BJC - FireAlarm Inspect Report 062923.pdf

PDF 109 KB Posted

Attached to
Fire Life Safety Maintenance and Testing at DEN, D01, BJC Federal contract opportunity
Solicitation number
697DCK-25-R-00096
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This is a fire alarm inspection report dated June 29, 2023, for the FAA Control Tower in Broomfield, Colorado, conducted by First Call Electric & Fire. The inspection covered a Class B system and was performed according to NFPA 72 and manufacturer's instructions. The facility contains 17 manual stations, 43 smoke detectors, 6 duct smoke detectors, 5 heat detectors, and 10 flow switches - all of which tested successfully. The system is monitored by Siemens central station (account #112002375).

The inspection revealed that while most system components are functioning properly, including control equipment, initiating devices, and auxiliary functions, the technician noted that two 55ah/12v batteries in the Fire Alarm Control Panel (FACP) need replacement. The report was signed by technician Josh Blatt and appears to be part of documentation related to a broader FAA solicitation (697DCK-25-R-00096) for Fire Life Safety Maintenance and Testing services at multiple FAA facilities.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Life Safety Maintenance and Testing at DEN, D01, BJC, newest first.
File Type Posted
697DCK-25-R-00096-0005.pdf PDF
697DCK-25-R-00096-0004.pdf PDF
D01 Sprinkler System As-Built Drawings 1992.pdf PDF
DEN-TRACO_Fire Alarm Set.pdf PDF
DIA ATCT-Fire Alarm-FA2.pdf PDF
DIA ATCT Wet 4.pdf PDF
697DCK-25-R-00096-0003.pdf PDF
BJC - System Breakdown 2023.pdf PDF
DEN ATCT Fire Suppression As-Built Binder.pdf PDF
DIA ATCT-Fire Alarm-FA3.pdf PDF
DIA ATCT Dry 1.pdf PDF
DIA ATCT Dry 2.pdf PDF
DIA ATCT Dry 3.pdf PDF
DIA ATCT Wet 6.pdf PDF
DIA ATCT Wet 7.pdf PDF
OandM Sprinkler.PDF PDF
BJC - Inspect-Test Report 013122.pdf PDF
DIA ATCT Wet 5.pdf PDF
ZDV Architecture Drawings.pdf PDF
DIA ATCT-Fire Alarm-FA1.pdf PDF
DIA ATCT Wet 8.pdf PDF
697DCK-25-R-00096-0002.pdf PDF
697DCK-25-R-00096-0001.pdf PDF
16 - 697DCK-25-R-00096.pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM INSPECTION REPORT

Has report been sent out?

(yes) (no)

Inspection Date: 06/29/23

Contractor: First Call Electric & Fire Phone # (303) 828-1362

Business Name: FAA Control Tower Broomfield Phone # (720) 633-8600 MGR Name: David Garcia

Business Address (Street Address): 11001 Control Tower Road, Broomfield, CO 80021, USA

System Class: B Style:

Test Standard NFPA 72 Manufacturer's Intructions

Please complete all of the following sections. All "no" answers must be explained in comments.

CONTROL EQUIPMENT SIGNALING DEVICES & CIRCUITS

Panel Function Yes n/a No Audible Yes n/a No

1. All alarms received? 11. # Horns All Tested successfully?

2. All circuits supervised? 12. # Chimes Tested successfully?

3. Ground fault indication tested successfully? 13. # Speakers Was voice clear?

4. Power supply tested successfully? 14. Other Tested successfully?

5. Fuses - Rating verified?

15. Is sound level at least 15 db above ambient noise level?

6. Interfaced equipment connections tested successfully? Visible

7. All lamps and LEDs operational? 16. # Strobes All Tested successfully?

8. Secondary power supply tested successfully? 17. # Lights Tested successfully?

9. Zone labeling is correct? 18. # Other Tested successfully?

10. Annunciator panel is operational? 19. 100% of all signalling devices tested?

ALARM INITIATING DEVICES & CIRCUITS

Yes n/a No

20. # Manual stations 17 Tested successfully?

21. # Flow switches 10 Tested successfully?

22. # Smoke detectors 43 Tested successfully?

23. All smoke detectors cleaned using an approved method?

24. Sensitivity of smoke detectors tested successfully? (every 2 years) Last test date

25. # Duct smoke detectors 6 Tested successfully?

26. Duct smoke detectors — anomemeter test results within manufacturer's specifications?

27. Duct smoke detectors successfully shut down AHUs on alarm?

28. Duct smoke detectors tied into fire alarm?

29. # Heat detectors 5 Tested successfully?

30. Sprinkler tamper switches reported to panel properly?

31. Other:

32. 100% of all initiating devices tested?

AUXILIARY FUNCTIONS/INTERFACED EQUIPMENT BATTERIES

Yes n/a No Yes n/a No

33. All smoke/fire dampers closed completely on alarm? 45. Charger test successful?

34. All smoke/fire dampers tied into alarm? 46. Discharge test successful?

35. All magnetic door holders release fire doors on alarm? 47. Load voltage test successful?

36. All door lock releases tested successfully? 48. Open circuit voltage test successful?

37. All door releases tied into fire alarm? 49. Primary battery load voltage test successful?

38. Positive pressure fans tested successfully? 50. Lead acid battery specific gravity test successful?

39. All smoke removal fans tested successfully?

(Attach separate Smoke Management System Report) CENTRAL STATION MONITORING

40. Hood extinguishing system tie-in tested successfully? 51. Is system monitored by central station?

41. Elevator recall tested successfully?

52. If so, were alarm/flow, tamper/supervisory, and trouble signals received by central station?

42. Voice evacuation system tested successfully?

43. Clean gas system (halon, FM200, etc.) tested successfully? (Attach separate report) Siemens / 112002375 (800) 560-8335

44. Other: (monitoring/Account Number) Phone Number

Technician's Comments:

Notes:

2 bad 55ah/12v batteries need replaced in FACP

Assigned Technician: Josh Blatt Signature Josh Blatt

(select Insert > Drawing > Scribble, draw signature, and insert into sheet)