Q2 ATOP-DSR CONTROL ROOM.pdf

PDF 224 KB Posted

Attached to
Fire Protection System Inspection, Testing and Maintenance Federal contract opportunity
Solicitation number
697DCK-24-R-00343
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This document is a Fire Alarm Inspection Report for a federal facility located in Ronkonkoma, NY. The report provides detailed test results for various fire alarm devices, including smoke detectors, pull stations, and others, as well as a summary of inspection deficiencies.

The related federal contract opportunity is for Fire Protection System Inspection, Testing and Maintenance services at the LaGuardia Air Traffic Control Tower Center and New York Air Route Control Center in Ronkonkoma, NY. This is a firm-fixed-price procurement set aside for small businesses, with a base year and four one-year option periods. The contract requires the contractor to provide all materials, supplies, and tools necessary to accomplish the tasks outlined in the Statement of Work. A site visit is scheduled for July 1-2, 2024, and all questions must be submitted by July 5, 2024. Proposals are due by the date and time specified in the solicitation document.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Protection System Inspection, Testing and Maintenance, newest first.
File Type Posted
Q1 PSB BOILERS CHILLERS EG ROOMS.pdf PDF
Simplex ZNY SOW.pdf PDF
Q3 DYSIM ERAM CODEX ADMIN.pdf PDF
Q1 2024 Ronkonkoma Fire Alarm Final Report.pdf PDF
Q4 ATOP-DSR CONTROL ROOM.pdf PDF
697DCK-24-R-00343 AMEND 0003.pdf PDF
697DCK-24-R-00343 AMEND 0002.pdf PDF
697DCK-24-R-00343 AMEND 00001.pdf PDF
2015-4157 Rev 24.pdf PDF
2015-4187 rev 28 April 2024.pdf PDF
SIR 697DCK-24-R-00343.pdf PDF
Customery Survey Form.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Firecraft of New York, Inc.

Fire Alarm Inspection Report

SITE: MCARTHUR 4205 JOHNSON AVE. RONKONKOMA NY 11779

Sales & Service: Fire, Smoke & Voice Evacuation Systems

TABLE OF CONTENTS

Monitoring/Jurisdiction Agencies 1

Summary Test Result – Alarm Initiating and Supervisory Devices 2

Detailed Test Results 3

Inspection Deficiencies Summary 7

Fire Alarm Inspection Report PAGE 1

Monitoring Agency: Federal Aviation Administration

Authority Having Jurisdiction” Bohemia Fire Department

Inspection Services: Firecraft of New York Inc.

Service Technician: Jake Enderle

NYC Fire Dept. Certificate: #88230529

Fire Alarm Inspection Report PAGE 2

SUMMARY TEST RESULTS –

ALARM INITIATING AND SUPERVISORY DEVICES

Device

Total

Number

Tested

Number

Failed

Number

Not Tested

Duct Detector 0 0 0 0

Heat Detector 0 0

Smoke Detector 111 111 0 0

Pull Station 2 2 0 0

Water Flow Detectors * 0 0 0 0

Tamper Switch* 0 0 0 0

*HEAT DETECTORS – VISUAL INSPECTION

Fire Alarm Inspection Report PAGE 3

DETAILED TEST RESULTS

NODE LOOP DEVICE DEVICE TYPE LOCATION TESTED NOTES

1 5 64 SMOKE ATOPS 1 FL ✓

1 5 62 SMOKE ATOPS 1 FL ✓

1 5 44 SMOKE 1 FL CTRL OPS ✓

1 5 15 SMOKE ATOPS 1 FL ✓

1 5 45 SMOKE 1 FL CTRL OPS ✓

1 5 43 SMOKE 1 FL CTRL OPS ✓

1 5 6 SMOKE ATOPS 1 FL ✓

1 5 6 SMOKE ATOPS 1 FL ✓

1 5 86 SMOKE ATOPS 1 FL ✓

1 5 70 SMOKE ATOPS 1 FL ✓

1 5 69 SMOKE ATOPS 1 FL ✓

1 5 65 SMOKE ATOPS 1 FL ✓

1 5 88 SMOKE ATOPS 1 FL ✓

1 5 127 SMOKE ATOPS 1 FL ✓

1 5 87 SMOKE ATOPS 1 FL ✓

1 5 114 SMOKE ATOPS 1 FL ✓

1 5 115 SMOKE ATOPS 1 FL ✓

1 5 123 PULL STATION 1 FL CORR TO ST 3 ✓

1 5 41 SMOKE 1 FL CTRL OPS ✓

1 5 124 SMOKE ATOPS 1 FL ✓

1 5 42 SMOKE ATOPS CTRL OPS ✓

1 5 113 SMOKE ATOPS 1 FL ✓

1 5 110 SMOKE DSR 1 FL ✓

2 1 95 SMOKE CTRL OPEN SPACE ✓

2 1 102 SMOKE C 1 OPEN SPACE ✓

2 1 103 SMOKE C 1 OPEN SPACE ✓

2 1 100 SMOKE C 1 OPEN SPACE ✓

2 1 99 SMOKE C 1 OPEN SPACE ✓

2 1 90 SMOKE C 1 OPEN SPACE ✓

1 5 118 SMOKE ATOPS 1 FL ✓

1 5 116 SMOKE ATOPS 1 FL ✓

1 5 112 SMOKE ATOPS 1 FL ✓

1 5 119 SMOKE ATOPS 1 FL ✓

1 5 121 SMOKE ATOPS 1 FL ✓

1 5 120 SMOKE ATOPS 1 FL ✓

2 5 111 SMOKE C 1 OPEN SPACE ✓

2 5 107 SMOKE C 1 OPEN SPACE ✓

1 5 51 SMOKE ATOPS 1 FL ST 4 ✓

Fire Alarm Inspection Report PAGE 4

NODE LOOP DEVICE DEVICE TYPE LOCATION TESTED NOTES

1 5 54 PULL STATION ATOPS 1 FL ✓

1 5 79 SMOKE ATOPS 1 FL ✓

1 5 80 SMOKE ATOPS 1 FL ✓

1 5 81 SMOKE ATOPS 1 FL ✓

1 5 95 SMOKE ATOPS 1 FL ✓

1 5 96 SMOKE ATOPS 1 FL ✓

1 5 94 SMOKE ATOPS 1 FL ✓

1 5 93 SMOKE ATOPS 1 FL ✓

1 5 83 SMOKE ATOPS 1 FL ✓

1 5 78 SMOKE ATOPS 1 FL ✓

1 5 55 SMOKE ATOPS 1 FL ✓

1 5 49 SMOKE ATOPS 1 FL ✓

1 5 99 SMOKE 1 FL WEATHER RM ✓

1 5 91 SMOKE ATOPS 1 FL ✓

1 5 84 SMOKE ATOPS 1 FL ✓

1 5 77 SMOKE ATOPS 1 FL ✓

1 5 56 SMOKE ATOPS 1 FL ✓

1 5 57 SMOKE ATOPS 1 FL ✓

1 5 47 SMOKE 1 FL CTRL OPS ✓

1 5 48 SMOKE 1 FL CTRL OPS ✓

1 5 46 SMOKE 1 FL CTRL OPS ✓

1 5 75 SMOKE ATOPS 1 FL ✓

1 5 76 SMOKE ATOPS 1 FL ✓

1 5 58 SMOKE ATOPS 1 FL ✓

1 5 60 SMOKE ATOPS 1 FL ✓

1 5 61 SMOKE ATOPS 1 FL ✓

1 5 59 SMOKE ATOPS 1 FL ✓

1 5 74 SMOKE ATOPS 1 FL ✓

1 5 85 SMOKE ATOPS 1 FL ✓

1 5 90 SMOKE ATOPS 1 FL ✓

1 5 126 SMOKE ATOPS 1 FL ✓

1 5 73 SMOKE ATOPS 1 FL ✓

1 5 100 SMOKE ATOPS MAINTENACNE ✓

1 5 10 SMOKE ATOPS MAINTENACNE ✓

1 5 102 SMOKE ATOPS MAINTENACNE ✓

1 5 103 SMOKE ATOPS MAINTENACNE ✓

2 1 110 SMOKE C1 OPEN SPACE ✓

2 1 108 SMOKE C1 OPEN SPACE ✓

2 1 85 SMOKE C1 OPEN SPACE ✓

2 1 82 SMOKE C1 OPEN SPACE

Fire Alarm Inspection Report PAGE 5

NODE LOOP DEVICE DEVICE TYPE LOCATION ✓ NOTES

2 1 83 SMOKE C1 OPEN SPACE ✓

2 1 86 SMOKE C1 OPEN SPACE ✓

2 1 87 SMOKE C1 OPEN SPACE ✓

2 1 89 SMOKE C1 OPEN SPACE ✓

2 3 91 SMOKE C1 OPEN SPACE ✓

2 3 17 SMOKE C1 ISS CNTRL ✓

2 3 3 SMOKE C1 ISS CNTRL ✓

2 3 5 SMOKE C1 ISS CNTRL ✓

2 3 17 SMOKE C1 ISS CNTRL ✓

2 3 11 SMOKE C1 ISS CNTRL ✓

2 3 12 SMOKE C1 ISS CNTRL ✓

2 3 15 SMOKE C1 ISS CNTRL 4

2 3 14 SMOKE C1 ISS CNTRL ✓

2 3 87 SMOKE C1 ISS CNTRL ✓

2 3 9 SMOKE C1 ISS CNTRL ✓

2 3 91 SMOKE C1 ISS CNTRL ✓

2 3 8 SMOKE C1 ISS CNTRL ✓

2 3 7 SMOKE C1 ISS CNTRL ✓

2 3 6 SMOKE C1 ISS CNTRL ✓

2 3 30 SMOKE C1 ISS CNTRL ✓

2 3 29 SMOKE C1 ISS CNTRL ✓

2 3 26 SMOKE C1 ISS CNTRL ✓

2 3 27 SMOKE C1 ISS CNTRL ✓

2 3 23 SMOKE C1 DRPS RM ✓

2 3 22 SMOKE C1 DRP SRM ✓

2 3 18 SMOKE C1 LCN RM ✓

2 3 20 SMOKE C1 LCN RM ✓

2 3 21 SMOKE C1 LCN RM ✓

2 3 93 SMOKE C1 LCN RM ✓

2 3 39 SMOKE C1 RM BY STAIR ✓

2 3 38 SMOKE C1 ISS CNTRL RM ✓

2 3 36 SMOKE C1 ISS CNTRL RM ✓

2 3 35 SMOKE C1 ISS CNTRL RM

2 3 34 SMOKE C1 ISS CNTRL RM

Fire Alarm Inspection Report PAGE 6

58INSPECTION DEFICIENCIES SUMMARY

LOCATIONS TESTED:

• ATOPS

• CTRL OPS

• DSR

• CTTL

• ATOPS MAINTENANCE

• C1 OPEN SPACE

• ISS CNTRL

• DRPS RM

*NOTE –

Fire Alarm Inspection Report PAGE 7

4/20/23 Customer (signature On-File) Date

Rogelio Smith Date

Salvatore Geraci Date

Ronkonkoma Q2 2023-Cover Letter
RONKONKOMA Fire Alarm Inspection Report April 2023
EnderleJake Cert X-08.31.2024

File details come from the government source that posted it. Updated .