Q3 DYSIM ERAM CODEX ADMIN.pdf

PDF 244 KB Posted

Attached to
Fire Protection System Inspection, Testing and Maintenance Federal contract opportunity
Solicitation number
697DCK-24-R-00343
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This document is a Fire Alarm Inspection Report for the McArthur facility located in Ronkonkoma, NY. The report details the results of a fire alarm system inspection, including a summary of the alarm initiating and supervisory devices tested, their locations, and any deficiencies found.

The related federal contract opportunity is for Fire Protection System Inspection, Testing and Maintenance services at the LaGuardia Air Traffic Control Tower Center and New York Air Route Control Center in Ronkonkoma, NY. This is a firm-fixed price procurement set aside for small businesses, with a base year and four one-year option periods. The government is encouraging potential offerors to attend a site visit on July 1-2, 2024. All questions must be submitted by July 5, 2024, and proposals are due by the date and time specified in the solicitation document.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Protection System Inspection, Testing and Maintenance, newest first.
File Type Posted
Q1 PSB BOILERS CHILLERS EG ROOMS.pdf PDF
Q2 ATOP-DSR CONTROL ROOM.pdf PDF
Q4 ATOP-DSR CONTROL ROOM.pdf PDF
Simplex ZNY SOW.pdf PDF
Q1 2024 Ronkonkoma Fire Alarm Final Report.pdf PDF
697DCK-24-R-00343 AMEND 0003.pdf PDF
697DCK-24-R-00343 AMEND 0002.pdf PDF
697DCK-24-R-00343 AMEND 00001.pdf PDF
2015-4157 Rev 24.pdf PDF
2015-4187 rev 28 April 2024.pdf PDF
SIR 697DCK-24-R-00343.pdf PDF
Customery Survey Form.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Firecraft of New York, Inc.

Fire Alarm Inspection Report

SITE: MCARTHUR 4205 JOHNSON AVE. RONKONKOMA NY 11779

Sales & Service: Fire, Smoke & Voice Evacuation Systems

TABLE OF CONTENTS

Monitoring/Jurisdiction Agencies 1

Summary Test Result – Alarm Initiating and Supervisory Devices 2

Detailed Test Results 3

Inspection Deficiencies Summary 7

Fire Alarm Inspection Report PAGE 1

Monitoring Agency: Federal Aviation Administration

Authority Having Jurisdiction” Bohemia Fire Department

Inspection Services: Firecraft of New York Inc.

Service Technician: Jake Enderle

NYC Fire Dept. Certificate: #88230529

Fire Alarm Inspection Report PAGE 2

SUMMARY TEST RESULTS –

ALARM INITIATING AND SUPERVISORY DEVICES

Device

Total

Number

Tested

Number

Failed

Number

Not Tested

Duct Detector 0 0 0 0

Heat Detector 0 0

Smoke Detector 132 132 0 0

Pull Station 2 2 0 0

Water Flow Detectors * 0 0 0 0

Tamper Switch* 0 0 0 0

*HEAT DETECTORS – VISUAL INSPECTION

Fire Alarm Inspection Report PAGE 3

DETAILED TEST RESULTS

NODE LOOP DEVICE DEVICE TYPE LOCATION TESTED NOTES

1 M2 44 SMOKE DYSIM W SIDE ✓

1 M2 38 SMOKE DYSIM W SIDE ✓

1 M2 32 SMOKE DYSIM CENTER ✓

1 M2 26 SMOKE DYSIM CENTER ✓

1 M2 20 SMOKE DYSIM EAST ✓

1 M2 14 SMOKE DYSIM EAST ✓

1 M2 62 SMOKE DYSIM EAST ✓

1 M2 8 SMOKE DYSIM STORAGE ✓

1 M2 6 SMOKE DYSIM STORAGE ✓

1 M2 4 SMOKE DYSIM NE NED OF CORR ✓

1 M2 10 SMOKE DYSIM EAST ✓

1 M2 16 SMOKE DYSIM EAST ✓

1 M2 22 SMOKE DYSIM CENTER ✓

1 M2 28 SMOKE DYSIM CENTER ✓

1 M2 34 SMOKE DYSIM WEST ✓

1 M2 40 SMOKE DYSIM WEST ✓

1 M2 42 SMOKE DYSIM WEST ✓

1 M2 36 PULL STATION DYSIM WEST ✓

1 M2 30 SMOKE DYSIM CENTER ✓

1 M2 24 SMOKE DYSIM CENTER ✓

1 M2 18 SMOKE DYSIM EAST ✓

2 M2 12 SMOKE DYSIM EAST ✓

2 M1 31 SMOKE NEAR RAMP ✓

2 M1 33 SMOKE CODEX RM ✓

2 M1 36 SMOKE CODEX RM ✓

2 M1 38 SMOKE CODEX RM ✓

2 M1 40 SMOKE CODEX RM ✓

2 M1 45 SMOKE CODEX RM ✓

2 M1 49 SMOKE C-B CODEX RM ✓

2 M1 47 SMOKE C-B CODEX RM ✓

2 M1 44 SMOKE C-B CODEX RM ✓

2 M1 37 SMOKE C-B CODEX RM ✓

2 M1 67 SMOKE C-B CODEX RM RAMP ✓

5 IDI 19 SMOKE CB RM B111 ✓

5 IDI 13 SMOKE CB RM B111 ✓

5 ISI 12 SMOKE CB RM B111 ✓

5 IDI 8 SMOKE COMP RM B68 ✓

5 IDI 7 SMOKE COMP RM B101 ✓

Fire Alarm Inspection Report PAGE 4

NODE LOOP DEVICE DEVICE TYPE LOCATION TESTED NOTES

5 IDI 6 SMOKE COMP RM B61 ✓

5 IDI 5 SMOKE COMP RM B61 ✓

5 IDI 4 SMOKE COMP RM B61 ✓

5 IDI 10 SMOKE COMP RM B115 ✓

5 IDI 9 SMOKE COMP RM B115 ✓

5 IDI 1 SMOKE COMP RM B101 ✓

5 IDI 24 SMOKE COMP RM B106 ✓

5 IDI 23 SMOKE COMP RM B106 ✓

5 IDI 2 SMOKE COMP RM B 101 ✓

5 IDI 3 SMOKE COMP RM B101 ✓

1 M4 11 PULL STATIONS ADMIN WING BSMT CONTRACTOR RM ✓

1 M4 93 SMOKE ADMIN WING SUP WINS OFFICE B22 ✓

1 M4 94 SMOKE ADMIN WING SUP WINS OFFICE B22 ✓

1 M4 92 SMOKE ADMIN WING SUP WINS OFFICE B22 ✓

1 M4 96 SMOKE ADMIN WING SUPP WIN GYM ✓

1 M4 95 SMOKE ADMIN WING SUPP WIN GYM ✓

1 M4 93 SMOKE ADMIN WING SUPP WIN OFFICAL ✓

1 M3 115 SMOKE SUPPORT BASEMENT STAIR 5 ✓

2 M2 21 SMOKE OB COMPLEX B122 ✓

2 M2 19 SMOKE OB COMPLEX B122 ✓

2 M2 23 SMOKE MPS/MCCP RM B123 ✓

2 M2 24 SMOKE MPS/MCCP RM B123 ✓

2 M2 86 SMOKE MPS COMP COMPEX B121 ✓

2 M2 83 SMOKE MPS COMP COMPEX B121 ✓

2 M2 81 SMOKE MPS COMP COMPEX B121 ✓

2 M2 78 SMOKE MPS COMP COMPEX B121 ✓

2 M2 76 SMOKE MPS COMP COMPEX B121 ✓

2 M2 73 SMOKE MPS COMP COMPEX B121 ✓ CRACKED

2 M2 74 SMOKE MPS COMP COMPEX B121 ✓

2 M2 79 SMOKE MPS COMP COMPEX B121 ✓

2 M2 82 SMOKE MPS COMP COMPEX B121 ✓

2 M2 84 SMOKE MPS COMP COMPEX B121 ✓

2 M2 27 SMOKE OB MPS/MCCP B123 ✓

2 M2 26 SMOKE OB MSP/MCCP B123 ✓

2 M2 18 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 17 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 15 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 18 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 28 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 30 SMOKE MPS COMP COMPLEX B122 ✓

Fire Alarm Inspection Report PAGE 5

NODE LOOP DEVICE DEVICE TYPE LOCATION ✓ NOTES

2 M2 65 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 67 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 68 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 70 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 72 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 60 SMOKE MPS COMP COMPLEX B122 ✓

2 M2 61 SMOKE OB COMP COMPLEX B121 ✓

2 M2 62 SMOKE OB COMP COMPLEX B121 ✓

2 M2 63 SMOKE OB COMP COMPLEX B121 ✓

2 M2 64 SMOKE OB COMP COMPLEX B121 ✓

2 M2 32 SMOKE OB COMP COMPLEX B122 ✓

2 M2 31 SMOKE OB COMP COMPLEX B122 ✓

2 M2 13 SMOKE OB COMP COMPLEX B122 ✓

2 M2 12 SMOKE OB COMP COMPLEX B122 ✓

2 M2 9 SMOKE OB COMP COMPLEX B122 ✓

2 M2 10 SMOKE OB COMP COMPLEX B122 ✓

2 M2 8 SMOKE OB COMP COMPLEX B122 ✓

2 M2 6 SMOKE OB COMP COMPLEX B122 ✓

2 M2 33 SMOKE OB COMP COMPLEX B122 ✓

2 M2 35 SMOKE OB COMP COMPLEX B122 ✓

2 M2 41 SMOKE OB COMP COMPLEX B122 ✓

2 M2 45 SMOKE OB COMP COMPLEX B122 ✓

2 M2 57 SMOKE OB COMP COMPLEX B122 ✓

2 M2 46 SMOKE OB COMP COMPLEX B122 ✓

2 M2 56 SMOKE OB COMP COMPLEX B122 ✓

2 M2 55 SMOKE OB COMP COMPLEX B121 ✓

2 M2 54 SMOKE OB COMP COMPLEX B121 ✓

2 M2 52 SMOKE OB COMP COMPLEX B121 ✓

2 M2 51 SMOKE OB COMP COMPLEX B121 ✓

2 M2 49 SMOKE OB COMP COMPLEX EQUIP RM 129 ✓

2 M2 47 SMOKE COMP COMPLEX B122 ✓

2 M2 44 SMOKE COMP COMPLEX B122 ✓

2 M2 39 SMOKE COMP COMPLEX B122 ✓

2 M2 38 SMOKE COMP COMPLEX B122 ✓

2 M2 36 SMOKE OB COMP COMPLEX B122 ✓

1 M1 59 SMOKE SUPPORT BASEMENT ELEVATOR 1 LOBBY ✓

1 M1 71 SMOKE SUPPORT BASEMENT ELEVATOR 2LOBBY ✓

1 M5 9 PULL STATION SUPPORT BASEMENT 1ST FL STAIR 4 ✓

1 M1

SMOKE SUPPORT BASEMENT 1ST FL ELEVATOR 2

LOBBY

1 M5 59 SMOKE 1ST FL ATOP MAINT ✓

Fire Alarm Inspection Report PAGE 6

NODE LOOP DEVICE DEVICE TYPE LOCATION ✓ NOTES

1 M5 102 SMOKE 1ST FL ATOP MAINT ✓

1 M5 101 SMOKE 1ST FL ATOP MAINT ✓

1 M5 100 SMOKE 1ST FL ATOP MAINT ✓

1 M5 104 SMOKE 1ST FL ATOP LOCKER ROOM ✓

1 M5 105 SMOKE 1ST FL ATOP LOCKER ROOM ✓

1 M5 106 SMOKE 1ST FL ATOP LOCKER ROOM ✓

1 M5 108 SMOKE 1ST FL ATOP BY STAIR 7 ✓

1 M5 109 SMOKE 1ST FL ATOP BY STAIR 7 ✓

2 M1 93 SMOKE ROOM BY STAIR ✓

2 M1 106 SMOKE ATOPLOCKER ROOM ✓

2 M3 21 SMOKE C1 LCN ROOM ✓

2 M3 18 SMOKE C1 LCN ROOM ✓

2 M3 20 SMOKE C1 LCN ROOM ✓

2 M3 22 SMOKE DRPS ROOM ✓

2 M3 44 SMOKE MAINTENANCE ROOM ✓

2 M3 45 SMOKE MAINTENANCE ROOM ✓

2 M3 25 SMOKE D & R ROOM ✓

Fire Alarm Inspection Report PAGE 7

58INSPECTION DEFICIENCIES SUMMARY

LOCATIONS TESTED:

• DYSIM BASEMENT

• CODEX BASEMENT

• BASEMENT COMPUTER ROOM

• ADMIN SUPPORT WING

• COMPLEX ROOM

• 1ST FLOOR ATOP MAINTENANCE AREA

*NOTE –

Fire Alarm Inspection Report PAGE 8

8/8/23 Customer (signature On-File) Date

Rogelio Smith Date

Salvatore Geraci Date

1 Ronkonkoma Q3 2023-Cover Letter
2 RONKONKOMA Fire Alarm Inspection Report Q3 2023
3 EnderleJake Cert X-08.31.2024