670070 UNH - Kingsbury Hall - Fire Alarm Drawings.pdf

PDF 9 MB Posted

Attached to
UNH Kingsbury Hall - Fire Alarm Replacement
Solicitation number
212026960
Issued by
New Hampshire

About this file

This document comprises fire alarm system design drawings and specifications for a fire alarm replacement project at Kingsbury Hall, University of New Hampshire, prepared by SFC Engineering. The project involves replacing three networked fire alarm control panels (FACPs)—specifically replacing existing discontinued 7100 Series panels and an E3 Series panel with new S3 Series fire alarm control units on a one-for-one basis while maintaining existing building fire alarm coverage. The scope includes replacing the existing copper network with single-mode fiber optic cabling, upgrading network interface cards and audio amplifier modules, and retaining existing initiating devices and notification appliances to the maximum extent practicable. The design addresses network communication failures that prevent coordinated alarm activation across panels and ensures compliance with NFPA 72 (2019), NFPA 101 (2021), NFPA 1 (2021), IBC (2021), and NFPA 70 (2020) standards. Three new S3 FACPs will be located in the Fire Alarm Command Center (Room S142) and electrical rooms N124A and W124.

The contractor is responsible for comprehensive submittal requirements including product data, fully coordinated working plans and shop drawings containing battery calculations, sequence of operations, voltage drop calculations, floor plans, and full system riser diagrams, all developed under the responsible charge of a NICET Level III or IV technician or professional engineer. System acceptance testing must comply with NFPA 72 Chapter 14 with 100% testing of all devices, and the contractor must provide notification five business days prior to testing to allow engineer attendance. Deliverables include an owner's manual, record (as-built) drawings showing all point-to-point wiring, record of completion form, contractor certificate of compliance, and written certification of punch list completion. Add Alternates include replacement of all addressable smoke and heat detectors in kind, replacement of the existing dialer with a Keltron LS NET9000 transceiver with network configuration and UPS equipment, and unit pricing for failed initiating devices, notification appliances, and additional NAC boosters or batteries if required by calculations. The installation must conform to manufacturer specifications and include a 20% safety margin in battery calculations to account for future system expansion, with batteries capable of 24-hour standby and 15-minute alarm operation.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

XX

A ALARM BELL

WEATHER PROOF EXTERIOR HORN / STROBE

SPEAKER ONLY

GAS DETECTOR TYPE DESIGNATOR

"CO" - CARBON MONOXIDE

SPEAKER / STROBE

VISUAL ONLY

1. PRODUCT DATA: A COMPREHENSIVE SUBMITTAL OF ALL PRODUCT DATA

REQUIRED FOR A COMPLETE FIRE ALARM SYSTEM SHALL BE PROVIDED

INCLUDING CUT SHEETS WITH ALL APPLICABLE OPTIONS SELECTED FOR

DEVICES, APPLIANCES, AND PANELS.

2. WORKING PLANS / SHOP DRAWINGS: SUBMIT COMPLETE, FULLY

COORDINATED WORKING PLANS / SHOP DRAWINGS CONTAINING

INFORMATION REQUIRED BY THE APPLICABLE EDITION OF NFPA 72. THESE

DRAWING SHALL CONTAIN:

A. BATTERY CALCULATIONS TO CONFIRM THAT THE DESIGN CRITERIA IS

MET. THE CONTRACTOR IS RESPONSIBLE FOR TRACING AND

ANALYZING ALL EXISTING DEVICES, AS REQUIRED TO SUBMIT

COMPLETE AND ACCURATE BATTERY CALCULATIONS.

B. SEQUENCE OF OPERATIONS.

C. VOLTAGE DROP CALCULATIONS.

D. FLOOR PLANS INCLUDING LOCATION OF ALL DEVICES, APPLIANCES,

AND PANELS.

E. FULL SYSTEM RISER DIAGRAM.

3. SHOP DRAWINGS SHALL BE DEVELOPED UNDER THE RESPONSIBLE

CHARGE OF A NICET LEVEL III OR IV TECHNICIAN OR A PROFESSIONAL

ENGINEER AND SHALL BEAR THE NAME, LICENSE NUMBER, AND

EXPIRATION DATE OF THE INSTALLING CONTRACTOR.

4. SHOP DRAWINGS SHALL BE APPROVED BY THE ENGINEER PRIOR TO

SUBMISSION TO THE AHJ.

5. AFTER INCORPORATION OF ENGINEER COMMENTS, THE APPROVED SHOP

DRAWING SHALL BE SUBMITTED TO THE AHJ FOR APPROVAL.

6. SYSTEM ACCEPTANCE TESTING SHALL BE PERFORMED IN ACCORDANCE

WITH NFPA 72, CHAPTER 14. AT MINIMUM, TESTING SHALL INCLUDE:

A. 100% TEST OF ENTIRE SYSTEM DEVICES.

7. NOTIFY THE ENGINEER, IN WRITING, OF DATE AND TIME OF SYSTEM

ACCEPTANCE TESTING, SO HE OR SHE (OR A DESIGNEE) MAY ATTEND AT

THEIR SOLE DISCRETION. NOTIFICATION SHOULD OCCUR FIVE (5)

BUSINESS DAYS PRIOR TO TEST. IF THE ENGINEER IS NOT NOTIFIED, THE

TEST MAY NEED TO BE PERFORMED AGAIN AT NO ADDITIONAL COST TO

THE OWNER.

8. AN OWNER’S MANUAL AND MANUFACTURER’S PUBLISHED INSTRUCTIONS

COVERING ALL SYSTEM EQUIPMENT. THIS MANUAL SHALL BE PROVIDED

TO THE ENGINEER FOR REVIEW NOT LESS THAN TEN (10) WORKING DAYS

PRIOR TO ANTICIPATED FINAL ENGINEER SIGNOFF.

9. RECORD (AS-BUILT) DRAWINGS. THESE DRAWINGS SHALL BE PROVIDED

TO THE ENGINEER FOR REVIEW NOT LESS THAN FIVE (5) WORKING DAYS

PRIOR TO ANTICIPATED FINAL ENGINEER SIGNOFF. FINAL AS-BUILT

DRAWINGS MUST SHOW ALL POINT-TO-POINT WIRING.

10. A COMPLETED RECORD OF COMPLETION FORM. THIS FORM SHALL BE

PROVIDED TO THE ENGINEER FOR REVIEW NOT LESS THAN THREE (3)

WORKING DAYS PRIOR TO ANTICIPATED FINAL ENGINEER SIGNOFF.

11. FOR SOFTWARE BASED SYSTEMS, A RECORD COPY OF THE SITE-

SPECIFIC SOFTWARE SHALL BE PROVIDED TO THE OWNER’S SERVICE

PROVIDER.

12. CONTRACTOR CERTIFICATE OF COMPLIANCE. CONTRACTOR SHALL

SUBMIT A LETTER ON COMPANY LETTERHEAD AND SIGNED BY AN

AUTHORIZED INDIVIDUAL THAT STATES TO THE CONTRACTOR’S BEST

KNOWLEDGE THE INSTALLATION OF THE SYSTEM WAS INSTALLED IN

ACCORDANCE WITH APPLICABLE CODES AND STANDARDS. THIS MANUAL

SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW NOT LESS THAN

THREE (3) WORKING DAYS PRIOR TO ANTICIPATED FINAL ENGINEER

SIGNOFF.

13. WRITTEN CERTIFICATION OF COMPLETION OF ALL PUNCH LIST ITEMS.

THIS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW NOT LESS

THAN FIVE (5) WORKING DAYS PRIOR TO ANTICIPATED FINAL ENGINEER

SIGNOFF.

14. THE FOLLOWING DOCUMENTS SHALL BE STORED IN AN APPROVED FIRE

ALARM CABINET AT THE MAIN FIRE ALARM CONTROL UNIT, OR OTHER

APPROVED LOCATION:

A. COPY OF SYSTEM RECORD OF COMPLETION.

B. COPY OF SYSTEM RECORD OF INSPECTION & TESTING.

C. COPY OF RECORD DRAWINGS.

D. COPY OF FIRE PROTECTION NARRATIVE

1. REFERENCE TO DESIGN DOCUMENTATION: PLEASE CONSULT THE

PROJECT SPECIFICATIONS, FIRE ALARM MATRIX, AND FIRE PROTECTION

NARRATIVE (AS APPLICABLE) FOR ADDITIONAL INSIGHTS INTO THE DESIGN

INTENT AND PRODUCT REQUIREMENTS.

2. COMPLIANCE WITH CODES AND REGULATIONS: ALL WORK MUST ADHERE

TO FEDERAL, STATE, AND LOCAL CODES AND REGULATIONS. IN CASES

WHERE THERE IS A CONFLICT BETWEEN SPECIFIED REQUIREMENTS AND

RELEVANT CODES OR REGULATIONS, THE STRICTER REQUIREMENTS

SHALL TAKE PRECEDENCE.

3. FIRE ALARM SYSTEM IMPARIMENTS: DURING EACH FACP REPLACEMENT,

THE FIRE ALARM SYSTEM IN A PORTION OF THE BUILDING WILL BE

OFFLINE UNTIL THE NEW PANEL IS INSTALLED AND ACCEPTANCE TESTING

IS COMPLETED. A DETAILED IMPAIRMENT PLAN WILL NEED TO BE

DEVELOPED BY THE CONTRACTOR, WHICH MAY INCLUDE INSTALLING A

TEMPORARY WIRELESS FIRE ALARM SYSTEM.

1. FIRE ALARM SYSTEM PROGRAMMING AND CERTIFICATION: THE

CONTRACTOR IS RESPONSIBLE FOR PROGRAMMING, TESTING, AND

CERTIFYING THE FIRE ALARM SYSTEM UPON THE COMPLETION OF THEIR

WORK.

2. SYSTEM DOCUMENTATION AND VERIFICATION: THE SYSTEM

MANUFACTURER IS REQUIRED TO PROVIDE AN INSTALLATION WIRING

DIAGRAM FOR THE FIRE ALARM SYSTEM AND A VERIFICATION

CERTIFICATE CONFIRMING SYSTEM FUNCTIONALITY BEFORE FINAL

ACCEPTANCE.

3. CONFORMANCE WITH MANUFACTURER'S SPECIFICATIONS: ALL FIELD

WIRING AND EQUIPMENT INSTALLATION SHALL CONFORM TO THE

MANUFACTURER'S WIRING DIAGRAMS.

4. CLEARANCE FOR CONTROL UNITS: ENSURE THAT ALL FIRE ALARM

CONTROL UNITS HAVE ADEQUATE WORKING CLEARANCE IN ACCORDANCE

WITH NFPA 70. PANEL MOUNTING HEIGHT SHALL ADHERE TO NFPA 72,

STIPULATING THAT OPERATOR CONTROLS SHOULD BE POSITIONED

BETWEEN THIRTY-SIX (36) AND SEVENTY-TWO (72) INCHES ABOVE THE

FINISHED FLOOR.

5. RISER DIAGRAM FOR OVERVIEW: THE FIRE ALARM RISER DIAGRAM

SERVES AS AN OVERVIEW OF THE INSTALLATION AND WIRING

REQUIREMENTS, NOT AS A REPRESENTATION OF DEVICE QUANTITY.

6. QUALITY AND COMPLIANCE STANDARDS: ALL SYSTEM COMPONENTS

MUST CARRY UL LISTING AND FM APPROVAL. THEIR INSTALLATION

SHOULD COMPLY WITH RELEVANT CODES, STANDARDS, MANUFACTURER

INSTRUCTIONS, AND LISTING REQUIREMENTS.

7. NETWORKED SYSTEM REDUNDANCY: FOR NETWORKED SYSTEMS, EACH

DISTRIBUTED FIRE ALARM CONTROL UNIT SHOULD INCLUDE ALL

ESSENTIAL COMPONENTS TO OPERATE INDEPENDENTLY IN THE EVENT OF

A NETWORK COMMUNICATION FAILURE. THESE COMPONENTS

ENCOMPASS AMPLIFIERS, POWER SUPPLIES, AND MORE.

8. CONDUCTOR SIZE AND LOADING: PLEASE REFER TO SPECIFICATIONS,

MANUFACTURER CUTSHEETS, AND UL LISTINGS/FM APPROVALS FOR

GUIDANCE ON CONDUCTOR SIZE, ACCOUNTING FOR VOLTAGE DROP, AND

CIRCUIT LOADING REQUIREMENTS.

9. SMOKE DETECTOR PLACEMENT: CEILING-MOUNTED SMOKE DETECTORS

MUST MAINTAIN A MINIMUM DISTANCE OF 3 FEET FROM AIR SUPPLY

DIFFUSERS.

1. PRIMARY POWER SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR

TO EACH FIRE ALARM CONTROL UNIT, NOTIFICATION APPLIANCE CIRCUIT

POWER EXTENDER, AND SUPERVISING STATION TRANSMITTING

EQUIPMENT. POWER SHALL BE PROVIDED VIA A DEDICATED 120V CIRCUIT

WITH A RED-LOCKABLE BREAKER WITH ALL ELECTRICAL WORK BEING IN

ACCORDANCE WITH NFPA 72. THE FIRE ALARM AND ELECTRICAL

CONTRACTOR SHALL COORDINATE THE REQUIRED NUMBER AND

LOCATION OF NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDERS

AND OTHER EQUIPMENT REQUIRING 120V AC POWER.

2. SECONDARY POWER SHALL BE PROVIDED BY VIA STORAGE BATTERIES

DEDICATED TO THE SYSTEM. THE CONTRACTOR SHALL PROVIDE

BATTERY CALCULATIONS SHOWING THAT THE END CONDITION OF THE

SYSTEM MEETS THE FOLLOWING CRITERIA:

A. BATTERY CALCULATIONS SHALL INCLUDE A 20% SAFETY MARGIN TO

ACCOUNT FOR FUTURE SYSTEM EXPANSION.

B. BATTERIES SHALL BE CAPABLE OF OPERATING THE SYSTEM UNDER

QUIESCENT LOAD FOR A MINIMUM OF 24 HOURS AND, AT THE END OF

THAT PERIOD, SHALL BE CAPABLE OF OPERATING THE SYSTEM

DURING A FIRE OR OTHER EMERGENCY FOR A PERIOD OF 15 MINUTES

IF ANY AHJ HAS MORE STRICT REQUIREMENTS, THOSE

REQUIREMENTS SHALL APPLY.

C. THE BATTERY CALCULATIONS MUST INCLUDE ALL LOADS INCLUDING

ANY LOADS CONNECTED TO AUXILIARY POWER CIRCUITS.

3. COORDINATION OF REQUIRED SMOKE DETECTION COVERAGE. A

PHOTOELECTRIC SMOKE DETECTOR SHALL BE PROVIDED WITHIN 21 FEET

OF ALL FIRE ALARM CONTROL UNITS, NOTIFICATION APPLIANCE CIRCUIT

POWER EXTENDERS, SUPERVISING STATION TRANSMITTING EQUIPMENT,

AND EMERGENCY RESPONDER RADIO COMMUNICATION SYSTEMS,

WHETHER INDICATED ON PLANS OR NOT.

1. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING 120VAC

NORMAL ELECTRICAL POWER TO ALL FIRE ALARM SYSTEM COMPONENTS

THAT REQUIRE IT.

1. PATHWAY SURVIVABILITY SHALL BE LEVEL 1 UNLESS NOTED OTHERWISE.

2. FIRE ALARM WIRING SHALL BE:

A. TYPE FPLR: PERMITTED FOR USE IN CONDUIT.

3. ALL FIRE ALARM WIRING SHALL BE ROUTED IN EMT CONDUIT.

4. PATHWAY CLASS DESIGNATIONS SHALL BE AS FOLLOWS. REFERENCE

FIRE ALARM RISER AND DETAILS FOR ADDITIONAL INFORMATION.

A. NOTIFICATION APPLIANCE CIRCUITS: MATCH EXISTING

B. SPEAKER CIRCUIT: MATCH EXISTING

C. SIGNALING LINE CIRCUITS: MATCH EXISTING

D. AUXILLARY POWER CIRCUIT: MATCH EXISTING

E. FIBER OPTIC NETWORKING CIRCUITS: CLASS X

5. CLASS A CIRCUITS UTILIZING PHYSICAL CONDUCTORS SHALL BE

INSTALLED SO THE OUTGOING AND RETURN CONDUCTORS SEPARATION

COMPLIES WITH NFPA 72 §12.3.8.

6. EMERGENCY CONTROL FUNCTION INTERFACE DEVICES SHALL BE

LOCATED WITHIN THREE (3) FEET OF THE COMPONENT CONTROLLING

THE EMERGENCY CONTROL FUNCTION. THE INSTALLATION WIRING

BETWEEN THE FIRE ALARM CONTROL UNIT AND THE EMERGENCY

CONTROL FUNCTION INTERFACE DEVICE SHALL BE OF A PATHWAY

CLASSIFICATION AS SPECIFIED ON THE FIRE ALARM RISER.

7. A SINGLE FAULT ON A PATHWAY CONNECTED TO THE ADDRESSABLE

DEVICES SHALL NOT CAUSE THE LOSS OF THE DEVICES IN MORE THAN

ONE ZONE PER NFPA 72 §23.6.1.

8. ALL TERMINATIONS SHALL BE MADE ON TERMINAL BLOCKS OR

TERMINALS THAT ARE AN INTEGRAL PART OF THE DEVICE / APPLIANCE.

SPLICING OF CABLES IS PROHIBITED.

9. COVER PLATES FOR ALL JUNCTION BOXES SHALL BE PAINTED RED. LABEL

CIRCUITS IN ACCORDANCE WITH SPECIFICATIONS.

F

BRIGHTNESS

WATTAGE

SHEET LIST

GENERAL NOTES WIRING

POWER SUPPLY

SUBMITTALS / CLOSEOUT

TRADE COORDINATION

ABC

EQUIPMENT DESIGNATOR

"FACU" - FIRE ALARM CONTROL UNIT

"MIC" - VOICE EVACUATION MICROPHONE

"RMIC" - REMOTE VOICE EVACUATION MICROPHONE

"AMP" - AMPLIFIER

"FAA" - FIRE ALARM ANNUNCIATOR

"NAC" - NOTIFICATION APPLIANCE CIRCUIT POWER EXT

SYMBOLS

FIRE ALARM EQUIPMENT

INITIATING DEVICES

X

PULL STATION TYPE

"F" - MANUAL PULL STATION

X

SPRINKLER INTERFACE DEVICE TYPE

"FS" - FLOW SWITCH

"P" - HIGH/LOW PRESSURE SWITCH

"TS" - VALVE SUPERVISORY SWITCH

SMOKE DETECTOR TYPE DESIGNATOR

"SC" - SMOKE / CO COMBINATION

OPTIONAL TYPE DESIGNATOR (SMOKE DETECTION)

"BLANK" - NO OPTION

"120V" - SMOKE ALARM (NON SYSTEM TYPE)

"SB" - LOW FREQUENCY SOUNDER BASE

X S

X

HEAT DETECTOR TYPE DESIGNATOR

"F" - FIXED TEMPERATURE

NOTIFICATION APPLIANCES

WATTAGE

BRIGHTNESS

MISCELLANEOUS

DOOR HOLDER

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

ISOLATION MODULE

END OF LINE RESISTOR

AIM

AOM

ISO

ELR

DH

FIRE ALARM OFF PREMISES COMMUNICATORX

"C" - DIGITAL DIALER

"K" - KELTRON LS NET9000 TRANSCIEVER

ADDRESSABLE ZONE INTERFACE MODULEAZM

x H

DESIGN NARRATIVE

J JUNCTION BOX

A. THE PROPOSED PROJECT CONSISTS OF A FIRE ALARM SYSTEM UPGRADE TO ADDRESS

NETWORK COMMUNICATION FAILURES AND OBSOLETE EQUIPMENT WHILE MAINTAINING

EXISTING BUILDING FIRE ALARM COVERAGE. THE EXISTING SYSTEM INCLUDES THREE

NETWORKED FIRE ALARM CONTROL PANELS (FACPS), SEVERAL REMOTE POWER

SUPPLIES, AND AUDIO AMPLIFIERS CONNECTED VIA A COPPER NETWORK.

THE BASIS OF DESIGN INCLUDES REPLACEMENT OF THE EXISTING FACPS WITH NEW

ADDRESSABLE FIRE ALARM CONTROL UNITS ON A ONE-FOR-ONE BASIS. THE EXISTING

COPPER NETWORK WILL BE FULLY REPLACED WITH FIBER AND NEW NETWORK

INTERFACE CARDS WILL BE PROVIDED AT EACH NETWORK NODE (FACPS AND AUDIO

AMPLIFIER NODES) TO ENSURE RELIABLE SYSTEM COMMUNICATION. EXISTING

INITIATING DEVICES, NOTIFICATION APPLIANCES, AND FIELD WIRING WILL BE REUSED TO

THE MAXIMUM EXTENT PRACTICABLE.

THE INSTALLING CONTRACTOR SHALL VERIFY VOLTAGE DROP, BATTERY CAPACITY, AND

PATHWAY SURVIVABILITY IN ACCORDANCE WITH NFPA 72. ADDITIONAL REMOTE POWER

SUPPLIES, AMPLIFIERS, OR BATTERIES SHALL BE PROVIDED AS REQUIRED TO MEET

MINIMUM STANDBY AND ALARM DURATION REQUIREMENTS.

THE SCOPE OF WORK IS LIMITED TO SYSTEM REPLACEMENT AND COMMUNICATION

RELIABILITY IMPROVEMENTS; INTELLIGIBILITY TESTING AND SOUND PRESSURE LEVEL

MEASUREMENTS ARE NOT INCLUDED. SFC ENGINEERING DID NOT VALIDATE EXISTING

SYSTEM LAYOUT OR DEVICE PLACEMENT. THIS ENGINEERING SEAL IS LIMITED TO THE

CPU-REPLACEMENT ASPECT OF THE SYSTEM.

SYSTEM ACCEPTANCE TESTING SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 72,

INCLUDING FULL FUNCTIONAL TESTING, DOCUMENTATION, AND RECORD DRAWINGS.

B. ADD ALTERNATES:

A. ADD ALTERNATE 1: REPLACE ALL EXISTING ADDRESSABLE SMOKE AND HEAT

DETECTORS IN KIND WITH EQUIVALENT NEW ADDRESSABLE SMOKE AND HEAT

DETECTION DEVICES.

B. ADD ALTERNATE 2: PREPLACE EXISTING DIALER WITH KELTRON LS NET9000

TRANSCEIVER. PROVIDE ALL REQUIRED CONNECTIONS TO FACP (SERIAL AND DRY

CONTACTS, AS APPLICABLE), ONE (1) DATA DROP AT FACP (COORDINATE WITH

OWNER), NETWORK CONFIGURATION, AND UPS FOR COMMUNICATION EQUIPMENT.

COORDINATE PROGRAMMING, INTEGRATION, AND POINT MAPPING WITH KELTRON.

PERFORM FULL END-TO-END TESTING TO CENTRAL MONITORING STATION IN

ACCORDANCE WITH NFPA 72.

C. ADD ALTERNATE 3: PROVIDE UNIT PRICING FOR THE FOLLOWING:

a. 2A: INITIATING DEVICES THAT FAIL DURING TESTING

b. 2B: NOTIFICATION APPLIANCES THAT FAIL DURING TESTING

c. 2C: ADDITIONAL NAC BOOSTERS, IF REQUIRED DUE TO CALCULATIONS

d. 2D: NAC BOOSTER BATTERIES REQUIRING REPLACEMENT

C. THE NEW FIRE ALARM SYSTEM WILL BE INSTALLED IN ACCORDANCE WITH THE

FOLLOWING CODES AND STANDARDS:

A. NFPA 101 - 2021 EDITION

B. NFPA 1 - 2021 EDITION

C. IBC - 2021 EDITION

D. NFPA 72 - 2019 EDITION

E. NFPA 70 - 2020 EDITION

REFERENCE THE FIRE ALARM RISER DIAGRAM FOR A DETAILED DESCRIPTION OF THE NEW

FIRE ALARM SYSTEM.

WEATHER PROOF SPEAKER / STROBE

BRIGHTNESS

WATTAGE

WP

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

12" = 1'-0"

/2

/2

1:

3:

A M

FA-001

FIRE ALARM LEGEND AND

NOTES

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM SHEET LIST

NUMBER NAME

FA-001 FIRE ALARM LEGEND AND NOTES

FA-100 FIRE ALARM DEMO BASEMENT PLAN

FA-101 FIRE ALARM DEMO LEVEL 1 PLAN

FA-101A FIRE ALARM DEMO LEVEL 1 PART PLANS

FA-102 FIRE ALARM DEMO LEVEL 2 PLAN

FA-102A FIRE ALARM DEMO LEVEL 2 PART PLANS

FA-103 FIRE ALARM DEMO LEVEL 3 PLAN

FA-103A FIRE ALARM DEMO LEVEL 3 PART PLAN

FA-104 FIRE ALARM DEMO LEVEL 4 PLAN

FA-201 FIRE ALARM LEVEL 1 PLAN

FA-201A FIRE ALARM - PART PLANS - LEVEL 1

FA-202 FIRE ALARM LEVEL 2 PLAN

FA-202A FIRE ALARM - PART PLANS - LEVEL 2

FA-203 FIRE ALARM LEVEL 3 PLAN

FA-203A FIRE ALARM - PART PLANS - LEVEL 3

FA-900 FIRE ALARM RISER DIAGRAM

FA-901 FIRE ALARM DETAILS AND MATRIX

No. Description Date

03/03/2026

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

ACCESS FROM

ROOM CORRIDOR

W100CRF ABOVE

SB10A

SB10

SB00STA

SB00CRA

SB03SB04

SB02

SB00ESA

SB25

WB36

UNEXCAVATED

UP

NIC

NIC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/16" = 1'-0"

/2

/2

1:

3:

A M

FA-100

FIRE ALARM DEMO

BASEMENT PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM GENERAL NOTES

1. NO FIRE ALARM CONTROL EQUIPMENT (E.G., FACP, BOOSTER

PANELS, AMPLIFIERS, ETC.) IS LOCATED IN THE BASEMENT. THIS

PLAN IS PROVIDED FOR OVERALL BUILDING CONTEXT AND

COORDINATION ONLY

F A

C P

N A

C

F A

C P

F A

C P

IN

C

C

IN

X

IN

X

IN

X

IN

X

N100CRH

N100LBB

N100STE

N100STF

N100VSD

N100VSE

N101

N101A

N104 N110

N111

N111A

N111B

N111CN111D

N113

N116

N118

N121

N124

N124A

N124B

N124C

N129

N130

N130A

N133

N134

N137

N138 N140

N141

N142

S100CRA

S100CRB

S100CRC

S100CRJ

S100ESA

S100LBA

S100STAS100STB

S100VSA

S100VSB

S101 S103

S105 S106

S107

S108

S109 S109A

S111 S113S115

S120

S120A

S120B

S123

S124

S124A

S124B S124C

S124CA

S124CB

S125

S130

S132

S136

S138

S140

S142

S145

S145A

S145B

S161

S161A

S162

S166

S166A

S168

S171

S172

S173

S174

S175S175A

S178

W100CRD

W100CRE

W100CRF

W100CRG

W100ESB

W100ESC

W100STC

W100VSC

W101

W101A

W105

W107

W108

W110

W111

W113

W114

W115

W117

W119

W121

W123 W124 W126

W131 W132

W133

W135

W136

W137

W138

W139

W141

W142

W159

W161

W163

W165

W167

W171

W173

W175

W177

W181

W183

W183A W183B

W183C

W189

W190

MORSE

200CRZ

DN

UP

UP

DN

UP

DN

UP

DN

UP

UP

IN

XIN

X

N A

C N

A C

N A

C N

A C

NAC

FA

A

F A

A

FA-101A

FA-101A

FA-101A

NIC

NIC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/16" = 1'-0"

/2

/2

1:

3:

A M

FA-101

FIRE ALARM DEMO LEVEL 1

PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM GENERAL NOTES

1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS

OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO

THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA

WHERE WORK IS OCCURRING.

F

C P

N A

C

IN

C

C

IN

X

IN

X

S100CRC

S100STB

S130

S132

S136

S138

S140

S142

N A

C N

A C

N A

C N

A C

F A

C P

W100CRD

W121

W123 W124 W126

IN

X

IN

X

F A

C P

IN

X

IN

X

N116

N118

N124

N124A

N124B

N124C

NAC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/4" = 1'-0"

/2

/2

1:

4:

A M

FA-101A

FIRE ALARM DEMO LEVEL 1

PART PLANS

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

1/4" = 1'-0"

Fire Alarm - Level 1 Demo - Part Plan- Building A

1/4" = 1'-0"

Fire Alarm - Level 1 Demo - Part Plan - Building B

1/4" = 1'-0"

Fire Alarm - Level 1 Demo - Part Plan - Building C

KEYNOTES

1 REPLACE THE EXISTING 7100 FACP WITH NEW S3 FIRE ALARM

CONTROL UNITS.TURN OVER EXISTING CPU TO UNH.

2 REPLACE THE EXISTING E3 FACU 1ST GENERATION ILI-MB-E3

MODULE WITH THE 2ND GENERATION ILI-MB-E3 MODULE. TURN

OVER EXISTING CPU TO UNH.

3 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS

SETS 1 – 5 SERVING BUILDING A

4 EXISTING INX VOICE AMPLIFIER PANELS (NODES 3 AND 4) SERVING

SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS B AND E.

REPLACE THE EXISTING SECOND-GENERATION INI-VGX MODULES

WITH THIRD-GENERATION INI-VGX MODULES.

5 EXISTING INX VOICE AMPLIFIER PANELS (NODES 9 AND 10) SERVING

SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS C AND D.

REPLACE THE EXISTING SECOND-GENERATION INI-VGX MODULES

WITH THIRD-GENERATION INI-VGX MODULE.

6 EXISTING INX VOICE AMPLIFIER PANELS (NODES 3 AND 4) SERVING

SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS A. REPLACE THE

EXISTING SECOND-GENERATION INI-VGX MODULES WITH

THIRD-GENERATION INI-VGX MODULES.

7 EXISTING INCC PANEL WITH MICROPHONE HANDSET SERVING THE

ENTIRE SPEAKER NOTIFICATION SYSTEM. REPLACE THE EXISTING

SECOND-GENERATION INI-VGC MODULE WITH THIRD-GENERATION

INI-VGC MODULE.

8 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS

SETS - 1 SERVING BUILDING C AND D

N200CRDN200LBB

N200STE

N200STF

N200ZOA

N203

N204

N207 N209

N210

N211

N212

N215

N215A N215B N215C N215D

N216 N218

N221

N221A N221B N221C

N221D

N224

N224A

N224B

N224C

N226

N229

N229A

N229B

N230

N233

N233A

N234

N235

N235A N235B

N235C

N238 N240

N241

N241A N241B

N242

S200CLA

S200CRA

S200CRE

S200ESA

S200STAS200STB

S200STH

S200STJ

S200ZOA

S200ZOB

S200ZOC

S203

S210

S211

S212

S215

S216S220

S221

S222

S223

S223A

S224

S225

S226S226A

S227

S230 S232

S234

S236

S236A S236B

S236C

S236D

S236F

S236LS236MS236NS236P

S236Q

S236T

S238

S240

S242

S245S247

S250S252S254S256

W200CRB

W200CRC

W200ESB

W200ESC

W200STC

W200STG

W201

W201A

W205

W207

W208

W211

W213

W214W215

W217

W219 W220

W220A

W220B

W221

W222

W223 W224

W226

W231

W233

W235

W236

W237

W239

W240

W241 W242

W243

W244

W247

W248

W250

W251

W253 W254

W255

W257

W283

W283A

W283B

W283C

W283D

W283E

W288

W289

W289A

W290

HATCH ACCESS

FROM ROOM S205

BELOW

UP

DN

DN

UP

UP

DN

UP

UP

DN

UP

DN

UP

UP

N A

C

NAC

N A

C N

A C

N A

C

FA-102A

FA-102A

NIC

NIC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/16" = 1'-0"

/2

/2

1:

4:

A M

FA-102

FIRE ALARM DEMO LEVEL 2

PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM GENERAL NOTES

1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS

OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO

THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA

WHERE WORK IS OCCURRING.

W220A

W221

W222

W223 W224

W226 N

A C

N A

C N

A C

N A

C

N200CRD

N218

N224

N224A

N224B

N224C

NAC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/4" = 1'-0"

/2

/2

1:

4:

A M

FA-102A

FIRE ALARM DEMO LEVEL 2

PART PLANS

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

1/4" = 1'-0"

Fire Alarm - Level 2 Demo - Part Plan - Building B

1/4" = 1'-0"

Fire Alarm - Level 2 Demo - Part Plan - Building C

KEYNOTES

1 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS

SETS 1 – 4 SERVING BUILDING B & E

2 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS

SETS 2 SERVING BUILDING C & D

N300CRD

N300LBB

N300STE

N300STF

N309

N309A

N309B N309C N309D N309E

N310 N314

N315

N315A N315B N315C N315D

N316 N318

N321

N321A N321B N321C N321D

N324

N324A

N324B

N324C

N328

N329

N330

N333

N333A

N333B N333C

N333D

N334 N338 N340

N341

N342

N343

N345

S300CRA

S300ESA

S300STAS300STB

S300STJ

S310

S311

S312

S315

S316

S319

S320

S321

S322

S323

S324

S325

S326

S332 S332A

S332B

S333S335

S336

S338

S340

S341

S342

S344

S344A

S344B

S360

S360B

W300CRB

W300CRC

W300ESB

W300ESC

W300STC

W300STG

W301

W301A

W305

W307

W308

W311

W313

W314W315

W317

W318

W319

W320

W321

W322

W323

W324

W325 W326

W331

W333

W334

W334A

W334B

W335 W336

W338

W338A

W338BW339

W341

W342 W343

W344

W345

W347

W348

W350

W351

W353 W354

W355

W381

W383

W383B

W385

W387

W388

W389

W390

ROOF

ROOF

ROOF

ROOF

ROOF

UP

DN

UP

DN

UP

DN

DN

UP

DN

UP

DN

NAC

FA-103A

NIC

NIC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/16" = 1'-0"

/2

/2

1:

4:

A M

FA-103

FIRE ALARM DEMO LEVEL 3

PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM GENERAL NOTES

1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS

OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO

THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA

WHERE WORK IS OCCURRING.

N318

N324

N324A

N324B

N324C

NAC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/4" = 1'-0"

/2

/2

1:

4:

A M

FA-103A

FIRE ALARM DEMO LEVEL 3

PART PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

1/4" = 1'-0"

Fire Alarm - Level 3 Demo - Part Plan - Building C

KEYNOTES

1 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS

SET 3 SERVING BUILDING C & D

EQ009403

(Above)

EQ009404

(Above)

EQ009405

(Above)

EQ006171

EQ006172

EQ014261

EQ014565EQ014566

EQ014233

EQ014234

EQ014235

EQ014236

EQ014260

EQ004057

EQ014228

EQ006167 EQ006166

EQ011799

(Above)

EQ014229EQ014227

EQ014538EQ014541

EQ014239

EQ014238

EQ014237

EQ006168

EQ006169

EQ006170

EQ014540

EQ014542

EQ014262

EQ014539

EQ014537

EQ005759

EQ014331

EQ014529

ELEV C

OVERIDE

DUCT

ENCLOSURE

DUCT

ENCLOSURE

ROOF

ROOF

ROOF

ROOF

ROOF

ROOF

ROOF

ROOF

1,778sf

5,027sf

187sf

3,133sf

239sf

408sf

131sf

1,111sf

7,057sf

556sf

237sf

426sf

102sf

201sf

53sf

132sf

W410

N410

N400STF

N400ZOA

N400ZOB

S400STB

W400STC

W400

S410

S400CRA

S400STA

S401

S400ESA

S403

S402

N400ZOC

W410

N410

N400STF

N400ZOA

N400ZOB

S400STB

W400STC

W400

S410

S400CRA

S400STA

S401

S400ESA

S403

S402

N400ZOC

DNDN

DNDN

DN

DN

NIC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/16" = 1'-0"

/2

/2

1:

4:

A M

FA-104

FIRE ALARM DEMO LEVEL 4

PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM GENERAL NOTES

1. NO FIRE ALARM CONTROL EQUIPMENT (E.G., FACP, BOOSTER

PANELS, AMPLIFIERS, ETC.) IS LOCATED IN THE BASEMENT. THIS

PLAN IS PROVIDED FOR OVERALL BUILDING CONTEXT AND

COORDINATION ONLY

N

C

N100CRH

N100LBB

N100STE

N100STF

N100VSD

N100VSE

N101

N101A

N104 N110

N111

N111A

N111B

N111CN111D

N113

N116

N118

N121

N124

N124A

N124B

N124C

N129

N130

N130A

N133

N134

N137

N138 N140

N141

N142

S100CRA

S100CRB

S100CRC

S100CRJ

S100ESA

S100LBA

S100STAS100STB

S100VSA

S100VSB

S101 S103

S105 S106

S107

S108

S109 S109A

S111 S113S115

S120

S120A

S120B

S123

S124

S124A

S124B S124C

S124CA

S124CB

S125

S130

S132

S136

S138

S140

S142

S145

S145A

S145B

S161

S161A

S162

S166

S166A

S168

S171

S172

S173

S174

S175S175A

S178

W100CRD

W100CRE

W100CRF

W100CRG

W100ESB

W100ESC

W100STC

W100VSC

W101

W101A

W105

W107

W108

W110

W111

W113

W114

W115

W117

W119

W121

W123 W124 W126

W131 W132

W133

W135

W136

W137

W138

W139

W141

W142

W159

W161

W163

W165

W167

W171

W173

W175

W177

W181

W183

W183A W183B

W183C

W189

W190

MORSE

200CRZ

DN

UP

UP

DN

UP

DN

UP

DN

UP

UP

N A

C N

A C

N A

C N

A C

NAC

F A

C P

F A

C P

F A

C P

IN

C

C

IN

X

IN

X

IN

XIN

X

IN

X

IN

X

S

S

S

S

FA

A

F A

A

FA-201A

FA-201A

FA-201A

NIC

NIC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/16" = 1'-0"

/2

/2

1:

4:

A M

FA-201

FIRE ALARM LEVEL 1 PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM GENERAL NOTES

1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS

OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO

THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA

WHERE WORK IS OCCURRING.

N

C

S100CRC

S100STB

S130

S132

S136

S138

S140

S142

N A

C N

A C

N A

C N

A C

F A

C P

IN

C

C

IN

X

IN

X

S

S

W100CRD

W121

W123 W124 W126F

A C

P

IN

X

IN

X

S

N116

N118

N124

N124A

N124B

N124C

NAC

F A

C P

IN

X

IN

X

S

K

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/4" = 1'-0"

/2

/2

1:

4:

A M

FA-201A

FIRE ALARM - PART PLANS

- LEVEL 1

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

1/4" = 1'-0" 1 Fire Alarm - Level 1 - Part Plan- Building A

1/4" = 1'-0" 2 Fire Alarm - Level 1 - Part Plan - Building B

1/4" = 1'-0" 3 Fire Alarm - Level 1 - Part Plan - Building C

KEYNOTES

1 PROVIDE A NEW S3 FIRE ALARM CONTROL PANEL. PROVIDE THE

FSL-E3 FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC

NETWORK. CONTRACTOR SHALL OWN REPROGRAMMING AND

REWIRING TO FACILITATE THE UPGRADE OF THE FIRE ALARM

CONTROL PANEL.

2 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS

SETS 1 – 5 SERVING BUILDING A

3 EXISTING INX VOICE AMPLIFIER PANELS (NODES 3 AND 4) SERVING

SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS B AND E.

PROVIDE WITH NEW 3RD GENERATION INI-VGX MODULE. PROVIDE

THE FSL-E3 FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC

NETWORK.

4 EXISTING INX VOICE AMPLIFIER PANELS (NODES 9 AND 10) SERVING

SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS C AND D.

PROVIDE WITH NEW 3RD GENERATION INI-VGX MODULE. PROVIDE

THE FSL-E3 FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC

NETWORK.

5 EXISTING INX VOICE AMPLIFIER PANELS (NODES 3 AND 4) SERVING

SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS A. PROVIDE

WITH NEW 3RD GENERATION INI-VGX MODULE. PROVIDE THE FSL-E3

FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC NETWORK.

6 EXISTING INCC PANEL WITH MICROPHONE HANDSET SERVING THE

ENTIRE SPEAKER NOTIFICATION SYSTEM. PROVIDE WITH 3RD

GENERATION INI-VGC MODULE. PROVIDE THE FSL-E3 FIBER MODULE

TO CONNECT TO THE NEW FIBER OPTIC NETWORK.

7 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS

SETS - 1 SERVING BUILDING C AND D

8 FOR THE EXISTING E3 FACU, PROVIDE AND INSTALL NEW

SECOND-GENERATION COMMUNICATION MODULES, INCLUDING

ILI-MB-E3, RPT-E3-UTP, AND FSL-E3 FIBER MODULES. CONTRACTOR

SHALL OWN REPROGRAMMING AND REWIRING TO FACILITATE THE

UPGRADE OF THE FIRE ALARM CONTROL PANEL.

9 ADD ALTERNATE NO. 2 - REPLACE EXISTING DIALER WITH KELTRON

LS NET9000 TRANSCEIVER. PROVIDE ALL REQUIRED CONNECTIONS

TO FACP (SERIAL AND DRY CONTACTS, AS APPLICABLE), ONE (1)

DATA DROP AT FACP (COORDINATE WITH OWNER), NETWORK

CONFIGURATION, AND UPS FOR COMMUNICATION EQUIPMENT.

COORDINATE PROGRAMMING, INTEGRATION, AND POINT MAPPING

WITH KELTRON. PERFORM FULL END-TO-END TESTING TO CENTRAL

MONITORING STATION IN ACCORDANCE WITH NFPA 72.

N200CRDN200LBB

N200STE

N200STF

N200ZOA

N203

N204

N207 N209

N210

N211

N212

N215

N215A N215B N215C N215D

N216 N218

N221

N221A N221B N221C

N221D

N224

N224A

N224B

N224C

N226

N229

N229A

N229B

N230

N233

N233A

N234

N235

N235A N235B

N235C

N238 N240

N241

N241A N241B

N242

S200CLA

S200CRA

S200CRE

S200ESA

S200STAS200STB

S200STH

S200STJ

S200ZOA

S200ZOB

S200ZOC

S203

S210

S211

S212

S215

S216S220

S221

S222

S223

S223A

S224

S225

S226S226A

S227

S230 S232

S234

S236

S236A S236B

S236C

S236D

S236F

S236LS236MS236NS236P

S236Q

S236T

S238

S240

S242

S245S247

S250S252S254S256

W200CRB

W200CRC

W200ESB

W200ESC

W200STC

W200STG

W201

W201A

W205

W207

W208

W211

W213

W214W215

W217

W219 W220

W220A

W220B

W221

W222

W223 W224

W226

W231

W233

W235

W236

W237

W239

W240

W241 W242

W243

W244

W247

W248

W250

W251

W253 W254

W255

W257

W283

W283A

W283B

W283C

W283D

W283E

W288

W289

W289A

W290

HATCH ACCESS

FROM ROOM S205

BELOW

UP

DN

DN

UP

UP

DN

UP

UP

DN

UP

DN

UP

UP

N A

C

NAC

N A

C N

A C

N A

C

S

S

FA-202A

FA-202A

NIC

NIC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/16" = 1'-0"

/2

/2

1:

4:

A M

FA-202

FIRE ALARM LEVEL 2 PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM GENERAL NOTES

1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS

OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO

THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA

WHERE WORK IS OCCURRING.

W220A

W221

W222

W223 W224

W226

N A

C N

A C

N A

C N

A C

S

N200CRD

N218

N224

N224A

N224B

N224C

NAC

S

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/4" = 1'-0"

/2

/2

1:

4:

A M

FA-202A

FIRE ALARM - PART PLANS

- LEVEL 2

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

1/4" = 1'-0" 2 Fire Alarm - Level 2 - Part Plan - Building B

1/4" = 1'-0" 3 Fire Alarm - Level 2 - Part Plan - Building C

KEYNOTES

1 EXISTING NOTIFICATION APPLIANCE BOOSTER PANELS SETS 1 – 4

SERVING BUILDING B & E

2 EXISTING NOTIFICATION APPLIANCE BOOSTER PANELS SETS 2

SERVING BUILDING C & D

N300CRD

N300LBB

N300STE

N300STF

N309

N309A

N309B N309C N309D N309E

N310 N314

N315

N315A N315B N315C N315D

N316 N318

N321

N321A N321B N321C N321D

N324

N324A

N324B

N324C

N328

N329

N330

N333

N333A

N333B N333C

N333D

N334 N338 N340

N341

N342

N343

N345

S300CRA

S300ESA

S300STAS300STB

S300STJ

S310

S311

S312

S315

S316

S319

S320

S321

S322

S323

S324

S325

S326

S332 S332A

S332B

S333S335

S336

S338

S340

S341

S342

S344

S344A

S344B

S360

S360B

W300CRB

W300CRC

W300ESB

W300ESC

W300STC

W300STG

W301

W301A

W305

W307

W308

W311

W313

W314W315

W317

W318

W319

W320

W321

W322

W323

W324

W325 W326

W331

W333

W334

W334A

W334B

W335 W336

W338

W338A

W338BW339

W341

W342 W343

W344

W345

W347

W348

W350

W351

W353 W354

W355

W381

W383

W383B

W385

W387

W388

W389

W390

ROOF

ROOF

ROOF

ROOF

ROOF

UP

DN

UP

DN

UP

DN

DN

UP

DN

UP

DN

NAC

S

FA-203A

NIC

NIC

NIC

NIC

NIC

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/16" = 1'-0"

/2

/2

1:

4:

A M

FA-203

FIRE ALARM LEVEL 3 PLAN

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

FIRE ALARM GENERAL NOTES

1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS

OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO

THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA

WHERE WORK IS OCCURRING.

N318

N324

N324A

N324B

N324C

NAC

S

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

1/4" = 1'-0"

/2

/2

1:

4:

A M

FA-203A

FIRE ALARM - PART PLANS

- LEVEL 3

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

1/4" = 1'-0" 3 Fire Alarm - Level 3 - Part Plan - Building C

KEYNOTES

1 EXISTING NOTIFICATION APPLIANCE BOOSTER PANELS SET 3

SERVING BUILDING C & D

(E) E3 SERIES

FACP

NODE #1

120 VAC

(E) INX AUDIO

PANEL

NODE #3

120 VAC

(E) INX AUDIO

PANEL

NODE #4

120 VAC

(E) INCC FCC

PANEL WITH

MICROPHONE

120 VAC

NEW S3 FACP

NODE #5

120 VAC

(E) INX AUDIO

PANEL

NODE #6

120 VAC

NEW S3 FACP

NODE #8

120 VAC

(E) INX AUDIO

PANEL

NODE #9

120 VAC

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4

(E) NAC

BOOSTER

PANEL

120 VAC

(E) INX AUDIO

PANEL

NODE #7

120 VAC

(E) INX AUDIO

PANEL

NODE #10

120 VAC

TOTAL OF (5) NAC

BOOSTER PANELS

LOCATED IN RM S130

NEW FIBER OPTIC

NETWORK CIRCUIT

NEW FIBER OPTIC

NETWORK CIRCUIT

(E) NAC

BOOSTER

PANEL

120 VAC

TOTAL OF (1) NAC BOOSTER

PANELS LOCATED IN RM

N124A

(E) NAC

BOOSTER

PANEL

120 VAC

TOTAL OF (1) NAC

BOOSTER PANELS

LOCATED IN RM N224A

(E) NAC

BOOSTER

PANEL

120 VAC

TOTAL OF (1) NAC BOOSTER

PANELS LOCATED IN RM

N324A

(E) NAC

BOOSTER

PANEL

120 VAC

TOTAL OF (4) NAC

BOOSTER PANELS

LOCATED IN RM W224

BUILDING A BUILDING B BUILDING C

1. THE INTENT OF THIS RISER DIAGRAM IS TO ILLUSTRATE THE GENERAL DESIGN INTENT OF THE FIRE ALARM SYSTEM. IT IS NOT

INTENDED TO DEPICT ALL DEVICES, MODULES, OR WIRING.

EXISTING SYSTEM DESCRIPTION:

• THE BUILDING IS CURRENTLY SERVED BY THREE NETWORKED FIRE ALARM CONTROL PANELS (FACPS). THESE PANELS INCLUDE AN FCI E3 SERIES PANEL LOCATED IN THE FIRE ALARM COMMAND CENTER (ROOM S142), AN FCI 7100 PANEL IN ELECTRICAL ROOM N124A, AND ANOTHER FCI 7100 PANEL IN ELECTRICAL ROOM W124. THE THREE FACPS ARE INTERCONNECTED THROUGH AN RPT-

E3-UTP NETWORK REPEATER CARD USING CLASS A, 14 AWG TWISTED, NON-SHIELDED WIRING.

• CURRENTLY THERE IS A NETWORKING ISSUE BETWEEN THE FACPS. WHEN ONE PANEL GOES INTO ALARM, THE OTHER PANELS DO NOT ACTIVATE OR INITIATE THE BUILDING’S NOTIFICATION APPLIANCES. THIS ISSUE IS THE MAIN REASON THAT A SYSTEM UPGRADE IS BEING PROPOSED. THE 7100 SERIES PANELS ARE ALSO DISCONTINUED, WHICH ADDS TO THE NEED FOR REPLACEMENT. BASED ON THE EXISTING TEST REPORTS, THE NETWORK COMMUNICATION ISSUE APPEARS TO BE THE ONLY ONGOING PROBLEM WITH

THE KINGSBURY HALL FIRE ALARM SYSTEM.

FIRE ALARM CONTROL UNIT AND POWER SUPPLIES:

• KINGSBURY HALL WILL BE SERVED BY A NEW CPU BACKBONE CONSISTING OF THREE NEW NETWORKED ADDRESSABLE FIRE ALARM CONTROL PANELS. THE BASIS OF DESIGN IS THE GAMEWELL-FCI S3 SERIES FIRE ALARM CONTROL UNIT. THE S3 SERIES FACP’S ARE INTENDED TO BE THE DIRECT UPGRADE FOR THE OLDER 7100 FACP’S. THREE NEW S3 FACPS WILL BE PROVIDED TO REPLACE THE EXISTING 7100 FACP’S AND E3 FACP ON A ONE-FOR-ONE BASIS. THE INTENT OF THE UPGRADE IS TO REPLACE THE EXISTING CPUS AND UPGRADE THE SYSTEM WHILE REUSING THE EXISTING WIRING, INITIATING DEVICES, AND NOTIFICATION

APPLIANCES TO THE MAXIMUM EXTENT PRACTICAL.

• THE NEW S3 FACPS WILL BE LOCATED IN THE FOLLOWING ROOMS:

1. FIRE ALARM COMMAND CENTER ROOM S142

2. ELECTRICAL ROOM N124A

3. ELECTRICAL ROOM W124

• EXISTING REMOTE POWER SUPPLIES AND AMPLIFIERS SHOULD BE REUSED WHERE POSSIBLE. THE CONTRACTOR MUST PERFORM VOLTAGE DROP CALCULATIONS ON THE EXISTING CIRCUITS TO CONFIRM THAT THE REMOTE POWER SUPPLIES ARE WITHIN THE ALLOWABLE VOLTAGE DROP LIMITS. NEW REMOTE POWER SUPPLIES AND AMPLIFIERS MUST BE ADDED AS NEEDED BASED ON THE RESULTS OF THE VOLTAGE DROP AND BATTERY CAPACITY CALCULATIONS PERFORMED BY THE CONTRACTOR.

• A SMOKE DETECTOR SHALL BE INSTALLED IN THE VICINITY OF EACH FIRE ALARM CONTROL UNIT, REMOTE POWER SUPPLY, AND

AMPLIFIER IN ACCORDANCE WITH NFPA 72.

• EACH FACP, REMOTE POWER SUPPLY, AND AUDIO DIGITAL AMPLIFIER SHALL HAVE A SECONDARY POWER SUPPLY CAPABLE OF OPERATING THE SYSTEM FOR A MINIMUM OF 24 HOURS IN STANDBY AND 15 MINUTES IN ALARM. THE INSTALLING CONTRACTOR SHALL VERIFY THE ADEQUACY OF THE EXISTING BATTERY CAPACITY THROUGH BATTERY CALCULATIONS. NEW BATTERIES SHALL BE PROVIDED AS NECESSARY TO ENSURE COMPLIANCE WITH THE REQUIRED MINIMUM OPERATING DURATIONS.

FIRE ALARM RISER DIAGRAM GENERAL NOTES

C

BUILDING E BUILDING D

SLC

LOOP #1

SLC LOOP #2

SLC

LOOP #1

SLC LOOP #2

SLC

LOOP #1

FIRE ALARM RISER LEGEND

= EXISTING SIGNILING LINE CIRCUIT (SLC)

= EXISTING SPEAKER CIRCUIT

= EXISTING VISUAL CIRCUIT

= NEW FIBER OPTIC NETWORK CIRCUIT

333444444 444 444 444 444

NOTIFICATION:

• AN IN-BUILDING EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM (EVACS) IS CURRENTLY INSTALLED THROUGHOUT KINGSBURY HALL. THE INTENT OF THIS PROJECT IS TO RETAIN THE EXISTING NOTIFICATION APPLIANCES AND TO CONTINUE UTILIZING THE EXISTING AMPLIFIERS AND REMOTE POWER SUPPLIES TO SERVE THE EXISTING NOTIFICATION APPLIANCES. SFC ENGINEERING DID NOT VALIDATE EXISTING SYSTEM LAYOUT OR DEVICE PLACEMENT. THIS ENGINEERING

SEAL IS LIMITED TO THE CPU-REPLACEMENT ASPECT OF THE SYSTEM.

• INTELLIGIBILITY AND SOUND PRESSURE LEVEL MEASUREMENTS WERE NOT EVALUATED AS PART OF THIS ENGINEERING EFFORT. SINCE THE PRIMARY ISSUE IDENTIFIED INVOLVES COMMUNICATION BETWEEN NETWORKED NODES, THE PROPOSED UPGRADE FOCUSES ON RESOLVING THIS ISSUE AND MAINTAINING

PROPER OPERATION OF THE EXISTING NOTIFICATION SYSTEM.

• AN EXISTING MICROPHONE HANDSET IS PROVIDED AT THE FIRE COMMAND CENTER. THE INX AUDIO AMPLIFIER NODES ARE NETWORKED WITH THE FACU'S VIA A CLASS A, 14 AWG TWISTED, NON-SHIELDED PAIR. AS PART OF THIS PROJECT, THE EXISTING CLASS A, 14 AWG TWISTED UNSHIELDED COPPER NETWORK WIRING SHALL BE REPLACED WITH A CLASS A SINGLE-MODE FIBER OPTIC NETWORK. PROVIDE AND REPLACE ALL REQUIRED NETWORK INTERFACE CARDS, FIBER MODULES, AND ASSOCIATED HARDWARE NECESSARY TO SUPPORT THE NEW FIBER NETWORK. THE INX AUDIO AMPLIFIER NODES ARE LOCATED IN THE

FOLLOWING ROOMS:

1. FIRE ALARM COMMAND CENTER ROOM S142

2. ELECTRICAL ROOM N124A

3. ELECTRICAL ROOM W124

PATHWAY SURVIVIBILITY:

• FIBER OPTIC NETWORK CABLE - LEVEL 1

• NOTIFICIATION APPLIANCE CIRCUIT (NAC) - LEVEL 1

• SPEAKER CIRCUIT - LEVEL 1

• SIGNILING LINE CIRCUIT (SLC) - LEVEL 1

• AUXILIARY POWER - LEVEL 1

SYSTEM ACCEPTANCE:

• THE FIRE ALARM EQUIPMENT SHALL UNDERGO A 100% ACCEPTANCE TEST PERFORMED BY THE INSTALLING CONTRACTOR AND APPROVED TESTING COMPANY.

THE FIRE ALARM SYSTEM WILL BE TESTED IN ACCORDANCE WITH NFPA 72. THE FOLLOWING DOCUMENTS SHALL BE REQUIRED AT PROJECT CLOSEOUT:

1. A RECORD OF COMPLETION REPORT

2. A RECORD OF INSPECTION AND TESTING REPORT. TESTING RESULTS SHALL BE DOCUMENTED IN ACCORDANCE WITH NFPA 72.

3. AS-BUILT DRAWINGS

• CONTRACTOR SHALL INCLUDE UNIT PRICING IN THEIR BID FOR REPLACEMENT OF NOTIFICATION APPLIANCES, MODULES, AND INITIATING DEVICES IN THE EVENT

ANY DEVICE FAILS ACCEPTANCE TESTING.

BASEMENT

E

SYNC

SYNC

SYNC

SYNC

FROM NAC ON

1ST FLR

FROM SPEAKER

CKT ON 1ST FLR

SYNC

SYNC = EXISTING SYNC MODULE SERVING NAC'S

= NEW WORK

(E) FAA (E) FAA

(E) FAA = EXISTING REMOTE ANNUNCIATOR

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

12" = 1'-0"

/2

/2

1:

4:

A M

FA-900

FIRE ALARM RISER

DIAGRAM

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

KEYNOTES

1 REMOVE THE EXISTING RPT-E3-UTP NETWORK REPEATER CARD

AND ASSOCIATED CLASS A, 14 AWG TWISTED, UNSHIELDED COPPER

NETWORK WIRING INTERCONNECTING THE NODES. PROVIDE NEW

RPT-E3-UTP NETWORK REPEATER ASSEMBLIES EQUIPPED WITH

FSL-E3 SINGLE-MODE FIBER OPTIC MODULES AT EACH NETWORK

NODE. INSTALL NEW SINGLE-MODE FIBER OPTIC CABLING BETWEEN

ALL NODES TO ESTABLISH THE COMPLETE FIRE ALARM NETWORK.

COORDINATE FINAL NETWORK CONFIGURATION AND TERMINATIONS

WITH THE FIRE ALARM MANUFACTURER’S REQUIREMENTS.

2 REPLACE THE EXISTING 7100 FACU'S WITH NEW S3 FIRE ALARM

CONTROL UNITS.

3 THE CURRENT INCC COMMAND CENTER IS UTILIZING THE SECOND

GENERATION INI-VGC CARD. THE INTENT IS TO UPGRADE THE

INI-VGC CARD TO 3RD GENERATION. PROVIDE THE FSL-E3 FIBER

MODULE TO CONNECT TO THE NEW FIBER OPTIC NETWORK.

4 THE CURRENT INI-VGX CARDS ARE SECOND GENERATION. THE

INTENT IS TO UPGRADE EACH INI-VGX CARD WITH A 3RD

GENERATION MODEL DUE TO UPGRADING THE FIRE ALARM

CONTROL PANEL. EACH INI-VGX SHALL BE PROVIDED WITH THE

FSL-E3 FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC

NETWORK.

5 FOR THE EXISTING E3 FACU, PROVIDE AND INSTALL NEW

SECOND-GENERATION COMMUNICATION MODULES, INCLUDING

ILI-MB-E3, RPT-E3-UTP, AND FSL-E3 FIBER MODULES.

No. Description Date

CLASS X

CLASS X

SUPPLY DIFFUSER

3 FEET MIN

MOUNT AT 66" AFF

TO TOP OF

ENCLOSURE MOUNT AT 60"

AFF. TO TOP OF

ENCLOSURE

CEILING MOUNTED SMOKE /

HEAT DETECTOR

WALL MOUNTED SMOKE /

HEAT DETECTOR

FINISHED FLOOR

4"

M A

X

5' MAX

SYCHRONIZE MORE THAN

TWO VISUAL APPLIANCES IN

ANY FIELD OF VIEW

4"

DO NOT MOUNT

DEVICE HERE

FACU

1. IN NON-SLEEPING AREAS WALL MOUNT VISIBLE

NOTIFICATION APPLIANCES SHALL BE INSTALLED

SUCH THAT THE ENTIRE LENS IS NOT LESS THAN

80 INCHES AND NOT GREATER THAN 90 INCHES

ABOVE THE FINISHED FLOOR. WHERE LOW

CEILING HEIGHTS DO NOT PERMIT MOUNTING AT A

MINIMUM OF 80 INCHES,VISIBLE APPLIANCES

SHALL BE MOUNTED WITHIN 6 INCHES OF THE

CEILING.

2. WALL-MOUNTED AUDIBLE APPLIANCE SHALL HAVE

THEIR TOPS NOT LESS THAN 90 IN. ABOVE THE

FLOOR AND NOT LESS THAN 6 IN. BELOW THE

CEILING.

FAA

PULL DOWN

FIRE ALARM

REMOTE

INDICATOR LIGHT

Scale

Date

Drawn By

Checked By

Project Number

SFC ENGINEERING

183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700

NOT FOR CONSTRUCTION

NTS

/2

/2

1:

4:

A M

FA-901

FIRE ALARM DETAILS AND

MATRIX

UNIVERSITY OF NEW

HAMPSHIRE

KINGSBURY HALL FIRE

ALARM UPGRADE

SJS

ARC

03/04/2026

670070

NTS

FIRE ALARM DEVICE MOUNTING

ELEVATIONS

File details come from the government source that posted it. Updated .