Q4 ATOP-DSR CONTROL ROOM.pdf
PDF 246 KB Posted
- Attached to
- Fire Protection System Inspection, Testing and Maintenance Federal contract opportunity
- Solicitation number
- 697DCK-24-R-00343
About this file
This document is a Fire Alarm Inspection Report for the McArthur facility located in Ronkonkoma, NY. The report details the results of testing 145 smoke detectors and 3 pull stations, all of which failed the inspection. The report lists the specific device locations and notes. It also includes a summary of the inspection deficiencies.
The related federal contract opportunity is a Solicitation for Fire Protection System Inspection, Testing and Maintenance services at the LaGuardia Air Traffic Control Tower Center and the New York Air Route Control Center in Ronkonkoma, NY. This is a firm-fixed price procurement set aside for small businesses, with a base year and four one-year option periods. The solicitation requires offerors to inspect the site and submit proposals by the specified due date. Questions must be submitted by the provided deadline, with answers posted via a solicitation amendment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Q1 PSB BOILERS CHILLERS EG ROOMS.pdf | ||
| Q2 ATOP-DSR CONTROL ROOM.pdf | ||
| 697DCK-24-R-00343 AMEND 0003.pdf | ||
| Simplex ZNY SOW.pdf | ||
| Q3 DYSIM ERAM CODEX ADMIN.pdf | ||
| Q1 2024 Ronkonkoma Fire Alarm Final Report.pdf | ||
| 697DCK-24-R-00343 AMEND 0002.pdf | ||
| 697DCK-24-R-00343 AMEND 00001.pdf | ||
| 2015-4157 Rev 24.pdf | ||
| SIR 697DCK-24-R-00343.pdf | ||
| Customery Survey Form.docx | DOCX document | |
| 2015-4187 rev 28 April 2024.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Firecraft of New York, Inc.
Fire Alarm Inspection Report
SITE: MCARTHUR 4205 JOHNSON AVE. RONKONKOMA NY 11779
Sales & Service: Fire, Smoke & Voice Evacuation Systems
TABLE OF CONTENTS
Monitoring/Jurisdiction Agencies 1
Summary Test Result – Alarm Initiating and Supervisory Devices 2
Detailed Test Results 3
Inspection Deficiencies Summary 7
Fire Alarm Inspection Report PAGE 1
Monitoring Agency: Federal Aviation Administration
Authority Having Jurisdiction” Bohemia Fire Department
Inspection Services: Firecraft of New York Inc.
Service Technician: Jake Enderle
NYC Fire Dept. Certificate: #88230529
Fire Alarm Inspection Report PAGE 2
SUMMARY TEST RESULTS –
ALARM INITIATING AND SUPERVISORY DEVICES
Device
Total
Number
Tested
Number
Failed
Number
Not Tested
Duct Detector 0 0 0 0
Heat Detector 0 0
Smoke Detector 145 145 0 0
Pull Station 3 3 0 0
Water Flow Detectors * 0 0 0 0
Tamper Switch* 0 0 0 0
*HEAT DETECTORS – VISUAL INSPECTION
Fire Alarm Inspection Report PAGE 3
DETAILED TEST RESULTS
NODE LOOP DEVICE DEVICE TYPE LOCATION TESTED NOTES
1 5 51 SMOKE ATOPS 1ST FL ST 4 ✓
1 5 50 PULL STATION ATOPS 1ST FL ✓
1 5 54 SMOKE ATOPS 1ST FL ✓
1 5 79 SMOKE ATOPS 1ST FL ✓
1 5 80 SMOKE ATOPS 1ST FL ✓
1 5 81 SMOKE ATOPS 1ST FL ✓
1 5 95 SMOKE ATOPS 1ST FL ✓
1 5 96 SMOKE ATOPS 1ST FL ✓
1 5 94 SMOKE ATOPS 1ST FL ✓
1 5 93 SMOKE ATOPS 1ST FL ✓
1 5 83 SMOKE ATOPS 1ST FL ✓
1 5 78 SMOKE ATOPS 1ST FL ✓
1 5 55 SMOKE ATOPS 1ST FL ✓
1 5 49 SMOKE ATOPS 1ST FL ✓
1 5 99 SMOKE 1ST FL WEATHER RM ✓
1 5 91 SMOKE ATOPS 1ST FL ✓
1 5 84 SMOKE ATOPS 1ST FL ✓
1 5 77 SMOKE ATOPS 1ST FL ✓
1 5 56 SMOKE ATOPS 1ST FL ✓
1 5 57 SMOKE ATOPS 1ST FL ✓
1 5 47 SMOKE 1ST FL CONTROL OPS ✓
1 5 48 SMOKE 1ST FL CONTROL OPS ✓
1 5 46 SMOKE 1ST FL CONTROL OPS ✓
1 5 75 SMOKE ATOP 1ST FL ✓
1 5 76 SMOKE ATOPS 1ST FL ✓
1 5 58 SMOKE ATOPS 1ST FL ✓
1 5 60 SMOKE ATOPS 1ST FL ✓
1 5 61 SMOKE ATOPS 1ST FL ✓
1 5 59 SMOKE ATOPS 1ST FL ✓
1 5 74 SMOKE ATOPS 1ST FL ✓
1 5 85 SMOKE ATOPS 1ST FL ✓
1 5 90 SMOKE ATOPS 1ST FL ✓
1 5 126 SMOKE ATOPS 1ST FL ✓
1 5 73 SMOKE ATOPS 1ST FL ✓
1 5 100 SMOKE ATOPS MAINTENANCE ✓
1 5 101 SMOKE ATOPS MAINTENANCE ✓
1 5 102 SMOKE ATOPS MAINTENANCE ✓
1 5 103 SMOKE ATOPS MAINTENANCE ✓
Fire Alarm Inspection Report PAGE 4
NODE LOOP DEVICE DEVICE TYPE LOCATION TESTED NOTES
1 5 64 SMOKE ATOPS 1ST FL ✓
1 5 62 SMOKE ATOPS 1ST FL ✓
1 5 44 SMOKE 1ST FL CONTROL OPS ✓
1 5 125 SMOKE ATOPS 1ST FL ✓
1 5 45 SMOKE 1ST FL CONTROL OPS ✓
1 5 43 SMOKE 1ST FL CONTROL OPS ✓
1 5 66 SMOKE ATOPS 1ST FL ✓
1 5 63 SMOKE ATOPS 1ST FL ✓
1 5 86 SMOKE ATOPS 1ST FL ✓
1 5 70 SMOKE ATOPS 1ST FL ✓
1 5 69 SMOKE ATOPS 1ST FL ✓
1 5 65 SMOKE ATOPS 1ST FL ✓
1 5 88 SMOKE ATOPS 1ST FL ✓
1 5 127 SMOKE ATOPS 1ST FL ✓
1 5 87 SMOKE ATOPS 1ST FL ✓
1 5 114 SMOKE ATOPS 1ST FL ✓
1 5 115 SMOKE ATOPS 1ST FL ✓
1 5 135 PULL STATION 1ST FL CORR TO STAIR 3 ✓
1 5 41 SMOKE 1ST FL CONTROL OPS ✓
1 5 124 SMOKE ATOPS 1ST FL ✓
1 5 42 SMOKE ATOPS CONTROL OPS ✓
1 5 113 SMOKE ATOPS 1ST FL ✓
1 5 110 SMOKE DSR 1ST FL ✓
2 1 95 SMOKE CONTROL OPEN SPACE ✓
2 1 102 SMOKE C1 OPEN SPACE ✓
2 1 103 SMOKE C1 OPEN SPACE ✓
2 1 100 SMOKE C1 OPEN SPACE ✓
2 1 99 SMOKE C1 OPEN SPACE ✓
2 1 90 SMOKE C1 OPEN SPACE ✓
1 5 118 SMOKE ATOPS 1ST FL ✓
1 5 116 SMOKE ATOPS 1ST FL ✓
1 5 112 SMOKE ATOPS 1ST FL ✓
1 5 119 SMOKE ATOPS 1ST FL ✓
1 5 121 SMOKE ATOPS 1ST FL ✓
1 5 120 SMOKE ATOPS 1ST FL ✓
2 5 111 SMOKE C1 OPEN SPACE ✓
2 5 107 SMOKE C1 OPEN SPACE ✓
2 1 110 SMOKE C1 OPEN SPACE ✓
2 1 108 SMOKE C1 OPEN SPACE ✓
2 1 85 SMOKE C1 OPEN SPACE ✓
Fire Alarm Inspection Report PAGE 5
NODE LOOP DEVICE DEVICE TYPE LOCATION ✓ NOTES
2 1 82 SMOKE C1 OPEN SPACE ✓
2 1 83 SMOKE C1 OPEN SPACE ✓
2 1 86 SMOKE C1 OPEN SPACE ✓
2 1 87 SMOKE C1 OPEN SPACE ✓
2 1 89 SMOKE C1 OPEN SPACE ✓
2 1 91 SMOKE C1 OPEN SPACE ✓
2 3 17 SMOKE C1 ISS CONTROL ✓
2 3 3 SMOKE C1 ISS CONTROL ✓
2 3 5 SMOKE C1 ISS CONTROL ✓
2 3 17 SMOKE C1 ISS CONTROL ✓
2 3 11 SMOKE C1 ISS CONTROL ✓
2 3 12 SMOKE C1 ISS CONTROL ✓
2 3 15 SMOKE C1 ISS CONTROL ✓
2 3 14 SMOKE C1 ISS CONTROL ✓
2 3 87 SMOKE C1 ISS CONTROL ✓
2 3 9 SMOKE C1 ISS CONTROL ✓
2 3 91 SMOKE C1 ISS CONTROL ✓
2 3 8 SMOKE C1 ISS CONTROL ✓
2 3 7 SMOKE C1 ISS CONTROL ✓
2 3 6 SMOKE C1 ISS CONTROL ✓
2 3 0 SMOKE C1 ISS CONTROL ✓
2 3 29 SMOKE C1 ISS CONTROL ✓
2 3 26 SMOKE C1 ISS CONTROL ✓
2 3 27 SMOKE C1 ISS CONTROL ✓
2 3 23 SMOKE C1 DRPS ROOM ✓
2 3 22 SMOKE C1 DRPS ROOM ✓
2 3 18 SMOKE C1 LCN ROOM ✓
2 3 20 SMOKE C1 LCN ROOM ✓
2 3 21 SMOKE C1 LCN ROOM ✓
2 1 9 SMOKE C1 ROOM BY STAIR ✓
2 3 39 SMOKE C1 ISS CONTROL ✓
2 3 38 SMOKE C1 ISS CONTROL ✓
2 3 36 SMOKE C1 ISS CONTROL ✓
2 3 35 SMOKE C1 ISS CONTROL ✓
2 3 34 SMOKE C1 ISS CONTROL ✓
2 3 32 SMOKE C1 ISS CONTROL ✓
2 3 56 SMOKE C1 ISS CONTROL ✓
2 3 55 SMOKE C1 ISS CONTROL ✓
2 3 48 SMOKE C1 ISS CONTROL ✓
2 3 49 SMOKE C1 ISS CONTROL ✓
Fire Alarm Inspection Report PAGE 6
NODE LOOP DEVICE DEVICE TYPE LOCATION ✓ NOTES
2 3 32 SMOKE C1 ISS CONTROL ✓
2 3 36 SMOKE C1 ISS CONTROL ✓
2 3 47 SMOKE C1 ISS CONTROL ✓
2 3 51 SMOKE C1 ISS CONTROL ✓
2 3 52 SMOKE C1 ISS CONTROL ✓
2 3 53 SMOKE C1 ISS CONTROL ✓
2 3 54 SMOKE C1 ISS CONTROL ✓
2 3 58 SMOKE C1 ISS CONTROL ✓
2 3 61 SMOKE C1 ISS CONTROL ✓
2 3 59 SMOKE C1 ISS CONTROL ✓
2 3 63 SMOKE C1 ISS CONTROL ✓
2 3 64 SMOKE C1 ISS CONTROL ✓
2 3 68 SMOKE C1 ISS CONTROL ✓
2 3 65 PULL STATION C1 ISS CONTROL ✓
2 3 69 SMOKE C1 ISS CONTROL ✓
2 3 108 SMOKE DSR NW ✓
2 3 87 SMOKE ISS CONTROL OPS ✓
2 3 86 SMOKE ISS CONTROL OPS ✓
2 3 71 SMOKE ISS CONTROL OPS ✓
2 3 72 SMOKE ISS CONTROL OPS ✓
2 3 73 SMOKE ISS CONTROL OPS ✓
2 3 75 SMOKE ISS CONTROL OPS ✓
2 3 107 SMOKE DSR NE ✓
2 3 81 SMOKE C1 CONTROL OPS ✓
2 3 76 SMOKE C1 CONTROL OPS ✓
2 3 77 SMOKE C1 CONTROL OPS ✓
2 3 80 SMOKE C1 CONTROL OPS ✓
2 3 83 SMOKE C1 CONTROL OPS ✓
2 3 85 SMOKE C1 CONTROL OPS ✓
2 3 88 SMOKE C1 CONTROL OPS ✓
Fire Alarm Inspection Report PAGE 7
58INSPECTION DEFICIENCIES SUMMARY
LOCATIONS TESTED:
• ATOPS 1ST FL
• 1ST FL WEATHER ROOM
• 1ST FL CONTROL OPS
• ATOPS MAINTENANCE
• 1ST FL CORR
• CONTROL OPEN SPACE
• C1 OPN SPACE
• C1 ISS CONTROL
• C1 DRDS ROOM
*NOTE –
Fire Alarm Inspection Report PAGE 8
10/18/23 Customer (signature On-File) Date
Rogelio Smith Date
Salvatore Geraci Date
| 1 Ronkonkoma Q4 2023-Cover Letter |
| 2 RONKONKOMA Fire Alarm Inspection Report September 2023 |
File details come from the government source that posted it. Updated .