This is an approved mechanical construction plans document for the State of Utah Division of Facilities Construction and Management (DFCM) for the Southwest Technical College (SWATC) Kanab Shop Mechanical Upgrade project (DFCM #26066270). The project involves removal of two existing evaporative coolers and infrared heaters, which will be replaced with two new ground-mounted packaged air handling units complete with associated ductwork. Additionally, a new wall-mounted exhaust fan with ductwork will be installed to support improved ventilation and bring the facility into current code compliance. The project is located at 733 S. Cowboy Way, Kanab, Utah 84741, at a 3,500 square foot single-story S-1 occupancy building with a height of 19'1". The approved plans include mechanical legend and general notes (sheet MG001), special instructions and testing (sheet MG002), mechanical plans (sheet ME101), mechanical details (sheets ME501-ME502), mechanical schedules (sheet ME601), and mechanical isometrics (sheet ME901). The work must comply with the 2021 International Mechanical Code (IMC) and International Plumbing Code (IPC) with Utah annotations, and all seismic design requirements must follow ASCE 7-05 standards with deferred submittals required approximately 15 days after notice to proceed.
The construction cost estimate for the project is $114,956.00. Only contractors prequalified under a Stage I Prequalification for Contractors and currently listed on the DFCM Prequalified Contractors list are eligible to bid on this Stage II Invitation to Bid. The plans specify that the mechanical contractor shall contract with a design-build electrical contractor for all electrical design and installation per the 2020 National Electrical Code, with all new control wiring and electrical feeders to be run in appropriately sized conduit. Key mechanical equipment specifications include two Carrier 48FEDM07C3A5 packaged air units each capable of 2,400 CFM occupied capacity with 1,300 CFM outside air and 480 CFM standby outside air, and one Greenheck AER-24-02-0515-VG exhaust fan with 2,750 CFM high-limit and 250 CFM standby capacity. New gas piping will tie into existing infrastructure with a gas meter rated for 375 CFH and 309 MBH. The project requires field verification of existing conditions, structural coordination for all penetrations, and coordination with a DFCM-approved roofing contractor for any roof modifications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SWATC KANAB
733 S. COWBOY WAY
KANAB, UT 84741
GENERAL:
G001--- TITLE SHEET
G002--- SPECIAL INSPECTIONS AND TESTING
MECHANICAL:
MG001 - MECHANICAL GENERAL NOTES AND LEGEND
ME101 - MECHANICAL PLAN
ME501 - MECHANICAL DETAILS
ME502 - MECHANICAL DETAILS
ME601 - MECHANICAL SCHEDULES
ME901 - MECHANICAL ISOMETRICS
DRAWING INDEX:
DEFERRED SUBMITTALS :
1. SEISMIC ENGINEER SHALL PROVIDE A SUBMITTAL INCLUDING
CALCULATIONS AND DETAILS TO THE DFCM BUILDING OFFICIALS
FOR REVIEW. SEISMIC SHALL BE DESIGNED TO RESIST THE EFFECTS
OF EARTHQUAKE MOTIONS IN ACCORDANCE WITH ASCE 7-05.
REFERENCE IBC SECTION 1613.1.
2. THE DATE OF DEFERRED SUBMITTALS IS APPROXIMATELY 15 DAYS AFTER
NOTICE TO PROCEED. MECHANICAL WORK CANNOT COMMENCE UNTIL THE
DFCM BUILDING OFFICIALS HAVE APPROVED THE SEISMIC
SUBMITTALS.
3. EACH DEFERRED SUBMITTAL IS REQUIRED TO HAVE THE PROJECT
NAME, DFCM NUMBER, PROJECT ADDRESS, CONFORMANCE LETTER
OR STAMP FROM THE DESIGNER AND A 3"x3" SPACE FOR THE
APPROVAL STAMP ON THE FRONT PAGE.
SPECIAL INSPECTIONS:
1. SEE SHEET DRAWING G002.
DESIGN CRITERIA:
THESE DOCUMENTS - DRAWINGS AND SPECIFICATIONS COMPLY WITH ALL THE
REQUIREMENTS OF THE DFCM STANDARDS FOR MECHANICAL UPGRADES OF
EXISTING BUILDING.
CODE INSPECTION REQUIREMENTS:
1. BEFORE A FINAL ACCEPTANCE CAN BE ISSUED, THE STATE APPOINTED CODE
INSPECTOR SHALL PROVIDE A FINAL REPORT RECOMMENDING THAT THE NEW
MECHANICAL WORK IS IN COMPLIANCE WITH THE DRAWINGS, SPECIFICATIONS
AND APPLICABLE CODES ESPECIALLY FOR THE FOLLOWING ITEMS.
a.)SEISMIC - MECHANICAL AND ELECTRICAL PER DEFERRED SUBMITTALS.
2. SEE ALSO SHEET G002.
PROJECT SCOPE:
THIS PROJECT INVOLVES THE REMOVAL OF TWO
EXISTING EVAPORATIVE COOLERS AND INFRARED
HEATERS CURRENTLY SERVING THE BUILDING. THESE
SYSTEMS WILL BE REPLACED WITH TWO NEW
GROUND-MOUNTED PACKAGED AIR HANDLING UNITS,
COMPLETE WITH ALL NEW ASSOCIATED DUCTWORK.
ADDITIONALLY, A NEW WALL-MOUNTED EXHAUST FAN
AND DUCTWORK WILL BE INSTALLED TO SUPPORT
IMPROVED VENTILATION.
SWATC KANAB SHOP
MECHANICAL UPGRADE
DFCM# 26066270
G001
CODE REVIEW STAMP
North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a
3) Three Story: A (3)______
2) Two Story: A (2)______
1) One Story: ______
c) Total Allowable Area for:
1_< Allowable Area
Actual Area
b) Sum of the Ratio Calculations for Mixed Occupancies:
a) 0.25I = 100f
F
P stA I
100100 fIA t taA = A + +
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
d) Drinking Fountains: ______ Service Sinks: ______
c) Bath Tubs or Showers: ______
b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: ______ Exit Width Provided: ______
Element Listing
Element AssemblyHours
Smoke Partitions
Fire Partitions
Exterior Bearing Walls
Interior Bearing Walls
Exterior Non-Bearing Walls
Structural Frame Partitions - Permanent
Fire Barriers
Floors - Ceiling Floors
Roofs - Ceiling Roofs
Exterior Doors and Windows Shaft Enclosures
Fire Walls
AHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: ______
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:
____________________________________________Tabular Area:
per Floor (square feet): ________3,500 SQ FT__________________Actual Area
Number of Stories: ___1___ Building Height: ___19' 1"__
Required: ______ Provided: ______ Type of Sprinkler System: ____________
Sprinklers:
Mixed Occupancies: ______ Nonseparated Uses: ______ separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance Rating
C. Type of Construction (circle one):
Change in Use: Yes ______ No ___x___ Mixed Occupancy: Yes ______ No ______
A. Occupancy and Group: __S-1_____ ________ ________ ________ _____
CODE ANALYSIS
Guidelines
ADA Accessibility Building Conservation
Uniform Code for
National Electrical Code
Conservation Code
International Energy International Fire Code
International Plumbing Code
International Mechanical Code
International Building Code
Year
APPLICABLE CODES
B
SEF
O
R P
HATUFOETATS
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
08.08.25
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/21/2025
REVIEWED FOR CODE
COMPLIANCE
M
M
P
T
S
PS
IBT
T
TT
F&T
F
MECHANICAL LEGEND
SYMBOL ABR, DESCRIPTION
GENERAL TERMINOLOGY
A
ME101
SECTION LETTER DESIGNATION
SECTION DRAWN ON THIS SHEET
A2
AH
DETAIL NUMBER DESIGNATION
CORRESPONDING WITH GRID
LOCATION
MECHANICAL EQUIPMENT DESIGNATION
EQUIPMENT ITEM DESIGNATION
REGISTER, GRILLE OR DIFFUSER
DESIGNATION WITH BALANCING CFM
LISTED BELOW
D-1
CFM
GRILLE OR LOUVER DESIGNATION
WHERE BALANCING NOT REQUIREDR-1
REVISION DESIGNATOR AND NUMBER
KEY NOTE DESIGNATOR AND NUMBER
POINT OF CONNECTION
POINT OF REMOVAL
ABOVE FINISHED FLOOR
ACCESS PANEL
CENTERLINE ELEVATION
GENERAL CONTRACTOR
AFF
AP
POC
POR
C EL.
GC
MECHANICAL CONTRACTORMC
CONTROLS CONTRACTORATC
ELECTRICAL CONTRACTOREC
FIRE PROTECTION CONTRACTORFPC
NOT IN CONTRACTNIC
NOT TO SCALENTS
VITRIFIED CLAY PIPEVCP
NORMALLY CLOSEDNC
COMMONC
NORMALLY OPENNO
SYMBOL ABR, DESCRIPTION
AIR SIDE
EXISTING AIR DUCT TO BE REMOVED
EXISTING AIR DUCT TO REMAIN
NEW AIR DUCT
RECT TO RECT AIR DUCT TAKE-OFF
RECT TO RND AIR DUCT TAKE-OFF
RND TO RND AIR DUCT TAKE-OFF
MEDIUM PRESSURE TAKE-OFF
FLEXIBLE AIR DUCT
LINED DUCT
RADIUS ELBOW
ECCENTRIC DUCT TRANSITION
CONCENTRIC DUCT TRANSITION
VOLUME DAMPER
SUPPLY AIR DIFFUSER
RETURN & TRANSFER AIR GRILLE
EXHAUST GRILLE OR CEILING EXH. FAN
RETURN & OUTSIDE AIR DUCT UP/DN
RETURN & OA ROUND DUCT UP/DN
SUPPLY AIR DUCT UP/DN
SUPPLY AIR ROUND DUCT UP/DN
EXHAUST AIR DUCT UP/DN
EXHAUST AIR ROUND DUCT UP/DN
ACCESS PANELAP
EXISTING EQUIPMENT TO BE REMOVED
EXISTING EQUIPMENT TO REMAIN
NEW EQUIPMENT
SUPPLY AIR
RETURN AIRRA
SA
EXHAUST AIREA
OUTSIDE AIROA
MIXED AIRMA
RELIEF AIRRF
FLAT OVALFO
MOTORIZED VOLUME DAMPER
BACKDRAFT DAMPER
FIRE DAMPER
SMOKE DAMPER
FIRE & SMOKE DAMPER
WALL MOUNTED THERMOSTAT
WALL MOUNTED TEMP. SENSOR
WALL MOUNTED HUMIDISTAT
WALL MOUNTED FIRESTAT
M
BD
F
S
FS
T
S
H
F
SYMBOL ABR, DESCRIPTION
WET SIDE
PUMP
MVD
BD
FD
SD
FS
T-STAT
H-STAT
F-STAT
REGULATOR
UNION
MANUAL ACTUATOR
PNUEMATIC DIAPHRAM ACTUATOR
ELECTRIC MOTOR ACTUATOR
SOLENOID ACTUATOR
BUTTERFLY VALVE
GATE VALVE
GLOBE VALVE - STRAIGHT PATTERN
GLOBE VALVE - ANGLE PATTERN
MOTORIZED 2-WAY CONTROL VALVE
MOTORIZED 3-WAY CONTROL VALVE
CHECK VALVE
CIRCUIT BALANCING VALVE
BALL VALVE
PRESSURE RELIEF VALVE
THERMAL RELIEF VALVE
SAFETY RELIEF VALVE
PLUG VALVE
NEEDLE VALVE
TRIPLE DUTY VALVE
AUTOMATIC AIR VENT
MANUAL AIR VENT
STRAINER
STRAINER W/ PLUG BLOW OFF
VENTURI
PRESSURE GAUGE W/ COCK - WATER
PRESSURE GAUGE W/ COCK - STEAM
THERMOMETER & THERMOWELL
WATER TEMP SENSOR & THERMOWELL
FLOW SWITCH
PRESSURE SWITCH
THERMOWELL
PRESSURE & TEMP TAP
INVERTED BUCKET STEAM TRAP
THERMOSTATIC STEAM TRAP
FLOAT & THERMOSTATIC STEAM TRAP
DIRECTION OF FLOW
BACKFLOW PREVENTING VALVE
SYMBOL ABR, DESCRIPTION
WET SIDE
PITCH DOWN
ELBOW UP/DN
TEE UP/DN
EXISTING PIPING TO BE REMOVED
EXISTING PIPING TO REMAIN
NEW PIPING
PIPE CAP OR PLUG
REDUCER - CONCENTRIC / ECCENTRIC
EXPANSION JOINT
FLEXIBLE CONNECTION
ANCHOR POINT
CONDENSATE DRAIN
NATURAL GAS PIPING
CHEMICAL FEED LINE
MAKE-UP WATER LINE
CULINARY COLD WATER
CULINARY HOT WATER
CULINARY HOT WATER RECIRC
CD
G
CF
MU
CW
HW
HWREC
GLYCOL FILL LINEGF
R
M
S
PRESSURE REDUCING VALVEPRV
S
VENT LINEV
SANITARY SEWERSS
GENERAL NOTES
G-1 - MECHANICAL INFORMATION IS NOT LIMITED TO THE MECHANICAL DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMATION OF THE EXISTING BUILDING AND SITE
CONDITIONS, EXISTING PIPING, EXISTING ELECTRICAL, AND EXISTING SUPPORTS.
A - EACH DRAWING SHEET AND THE SPECIFICATIONS HAVE BEEN PREPARED TO SUPPLEMENT
EACH OTHER AND THEY SHALL BE INTERPRETED AS AN INTEGRAL UNIT WITH ITEMS SHOWN
AND NOTED ON ONE AND NOT THE OTHER BEING FURNISHED AND INSTALLED AS THOUGH
SHOWN AND CALLED OUT IN ALL PLACES. ITEMS IN SPECIFICATIONS OR DRAWINGS LISTED
WHICH ARE DIFFERING IN EFFICIENCY OR QUALITY SHALL BE HELD TO THE GREATEST OF:
EFFICIENCY, QUALITY OR GOVERNING CODE.
B - THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR THE INSTALLATION OF THE SYSTEMS
ACCORDING TO THE TRUE INTENT AND MEANING OF THE CONTRACT DOCUMENTS.
C - THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH PROPER SERVICE ACCESS AND
CLEARANCES ACCORDING TO MANUFACTURERS RECOMMENDATIONS. THE CONTRACTOR SHALL
REVIEW SUPPLIERS BID PACKAGES FOR COMPLETENESS AND COMPLIANCE TO THE
SPECIFICATIONS, SCHEDULES, AND DESIGN INTENT (ALL EQUIPMENT AND METHODS). THE
CONTRACTOR SHALL REMOVE AND REINSTALL CORRECTLY AT HIS OWN EXPENSE ANY
EQUIPMENT NOT IN COMPLIANCE.
D - THE CONTRACTOR SHALL CONSULT MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
SIZES, METHODS, ACCESSORIES, AND CLEARANCES IN SPACE AVAILABLE PRIOR TO BIDDING
PROJECT.
E - ANYTHING NOT CLEAR OR IN CONFLICT WILL BE EXPLAINED BY MAKING APPLICATION TO THE
ENGINEER IN WRITING.
G-2 - ANY AND ALL ALTERATIONS TO THE SYSTEM SHOWN SHALL BE SUBMITTED TO THE
ENGINEER PRIOR TO CHANGES FOR APPROVAL. CONTRACTOR SHALL NOT START ANY CHANGES
UNTIL NOTIFIED IN WRITING. IF CHANGES ARE MADE PRIOR TO APPROVAL CONTRACTOR SHALL TAKE ALL RESPONSIBILITY FOR THE CHANGES MADE AND ALL COSTS RELATING TO FAILURE OR
REPLACEMENT OF ALTERATIONS.
G-3 - CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND LOCATIONS.
G-4 - THE WORKING DRAWINGS ARE DIAGRAMMATIC. THEY DO NOT SHOW EVERY OFFSET,
BEND, OR ELBOW NECESSARY FOR THE COMPLETE INSTALLATION IN THE SPACE PROVIDED. ALL
LOCATIONS FOR MECHANICAL EQUIPMENT SHALL BE FIELD VERIFIED AND COORDINATED WITH
ALL DRAWINGS. THE CONTRACTOR SHALL PROVIDE OR COORDINATE WITH THE GENERAL
CONTRACTOR PROVISIONS FOR BLOCKOUTS OR CORE DRILLS THROUGH STRUCTURE.
G-5 - THE INSTRUCTION TO "PROVIDE" ALSO INCLUDES INSTALLATION.
G-6 - MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL SMOKE AND FIRE DAMPERS AS
REQUIRED BY LOCAL CODES AND AUTHORITIES.
G-7 - SHEET METAL DUCT SIZES SHOWN ON DRAWINGS ARE FREE AREA DIMENSIONS.
G-8 - PROVIDE AND INSTALL BALANCING DAMPERS IN ALL SUPPLY AND EXHAUST AIR BRANCH
DUCTS. BALANCE TO CFM SHOWN ON PLAN.
G-9 - SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF DIFFUSERS AND
GRILLES.
G-10 - PROVIDE TURNING VANES IN ALL ELBOWS OF RECTANGULAR DUCT.
G-11 - THE CONTRACTOR SHALL ASSUME ALL RESPONSIBILITY IN HANDLING AND DISPOSING OF REFRIGERANTS, OILS, ETC. ALL SUCH MATERIALS SHALL BE HANDLED, DISPOSED, AND USED IN
ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL LAWS.
G-12 - THE MECHANICAL CONTRACTOR SHALL VERIFY MOTOR VOLTAGES WITH THE ELECTRICAL
DRAWING BEFORE ORDERING MOTORIZED EQUIPMENT AND CONTROLS.
G-13 - C.F.M. LISTED IS ACTUAL AIR.
G-14 - SUPPLIERS SHALL REVIEW ALL DRAWINGS AND THE SPECIFICATIONS PRIOR TO
SUBMITTING PRICES TO THE CONTRACTOR. ALL QUESTIONS AND DISCREPANCIES SHALL BE
BROUGHT TO THE ENGINEERS ATTENTION PRIOR TO BIDDING.
G-15 - CONTRACTOR SHALL THOROUGHLY REVIEW AND SIGN SUBMITTALS FOR COMPLETENESS
AND COMPLIANCE TO THE SPECIFICATIONS PRIOR TO ENGINEERS REVIEW. SUPPLIERS SHALL
HIGHLIGHT OR MARK ALL INFORMATION REQUIRED TO SHOW COMPLIANCE TO THE
SPECIFICATIONS. ALL REQUESTED EXCEPTIONS TO THE SPECIFICATIONS, OR SCHEDULES
SHALL BE CLEARLY NOTED AND EXPLAINED. SUBMITTAL REVIEW AND ACCEPTANCE IS FOR
DESIGN CONCEPT ONLY, AND DOES NOT AT ANY TIME RELIEVE THE CONTRACTOR OF
RESPONSIBILITY TO MEET SPECIFICATIONS, CAPACITIES, OR DESIGN INTENT.
G-16 - ALL MECHANICAL SHALL BE INSTALLED AND CONFORM TO THE 2021 EDITION OF THE IMC
AND IPC WITH UTAH ANNOTATIONS AND LOCAL AUTHORITY REQUIREMENTS.
G-17 - THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE DRAINING DOWN AND RE-FILLING
OF ALL SYSTEMS NECESSARY TO COMPLETE THE WORK OUTLINED BY THIS PROJECT. THIS
INCLUDES PROVIDING THE REQUIRED CHEMICAL TREATMENT WHEN RE-FILLING THE SYSTEM.
G-18 - ALL PIPING, MATERIALS, ETC. SHALL BE NEW AND DOMESTIC MADE UNLESS SPECIFICALLY
AUTHORIZED IN WRITING PRIOR TO BID.
G-19 - THIS CONTRACTOR SHALL CONTRACT WITH A DESIGN BUILD ELECTRICAL CONTRACTOR
FOR THE DESIGN AND CONSTRUCTION OF THE ELECTRICAL PORTION OF THIS PROJECT.
ELECTRICAL INSTALLATION AND DESIGN SHALL BE PER 2020 NEC.
G-20 - ALL NEW CONTROL WIRING, ELECTRICAL WIRING AND FEEDERS SHALL BE RUN IN
APPROPRIATELY SIZED CONDUIT AND SECURED TO WALL PER CODE.
SEF
O
R P
HATUFOETATS
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities
Department of Administrative Services
Internet: http://www.dfcm.state.ut.us
State of Utah A
LL
ID
E A
S , D
E S
IG
N
S , A
R R
A N
G E
M E
N T
S A
N D
P
LA
N S
IN
D
IC
A
T E
D O
R R
E P
R E
S E
N T
E D
B Y
T H
IS
D
R A
W
IN
G A
R E
O W
N E
D B
Y A
N D
T H
E P
R O
P E
R T
Y O
F W
H W
E N
G
IN
E E
R
IN
G
IN
C . A
N D
W E
R E
C R
E A
T E
D
E V
O
LV
E D
A
N D
D E
V E
LO
P
E D
F O
R U
S E
O N
A N
D
IN
C O
N N
E C
T
IO
N W
IT
H
T H
E S
P E
C
IF
IE
D
P R
O
JE
C T
N
O N
E O
F T
H E
ID
E
A S
D
E S
IG
N
S
A R
R A
N G
E M
E N
T S
O R
P
LA
N S
S H
A
LL
B E
U S
E D
B Y
O R
D
IS
C
LO
S E
D T
O A
N Y
P E
R S
O N
, F
IR
M
O R
C O
R P
O R
A T
IO
N
F O
R A
N Y
P U
R P
O S
E W
H A
T S
O E
V E
R W
IT
H
O U
T W
R
IT
T E
N C
O N
S E
N T
O F
W H
W E
N G
IN
E
E R
IN
G
IN
C
W
R
IT
T E
N D
IM
E
N S
IO
N
S O
N T
H E
S E
D R
A W
IN
G
S S
H A
LL
H
A V
E P
R E
C E
D E
N C
E O
V E
R S
C A
LE
D
IM
E
N S
IO
N
S
C O
N T
R A
C T
O R
S S
H A
LL
V
E R
IF
Y
A N
D B
E R
E S
P O
N S
IB
LE
F O
R A
LL
D
IM
E
N S
IO
N
S A
N D
C O
N D
IT
IO
N S
O N
T H
E J
O B
A N
D T
H
IS
O F
F
IC
E M
U S
T B
E N
O T
IF
IE
D O
F A
N Y
V A
R
IA
T
IO
N F
R O
M T
H E
D
IM
E N
S
IO
N S
A N
D C
O N
D
IT
IO
N
S S
H O
W N
B Y
T H
E S
E D
R A
W
IN
G S
W
A R
N
IN
G : R
E P
R O
D U
C T
IO
N
H E
R E
O F
IS
A
C R
IM
IN
A L
O F
F E
N S
E U
N D
E R
U .S
.C . S
E C
. 5
. U N
A U
T H
O R
IZ
E
D D
IS
C
LO
S
U R
E M
A Y
C O
N S
T
IT
U T
E T
R A
D E
S E
C R
E T
M
IS
A P
P R
O P
R
IA
T
IO
N
IN
V
IO
LA
T
IO
N
O F
I.
C
.2 4-
2-
-1 E
T . S
E Q
. A N
D O
T H
E R
L A
W S
CONSULTANTS
PROJECT NAME & ADDRESS
CODE REVIEW STAMP
SHEET NO.
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
08/08/2025
WHW JOB NO.:
25078
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SHEET TITLE
E E
WP
STAFF
CL
733 S Cowboy Way Kanab, UT 84741
SWATC KANAB
SHOP
MECHANICAL
UPGRADE
DFCM #26066270
08/08/25
MECHANICAL LEGEND
AND GENERAL NOTES
MG001
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/21/2025
SEF
O
R P
HATUFOETATS
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities
Department of Administrative Services
Internet: http://www.dfcm.state.ut.us
State of Utah A
LL
ID
E A
S , D
E S
IG
N
S , A
R R
A N
G E
M E
N T
S A
N D
P
LA
N S
IN
D
IC
A
T E
D O
R R
E P
R E
S E
N T
E D
B Y
T H
IS
D
R A
W
IN
G A
R E
O W
N E
D B
Y A
N D
T H
E P
R O
P E
R T
Y O
F W
H W
E N
G
IN
E E
R
IN
G
IN
C . A
N D
W E
R E
C R
E A
T E
D
E V
O
LV
E D
A
N D
D E
V E
LO
P
E D
F O
R U
S E
O N
A N
D
IN
C O
N N
E C
T
IO
N W
IT
H
T H
E S
P E
C
IF
IE
D
P R
O
JE
C T
N
O N
E O
F T
H E
ID
E
A S
D
E S
IG
N
S
A R
R A
N G
E M
E N
T S
O R
P
LA
N S
S H
A
LL
B E
U S
E D
B Y
O R
D
IS
C
LO
S E
D T
O A
N Y
P E
R S
O N
, F
IR
M
O R
C O
R P
O R
A T
IO
N
F O
R A
N Y
P U
R P
O S
E W
H A
T S
O E
V E
R W
IT
H
O U
T W
R
IT
T E
N C
O N
S E
N T
O F
W H
W E
N G
IN
E
E R
IN
G
IN
C
W
R
IT
T E
N D
IM
E
N S
IO
N
S O
N T
H E
S E
D R
A W
IN
G
S S
H A
LL
H
A V
E P
R E
C E
D E
N C
E O
V E
R S
C A
LE
D
IM
E
N S
IO
N
S
C O
N T
R A
C T
O R
S S
H A
LL
V
E R
IF
Y
A N
D B
E R
E S
P O
N S
IB
LE
F O
R A
LL
D
IM
E
N S
IO
N
S A
N D
C O
N D
IT
IO
N S
O N
T H
E J
O B
A N
D T
H
IS
O F
F
IC
E M
U S
T B
E N
O T
IF
IE
D O
F A
N Y
V A
R
IA
T
IO
N F
R O
M T
H E
D
IM
E N
S
IO
N S
A N
D C
O N
D
IT
IO
N
S S
H O
W N
B Y
T H
E S
E D
R A
W
IN
G S
W
A R
N
IN
G : R
E P
R O
D U
C T
IO
N
H E
R E
O F
IS
A
C R
IM
IN
A L
O F
F E
N S
E U
N D
E R
U .S
.C . S
E C
. 5
. U N
A U
T H
O R
IZ
E
D D
IS
C
LO
S
U R
E M
A Y
C O
N S
T
IT
U T
E T
R A
D E
S E
C R
E T
M
IS
A P
P R
O P
R
IA
T
IO
N
IN
V
IO
LA
T
IO
N
O F
I.
C
.2 4-
2-
-1 E
T . S
E Q
. A N
D O
T H
E R
L A
W S
CONSULTANTS
PROJECT NAME & ADDRESS
CODE REVIEW STAMP
SHEET NO.
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
08/08/2025
WHW JOB NO.:
25078
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SHEET TITLE
E E
WP
STAFF
CL
733 S Cowboy Way Kanab, UT 84741
SWATC KANAB
SHOP
MECHANICAL
UPGRADE
DFCM #26066270
08/08/25
SPECIAL INSTRUCTIONS
AND TESTING
MG002
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/21/2025
2 2 1 1/4"ø NG (E)
S
COS
NO2
EF
D-1
TYP 24
T
PAU-1,2
PAU
PAU
20"ø SA
12"ø EA
20"ø SA
20"ø EA
12"ø EA
12"ø EA 12"ø EA
12"ø EA
3/4"ø NG 1/2"ø NG 1/2"ø NG
1 1/4"ø NG (E)
5 5
R-1 R-1
20"x20" RA20"x20" RA
EG-1
TYP 5
10 11
SEF
O
R P
HATUFOETATS
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities
Department of Administrative Services
Internet: http://www.dfcm.state.ut.us
State of Utah A
LL
ID
E A
S , D
E S
IG
N
S , A
R R
A N
G E
M E
N T
S A
N D
P
LA
N S
IN
D
IC
A
T E
D O
R R
E P
R E
S E
N T
E D
B Y
T H
IS
D
R A
W
IN
G A
R E
O W
N E
D B
Y A
N D
T H
E P
R O
P E
R T
Y O
F W
H W
E N
G
IN
E E
R
IN
G
IN
C . A
N D
W E
R E
C R
E A
T E
D
E V
O
LV
E D
A
N D
D E
V E
LO
P
E D
F O
R U
S E
O N
A N
D
IN
C O
N N
E C
T
IO
N W
IT
H
T H
E S
P E
C
IF
IE
D
P R
O
JE
C T
N
O N
E O
F T
H E
ID
E
A S
D
E S
IG
N
S
A R
R A
N G
E M
E N
T S
O R
P
LA
N S
S H
A
LL
B E
U S
E D
B Y
O R
D
IS
C
LO
S E
D T
O A
N Y
P E
R S
O N
, F
IR
M
O R
C O
R P
O R
A T
IO
N
F O
R A
N Y
P U
R P
O S
E W
H A
T S
O E
V E
R W
IT
H
O U
T W
R
IT
T E
N C
O N
S E
N T
O F
W H
W E
N G
IN
E
E R
IN
G
IN
C
W
R
IT
T E
N D
IM
E
N S
IO
N
S O
N T
H E
S E
D R
A W
IN
G
S S
H A
LL
H
A V
E P
R E
C E
D E
N C
E O
V E
R S
C A
LE
D
IM
E
N S
IO
N
S
C O
N T
R A
C T
O R
S S
H A
LL
V
E R
IF
Y
A N
D B
E R
E S
P O
N S
IB
LE
F O
R A
LL
D
IM
E
N S
IO
N
S A
N D
C O
N D
IT
IO
N S
O N
T H
E J
O B
A N
D T
H
IS
O F
F
IC
E M
U S
T B
E N
O T
IF
IE
D O
F A
N Y
V A
R
IA
T
IO
N F
R O
M T
H E
D
IM
E N
S
IO
N S
A N
D C
O N
D
IT
IO
N
S S
H O
W N
B Y
T H
E S
E D
R A
W
IN
G S
W
A R
N
IN
G : R
E P
R O
D U
C T
IO
N
H E
R E
O F
IS
A
C R
IM
IN
A L
O F
F E
N S
E U
N D
E R
U .S
.C . S
E C
. 5
. U N
A U
T H
O R
IZ
E
D D
IS
C
LO
S
U R
E M
A Y
C O
N S
T
IT
U T
E T
R A
D E
S E
C R
E T
M
IS
A P
P R
O P
R
IA
T
IO
N
IN
V
IO
LA
T
IO
N
O F
I.
C
.2 4-
2-
-1 E
T . S
E Q
. A N
D O
T H
E R
L A
W S
CONSULTANTS
PROJECT NAME & ADDRESS
CODE REVIEW STAMP
SHEET NO.
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
08/08/2025
WHW JOB NO.:
25078
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SHEET TITLE
E E
WP
STAFF
CL
733 S Cowboy Way Kanab, UT 84741
SWATC KANAB
SHOP
MECHANICAL
UPGRADE
DFCM #26066270
08/08/25
MECHANICAL PLAN
ME101
1/4" = 1'-0"
MECHANICAL DEMOLITION PLAN
0'
SCALE : 1/4" = 1'-0"
4'2' 12'8' 0'
SCALE : 1/4" = 1'-0"
4'2' 12'8'
1/4" = 1'-0"
MECHANICAL PLAN
SHEET NOTES
1 REMOVE EXISTING RADIANT HEATER AND ALL
ASSOCIATED ITEMS IN THIS APPROXIMATE
LOCATION. REMOVE ALL ELECTRICAL
ACCOMMODATIONS BACK TO PANEL. REMOVE
EXISTING FLUE. COORDINATE WITH DFCM SHORT
LIST ROOFING CONTRACTOR TO SEAL AND
WEATHERPROOF FLUE PENETRATION.
2 REMOVE EXISTING EVAPORATIVE COOLER AND ALL
ASSOCIATED ITEMS IN THIS APPROXIMATE
LOCATION. REMOVE EXISTING WATER LINE SERVING
THE COOLER, REMOVE BACK TO MAIN AND CAP.
REPAIR AND PATCH PENETRATION IN WALL. PAINT TO
MATCH EXISTING COLOR. FIELD VERIFY.
3 REMOVE EXISTING NATURAL GAS PIPING AND ALL
ASSOCIATED ITEMS BACK TO THIS APPROXIMATE
LOCATION AND CAP. PIPING SERVING EXISTING
WATER HEATER AND ALL OTHER EQUIPMENT SHALL
REMAIN. FIELD VERIFY EXACT PIPE ROUTING AND
POINTS OF REMOVAL.
4 TIE INTO EXISTING NATURAL GAS PIPING IN THIS
APPROXIMATE LOCATION. SECURE PIPING TO WALL.
UV PAINT ALL OUTDOOR GAS PIPING. PAINT ALL
EXPOSED GAS PIPING WITH UV RESISTANT PAINT.
FIELD VERIFY EXACT PIPE ROUTING AND POINTS OF
CONNECTION.
5 PROVIDE NEW GROUND-MOUNTED PACKAGED AIR
UNIT IN THIS APPROXIMATE LOCATION. PROVIDE
WITH ALL NEW ELECTRICAL ACCOMMODATIONS BY A
LICENSED DESIGN BUILD ELECTRICIAN. PROVIDE
NEW DUCTWORK THROUGH WALL PENETRATION.
SEAL AND WEATHERPROOF WALL PENETRATION.
PROVIDE OUTDOOR RATED PRE INSULATED, CLOSED
CELL DUCTWORK WITH IMPACT RESISTANT JACKET.
THERAMDUCT OR APPROVED EQUAL ON ALL
EXPOSED DUCTWORK. FIELD VERIFY DIMENSIONS
PRIOR TO COMMENCING WORK. PROVIDE NEW GAS
TRAIN AND PIPING AND TIE INTO EXISTING GAS
PIPING. FIELD VERIFY EXACT ROUTING. PROVIDE
WITH COIL HAIL GUARDS. PROVIDE WITH
OCCUPANCY SENSOR TO TURN ON EXHAUST FAN
AND SWITCH PACKAGED AIR OUTSIDE AIR TO MATCH
EXHAUST FAN RATE WHEN SHOP IS OCCUPIED.
PROVIDE WITH NEW 3" CONCRETE EQUIPMENT CURB.
INSTALL PER MANUFACTURERS RECOMMENDATIONS
FOR A COMPLETE INSTALL.
6 PROVIDE SPIRAL DUCT MOUNTED DIFFUSER IN THIS
APPROXIMATE LOCATION. BALANCE TO CFM SHOWN.
FIELD VERIFY.
7 PROVIDE HIGH WALL-MOUNTED EXHAUST FAN IN
THIS APPROXIMATE LOCATION. PROVIDE WITH NEMA
4 RATED WEATHER HOOD AND BACK DRAFT DAMPER.
PROVIDE WITH 2 SPEED CONTROLLER. PROVIDE
WITH OCCUPANCY SENSOR AND INTERLOCK WITH
NEW PACKAGE AIR UNIT TO RUN OCCUPIED HIGH
FLOW RATE OF 2,750 CFM WHILE OCCUPIED.
BALANCE STANDBY FLOW RATE TO 250 CFM WHILE
UNOCCUPIED. FIELD VERIFY.
8 PROVIDE NEW UL LISTED 2075 CO SENSOR 5' AFF IN
THIS APPROXIMATE LOCATION. TIE INTO AUDIBLE
AND VISABLE ALARM COMBO TO ACTIVATE WHEN CO
OR NO2 IS DETECTED, AUTOMATION COMPONENTS
FSIG-SLM500 OR APPROVED EQUAL. SENSOR SHALL
ACTIVATE HIGH RATE CFM FOR BOTH EXHAUST FAN
AND PACKAGED AIR UNIT. PROVIDE ALL NEW
ELECTRICAL ACCOMMODATIONS. PROVIDE WITH
MEANS FOR MANUAL SILENCE OVERRIDE. FIELD
VERIFY.
9 PROVIDE NEW UL LISTED 2075 NO2 SENSOR 12" AFF
IN THIS APPROXIMATE LOCATION. TIE INTO AN
AUDIBLE AND VISABLE ALARM COMBO TO ACTIVATE
WHEN CO OR NO2 IS DETECTED, AUTOMATION
COMPONENTS FSIG-SLM500 OR APPROVED EQUAL.
SENSOR SHALL ACTIVATE HIGH RATE CFM FOR BOTH
EXHAUST FAN AND PACKAGED AIR UNIT. PROVIDE
ALL NEW ELECTRICAL ACCOMMODATIONS. PROVIDE
WITH MEANS FOR MANUAL SILENCE OVERRIDE.
FIELD VERIFY.
10 PROVIDE EXHAUST GRILLE 8' 6" AFF IN THIS
APPROXIMATE LOCATION. BALANCE TO CFM SHOWN.
PROVIDE WITH BALANCING DAMPERS ABOVE AND
BELOW GRILLE. THE INTENT IS TO PROVIDE A HIGH
AND LOW BALANCED EXHAUST RATE ON EACH
EXHAUST DROP. FIELD VERIFY EXACT POSITIONING.
11 TERMINATE EXHAUST DUCTWORK 12" AFF IN THIS
APPROXIMATE LOCATION. BALANCE EXHAUST TO 275
CFM. COVER OPENING WITH NON CORROSIVE BIRD
SCREEN. THE INTENT IS TO PROVIDE A HIGH AND
LOW BALANCED EXHAUST RATE ON EACH EXHAUST
DROP. FIELD VERIFY EXACT POSITIONING.
12 PROVIDE DUCT MOUNTED RETURN GRILLE IN THIS
APPROXIMATE LOCATION. FIELD VERIFY.
13 PROVIDE 7 DAY-PROGRAMMBLE THERMOSTAT IN
THIS APPROXIMATE LOCATION. PROVIDE WITH
OCCUPANCY SENSORS TO SWITCH FROM
UNOCCUPIED TO OCCUPIED MODE. SWITCH TO
UNOCCUPIED MODE AFTER 30 MIN DELAY. FIELD
VERIFY.
GENERAL NOTES:
1.CONTRACTOR SHALL FIELD VERIFY EXISTING
MECHANICAL, STRUCTURAL, ELECTRICAL AND
ARCHITECTURAL CONDITIONS, INCLUDING, BUT NOT LIMITED
TO: EXISTING ROUTING AND LOCATION OF DUCTWORK,
PIPING, ELECTRICAL, AND STRUCTURAL ELEMENTS.
CONTRACTOR SHALL FIELD VERIFY ANY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL ELEMENTS AND
EXISTING CONDITIONS PRIOR TO BEGINNING FABRICATION
OR ORDERING NEW EQUIPMENT.
2. PRIME CONTRACTOR SHALL PROVIDE ALL COORDINATION
BETWEEN SUB-TIER CONTRACTORS. THIS SHALL INCLUDE
THE COORDINATION BETWEEN SUB-TIER CONTRACTORS,
SUB-TIER CONTRACTORS AND FACILITIES, SUB-TIER
CONTRACTORS AND ARCHITECT/ENGINEER, ETC.
KEYPLAN
3. FIELD VERIFY STRUCTURAL COMPONENTS PRIOR TO
CUTTING PENETRATIONS FOR MECHANICAL EQUIPMENT.
AVOID ALL STRUCTURAL COMPONENTS.
4. ALL ROOFING MODIFICATIONS MUST BE DONE THE
ROOFING WARRANTY HOLDING CONTRACTOR. IF
WARRANTY IS EXPIRED, ROOFING MODIFICATIONS MUST BE
BY A DFCM APPROVED SHORT LIST ROOFING CONTRACTOR.
5. ISOMETRIC AND COORDINATION VIEWS ARE FOR
GENERAL LAYOUT ROUTING AND NOT FOR PART COUNT OR
BIDDING PURPOSE. CONTRACTOR SHALL BE REQUIRED TO
PROVIDE ALL PIPING, DUCT, BENDS, FITTINGS,
ACCESSORIES, OFFSETS, ETC AS NEEDED FOR A COMPLETE
INSTALLATION DETERMINED BY THE EXISTING FIELD
VERIFIED CONDITIONS.
6. CONTRACTOR SHALL COORDINATE WITH DFCM PROVIDED
HAZMAT REPORT PRIOR TO THE DEMOLITION OF ANY
EQUIPMENT, DUCTWORK, DUCT INSULATION, PIPING, PIPE
INSULATION, ETC.
7. PROVIDE BALANCING DAMPERS ON ALL SUPPLY AND
RETURN BRANCHES.
8. ALL DEMOLISHED EQUIPMENT AND MATERIAL SHALL BE
BROKEN DOWN TO FIT THROUGH EXISTING DOOR,
OPENINGS, AND HATCHES. FIELD VERIFY EXACT SCOPE OF
DEMOLITION AND REMOVAL PATH. CONTRACTOR SHALL BE
RESPONSIBLE TO REPAIR ANY DAMAGE TO BUILDING
DURING REMOVAL OF EQUIPMENT AND MATERIAL.
9. ALL DUCTWORK LOCATED OUTDOORS SHALL BE PRE-
INSULATED, CLOSED CELL DUCTWORK WITH IMPACT
RESISTANT JACKET. PROVIDE WITH THERMADUCT OR
APPROVED EQUAL.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/21/2025
1/2"ø NGPAU
PAU
GAS METER:
LENGTH 150 FT
CFH: 375
MBH: 309
PRESSURE: 2PSIG
EXISTING WATER HEATER
1 1/4"ø NG (E)
1/2"ø NG (E)
1/2"ø NG
3/4"ø NG
GAS PRESSURE
REGULATOR
2PSIG TO 4OZ
GAS PRESSURE
REGULATOR
2PSIG TO 4OZ
2"
2"
12"C .C.M
AX.
2"
12"C.C.MAX.
ENDS OF LINER SHALL BE
BUTTED FIRMLY TOGETHER.
ALL JOINTS, SEAMS, AND TEARS
SHALL BE COATED W/ ADHESIVE
DURING INSTALLATION.
NOT MORE THAN 2"
FROM EDGE OF LINER.
ALL ENDS OF LINER TO
BE COATED W/ ADHESIVE
DUCTLINER
ONE INCH THICK 1-1/2 LB
DENSITY FIBERGLASS.
TOP AND BOTTOM
SECTIONS OF LINER
SHALL OVERLAP THE
SIDES
GRIP NAILS SHALL BE
INSTALLED BY AIR
HAMMER OR BY
AUTOMATIC FASTENER
EQUIPMENT.
INSULATED PINS, FASTENERS
OR GRIP NAILS.
1" THICK
DUCT LINER
METAL FASTENERS
SHEET METAL DUCT
INSULATION SHALL HAVE A MINIMUM
R-VALUE OF 5 FOR INDOOR AND 8 FOR
OUTDOOR INSTALLATION.
#10 x 3/4" SELF
TAPPING CADMIUM PLATED
SHEET METAL SCREWS TO
ANCHOR STRAPS TO DUCT.
ALL STRAPS TO BE TIGHT
AGAINST DUCT AND SUPPORT
MEMBERS. (TYPICAL)
1"
1" x 18 GAUGE STRAP
HANGERS AT 8'-0"
SPACING.
1" x 18 GAUGE STRAP
HANGERS AT 8'-0"
SPACING.
NO POP RIVETS
ALLOWED
NOTES:
1. DUCT OUTSIDE OF BUILDING
ENVELOPE SHALL BE WRAPPED
EXTERNALLY AS PER THE
SPECIFICATIONS.
2. SEE SPECIFICATIONS SECTION
15074 FOR SEISMIC RESTRAINT
REQUIREMENTS.
ATTACH SECURELY TO
STRUCTURE.
1" x 16 GA.
HANGER STRAP
1" x 18 GA.
HANGER STRAP
SIZE PER
SMACNA
NOTE:
MAXIMUM
SPACING OF 10'-0"
ATTACH HANGER STRAPS
TO STRUCTURE
SHEET METAL SCREW
3/8" BOLT
DUCT
DUCTS < 20"ø
20" DIA TO 36" DIA.
DUCTS > 36"ø
HANGERS MUST NOT DEFORM DUCT SHAPE
NOTE:
SEE SPECIFICATIONS
SECTION 15074 FOR SEISMIC
RESTRAINTREQUIREMENTS.
D
RETURN AIR FLOW
MAIN AIR DUCT
SUPPLY AIR FLOW
R
LOCKING QUADRANT
HANDLE OR REMOTE
CEILING OPERATOR
WHERE DAMPER
IS INACCESSIBLE.
FASTEN RIGID DUCT
TO FITTING W/ #10x3/4"
SHEET METAL SCREWS.
DO NOT INTERFERE W/
VOLUME DAMPER
OPERATION.
AIR
BRANCH
DUCT (TYP.)
SIZE CUT OUT ACCORDING
TO MANUFACTURERS
RECOMMENDATIONS.
INSULATION NOT
SHOWN SEE
SPECIFICATIONS
22GA. RIGID SHEET METAL
WRAPPED WITH
INSULATION.
NEOPRENE BUSHING
EACH END
#10x3/4" SHEET METAL
SCREWS
SEAL SEAM WITH
HARD-CAST
DUCT SEALER
22 GA. BLADE
3/8" SQUARE ROD
45°
HANGER ROD
HANGER ROD
16 GA. ZINC COATED
SHEET STEEL SADDLE
AT LEAST 12" LONG.
VAPOR BARRIER
INSULATION
PIPE
45°
INSULATION WITH OR
WITHOUT VAPOR BARRIER
HEAVY DUTY
CLEVIS HANGER 16 GA. ZINC COATED
SHEET STEEL SHIELD
AT LEAST 12" LONG.
HANGER ROD, ATTACH
TO OVERHEAD STRUCTURE
LOCKING NUT
SUPPORT NUT
PIPE
CALCIUM SILICATE
BLOCK TYPICAL
CONNECT TO STRUCTURE
MAX. 1/4" SLACK.
PULL HAND TIGHT
PRE-STRECHED, COLOR CODED
CERTIFIED BREAK STRENGTH CABLE
(2) CABLES PER RESTRAINT PACKAGE
45°
CONNECT TO
STRUCTURE
DETAIL NOTES:
1.SEE SPECIFICATION SECTION 15074
FOR SEISMIC BRACING REQUIREMENTS.
TURNBUCKLE WITH 3"
ADJUSTMENT - BY
HEATER MANUFACTURER
3/8 " THREADED ROD - BY MC
NUT - BY MC
ADJUSTABLE BEAM
CLAMP OR "U" BOLT WITH
CHAIR ANCHOR - BY MC
DETAIL NOTES:
1. PROVIDE UNISTRUT SUPPORT BETWEEN ROOF
JOISTS AS REQUIRED FOR SUPPORT.
V E
R T
IC
A
L
GAS SUPPLY
MANUAL
SHUT-OFF
VALVE
GAS PRESSURE
REGULATOR
(2 PSI TO 4 OZ)
DRIP LEG
GROUND
JOINT
UNION
EQUIPMENT
CONNECTION
FLEXIBLE GAS
CONNECTOR
18" MAX.
CAP
MIN 10 PIPE
DIAMETERS
NOTE: COORDINATE WITH
MANUFACTURER FOR GAS
REQUIREMENTS
HANGER ROD
PIPE
HANGER
SUPPORT NUT
LOCKING NUT
CALCIUM SILICATE BLOCK
16 GA. ZINC COATED SHEET
STEEL SHIELD AT LEAST 12" LONG
(TYP)
MOUNT PIPING TO UNISTRUT
PROVIDE PIPE CLAMPS
WITH BOLTS AND NUTS
CALCIUM SILICATE
BLOCK
CALCIUM SILICATE
BLOCK
BOLT UNISTRUT TO EXISTING
WALL AND CONCRETE USING
EXPANSION ANCHOR BOLTS
ATTACH TO ROOM
OVERHEAD STRUCTURE
SPRING TYPE ISOLATOR
FOR INSTALLATION
NEAR HOT WATER
PUMPS
CLEVIS HANGER
INSULATION
16 GAGE ZINC
COATED SHEET
STEEL SHIELD AT
LEAST 12" LONG.
HEAVY DUTY
CLEVIS HANGER
HEAVY DUTY
CLEVIS HANGER
PIPE
SINGLE HORIZONTAL RUN
WITHOUT INSULATION
CLEVIS HANGER
ATTACH TO EXISTING
CEILING
INSULATION WITH OR WITHOUT
VAPOR BARRIER
NOTE:
PROVIDE WITH VAPOR BARRIER
ON CHILLED WATER AND
DOMESTIC COLD WATER PIPING
HANGER ROD
SUPPORT NUT
LOCKING NUT
SEF
O
R P
HATUFOETATS
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities
Department of Administrative Services
Internet: http://www.dfcm.state.ut.us
State of Utah A
LL
ID
E A
S , D
E S
IG
N
S , A
R R
A N
G E
M E
N T
S A
N D
P
LA
N S
IN
D
IC
A
T E
D O
R R
E P
R E
S E
N T
E D
B Y
T H
IS
D
R A
W
IN
G A
R E
O W
N E
D B
Y A
N D
T H
E P
R O
P E
R T
Y O
F W
H W
E N
G
IN
E E
R
IN
G
IN
C . A
N D
W E
R E
C R
E A
T E
D
E V
O
LV
E D
A
N D
D E
V E
LO
P
E D
F O
R U
S E
O N
A N
D
IN
C O
N N
E C
T
IO
N W
IT
H
T H
E S
P E
C
IF
IE
D
P R
O
JE
C T
N
O N
E O
F T
H E
ID
E
A S
D
E S
IG
N
S
A R
R A
N G
E M
E N
T S
O R
P
LA
N S
S H
A
LL
B E
U S
E D
B Y
O R
D
IS
C
LO
S E
D T
O A
N Y
P E
R S
O N
, F
IR
M
O R
C O
R P
O R
A T
IO
N
F O
R A
N Y
P U
R P
O S
E W
H A
T S
O E
V E
R W
IT
H
O U
T W
R
IT
T E
N C
O N
S E
N T
O F
W H
W E
N G
IN
E
E R
IN
G
IN
C
W
R
IT
T E
N D
IM
E
N S
IO
N
S O
N T
H E
S E
D R
A W
IN
G
S S
H A
LL
H
A V
E P
R E
C E
D E
N C
E O
V E
R S
C A
LE
D
IM
E
N S
IO
N
S
C O
N T
R A
C T
O R
S S
H A
LL
V
E R
IF
Y
A N
D B
E R
E S
P O
N S
IB
LE
F O
R A
LL
D
IM
E
N S
IO
N
S A
N D
C O
N D
IT
IO
N S
O N
T H
E J
O B
A N
D T
H
IS
O F
F
IC
E M
U S
T B
E N
O T
IF
IE
D O
F A
N Y
V A
R
IA
T
IO
N F
R O
M T
H E
D
IM
E N
S
IO
N S
A N
D C
O N
D
IT
IO
N
S S
H O
W N
B Y
T H
E S
E D
R A
W
IN
G S
W
A R
N
IN
G : R
E P
R O
D U
C T
IO
N
H E
R E
O F
IS
A
C R
IM
IN
A L
O F
F E
N S
E U
N D
E R
U .S
.C . S
E C
. 5
. U N
A U
T H
O R
IZ
E
D D
IS
C
LO
S
U R
E M
A Y
C O
N S
T
IT
U T
E T
R A
D E
S E
C R
E T
M
IS
A P
P R
O P
R
IA
T
IO
N
IN
V
IO
LA
T
IO
N
O F
I.
C
.2 4-
2-
-1 E
T . S
E Q
. A N
D O
T H
E R
L A
W S
CONSULTANTS
PROJECT NAME & ADDRESS
CODE REVIEW STAMP
SHEET NO.
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
08/08/2025
WHW JOB NO.:
25078
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SHEET TITLE
E E
WP
STAFF
CL
733 S Cowboy Way Kanab, UT 84741
SWATC KANAB
SHOP
MECHANICAL
UPGRADE
DFCM #26066270
08/08/25
MECHANICAL DETAILS
ME501
SCALE: NONE
1 NATURAL GAS ISOMETRIC
SCALE: NONE
DUCT LINER DETAIL
SCALE: NONE
DUCT STRAP HANGER DETAIL
SCALE: NONE
4 ROUND DUCT SUPPORT DETAIL
SCALE: NONE
ROUND-TO-ROUND DUCT CONSTRUCTION DETAIL
SCALE: NONE
6 SEISMIC SWAY BRACING DETAILS
SCALE: NONE
SUSPENSION DETAIL
SCALE: NONE
8 GAS LINE CONNECTION DETAIL
SCALE: NONE
9 PIPE HANGER DETAIL
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/21/2025
SMOKE SENSORS IN SUPPLY
AND RETURN AIR DUCTS WHERE
REQUIRED.
S
MOUNT ON LEGS
OR RAILS
MOUNT ON SPRING ISOLATORS
PROVIDE EXTERIOR 1-1/2"
INSULATION AND ALUMINUM
JACKET AT EXTERIOR
EXPOSED DUCT.
PROVIDE EXTERIOR WALL
PENETRATION. FLASH AND
SEAL WEATHER TIGHT
CONDENSATE DRAIN AND TRAP.
TYPICAL
ROOFTOP UNIT
ECONOMIZER
PROVIDE FLEXIBLE
DUCT CONNECTION.
4" CONCRETE PAD
S
TRANSITION DUCT AS NECESSARY
TO PENETRATE WALL AT CRAWL
SPACE LEVEL.
DRUM LOUVERS
MANUAL BALANCING
DAMPER W/ LOCKING
QUADRANT, MAY BE A
PART OF DRUM LOUVER.
SEAL DUCT
CONNECTION
MAIN AIR
ROUND DUCT
1/
2" W
ID
E
R U N N E R
F
LO
W
A
IR
SINGLE THICKNESS
TURNING VANES
LEADING AND TRAILING
EDGE TO BE PARALLEL
WITH SIDE OF DUCT.
1" LONG MINIMUM
TRAILING EDGE
COORDINATE
OPENING WITH G.C.
NEW WALL
BACKDRAFT DAMPER SET
TO OPEN FROM EXHAUST
FAN DISCHARGE PRESSURE.
ATTACH TO WALL WITH
1-1/2" SCREWS AND
INSERTS.
EXHAUST FAN
FRAME AND HOUSING.
INLET SCREEN
NEMA 4
WEATHERPROOF
HOOD
AND FRAME.
BALANCING DAMPER.
SET TO ALLOW
SCHEDULED
CFM TO BE EXHAUSTED.
BOLT FRAME OF FAN
HOUSING TO SUPPORT
FRAME WITH 1/4"Ø
BOLTS.
2"x2"x1/8" ANGLE
SUPPORT FRAME.
WELD ALL
AROUND.
ATTACH TO WALL
WITH 3/8"x2" LAG
BOLTS AND
INSERTS
WALL
UNISTRUT ANCHORED TO WALL
UNISTRUT CLAMP
GAS PIPING
SEF
O
R P
HATUFOETATS
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities
Department of Administrative Services
Internet: http://www.dfcm.state.ut.us
State of Utah A
LL
ID
E A
S , D
E S
IG
N
S , A
R R
A N
G E
M E
N T
S A
N D
P
LA
N S
IN
D
IC
A
T E
D O
R R
E P
R E
S E
N T
E D
B Y
T H
IS
D
R A
W
IN
G A
R E
O W
N E
D B
Y A
N D
T H
E P
R O
P E
R T
Y O
F W
H W
E N
G
IN
E E
R
IN
G
IN
C . A
N D
W E
R E
C R
E A
T E
D
E V
O
LV
E D
A
N D
D E
V E
LO
P
E D
F O
R U
S E
O N
A N
D
IN
C O
N N
E C
T
IO
N W
IT
H
T H
E S
P E
C
IF
IE
D
P R
O
JE
C T
N
O N
E O
F T
H E
ID
E
A S
D
E S
IG
N
S
A R
R A
N G
E M
E N
T S
O R
P
LA
N S
S H
A
LL
B E
U S
E D
B Y
O R
D
IS
C
LO
S E
D T
O A
N Y
P E
R S
O N
, F
IR
M
O R
C O
R P
O R
A T
IO
N
F O
R A
N Y
P U
R P
O S
E W
H A
T S
O E
V E
R W
IT
H
O U
T W
R
IT
T E
N C
O N
S E
N T
O F
W H
W E
N G
IN
E
E R
IN
G
IN
C
W
R
IT
T E
N D
IM
E
N S
IO
N
S O
N T
H E
S E
D R
A W
IN
G
S S
H A
LL
H
A V
E P
R E
C E
D E
N C
E O
V E
R S
C A
LE
D
IM
E
N S
IO
N
S
C O
N T
R A
C T
O R
S S
H A
LL
V
E R
IF
Y
A N
D B
E R
E S
P O
N S
IB
LE
F O
R A
LL
D
IM
E
N S
IO
N
S A
N D
C O
N D
IT
IO
N S
O N
T H
E J
O B
A N
D T
H
IS
O F
F
IC
E M
U S
T B
E N
O T
IF
IE
D O
F A
N Y
V A
R
IA
T
IO
N F
R O
M T
H E
D
IM
E N
S
IO
N S
A N
D C
O N
D
IT
IO
N
S S
H O
W N
B Y
T H
E S
E D
R A
W
IN
G S
W
A R
N
IN
G : R
E P
R O
D U
C T
IO
N
H E
R E
O F
IS
A
C R
IM
IN
A L
O F
F E
N S
E U
N D
E R
U .S
.C . S
E C
. 5
. U N
A U
T H
O R
IZ
E
D D
IS
C
LO
S
U R
E M
A Y
C O
N S
T
IT
U T
E T
R A
D E
S E
C R
E T
M
IS
A P
P R
O P
R
IA
T
IO
N
IN
V
IO
LA
T
IO
N
O F
I.
C
.2 4-
2-
-1 E
T . S
E Q
. A N
D O
T H
E R
L A
W S
CONSULTANTS
PROJECT NAME & ADDRESS
CODE REVIEW STAMP
SHEET NO.
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
08/08/2025
WHW JOB NO.:
25078
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SHEET TITLE
E E
WP
STAFF
CL
733 S Cowboy Way Kanab, UT 84741
SWATC KANAB
SHOP
MECHANICAL
UPGRADE
DFCM #26066270
08/08/25
MECHANICAL DETAILS
ME502
SCALE: NONE
1 DRUM LOUVER DETAIL
SCALE: NONE
2 TURNING VANE DETAIL
SCALE: NONE
3 WALL MOUNTED EXHAUST FAN DETAIL
1/8" = 1'-0"
GAS LINE WALL ANCHOR DETAIL
1/8" = 1'-0"
ME501
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/21/2025
1. PROVIDE SMOKE DETECTOR IN SUPPLY AND RETURN AIR FOR ALL UNITS OVER 2,000 CFM.
2. RATED MINIMUM INPUT AT 5000'.
3. PROVIDE ONE 15 AMP, 120 VOLT, DUPLEX GFCI SERVICE OUTLET. FACTORY INSTALLED, FIELD WIRED.
4. ESP DOES NOT INCLUDE LOSSES THROUGH ACCESSORIES.
5. BELT DRIVE UNIT.
6. PROVIDE 100% OUTSIDE AIR ECONOMIZER.
7. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.
8. PROVIDE VOLTAGE AND PHASE MONITORS.
9. PROVIDE WITH COIL HAIL GUARDS.
10. SET OUTSIDE AIR TO 1300 CFM WHILE OCCUPIED AND WHEN EXHAUST SYSTEM IS RUNNING. SET STANDBY OUTSIDE AIR TO 260 CFM WHILE UNOCCUPIED.
11. PROVIDE WITH POWERED EXHAUST.
12. PROVIDE WITH COMPRESSOR BLANKETS FOR NOISE DAMPENING. COPELAND SOUND SHELL OR APPROVED EQUAL.
1. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.
2. FINISH SHALL BE STANDARD WHITE.
1. PROVIDE WITH 2 SPEED CONTROLLER. RUN HIGH LIMIT CFM WHILE OCCUPIED. TIE INTO OCCUPANCY SENSOR. RUN STANDBY CFM WHILE UNOCCUPIED.
2. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.
SEF
O
R P
HATUFOETATS
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities
Department of Administrative Services
Internet: http://www.dfcm.state.ut.us
State of Utah A
LL
ID
E A
S , D
E S
IG
N
S , A
R R
A N
G E
M E
N T
S A
N D
P
LA
N S
IN
D
IC
A
T E
D O
R R
E P
R E
S E
N T
E D
B Y
T H
IS
D
R A
W
IN
G A
R E
O W
N E
D B
Y A
N D
T H
E P
R O
P E
R T
Y O
F W
H W
E N
G
IN
E E
R
IN
G
IN
C . A
N D
W E
R E
C R
E A
T E
D
E V
O
LV
E D
A
N D
D E
V E
LO
P
E D
F O
R U
S E
O N
A N
D
IN
C O
N N
E C
T
IO
N W
IT
H
T H
E S
P E
C
IF
IE
D
P R
O
JE
C T
N
O N
E O
F T
H E
ID
E
A S
D
E S
IG
N
S
A R
R A
N G
E M
E N
T S
O R
P
LA
N S
S H
A
LL
B E
U S
E D
B Y
O R
D
IS
C
LO
S E
D T
O A
N Y
P E
R S
O N
, F
IR
M
O R
C O
R P
O R
A T
IO
N
F O
R A
N Y
P U
R P
O S
E W
H A
T S
O E
V E
R W
IT
H
O U
T W
R
IT
T E
N C
O N
S E
N T
O F
W H
W E
N G
IN
E
E R
IN
G
IN
C
W
R
IT
T E
N D
IM
E
N S
IO
N
S O
N T
H E
S E
D R
A W
IN
G
S S
H A
LL
H
A V
E P
R E
C E
D E
N C
E O
V E
R S
C A
LE
D
IM
E
N S
IO
N
S
C O
N T
R A
C T
O R
S S
H A
LL
V
E R
IF
Y
A N
D B
E R
E S
P O
N S
IB
LE
F O
R A
LL
D
IM
E
N S
IO
N
S A
N D
C O
N D
IT
IO
N S
O N
T H
E J
O B
A N
D T
H
IS
O F
F
IC
E M
U S
T B
E N
O T
IF
IE
D O
F A
N Y
V A
R
IA
T
IO
N F
R O
M T
H E
D
IM
E N
S
IO
N S
A N
D C
O N
D
IT
IO
N
S S
H O
W N
B Y
T H
E S
E D
R A
W
IN
G S
W
A R
N
IN
G : R
E P
R O
D U
C T
IO
N
H E
R E
O F
IS
A
C R
IM
IN
A L
O F
F E
N S
E U
N D
E R
U .S
.C . S
E C
. 5
. U N
A U
T H
O R
IZ
E
D D
IS
C
LO
S
U R
E M
A Y
C O
N S
T
IT
U T
E T
R A
D E
S E
C R
E T
M
IS
A P
P R
O P
R
IA
T
IO
N
IN
V
IO
LA
T
IO
N
O F
I.
C
.2 4-
2-
-1 E
T . S
E Q
. A N
D O
T H
E R
L A
W S
CONSULTANTS
PROJECT NAME & ADDRESS
CODE REVIEW STAMP
SHEET NO.
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
08/08/2025
WHW JOB NO.:
25078
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SHEET TITLE
E E
WP
STAFF
CL
733 S Cowboy Way Kanab, UT 84741
SWATC KANAB
SHOP
MECHANICAL
UPGRADE
DFCM #26066270
08/08/25
MECHANICAL
SCHEDULES
ME601
DIFFUSER AND GRILLE SCHEDULE
TAG
MAX
FLOW
FACE SIZE NECK SIZE
CEILING
TYPE
BLOW
PATTERN
THROW @
50 FPM MAX NC
MANUF &
MODEL
SCHEDULE
NOTESLENGTH WIDTH
LENGTH/
DIAMETER WIDTH
D-1 2,800 CFM 12" 6" 12" 6" DUCT
MOUNTED
0 38' 25 PRICE
HCD
1,2
EG-1 350 CFM 18" 6" 18" 6" SPIRAL 0 0' 25 PRICE
SDGER
1,2
R-1 2,800 CFM 42" 18" 40" 16" DUCT
MOUNTED
N/A 0' 25 PRICE 95 1,2
PACKAGED AIR UNIT SCHEDULE
TAG
AREA
SERVED CFM
OCCUPIED
CFM (OUTSIDE
AIR)
STANDBY
CFM
(OUTSIDE
AIR) ESP
HEATING COOLING ELECTRICAL
ARI EER (7.5+
TON)
OPERATING
WEIGHT MANUF & MODEL SCHEDULE NOTESTYPE #
INPUT
(BTU/HR)
OUTPUT
(BTU/HR) EAT (DB) EAT (WB)
TOTAL LOAD
(BTU/HR) VOLTAGE PHASE
FREQUENC
Y
# OF
COMPRESSORS MCA MOCP
PAU 1 SERVICE
CENTER
2,400 CFM 1,300 CFM 480 CFM 1.5 in-wg 53,600 Btu/h
43,200 Btu/h
80 °F 62 °F 60000 Btu/h 208 V 3 60 Hz 1 34 A 50 A 11.2 607 lb CARRIER
48FEDM07C3A5
1,2,3,4,5,6,7,8,9,10,11,12
PAU 2 SERVICE
CENTER
2,400 CFM 1,300 CFM 480 CFM 1.5 in-wg 53,600 Btu/h
43,200 Btu/h
80 °F 62 °F 60000 Btu/h 208 V 3 60 Hz 1 34 A 50 A 11.2 607 lb CARRIER
48FEDM07C3A5
1,2,3,4,5,6,7,8,9,10,11,12
EXHAUST FAN SCHEDULE
TAG AREA
SERVED
HIGH
LIMIT CFM
STANDBY
CFM ESP
ELECTRICAL MAX
SONES
OPERATING
WEIGHT MANUF & MODEL
SCHEDULE
NOTESTYPE # VOLTAGE PHASE FREQUENCY RPM HP FLA
EF 1 SERVICE
CENTER
2,750 CFM 250 CFM 0.30 in-wg 120 V 1 60 Hz 1600 1 hp 16 11.5 83 lb GREENHECK
AER-24-02-0515-VG
1,2
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/21/2025
R-1
R-1
20"x20" RA
20"x20" RA
20"ø SA20"ø SA
PAU
PAU
D-1
TYP 24
EF
EG-1
EG-1
EG-1
EG-1
EG-1
2 2
20"ø EA12"ø EA
12"ø EA
12"ø EA
12"ø EA
12"ø EA
12"ø EA
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
S
CO
S
NO2
SEF
O
R P
HATUFOETATS
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
Fax: (801) 538 - 3267 Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building Construction & Management Division of Facilities
Department of Administrative Services
Internet: http://www.dfcm.state.ut.us
State of Utah A
LL
ID
E A
S , D
E S
IG
N
S , A
R R
A N
G E
M E
N T
S A
N D
P
LA
N S
IN
D
IC
A
T E
D O
R R
E P
R E
S E
N T
E D
B Y
T H
IS
D
R A
W
IN
G A
R E
O W
N E
D B
Y A
N D
T H
E P
R O
P E
R T
Y O
F W
H W
E N
G
IN
E E
R
IN
G
IN
C . A
N D
W E
R E
C R
E A
T E
D
E V
O
LV
E D
A
N D
D E
V E
LO
P
E D
F O
R U
S E
O N
A N
D
IN
C O
N N
E C
T
IO
N W
IT
H
T H
E S
P E
C
IF
IE
D
P R
O
JE
C T
N
O N
E O
F T
H E
ID
E
A S
D
E S
IG
N
S
A R
R A
N G
E M
E N
T S
O R
P
LA
N S
S H
A
LL
B E
U S
E D
B Y
O R
D
IS
C
LO
S E
D T
O A
N Y
P E
R S
O N
, F
IR
M
O R
C O
R P
O R
A T
IO
N
F O
R A
N Y
P U
R P
O S
E W
H A
T S
O E
V E
R W
IT
H
O U
T W
R
IT
T E
N C
O N
S E
N T
O F
W H
W E
N G
IN
E
E R
IN
G
IN
C
W
R
IT
T E
N D
IM
E
N S
IO
N
S O
N T
H E
S E
D R
A W
IN
G
S S
H A
LL
H
A V
E P
R E
C E
D E
N C
E O
V E
R S
C A
LE
D
IM
E
N S
IO
N
S
C O
N T
R A
C T
O R
S S
H A
LL
V
E R
IF
Y
A N
D B
E R
E S
P O
N S
IB
LE
F O
R A
LL
D
IM
E
N S
IO
N
S A
N D
C O
N D
IT
IO
N S
O N
T H
E J
O B
A N
D T
H
IS
O F
F
IC
E M
U S
T B
E N
O T
IF
IE
D O
F A
N Y
V A
R
IA
T
IO
N F
R O
M T
H E
D
IM
E N
S
IO
N S
A N
D C
O N
D
IT
IO
N
S S
H O
W N
B Y
T H
E S
E D
R A
W
IN
G S
W
A R
N
IN
G : R
E P
R O
D U
C T
IO
N
H E
R E
O F
IS
A
C R
IM
IN
A L
O F
F E
N S
E U
N D
E R
U .S
.C . S
E C
. 5
. U N
A U
T H
O R
IZ
E
D D
IS
C
LO
S
U R
E M
A Y
C O
N S
T
IT
U T
E T
R A
D E
S E
C R
E T
M
IS
A P
P R
O P
R
IA
T
IO
N
IN
V
IO
LA
T
IO
N
O F
I.
C
.2 4-
2-
-1 E
T . S
E Q
. A N
D O
T H
E R
L A
W S
CONSULTANTS
PROJECT NAME & ADDRESS
CODE REVIEW STAMP
SHEET NO.
PROJECT MANAGER:
DATE:
CHECKED BY:
DRAWN BY:
REVISIONDATEMARK
08/08/2025
WHW JOB NO.:
25078
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SHEET TITLE
E E
WP
STAFF
CL
733 S Cowboy Way Kanab, UT 84741
SWATC KANAB
SHOP
MECHANICAL
UPGRADE
DFCM #26066270
08/08/25
MECHANICAL
ISOMETRICS
ME901
MECHANICAL ISOMETRIC
MECHANICAL EXHAUST AIR SWEEP
ISOMETRIC
SHEET NOTES
1 PROVIDE EXHAUST GRILLE 8' 6" AFF IN THIS
APPROXIMATE LOCATION. BALANCE TO CFM SHOWN.
PROVIDE WITH BALANCING DAMPERS ABOVE AND
BELOW GRILLE. THE INTENT IS TO PROVIDE A HIGH
AND LOW BALANCED EXHAUST RATE ON EACH
EXHAUST DROP. FIELD VERIFY EXACT POSITIONING.
2 TERMINATE EXHAUST DUCTWORK 12" AFF IN THIS
APPROXIMATE LOCATION. BALANCE EXHAUST TO 275
CFM. COVER OPENING WITH NON CORROSIVE BIRD
SCREEN. THE INTENT IS TO PROVIDE A HIGH AND
LOW BALANCED EXHAUST RATE ON EACH EXHAUST
DROP. FIELD VERIFY EXACT POSITIONING.
3 PROVIDE HIGH WALL-MOUNTED EXHAUST FAN IN
THIS APPROXIMATE LOCATION. PROVIDE WITH NEMA
4 RATED WEATHER HOOD AND BACK DRAFT DAMPER.
PROVIDE WITH 2 SPEED CONTROLLER. PROVIDE
WITH OCCUPANCY SENSOR AND INTERLOCK WITH
NEW PACKAGE AIR UNIT TO RUN OCCUPIED HIGH
FLOW RATE OF 2,750 CFM WHILE OCCUPIED.
BALANCE STANDBY FLOW RATE TO 250 CFM WHILE
UNOCCUPIED. FIELD VERIFY.
4 PROVIDE NEW GROUND-MOUNTED PACKAGED AIR
UNIT IN THIS APPROXIMATE LOCATION. PROVIDE
WITH ALL NEW ELECTRICAL ACCOMMODATIONS BY A
LICENSED DESIGN BUILD ELECTRICIAN. PROVIDE
NEW DUCTWORK THROUGH WALL PENETRATION.
SEAL AND WEATHERPROOF WALL PENETRATION.
PROVIDE OUTDOOR RATED PRE INSULATED, CLOSED
CELL DUCTWORK WITH IMPACT RESISTANT JACKET.
THERAMDUCT OR APPROVED EQUAL ON ALL
EXPOSED DUCTWORK. FIELD VERIFY DIMENSIONS
PRIOR TO COMMENCING WORK. PROVIDE NEW GAS
TRAIN AND PIPING AND TIE INTO EXISTING GAS
PIPING. FIELD VERIFY EXACT ROUTING. PROVIDE
WITH COIL HAIL GUARDS. PROVIDE WITH
OCCUPANCY SENSOR TO TURN ON EXHAUST FAN
AND SWITCH PACKAGED AIR OUTSIDE AIR TO MATCH
EXHAUST FAN RATE WHEN SHOP IS OCCUPIED.
PROVIDE WITH NEW 3" CONCRETE EQUIPMENT CURB.
INSTALL PER MANUFACTURERS RECOMMENDATIONS
FOR A COMPLETE INSTALL.
5 PROVIDE NEW RETURN GRILLE IN THIS
APPROXIMATE LOCATION. FIELD VERIFY.
6 PROVIDE RETURN AIR DUCTWORK IN THIS
APPROXIMATE LOCATION. KEEP 8' AFF. FIELD VERIFY
EXACT DUCT ROUTING.
7 PROVIDE SPIRAL DUCT MOUNTED DIFFUSER IN THIS
APPROXIMATE LOCATION. BALANCE TO CFM SHOWN.
FIELD VERIFY.
8 PROVIDE NEW UL LISTED 2075 NO2 SENSOR 12" AFF
IN THIS APPROXIMATE LOCATION. TIE INTO AN
AUDIBLE AND VISABLE ALARM COMBO TO ACTIVATE
WHEN CO OR NO2 IS DETECTED, AUTOMATION
COMPONENTS FSIG-SLM500 OR APPROVED EQUAL.
SENSOR SHALL ACTIVATE HIGH RATE CFM FOR BOTH
EXHAUST FAN AND PACKAGED AIR UNIT. PROVIDE
ALL NEW ELECTRICAL ACCOMMODATIONS. PROVIDE
WITH MEANS FOR MANUAL SILENCE OVERRIDE.
FIELD VERIFY.
9 PROVIDE NEW UL LISTED 2075 CO SENSOR 5' AFF IN
THIS APPROXIMATE LOCATION. TIE INTO AUDIBLE
AND VISABLE ALARM COMBO TO ACTIVATE WHEN CO
OR NO2 IS DETECTED, AUTOMATION COMPONENTS
FSIG-SLM500 OR APPROVED EQUAL. SENSOR SHALL
ACTIVATE HIGH RATE CFM FOR BOTH EXHAUST FAN
AND PACKAGED AIR UNIT. PROVIDE ALL NEW
ELECTRICAL ACCOMMODATIONS. PROVIDE WITH
MEANS FOR MANUAL SILENCE OVERRIDE. FIELD
VERIFY.
GENERAL NOTES:
1.CONTRACTOR SHALL FIELD VERIFY EXISTING
MECHANICAL, STRUCTURAL, ELECTRICAL AND
ARCHITECTURAL CONDITIONS, INCLUDING, BUT NOT LIMITED
TO: EXISTING ROUTING AND LOCATION OF DUCTWORK,
PIPING, ELECTRICAL, AND STRUCTURAL ELEMENTS.
CONTRACTOR SHALL FIELD VERIFY ANY POTENTIAL
CONFLICTS BETWEEN NEW MECHANICAL ELEMENTS AND
EXISTING CONDITIONS PRIOR TO BEGINNING FABRICATION
OR ORDERING NEW EQUIPMENT.
2. PRIME CONTRACTOR SHALL PROVIDE ALL COORDINATION
BETWEEN SUB-TIER CONTRACTORS. THIS SHALL INCLUDE
THE COORDINATION BETWEEN SUB-TIER CONTRACTORS,
SUB-TIER CONTRACTORS AND FACILITIES, SUB-TIER
CONTRACTORS AND ARCHITECT/ENGINEER, ETC.
3. FIELD VERIFY STRUCTURAL COMPONENTS PRIOR TO
CUTTING PENETRATIONS FOR MECHANICAL EQUIPMENT.
AVOID ALL STRUCTURAL COMPONENT.
4. ALL ROOFING MODIFICATIONS MUST BE DONE THE
ROOFING WARRANTY HOLDING CONTRACTOR. IF
WARRANTY IS EXPIRED, ROOFING MODIFICATIONS MUST BE
BY A DFCM APPROVED SHORT LIST ROOFING CONTRACTOR.
5. ISOMETRIC AND COORDINATION VIEWS ARE FOR
GENERAL LAYOUT ROUTING AND NOT FOR PART COUNT OR
BIDDING PURPOSE. CONTRACTOR SHALL BE REQUIRED TO
PROVIDE ALL PIPING, DUCT, BENDS, FITTINGS,
ACCESSORIES, OFFSETS, ETC AS NEEDED FOR A COMPLETE
INSTALLATION DETERMINED BY THE EXISTING FIELD
VERIFIED CONDITIONS.
6. CONTRACTOR SHALL COORDINATE WITH DFCM PROVIDED
HAZMAT REPORT PRIOR TO THE DEMOLITION OF ANY
EQUIPMENT, DUCTWORK, DUCT INSULATION, PIPING, PIPE
INSULATION, ETC.
7. PROVIDE BALANCING DAMPERS ON ALL SUPPLY AND
RETURN BRANCHES.
8. ISOMETRIC AND COORDINATION VIEWS ARE FOR
GENERAL LAYOUT ROUTING AND NOT FOR PART COUNT OR
BIDDING PURPOSE. CONTRACTOR SHALL BE REQUIRED TO
PROVIDE ALL PIPING, DUCT, BENDS, FITTINGS,
ACCESSORIES, OFFSETS, ETC AS NEEDED FOR A COMPLETE
INSTALLATION DETERMINED BY THE EXISTING FIELD
VERIFIED CONDITIONS.
9. ALL DUCTWORK LOCATED OUTDOORS SHALL BE PRE-
INSULATED, CLOSED CELL DUCTWORK WITH IMPACT
RESISTANT JACKET. PROVIDE WITH THERMADUCT OR
APPROVED EQUAL.
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
08/21/2025
| Sheets |
| G001 - TITLE |
| ME101 - MECHANICAL PLAN |
| ME501 - MECHANICAL DETAILS |
| ME502 - MECHANICAL DETAILS |
| ME601 - MECHANICAL SCHEDULES |
| ME901 - MECHANICAL ISOMETRICS |
| MG001 - MECHANICAL LEGEND AND GENERAL NOTES |
| MG002 - SPECIAL INSTRUCTIONS AND TESTING |