7-2-CR27014-26066270 Approved Plans.pdf

PDF 5 MB Posted

Attached to
DFCM Construction - Prequalified Mechanical Stage II - Southwest Technical College- Kanab Shop Mechanical Upgrade - Project #26066270
Solicitation number
CR27014
Issued by
Utah

About this file

This is an approved mechanical construction plans document for the State of Utah Division of Facilities Construction and Management (DFCM) for the Southwest Technical College (SWATC) Kanab Shop Mechanical Upgrade project (DFCM #26066270). The project involves removal of two existing evaporative coolers and infrared heaters, which will be replaced with two new ground-mounted packaged air handling units complete with associated ductwork. Additionally, a new wall-mounted exhaust fan with ductwork will be installed to support improved ventilation and bring the facility into current code compliance. The project is located at 733 S. Cowboy Way, Kanab, Utah 84741, at a 3,500 square foot single-story S-1 occupancy building with a height of 19'1". The approved plans include mechanical legend and general notes (sheet MG001), special instructions and testing (sheet MG002), mechanical plans (sheet ME101), mechanical details (sheets ME501-ME502), mechanical schedules (sheet ME601), and mechanical isometrics (sheet ME901). The work must comply with the 2021 International Mechanical Code (IMC) and International Plumbing Code (IPC) with Utah annotations, and all seismic design requirements must follow ASCE 7-05 standards with deferred submittals required approximately 15 days after notice to proceed.

The construction cost estimate for the project is $114,956.00. Only contractors prequalified under a Stage I Prequalification for Contractors and currently listed on the DFCM Prequalified Contractors list are eligible to bid on this Stage II Invitation to Bid. The plans specify that the mechanical contractor shall contract with a design-build electrical contractor for all electrical design and installation per the 2020 National Electrical Code, with all new control wiring and electrical feeders to be run in appropriately sized conduit. Key mechanical equipment specifications include two Carrier 48FEDM07C3A5 packaged air units each capable of 2,400 CFM occupied capacity with 1,300 CFM outside air and 480 CFM standby outside air, and one Greenheck AER-24-02-0515-VG exhaust fan with 2,750 CFM high-limit and 250 CFM standby capacity. New gas piping will tie into existing infrastructure with a gas meter rated for 375 CFH and 309 MBH. The project requires field verification of existing conditions, structural coordination for all penetrations, and coordination with a DFCM-approved roofing contractor for any roof modifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SWATC KANAB

733 S. COWBOY WAY

KANAB, UT 84741

GENERAL:

G001--- TITLE SHEET

G002--- SPECIAL INSPECTIONS AND TESTING

MECHANICAL:

MG001 - MECHANICAL GENERAL NOTES AND LEGEND

ME101 - MECHANICAL PLAN

ME501 - MECHANICAL DETAILS

ME502 - MECHANICAL DETAILS

ME601 - MECHANICAL SCHEDULES

ME901 - MECHANICAL ISOMETRICS

DRAWING INDEX:

DEFERRED SUBMITTALS :

1. SEISMIC ENGINEER SHALL PROVIDE A SUBMITTAL INCLUDING

CALCULATIONS AND DETAILS TO THE DFCM BUILDING OFFICIALS

FOR REVIEW. SEISMIC SHALL BE DESIGNED TO RESIST THE EFFECTS

OF EARTHQUAKE MOTIONS IN ACCORDANCE WITH ASCE 7-05.

REFERENCE IBC SECTION 1613.1.

2. THE DATE OF DEFERRED SUBMITTALS IS APPROXIMATELY 15 DAYS AFTER

NOTICE TO PROCEED. MECHANICAL WORK CANNOT COMMENCE UNTIL THE

DFCM BUILDING OFFICIALS HAVE APPROVED THE SEISMIC

SUBMITTALS.

3. EACH DEFERRED SUBMITTAL IS REQUIRED TO HAVE THE PROJECT

NAME, DFCM NUMBER, PROJECT ADDRESS, CONFORMANCE LETTER

OR STAMP FROM THE DESIGNER AND A 3"x3" SPACE FOR THE

APPROVAL STAMP ON THE FRONT PAGE.

SPECIAL INSPECTIONS:

1. SEE SHEET DRAWING G002.

DESIGN CRITERIA:

THESE DOCUMENTS - DRAWINGS AND SPECIFICATIONS COMPLY WITH ALL THE

REQUIREMENTS OF THE DFCM STANDARDS FOR MECHANICAL UPGRADES OF

EXISTING BUILDING.

CODE INSPECTION REQUIREMENTS:

1. BEFORE A FINAL ACCEPTANCE CAN BE ISSUED, THE STATE APPOINTED CODE

INSPECTOR SHALL PROVIDE A FINAL REPORT RECOMMENDING THAT THE NEW

MECHANICAL WORK IS IN COMPLIANCE WITH THE DRAWINGS, SPECIFICATIONS

AND APPLICABLE CODES ESPECIALLY FOR THE FOLLOWING ITEMS.

a.)SEISMIC - MECHANICAL AND ELECTRICAL PER DEFERRED SUBMITTALS.

2. SEE ALSO SHEET G002.

PROJECT SCOPE:

THIS PROJECT INVOLVES THE REMOVAL OF TWO

EXISTING EVAPORATIVE COOLERS AND INFRARED

HEATERS CURRENTLY SERVING THE BUILDING. THESE

SYSTEMS WILL BE REPLACED WITH TWO NEW

GROUND-MOUNTED PACKAGED AIR HANDLING UNITS,

COMPLETE WITH ALL NEW ASSOCIATED DUCTWORK.

ADDITIONALLY, A NEW WALL-MOUNTED EXHAUST FAN

AND DUCTWORK WILL BE INSTALLED TO SUPPORT

IMPROVED VENTILATION.

SWATC KANAB SHOP

MECHANICAL UPGRADE

DFCM# 26066270

G001

CODE REVIEW STAMP

North: ______ South: ______ East: ______ West: ______

Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________

d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a

3) Three Story: A (3)______

2) Two Story: A (2)______

1) One Story: ______

c) Total Allowable Area for:

1_< Allowable Area

Actual Area

b) Sum of the Ratio Calculations for Mixed Occupancies:

a) 0.25I = 100f

F

P stA I

100100 fIA t taA = A + +

Official for Complex Buildings. Including, but not limited to:

g) Fire Stopping, Including Tested Design Number.

f) Exterior and Interior Accessibility Route.

e) Fire Assembly Locator Sheet.

a) High Rise Requirements.

b) Atriums.

c) Performance Based Criteria.

d) Means or Egress Analysis.

2) Additional Code Information shall be provided at the discretion of the Building

Code Accessibility Chapters, the more restrictive requirement shall govern.

through - ADA Guidelines and specific reference to the International Building

1) In case of conflict with the U.S. Department of Justice Federal Registers Parts

FOOTNOTES:

d) Drinking Fountains: ______ Service Sinks: ______

c) Bath Tubs or Showers: ______

b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______

a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____

M. Minimum Number of Required Plumbing Facilities:

Exit Width Required: ______ Exit Width Provided: ______

Element Listing

Element AssemblyHours

Smoke Partitions

Fire Partitions

Exterior Bearing Walls

Interior Bearing Walls

Exterior Non-Bearing Walls

Structural Frame Partitions - Permanent

Fire Barriers

Floors - Ceiling Floors

Roofs - Ceiling Roofs

Exterior Doors and Windows Shaft Enclosures

Fire Walls

AHTBABABA

Design Wind Speed: ______ mphB. Seismic Design Category: ______

L. Design Occupant Load: ______

K. Fire Resistance Rating Requirements for Building Elements (hours).

Area Modifications:

____________________________________________Tabular Area:

per Floor (square feet): ________3,500 SQ FT__________________Actual Area

Number of Stories: ___1___ Building Height: ___19' 1"__

Required: ______ Provided: ______ Type of Sprinkler System: ____________

Sprinklers:

Mixed Occupancies: ______ Nonseparated Uses: ______ separation distance (in hours):

Requirements for the Exterior Walls based on the fireFire Resistance Rating

C. Type of Construction (circle one):

Change in Use: Yes ______ No ___x___ Mixed Occupancy: Yes ______ No ______

A. Occupancy and Group: __S-1_____ ________ ________ ________ _____

CODE ANALYSIS

Guidelines

ADA Accessibility Building Conservation

Uniform Code for

National Electrical Code

Conservation Code

International Energy International Fire Code

International Plumbing Code

International Mechanical Code

International Building Code

Year

APPLICABLE CODES

B

SEF

O

R P

HATUFOETATS

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

08.08.25

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/21/2025

REVIEWED FOR CODE

COMPLIANCE

M

M

P

T

S

PS

IBT

T

TT

F&T

F

MECHANICAL LEGEND

SYMBOL ABR, DESCRIPTION

GENERAL TERMINOLOGY

A

ME101

SECTION LETTER DESIGNATION

SECTION DRAWN ON THIS SHEET

A2

AH

DETAIL NUMBER DESIGNATION

CORRESPONDING WITH GRID

LOCATION

MECHANICAL EQUIPMENT DESIGNATION

EQUIPMENT ITEM DESIGNATION

REGISTER, GRILLE OR DIFFUSER

DESIGNATION WITH BALANCING CFM

LISTED BELOW

D-1

CFM

GRILLE OR LOUVER DESIGNATION

WHERE BALANCING NOT REQUIREDR-1

REVISION DESIGNATOR AND NUMBER

KEY NOTE DESIGNATOR AND NUMBER

POINT OF CONNECTION

POINT OF REMOVAL

ABOVE FINISHED FLOOR

ACCESS PANEL

CENTERLINE ELEVATION

GENERAL CONTRACTOR

AFF

AP

POC

POR

C EL.

GC

MECHANICAL CONTRACTORMC

CONTROLS CONTRACTORATC

ELECTRICAL CONTRACTOREC

FIRE PROTECTION CONTRACTORFPC

NOT IN CONTRACTNIC

NOT TO SCALENTS

VITRIFIED CLAY PIPEVCP

NORMALLY CLOSEDNC

COMMONC

NORMALLY OPENNO

SYMBOL ABR, DESCRIPTION

AIR SIDE

EXISTING AIR DUCT TO BE REMOVED

EXISTING AIR DUCT TO REMAIN

NEW AIR DUCT

RECT TO RECT AIR DUCT TAKE-OFF

RECT TO RND AIR DUCT TAKE-OFF

RND TO RND AIR DUCT TAKE-OFF

MEDIUM PRESSURE TAKE-OFF

FLEXIBLE AIR DUCT

LINED DUCT

RADIUS ELBOW

ECCENTRIC DUCT TRANSITION

CONCENTRIC DUCT TRANSITION

VOLUME DAMPER

SUPPLY AIR DIFFUSER

RETURN & TRANSFER AIR GRILLE

EXHAUST GRILLE OR CEILING EXH. FAN

RETURN & OUTSIDE AIR DUCT UP/DN

RETURN & OA ROUND DUCT UP/DN

SUPPLY AIR DUCT UP/DN

SUPPLY AIR ROUND DUCT UP/DN

EXHAUST AIR DUCT UP/DN

EXHAUST AIR ROUND DUCT UP/DN

ACCESS PANELAP

EXISTING EQUIPMENT TO BE REMOVED

EXISTING EQUIPMENT TO REMAIN

NEW EQUIPMENT

SUPPLY AIR

RETURN AIRRA

SA

EXHAUST AIREA

OUTSIDE AIROA

MIXED AIRMA

RELIEF AIRRF

FLAT OVALFO

MOTORIZED VOLUME DAMPER

BACKDRAFT DAMPER

FIRE DAMPER

SMOKE DAMPER

FIRE & SMOKE DAMPER

WALL MOUNTED THERMOSTAT

WALL MOUNTED TEMP. SENSOR

WALL MOUNTED HUMIDISTAT

WALL MOUNTED FIRESTAT

M

BD

F

S

FS

T

S

H

F

SYMBOL ABR, DESCRIPTION

WET SIDE

PUMP

MVD

BD

FD

SD

FS

T-STAT

H-STAT

F-STAT

REGULATOR

UNION

MANUAL ACTUATOR

PNUEMATIC DIAPHRAM ACTUATOR

ELECTRIC MOTOR ACTUATOR

SOLENOID ACTUATOR

BUTTERFLY VALVE

GATE VALVE

GLOBE VALVE - STRAIGHT PATTERN

GLOBE VALVE - ANGLE PATTERN

MOTORIZED 2-WAY CONTROL VALVE

MOTORIZED 3-WAY CONTROL VALVE

CHECK VALVE

CIRCUIT BALANCING VALVE

BALL VALVE

PRESSURE RELIEF VALVE

THERMAL RELIEF VALVE

SAFETY RELIEF VALVE

PLUG VALVE

NEEDLE VALVE

TRIPLE DUTY VALVE

AUTOMATIC AIR VENT

MANUAL AIR VENT

STRAINER

STRAINER W/ PLUG BLOW OFF

VENTURI

PRESSURE GAUGE W/ COCK - WATER

PRESSURE GAUGE W/ COCK - STEAM

THERMOMETER & THERMOWELL

WATER TEMP SENSOR & THERMOWELL

FLOW SWITCH

PRESSURE SWITCH

THERMOWELL

PRESSURE & TEMP TAP

INVERTED BUCKET STEAM TRAP

THERMOSTATIC STEAM TRAP

FLOAT & THERMOSTATIC STEAM TRAP

DIRECTION OF FLOW

BACKFLOW PREVENTING VALVE

SYMBOL ABR, DESCRIPTION

WET SIDE

PITCH DOWN

ELBOW UP/DN

TEE UP/DN

EXISTING PIPING TO BE REMOVED

EXISTING PIPING TO REMAIN

NEW PIPING

PIPE CAP OR PLUG

REDUCER - CONCENTRIC / ECCENTRIC

EXPANSION JOINT

FLEXIBLE CONNECTION

ANCHOR POINT

CONDENSATE DRAIN

NATURAL GAS PIPING

CHEMICAL FEED LINE

MAKE-UP WATER LINE

CULINARY COLD WATER

CULINARY HOT WATER

CULINARY HOT WATER RECIRC

CD

G

CF

MU

CW

HW

HWREC

GLYCOL FILL LINEGF

R

M

S

PRESSURE REDUCING VALVEPRV

S

VENT LINEV

SANITARY SEWERSS

GENERAL NOTES

G-1 - MECHANICAL INFORMATION IS NOT LIMITED TO THE MECHANICAL DRAWINGS.

CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMATION OF THE EXISTING BUILDING AND SITE

CONDITIONS, EXISTING PIPING, EXISTING ELECTRICAL, AND EXISTING SUPPORTS.

A - EACH DRAWING SHEET AND THE SPECIFICATIONS HAVE BEEN PREPARED TO SUPPLEMENT

EACH OTHER AND THEY SHALL BE INTERPRETED AS AN INTEGRAL UNIT WITH ITEMS SHOWN

AND NOTED ON ONE AND NOT THE OTHER BEING FURNISHED AND INSTALLED AS THOUGH

SHOWN AND CALLED OUT IN ALL PLACES. ITEMS IN SPECIFICATIONS OR DRAWINGS LISTED

WHICH ARE DIFFERING IN EFFICIENCY OR QUALITY SHALL BE HELD TO THE GREATEST OF:

EFFICIENCY, QUALITY OR GOVERNING CODE.

B - THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR THE INSTALLATION OF THE SYSTEMS

ACCORDING TO THE TRUE INTENT AND MEANING OF THE CONTRACT DOCUMENTS.

C - THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH PROPER SERVICE ACCESS AND

CLEARANCES ACCORDING TO MANUFACTURERS RECOMMENDATIONS. THE CONTRACTOR SHALL

REVIEW SUPPLIERS BID PACKAGES FOR COMPLETENESS AND COMPLIANCE TO THE

SPECIFICATIONS, SCHEDULES, AND DESIGN INTENT (ALL EQUIPMENT AND METHODS). THE

CONTRACTOR SHALL REMOVE AND REINSTALL CORRECTLY AT HIS OWN EXPENSE ANY

EQUIPMENT NOT IN COMPLIANCE.

D - THE CONTRACTOR SHALL CONSULT MANUFACTURERS INSTALLATION INSTRUCTIONS FOR

SIZES, METHODS, ACCESSORIES, AND CLEARANCES IN SPACE AVAILABLE PRIOR TO BIDDING

PROJECT.

E - ANYTHING NOT CLEAR OR IN CONFLICT WILL BE EXPLAINED BY MAKING APPLICATION TO THE

ENGINEER IN WRITING.

G-2 - ANY AND ALL ALTERATIONS TO THE SYSTEM SHOWN SHALL BE SUBMITTED TO THE

ENGINEER PRIOR TO CHANGES FOR APPROVAL. CONTRACTOR SHALL NOT START ANY CHANGES

UNTIL NOTIFIED IN WRITING. IF CHANGES ARE MADE PRIOR TO APPROVAL CONTRACTOR SHALL TAKE ALL RESPONSIBILITY FOR THE CHANGES MADE AND ALL COSTS RELATING TO FAILURE OR

REPLACEMENT OF ALTERATIONS.

G-3 - CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND LOCATIONS.

G-4 - THE WORKING DRAWINGS ARE DIAGRAMMATIC. THEY DO NOT SHOW EVERY OFFSET,

BEND, OR ELBOW NECESSARY FOR THE COMPLETE INSTALLATION IN THE SPACE PROVIDED. ALL

LOCATIONS FOR MECHANICAL EQUIPMENT SHALL BE FIELD VERIFIED AND COORDINATED WITH

ALL DRAWINGS. THE CONTRACTOR SHALL PROVIDE OR COORDINATE WITH THE GENERAL

CONTRACTOR PROVISIONS FOR BLOCKOUTS OR CORE DRILLS THROUGH STRUCTURE.

G-5 - THE INSTRUCTION TO "PROVIDE" ALSO INCLUDES INSTALLATION.

G-6 - MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL SMOKE AND FIRE DAMPERS AS

REQUIRED BY LOCAL CODES AND AUTHORITIES.

G-7 - SHEET METAL DUCT SIZES SHOWN ON DRAWINGS ARE FREE AREA DIMENSIONS.

G-8 - PROVIDE AND INSTALL BALANCING DAMPERS IN ALL SUPPLY AND EXHAUST AIR BRANCH

DUCTS. BALANCE TO CFM SHOWN ON PLAN.

G-9 - SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF DIFFUSERS AND

GRILLES.

G-10 - PROVIDE TURNING VANES IN ALL ELBOWS OF RECTANGULAR DUCT.

G-11 - THE CONTRACTOR SHALL ASSUME ALL RESPONSIBILITY IN HANDLING AND DISPOSING OF REFRIGERANTS, OILS, ETC. ALL SUCH MATERIALS SHALL BE HANDLED, DISPOSED, AND USED IN

ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL LAWS.

G-12 - THE MECHANICAL CONTRACTOR SHALL VERIFY MOTOR VOLTAGES WITH THE ELECTRICAL

DRAWING BEFORE ORDERING MOTORIZED EQUIPMENT AND CONTROLS.

G-13 - C.F.M. LISTED IS ACTUAL AIR.

G-14 - SUPPLIERS SHALL REVIEW ALL DRAWINGS AND THE SPECIFICATIONS PRIOR TO

SUBMITTING PRICES TO THE CONTRACTOR. ALL QUESTIONS AND DISCREPANCIES SHALL BE

BROUGHT TO THE ENGINEERS ATTENTION PRIOR TO BIDDING.

G-15 - CONTRACTOR SHALL THOROUGHLY REVIEW AND SIGN SUBMITTALS FOR COMPLETENESS

AND COMPLIANCE TO THE SPECIFICATIONS PRIOR TO ENGINEERS REVIEW. SUPPLIERS SHALL

HIGHLIGHT OR MARK ALL INFORMATION REQUIRED TO SHOW COMPLIANCE TO THE

SPECIFICATIONS. ALL REQUESTED EXCEPTIONS TO THE SPECIFICATIONS, OR SCHEDULES

SHALL BE CLEARLY NOTED AND EXPLAINED. SUBMITTAL REVIEW AND ACCEPTANCE IS FOR

DESIGN CONCEPT ONLY, AND DOES NOT AT ANY TIME RELIEVE THE CONTRACTOR OF

RESPONSIBILITY TO MEET SPECIFICATIONS, CAPACITIES, OR DESIGN INTENT.

G-16 - ALL MECHANICAL SHALL BE INSTALLED AND CONFORM TO THE 2021 EDITION OF THE IMC

AND IPC WITH UTAH ANNOTATIONS AND LOCAL AUTHORITY REQUIREMENTS.

G-17 - THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE DRAINING DOWN AND RE-FILLING

OF ALL SYSTEMS NECESSARY TO COMPLETE THE WORK OUTLINED BY THIS PROJECT. THIS

INCLUDES PROVIDING THE REQUIRED CHEMICAL TREATMENT WHEN RE-FILLING THE SYSTEM.

G-18 - ALL PIPING, MATERIALS, ETC. SHALL BE NEW AND DOMESTIC MADE UNLESS SPECIFICALLY

AUTHORIZED IN WRITING PRIOR TO BID.

G-19 - THIS CONTRACTOR SHALL CONTRACT WITH A DESIGN BUILD ELECTRICAL CONTRACTOR

FOR THE DESIGN AND CONSTRUCTION OF THE ELECTRICAL PORTION OF THIS PROJECT.

ELECTRICAL INSTALLATION AND DESIGN SHALL BE PER 2020 NEC.

G-20 - ALL NEW CONTROL WIRING, ELECTRICAL WIRING AND FEEDERS SHALL BE RUN IN

APPROPRIATELY SIZED CONDUIT AND SECURED TO WALL PER CODE.

SEF

O

R P

HATUFOETATS

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities

Department of Administrative Services

Internet: http://www.dfcm.state.ut.us

State of Utah A

LL

ID

E A

S , D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D

E V

O

LV

E D

A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

D

E S

IG

N

S

A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

F

IC

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O F

F E

N S

E U

N D

E R

U .S

.C . S

E C

. 5

. U N

A U

T H

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U T

E T

R A

D E

S E

C R

E T

M

IS

A P

P R

O P

R

IA

T

IO

N

IN

V

IO

LA

T

IO

N

O F

I.

C

.2 4-

2-

-1 E

T . S

E Q

. A N

D O

T H

E R

L A

W S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/08/2025

WHW JOB NO.:

25078

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

SHEET TITLE

E E

WP

STAFF

CL

733 S Cowboy Way Kanab, UT 84741

SWATC KANAB

SHOP

MECHANICAL

UPGRADE

DFCM #26066270

08/08/25

MECHANICAL LEGEND

AND GENERAL NOTES

MG001

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/21/2025

SEF

O

R P

HATUFOETATS

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities

Department of Administrative Services

Internet: http://www.dfcm.state.ut.us

State of Utah A

LL

ID

E A

S , D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D

E V

O

LV

E D

A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

D

E S

IG

N

S

A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

F

IC

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O F

F E

N S

E U

N D

E R

U .S

.C . S

E C

. 5

. U N

A U

T H

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U T

E T

R A

D E

S E

C R

E T

M

IS

A P

P R

O P

R

IA

T

IO

N

IN

V

IO

LA

T

IO

N

O F

I.

C

.2 4-

2-

-1 E

T . S

E Q

. A N

D O

T H

E R

L A

W S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/08/2025

WHW JOB NO.:

25078

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

SHEET TITLE

E E

WP

STAFF

CL

733 S Cowboy Way Kanab, UT 84741

SWATC KANAB

SHOP

MECHANICAL

UPGRADE

DFCM #26066270

08/08/25

SPECIAL INSTRUCTIONS

AND TESTING

MG002

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/21/2025

2 2 1 1/4"ø NG (E)

S

COS

NO2

EF

D-1

TYP 24

T

PAU-1,2

PAU

PAU

20"ø SA

12"ø EA

20"ø SA

20"ø EA

12"ø EA

12"ø EA 12"ø EA

12"ø EA

3/4"ø NG 1/2"ø NG 1/2"ø NG

1 1/4"ø NG (E)

5 5

R-1 R-1

20"x20" RA20"x20" RA

EG-1

TYP 5

10 11

SEF

O

R P

HATUFOETATS

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities

Department of Administrative Services

Internet: http://www.dfcm.state.ut.us

State of Utah A

LL

ID

E A

S , D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D

E V

O

LV

E D

A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

D

E S

IG

N

S

A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

F

IC

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O F

F E

N S

E U

N D

E R

U .S

.C . S

E C

. 5

. U N

A U

T H

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U T

E T

R A

D E

S E

C R

E T

M

IS

A P

P R

O P

R

IA

T

IO

N

IN

V

IO

LA

T

IO

N

O F

I.

C

.2 4-

2-

-1 E

T . S

E Q

. A N

D O

T H

E R

L A

W S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/08/2025

WHW JOB NO.:

25078

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

SHEET TITLE

E E

WP

STAFF

CL

733 S Cowboy Way Kanab, UT 84741

SWATC KANAB

SHOP

MECHANICAL

UPGRADE

DFCM #26066270

08/08/25

MECHANICAL PLAN

ME101

1/4" = 1'-0"

MECHANICAL DEMOLITION PLAN

0'

SCALE : 1/4" = 1'-0"

4'2' 12'8' 0'

SCALE : 1/4" = 1'-0"

4'2' 12'8'

1/4" = 1'-0"

MECHANICAL PLAN

SHEET NOTES

1 REMOVE EXISTING RADIANT HEATER AND ALL

ASSOCIATED ITEMS IN THIS APPROXIMATE

LOCATION. REMOVE ALL ELECTRICAL

ACCOMMODATIONS BACK TO PANEL. REMOVE

EXISTING FLUE. COORDINATE WITH DFCM SHORT

LIST ROOFING CONTRACTOR TO SEAL AND

WEATHERPROOF FLUE PENETRATION.

2 REMOVE EXISTING EVAPORATIVE COOLER AND ALL

ASSOCIATED ITEMS IN THIS APPROXIMATE

LOCATION. REMOVE EXISTING WATER LINE SERVING

THE COOLER, REMOVE BACK TO MAIN AND CAP.

REPAIR AND PATCH PENETRATION IN WALL. PAINT TO

MATCH EXISTING COLOR. FIELD VERIFY.

3 REMOVE EXISTING NATURAL GAS PIPING AND ALL

ASSOCIATED ITEMS BACK TO THIS APPROXIMATE

LOCATION AND CAP. PIPING SERVING EXISTING

WATER HEATER AND ALL OTHER EQUIPMENT SHALL

REMAIN. FIELD VERIFY EXACT PIPE ROUTING AND

POINTS OF REMOVAL.

4 TIE INTO EXISTING NATURAL GAS PIPING IN THIS

APPROXIMATE LOCATION. SECURE PIPING TO WALL.

UV PAINT ALL OUTDOOR GAS PIPING. PAINT ALL

EXPOSED GAS PIPING WITH UV RESISTANT PAINT.

FIELD VERIFY EXACT PIPE ROUTING AND POINTS OF

CONNECTION.

5 PROVIDE NEW GROUND-MOUNTED PACKAGED AIR

UNIT IN THIS APPROXIMATE LOCATION. PROVIDE

WITH ALL NEW ELECTRICAL ACCOMMODATIONS BY A

LICENSED DESIGN BUILD ELECTRICIAN. PROVIDE

NEW DUCTWORK THROUGH WALL PENETRATION.

SEAL AND WEATHERPROOF WALL PENETRATION.

PROVIDE OUTDOOR RATED PRE INSULATED, CLOSED

CELL DUCTWORK WITH IMPACT RESISTANT JACKET.

THERAMDUCT OR APPROVED EQUAL ON ALL

EXPOSED DUCTWORK. FIELD VERIFY DIMENSIONS

PRIOR TO COMMENCING WORK. PROVIDE NEW GAS

TRAIN AND PIPING AND TIE INTO EXISTING GAS

PIPING. FIELD VERIFY EXACT ROUTING. PROVIDE

WITH COIL HAIL GUARDS. PROVIDE WITH

OCCUPANCY SENSOR TO TURN ON EXHAUST FAN

AND SWITCH PACKAGED AIR OUTSIDE AIR TO MATCH

EXHAUST FAN RATE WHEN SHOP IS OCCUPIED.

PROVIDE WITH NEW 3" CONCRETE EQUIPMENT CURB.

INSTALL PER MANUFACTURERS RECOMMENDATIONS

FOR A COMPLETE INSTALL.

6 PROVIDE SPIRAL DUCT MOUNTED DIFFUSER IN THIS

APPROXIMATE LOCATION. BALANCE TO CFM SHOWN.

FIELD VERIFY.

7 PROVIDE HIGH WALL-MOUNTED EXHAUST FAN IN

THIS APPROXIMATE LOCATION. PROVIDE WITH NEMA

4 RATED WEATHER HOOD AND BACK DRAFT DAMPER.

PROVIDE WITH 2 SPEED CONTROLLER. PROVIDE

WITH OCCUPANCY SENSOR AND INTERLOCK WITH

NEW PACKAGE AIR UNIT TO RUN OCCUPIED HIGH

FLOW RATE OF 2,750 CFM WHILE OCCUPIED.

BALANCE STANDBY FLOW RATE TO 250 CFM WHILE

UNOCCUPIED. FIELD VERIFY.

8 PROVIDE NEW UL LISTED 2075 CO SENSOR 5' AFF IN

THIS APPROXIMATE LOCATION. TIE INTO AUDIBLE

AND VISABLE ALARM COMBO TO ACTIVATE WHEN CO

OR NO2 IS DETECTED, AUTOMATION COMPONENTS

FSIG-SLM500 OR APPROVED EQUAL. SENSOR SHALL

ACTIVATE HIGH RATE CFM FOR BOTH EXHAUST FAN

AND PACKAGED AIR UNIT. PROVIDE ALL NEW

ELECTRICAL ACCOMMODATIONS. PROVIDE WITH

MEANS FOR MANUAL SILENCE OVERRIDE. FIELD

VERIFY.

9 PROVIDE NEW UL LISTED 2075 NO2 SENSOR 12" AFF

IN THIS APPROXIMATE LOCATION. TIE INTO AN

AUDIBLE AND VISABLE ALARM COMBO TO ACTIVATE

WHEN CO OR NO2 IS DETECTED, AUTOMATION

COMPONENTS FSIG-SLM500 OR APPROVED EQUAL.

SENSOR SHALL ACTIVATE HIGH RATE CFM FOR BOTH

EXHAUST FAN AND PACKAGED AIR UNIT. PROVIDE

ALL NEW ELECTRICAL ACCOMMODATIONS. PROVIDE

WITH MEANS FOR MANUAL SILENCE OVERRIDE.

FIELD VERIFY.

10 PROVIDE EXHAUST GRILLE 8' 6" AFF IN THIS

APPROXIMATE LOCATION. BALANCE TO CFM SHOWN.

PROVIDE WITH BALANCING DAMPERS ABOVE AND

BELOW GRILLE. THE INTENT IS TO PROVIDE A HIGH

AND LOW BALANCED EXHAUST RATE ON EACH

EXHAUST DROP. FIELD VERIFY EXACT POSITIONING.

11 TERMINATE EXHAUST DUCTWORK 12" AFF IN THIS

APPROXIMATE LOCATION. BALANCE EXHAUST TO 275

CFM. COVER OPENING WITH NON CORROSIVE BIRD

SCREEN. THE INTENT IS TO PROVIDE A HIGH AND

LOW BALANCED EXHAUST RATE ON EACH EXHAUST

DROP. FIELD VERIFY EXACT POSITIONING.

12 PROVIDE DUCT MOUNTED RETURN GRILLE IN THIS

APPROXIMATE LOCATION. FIELD VERIFY.

13 PROVIDE 7 DAY-PROGRAMMBLE THERMOSTAT IN

THIS APPROXIMATE LOCATION. PROVIDE WITH

OCCUPANCY SENSORS TO SWITCH FROM

UNOCCUPIED TO OCCUPIED MODE. SWITCH TO

UNOCCUPIED MODE AFTER 30 MIN DELAY. FIELD

VERIFY.

GENERAL NOTES:

1.CONTRACTOR SHALL FIELD VERIFY EXISTING

MECHANICAL, STRUCTURAL, ELECTRICAL AND

ARCHITECTURAL CONDITIONS, INCLUDING, BUT NOT LIMITED

TO: EXISTING ROUTING AND LOCATION OF DUCTWORK,

PIPING, ELECTRICAL, AND STRUCTURAL ELEMENTS.

CONTRACTOR SHALL FIELD VERIFY ANY POTENTIAL

CONFLICTS BETWEEN NEW MECHANICAL ELEMENTS AND

EXISTING CONDITIONS PRIOR TO BEGINNING FABRICATION

OR ORDERING NEW EQUIPMENT.

2. PRIME CONTRACTOR SHALL PROVIDE ALL COORDINATION

BETWEEN SUB-TIER CONTRACTORS. THIS SHALL INCLUDE

THE COORDINATION BETWEEN SUB-TIER CONTRACTORS,

SUB-TIER CONTRACTORS AND FACILITIES, SUB-TIER

CONTRACTORS AND ARCHITECT/ENGINEER, ETC.

KEYPLAN

3. FIELD VERIFY STRUCTURAL COMPONENTS PRIOR TO

CUTTING PENETRATIONS FOR MECHANICAL EQUIPMENT.

AVOID ALL STRUCTURAL COMPONENTS.

4. ALL ROOFING MODIFICATIONS MUST BE DONE THE

ROOFING WARRANTY HOLDING CONTRACTOR. IF

WARRANTY IS EXPIRED, ROOFING MODIFICATIONS MUST BE

BY A DFCM APPROVED SHORT LIST ROOFING CONTRACTOR.

5. ISOMETRIC AND COORDINATION VIEWS ARE FOR

GENERAL LAYOUT ROUTING AND NOT FOR PART COUNT OR

BIDDING PURPOSE. CONTRACTOR SHALL BE REQUIRED TO

PROVIDE ALL PIPING, DUCT, BENDS, FITTINGS,

ACCESSORIES, OFFSETS, ETC AS NEEDED FOR A COMPLETE

INSTALLATION DETERMINED BY THE EXISTING FIELD

VERIFIED CONDITIONS.

6. CONTRACTOR SHALL COORDINATE WITH DFCM PROVIDED

HAZMAT REPORT PRIOR TO THE DEMOLITION OF ANY

EQUIPMENT, DUCTWORK, DUCT INSULATION, PIPING, PIPE

INSULATION, ETC.

7. PROVIDE BALANCING DAMPERS ON ALL SUPPLY AND

RETURN BRANCHES.

8. ALL DEMOLISHED EQUIPMENT AND MATERIAL SHALL BE

BROKEN DOWN TO FIT THROUGH EXISTING DOOR,

OPENINGS, AND HATCHES. FIELD VERIFY EXACT SCOPE OF

DEMOLITION AND REMOVAL PATH. CONTRACTOR SHALL BE

RESPONSIBLE TO REPAIR ANY DAMAGE TO BUILDING

DURING REMOVAL OF EQUIPMENT AND MATERIAL.

9. ALL DUCTWORK LOCATED OUTDOORS SHALL BE PRE-

INSULATED, CLOSED CELL DUCTWORK WITH IMPACT

RESISTANT JACKET. PROVIDE WITH THERMADUCT OR

APPROVED EQUAL.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/21/2025

1/2"ø NGPAU

PAU

GAS METER:

LENGTH 150 FT

CFH: 375

MBH: 309

PRESSURE: 2PSIG

EXISTING WATER HEATER

1 1/4"ø NG (E)

1/2"ø NG (E)

1/2"ø NG

3/4"ø NG

GAS PRESSURE

REGULATOR

2PSIG TO 4OZ

GAS PRESSURE

REGULATOR

2PSIG TO 4OZ

2"

2"

12"C .C.M

AX.

2"

12"C.C.MAX.

ENDS OF LINER SHALL BE

BUTTED FIRMLY TOGETHER.

ALL JOINTS, SEAMS, AND TEARS

SHALL BE COATED W/ ADHESIVE

DURING INSTALLATION.

NOT MORE THAN 2"

FROM EDGE OF LINER.

ALL ENDS OF LINER TO

BE COATED W/ ADHESIVE

DUCTLINER

ONE INCH THICK 1-1/2 LB

DENSITY FIBERGLASS.

TOP AND BOTTOM

SECTIONS OF LINER

SHALL OVERLAP THE

SIDES

GRIP NAILS SHALL BE

INSTALLED BY AIR

HAMMER OR BY

AUTOMATIC FASTENER

EQUIPMENT.

INSULATED PINS, FASTENERS

OR GRIP NAILS.

1" THICK

DUCT LINER

METAL FASTENERS

SHEET METAL DUCT

INSULATION SHALL HAVE A MINIMUM

R-VALUE OF 5 FOR INDOOR AND 8 FOR

OUTDOOR INSTALLATION.

#10 x 3/4" SELF

TAPPING CADMIUM PLATED

SHEET METAL SCREWS TO

ANCHOR STRAPS TO DUCT.

ALL STRAPS TO BE TIGHT

AGAINST DUCT AND SUPPORT

MEMBERS. (TYPICAL)

1"

1" x 18 GAUGE STRAP

HANGERS AT 8'-0"

SPACING.

1" x 18 GAUGE STRAP

HANGERS AT 8'-0"

SPACING.

NO POP RIVETS

ALLOWED

NOTES:

1. DUCT OUTSIDE OF BUILDING

ENVELOPE SHALL BE WRAPPED

EXTERNALLY AS PER THE

SPECIFICATIONS.

2. SEE SPECIFICATIONS SECTION

15074 FOR SEISMIC RESTRAINT

REQUIREMENTS.

ATTACH SECURELY TO

STRUCTURE.

1" x 16 GA.

HANGER STRAP

1" x 18 GA.

HANGER STRAP

SIZE PER

SMACNA

NOTE:

MAXIMUM

SPACING OF 10'-0"

ATTACH HANGER STRAPS

TO STRUCTURE

SHEET METAL SCREW

3/8" BOLT

DUCT

DUCTS < 20"ø

20" DIA TO 36" DIA.

DUCTS > 36"ø

HANGERS MUST NOT DEFORM DUCT SHAPE

NOTE:

SEE SPECIFICATIONS

SECTION 15074 FOR SEISMIC

RESTRAINTREQUIREMENTS.

D

RETURN AIR FLOW

MAIN AIR DUCT

SUPPLY AIR FLOW

R

LOCKING QUADRANT

HANDLE OR REMOTE

CEILING OPERATOR

WHERE DAMPER

IS INACCESSIBLE.

FASTEN RIGID DUCT

TO FITTING W/ #10x3/4"

SHEET METAL SCREWS.

DO NOT INTERFERE W/

VOLUME DAMPER

OPERATION.

AIR

BRANCH

DUCT (TYP.)

SIZE CUT OUT ACCORDING

TO MANUFACTURERS

RECOMMENDATIONS.

INSULATION NOT

SHOWN SEE

SPECIFICATIONS

22GA. RIGID SHEET METAL

WRAPPED WITH

INSULATION.

NEOPRENE BUSHING

EACH END

#10x3/4" SHEET METAL

SCREWS

SEAL SEAM WITH

HARD-CAST

DUCT SEALER

22 GA. BLADE

3/8" SQUARE ROD

45°

HANGER ROD

HANGER ROD

16 GA. ZINC COATED

SHEET STEEL SADDLE

AT LEAST 12" LONG.

VAPOR BARRIER

INSULATION

PIPE

45°

INSULATION WITH OR

WITHOUT VAPOR BARRIER

HEAVY DUTY

CLEVIS HANGER 16 GA. ZINC COATED

SHEET STEEL SHIELD

AT LEAST 12" LONG.

HANGER ROD, ATTACH

TO OVERHEAD STRUCTURE

LOCKING NUT

SUPPORT NUT

PIPE

CALCIUM SILICATE

BLOCK TYPICAL

CONNECT TO STRUCTURE

MAX. 1/4" SLACK.

PULL HAND TIGHT

PRE-STRECHED, COLOR CODED

CERTIFIED BREAK STRENGTH CABLE

(2) CABLES PER RESTRAINT PACKAGE

45°

CONNECT TO

STRUCTURE

DETAIL NOTES:

1.SEE SPECIFICATION SECTION 15074

FOR SEISMIC BRACING REQUIREMENTS.

TURNBUCKLE WITH 3"

ADJUSTMENT - BY

HEATER MANUFACTURER

3/8 " THREADED ROD - BY MC

NUT - BY MC

ADJUSTABLE BEAM

CLAMP OR "U" BOLT WITH

CHAIR ANCHOR - BY MC

DETAIL NOTES:

1. PROVIDE UNISTRUT SUPPORT BETWEEN ROOF

JOISTS AS REQUIRED FOR SUPPORT.

V E

R T

IC

A

L

GAS SUPPLY

MANUAL

SHUT-OFF

VALVE

GAS PRESSURE

REGULATOR

(2 PSI TO 4 OZ)

DRIP LEG

GROUND

JOINT

UNION

EQUIPMENT

CONNECTION

FLEXIBLE GAS

CONNECTOR

18" MAX.

CAP

MIN 10 PIPE

DIAMETERS

NOTE: COORDINATE WITH

MANUFACTURER FOR GAS

REQUIREMENTS

HANGER ROD

PIPE

HANGER

SUPPORT NUT

LOCKING NUT

CALCIUM SILICATE BLOCK

16 GA. ZINC COATED SHEET

STEEL SHIELD AT LEAST 12" LONG

(TYP)

MOUNT PIPING TO UNISTRUT

PROVIDE PIPE CLAMPS

WITH BOLTS AND NUTS

CALCIUM SILICATE

BLOCK

CALCIUM SILICATE

BLOCK

BOLT UNISTRUT TO EXISTING

WALL AND CONCRETE USING

EXPANSION ANCHOR BOLTS

ATTACH TO ROOM

OVERHEAD STRUCTURE

SPRING TYPE ISOLATOR

FOR INSTALLATION

NEAR HOT WATER

PUMPS

CLEVIS HANGER

INSULATION

16 GAGE ZINC

COATED SHEET

STEEL SHIELD AT

LEAST 12" LONG.

HEAVY DUTY

CLEVIS HANGER

HEAVY DUTY

CLEVIS HANGER

PIPE

SINGLE HORIZONTAL RUN

WITHOUT INSULATION

CLEVIS HANGER

ATTACH TO EXISTING

CEILING

INSULATION WITH OR WITHOUT

VAPOR BARRIER

NOTE:

PROVIDE WITH VAPOR BARRIER

ON CHILLED WATER AND

DOMESTIC COLD WATER PIPING

HANGER ROD

SUPPORT NUT

LOCKING NUT

SEF

O

R P

HATUFOETATS

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities

Department of Administrative Services

Internet: http://www.dfcm.state.ut.us

State of Utah A

LL

ID

E A

S , D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D

E V

O

LV

E D

A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

D

E S

IG

N

S

A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

F

IC

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O F

F E

N S

E U

N D

E R

U .S

.C . S

E C

. 5

. U N

A U

T H

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U T

E T

R A

D E

S E

C R

E T

M

IS

A P

P R

O P

R

IA

T

IO

N

IN

V

IO

LA

T

IO

N

O F

I.

C

.2 4-

2-

-1 E

T . S

E Q

. A N

D O

T H

E R

L A

W S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/08/2025

WHW JOB NO.:

25078

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

SHEET TITLE

E E

WP

STAFF

CL

733 S Cowboy Way Kanab, UT 84741

SWATC KANAB

SHOP

MECHANICAL

UPGRADE

DFCM #26066270

08/08/25

MECHANICAL DETAILS

ME501

SCALE: NONE

1 NATURAL GAS ISOMETRIC

SCALE: NONE

DUCT LINER DETAIL

SCALE: NONE

DUCT STRAP HANGER DETAIL

SCALE: NONE

4 ROUND DUCT SUPPORT DETAIL

SCALE: NONE

ROUND-TO-ROUND DUCT CONSTRUCTION DETAIL

SCALE: NONE

6 SEISMIC SWAY BRACING DETAILS

SCALE: NONE

SUSPENSION DETAIL

SCALE: NONE

8 GAS LINE CONNECTION DETAIL

SCALE: NONE

9 PIPE HANGER DETAIL

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/21/2025

SMOKE SENSORS IN SUPPLY

AND RETURN AIR DUCTS WHERE

REQUIRED.

S

MOUNT ON LEGS

OR RAILS

MOUNT ON SPRING ISOLATORS

PROVIDE EXTERIOR 1-1/2"

INSULATION AND ALUMINUM

JACKET AT EXTERIOR

EXPOSED DUCT.

PROVIDE EXTERIOR WALL

PENETRATION. FLASH AND

SEAL WEATHER TIGHT

CONDENSATE DRAIN AND TRAP.

TYPICAL

ROOFTOP UNIT

ECONOMIZER

PROVIDE FLEXIBLE

DUCT CONNECTION.

4" CONCRETE PAD

S

TRANSITION DUCT AS NECESSARY

TO PENETRATE WALL AT CRAWL

SPACE LEVEL.

DRUM LOUVERS

MANUAL BALANCING

DAMPER W/ LOCKING

QUADRANT, MAY BE A

PART OF DRUM LOUVER.

SEAL DUCT

CONNECTION

MAIN AIR

ROUND DUCT

1/

2" W

ID

E

R U N N E R

F

LO

W

A

IR

SINGLE THICKNESS

TURNING VANES

LEADING AND TRAILING

EDGE TO BE PARALLEL

WITH SIDE OF DUCT.

1" LONG MINIMUM

TRAILING EDGE

COORDINATE

OPENING WITH G.C.

NEW WALL

BACKDRAFT DAMPER SET

TO OPEN FROM EXHAUST

FAN DISCHARGE PRESSURE.

ATTACH TO WALL WITH

1-1/2" SCREWS AND

INSERTS.

EXHAUST FAN

FRAME AND HOUSING.

INLET SCREEN

NEMA 4

WEATHERPROOF

HOOD

AND FRAME.

BALANCING DAMPER.

SET TO ALLOW

SCHEDULED

CFM TO BE EXHAUSTED.

BOLT FRAME OF FAN

HOUSING TO SUPPORT

FRAME WITH 1/4"Ø

BOLTS.

2"x2"x1/8" ANGLE

SUPPORT FRAME.

WELD ALL

AROUND.

ATTACH TO WALL

WITH 3/8"x2" LAG

BOLTS AND

INSERTS

WALL

UNISTRUT ANCHORED TO WALL

UNISTRUT CLAMP

GAS PIPING

SEF

O

R P

HATUFOETATS

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities

Department of Administrative Services

Internet: http://www.dfcm.state.ut.us

State of Utah A

LL

ID

E A

S , D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D

E V

O

LV

E D

A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

D

E S

IG

N

S

A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

F

IC

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O F

F E

N S

E U

N D

E R

U .S

.C . S

E C

. 5

. U N

A U

T H

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U T

E T

R A

D E

S E

C R

E T

M

IS

A P

P R

O P

R

IA

T

IO

N

IN

V

IO

LA

T

IO

N

O F

I.

C

.2 4-

2-

-1 E

T . S

E Q

. A N

D O

T H

E R

L A

W S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/08/2025

WHW JOB NO.:

25078

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

SHEET TITLE

E E

WP

STAFF

CL

733 S Cowboy Way Kanab, UT 84741

SWATC KANAB

SHOP

MECHANICAL

UPGRADE

DFCM #26066270

08/08/25

MECHANICAL DETAILS

ME502

SCALE: NONE

1 DRUM LOUVER DETAIL

SCALE: NONE

2 TURNING VANE DETAIL

SCALE: NONE

3 WALL MOUNTED EXHAUST FAN DETAIL

1/8" = 1'-0"

GAS LINE WALL ANCHOR DETAIL

1/8" = 1'-0"

ME501

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/21/2025

1. PROVIDE SMOKE DETECTOR IN SUPPLY AND RETURN AIR FOR ALL UNITS OVER 2,000 CFM.

2. RATED MINIMUM INPUT AT 5000'.

3. PROVIDE ONE 15 AMP, 120 VOLT, DUPLEX GFCI SERVICE OUTLET. FACTORY INSTALLED, FIELD WIRED.

4. ESP DOES NOT INCLUDE LOSSES THROUGH ACCESSORIES.

5. BELT DRIVE UNIT.

6. PROVIDE 100% OUTSIDE AIR ECONOMIZER.

7. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.

8. PROVIDE VOLTAGE AND PHASE MONITORS.

9. PROVIDE WITH COIL HAIL GUARDS.

10. SET OUTSIDE AIR TO 1300 CFM WHILE OCCUPIED AND WHEN EXHAUST SYSTEM IS RUNNING. SET STANDBY OUTSIDE AIR TO 260 CFM WHILE UNOCCUPIED.

11. PROVIDE WITH POWERED EXHAUST.

12. PROVIDE WITH COMPRESSOR BLANKETS FOR NOISE DAMPENING. COPELAND SOUND SHELL OR APPROVED EQUAL.

1. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.

2. FINISH SHALL BE STANDARD WHITE.

1. PROVIDE WITH 2 SPEED CONTROLLER. RUN HIGH LIMIT CFM WHILE OCCUPIED. TIE INTO OCCUPANCY SENSOR. RUN STANDBY CFM WHILE UNOCCUPIED.

2. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.

SEF

O

R P

HATUFOETATS

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities

Department of Administrative Services

Internet: http://www.dfcm.state.ut.us

State of Utah A

LL

ID

E A

S , D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D

E V

O

LV

E D

A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

D

E S

IG

N

S

A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

F

IC

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O F

F E

N S

E U

N D

E R

U .S

.C . S

E C

. 5

. U N

A U

T H

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U T

E T

R A

D E

S E

C R

E T

M

IS

A P

P R

O P

R

IA

T

IO

N

IN

V

IO

LA

T

IO

N

O F

I.

C

.2 4-

2-

-1 E

T . S

E Q

. A N

D O

T H

E R

L A

W S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/08/2025

WHW JOB NO.:

25078

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

SHEET TITLE

E E

WP

STAFF

CL

733 S Cowboy Way Kanab, UT 84741

SWATC KANAB

SHOP

MECHANICAL

UPGRADE

DFCM #26066270

08/08/25

MECHANICAL

SCHEDULES

ME601

DIFFUSER AND GRILLE SCHEDULE

TAG

MAX

FLOW

FACE SIZE NECK SIZE

CEILING

TYPE

BLOW

PATTERN

THROW @

50 FPM MAX NC

MANUF &

MODEL

SCHEDULE

NOTESLENGTH WIDTH

LENGTH/

DIAMETER WIDTH

D-1 2,800 CFM 12" 6" 12" 6" DUCT

MOUNTED

0 38' 25 PRICE

HCD

1,2

EG-1 350 CFM 18" 6" 18" 6" SPIRAL 0 0' 25 PRICE

SDGER

1,2

R-1 2,800 CFM 42" 18" 40" 16" DUCT

MOUNTED

N/A 0' 25 PRICE 95 1,2

PACKAGED AIR UNIT SCHEDULE

TAG

AREA

SERVED CFM

OCCUPIED

CFM (OUTSIDE

AIR)

STANDBY

CFM

(OUTSIDE

AIR) ESP

HEATING COOLING ELECTRICAL

ARI EER (7.5+

TON)

OPERATING

WEIGHT MANUF & MODEL SCHEDULE NOTESTYPE #

INPUT

(BTU/HR)

OUTPUT

(BTU/HR) EAT (DB) EAT (WB)

TOTAL LOAD

(BTU/HR) VOLTAGE PHASE

FREQUENC

Y

# OF

COMPRESSORS MCA MOCP

PAU 1 SERVICE

CENTER

2,400 CFM 1,300 CFM 480 CFM 1.5 in-wg 53,600 Btu/h

43,200 Btu/h

80 °F 62 °F 60000 Btu/h 208 V 3 60 Hz 1 34 A 50 A 11.2 607 lb CARRIER

48FEDM07C3A5

1,2,3,4,5,6,7,8,9,10,11,12

PAU 2 SERVICE

CENTER

2,400 CFM 1,300 CFM 480 CFM 1.5 in-wg 53,600 Btu/h

43,200 Btu/h

80 °F 62 °F 60000 Btu/h 208 V 3 60 Hz 1 34 A 50 A 11.2 607 lb CARRIER

48FEDM07C3A5

1,2,3,4,5,6,7,8,9,10,11,12

EXHAUST FAN SCHEDULE

TAG AREA

SERVED

HIGH

LIMIT CFM

STANDBY

CFM ESP

ELECTRICAL MAX

SONES

OPERATING

WEIGHT MANUF & MODEL

SCHEDULE

NOTESTYPE # VOLTAGE PHASE FREQUENCY RPM HP FLA

EF 1 SERVICE

CENTER

2,750 CFM 250 CFM 0.30 in-wg 120 V 1 60 Hz 1600 1 hp 16 11.5 83 lb GREENHECK

AER-24-02-0515-VG

1,2

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/21/2025

R-1

R-1

20"x20" RA

20"x20" RA

20"ø SA20"ø SA

PAU

PAU

D-1

TYP 24

EF

EG-1

EG-1

EG-1

EG-1

EG-1

2 2

20"ø EA12"ø EA

12"ø EA

12"ø EA

12"ø EA

12"ø EA

12"ø EA

BD

BD

BD

BD

BD

BD

BD

BD

BD

BD

S

CO

S

NO2

SEF

O

R P

HATUFOETATS

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities

Department of Administrative Services

Internet: http://www.dfcm.state.ut.us

State of Utah A

LL

ID

E A

S , D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D

E V

O

LV

E D

A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

D

E S

IG

N

S

A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

F

IC

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O F

F E

N S

E U

N D

E R

U .S

.C . S

E C

. 5

. U N

A U

T H

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U T

E T

R A

D E

S E

C R

E T

M

IS

A P

P R

O P

R

IA

T

IO

N

IN

V

IO

LA

T

IO

N

O F

I.

C

.2 4-

2-

-1 E

T . S

E Q

. A N

D O

T H

E R

L A

W S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/08/2025

WHW JOB NO.:

25078

A

B

C

D

2 3 4

1 2 3 4

A

B

C

D

SHEET TITLE

E E

WP

STAFF

CL

733 S Cowboy Way Kanab, UT 84741

SWATC KANAB

SHOP

MECHANICAL

UPGRADE

DFCM #26066270

08/08/25

MECHANICAL

ISOMETRICS

ME901

MECHANICAL ISOMETRIC

MECHANICAL EXHAUST AIR SWEEP

ISOMETRIC

SHEET NOTES

1 PROVIDE EXHAUST GRILLE 8' 6" AFF IN THIS

APPROXIMATE LOCATION. BALANCE TO CFM SHOWN.

PROVIDE WITH BALANCING DAMPERS ABOVE AND

BELOW GRILLE. THE INTENT IS TO PROVIDE A HIGH

AND LOW BALANCED EXHAUST RATE ON EACH

EXHAUST DROP. FIELD VERIFY EXACT POSITIONING.

2 TERMINATE EXHAUST DUCTWORK 12" AFF IN THIS

APPROXIMATE LOCATION. BALANCE EXHAUST TO 275

CFM. COVER OPENING WITH NON CORROSIVE BIRD

SCREEN. THE INTENT IS TO PROVIDE A HIGH AND

LOW BALANCED EXHAUST RATE ON EACH EXHAUST

DROP. FIELD VERIFY EXACT POSITIONING.

3 PROVIDE HIGH WALL-MOUNTED EXHAUST FAN IN

THIS APPROXIMATE LOCATION. PROVIDE WITH NEMA

4 RATED WEATHER HOOD AND BACK DRAFT DAMPER.

PROVIDE WITH 2 SPEED CONTROLLER. PROVIDE

WITH OCCUPANCY SENSOR AND INTERLOCK WITH

NEW PACKAGE AIR UNIT TO RUN OCCUPIED HIGH

FLOW RATE OF 2,750 CFM WHILE OCCUPIED.

BALANCE STANDBY FLOW RATE TO 250 CFM WHILE

UNOCCUPIED. FIELD VERIFY.

4 PROVIDE NEW GROUND-MOUNTED PACKAGED AIR

UNIT IN THIS APPROXIMATE LOCATION. PROVIDE

WITH ALL NEW ELECTRICAL ACCOMMODATIONS BY A

LICENSED DESIGN BUILD ELECTRICIAN. PROVIDE

NEW DUCTWORK THROUGH WALL PENETRATION.

SEAL AND WEATHERPROOF WALL PENETRATION.

PROVIDE OUTDOOR RATED PRE INSULATED, CLOSED

CELL DUCTWORK WITH IMPACT RESISTANT JACKET.

THERAMDUCT OR APPROVED EQUAL ON ALL

EXPOSED DUCTWORK. FIELD VERIFY DIMENSIONS

PRIOR TO COMMENCING WORK. PROVIDE NEW GAS

TRAIN AND PIPING AND TIE INTO EXISTING GAS

PIPING. FIELD VERIFY EXACT ROUTING. PROVIDE

WITH COIL HAIL GUARDS. PROVIDE WITH

OCCUPANCY SENSOR TO TURN ON EXHAUST FAN

AND SWITCH PACKAGED AIR OUTSIDE AIR TO MATCH

EXHAUST FAN RATE WHEN SHOP IS OCCUPIED.

PROVIDE WITH NEW 3" CONCRETE EQUIPMENT CURB.

INSTALL PER MANUFACTURERS RECOMMENDATIONS

FOR A COMPLETE INSTALL.

5 PROVIDE NEW RETURN GRILLE IN THIS

APPROXIMATE LOCATION. FIELD VERIFY.

6 PROVIDE RETURN AIR DUCTWORK IN THIS

APPROXIMATE LOCATION. KEEP 8' AFF. FIELD VERIFY

EXACT DUCT ROUTING.

7 PROVIDE SPIRAL DUCT MOUNTED DIFFUSER IN THIS

APPROXIMATE LOCATION. BALANCE TO CFM SHOWN.

FIELD VERIFY.

8 PROVIDE NEW UL LISTED 2075 NO2 SENSOR 12" AFF

IN THIS APPROXIMATE LOCATION. TIE INTO AN

AUDIBLE AND VISABLE ALARM COMBO TO ACTIVATE

WHEN CO OR NO2 IS DETECTED, AUTOMATION

COMPONENTS FSIG-SLM500 OR APPROVED EQUAL.

SENSOR SHALL ACTIVATE HIGH RATE CFM FOR BOTH

EXHAUST FAN AND PACKAGED AIR UNIT. PROVIDE

ALL NEW ELECTRICAL ACCOMMODATIONS. PROVIDE

WITH MEANS FOR MANUAL SILENCE OVERRIDE.

FIELD VERIFY.

9 PROVIDE NEW UL LISTED 2075 CO SENSOR 5' AFF IN

THIS APPROXIMATE LOCATION. TIE INTO AUDIBLE

AND VISABLE ALARM COMBO TO ACTIVATE WHEN CO

OR NO2 IS DETECTED, AUTOMATION COMPONENTS

FSIG-SLM500 OR APPROVED EQUAL. SENSOR SHALL

ACTIVATE HIGH RATE CFM FOR BOTH EXHAUST FAN

AND PACKAGED AIR UNIT. PROVIDE ALL NEW

ELECTRICAL ACCOMMODATIONS. PROVIDE WITH

MEANS FOR MANUAL SILENCE OVERRIDE. FIELD

VERIFY.

GENERAL NOTES:

1.CONTRACTOR SHALL FIELD VERIFY EXISTING

MECHANICAL, STRUCTURAL, ELECTRICAL AND

ARCHITECTURAL CONDITIONS, INCLUDING, BUT NOT LIMITED

TO: EXISTING ROUTING AND LOCATION OF DUCTWORK,

PIPING, ELECTRICAL, AND STRUCTURAL ELEMENTS.

CONTRACTOR SHALL FIELD VERIFY ANY POTENTIAL

CONFLICTS BETWEEN NEW MECHANICAL ELEMENTS AND

EXISTING CONDITIONS PRIOR TO BEGINNING FABRICATION

OR ORDERING NEW EQUIPMENT.

2. PRIME CONTRACTOR SHALL PROVIDE ALL COORDINATION

BETWEEN SUB-TIER CONTRACTORS. THIS SHALL INCLUDE

THE COORDINATION BETWEEN SUB-TIER CONTRACTORS,

SUB-TIER CONTRACTORS AND FACILITIES, SUB-TIER

CONTRACTORS AND ARCHITECT/ENGINEER, ETC.

3. FIELD VERIFY STRUCTURAL COMPONENTS PRIOR TO

CUTTING PENETRATIONS FOR MECHANICAL EQUIPMENT.

AVOID ALL STRUCTURAL COMPONENT.

4. ALL ROOFING MODIFICATIONS MUST BE DONE THE

ROOFING WARRANTY HOLDING CONTRACTOR. IF

WARRANTY IS EXPIRED, ROOFING MODIFICATIONS MUST BE

BY A DFCM APPROVED SHORT LIST ROOFING CONTRACTOR.

5. ISOMETRIC AND COORDINATION VIEWS ARE FOR

GENERAL LAYOUT ROUTING AND NOT FOR PART COUNT OR

BIDDING PURPOSE. CONTRACTOR SHALL BE REQUIRED TO

PROVIDE ALL PIPING, DUCT, BENDS, FITTINGS,

ACCESSORIES, OFFSETS, ETC AS NEEDED FOR A COMPLETE

INSTALLATION DETERMINED BY THE EXISTING FIELD

VERIFIED CONDITIONS.

6. CONTRACTOR SHALL COORDINATE WITH DFCM PROVIDED

HAZMAT REPORT PRIOR TO THE DEMOLITION OF ANY

EQUIPMENT, DUCTWORK, DUCT INSULATION, PIPING, PIPE

INSULATION, ETC.

7. PROVIDE BALANCING DAMPERS ON ALL SUPPLY AND

RETURN BRANCHES.

8. ISOMETRIC AND COORDINATION VIEWS ARE FOR

GENERAL LAYOUT ROUTING AND NOT FOR PART COUNT OR

BIDDING PURPOSE. CONTRACTOR SHALL BE REQUIRED TO

PROVIDE ALL PIPING, DUCT, BENDS, FITTINGS,

ACCESSORIES, OFFSETS, ETC AS NEEDED FOR A COMPLETE

INSTALLATION DETERMINED BY THE EXISTING FIELD

VERIFIED CONDITIONS.

9. ALL DUCTWORK LOCATED OUTDOORS SHALL BE PRE-

INSULATED, CLOSED CELL DUCTWORK WITH IMPACT

RESISTANT JACKET. PROVIDE WITH THERMADUCT OR

APPROVED EQUAL.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

08/21/2025

Sheets
G001 - TITLE
ME101 - MECHANICAL PLAN
ME501 - MECHANICAL DETAILS
ME502 - MECHANICAL DETAILS
ME601 - MECHANICAL SCHEDULES
ME901 - MECHANICAL ISOMETRICS
MG001 - MECHANICAL LEGEND AND GENERAL NOTES
MG002 - SPECIAL INSTRUCTIONS AND TESTING

File details come from the government source that posted it. Updated .