SECTION 08 71 00 Door Hardware with Schedule QNA ARSR 2026 Sept 22.pdf
PDF 166 KB Posted
- Solicitation number
- 6973GH-27-R-00042
About this file
This is Section 08 71 00 (Door Hardware) of a specification document for a federal construction project (JCN 1703883) to refurbish and reseal a building in Morales, Texas to correct water damage and prevent water intrusion. The section specifies the supply and installation of finish hardware for all doors, including field verification of existing conditions and replacement with BHMA Grade 1 systems utilizing universal 7-pin removable and interchangeable cores.
The contractor must replace all door hardware with lever handles on single and double doors, provide new rim cylinders, mortise cylinders, SFIC cores, gasketing, door sweeps, thresholds, and panic hardware on Equipment Room and Generator Room hollow metal exterior doors. For the main Equipment Room entrance double doors with existing CDX-10 locks and Hoffman boxes, the contractor must include costs for a GSA-certified locksmith to remove and reinstall these locks in new doors. Exterior Equipment Room doors (one double door front, one single door back) must be replaced with 14-gauge steel, label "B" fire-rated doors complying with FAA 1600.69D 4-3-13 requirements. All exterior perimeter and restricted-access interior doors must have BHMA Grade 1 locking systems with universal 7-pin interchangeable cores or equivalent electronic systems. Specified manufacturers include Ives, Hager, Stanley, Best, Von Duprin, LCN, Zero, National Guard, Pemko, Trimco, Rockwood, and Glynn Johnson across categories of hinges, locks, exit devices, closers, and related hardware. The contractor must coordinate keying with RE/COR and SSCM, provide training to site staff on hardware operation and programming, and deliver an operations and maintenance manual in a labeled hardcover binder containing final schedules, maintenance instructions, catalog pages, installation guides, and warranties. All hardware must be installed by qualified finish hardware installers following DHI publications and ANSI standards, with a one-year factory warranty from substantial completion and field quality control verification by an Architectural Hardware Consultant.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-1
SECTION 08 71 00
DOOR HARDWARE
PART 1 – GENERAL
1.01 SUMMARY
A. Section includes the supply and installation of the Finish Hardware.
1. Contractor shall include field verification of all existing exterior doors condition that are to remain and hardware.
2. Replace all door hardware with lever handles on single and double doors. They must comply with BHMA Grade 1 system that accepts a universal 7-pin removable and interchangeable core.
3. Provide new rim cylinders, mortise cylinders, SFIC cores, gasketing, door sweeps, thresholds, and BHMA Grade 1 door hardware.
4. Provide the appropriate keying system and coordinate it with RE/COR and SSCM unless instructed otherwise by Project Engineer/Contracting Officer.
5. Provide panic hardware on the Equipment Room and Generator Room hollow metal exterior doors.
6. The main entrance double doors to the Equipment Room has a CDX-10 lock and a Hoffman box. The Contractor must include their bid the cost to coordinate and pay for a GSA-certified locksmith to remove it and reinstall it in the new door.
7. Only replace the exterior Equipment Rooms (this includes 1 double door in the front, and one single door in the back) and frames with 14 gauge steel, label “B” fire rated doors that comply with FAA 1600.69D 4-3-13. Perimeter Doors and Door Locks requirements herein.
a. Door Requirements, existing doors and frames remain.
(1) Perimeter doors and critical operational area doors must be equipped with latch guards or be designed to protect the latching hardware from tampering. Perimeter double doors must be equipped with full-length astragals or other mechanism (e.g., rim latch hardware, interior mullion) to prevent defeat of the locking hardware.
(2) Exterior perimeter doors and controlled area doors will be kept closed and always locked unless there are personnel providing access control. Doors of facility outbuildings that the SSE determines do not house critical equipment, do not lead to critical areas, do not protect valuable or easily pilfered government equipment and supplies, and are within a properly fenced perimeter are excluded from this requirement.
b. Locking Systems. All exterior perimeter doors and those interior doors through which the FM restricts access will be fitted with any BHMA Grade 1 system that accepts a universal 7-pin removable and interchangeable core that can be changed without
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-2
disassembling the entire core or BHMA Grade 1 equivalent electronic lock cylinders and programmable smart key systems. Electronic/programmable systems are recommended in circumstances where they are more cost-effective than traditional cores and keys. Keys and access cards must be numbered to facilitate inventory control (see paragraph 4-3-14b).
(1) For FAA-leased facilities, the lessor will furnish FAA standard BHMA Grade 1 locking hardware except for lock cores and keys, which will be provided by the FAA. The FAA will maintain its own key system.
(2) Mechanical push-button keypads or hard-coded electronic keypads may be used in addition to FAA standard locks on any FSL 1 or FSL 1A facility perimeter door; perimeter doors of facility outbuildings that do not house critical equipment or lead to critical areas and are within a fenced perimeter; any internal door not otherwise protected with PACS; and pedestrian gates at FSL 2 and 1 facilities.
B. Related Sections
1. Division 1
2. Sealants – Division 7
3. Openings – Division 8
4. Finishes – Division 9
5. Electrical – Division 26
1.02 REFERENCES
A. UL LLC
1. UL 10B - Fire Test of Door Assemblies
2. UL 10C - Positive Pressure Test of Fire Door Assemblies
3. UL 1784 - Air Leakage Tests of Door Assemblies
4. UL 305 - Panic Hardware
B. DHI - Door and Hardware Institute
1. Sequence and Format for the Hardware Schedule
2. Recommended Locations for Builders Hardware
3. Keying Systems and Nomenclature
4. Installation Guide for Doors and Hardware
C. NFPA – National Fire Protection Association
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-3
1. NFPA 70 – National Electric Code
2. NFPA 80 – 2016 Edition – Standard for Fire Doors and Other Opening Protectives
3. NFPA 101 – Life Safety Code
4. NFPA 105 – Smoke and Draft Control Door Assemblies
5. NFPA 252 – Fire Tests of Door Assemblies
D. ANSI - American National Standards Institute
1. ANSI A117.1 – 2017 Edition – Accessible and Usable Buildings and Facilities
2. ANSI/BHMA A156.1 - A156.29, and ANSI/BHMA A156.31 - Standards for Hardware and Specialties
3. ANSI/BHMA A156.28 - Recommended Practices for Keying Systems
4. ANSI/WDMA I.S. 1A - Interior Architectural Wood Flush Doors
5. ANSI/SDI A250.8 - Standard Steel Doors and Frames
1.03 SUBMITTALS
A. Comply with pertinent provisions of Division 01.
B. Finish Hardware Schedule to be in vertical format to include:
1. Heading number and/or Hardware Set number.
2. Door number, Location, Hand, Degree of Opening, Door Size and Type, Frame Size and Type, Fire Rating
3. Quantity, type, style, function, product, product number, size, fasteners, finish and manufacturer of each hardware item.
4. Title Sheet, Index, Abbreviations, Manufacturers List, Template List and Templates.
5. Mounting locations for hardware.
6. Explanation of abbreviations, symbols, and codes contained in schedule.
7. Date of the Finish Hardware Specification and Drawing / Door Schedule used in completing the Finish Hardware Schedule.
8. Name, Company and Date of Field Verification if required.
9. Door Index; include door number, heading number, and hardware group.
10. Operation Description of openings with electrified hardware.
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-4
C. Product Data: Provide product data in the form of a binder, manufacturer’s technical product fact sheets for each item of hardware. Include whatever information may be necessary to show compliance with requirements, including instructions for installation and for maintenance of operating parts and finish.
D. Wiring Diagrams: Provide Riser/Elevation and Point to Point Wiring Diagrams for all openings with electrified hardware. Include all information that is necessary for coordination with other trades.
E. Samples: Provide samples as requested by Owner or Architect. All samples will be returned to the contractor and used on doors for which they were marked.
F. Templates: Provide templates of finish hardware items to each fabricator of doors, frames and other work to be factory or shop prepared for the installation of hardware.
G. Keying Schedule: After meeting with the Owner, a keying schedule shall be submitted using keyset symbols referenced in DHI manual “Keying Systems and Nomenclature." The keying schedule shall be indexed by door number, keyset, hardware heading number, cross keying instructions and special key stamping instructions.
H. Operations and maintenance data: At the completion of the job, provide to the Owner one hard copy or one electronic copy of an Owner’s operation and maintenance manual. The manual shall consist of a labeled hardcover three ring binder with the following technical information:
1. Title page containing: Project name, address and phone numbers.
Supplier’s name, address and phone numbers.
2. Table of Contents.
3. Copy of final (file and field use/as-installed) Finish Hardware Schedule.
4. Final Keying Schedule.
5. Maintenance instruction, adjustment, and preservation of finishes for each item of hardware.
6. Catalog pages for each items of hardware.
7. Installation Instructions for each item of hardware
8. Warranties include Order #.
1.04 QUALITY ASSURANCES
A. Substitutions: Request for substitutions shall not be accepted within this project. Project Engineer, FAA and Finish Hardware Consultant have selected one (1) specified and two (2) equals listed hereinafter in the Hardware Schedule. By this selection process they have established three (3) equal products for competitive pricing, while insuring no unnecessary delays by a substitution process. If any specified product is listed as a “No Substitution” product, this product will be supplied as specified, with no alteration or request of substitution. The reason for this is to comply with the uniformity established at this project.
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-5
Parts and supplies are inventoried for these products for ease and standardization of replacement.
B. Supplier Qualifications: Supplier shall be recognized architectural finish hardware supplier, with warehousing facilities in the project vicinity and who is or employs a DHI Certified AHC, DHC, DHSC or person with a minimum of 10 years of experience as a hardware supplier. This person shall be available at reasonable times during the work for consultation about products hardware requirements, to the FAA, Project Engineer and General Contractor.
C. Installer Qualifications (Mechanical Hardware): All finish hardware shall be installed by a qualified Finish Hardware Installer. Installer shall attend a pre-installation meeting between the General Contractor, Finish Hardware Supplier/s, hardware manufacturer’s representative for locks, closers and exit devices, and all door / frame suppliers. The Finish Hardware Installer shall be responsible for the proper installation and function of all doors and hardware.
D. Installer Qualifications (Electrified Hardware): All electrified finish hardware (power source, electrified locking or control device, switching device, through wire device and monitoring device) shall be installed by a qualified Electronic Access Control Installer. Installer shall attend a pre-installation meeting between the General Contractor, Finish Hardware Supplier/s, Electrical Contractor, Fire Alarm Contractor, Security Contractor, hardware manufacturer’s representative for electrified hardware, all door / frame suppliers. The Electrified Finish Hardware Installer shall be responsible for the proper installation, termination and function of all opening with electrified hardware. Installation shall include termination of all electrified products (including the required wire to the power supply and/or junction box).
1.05 DELIVERY, STORAGE AND HANDLING
A. Marking and packaging: Mark each item or package separately, with identification related to hardware set number, door number and keyset symbol.
B. Delivery:
1. Deliver individually packaged and properly marked finish hardware at the proper time and location to avoid any delays in construction or installation.
2. At time of delivery, inventory hardware jointly with representatives of hardware supplier and hardware installer until each is satisfied that count is correct.
C. Storage: Store hardware in enclosed, dry and locked area.
1.06 WARRANTY
A. All finish hardware products shall be covered by a 1 year factory warranty from the date of substantial completion of the project.
B. Supply warranty verification to the owner for all products that provide factory warranty.
Warranty should include Factory Order # and date.
1.07 MAINTENANCE
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-6
A. Maintenance Service
1. None
B. Extra Materials:
1. All extra screws, fasteners, and all special installation tools furnished with the hardware shall be turned over to the owner at the completion of the job.
PART 2 – PRODUCTS
2.01 MATERIALS
A. Screws and Fasteners:
1. Coordinate with door supplier and manufacturer to ensure proper blocking and reinforcement is provided to support wood or machine screws when mounting panic hardware and door closers. If proper blocking and reinforcement is not included provide through bolts sized to the thickness of the door. All fasteners should be the proper type and length for the product being supplied.
2. All finish hardware shall be installed to manufacturer’s recommendations, using screws, attachments and installation tools provided with the hardware. No other screws or attachments are acceptable.
3. All other products to meet door and frame conditions.
B. Hinges:
1. Template: Provide templated units only.
2. All hinges on doors over 36” wide be heavy weight.
3. Electric Hinge: Provide minimum 8 wire.
4. Provide non-removable pins for out swinging doors that are locked or are lockable.
5. All hinges on doors with door closers shall be ball bearing.
6. All hinges shall be full mortise.
7. Size: Provide 4 ½ x 4 ½ hinges on doors up to 3’0” in width. Provide 5 x 4 ½ hinges over 3’0” to 4’0” in width. Reference manufacturers catalog for all other sizes.
8. Number of Hinges: Provide number of hinges indicated but not less than 3 hinges for door leaf for doors 90” or less in height and one additional hinge for each 30” of additional height.
9. Adjust hinge width as required for door, frame, trim and wall conditions to allow proper degree of opening.
10. Provide hinges conforming to ANSI/BHMA A156.1.
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-7
11. Provide spring hinges where specified. Provide two spring hinges and one bearing hinge per door leaf for doors 90 inches (2286 mm) or less in height. Provide one additional bearing hinge for each 30 inches (762 mm) of additional door height.
12. Supply from the following list of manufacturers:
Ives IVE 5BB Series
Hager HAG BB1191/1279 Series
Stanley STA FBB Series
C. Continuous Hinges:
1. Continuous hinges to be manufactured of 6063-T6 aluminum.
2. Continuous hinge shall be certified to ANSI 156.26, Grade 1
3. Continuous hinge should be tested an approved UL10C.
4. Electrified – Provide minimum 8 wire with removable panel.
5. Provide hinges 1 inch shorter in length than nominal height of door, unless otherwise noted.
6. Provide reinforcing for doors weighing over 450 pounds and up to 600 pounds.
7. Supply from the following list of manufacturers:
Ives IVE
Select SEL
Hager HAG
D. Cylindrical Locks
1. All locks on this project should be manufacturer by the same manufacturer.
2. All locks shall meet the new ANSI/BHMA A156.2, Series 4000, Grade 1.
3. All cylindrical locks shall be UL Listed for 3 hour fire door. Review lock for any height restriction.
4. Provide locks with standard 2-3/4 inches (70 mm) backset, unless noted otherwise, with a 1/2 inch (13 mm) latch throw. Provide proper latch throw for UL listing at pairs.
5. Provide standard ASA strikes unless extended lip strike is necessary for frame/trim or 7/8” lip strike is necessary at pair with overlapping astragal.
6. Provide dust box.
7. Lockset shall adjust to fit door thickness from 1 ¾” to 2 1/8”.
8. Supply from the following list of manufacturers: Best BES 9K3
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-8
E. Exit Devices
1. All exit device types on this project should be manufactured by the same manufacturer.
2. Exit devices are to be architectural grade touch bar type. Touchpad to extend one half of door width.
3. Mechanism case to be smooth.
4. Exit devices shall meet ANSI A156.3, Grade 1.
5. All exit devices are UL listed Panic Exit or Fire Exit Hardware.
6. All lever trim to match lock trim in design and finish.
7. Dogging: Non-rated devices are to be provided with dogging. Less dogging where shown in Hardware Sets (some exterior, electrical rooms, electrified) Cylinder dogging as shown in hardware sets.
8. Exit devices are to be supplied and installed with thru-bolts for exterior, hollow metal doors, or as required for application.
9. Provide proper power supply for exit devices as required. Coordinate with Fire Alarm, Electrical and Security Contractor.
10. Push pads shall be metal, no plastic inserts allowed.
11. Exit devices shall have a flush end cap.
12. Exit devices shall be ordered with the correct strike for application.
13. Exit devices shall be order in the proper length to meet door width.
14. Exit devices shall have dead latching.
15. Exit device shall be provided in width/height required based on door size.
16. Install exit devices with fasteners supplied by exit device manufacturer.
17. Mount mechanism case flush on face of doors or provide spacers to fill gaps behind devices. Where glass trim or molding projects off face of door, provide glass bead kits as required.
18. Provide proper concealed vertical rods for wood or hollow metal doors as required.
19. Factory or field drill weep holes for exit devices used in full exterior applications, highly corrosive areas, and where noted in the hardware sets.
20. Supply from the following list of manufacturers:
Von Duprin VON 33/99 Series
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-9
F. Flush Bolts
1. Provide automatic, constant latching, and manual flush bolts with forged bronze or stainless steel face plates, extruded brass levers, and with wrought brass guides and strikes. Provide 12 inch (305 mm) steel or brass rods at doors up to 90 inches (2286
mm) in height. For doors over 90 inches (2286 mm) in height increase top rods by 6 inches (152 mm) for each additional 6 inches (152 mm) of door height. Provide dust-proof strikes at each bottom flush bolt.
2. Supply from the following list of manufacturers:
Ives IVE
Trimco TRI
Rockwood ROC
G. Coordinators
1. Where pairs of doors are equipped with automatic flush bolts, an astragal, or other hardware that requires synchronized closing of the doors, provide bar-type coordinating device, surface applied to underside of stop at frame head.
2. Provide filler bar of correct length for unit to span entire width of opening, and appropriate brackets for parallel arm door closers and surface vertical rod exit device strikes. Factory-prep coordinators for vertical rod devices and hardware as required.
3. Supply from the following list of manufacturers:
Ives IVE
Trimco TRI
Rockwood ROC
H. Pull Plates/Pulls/Push Plate
1. Pull and Push Plates to meet ANSI 156.6 for .050” thickness.
2. Pull and Push Plate size to 4” x 16”.
3. Pull Plate to have 10” center and 1” round on pull plate with concealed fasteners.
4. Provide straight and offset pulls with fasteners as required
5. Provide concealed fasteners for all applications.
6. Prep plate for cylinder/lock as required.
7. Supply from the following list of manufacturers
Ives IVE
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-10
Trimco TRI
Rockwood ROC
I. Door Closers
1. All door closers on this project should be manufactured by the same manufacturer.
2. Provide door closers conforming to ANSI/BHMA A156.4 Grade 1 requirements by BHMA certified independent testing laboratory. ISO 9000 certify closers. Stamp units with date of manufacture code.
3. Door closers shall be furnished with standard cover. Provide full cover as shown in hardware sets.
4. Size in accordance with the manufacturers recommendations for door size and condition.
5. Door closers shall be furnished with delayed action, hold-open as listed in the Hardware Sets.
6. Door closers shall be mounted out of the line of sight wherever possible (i.e., room side of corridor doors, etc.) with parallel arm mounting on out swinging doors.
7. Provide special templates, drop plates, mounting brackets, or adapters for arms as required for details, overhead stops, and other door hardware items interfering with closer mounting.
8. Hydraulic Fluid: Fireproof, passing requirements of UL10C, and requiring no seasonal closer adjustment for temperatures ranging from 120 degrees F to -30 degrees F.
9. Spring Power: Continuously adjustable over full range of closer sizes, and providing reduced opening force as required by accessibility code and standards.
10. Supply from the following list of manufacturers LCN 4040XP Series
J. Door Protection Plates
1. Protective plates shall meet ANSI A156.6 requirements for .050 thickness.
2. Protection plates should be fabricated from stainless steel.
3. Protection plate shall be height as shown in Hardware Sets. Width shall be 10” by 2” less than door width on single door or pair with a mullion and 1” less than door width on pair of doors without a mullion.
4. Beveled 4 edges.
5. Provide kickplate on all doors with closers, unless not required for aesthetic reasons.
6. Prep protective plates for hardware as required.
7. Supply from the following list of manufacturers:
Ives IVE
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-11
Rockwood ROC
Trimco TRI
K. Door Stops and Holders:
1. Supply wall stops at all openings to protect doors or door hardware. Install so lock does not lock unintentionally. Install blocking in wall where wall stop will be mounted.
2. When wall conditions do not permit use of wall stop provide floor stops with risers as needed to adjust for floor conditions.
3. When wall conditions do not permit use of wall stop provide overhead stops. Jamb mount where required not to be visible from Corridor.
4. Exterior Ground Level Doors: Provide security floor stop.
5. Supply from the following list of manufacturers:
Glynn Johnson GLY
Rockwood ROC
Trimco TRI
L. Silencers
1. Provide silencers on all doors without seal. 3 for single doors and 2 for pairs.
2. Provide silencers as required for frame conditions. SR64 for hollow metal frames.
SR65/SR66 for wood frames.
3. At wood frames, insure height of stop is compatible with silencer.
4. Supply from the following list of manufacturer’s
Ives IVE
Rockwood ROC
Trimco TRI
M. Thresholds/Weatherstripping
1. Thresholds on doors in the accessible path shall conform to accessibility codes.
2. Threshold should be based on sill detail.
3. Smoke seal shall be teardrop design bulb seal.
4. Exterior seal/thresholds shall be silicone or brush as shown in hardware sets.
5. Drip strips shall protrude 2 ½” and be 4” wider than opening.
6. At S Label single doors provide seals on frame to comply with UL1784
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-12
7. At S Label pair of doors provide seals on frame and as meeting stile to comply with
UL1784.
8. Automatic Door Bottom shall be mortised to comply with accessibility codes.
9. Supply from the following list of manufacturer’s
Zero ZER
National Guard GP
Pemko PEM
2.03 KEYING:
A. General: Finish Hardware Supplier shall meet in person with owner to finalize keying requirements prior to the locks and exit devices being ordered and start a new Master Key System for the project. During keying meeting all hardware functions should be reviewed with the owner to finalize lock and exit device functions. During keying meeting determine all expansion required.
B. Cylinders: Provide the correct quantity of cylinders for all applications.
C. Keys: Provide nickel silver keys only. Furnish 2 change keys for each lock: 5 control keys: 5 master keys for each master system and 5 grandmaster keys for each grandmaster key system. Deliver all keys to FAA’s Representative.
D. Cores and keys shall be provided with identification stamping.
E. Provide construction keying / construction cores for this project with constructions keys.
F. Provide Bitting List to Owner.
2.04 KEY CONTROL:
A. Key Management: Key control shall be provided, by supplying a complete key storage and management system. Each key shall be fully cut, indexed, tagged and installed on cabinet hooks by the lock supplier and shipped with the locks. Key cabinet provided shall be wall-mounted type with capacity plus 50%.
PART 3 – EXECUTION
3.01 EXAMINATION:
A. Examine doors, frames and related items for conditions that would prevent the proper application of any finish hardware items. Do not proceed with installation until all defects are corrected.
B. Existing Door and Frame Compatibility: Field verify existing doors and frames receiving new hardware and existing conditions receiving new openings. Verify that new hardware is compatible with existing door and frame preparation and existing conditions.
C. Examine roughing-in for electrical power systems to verify actual locations of wiring
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-13
connections before electrified door hardware installation.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 INSTALLATION:
A. Follow Door and Hardware Institute Publication:
Recommended Location for Architectural Hardware for Standard Steel Doors and Frames.
Recommended Location for Builder’s Hardware for Custom Steel Doors and Frames Recommended Locations for Architectural Hardware for Wood Flush Door.
B. Install each hardware item in compliance with manufacturer’s instructions and recommendations, using only fasteners provided by manufacturer.
C. Follow ANSI A117.1-1998 Accessible and Usable Building and Facilities.
D. Review mounting locations with Architect where required.
E. Mount closers on room side of corridor doors, inside of exterior doors, and stair side of stairway doors from corridors. Closers should not be visible in corridors, lobbies and other public spaces where possible.
F. Locate power supplies in accessible location and indicate in as-builts where located.
G. Set threshold in full bed of sealant complying with requirements specified in Division 07.
H. Pre Installation meeting required with attendees to include FAA Project Engineer, General Contractor, Mechanical Hardware Installer, Electrified Hardware Installer, Finish Hardware Supplier and Manufacturer’s Representative for Exit Device, Locks and Closers and Door/Frame Suppliers before installation begins.
3.03 FIELD QUALITY CONTROL:
A. After installation has been completed, obtain the services of an Architectural Hardware Consultant to check for proper installation of finish hardware, according to the finish hardware schedule and keying schedule. In addition, check all hardware for adjustments and proper operation.
3.04 ADJUST AND CLEAN:
A. Adjust, clean and inspect all hardware, to ensure proper operation and function of every opening. Replace items, which cannot be adjusted to operate freely and smoothly as intended for the application made.
3.05 PROTECTION:
A. The General Contractor shall use all means at his disposal to protect all finish hardware items from abuse, corrosion and other damage until the owner accepts the project as complete.
3.06 TRAINING
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-14
A. After installation has been completed, provide training to the SSC site staff on the operation of the Finish Hardware and programming of any electrified hardware.
3.07 HARDWARE SCHEDULE
A. The hardware set(s) shown below are for use as a guideline. Provide hardware as required to meet the requirements of the openings, security, and code requirements.
B. Contractor shall field verify existing hardware and replace them with BHMA Grade 1 system that accepts a universal 7-pin removable and interchangeable core.
C. Provide any missing items as noted in the hardware schedule guideline tables below.
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-15
PROVIDE EACH SGL DOOR(S) WITH THE FOLLOWING:
HARDWARE GROUP
PROVIDE EACH SINGLE DOOR(S) MATCH EXISTING OR IF MISSING WITH THE FOLLOWING:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
3 EA HINGE 5BB1HW 4.5 X 4.5 NRP 630 IVE
1 EA PANIC HARDWARE CD-99-NL LENGTH AS REQ 626 VON
1 EA RIM CYLINDER 1E-72 626 BES
1 EA MORTISE CYLINDER 1E-74 X CAM & COLLAR AS REQ 626 BES
2 EA SFIC CORE PERMANENT CORE AS REQ 626 BES
1 EA SURFACE CLOSER 4040XP SCUSH TBSRT 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA GASKETING 328A (HEAD & JAMBS) AA ZER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD 655A A ZER
1 EA PUSH PLATE 8200 4" X 16" 630 IVE
1 EA PULL PLATE 8303 10" 4" X 16" 630 IVE
1 EA PROTECTION PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA FLOOR STOP WS406/407CCV 630 IVE
1 EA GASKETING 188S H & J BK ZER
1 EA DOOR BOTTOM 369AA AA ZER
1 EA THRESHOLD 655A A ZER
JCN 1703883, QNA ARSR, Refurbish & Reseal Building to Correct Water Damage, Prevent Water Intrusion, Morales TX
DOOR HARDWARE 08 71 00-16
PROVIDE EACH PAIR DOOR(S) MATCH EXISTING OR IF MISSING WITH THE FOLLOWING:
QTY DESCRIPTION CATALOG NUMBER FINISH MFR
6 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
1 SET CONST LATCHING BOLT FB51P 630 IVE
1 EA DUST PROOF STRIKE DP1 626 IVE
1 EA SFIC CORE PERMANENT CORE AS REQ 626 BES
1 EA OH STOP 90S X SIZE AS REQ (INACTIVE) 630 GLY
1 EA SURFACE CLOSER 4040XP SCUSH TBSRT (ACTIVE) 689 LCN
2 EA PROTECTION PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA ASTRAGAL ACTIVE LEAF Z ASTRAGAL BY
HOLLOW METAL DOOR
MANUFACTURE
1 EA FLOOR STOP WS406/407CCV 630 IVE
1 EA GASKETING 188S H & J BK ZER
2 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD 655A A ZER
END OF SECTION