BJC - Inspect-Test Report 013122.pdf
PDF 330 KB Posted
- Attached to
- Fire Life Safety Maintenance and Testing at DEN, D01, BJC Federal contract opportunity
- Solicitation number
- 697DCK-25-R-00096
About this file
This is a NFPA 72 inspection and testing report for the fire alarm system at Rocky Mountain Metropolitan Airport completed by Siemens Industry on January 31, 2022. The report documents testing of a Siemens XLS fire alarm control panel located in the main lobby at 11755 Airport Way, Broomfield, CO.
The inspection evaluated multiple system components including the control unit, primary/secondary power, notification appliances, initiating devices, and interface equipment. Key findings show that most systems passed functional testing, with two failures noted: Level 6 Elevator Lobby SD 1-159 was not in disables, and PSC-12 had a battery charger fail trouble. The report details testing of 14 control valve switches, 6 duct smoke detectors, 5 heat detectors, 17 manual pull stations, 43 system smoke detectors, and 11 waterflow devices across multiple building levels. Battery testing revealed replacement of failed batteries in Level 1 RPS units was completed during the inspection. The testing was witnessed by property representative David Garcia of the FAA, with notifications made to building management and Siemens CMS monitoring center before and after testing.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 697DCK-25-R-00096-0005.pdf | ||
| 697DCK-25-R-00096-0004.pdf | ||
| BJC - FireAlarm Inspect Report 062923.pdf | ||
| D01 Sprinkler System As-Built Drawings 1992.pdf | ||
| DEN-TRACO_Fire Alarm Set.pdf | ||
| DIA ATCT-Fire Alarm-FA2.pdf | ||
| DIA ATCT Wet 4.pdf | ||
| 697DCK-25-R-00096-0003.pdf | ||
| DIA ATCT-Fire Alarm-FA1.pdf | ||
| DIA ATCT Wet 8.pdf | ||
| DIA ATCT Wet 5.pdf | ||
| ZDV Architecture Drawings.pdf | ||
| BJC - System Breakdown 2023.pdf | ||
| DEN ATCT Fire Suppression As-Built Binder.pdf | ||
| DIA ATCT-Fire Alarm-FA3.pdf | ||
| DIA ATCT Dry 1.pdf | ||
| DIA ATCT Dry 2.pdf | ||
| DIA ATCT Dry 3.pdf | ||
| DIA ATCT Wet 6.pdf | ||
| DIA ATCT Wet 7.pdf | ||
| OandM Sprinkler.PDF | ||
| 697DCK-25-R-00096-0002.pdf | ||
| 697DCK-25-R-00096-0001.pdf | ||
| 16 - 697DCK-25-R-00096.pdf |
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NFPA 72 REPORT
© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2022. All rights reserved.
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 7
SYSTEM RECORD OF INSPECTION AND TESTING
System Name: Fire Alarm Control Panel Panel Name: 01 - Rocky Mountain Metro Airport
Inspection/Test Start Date/Time: 31 Jan 2022 0900 Inspection/Test Completion Date/Time: 31 Jan 2022 1530
Contract Info: BCO2-FIS-Denver FAA Fire and Sprinkler S (2600118537) Notification Number: 5102182085
Supplemental Form(s) Attached: Yes
1. PROPERTY INFORMATION
Name of property: ROCKY MOUNTAIN METROPOLITAN AIRPORT (4433-80021-00032)
Address: Main Lobby
Description of property:
Name of property representative: UNITED STATES (30635200), DAVID GARCIA
Address: 2200 S 216TH ST, DES MOINES, WA 98198-6547
Phone: 720-633-8620 Fax: None E-mail: DAVID.B.GARCIA@FAA.GOV
2. TESTING AND MONITORING INFORMATION
Testing organization: SIEMENS
Address: 143 Union Blvd, Suite 300, Lakewood, CO 80228
Phone: 303-279-8500 Fax: NA E-mail: NA
Monitoring organization: Siemens
Address: 8600 N Royal Lane, Suite 100, Irving, TX 75063
Phone: 866-552-7823 Fax: 800-315-4432 E-mail: alarm.admin.industry@siemens.com
Account number: NA Phone line 1: NA Phone line 2: NA
Means of transmission: Parallel Phone
Entity to which alarms are retransmitted: NA Phone: NA
3. DOCUMENTATION
On-site location of the required record documents and site-specific software:
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
System Name: Fire Alarm Control Panel Panel Name: 01 - Rocky Mountain Metro Airport
Panel Location and Address: Main Lobby, 11755 Airport Way, Broonmfield, CO 80021
Manufacturer: Siemens Model number: XLS
4.2 Software and Firmware
Firmware revision number: 12.03
4.3 System Power
4.3.1 Primary (Main) Power
Nominal voltage: 123.5 vac Amps: 5 Location: Main Lobby
Overcurrent protection type: Breaker Amps: 20
Disconnecting means location: Electric Room 124, EBL124, Breaker 34
4.3.2 Secondary Power
Type: Storage Battery Location: Main Lobby
Battery type (if applicable): Sealed Lead Acid Manufactured Date:
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 7
4.4 Notification Appliance Power Extender Panels
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: Siemens CMS Time: 0959
Building management Contact: David Garcia Time: 0950
Building occupants Contact: Time:
Authority having jurisdiction (AHJ) Contact: Time:
Other, if required Contact: Time:
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Description Visual Inspection or Functional Test Comments
Control unit Visual, Functional
Disconnect switches Functional
Fuses Not Tested
Ground-fault monitoring Functional
Interface Equipment Not Tested
Lamps/LEDs/LCDs Visual, Functional
Local annunciator Visual, Functional
Primary Power Functional
Remote annunciators Visual, Functional 200 Level 1 Link Vestibule, 201 Level 1 Exit Stair, 208 Level 8 CAB
Remote power panels Functional
Supervision Functional
Trouble signals Functional
6.2 Secondary Power
Description Visual Inspection or Functional Test Comments
Battery condition Visual, Functional
Charger test Functional
Discharge test Functional
Load voltage Functional
Remote panel batteries Visual, Functional Customer replaced failed Batteries in Level 1 RPS's
6.4 Alarm and Supervisory Alarm Initiating Device
Attach supplementary device test sheets for all initiating devices.
6.5 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances.
6.6 Interface Equipment
Attach supplementary interface component test sheets for all interface components.
LOCATION SIZE TEST DATE CHARGE STATIC % GOOD CONNECTION INSTALL DATE COMMENT
FACP 55 AH 1/31/22 27.22 26.25 100% / 100% ok 2/18
Level 1 Electric Room 124 RPS 7 AH 1/31/22 27.46 0% / 40% ok Customer Replaced 1/31/22
Level 1 Link RPS 7 AH 1/31/22 27.41 0% / 40% ok Customer Replaced 1/31/22
Level 6 Tower Room 610 RPS 7 AH 1/31/22 27.55 26.7 100% / 100% ok 1/21
BATTERY TESTING
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 7
6.7 Supervising Station Monitoring
Description Received Time / Elapsed
Time Pass/Fail Comments
Alarm signal Yes 1014 Pass
Alarm restoration Yes 1145 Pass
Trouble signal Yes 1001 Pass
Trouble restoration Yes 1145 Pass
Supervisory signal Yes 1041 Pass
Supervisory restoration Yes 1111 Pass
7. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: Siemens CMS Time: 1500
Building management Contact: David Garcia Time: 1515
Building occupants Contact: Time:
Authority having jurisdiction (AHJ) Contact: Time:
Other, if required Contact: Time:
8. SYSTEM RESTORED TO NORMAL OPERATION
Date: 31 Jan 2022 Time: 1530
9. CERTIFICATION
This Testing Was Performed in Accordance with Applicable NFPA Standards.
Signed: Scott Butler Date: 1/31/22
Printed name: Scott Butler, Casey Johnson Title: Technician License No.:
Organization: SIEMENS Phone: 303-279-8500
Qualifications (refer to NFPA 72, Section 10.5.3): Inspection, Testing, Service, Programming
10. SUMMARY OF EQUIPMENT MARKED AS FAILED WHEN INSPECTED OR TESTED
D1. Level 6 Elevator Lobby SD 1-159 Not In Disables
D2. PSC-12 Has ‘Battery Charger Fail’ Trouble
11. ACCEPTANCE BY OWNER OR OWNER’S REPRESENTATIVE
The undersigned accepted the test report for the system as specified herein:
Signed: Printed name: David Garcia Date:
Organization: UNITED STATES (30635200) Phone: 720-633-8620
Pursuant to applicable codes and standards, the owner or designated representative is responsible for proper maintenance and care of the system(s) identified in this report. During the site inspection, if Siemens has identified code deficiencies or impairments, Siemens will recommend certain corrective actions contained in this report. In the event the owner fails to correct such deficiencies or impairments within the required time period per the code, Siemens may be required to report such deficiencies or impairments to the Local AHJ or Fire Marshall per regulatory requirements. Customer shall hold Siemens harmless and releases Siemens of any and all liability due to Customer’s failure to correct such deficiencies or impairments.
12. OTHER
12.1 Special Procedures
12.2 Comments
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 7
INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
System Name: Fire Alarm Control Panel Panel Name: 01 - Rocky Mountain Metro Airport
Inspection/Test Start Date/Time: 31 Jan 2022 0900 Inspection/Test Completion Date/Time: 31 Jan 2022 1530
Contract Info: BCO2-FIS-Denver FAA Fire and Sprinkler S (2600118537) Notification Number: 5102182085
1. PROPERTY INFORMATION
Name of property: ROCKY MOUNTAIN METROPOLITAN AIRPORT (4433-80021-00032)
Address: Main Lobby
2. INITIATING DEVICE TEST RESULTS
2.1 Initiating Devices Equipment Summary by Type
Total Qty Functionally Tested Qty
Functionally Tested %
Visually Tested
Qty
Visually Tested %
Failed Qty Failed % Device or System Type
14 14 100% 0 0% 0 0% Control Valve Switches
6 6 100% 0 0% 0 0% Duct Smoke Detectors (P) (Supv)
1 0 0% 0 0% 0 0% Generator Running
1 0 0% 0 0% 0 0% Generator Trouble
5 3 60% 2 40% 0 0% Heat Detectors
1 1 100% 0 0% 0 0% High- or Low-Pressure Switches
17 17 100% 0 0% 0 0% Manual Pull Stations
1 0 0% 0 0% 0 0% Other Alarm Initiating Devices
43 43 100% 0 0% 0 0% System Smoke Detectors (P)
11 11 100% 0 0% 0 0% Waterflow Devices
2.2 Initiating Devices Testing Results by Type
Control Valve Switches
Row Date Dev.# Location Model Visual/ Functional
Pass/ Fail
1 01/31/22 001-011^1 Main Level Backflow Tamper HTRI-D Functional Pass
2 01/31/22 001-011^2 Main Level Backflow Tamper HTRI-D Functional Pass
3 01/31/22 001-015^2 Main Level Tamper HTRI-D Functional Pass
4 01/31/22 001-048^2 Main Lvl Dry System Tamper Valve HTRI-D Functional Pass
5 01/31/22 001-103^2 Level 1 Tower Standpipe Tamper HTRI-D Functional Pass
6 01/31/22 001-104^2 Level 1 Tower Tamper HTRI-D Functional Pass
7 01/31/22 001-114^2 Level 2 Tower Tamper HTRI-D Functional Pass
8 01/31/22 001-121^2 Level 3 Tower Tamper HTRI-D Functional Pass
9 01/31/22 001-124^1 Lvl 6 Elevator Closet Tamper HTRI-R Functional Pass
10 01/31/22 001-128^2 Level 4 Tower Tamper HTRI-D Functional Pass
11 01/31/22 001-135^2 Level 5 Tower Tamper HTRI-D Functional Pass
12 01/31/22 001-151^2 Level 6 Tower Tamper HTRI-D Functional Pass
13 01/31/22 001-169^2 Level 7 Tower Tamper HTRI-D Functional Pass
14 01/31/22 001-170^2 Level 8 Tower Tamper HTRI-D Functional Pass
Duct Smoke Detectors (P) (Supv)
Functional
Pass/ Fail
1 01/31/22 001-017 Main Lvl AHU-1 Duct HFP-11 Functional Pass
2 01/31/22 001-046^1 Main Lvl Rm 132 CRAC Unit #1 HTRI-D
3 01/31/22 001-046^2 Main Lvl Rm 132 CRAC Unit #2 HTRI-D
4 01/31/22 001-138 Level 5 SPF-1 Duct HFP-11 Functional Pass
5 01/31/22 001-152 Level 6 AHU-2 Duct HFP-11 Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 5 of 7
Duct Smoke Detectors (P) (Supv)
Row Date Dev.# Location Model Visual/ Functional
Pass/ Fail
6 01/31/22 001-154 Level 6 AHU-3 Duct HFP-11 Functional Pass
Generator Running
Functional
Pass/ Fail
1 001-043^1 Main Lvl Generator Running HTRI-D
Comment: Tested By Others
Generator Trouble
Functional
Pass/ Fail
1 001-043^2 Main Lvl Generator Trouble HTRI-D
Heat Detectors
Functional
Pass/ Fail
1 01/31/22 001-007 Main Lvl Break Room 113 Heat HFPT-11 Functional Pass
2 01/31/22 001-010 Main Lvl Break Room 113 Heat HFPT-11 Functional Pass
3 01/31/22 001-014 Main Lvl Mech Room 123 Heat HFPT-11 Functional Pass
4 01/31/22 001-021^1 Main Lvl Generator Room 125 Heat HTRI-M Visual Pass
Comment: One Use HD, Visual Only
5 01/31/22 001-142^1 Level 6 Elevator Closet 608 Heat HTRI-M Visual Pass
Comment: One Use Heat Detector, Visual Only
High- or Low-Pressure Switches
Functional
Pass/ Fail
1 01/31/22 001-049^1 Main Lvl Dry System Low Air HTRI-M Functional Pass
Comment: Tested Signaling Only
Manual Pull Stations
Functional
Pass/ Fail
1 01/31/22 001-002 Main Lvl Reception 102 Pull HMS Functional Pass
2 01/31/22 001-009 Main Lvl Break Room 113 Pull HMS Functional Pass
3 01/31/22 001-013 Main Lvl Mech Room 123 Pull HMS Functional Pass
4 01/31/22 001-020 Main Lvl Generator Room 125 Pull HMS Functional Pass
5 01/31/22 001-022 Main Lvl Electric Room 124 Pull HMS Functional Pass
6 01/31/22 001-024 Main Lvl Exit Vestibule 127 Pull HMS Functional Pass
7 01/31/22 001-027 Main Lvl Tech Area 129 Exit Pull HMS Functional Pass
8 01/31/22 001-038 Main Lvl Link 134 Exit Pull HMS Functional Pass
9 01/31/22 001-040 Main Lvl Link Vestibule136 Pull HMS Functional Pass
10 01/31/22 001-106 Level 1 Exit Stair Pull HMS Functional Pass
11 01/31/22 001-112 Level 2 Elevator Lobby Pull HMS Functional Pass
12 01/31/22 001-120 Level 3 Elevator Lobby Pull HMS Functional Pass
13 01/31/22 001-127 Level 4 Elevator Lobby Pull HMS Functional Pass
14 01/31/22 001-134 Level 5 Elevator Lobby Pull HMS Functional Pass
15 01/31/22 001-148 Level 6 Stair Vestibule Pull HMS Functional Pass
16 01/31/22 001-174 Level 7 Stair Vestibule Pull HMS Functional Pass
17 01/31/22 001-178 Level 8 CAB Pull HMS Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 6 of 7
Other Alarm Initiating Devices
Row Date Dev.# Location Model Visual/ Functional
Pass/ Fail
1 001-034^1 Main Lvl Break Room 113 Hood Sys HTRI-M
System Smoke Detectors (P)
Functional
Pass/ Fail
1 01/31/22 001-001 Main Lvl Entrance Vestibule 100 HFP-11 Functional Pass
2 01/31/22 001-003 Main Lvl Corridor 103 HFP-11 Functional Pass
3 01/31/22 001-004 Main Lvl Reception 102 HFP-11 Functional Pass
4 01/31/22 001-005 Main Lvl Waiting Area 101 HFP-11 Functional Pass
5 01/31/22 001-006 Main Lvl Lockers 117 HFP-11 Functional Pass
6 01/31/22 001-016 Main Lvl Exit Vestibule 127 HFP-11 Functional Pass
7 01/31/22 001-019 Main Lvl Electric Room 124 HFP-11 Functional Pass
8 01/31/22 001-023 Main Lvl Electric Room 124 HFP-11 Functional Pass
9 01/31/22 001-025 Main Lvl Corridor 121 HFP-11 Functional Pass
10 01/31/22 001-026 Main Lvl Tech Work Area 129 HFP-11 Functional Pass
11 01/31/22 001-028 Main Lvl Tech Work Area 129 HFP-11 Functional Pass
12 01/31/22 001-029 Main Lvl Telco/LAN Room 131 HFP-11 Functional Pass
13 01/31/22 001-030 Main Lvl Electronics Room 132 HFP-11 Functional Pass
14 01/31/22 001-031 Main Lvl Electronics 132 Underfl HFP-11 Functional Pass
15 01/31/22 001-033 Main Lvl Electronics 132 Underfl HFP-11 Functional Pass
16 01/31/22 001-035 Main Lvl Corridor 114 HFP-11 Functional Pass
17 01/31/22 001-036 Main Lvl Corridor 133 HFP-11 Functional Pass
18 01/31/22 001-039 Main Lvl Link Room 135 HFP-11 Functional Pass
19 01/31/22 001-041 Main Lvl Link 134 HFP-11 Functional Pass
20 01/31/22 001-044 Main Lvl Link Vestibule 136 HFP-11 Functional Pass
21 01/31/22 001-101 Level 1 Elevator Lobby HFP-11 Functional Pass
22 01/31/22 001-111 Level 2 Elevator Lobby HFP-11 Functional Pass
23 01/31/22 001-119 Level 3 Elevator Lobby HFP-11 Functional Pass
24 01/31/22 001-126 Level 4 Elevator Lobby HFP-11 Functional Pass
25 01/31/22 001-133 Level 5 Elevator Lobby HFP-11 Functional Pass
26 01/31/22 001-136 Level 5 Data 503 HFP-11 Functional Pass
27 01/31/22 001-137 Level 5 Plumbing 504 HFP-11 Functional Pass
28 01/31/22 001-140 Level 6 Open Area 609 HFP-11 Functional Pass
29 01/31/22 001-141 Level 6 Elevator Closet 608 HFP-11 Functional Pass
30 01/31/22 001-146 Level 6 Central Vacuum Unit 603 HFP-11 Functional Pass
31 01/31/22 001-147 Level 6 Corridor by Restrooms HFP-11 Functional Pass
32 01/31/22 001-149 Level 6 Stair Vestibule HFP-11 Functional Pass
33 01/31/22 001-150 Level 6 Mechanical Room 611 HFP-11 Functional Pass
34 01/31/22 001-156 Level 6 Mechanical Room 611 HFP-11 Functional Pass
35 01/31/22 001-157 Level 6 Electronics Room 610 HFP-11 Functional Pass
36 01/31/22 001-159 Level 6 Elevator Lobby HFP-11 Functional Pass
37 01/31/22 001-163 Level 7 Stair 701 HFP-11 Functional Pass
38 01/31/22 001-166 Level 7 Elevator Shaft Access HFP-11 Functional Pass
39 01/31/22 001-168 Level 7 Console Access Ring HFP-11 Functional Pass
40 01/31/22 001-171 Level 7 Stair Vestibule HFP-11 Functional Pass
41 01/31/22 001-172 Level 7 Console Access Ring HFP-11 Functional Pass
42 01/31/22 001-173 Level 7 Stair 701 HFP-11 Functional Pass
43 01/31/22 001-179 Level 8 CAB HFP-11 Functional Pass
This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 7 of 7
Waterflow Devices
Row Date Dev.# Location Model Visual/ Functional
Pass/ Fail
1 01/31/22 001-015^1 Main Level Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
2 01/31/22 001-048^1 Main Lvl Dry System Waterflow HTRI-D Functional Pass
Comment: Tested Signaling Only
3 01/31/22 001-103^1 Lvl 1 Tower Standpipe Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
4 01/31/22 001-104^1 Level 1 Tower Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
5 01/31/22 001-114^1 Level 2 Tower Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
6 01/31/22 001-121^1 Level 3 Tower Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
7 01/31/22 001-128^1 Level 4 Tower Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
8 01/31/22 001-135^1 Level 5 Tower Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
9 01/31/22 001-151^1 Level 6 Tower Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
10 01/31/22 001-169^1 Level 7 Tower Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
11 01/31/22 001-170^1 Level 8 Tower Water Flow HTRI-D Functional Pass
Comment: Tested Signaling Only
See main System Record of Inspection and Testing for additional information, certifications, and approvals.