DIA ATCT Dry 2.pdf
PDF 148 KB Posted
- Solicitation number
- 697DCK-25-R-00096
About this file
This is a Contractor's Material & Test Certificate for Aboveground Piping completed for the Denver International Airport Air Traffic Control Tower (DIA ATCT) located at 8500 Pena Blvd, Denver, CO dated 11-02-10. The document details the installation and testing of fire protection equipment between the fifth and eighth floors of the supplies building.
The certificate provides specific technical information about the sprinkler system components, including Reliable F1FR-300 SSU sprinklers (8 rated at 286°F and 32 rated at 155°F), Schedule 10 and 40 galvanized piping, and a Victaulic Firelock NXT 768 dry valve. Testing data shows the system was pneumatically tested at 40 psi air pressure with successful results. The installation was completed by Western States Fire Protection Company and approved by the Federal Aviation Administration, with all required inspections, testing, and documentation verified as compliant with specifications.
View the file
Other files
Show all 24