACTORY TO
ACTIVITY
DATE
FOR COMMANDER NAVFAC
OF
EPROJECT NO.:
AS NOTED
<<PM/DM>>
BRANCH MANAGER
CHIEF ENG/ARCH
<<XX>>
4325 Lake Boone Trail|Suite 301|Raleigh, NC 27607
(984) 204-4500 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
4 5
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
MC
AS
C
HE
RR
Y
PO
IN
T, N
C
CH
ER
RY
P
OI
NT
, N
C
FA
C
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
A
C Q
U
IS
IT
IO
N S
D
IV
IS
IO
N M
C
AS
C H
ER
R
Y
PO
IN
T
- C H
ER
R
Y
PO
IN
T, N C
BU
IL
DI
NG
RE
PL
AC
E
CH
IL
LE
RS
C
OO
LI
NG
T
OW
ER
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
7440851
NICHOLAS A. HALL
PATRICK FAULKNER
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M-102 12939360
CO
NT
RO
L V
AL
VE
P
LA
N
ZAC ZAC WAN
GENERAL NOTES
NOTES
1. OVER A WEEKEND OUTAGE, REMOVE EXISTING THREE-WAY
CONTROL VALVE AND ASSOCIATED BYPASS PIPING AND PROVIDE
TWO WAY CONTROL VALVE. BALANCE NEW VALVE PER SCHEDULE
ON M-601.
G1. ALL WORK MUST BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
N
8'0 4' 1/4"=1'-0"
(E)AHU-1 CONTROL VALVE2 KEY PLAN
N.T.S.
N
N
8'0 4' 1/4"=1'-0"
(E)RTU-5&10 CONTROL VALVES1 KEY PLAN
N.T.S.
N
D.4
(E)3"CW
(E)3"CW
(E)FIRE PROTECTION
EQUIPMENT
(E)2"CW
(E)6"HWS
(E)6"HWR
(E)6"HWS
(E)HWP
(E)HWP
(E)3/4"CW
(…