Simplex ZNY SOW.pdf

PDF 125 KB Posted

Attached to
Fire Protection System Inspection, Testing and Maintenance Federal contract opportunity
Solicitation number
697DCK-24-R-00343
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This document is a Statement of Work (SOW) for quarterly fire alarm system testing at the Federal Aviation Administration (FAA) New York Air Route Traffic Control Center (NY ARTCC) in Ronkonkoma, NY. The SOW outlines the scope of work, which includes testing components and verifying operation of the Simplex 4100U fire alarm system, including testing a percentage of various system devices such as duct detectors, heat detectors, smoke detectors, manual pull stations, elevator shunt trips, VESDA early detection devices, door closers/holders, and fire alarm audio/visual devices. The work must be performed during the week starting at 10:00 p.m. and coordinated with the Contracting Officer's Representative (COR), who must be present during performance. The contractor must furnish all necessary equipment and supplies.

This SOW is related to a federal contract opportunity, Solicitation Number 697DCK-24-R-00343, for Fire Protection System Inspection, Testing and Maintenance at the LaGuardia Air Traffic Control Tower Center and NY ARTCC. This is a firm-fixed-price procurement set aside for small businesses, with a base year of 10/01/2024 to 09/30/2025 and four one-year option periods. A site visit is scheduled for July 1-2, 2024, and questions are due by July 5, 2024. Proposals are due by the date and time specified in the solicitation document.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Protection System Inspection, Testing and Maintenance, newest first.
File Type Posted
Q4 ATOP-DSR CONTROL ROOM.pdf PDF
Q1 PSB BOILERS CHILLERS EG ROOMS.pdf PDF
Q2 ATOP-DSR CONTROL ROOM.pdf PDF
Q3 DYSIM ERAM CODEX ADMIN.pdf PDF
Q1 2024 Ronkonkoma Fire Alarm Final Report.pdf PDF
697DCK-24-R-00343 AMEND 0003.pdf PDF
697DCK-24-R-00343 AMEND 0002.pdf PDF
697DCK-24-R-00343 AMEND 00001.pdf PDF
2015-4157 Rev 24.pdf PDF
2015-4187 rev 28 April 2024.pdf PDF
SIR 697DCK-24-R-00343.pdf PDF
Customery Survey Form.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FEDERAL AVIATION ADMINISTRATION

New York Air Route Traffic Control Center (NY ARTCC)

4205 Johnson Ave.

Ronkonkoma, NY 11779

July 2024

STATEMENT OF WORK

QUARTERLY FIRE ALARM SYSTEM TESTING

SCOPE OF WORK:

Contractor shall test components and verify operation of the Simplex 4100U fire alarm system at the FAA New York ARTCC on a quarterly basis.

Work shall include testing 25 percent of:

▪ 54 Duct Detector

▪ 35 Heat Detector: Restorable

▪ 700 Smoke Detectors

▪ 64 Fire Alarm Boxes (Manual Pull Station)

▪ 2 Elevator Shunt Trip Test/Per Bank

▪ 6 Vesda Early Detection Device-Visual inspection only to verify system is in normal configuration and that no alarms are present

▪ 6 Door Closer/Holder

▪ 145 Fire Alarm Audio Visual Device (A/V)

1,000 devices consisting of: smoke detectors, heat detectors, manual pull stations, horns and strobe lights.

SPECIAL REQUIREMENTS:

All work is to be accomplished during the week starting at 10:00 p.m. The work schedule shall be coordinated with the COR. An FAA employee must be present at all times during the performance of this contract.

Contractor shall furnish all equipment and supplies necessary to perform the work in accordance with this statement of work and whatever governmental and other codes and standards that may apply. Contractor warrants that all equipment will be of such type as to cause no hazard or danger reasonably foreseeable.