AMENDMENT 3 - ADDITIONAL QUESTIONS AND GOVT RESPONSE.pdf
PDF 251 KB Posted
- Attached to
- DHS FLETC GLYNCO - ATF COMPLEX
- Solicitation number
- 70LGLY26QSSB00067
About this file
This document comprises government responses to contractor questions regarding the ATF Complex project and memoranda providing fire protection classifications for two proposed pre-engineered metal buildings (PEMBs).
500-Gallon Drainage Tank and Insulation Requirements: The government clarified that gutters and downspouts will not drain to the 500-gallon tank, which serves only the Simulator Building. The contractor must supply and install a new 500-gallon tank with a gravel bottom for subsurface drainage, indicating below-grade installation. No specific tank make or model is mandated. Regarding insulation, the contractor is required to use closed-cell spray foam as specified in the Performance Work Statement, with no alternative methods approved despite potential warranty concerns.
Fire Protection Classifications: Two separate fire systems memoranda from Ryan Dunnagan, Fire Systems SME (dated 8-24-2026), establish occupancy classifications and fire protection requirements for the ATF Complex facilities. The 3,500 square foot Warehouse PEMB (approximately 50 feet by 70 feet) is classified as Group S-1 (Moderate-Hazard Storage) for temporary equipment storage. Based on its size, configuration, and stated use, automatic sprinkler protection is not required by default, though fire alarm and other protection may be required if the stored contents, storage height, commodity classification, or hazardous material quantities change. The 4,500 square foot Simulator Facility PEMB (50 feet by 90 feet) is classified as Group B (Business) with an estimated occupant load of 30 persons. This facility does not require automatic sprinkler protection or manual fire alarm systems by default under the 2018 International Building Code, provided no hazardous materials, special storage, or mixed occupancy conditions are present. Both determinations are contingent on maintaining the stated uses and require reevaluation if circumstances change.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATF COMPLEX – GOV’T RESPONSE TO QUESTIONS
1. 500-Gallon Drainage Tank
Contractor’s Questions:
1. “Please confirm that gutters/downspouts for each building will need to drain into the tank.”
2. “Will one tank service both buildings?”
3. “Please confirm if this is shown correctly, or a new tank will be required.”
4. “Are the contractors required to supply the tank, if yes what make/model?”
5. “Will this tank be above ground or below grade?”
GOV’T RESPONSE:
1. Gutters/Downspouts: NO – WILL NOT DRAIN TO TANK
2. One Tank for Both Buildings: NO – only simulator building has water. The PWS only mentions the tank in the section for the Simulator Building (4.3.9), implying it serves that building alone.
3. New or Existing Tank: Section 4.3.9 requires the contractor to “install a 500-gallon tank,” indicating it is a new installation.
4. Contractor to Supply: Answered. The requirement to “install” the tank confirms the contractor must supply it. No make or model is specified.
5. Above or Below Grade: Answered. The requirement for the tank to have a “gravel bottom to facilitate subsurface drainage” strongly implies it will be installed below grade.
2. Insulation Warranty
Contractor’s Question:
“Please confirm that spray foam applied directly to the wall panels will be acceptable, acknowledging the potential warranty issue related to this installation. Otherwise, please provide an alternate method of insulation, for example Insulated Metal Panels (IMP).”
GOV’T RESPOSNE: Based on the PWS, the contractor is required to use closed-cell spray foam.
3. Fire & Life Safety Systems
Contractor’s Question:
“Please confirm Fire Sprinkler Protection, emergency exit signs, fire alarm, etc. will not be required for these PEMB’s.”
GOV’T RESPONSE –
AMENDMENT #3
MEMORANDUM
TO: DCB
FROM: Ryan Dunnagan, Fire Systems SME
SUBJECT:
DATE: 8-24-2026
Purpose:
3,500 square foot Warehouse pre-engineered metal building (PEMB)
Fire Suppression System Requirements:
Group: S-1, Moderate-Hazard Storage
-2 low-
-1 is
Code Reference: -1 Mandate:
- 12,000 square feet;
24,000 square feet;
5,000 square feet;
Conclusion: 50 feet by 70 feet
3,500 square feet -story not -not -not required -1 storage, Fire Alarm System Requirements:
1. Manual Fire Alarm System:
Code Reference:
Mandate: -
Recommendation:
Conditions and Limitations:
again
SME Conclusion:
Group S-1, Moderate-Hazard Storage -story
3,500 square foot not required
RYAN N
DUNNAGAN
Digitally signed by RYAN N
Date: 2026.08.24 13:34:58 -04'00'
MEMORANDUM
TO: DCB
FROM: Ryan Dunnagan, Fire Systems SME
SUBJECT:
DATE: 8-24-2026
Purpose:
4,500 square foot Simulator Facility 50 ft x 90 ft pre-engineered metal building (PEMB)
Fire Suppression System Requirements:
Occupancy Classi cation:
Group: B, Business
Section 304, Business Group B training and skill development not within a school or academic program
Group B, Business a ard Classi cation for Sprinkler Design:
Category: Not applicable unless sprinkler protection is required or voluntarily provided
3. Sprinkler System Requirement:
Code Reference:
Mandate:
- IBC
Section 903.2.2 ambulatory care facilities criteria;
Conclusion: 50 feet by 90 feet 4,500 square feet -story not required
Fire Alarm System Requirements:
1. Manual Fire Alarm System:
Code Reference:
Mandate:
500 or more;
more than 100 persons above or below the lowest level of exit discharge;
Occupant Load Evaluation: 4,500 square feet 150 gross square feet per occupant
4,500 square feet ÷ 150 gross square feet per occupant = 30 occupants
30 occupants 500 occupant
100 occupants above or below the lowest level of exit discharge
Recommendation:
Conditions and Limitations:
SME Conclusion:
Group B, Business, in IBC Section 304 -
30 occupants, 150 gross square feet per occupant 2018 IBC Section 907.2.2 not required by default or
RYAN N
DUNNAGAN
Digitally signed by RYAN N
Date: 2026.08.24 13:57:54 -04'00'
| CONTRACTOR QUESTIONS -- GOV'T RESPONSE |
| Fire Suppression Evaluation_ATF Warehouse--RND |
| Fire Suppression Evaluation_ATF_Simulator--RND |
File details come from the government source that posted it. Updated .