This is a Time Compliance Technical Order (TCTO) issued by the U.S. Coast Guard for replacing the fire and smoke detection system aboard Medium Endurance (WMEC-270) Class Cutter hulls 901 through 913.
The order directs contractors to remove the existing Siemens/Pyrotronics III fire detection system and all ancillary components, replacing them with the Consilium Salwico Fire detection system. The replacement must be accomplished within 60 months of receipt and includes removal of approximately 79 detector bases, 73 mounting plates, and numerous control units, annunciators, and supporting components. The contractor must supply Government-furnished equipment (GFE) consisting of one Control System Fire Suppression kit (P/N Q2401251-8, NSN 5998-01-F25-7076, valued at $77,550) containing 73 heat detectors, 59 smoke detectors, and associated hardware. Work requires 1,498 total labor hours: 1,490 hours for electrical installation by electricians, 3 hours for QA inspection, and 5 hours for painting. The contractor must provide an OEM-certified technical representative for the Consilium system to ensure compliance with manufacturer procedures, deliver operator training documentation, provide temporary fire detection coverage during installation, and conduct comprehensive system testing across 16 zones covering engine rooms, staterooms, storage spaces, and other compartments. A prototype system was installed on USCGC Spencer (WMEC-905) and USCGC Escanaba (WMEC-907) in November 2025. The order references multiple Coast Guard drawings, technical publications, and SFLC standard specifications for electrical work, cable testing, cable installation, and ship preservation. Upon completion, units must submit TCTO sign-off sheets, update Maintenance Standards in the Fleet Logistics System, and complete SFLC Form 47 documentation. Warranty coverage extends 12 months after installation and no more than 18 months after delivery.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. COAST GUARD
COMPUTERIZED MAINTENANCE SYSTEM
ASSET NUMBER OPERATING ACTIVITY MAINTENANCE ACCOMPLISHED MAINTENANCE DUE
DATE ASSET HOURS DATE ASSET HOURS
MO DAY YEAR MO DAY YEAR
ZULU DATE ZULU HOURS
MO DAY YEAR
ITEM 1
DUE
CMS CODE ACTION DESCRIPTION CEINUM
SCHEDULED UNSCHEDULED
MAN HOURS: MK___.___ DC___.___ EM___.___ ET___.___ GM___.___ BM___.___ FN___.___ SN___.___ ME___.___ IT___.___ OTHER___.___
REMARKS:
TECHNICIAN’S
SIGNATURE
TECHNICIAN’S
ID
* ASTERISK INDICATES QA REQUIRED
IMMEDIATE ATTENTION REQUIRED
TIME COMPLIANCE TECHNICAL ORDER
Authority: 44 U.S.C. 3101; 44 U.S.C. 3534; 5 U.S.C. §552a (e)(3); and Executive Order 9397.
Purpose: To account for scheduled and unscheduled maintenance performed on CG aircraft and surface assets.
Routine Uses: Authorized CG personnel will use this information to document scheduled and unscheduled maintenance, man-hours expended, and the technician respon-sible for tasks performed on CG aircraft and surface assets. Any external disclosures of data within this record will be made in accor-dance with DHS/ALL-004, General Information Technology Access Account Records, 77 Federal Register 70792, November 27, 2012.
Disclosure: Furnishing your Tech ID is voluntary; however, the inability to collect this information could result in untimely or incomplete Asset Computer-ized Maintenance System reports or the inability for the CG to make informed decisions regarding manpower analysis.
Distribution Statement D: Distribution authorized to the DHS/CG/DoD and their contractors Administrative/Operational use, 03/05/24. Other requests shall be referred to the appropriate asset product line.
WARNING: This document contains technical data whose export is restricted by the Arms Export-Control Act (Title 22, U.S.C., Sec 2751, et. seq.) or the Export Administration Act of 1979, as amended, Title 50, U.S.C. App 2401 et. seq. Violations of these export laws are subject to severe criminal penalties.
Disseminate in accordance with provisions of DoD Directive 5230.25.
DESTRUCTION NOTICE: For classified documents, follow the procedures in DoD 5200.22-M, National Industrial Security Program Operating Manual, Sec-tion 5-705 or DoD 5200.1-R, Information Security Program Regulation, Chapter VI, Section 7. For unclassified, limited documents, destroy by any method that will prevent disclosure of contents or reconstruction of the document.
PRIVACY ACT STATEMENT
REVIEWED
BY
LOG YN DATA
ENTRY
COMPLETED
WEIGHT AND BALANCE OFFICER’S
SIGNATURE
UNIT DOCUMENT
NUMBER
UNI
TE
D
ST
ATES COAST
GUARD
UNI
TE
D
ST
ATES COAST
GUARD
* QA (1)
TN3060 REPLACE FIRE & SMOKE DETECTION SYSTEM M3-B000-001
TCTO WMEC-270-TN3060
THIS TECHNICAL ORDER IS APPLICABLE TO ALL COAST GUARD
MEDIUM ENDURANCE (WMEC-270) CLASS CUTTER HULLS 901
THROUGH 913.
WMEC-270
TN3060.0
REV’D 05/13/26
U.S. COAST GUARD
COMPUTERIZED MAINTENANCE SYSTEM
WMEC-270
TN3060.0
REV’D 05/13/26
Distribution Statement D: Distribution authorized to the DHS/CG/DoD and their contractors Administrative/Operational use, 03/05/24. Other requests shall be referred to the appropriate asset product line.
WARNING: This document contains technical data whose export is restricted by the Arms Export-Control Act (Title 22, U.S.C., Sec 2751, et. seq.) or the Export Administration Act of 1979, as amended, Title 50, U.S.C. App 2401 et. seq. Violations of these export laws are subject to severe criminal penalties.
Disseminate in accordance with provisions of DoD Directive 5230.25.
DESTRUCTION NOTICE: For classified documents, follow the procedures in DoD 5200.22-M, National Industrial Security Program Operating Manual, Sec-tion 5-705 or DoD 5200.1-R, Information Security Program Regulation, Chapter VI, Section 7. For unclassified, limited documents, destroy by any method that will prevent disclosure of contents or reconstruction of the document.
REVIEWED
BY
LOG YN DATA
ENTRY
COMPLETED
WEIGHT AND BALANCE OFFICER’S
SIGNATURE
UNIT DOCUMENT
NUMBER
UNI
TE
D
ST
ATES COAST
GUARD
UNI
TE
D
ST
ATES COAST
GUARD
THIS TECHNICAL ORDER DIRECTS AND AUTHORIZES THE
REPLACEMENT OF THE EXISTING SIEMENS / PYROTRONICS III SYSTEM
TO INCLUDE ALL ANCILLARY COMPONENTS WITH THE CONSILIUM
SALWICO FIRE DETECTION SYSTEM.
PROTOTYPE WAS INSTALLED ON USCGC SPENCER (WMEC-905 AND
USCGC ESCANABA (WMEC-907) AT PORTSMOUTH, VA, IN NOVEMBER,
2025, AND WILL REMAIN INSTALLED.
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
TCTO WMEC-270 TN3060
1. APPLICATION
This technical order is applicable to all Coast Guard Medium Endurance (WMEC-270) Class Cutter Hulls 901 through 913.
2. PURPOSE
This Engineering Change (EC) provides instructions for the Contractor to replace the existing Siemens/ Pyrotronic III system to include all ancillary components with the Consilium Salwico Fire detection system.
3. EC COORDINATOR
Technical questions or comments associated with this EC must be directed to:
EC Coordinators Office: USCG Surface Forces Logistics Center, MECPL Primary POC: LT. Aaron D. Benson (TCTO Developer) Telephone: (206) 820-3212 E-mail: Aaron.D.Benson@uscg.mil
Additional contact information can be found on the appropriate Product Line’s webpage on SFLC’s Coast Guard SharePoint Site at SFLC - Home (sharepoint-mil.us).
4. WHEN TO BE ACCOMPLISHED
This EC must be accomplished within 60 months after receipt of this EC.
5. BY WHOM TO BE ACCOMPLISHED
This EC must be accomplished by commercial contractor. MECPL.
PDM Branch must coordinate the scheduling and execution of this EC for each asset.
6. WHAT IS REQUIRED
a. SUPPLY SUPPORT
(1) Kits/Parts/Materials Required
The following parts, kits, and/or materials are required to accomplish this EC and will be acquired through the supply sources discussed herein:
Table 6-1. GFE KITS
QTY NSN/ACN PART
NUMBER ITEM DESCRIPTION SOURCE
1 kt 5998-01-F25-7076 Q2401251-8 Control System, Fire Suppression CAGE: 3EGT0
The parts listed in the table below are contained in kit, P/N: Q2401251-8 and are not required to be requisitioned separately.
Table 6-2. CONTROL SYSTEM, FIRE SUPPRESSION GFE KIT CONTENTS
QTY NSN PART NUMBER ITEM DESCRIPTION
73 ea 5975-01-729-5992 5100776-00A Plate, Mounting
79 ea 5975-01-736-4629 5100774-00A Detector Base mailto:Aaron.D.Benson%40uscg.mil?subject=
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
QTY NSN PART NUMBER ITEM DESCRIPTION
4 ea 6350-01-729-5962 5101060-00A Detector, Heat
2 ea 5980-01-728-0377 5200236-00A Semiconductor Device, Photo
2 ea 5935-01-729-0487 5200237-00A Connector Assembly, Electrical
10 ea 6350-01-729-5877 5200031-02B Station, Fire Alarm, Manual
2 ea 6350-33-208-8133 N11250 Alarm, Monitor
2 ea 5975-01-729-0536 5100775-00A Panel, Alarm (Detection Fire & Smoke)
2 ea N/A 5600965-00 Fire Detection Isolator
5 ea 6350-01-734-1761 5100195-20A Control Unit, Alarm
1 ea 6350-37-524-6448 5200123-00A Sensing Element, Fire Detector
14 ea N/A 712 A Misc-002, Bells
1 ea N/A 712 B Misc-003, Network
1 ea N/A 712 C Local Supply
1 ea N/A SG52127-FDS-Port Salwico fire Detection System
1 ea N/A SG52127-FDS Salwico fire Detection System
14 ea 6350-01-729-0504 040030 Detector, Heat
59 ea 6350-01-661-3650 040020 Alarm, Smoke, Automatic
(3) Disposition of Removed and Replaced Parts/Materials and Initial Seed of New Parts/Materials. SFLC will be responsible for action on Inventory Control Point (ICP) items.
Disposition instructions for parts and materials removed as a result of this EC:
Table 6-3. DISPOSITION OF REMOVED PARTS AND MATERIALS
NSN PART NUMBER ITEM
DESCRIPTION DISPOSITION COMMENTS
5998-01-453-4620 PMD-45 Display Panel Return to ICP (4 ea)
Refer to Enclosure 1, Table 1
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
NSN PART NUMBER ITEM
DESCRIPTION DISPOSITION COMMENTS
1265-01-F25-7046 A-181610CHQRFG PLC Box Return to ICP (1 ea)
Refer to Enclosure 1, Table 1
6350-01-F25-7045 A-20H1606GQRLP Annunciator Return to ICP (1 ea)
Refer to Enclosure 1, Table 1
6350-01-F25-7042 A-12106CHQRFG Annunciator Return to ICP (1 ea)
Refer to Enclosure 1, Table 1
6350-01-F25-7041 A16128JFGQRR Annunciator Return to ICP (1 ea)
Refer to Enclosure 1, Table 1
The parts and quantities listed in Table 6-4 have been updated as a result of this EC.
TABLE 6-4. REMOVE FROM OPERATING STOREROOM ITEMS (OSI)
QTY NSN PART
NUMBER ITEM DESCRIPTION DISPOSITION
0 ea 6350-01-481-3961 DB-11 Base, Detector Return To Warehouse
0 ea 6350-01-642--4361 516.037.004 Detector, Flame Infrared Return To Warehouse
1 ea 6350-01-391-2669 DT-200WP Detector, Heat Return To Warehouse
20 ea 6350-01-679-1774 S54372-F1-A1 Fire Detector Return To Warehouse
The following parts and quantities managed in inventory aboard operational assets have been updated as a result of this EC.
Table 6-5. NEW STOCK FOR OPERATING STOREROOM ITEMS (OSI)
QTY NSN PART NUMBER ITEM DESCRIPTION SOURCE OF
SUPPLY
1 ea 6350-33-208-8133 N11250 Alarm, Smoke, Automatic CAGE: A188N
6 ea 350-01-661-3650 040020 Alarm, Smoke, Automatic CAGE: 3EGT0
2 ea 6350-01-729-0504 040030 Detector, Heat CAGE: 3EGT0
1 ea 6130-01-729-0482 5100087-02A Power Supply CAGE: 3EGT0
1 ea 6625-01-729-0516 5100554-00A Light, Test CAGE: 3EGT0
1 ea 5975-01-729-0536 5100775-00A Plate, Mounting CAGE: 3EGT0
8 ea 5975-01-729-5992 5100776-00A Plate, Mounting CAGE: 3EGT0
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
QTY NSN PART NUMBER ITEM DESCRIPTION SOURCE OF
SUPPLY
1 ea 6350-01-729-5962 5101060-00A Detector, Heat CAGE: 3EGT0
1 ea 6350-01-729-5877 5200031-02B Station, Fire Alarm, Manual CAGE: 3EGT0
1 ea 5980-01-728-0377 5200236-00A Semiconductor Device, Photo A/C IR Flame Detector, Salwico AC-IR-3FO
CAGE: 3EGT0
1 ea 5935-01-729-0487 5200237-00A Connector, Assembly Addressable Base for IR Flame detector.
CAGE: 3EGT0
1 ea 6350-33-208-8133 N11250 Alarm, Smoke, Automatic CAGE: 3EGT0
The parts listed in Table 6-6 have been updated as a result of this EC.
TABLE 6-6. REMOVE FROM ICP
NSN PART NUMBER ITEM DESCRIPTION DISPOSITION COMMENTS
5920-00-199-9502 ABC15-250V Fuse Cartridge Determined by Warehouse (IM).
Remove WMEC-270’s
6350-01-230-7985 AE-30U Control, Alarm Determined by Warehouse (IM).
Remove WMEC-270’s
5920-00-280-4960 AGC-2 Fuse, Cartridge Determined by Warehouse (IM).
Remove WMEC-270’s
5998-01-453-4687 AS-BDAP-204 Circuit Card Assembly
Determined by Warehouse (IM)
Remove WMEC-270’s
5945-01-399-5980 AS-BDAP-212 Relay, Solid State Determined by Warehouse (IM)
Remove WMEC-270’s
5998-01-364-2516 AS-BDEP-216 Circuit Card Assembly
Determined by Warehouse (IM)
Remove WMEC-270’s
5998-01-461-5647 AS-BDEP-217 Circuit Card Assembly
Determined by Warehouse (IM)
Remove WMEC-270’s
6130-01-370-0552 AS-P120-000 Power Supply, Assembly
Determined by Warehouse (IM)
Remove WMEC-270’s
6130-01-223-6133 BC-35 Battery Charger Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-461-7152 BBT-120T-A Annunciator Determined by Warehouse (IM)
Remove WMEC-270’s
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
NSN PART NUMBER ITEM DESCRIPTION DISPOSITION COMMENTS
6140-01-316-8625 BT-34 Battery, Storage Determined by Warehouse (IM)
Remove WMEC-270’s
6320-01-283-9370 CP-35 Control Unit Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-452-1123 DB-3S Base, Detector Determined by Warehouse (IM)
Remove WMEC-270’s
4210-01-185-2762 DI-3 Smoke Detector, Ionization
Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-322-4446 DI-3IS Sensor, Opaque Particle
Determined by Warehouse (IM)
Remove WMEC-270’s
6240-01-425-8723 DL1CB006 Lamp, Incandescent Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-391-2669 DT-200WP Detector, Heat Determined by Warehouse (IM)
Remove WMEC-270’s
5920-01-168-9907 GDB-500MA Fuse, Cartridge Determined by Warehouse (IM)
Remove WMEC-270’s
5920-01-302-0423 GDC800MA Fuse, Cartridge Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-391-2670 MBDC-10 Bell, Electrical Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-300-6267 MM-35 Module, Meter, Battery
Determined by Warehouse (IM)
Remove WMEC-270’s
5998-01-461-5734 NW-BP-85-000 Circuit Card Assembly
Determined by Warehouse (IM).
Remove WMEC-270’s
5998-01-399-5982 PC-A984-145 Controller, Logic Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-455-4439 PE-11 Alarm, Smoke, Automatic
Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-418-5672 PE-3 Sensing Element, Fire
Determined by Warehouse (IM)
Remove WMEC-270’s
5961-01-359-4237 PM-32 Semiconductor Device Assembly
Determined by Warehouse (IM)
Remove WMEC-270’s
6130-01-284-1575 PS-35 Power Supply Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-679-4361 S121 Detector, Flame Infrared
Determined by Warehouse (IM)
Remove
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
NSN PART NUMBER ITEM DESCRIPTION DISPOSITION COMMENTS
6350-01-679-1774 S54372-F1-A1 Detector, Light Intensity
Determined by Warehouse (IM)
Remove WMEC-270’s
4210-01-123-7286 SR-32 Module, Relay Determined by Warehouse (IM)
Remove WMEC-270’s
6930-01-126-3849 TL-30U Module, Time Limit Determined by Warehouse (IM)
Remove WMEC-270’s
5930-01-379-4998 ZA2-BD2 Switch Determined by Warehouse (IM)
Remove WMEC-270’s
5998-01-211-3166 ZS-30 Circuit Card Assembly
Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-300-6268 ZU-35TS Module, Alarm, Smoke
Determined by Warehouse (IM)
Remove WMEC-270’s
5905-00-141-1116 11204-074 Resistor, Fixed, Comp
Determined by Warehouse (IM)
Remove WMEC-270’s
5998-01-461-5716 170AAI52040 Circuit Card Assembly
Determined by Warehouse (IM)
Remove WMEC-270’s
5998-01-461-5692 170BDI54250 Modbus Module Determined by Warehouse (IM)
Remove WMEC-270’s
5998-01-461-5688 170NEF11021 Circuit Card Assembly
Determined by Warehouse (IM)
Remove WMEC-270’s
6130-01-453-5215 2426418.00 Power Supply Determined by Warehouse (IM)
Remove WMEC-270’s
5935-01-090-1561 206060-1 Connector, Plug, Elec Determined by Warehouse (IM)
Remove WMEC-270’s
3010-01-478-0692 213811-1 Coupling Ring, Size
Determined by Warehouse (IM)
Remove WMEC-270’s
0000-XF-C-33-7919 500-025402 Sensor, Opaque, Particle
Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-333-2538 500-083263 Sensor, Opaque, Particle
Determined by Warehouse (IM)
Remove WMEC-270’s
0000-XF-C33-7921 500-86495 Housing, Air Duct Determined by Warehouse (IM)
Remove
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
NSN PART NUMBER ITEM DESCRIPTION DISPOSITION COMMENTS
000-XF-C33-7920 500-094150 Sensor, Opaque, Particle
Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-481-3961 500-094151 Fire Detector Base Determined by Warehouse (IM)
Remove WMEC-270’s
5340-01-679-1803 500-094187 Plate, Mounting Determined by Warehouse (IM)
Remove WMEC-270’s
6350-01-642-4361 516.037.004 Sensing Element, Fire Detector
Determined by Warehouse (IM)
Remove WMEC-270’s
5999-01-340-1407 66181-1 Contact, Electrical Determined by Warehouse (IM)
Remove WMEC-270’s
5998-01-453-4620 76737-16 Operator Interface, PMD 475
Determined by Warehouse (IM)
Remove WMEC-270’s
6210-01-461-7869 76801 Keyboard Expander Determined by Warehouse (IM)
Remove WMEC-270’s
The parts and quantities listed in Table 6-7 have been updated as a result of this EC.
Table 6-7. NEW STOCK FOR ICP
QTY NSN PART NUMBER ITEM DESCRIPTION SOURCE OF
SUPPLY
13 ea 5998-01-F25-7076 Q2401251-8 Control System, Fire and Smoke Detection Installation Kit. CAGE: 3EGT0
b. MANPOWER AND PERSONNEL
WORK PHASE SKILLS LABOR-HOURS
Electrical Remove & Installation Electrician 1490.0
Inspection QA 3.0
Paint and Preservation Painter 5.0
TOTAL 1498.0
c. SUPPORT AND TEST EQUIPMENT
(1) Special Tools
None.
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
(2) Special Test Equipment
None.
(3) Software
None.
d. TECHNICAL DOCUMENTS
The tables listed below are used to identify the documents that have been affected by and/or are required to accomplish this configuration change. The source codes listed below each table are used to identify the intended reason for inclusion in this EC; multiple codes may be applicable to each document:
(1) Drawings – Below are the drawing revisions that have been affected, created, or will be referenced while completing the changes called for in this EC. Consult CG-LIMS STIP, “https://timsweb.uscg.
mil:7012/STIP_EE/#!” for the most current drawing revision when making the installations.
CG DWG REV TITLE ACTION(s) TAKEN*
901-WMEC-320-035 AV As-Built Electrical One-Line Diagram Q
901-WMEC-436-003 W Fire & Smoke Detection & Quarterdeck Monitoring System Blk & IWD Q
901-WMEC-436-006 - Fire and Smoke Detection system Upgrade, Rip out and Installation Q
905-WMEC-320-014 AR Electrical One-Line Diagram Q
*ACTION TAKEN CODES (more than one code may be used) R – Revised as a result of EC Q – Required to complete EC A – Added as a result of EC D – Deleted (upon completion of EC) https://timsweb.uscg.mil:7012/STIP_EE/#!
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
(2) Technical Publications (TP) – Below are the TP revisions that have been affected, created, or will be referenced while completing the changes called for in this EC. Consult CG-LIMS STIP, “https:// timsweb.uscg.mil:7012/STIP_EE/#!” for the most current TP revision when making the installations.
TP NUMBER TITLE DATE ACTION(s)
TAKEN*
3365B-436 Fire and Smoke Detection System 15 OCT 2000 Q, D
ME-H4-0001-V0-436
Fire Detection System – Salwico Cruise – Quick & User Guide, Service, Maint & Install Manual
01 APR 2025 Q, A
*ACTION TAKEN CODES (more than one code may be used) R – Revised as a result of EC Q – Required to complete EC A – Added as a result of EC D – Deleted (upon completion of EC)
(3) Maintenance Procedure Cards (MPC) – Below are the MPC revisions that have been affected, created, or will be referenced while completing the changes called for in this EC. Consult CG-LIMS STIP, “https://timsweb.uscg.mil:7012/STIP_EE/#!” for the most recent version.
MPC
NUMBER DESCRIPTION ACTION REV DATE ACTION(s)
TAKEN*
E-C-14274 Fire Detector Sensor REPLACE 15 MAY 2023 D
E-M-6841 Fire Detector System INSP/CHK 15 OCT 2023 D
E-S-1338 Air Duct Smoke Detectors INSP/CLN 15 JUN 2021 D
E-S-6840 Fire Detector System INSP/CLN 15 NOV 2023 D
E-A-18277 Fire Detector System INSP/CLN TBD/ IN
WORKFLOW A
E-M-18278 Fire Detector System INSP/CHK TBD/ IN
WORKFLOW A
E-C-18279 Smoke Detector REPLACE TBD/ IN
WORKFLOW A
*ACTION TAKEN CODES (more than one code may be used) R – Revised as a result of EC Q – Required to complete EC A – Added as a result of EC D – Deleted (upon completion of EC) https://timsweb.uscg.mil:7012/STIP_EE/#!
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
(4) Other – Below are all other documents that are required to complete this EC.
DOCUMENT
TYPE TITLE DOCUMENT NUMBER REV DATE ACTION(s)
TAKEN*
Enclosure 1 Fire and Smoke Detection System, Renew
TCTO_TN3060_43600_
KFM_0725_270 01 JUL 2025 Q
NSTM Gas Free Engineering Chapter 074, Volume 3 01 FEB 2019 Q
COMDTINST Equipment Lock/ Tags-Pls 9077.1 (series) 08 NOV 2018 Q
COMDTINST Naval Engineering Manual M9000.6 (series) 08 NOV 2018 Q
SFLC Std Spec
General Requirements 0000 2022 Q
SFLC Std Spec
Shipboard Electrical Cable Test
3041 2022 Q
SFLC Std Spec
Shipboard Electrical Cable Removal, Relocation, Splice, Repair, and Installation
3042 2022 Q
SFLC Std Spec
Requirements for Preservation of Ship Structures
6310 2022 Q
*ACTION TAKEN CODES (more than one code may be used) R – Revised as a result of EC Q – Required to complete EC A – Added as a result of EC D – Deleted (upon completion of EC)
7. HOW WORK IS ACCOMPLISHED
a. PRELIMINARY STEPS
(1) Complete Red Danger Tags IAW COMDTINST 9077.1 (series).
(2) Have a marine chemist certify all affected spaces are “Safe for Hot Work”, (Refer to COMDTINST M9000.6 (series) and NSTM Chapter 074, Vol 3).
(a) Maintain the gas free certification by a competent person throughout the duration of this installation, (Refer to COMDTINST M9000.6 (series) and NSTM Chapter 074, Vol 3).
https://uscg.sharepoint-mil.us/sites/electricians-mate/LOCKOUT%20%20TAGOUT/Equipment%20Lockout%20Tags%20Plus%20Instruction,%20COMDTINST%209077.1D.pdf https://uscg.sharepoint-mil.us/sites/erats_spo/EM/Shared%20Documents/Forms/AllItems.aspx?id=%2Fsites%2Ferats_spo%2FEM%2FShared%20Documents%2FOld%20References%202023%2Fas_Naval%20Engineering%20Manual%20CIM%209000%2E6G%2Epdf&parent=%2Fsites%2Ferats_spo%2FEM%2FShared%20Documents%2FOld%20References%202023 https://uscg.sharepoint-mil.us/sites/erats_spo/EM/Shared%20Documents/Forms/AllItems.aspx?id=%2Fsites%2Ferats_spo%2FEM%2FShared%20Documents%2FOld%20References%202023%2Fas_Naval%20Engineering%20Manual%20CIM%209000%2E6G%2Epdf&parent=%2Fsites%2Ferats_spo%2FEM%2FShared%20Documents%2FOld%20References%202023 https://uscg.sharepoint-mil.us/sites/erats_spo/EM/Shared%20Documents/Forms/AllItems.aspx?id=%2Fsites%2Ferats_spo%2FEM%2FShared%20Documents%2FOld%20References%202023%2Fas_Naval%20Engineering%20Manual%20CIM%209000%2E6G%2Epdf&parent=%2Fsites%2Ferats_spo%2FEM%2FShared%20Documents%2FOld%20References%202023
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
(3) Provide protection to all vessel components, spaces, equipment, and interferences, (Refer to SFLC Std Spec 0000, Enclosure 1).
b. REMOVAL
(1) Remove the following Siemens / Pyrotronics system III components associated with the existing fire detection system equipment, (Refer to Coast Guard Dwgs 901-WMEC-436-003, 901-WMEC-320-035, 905-WMEC-320-014, SFLC Std Spec 3041, SFLC Std Spec 3042, SFLC Std Spec 0000, TP 3365B- 436, and Enclosure 1):
(a) Display Panel, P/N: PMD-45.
(b) PLC Box, P/N: A-181610CHQRFG.
(c) Annunciator, P/N: A-20H1606GQRLP.
(d) Annunciator, P/N: A-12106CHQRFG.
(e) Annunciator, P/N: A16128JFGQRR.
(f) Base, Detector, P/N: DB-11.
(g) Detector, Flame Infrared, P/N: 516.037.004.
(h) Detector, Heat, P/N: DT-200WP.
(i) Fire Detector, P/N: S54372-F1-A1.
(j) Fuse Cartridge, P/N: ABC15-250V.
(k) Control, Alarm, P/N: AE-30U.
(l) Fuse, Cartridge, P/N: AGC-2.
(m) Circuit Card Assembly, P/N: AS-BDAP-204.
(n) Relay, Solid State, P/N: AS-BDAP-212.
(o) Circuit Card Assembly, P/N: AS-BDEP-216.
(p) Circuit Card Assembly, P/N: AS-BDEP-217.
(q) Power Supply, Assembly, P/N: AS-P120-000.
(r) Battery Charger, P/N: BC-35.
(s) Annunciator, P/N: BBT-120T-A.
(t) Battery, Storage, P/N: BT-34.
(u) Control Unit, P/N: CP-35.
(v) Base, Detector, P/N: DB-3S.
(w) Smoke Detector, Ionization, P/N: DI-3.
(x) Sensor, Opaque Particle, P/N: DI-3IS.
(y) Lamp, Incandescent, P/N: DL1CB006.
(z) Detector, Heat, P/N: DT-200WP.
(aa) Fuse, Cartridge, P/N: GDB-500MA.
(bb) Fuse, Cartridge, P/N: GDC800MA.
(cc) Bell, Electrical, P/N: MBDC-10.
https://www.dcms.uscg.mil/Portals/10/CG-4/documents/SFLC/StandardSpec2022/SFLC-Std-Spec-0000-(2022).pdf?ver=jYndFEwQDbwd0xBee3-2gw%3d%3d https://www.dcms.uscg.mil/Portals/10/CG-4/documents/SFLC/StandardSpec2022/SFLC-Std-Spec-3041-(2022).pdf?ver=9OJDyhBvy49IOKVi1_c0dw%3d%3d https://www.dcms.uscg.mil/Portals/10/CG-4/documents/SFLC/StandardSpec2022/SFLC-Std-Spec-3042-(2022).pdf?ver=Nwz53ns7j5Js20eCq9Q6cw%3d%3d https://www.dcms.uscg.mil/Portals/10/CG-4/documents/SFLC/StandardSpec2022/SFLC-Std-Spec-0000-(2022).pdf?ver=jYndFEwQDbwd0xBee3-2gw%3d%3d
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
(dd) Module, Meter, Battery, P/N: MM-35.
(ee) Circuit Card Assembly, P/N: NW-BP-85-000.
(ff) Controller, Logic, P/N: PC-A984-145.
(gg) Alarm, Smoke, Automatic, P/N: PE-11.
(hh) Sensing Element, Fire, P/N: PE-3.
(ii) Semiconductor Device Assembly, P/N: PM-32.
(jj) Power Supply, P/N: PS-35.
(kk) Detector, Flame Infrared, P/N: S121.
(ll) Detector, Light Intensity, P/N: S54372-F1-A1.
(mm) Module, Relay, P/N: SR-32.
(nn) Module, Time Limit, P/N: TL-30U.
(oo) Switch, P/N: ZA2-BD2.
(pp) Circuit Card Assembly, P/N: ZS-30.
(qq) Module, Alarm, Smoke, P/N: ZU-35TS.
(rr) Resistor, Fixed, Comp, P/N: 11204-074.
(ss) Circuit Card Assembly, P/N: 170AAI52040.
(tt) Modbus Module, P/N: 170BDI54250.
(uu) Circuit Card Assembly, P/N: 170NEF11021.
(vv) Power Supply, P/N: 2426418.00.
(ww) Connector, Plug, Elec, P/N: 206060-1.
(xx) Coupling Ring, Size 11, P/N: 213811-1.
(yy) Sensor, Opaque, Particle, P/N: 500-025402.
(zz) Sensor, Opaque, Particle, P/N: 500-083263.
(aaa) Housing, Air Duct, P/N: 500-86495.
(bbb) Sensor, Opaque, Particle, P/N: 500-094150.
(ccc) Fire Detector Base, P/N: 500-094151.
(ddd) Plate, Mounting, P/N: 500-094187.
(eee) Sensing Element, Fire Detector, P/N: 516.037.004.
(fff) Contact, Electrical, P/N: 66181-1.
(ggg) Operator Interface, PMD 475, P/N: 76737-16.
(hhh) Keyboard Expander, P/N: 76801.
c. INSTALLATION
(1) Install Control System, Fire Suppression, P/N: Q2401251-8, (Refer to Coast Guard Dwg 901 WMEC 436-006, TP ME-H4-0001-V0-436, and Enclosure 1).
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
d. FINAL STEPS
(1) Remove Red Danger Tags IAW COMDTINST 9077.1 (series).
(2) Reenergized all circuits following completion of work.
** QA (1) REQUIRED AT THIS POINT **
(3) Test the Control System, Fire Suppression, P/N: Q2401251-8, (Refer to Enclosure 1).
WARNING
AVOID EYE CONTACT, SKIN CONTACT, AND IN-
HALATION WITH PAINT. KEEP AWAY FROM ALL
SOURCES OF IGNITION. USE IN A WELL VENTILAT-
ED AREA. WASH EXPOSED SKIN THOROUGHLY
AFTER HANDLING. FAILURE TO COMPLY MAY RE-
SULT IN PERSONAL INJURY.
(4) Paint all new and disturbed surfaces, (Refer to SFLC Std Spec 6310).
8. SUPPLEMENTAL INFORMATION
a. DESIGN INTERFACE
The Consilium Salwico fire detection system installed is mounted on the existing foundation. The new Consilium Salwico fire detection system interfaces with the “Zone Descriptions” as shown on Coast Guard Dwg 901-WMEC-436-003.
b. WEIGHT AND MOMENT INFORMATION
This EC presents Negligible change in weight and Center-of-Gravity as shown below. Compensation is NOT required.
Total weight removed: 1069.6 pounds at:
18.00 ft above the baseline
0.77 ft of centerline (+stbd,-port)
139.63 ft aft of FP
Total weight added: 1406.2 pounds at:
18.00 ft above baseline
0.32 ft of centerline (+stbd, -port)
136.92 ft aft of FP
Net change in:
Weight: +336.6 pounds VCG: +0.000 ft (+higher, -lower) TCG: 0.000 ft (+stbd, -port) LCG: 0.000 ft (+aft, -fwd) List: 0.00 deg (+stbd, -port) Trim: 0.00 ft (+by stern, -by bow)
Resulting Centers of Gravity:
New VCG: 17.000 ft above baseline New TCG: 0.000 ft of centerline (+stbd, -port) New LCG: 133.200 ft aft of FP https://uscg.sharepoint-mil.us/sites/electricians-mate/LOCKOUT%20%20TAGOUT/Equipment%20Lockout%20Tags%20Plus%20Instruction,%20COMDTINST%209077.1D.pdf https://www.dcms.uscg.mil/Portals/10/CG-4/documents/SFLC/StandardSpec2022/SFLC-Std-Spec-6310-(2022).pdf?ver=79FPuot6fsxS2yVAAL4r0w%3d%3d
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
c. TRAINING AND TRAINING SUPPORT
Required crew training is provided by the Consilium representative, and familiarize themselves with the applicable Tech Pub.
d. COMPUTER RESOURCES SUPPORT
None.
e. PACKAGING, HANDLING, STORAGE AND TRANSPORTATION
None.
f. FACILITIES
None.
9. RECORDS
a. ACTION REQUIRED ON MAINTENANCE RECORDS
(1) TCTO Sign-Off Sheet Submission
Upon completion of this EC, the unit must complete the applicable portion of the TCTO sign-off sheet:
Asset Number, Operating Facility (OPFAC), Technician’s Signature, and Technician’s ID blocks, and any desired remarks. Additional remarks may be made on the reverse side of the TCTO sign-off sheet.
The unit must then submit via e-mail the completed and signed TCTO sign-off sheet to:
USCG Surface Forces Logistics Center (MECPL-ENG-SES) E-mail: Stephanie.l.eldrege@uscg.mil or Julius.k.toida@uscg.mil
(2) Maintenance Standards in FLS
Maintenance Standards/Maintenance Items (MI) have been created in Fleet Logistics System (FLS) to schedule and track completion of this EC aboard each asset and must be marked as “Completed” for each asset as the EC is accomplished. The configuration tree within FLS will automatically be updated upon moving the MI status to “Completed”.
Maintenance Standards have been created in FLS for each applicable maintenance procedure card.
Once the configuration tree within FLS is updated maintenance tasks will populate the maintenance due list in FLS and Fleet Logistics System - Mobile Asset Manager (FLS-MAM), (Refer to Table 9-1).
(3) SFLC Form 47 Documentation
The installing activity (IA) shall complete the Standardized Configuration Change Form (SFLC-ESD-47) and Standard Configuration Continuation Page (SFLC-ESD-48), listing all equipment that was removed or installed and submit via E-mail to: D05-DG-SFLC-ESD-SSB-CMS-CDMM-MCPL@USCG.MIL and a copy to the Point-Of-Contact (POC) identified in Section 3.
(4) Warranty Information
12 months after date of installation and no more than 18 months after delivery.
mailto:Stephanie.l.eldrege%40uscg.mil?subject= mailto:Julius.k.toida%40uscg.mil?subject= mailto:D05-DG-SFLC-ESD-SSB-CMS-CDMM-MCPL%40USCG.MIL?subject=
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
b. ACTION REQUIRED ON SUPPLY RECORDS
None.
(1) APL(s) Affected
Upon completion of this EC, perform the appropriate action to the APL(s) listed in Table 9-1.
Table 9-1. MODIFICATION TO APL(S)
APL NO ACTION * QTY HSC FUNCTIONAL DESCRIPTION
50053510B2 D 1 ea 43600 Panel, Alarm (Detection, Fire & Smoke)
503EGT00A2 A 1 ea 43600 Panel, Alarm (Detection, Fire & Smoke)
Actions are identified by the following:
A – Add
D – Delete
M – Modify
(2) Personal Property Records
None.
TABLE 9-2. MPC TO CONFIGURATION ITEM FUNCTIONAL DESCRIPTION GUIDANCE FOR SCHEDULING
MPC NUMBER MAINTENANCE STANDARD
TITLE WORK CENTER RESPONSIBLE
LEVEL CIFD
E-C-18279 FIRE DETECTOR SENSOR,
REPLACE EEM O MONITOR-SVC
E-M-18278 FIRE DETECTOR SYSTEM,
INSP/CHK EEM O MONITOR-SVC
E-A-18277 FIRE DETECTOR SYSTEM,
INSP/CLN EEM O MONITOR-SVC
TCTO_TN3060_43600_KFM_0725_270
WORK ITEM 1: Fire and Smoke Detection System, Renew APM: Do not edit any part of the Work Item Title.
1. SCOPE
1.1 Intent. This work item describes the requirements for the Contractor to replace the existing Siemens/Pyrotronic III system to include all ancillary components with the Consilium Salwico Fire detection system.
1.2 Government-furnished property.
APM: Validate all GFP data. If the Spec Package's Consolidated List of GFP is changed, ensure it is changed in the source WI and GFP style is applied.
MTI ITEM DESCRIPTION NSN/PN QTY ESTIMATED
COST
($/UNIT)
N Consilium Salwico Fire detection system installation
Kit
NSN: 5998-01-F25-7076
PN: Q2401251-8
1 kt. 77,550.00
2. REFERENCES
APM: Ensure all references are latest version in CG-LIMS. If editing a WI's References, change the same ref. in the Spec's Consolidated List of References and contact the SES section chief to change the source WI. Ensure any MS Word “Comments” and Tracked Changes are removed before uploading the Spec package or delivering to CPD.
COAST GUARD DRAWINGS
Developer: Select applicable references for A or B class and remove the others.
FOR A CLASS CUTTERS
Coast Guard Drawing 901 WMEC 320-035, Rev AV, As-Built Electrical One-Line Diagram Coast Guard Drawing 901 WMEC 436-003, Rev W, Fire & Smoke Detection & Quarterdeck
Monitoring System Blk & IWD Coast Guard Drawing 901 WMEC 436-006, Rev -, Fire and Smoke Detection System Upgrade –
Ripout and Installation
FOR B CLASS CUTTERS
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
TCTO WMEC-270 TN3060 Enclosure 1
Coast Guard Drawing 901 WMEC 436-003, Rev W, Fire & Smoke Detection & Quarterdeck Monitoring System Blk & IWD
Coast Guard Drawing 901 WMEC 436-006, Rev -, Fire and Smoke Detection System Upgrade – Ripout and Installation
Coast Guard Drawing 905 WMEC 320-014, Rev AR, Electrical One-Line Diagram
COAST GUARD PUBLICATIONS
Coast Guard Technical Publication (TP) 3365B, SWBS 436, Oct 2000, Fire and Smoke Detection
System Coast Guard Technical Publication (TP) ME-H4-0001-V0, SWBS 436, April 2025, Fire
Detection System – Salwico Cruise – Quick & User Guide, Service, Maint & Install Manual Surface Forces Logistics Center Standard Specification 0000 (SFLC Std Spec 0000), 2022, General Requirements Surface Forces Logistics Center Standard Specification 3041 (SFLC Std Spec 3041), 2022, Shipboard Electrical Cable Test Surface Forces Logistics Center Standard Specification 3042 (SFLC Std Spec 3042), 2022, Shipboard Electrical Cable Removal, Relocation, Splice, Repair, and Installation Surface Forces Logistics Center Standard Specification 6310 (SFLC Std Spec 6310), 2022, Requirements for Preservation of Ship Structures
OTHER REFERENCES
MIL-DTL-24643B, August 2002, Cables, Electric, Low Smoke Halogen-Free, for Shipboard Use
General Specification MIL-STD-2003B, October 2020, Department of Defense Standard Practice: Electric Plant
Installation Standard Methods for Surface and Submarines 46 CFR 113.10, July 2024, Fire and Amoke Detecting and Alarm Systems 46 CFR 161.002, July 2024, Fire Detection System
3. REQUIREMENTS
3.1 General.
3.1.1 CIR.
None.
3.1.2 Tech Rep. The Contractor must provide the services of an OEM authorized/ licensed Tech Rep for the Consilium Salwico fire detection system to accomplish the following on site:
• Provide manufacturer's proprietary system/ equipment information, software, and tools.
• Assist with and ensure compliance with manufacturer's procedures and standards during disassembly, inspection, repair, modification, calibration, and reassembly of the equipment/system.
3.1.2.1 Ensure the Tech Rep is an OEM Certified Representative for the system/equipment stated above and demonstrated on their résumé.
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
3.1.2.2 Submit the name and résumé of the Tech Rep to the COR at the Arrival Conference.
3.1.2.3 Training. The Tech Rep must provide training documents on how to operate and troubleshoot newly installed Consilium Salwico system to the cutter due upon completion of installation and testing of system.
3.1.2.3.1 Provide onsite training, which must include the following
• Review of documentation
• Safety
• Review of start-up and operation procedures
• Emergency procedures
• Troubleshooting
3.1.3 Protective measures. The Contractor must furnish and install all protective measures in accordance with SFLC Std Spec 0000, paragraph 3.3.3 (Vessel component, space, and equipment protection).
3.1.4 Interferences. The Contractor must handle all interferences in accordance with SFLC Std Spec 0000, (Interferences). Known interferences include, but are not limited to the following:
• Sheathing
• Bulkhead insulation
• Cable ways
3.2 Electrical work. The Contractor must accomplish all electrical work in accordance with SFLC Std Spec 3042, and test cables in accordance with SFLC Std Spec 3041. Utilize the existing wire ways for new cable runs as much as possible.
NOTE
Coast Guard personnel will operate all shipboard machinery and equipment.
3.3 Operational test, initial. Prior to commencement of work, the Contractor must witness Coast Guard personnel perform an initial operational test of all items or shipboard devices to be disturbed, used, repaired, or altered, to demonstrate existing operational condition. Submit a CFR.
3.4 Temporary fire and smoke detection system. The Contractor must provide a temporary fire detection system or leave the existing system in place and functional while installing the new fire and smoke detection system.
3.5 Fire and Smoke Detection system removal. The Contractor must accomplish the following
Select applicable drawing below for A or B Class and delete other.
3.5.1 Remove all existing Siemens/Pyrotronics system III components associated with the existing fire detection system as shown on Coast Guard drawing 901 WMEC 436-003 and using Coast Guard drawing 901 WMEC 320-035 FOR A CLASS CUTTERS 905 WMEC 320-014 FOR B CLASS CUTTERS, as guidance.
3.5.1.1 Contractor must retain the following fire detection system components and package and ship to the address indicated below. Contractor must notify COR when shipped:
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
NOTE
COR will notify SFLC Supply item manager that components below are being shipped to warehouse and request a due in for the material.
TABLE 1 – SIEMENS/PYROTRONIC SYSTEM III PARTS RETAINED
COMPONENT NSN QTY
Display Panel PMD-45 NSN: 5998-01-453-4620 4 PLC box located in ECC (contains: PLC, I/O cards, Power
Supply) NSN: 1265-01-F25-7046 1
Aft Vestibule Network Connection Box NSN: 6350-01-F25-7045 1 Aft Vestibule Temperature Box NSN: 6350-01-F25-7042 1
Quarterdeck Remote Annunciator NSN: 6350-01-F25-7041 1
Commander U.S. Coast Guard Surface Forces Logistics Center
2401 Hawkins Point Rd Building 88
Baltimore, MD 21226-5000
ATTN: Receiving
3.5.2 Contractor must remove all existing cables associated with the Siemens/Pyrotronics system III in accordance with SFLC Std Spec 3042.
3.5.3 The Contractor must dispose of all components and cabling not listed in paragraph 3.5.1.1 in accordance with Federal, State and local regulations.
3.6 Fire and Smoke Detection system installation. The Contractor must install the government furnished Consilium Salwico fire detection system as shown on Coast Guard drawing 901 WMEC 436-006 and in accordance with MIL-STD-2003B, 46 CFR 113.10 and 46 CFR 161.002.
3.6.1 The Contractor must run new electrical cabling to the newly installed Consilium Salwico fire detection system and all its ancillary components as shown on Coast Guard Drawing 901 WMEC 436- 006 and in accordance with SFLC Std Spec 3041, SFLC Std Spec 3042 and MIL-DTL-24643B.
3.6.2 The Contractor must turn over all spare parts included in the government furnished installation kit to the cutter to retain as on board spare parts.
3.7 Operational test, post repairs. After completion of work, the Contractor must thoroughly test, in the presence of the Coast Guard Inspector and demonstrate all items or shipboard devices that have been disturbed, used, repaired, altered, or installed to be in satisfactory operating condition. Submit a CFR.
3.7.1 The Contractor must test the newly installed Consilium Salwico fire detection system in accordance with paragraph 4.1 Fire and smoke detection test procedures.
3.8 Touch-up preservation. The Contractor must prepare and coat all new and disturbed surfaces to match existing adjacent surfaces in accordance with SFLC Std Spec 6310, (Touch-ups and minor coating repairs.)
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
3.9 Boundary test, generic. The Contractor must verify the integrity of all boundaries affected by this work item using one of the methods described in SFLC Std Spec 0740, Appendix C. Submit a CFR.
4. NOTES
4.1 Fire and smoke detection system test procedures. The Contractor must accomplish the following test procedure.
4.1.1 Test each detector listed in the Data Sheet. Contractor must submit a CFR for any discrepancies in the Data Sheet (incorrect locations, incorrect detector type in the space, etc) and provide a “red-line” markup of the corrected Data Sheet. Do not record “UNSAT” data. Any discrepancies must be corrected and retested prior to signing off as “SAT”.
• An ionization or photoelectric detector may be activated by blowing smoke into it or introducing an acceptable aerosol slightly away from the chamber.
• A thermal detector may be activated by an electric heat gun.
• A flame detector may be activated by holding the flame of a cigarette lighter slightly below or in front of the lens or by producing and infrared light from an IR source into the detector lens.
4.1.2 To test the system, activate a detector or manual pull station. Record each detector and device tested on the attached Data Sheets. Verify the following:
• All audible devices sound and can be silenced from remote annunciators and from the main fire alarm panel.
• System alarm lamp illuminates.
• Proper zone lamp illuminates at the zone module and the remote annunciators.
• Fire Detection System General Alarm activates.
4.1.3 Acknowledge alarm.
• Acknowledge the alarm at the annunciator (without silencing the alarm at the main fire panel).
• Acknowledge alarm at the alarm panel.
4.1.4 Reset the main fire alarm panel.
• Allow time for the smoke to clear out of the detector sensor or for the thermal fire detector to cool down.
• Reset alarm panel.
• Verify on the remote annunciator that the corresponding red LED is not illuminated over the zone for the zone detector sensor being tested.
• Verify on the main fire alarm panel that the corresponding zone is not illuminated.
4.1.5 Record results in Data Sheets below.
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Fire Detection and Alarm System Test Data Sheet
Zone 1
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ar m
Audible alarm (with strobe)
Sm ok e De te ct or
IR
F la m e De te
Th er m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-
-0
An nu nc ia to r, Q ua rt er de ck nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-
-L
Pa ss ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o nl y)
En gi ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
JP
-5
P um p Ro om
Example X X J. Smith 2/16/24
Pilothouse 02-48-0-C X
Passage 02-63-2-L X
XO Stateroom 01-47-2-L X
CO Stateroom 01-47-5-L X
Passage 01-52-0-L X X
P-Way 01-52-0-L in Exh Vent
E02-58-2 X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
EO Stateroom 01-58-2-L X
Ward Rm Stateroom 01-68-0-L
X
Ward Rm Stateroom
01-68-3-L
X
Ward Rm Stateroom
01-68-4-L
X
A-Class Only:
Passage
01-68-01-L
(x2)
X
X
B-Class Only:
Passage
01-68-01-L
X X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
Passenger Stateroom
01-82-0-L
X
Ward Rm Stateroom
01-84-2-L
X
Ward Rm Stateroom
01-85-0-L
X
Crew Locker Rm
1-58-1-L
X
Engr Office/DC Central
1-73-1-Q
X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
A-Class Only:
Passage
1-47-0-L
X
B-Class Only:
Passage
1-47-0-L
X
A-Class only: P- Way 1-47-0-L in
Exh Vnt E02-56-2
X
A-Class only: P- Way 1-47-0-L in
Exh Vnt E02-58-2
X
B-Class only: P- Way 1-47-0-L in
Exh Vnt E02-57-2
X
B-Class only: Lkr 1-56-1-Q in Exh Vent E02-53-1
X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
Crew Berthing
1-61-2-L
X
Passage
2-56-0-L (fwd)
X X
A-Class only: P- Way 2-56-0-L in
Exh Vnt E02-58-2
X
B-Class only: P- Way 2-56-0-L in
Exh Vnt E02-57-2
X
IC Room
2-47-1-C
X
Crew Berthing
2-47-0-L
X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
Crew Locker Rm
2-59-4-L
X
Crew Lounge
2-72-2-L
X
A-Class Only:
Passage
2-56-0-L (aft)
X X
B-Class Only:
Passage
2-56-0-L (aft)
X
Crew Locker Rm
2-64-1-L
X
Crew Berthing
2-66-1-L
X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
This Page is left blank Intentionally
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Zone 2
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
Passage 1-186-01-L X
CPO Stateroom 1-199-0-L X
CPO Stateroom 1-199-2-L X
Eng Stores 1-186-2-A X
CPO Stateroom 1-177-0-L X
CPO Stateroom 1-165-4-L X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
CPO Stateroom 1-165-2-L X
Passage 1-165-0-L X X
CPO Lounge
1-165-3-L
X
Dispensary
1-179-1-L
X
Crew Lounge
2-186-1-L
X
Crew Locker Rm
2-194-0-L
X
Crew Berthing
2-186-4-L
X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
Crew Lounge
2-165-2-L
X
Crew Locker Rm
2-175-0-L
X
Crew Berthing
2-165-3-L
X
DESTRUCTION NOTICE- Destroy by any method that will prevent disclosure of contents or reconstruction of the document
Zone 3
Location
Fire Detection/Alarm System Appliance being tested
Alarm Type ( for satisfactory alarm operation and proper Zone indicated on all annunciators)
Signature and date for SAT appliance operation
Be ll
Au di bl e
Al ok e De te la m e De te m al
D et ec to r
Pu ll
St at io n
Re m ot e
Al ar m L am p
An nu nc ia to r, Pi lo t H ou se
2-nc ia to r, Q ua rt er nc ia to r, He lo
H an ga r 0
1-
7- 0-
L
An nu nc ia to r, Ve st ib ul e
-4 7-
1- L
An nu nc ia to r, Ve st ib ul e 1-
7-
1- L
Pa ss ag e
-6
8-ag e
1-ag e
1-
5- 0-
L
Pa ss ag e
2-ag e
2-
0- 0-
L
Au x
M ac hi n
Sp ac es (w ith B el l, B- Cl as s o ne R oo m
(Q ty
)(w ith B el l, B- Cl as s o
P um p
Flammable Liquid Stores
1-J-0-KL