7-Attachment 7- Project Drawings.pdf

PDF 13 MB Posted

Attached to
Ft. Worth 1st Floor Restroom Renovation
Solicitation number
3202500095
Issued by
Tarrant County, Texas

About this file

This is a set of project drawings for the City of Fort Worth's 1st Floor Restroom Renovation project located at 307 W 13th St., Fort Worth, TX 76102. The renovation scope includes mechanical, plumbing, and electrical work to bring the restrooms into compliance with ADA code requirements and low water consumption standards for the State of Texas. The mechanical work encompasses HVAC demolition and installation, including the removal of existing ductwork and air devices with subsequent installation of new supply diffusers and exhaust grilles sized between 6 inches and 24 inches, with a system rebalance target of 940 CFM maximum. Plumbing work involves the installation of new water closets (WC-1), wall-hung urinals (UR-1 and UR-2) with floor-mounted carriers, accessible lavatories (L-1), sinks (S-1 and S-2), floor drains (FD-1), and a bottle filler station with remote chiller. Electrical work includes demolition of existing fixtures and installation of new LED lighting fixtures (types A2, A4, C, and D), occupancy sensors, lighting control systems with 0-10V dimming capability, GFI-protected circuits for appliances, and fire alarm components.

The project drawings indicate that all fixtures must comply with accessibility standards and include provisions for new water supply and waste piping with proper insulation, recirculated hot water systems to meet energy code requirements, and coordinated installations between trades. The design includes detailed schedules for HVAC components with CFM ratings, plumbing fixtures with specific model numbers and specifications from manufacturers such as American Standard, Delta, Sloan, and Halsey Taylor, and electrical fixtures from Lithonia and Finelite. The contractor is required to perform field verification of existing utilities, coordinate final lengths and placements with the architect, and submit approved plans in accordance with applicable state codes. The project documents are prepared by BHB Inc., a TBPELS-certified firm, with project number 2025.011.001 and dated January 5, 2026.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FAN ROOM

HALL

HALL

JANITOR

WOMEN

LOUNGE

CORRIDOR

VESTIBULE

MEN

ELECTRICAL

OPEN OFFICE BREAK ROOM

OPEN OFFICE

14/10 EXH.

14/10 EXH.

(E) 14/12 EXHAUST

DUCT UP IN CHASE14/10 EXH.

T

EXISTING

AC-1

18/610/6 12/6

6/6

24/18 OA

46/30

24/16 EXH. EXH.

FAN

RR

RR

EXISTING

VAV-1-1

12"Ø10"Ø

Fort Worth 1st Floor

Restrooms Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

1ST FLOOR - MECHANICAL

DEMOLITION PLAN

M1.0

1ST FLOOR - MECHANICAL DEMOLITION PLAN

0 4' 8' 12'1

1. REMOVE EXISTING AIR DEVICE AND BRANCH DUCT AS INDICATED.

2. REMOVE EXISTING DUCTWORK AND CAP AT MAIN.

NOTES BY SYMBOL: " " #

1. REFER TO ARCHITECTURAL DOCUMENTS FOR ABATEMENT REQUIREMENTS. ALL DUCTWORK

INSULATION REMOVED DURING ABATEMENT SHALL BE REPLACED UNDER THIS CONTRACT.

VERIFY DUCT SIZES AND LENGTHS IN FIELD.

2. CONTRACTOR SHALL TEST AND DOCUMENT AIRFLOW AT EACH EXISTING SUPPLY AND

EXHAUST AIR DEVICE ASSOCIATED WITH THE REMODEL WORK PRIOR TO ANY DEMOLITION.

REPORT SHALL BE ISSUED TO THE ARCHITECT/ENGINEER PRIOR TO ANY DEMOLITION WORK.

GENERAL NOTES:

HVAC LEGEND

EXISTING (E)

DEMOLITION

NEW DUCTWORK

SUPPLY AIR DIFFUSER

RETURN OR EXHAUST AIR GRILLE

ROUND FLEXIBLE DUCTWORK

VOLUME DAMPER

CONNECT TO EXISTING

DIFFUSER OR GRILLE DESIGNATION

EX: EXISTINGTYPE CFM

A 150

01/05/2026

14/10 EXH.

14/10 EXH.

(E) 14/12 EXHAUST

DUCT UP IN CHASE14/10 EXH.

T

EXISTING

AC-1

18/610/6 12/6

6/6

24/18 OA

46/30

24/16 EXH.

EXIST.

EXH.

FAN

EXISTING

VAV-1-1

12"Ø10"Ø

EX 100 EX 100

S1 75

S2 200

S2 200

S1 50

S1 50

EX 90

S1 75

E1 300

E1 300

REBALANCE FOR

940 CFM MAX.

/14

8"Ø

6"Ø

10"Ø

6"Ø

8"Ø

10"Ø

8"Ø

E2 100

E2 100

Restrooms Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

1ST FLOOR -

MECHANICAL PLAN

M2.0

1ST FLOOR - MECHANICAL PLAN

0 4' 8' 12'1

1. UTILIZE EXISTING TAP AND EXTEND 6"Ø SUPPLY DUCT TO NEW AIR DEVICE.

NOTES BY SYMBOL: " " #

1. CONTRACTOR SHALL REPAIR OR REPLACE ANY DAMAGED INSULATION FOR EXISTING

SUPPLY DUCTWORK DOWNSTREAM OF (E) VAV-1-1; REFER TO 230713, 3.05.

GENERAL NOTES:

24"x24" SQ. LOUVERED FACE

CEILING DIFFUSER, 8"Ø NECK

NOTES:

1. ALL SUPPLY DIFFUSERS LISTED AS LOUVERED FACE TYPE SHALL BE (4) CONE LOUVER

TYPE, NO OPPOSED BLADE DAMPER.

2. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES.

3. NEW AIR DEVICES INSTALLED IN GYP BOARD, PLASTER, OR OTHER HARD CEILINGS

SHALL HAVE A SEPARATE MOUNTING FRAME.

WHITE ENAMEL

AIR DEVICE SCHEDULE

TYPE DESCRIPTION FINISH PRICE MODEL NO.

SCDS2

24"x24" PERFORATED FACE CEILING EXHAUST GRILLE, 22"x22" NECK WHITE ENAMELE1 PDDR

24"x24" SQ. LOUVERED FACE

CEILING DIFFUSER, 6"Ø NECK WHITE ENAMEL SCDS1

EXISTING TO REMAINEX

12"x12" PERFORATED FACE CEILING EXHAUST GRILLE, 10"x10" NECK WHITE ENAMELE2 PDDR

Restrooms Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

PLUMBING NOTES

AND SCHEDULES

P0.1

PLUMBING LEGEND

COLD WATER (CW)

HOT WATER (HW)

HOT WATER RETURN (HWR)

WASTE (SANITARY SEWER) (W)

VENT (SANITARY SEWER) (V)

BALL VALVE

NEW TO EXISTING CONNECTION

EXISTING (E)

V

FCO FLOOR CLEANOUT

WCO WALL CLEANOUT

VTR VENT THRU ROOF

DEMOLITION

NOTES:

1. ALL FIXTURES SHALL MEET LOW WATER CONSUMPTION REQUIREMENTS FOR THE STATE OF TEXAS.

2. PROVIDE STOPS AT ALL FIXTURES.

3. PROVIDE INSULATION KIT FOR ALL ACCESSIBLE LAVATORIES & SINKS WITH EXPOSED PIPING (TRUBRO LAV-GUARD OR APPROVED EQUAL).

4. PROVIDE NEW FLOOR MOUNTED WALL CARRIERS FOR ALL WALL MOUNTED FIXTURES.

5. ALL 'ACCESSIBLE' FIXTURES AND INSTALLATIONS SHALL COMPLY WITH TAS.

ACCESSIBLE

1/2"

1/2"

2"

LAVATORY

UNDERMOUNTL-1 2" 2"

1/2"

PLUMBING FIXTURE SCHEDULE

CW

ROUGH-IN SIZE

FLOOR MOUNTED

WATER CLOSET

WC-1

TAG FIXTURE

4"

W

2"

V HW

1" -

DESCRIPTION

ACCESSIBLE

AMERICAN STANDARD #3461.001, VITREOUS CHINA ELONGATED TOILET WITH EVERCLEAN.

SLOAN ROYAL #111 MANUAL FLUSH VALVE, 1.28 GPF, CHROME FINISH.

CHURCH #9500SSCT OPEN FRONT SEAT WITH SELF-SUSTAINING STA-TITE HINGES, NO COVER.

FLUSH VALVE SHALL BE MOUNTED TO OPERATE FROM WIDE SIDE OF STALL. TOP OF SEAT 17-1/2" A.F.F.

BOTTLE FILLER

FILTERED, ACCESSIBLE

REMOTE CHILLER

AMERICAN STANDARD #0496200.020. VITREOUS CHINA UNDERMOUNT LAVATORY.

DELTA #22C101 CENTERSET SINGLE LEVER FAUCET, GRID STRAINER & P-TRAP. ADA INSULATION PACKAGE.

-FD-1 -FLOOR DRAIN

HALSEY TAYLOR #HTHBGRN8-WF, BARRIER FREE, SINGLE STATION WALL MOUNTED BOTTLE FILLING STATION.

CABINET SHALL BE STAINLESS STEEL. COOLER SHALL HAVE AN INTEGRAL WATER FILTER AND DELIVER 8.0 GPH OF 50°F DRINKING WATER, 115/1Ø/60HZ, UTILIZE R-134A REFRIGERANT. PROVIDE WITH (2) ADDITIONAL WATER FILTERS.

REMOTE CHILLER SHALL BE INSTALLED ABOVE CEILING WITH PIPING AS REQUIRED.

SQUARE STRAINER 3"

AMERICAN STANDARD #6590.001EC VITREOUS CHINA, ELONGATED RIM WITH TOP SPUD.

SLOAN ROYAL #186-0.5 MANUAL FLUSH VALVE (0.5 GPF). MOUNT RIM 17" AFF.3/4"UR-1 -

URINAL, WALL HUNG

FLUSH VALVE 2" 2"

WATTS FD-100-M COATED CAST IRON WITH ADJUSTABLE SQUARE NICKEL BRONZE STRAINER.

FLOOR DRAIN SHALL HAVE NO HUB CONNECTION AND PROSET TRAP GUARD.

BF-1 1-1/2"

AMERICAN STANDARD #6590.001EC VITREOUS CHINA, ELONGATED RIM WITH TOP SPUD.

SLOAN ROYAL #186-0.5 MANUAL FLUSH VALVE (0.5 GPF). MOUNT RIM 24" AFF.3/4"UR-2 -URINAL, WALL HUNG

FLUSH VALVE 2" 2"

ACCESSIBLE

2"

1/2"

SINK, SINGLE COMPARTMENT

DROP-INS-1 2" 2" 1/2"

ACCESSIBLE

1/2"S-2 2" 2" 1/2"

SINK, SINGLE COMPARTMENT

DROP-IN

ACCESSIBLE

ELKAY #LRAD-2522-65-PD-2, 18 GA. STAINLESS STEEL 25" x 22" x 6-1/2" DEEP COUNTERTOP SINK WITH 2 FAUCET HOLES. DRAIN OPENING TO BE IN THE CENTER REAR LOCATION. DELTA #27C4944 FAUCET WITH LEVER HANDLES, GOOSENECK SPOUT, AERATOR, STRAINER AND P-TRAP. ADA INSULATION PACKAGE.

ELKAY #LRAD-1919-65-PD-2, 18 GA. STAINLESS STEEL 19" x 19" x 6-1/2" DEEP COUNTERTOP SINK WITH 2 FAUCET HOLES. DRAIN OPENING TO BE IN THE CENTER REAR LOCATION. DELTA #27C4944 FAUCET WITH LEVER HANDLES, GOOSENECK SPOUT, AERATOR, STRAINER AND P-TRAP. ADA INSULATION PACKAGE.

1. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF ALL EXISTING UTILITIES REQUIRED FOR

CONNECTIONS TO NEW PLUMBING FIXTURES.

2. REFER TO PLUMBING FIXTURE SCHEDULE FOR REQUIRED UTILITY CONNECTION SIZES.

3. REFER TO ARCHITECTURAL DOCUMENTS FOR ABATEMENT REQUIREMENTS. ALL PIPING

INSULATION REMOVED DURING ABATEMENT SHALL BE REPLACED. VERIFY PIPE SIZES AND

LENGTHS IN FIELD.

4. ALL PVC WASTE AND VENT PIPING ABOVE CEILING SHALL BE ASTM E84 INSULATED, RATED

AND APPROVED FOR USE IN PLENUM APPLICATIONS.

5. HOT WATER PIPING TO LAVATORIES SHALL BE RECIRCULATED TO COMPLY WITH APPLICABLE

ENERGY CODE (IECC). CIRCULATED HW PIPE SHALL BE ROUTED HORIZONTALLY WITHIN WALL

BEHIND EACH FIXTURE TO COMPLY WITH MAXIMUM PIPING LENGTH.

6. REMOVE ALL EXISTING WALL CARRIERS AND INSTALL NEW FLOOR MOUNTED WALL CARRIERS

FOR NEW WALL HUNG FIXTURES.

7. ALL PIPING WITHIN WALLS AND CHASES SERVING NEW PLUMBING FIXTURES SHALL BE NEW

WITH NEW INSULATION.

8. THE CONTRACTOR SHALL REPLACE ANY DAMAGED PIPE INSULATION FOR DOMSTIC HOT AND

COLD WATER SYSTEMS BELOW FLOOR OR ABOVE CEILING THAT SERVE THESE RESTROOMS -

REFER TO 220716, 3.05.

9. REPLACE EXISTING WALL CLEAN OUT COVERS WITH NEW STAINLESS STEEL ROUND COVER

WITH SCREW, EQUAL TO MIFAB C1400-RD (QTY. 4 ON THIS PROJECT).

10. REMOVE ALL EXISTING TRAP PRIMER VALVES AND PIPING SERVING EXISTING FLOOR DRAINS.

INSTALL A NEW PROSET TRAP GUARD FOR ALL NEW FLOOR DRAINS.

11. FURNISH AND INSTALL A PDI WATER HAMMER ARRESTOR WHERE INDICATED ON PLANS

AND/OR AS REQUIRED BY ASSE 1010 AND PDI.

GENERAL PLUMBING NOTES

WHA WATER HAMMER ARRESTOR

FAN ROOM

RESTROOM

HALL

HALL

RESTROOM

JANITOR WOMEN

LOUNGE

CORRIDOR

VESTIBULE

MEN

ELECTRICAL

OPEN OFFICE BREAK ROOM

OPEN OFFICE

AB

AN

DO

NE

D 8"

S

AN

. S

EW

ER

(E ) 5

" S

AN

. S

EW

ER

(E) 5"W FROM ABOVE

(E) 3" CW

(E) FIRE RISER

(E) FD

(E) 3" CW (E) 3" CW UP

(E) 1-1/2" HW FROM ABOVE

(E) 1-1/2" HW

(E) 1-1/2" HW

(E) 4" SAN. SEWER

(E) 5" SAN. SEWER

(E) 3/4" HWR UP

(E) FCO

(E) WCO

(E) WCO

(E) 2" CW

(E ) 3

/4" H

W R

(E) WCO

(E) WCO

(E) FIRE HOSE CABINET

(E) JAN. SINK

NOTE: CONFIRM EXISTING

ROUTING OF UTILITIES TO THIS

SINK TO MAINTAIN SERVICE.

Restrooms Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

1ST FLOOR - PLUMBING

DEMOLITION PLAN

P1.0

1ST FLOOR - PLUMBING DEMOLITION PLAN

0 4' 8' 12'1

1. REMOVE EXISTING PLUMBING FIXTURE INCLUDING ALL ASSOCIATED PIPING WITHIN THE WALL.

REMOVE EXISTING WALL CARRIER FOR URINALS. PLUG WASTE PIPING BELOW FLOOR AND

CAP VENT/WATER PIPING ABOVE CEILING. REPAIR AND SEAL FLOOR OPENINGS TO MATCH

EXISTING.

2. REMOVE EXISTING SINK AND PREPARE PIPING FOR INSTALLATION OF A NEW SINK AT THIS

APPROXIMATE LOCATION.

NOTES BY SYMBOL: " " #

WOMEN

JANITOR

CORRIDOR

MEN

VESTIBULE

HALL

BREAK ROOM

OPEN OFFICE

QUIET

HALL

ELECTRICAL

(E) 3" CW (E) 3" CW

(E) 1-1/2" HW

(E) 1-1/2" HW

(E) 2" CW

(E ) 3

/4" H

W R

FAN ROOM

L-13

WC-11

WC-1

UR-22

UR-1

L-13

WC-1

WC-1

L-1 3

L-1

L-1 3

L-1 3

S-1 4

S-2 5

BF-16

(E) FIRE HOSE CABINET

(E) JAN. SINK

(E) 3" CW UP

(E) 1-1/2" HW FROM ABOVE

(E) 3/4" HWR UP

WC-1 1

NEW ICE MAKER

(E)1/2"

2"

1/2"

2"

2"

INSTALL NEW

SHUT-OFF VALVE

(E) FIRE RISER

WC-2

WC-2

WC-2

WHA 'B'

WHA 'A'

WHA 'A'

WHA 'A'

WHA 'A'

WHA 'A' (TYP. 2)

3/4"

FLO-1

FLO-1

3/4"

1"

1"

PROVIDE

REDUCER TO 1"

Restrooms Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001 P2.0

1ST FLOOR - PLUMBING PLAN - WATER SUPPLY

0 4' 8' 12'1

1. PROVIDE AND INSTALL NEW WATER CLOSET. CORE DRILL NEW OPENINGS IN SLAB FOR

WASTE CONNECTIONS AS REQUIRED. EXTEND 4"W, 2"V AND 1" CW TO NEW FIXTURE.

2. PROVIDE AND INSTALL NEW URINAL WITH A NEW FLOOR MOUNTED WALL CARRIER. EXTEND

2"W, 2"V AND 3/4" CW TO NEW FIXTURE.

3. PROVIDE AND INSTALL NEW LAVATORY AND FAUCET. EXTEND 2"W, 2"V, 1/2" CW AND 1/2" HW TO EACH NEW FIXTURE. INSTALL A NEW FLOW SPLITTER ON THE EXISTING MAIN RECIRC LINE;

REDUCE BRANCH LINES FROM 1" TO 3/4", THEN EXTEND 3/4" RECIRCULATED HW DOWN IN

WALL BEHIND FIXTURE TO COMPLY WITH MAX PIPING LENGTH PER 2015 IECC.

4. PROVIDE AND INSTALL NEW SINK AND FAUCET. EXTEND 2"W, 2"V, 1/2" CW AND 1/2" HW TO

NEW FIXTURE.

5. PROVIDE AND INSTALL NEW SINK AND FAUCET. RECONNECT 2"W, 2"V, 1/2" CW AND 1/2" HW TO

NEW FIXTURE; EXTEND 1/2" CW WITH SHUT-OFF VALVE BELOW COUNTER TO NEW ICE MAKER.

6. PROVIDE AND INSTALL NEW BOTTLE FILLER. EXTEND 2"W, 1-1/2"V AND 1/2" CW TO NEW

FIXTURE. INSTALL FLOOR MOUNTED FRAME AND INSTALL REMOTE CHILLER ABOVE CEILING

PER MANUFACTURER'S INSTRUCTIONS.

NOTES BY SYMBOL: " " #

1ST FLOOR - PLUMBING

WATER SUPPLY

FLOW SPLITTERS

FLO-1

TAG MAIN PIPE SIZE BRANCH SIZE

NOTES:

1. FLOW SPLITTERS SHALL BE MANUFACTURED BY KEMPER

WATER CONTROL SYSTEMS WITH STOP VALVES (# 651 06).

1-1/2" 1"

WOMEN

JANITOR

CORRIDOR

MEN

VESTIBULE

HALL

BREAK ROOM

OPEN OFFICE

QUIET

HALL

ELECTRICAL

L-13

WC-11

WC-11

WC-11

WC-11

WC-11

UR-22

UR-12

L-13

WC-1

WC-1

L-1 3

L-1 3 L-1 3

L-1 3

S-1 4

S-2 4BF-15

(E ) 5

" S

AN

. S

EW

ER

(E) 4" SAN. SEWER

(E) 5" SAN. SEWER

(E) FIRE HOSE CABINET

FAN ROOM

(E) JAN. SINK

(E) 5"W FROM ABOVE

(E) FCO

(E) WCO

(E) WCO(E) WCO

FD-1

WC-1 1

NEW ICE MAKER

FD-1

FD-1

(E) FD

6 6

2"

2-1/2" 2"

(E) WCO

3"W, 2"V (TYP. FD)

SEE GENERAL NOTE 9 (TYP.)

1ST FLOOR - PLUMBING

WASTE & VENT

P2.1

Restrooms Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

1ST FLOOR - PLUMBING PLAN - WASTE & VENT

0 4' 8' 12'1

1. PROVIDE AND INSTALL NEW WATER CLOSET. CORE DRILL NEW OPENINGS IN SLAB FOR

WASTE CONNECTIONS AS REQUIRED. EXTEND 4"W, 2"V AND 1" CW TO NEW FIXTURE.

2. PROVIDE AND INSTALL NEW URINAL WITH A NEW FLOOR MOUNTED WALL CARRIER. EXTEND

2"W, 2"V AND 3/4" CW TO NEW FIXTURE.

3. PROVIDE AND INSTALL NEW LAVATORY AND FAUCET. EXTEND 2"W, 2"V, 1/2" CW AND 1/2" HW

TO NEW FIXTURE. THE HW RECIRCULATED LINE SHALL BE EXTENDED IN WALL BEHIND

FIXTURE TO COMPLY WITH MAX PIPING LENGTH PER 2015 IECC.

4. PROVIDE AND INSTALL NEW SINK AND FAUCET. EXTEND 2"W, 2"V, 1/2" CW AND 1/2" HW TO

NEW FIXTURE.

5. PROVIDE AND INSTALL NEW BOTTLE FILLER. EXTEND 2"W, 1-1/2"V AND 1/2" CW TO NEW

FIXTURE. INSTALL FLOOR MOUNTED FRAME AND INSTALL REMOTE CHILLER ABOVE CEILING

PER MANUFACTURER'S INSTRUCTIONS.

6. EXTEND NEW VENT LINE ABOVE CEILING AND CONNECT TO NEAREST EXISTING VENT MAIN.

NOTES BY SYMBOL: " " #

Restrooms Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

E INDICATES EXISTING DEVICE OR EQUIPMENT TO REMAIN

CONDUIT WITH ONE PHASE, ONE NEUTRAL, AND ONE GROUND

FIRE ALARM SPEAKER/STROBE UNIT

ELECTRICAL SYMBOL LIST

SYMBOL DESCRIPTION

FIRE ALARM STROBE ONLY

JUNCTION BOX

GFI RECEPTACLE

DUPLEX RECEPTACLE

PUSHBUTTON

GROUND

CONDUIT AND HOMERUN TO PANEL - NOTE 2

208/120 V PANELBOARD

LOW VOLTAGE SWITCH WITH ON/OFF AND 0-10V DIMMING

EMERGENCY LIGHTING UNIT WITH 2 LAMPS

LED LIGHT FIXTURE (2'X2', 2'X4') - REFER TO NOTE 1

NOTES:

1. LETTER ADJACENT TO FIXTURE DENOTES FIXTURE TYPE. REFER TO FIXTURE SCHEDULE.

2. WHEN NO HASH MARKS ARE SHOWN, PROVIDE ONE PHASE, ONE NEUTRAL, AND ONE GROUND CONDUCTOR.

3. SOME OF THESE SYMBOLS AND ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS.

XR INDICATES EXISTING DEVICE OR EQUIPMENT TO BE RELOCATED

PP

OS

CEILING MOUNTED POWER PACK

CEILING MOUNTED OCCUPANCY SENSOR

ELECTRICAL SYMBOL LIST

& IECC DOCUMENTS

E0.1

XN INDICATES NEW LOCATION OF EXISTING DEVICE OR EQUIPMENT

LOW VOLTAGE SWITCH WITH ON/OFF CONTROL

ER INDICATES EXISTING DEVICE OR EQUIPMENT TO BE REMOVED

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION LAMPS

A4

A2 2'X2' TROFFER, SMOOTH REFLECTOR, 3300 LUMENS, CURVED & RIBBED DIFFUSER, UNIVERSAL 120-277

VOLTAGE, 0-10V DIMMING, 82CRI, 3500K CCT

LITHONIA #2BLT2-33L-ADP-EZ1-LP835

26.6 W LED

WITH UNIT

2'X4' TROFFER, SMOOTH REFLECTOR, 4000 LUMENS, CURVED & RIBBED DIFFUSER, UNIVERSAL 120-277

VOLTAGE, 0-10V DIMMING, 82CRI, 3500K CCT

LITHONIA #2BLT4-40L-ADP-EZ1-LP835

30.5 W LED

WITH UNIT

C RECESSED LINEAR, 381 LUMENS/FT, 3500K CCT, 120V, REFER TO DRAWING FOR EACH FIXTURE LENGTH, COORDINATE MOUNTING SELECTION WITH ARCHITECT

FINELITE #HP-4R-D-[LENGTH]-S-835-F-96LG-277-SC-FC-10%-[MOUNTING]

3.6 W/FT LED

WITH UNIT

D 18" LONG UNDERCABINET LIGHT, 100% FROSTED LENS, [FINISH], 3500K CCT, 480 LUMENS/FT, 0-10V DIMMING, NO FEED, INDOOR LISTING, UNIVERSAL VOLTAGE, NO ROCKER SWITCH, NO OCCUPANCY SENSOR, HARDWIRED

ALUZ LIGHTING #A1-ZADY-STN-F-[FINISH], 35K-5W-10V-NF-DRY-UNV-18"

5 W/FT LED

WITH UNIT

WOMEN

JANITOR

CORRIDOR

MEN

VESTIBULE

HALL

BREAK ROOM

OPEN OFFICE

QUIET

HALL

ELECTRICAL

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

ER

E

ER

ER

ER

E

E

XR

E E

E

XR

XR

CLG

CLG

CLG

XR

CLG

E

F

XR

CLG

F

XR

CLG

F

E

CLG

F

E

CLG

F

F

E

CLG

F

E

CLG

F

E

E

CLG

E

PANEL A1

E

PANEL A2

E

E

E

E

E

E

E

E

E

E

E

E

CLG

F

E E

CLG

F

ER* *

E

E

E E E

E E

EE

EE

EE

EE

E

E

E

E

XR

CLG

F

ER *

Restrooms

Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

1ST FLOOR - ELECTRICAL

DEMOLITION PLAN

E1.0

NOTE BY SYMBOL: " "

1. CONTRACTOR SHALL REMOVE EXISTING LIGHT FIXTURE AND PREPARE EXISTING EXISTING

LIGHTING CIRCUIT FOR NEW LIGHT FIXTURES IN THE SAME ROOM. REFER TO SHEET E2.0 FOR

ADDITIONAL INFORMATION.

2. ALL LIGHTING AND LIGHTING CONTROLS IN THIS ROOM ARE EXISTING TO REMAIN.

3. INTERCEPT RECEPTACLE CIRCUIT AND EXTEND TO NEW DEVICE AS NOTED BY NOTE BY

SYMBOL #3, SHEET E2.0 FOR NEW LOCATION.

4. INTERCEPT RECEPTACLE CIRCUIT AND EXTEND TO NEW DEVICE AS NOTED BY NOTE BY

SYMBOL #4, SHEET E2.0 FOR NEW LOCATION.

1ST FLOOR - ELECTRICAL DEMOLITION PLAN

0 4' 8' 12'1

WOMEN

JANITOR

CORRIDOR

MEN

VESTIBULE

HALL

BREAK ROOM

OPEN OFFICE

QUIET

HALL

ELECTRICAL

E

E

E E

E

E

PANEL A1

E

PANEL A2

LA-6

LA-23

LA-21

E

PANEL LA

LA-10

E *

E

LA-24

LA-12

LA-12

LA-22LA-19

LA-18

Restrooms

Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

SHEET NOTES:

1. CONTRACTOR SHALL DEMOLISH ALL DEVICES SHOWN ON DETAIL 1, SHEET E1.0 UNLESS

OTHERWISE NOTED.

2. FIRE ALARM LAYOUT IS SCHEMATIC AND INTENDED TO ILLUSTRATE THE APPROXIMATE

LOCATIONS OF DEVICES. SUBMIT APPROVED PLANS IN ACCORDANCE WITH APPLICABLE

STATE CODES AND INSTALL FIRE ALARM SYSTEM BY AN APPROVED FIRE ALARM INSTALLER.

REFER TO FIRE ALARM SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

3. VERIFY FINAL LENGTHS OF ALL TYPE 'C' LIGHT FIXTURES WITH ARCHITECT.

NOTE BY SYMBOL: " "

1. POWER FOR ICE MAKER. PROVIDE A NEW 20A/1P GFI PROTECTED CIRCUIT BREAKER IN

EXISTING SPACE IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL

FINAL CONNECTIONS.

2. POWER FOR UNDERCOUNTER REFRIGERATOR. PROVIDE A NEW 20A/1P GFI PROTECTED

CIRCUIT BREAKER IN EXISTING SPACE IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN

3/4"C. AND MAKE ALL FINAL CONNECTIONS.

3. NEW LOCATION OF EXISTING CIRCUIT MADE AVAILABLE BY DEMOLITION OF EXISTING

RECEPTACLE. REFER TO NOTE BY SYMBOL #3, SHEET E1.0 FOR EXISTING LOCATION.

4. NEW LOCATION OF EXISTING CIRCUIT MADE AVAILABLE BY DEMOLITION OF EXISTING

RECEPTACLE. REFER TO NOTE BY SYMBOL #4, SHEET E1.0 FOR EXISTING LOCATION.

5. POWER FOR BOTTLE FILLER CONDENSER IN CEILING. PROVIDE A NEW 20A/1P GFI PROTECTED

CIRCUIT BREAKER IN EXISTING SPACE IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN

3/4"C. AND MAKE ALL FINAL CONNECTIONS. CONFIRM EXACT INSTALLATION LOCATION AND

CONNECTION REQUIREMENTS WITH PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.

6. POWER FOR HAND DRYER. CONNECT TO AN EXISTING SPARE 20A/1P CIRCUIT BREAKER IN

EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL FINAL CONNECTIONS.

7. COORDINATE AUTOMATIC DOOR SWING ACTIVATOR SELECTION AND LOCATION WITH

ARCHITECT. PROVIDE 3/4" CONDUIT WITH PULL STRING BETWEEN ACTIVATOR AND SWING

DOOR OPERATOR PER MANUFACTURER'S SPECIFICATIONS.

8. POWER FOR SWING DOOR OPERATOR AT WOMEN 105. CONNECT TO TO AN EXISTING 20A/1P

CIRCUIT BREAKER IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL

FINAL CONNECTIONS.

9. POWER FOR SWING DOOR OPERATOR AT VESTIBULE 102. PROVIDE 2#12, 1#12G., IN 3/4"C. TO

DOOR OPENER AT WOMEN 105 AND MAKE ALL FINAL CONNECTIONS.

10. POWER FOR MICROWAVE ABOVE COUNTER. PROVIDE A NEW 20A/1P GFI PROTECTED CIRCUIT

BREAKER IN EXISTING SPACE IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND

MAKE ALL FINAL CONNECTIONS. CONFIRM EXACT INSTALLATION LOCATION AND CONNECTION

REQUIREMENTS WITH PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.

11. CONNECT TO AN EXISTING SPARE 20A/1P CIRCUIT BREAKER IN EXISTING PANEL 'LA' AND

EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL FINAL CONNECTIONS.

1ST FLOOR - ELECTRICAL

POWER PLAN

E2.0

1ST FLOOR - ELECTRICAL POWER PLAN

WOMEN

JANITOR

CORRIDOR

MEN

VESTIBULE

HALL

BREAK ROOM

OPEN OFFICE

QUIET

HALL

ELECTRICAL

C

(9'-11")

C

(6'-0")

C

(6'-0")

A2

A4 a a a b b a,b a,b a,b a,b

A4

A4 A4 A4 a,ba,b

C

(15'-11")

C

(8'-9")

A4

A4

A4 a a a b b a,ba,b a,b a,b

E

E

E

E

XN

E

XN

CLG

CLG

E

CLG

F

E

CLG

F

E

E

E

E

E

CLG

F

E E

CLG

F

E

E E E

E E

EE

EE

EE

EE

E

E

E

E

XN

CLG

F

XN

CLG

F

XN

CLG

F

LA-20

XN

CLG

F

E

CLG

XN

CLGF

D b D b

D a D aD aD a a a

Restrooms

Renovation

307 W 13th St., Fort Worth, TX.

76102

6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com

TBPELS Firm #44, #10011300, #1001302, #10194146

BHB PROJECT # 2025.011.001

PP OS

CAT-5E CABLE

LINE VOLTAGE

TO LIGHT FIXTURES

ACUITY NLIGHT NPODMA SERIES

WALLPOD SWITCH. NUMBER OF

DEVICES AS SHOWN ON DETAIL 2,

SHEET E1.0.

LIGHTING CONTROL DETAIL

1ST FLOOR - ELECTRICAL

LIGHTING PLAN

E3.0

ACUITY NLIGHT NPP16

POWER/RELAY PACK. NUMBER

OF DEVICES AS SHOWN ON

DETAIL 2, SHEET E1.0.

ACUITY NLIGHT NCM PDT 10 RJB

CEILING MOUNT SENSOR.

NUMBER OF DEVICES AS SHOWN

ON DETAIL 2, SHEET E1.0.

NOTE BY SYMBOL: " "

1. CONNECT TO EXISTING LIGHTING CIRCUIT MADE SPARE BY DEMOLITION OF EXISTING

LIGHTING IN THIS AREA. REFER TO DETAIL 2, SHEET E3.0 FOR ADDITIONAL INFORMATION

REGARDING LIGHTING CONTROL REQUIREMENTS IN THIS ROOM.

2. POWER FOR VANITY MIRROR LIGHTING. CONNECT TO AN EXISTING SPARE 20A/1P CIRCUIT

BREAKER IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL FINAL

CONNECTIONS. CONFIRM EXACT INSTALLATION LOCATION AND CONNECTION REQUIREMENTS

WITH GENERAL CONTRACTOR PRIOR TO ROUGH-IN.

3. CONNECT TO EXISTING LIGHTING CIRCUIT AS DIRECTED IN APPLICABLE NOTE BY SYMBOLS

SHOWN AT EACH LIGHTING POWER PACK.

4. INTERCEPT EXISTING UN-SWITCHED LIGHTING CIRCUIT IN THIS ROOM TO POWER NEW UNDER

CABINET LIGHTING IN THIS ROOM. REFER TO DETAIL 2, SHEET E3.0 FOR ADDITIONAL

INFORMATION REGARDING LIGHTING CONTROL REQUIREMENTS IN THIS AREA.

SHEET NOTES:

1. CONTRACTOR SHALL DEMOLISH ALL DEVICES SHOWN ON DETAIL 1, SHEET E1.0 UNLESS

OTHERWISE NOTED.

2. FIRE ALARM LAYOUT IS SCHEMATIC AND INTENDED TO ILLUSTRATE THE APPROXIMATE

LOCATIONS OF DEVICES. SUBMIT APPROVED PLANS IN ACCORDANCE WITH APPLICABLE

STATE CODES AND INSTALL FIRE ALARM SYSTEM BY AN APPROVED FIRE ALARM INSTALLER.

REFER TO FIRE ALARM SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

3. VERIFY FINAL LENGTHS OF ALL TYPE 'C' LIGHT FIXTURES WITH ARCHITECT.

1ST FLOOR - ELECTRICAL LIGHTING PLAN

G0.0
G0.1
G0.2
G0.3
A1.1
A2.1
A2.2
A5.1
A6.1
A9.1
Mech-Plum
M1.0
Electrical
E0.1
E1.0
E1.0
E2.0
E3.0

File details come from the government source that posted it. Updated .