670070 UNH - Kingsbury Hall - Fire Alarm Drawings.pdf
PDF 9 MB Posted
- Attached to
- UNH Kingsbury Hall - Fire Alarm Replacement
- Solicitation number
- 212026960
- Issued by
- New Hampshire
About this file
This document comprises fire alarm system design drawings and specifications for a fire alarm replacement project at Kingsbury Hall, University of New Hampshire, prepared by SFC Engineering. The project involves replacing three networked fire alarm control panels (FACPs)—specifically replacing existing discontinued 7100 Series panels and an E3 Series panel with new S3 Series fire alarm control units on a one-for-one basis while maintaining existing building fire alarm coverage. The scope includes replacing the existing copper network with single-mode fiber optic cabling, upgrading network interface cards and audio amplifier modules, and retaining existing initiating devices and notification appliances to the maximum extent practicable. The design addresses network communication failures that prevent coordinated alarm activation across panels and ensures compliance with NFPA 72 (2019), NFPA 101 (2021), NFPA 1 (2021), IBC (2021), and NFPA 70 (2020) standards. Three new S3 FACPs will be located in the Fire Alarm Command Center (Room S142) and electrical rooms N124A and W124.
The contractor is responsible for comprehensive submittal requirements including product data, fully coordinated working plans and shop drawings containing battery calculations, sequence of operations, voltage drop calculations, floor plans, and full system riser diagrams, all developed under the responsible charge of a NICET Level III or IV technician or professional engineer. System acceptance testing must comply with NFPA 72 Chapter 14 with 100% testing of all devices, and the contractor must provide notification five business days prior to testing to allow engineer attendance. Deliverables include an owner's manual, record (as-built) drawings showing all point-to-point wiring, record of completion form, contractor certificate of compliance, and written certification of punch list completion. Add Alternates include replacement of all addressable smoke and heat detectors in kind, replacement of the existing dialer with a Keltron LS NET9000 transceiver with network configuration and UPS equipment, and unit pricing for failed initiating devices, notification appliances, and additional NAC boosters or batteries if required by calculations. The installation must conform to manufacturer specifications and include a 20% safety margin in battery calculations to account for future system expansion, with batteries capable of 24-hour standby and 15-minute alarm operation.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
XX
A ALARM BELL
WEATHER PROOF EXTERIOR HORN / STROBE
SPEAKER ONLY
GAS DETECTOR TYPE DESIGNATOR
"CO" - CARBON MONOXIDE
SPEAKER / STROBE
VISUAL ONLY
1. PRODUCT DATA: A COMPREHENSIVE SUBMITTAL OF ALL PRODUCT DATA
REQUIRED FOR A COMPLETE FIRE ALARM SYSTEM SHALL BE PROVIDED
INCLUDING CUT SHEETS WITH ALL APPLICABLE OPTIONS SELECTED FOR
DEVICES, APPLIANCES, AND PANELS.
2. WORKING PLANS / SHOP DRAWINGS: SUBMIT COMPLETE, FULLY
COORDINATED WORKING PLANS / SHOP DRAWINGS CONTAINING
INFORMATION REQUIRED BY THE APPLICABLE EDITION OF NFPA 72. THESE
DRAWING SHALL CONTAIN:
A. BATTERY CALCULATIONS TO CONFIRM THAT THE DESIGN CRITERIA IS
MET. THE CONTRACTOR IS RESPONSIBLE FOR TRACING AND
ANALYZING ALL EXISTING DEVICES, AS REQUIRED TO SUBMIT
COMPLETE AND ACCURATE BATTERY CALCULATIONS.
B. SEQUENCE OF OPERATIONS.
C. VOLTAGE DROP CALCULATIONS.
D. FLOOR PLANS INCLUDING LOCATION OF ALL DEVICES, APPLIANCES,
AND PANELS.
E. FULL SYSTEM RISER DIAGRAM.
3. SHOP DRAWINGS SHALL BE DEVELOPED UNDER THE RESPONSIBLE
CHARGE OF A NICET LEVEL III OR IV TECHNICIAN OR A PROFESSIONAL
ENGINEER AND SHALL BEAR THE NAME, LICENSE NUMBER, AND
EXPIRATION DATE OF THE INSTALLING CONTRACTOR.
4. SHOP DRAWINGS SHALL BE APPROVED BY THE ENGINEER PRIOR TO
SUBMISSION TO THE AHJ.
5. AFTER INCORPORATION OF ENGINEER COMMENTS, THE APPROVED SHOP
DRAWING SHALL BE SUBMITTED TO THE AHJ FOR APPROVAL.
6. SYSTEM ACCEPTANCE TESTING SHALL BE PERFORMED IN ACCORDANCE
WITH NFPA 72, CHAPTER 14. AT MINIMUM, TESTING SHALL INCLUDE:
A. 100% TEST OF ENTIRE SYSTEM DEVICES.
7. NOTIFY THE ENGINEER, IN WRITING, OF DATE AND TIME OF SYSTEM
ACCEPTANCE TESTING, SO HE OR SHE (OR A DESIGNEE) MAY ATTEND AT
THEIR SOLE DISCRETION. NOTIFICATION SHOULD OCCUR FIVE (5)
BUSINESS DAYS PRIOR TO TEST. IF THE ENGINEER IS NOT NOTIFIED, THE
TEST MAY NEED TO BE PERFORMED AGAIN AT NO ADDITIONAL COST TO
THE OWNER.
8. AN OWNER’S MANUAL AND MANUFACTURER’S PUBLISHED INSTRUCTIONS
COVERING ALL SYSTEM EQUIPMENT. THIS MANUAL SHALL BE PROVIDED
TO THE ENGINEER FOR REVIEW NOT LESS THAN TEN (10) WORKING DAYS
PRIOR TO ANTICIPATED FINAL ENGINEER SIGNOFF.
9. RECORD (AS-BUILT) DRAWINGS. THESE DRAWINGS SHALL BE PROVIDED
TO THE ENGINEER FOR REVIEW NOT LESS THAN FIVE (5) WORKING DAYS
PRIOR TO ANTICIPATED FINAL ENGINEER SIGNOFF. FINAL AS-BUILT
DRAWINGS MUST SHOW ALL POINT-TO-POINT WIRING.
10. A COMPLETED RECORD OF COMPLETION FORM. THIS FORM SHALL BE
PROVIDED TO THE ENGINEER FOR REVIEW NOT LESS THAN THREE (3)
WORKING DAYS PRIOR TO ANTICIPATED FINAL ENGINEER SIGNOFF.
11. FOR SOFTWARE BASED SYSTEMS, A RECORD COPY OF THE SITE-
SPECIFIC SOFTWARE SHALL BE PROVIDED TO THE OWNER’S SERVICE
PROVIDER.
12. CONTRACTOR CERTIFICATE OF COMPLIANCE. CONTRACTOR SHALL
SUBMIT A LETTER ON COMPANY LETTERHEAD AND SIGNED BY AN
AUTHORIZED INDIVIDUAL THAT STATES TO THE CONTRACTOR’S BEST
KNOWLEDGE THE INSTALLATION OF THE SYSTEM WAS INSTALLED IN
ACCORDANCE WITH APPLICABLE CODES AND STANDARDS. THIS MANUAL
SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW NOT LESS THAN
THREE (3) WORKING DAYS PRIOR TO ANTICIPATED FINAL ENGINEER
SIGNOFF.
13. WRITTEN CERTIFICATION OF COMPLETION OF ALL PUNCH LIST ITEMS.
THIS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW NOT LESS
THAN FIVE (5) WORKING DAYS PRIOR TO ANTICIPATED FINAL ENGINEER
SIGNOFF.
14. THE FOLLOWING DOCUMENTS SHALL BE STORED IN AN APPROVED FIRE
ALARM CABINET AT THE MAIN FIRE ALARM CONTROL UNIT, OR OTHER
APPROVED LOCATION:
A. COPY OF SYSTEM RECORD OF COMPLETION.
B. COPY OF SYSTEM RECORD OF INSPECTION & TESTING.
C. COPY OF RECORD DRAWINGS.
D. COPY OF FIRE PROTECTION NARRATIVE
1. REFERENCE TO DESIGN DOCUMENTATION: PLEASE CONSULT THE
PROJECT SPECIFICATIONS, FIRE ALARM MATRIX, AND FIRE PROTECTION
NARRATIVE (AS APPLICABLE) FOR ADDITIONAL INSIGHTS INTO THE DESIGN
INTENT AND PRODUCT REQUIREMENTS.
2. COMPLIANCE WITH CODES AND REGULATIONS: ALL WORK MUST ADHERE
TO FEDERAL, STATE, AND LOCAL CODES AND REGULATIONS. IN CASES
WHERE THERE IS A CONFLICT BETWEEN SPECIFIED REQUIREMENTS AND
RELEVANT CODES OR REGULATIONS, THE STRICTER REQUIREMENTS
SHALL TAKE PRECEDENCE.
3. FIRE ALARM SYSTEM IMPARIMENTS: DURING EACH FACP REPLACEMENT,
THE FIRE ALARM SYSTEM IN A PORTION OF THE BUILDING WILL BE
OFFLINE UNTIL THE NEW PANEL IS INSTALLED AND ACCEPTANCE TESTING
IS COMPLETED. A DETAILED IMPAIRMENT PLAN WILL NEED TO BE
DEVELOPED BY THE CONTRACTOR, WHICH MAY INCLUDE INSTALLING A
TEMPORARY WIRELESS FIRE ALARM SYSTEM.
1. FIRE ALARM SYSTEM PROGRAMMING AND CERTIFICATION: THE
CONTRACTOR IS RESPONSIBLE FOR PROGRAMMING, TESTING, AND
CERTIFYING THE FIRE ALARM SYSTEM UPON THE COMPLETION OF THEIR
WORK.
2. SYSTEM DOCUMENTATION AND VERIFICATION: THE SYSTEM
MANUFACTURER IS REQUIRED TO PROVIDE AN INSTALLATION WIRING
DIAGRAM FOR THE FIRE ALARM SYSTEM AND A VERIFICATION
CERTIFICATE CONFIRMING SYSTEM FUNCTIONALITY BEFORE FINAL
ACCEPTANCE.
3. CONFORMANCE WITH MANUFACTURER'S SPECIFICATIONS: ALL FIELD
WIRING AND EQUIPMENT INSTALLATION SHALL CONFORM TO THE
MANUFACTURER'S WIRING DIAGRAMS.
4. CLEARANCE FOR CONTROL UNITS: ENSURE THAT ALL FIRE ALARM
CONTROL UNITS HAVE ADEQUATE WORKING CLEARANCE IN ACCORDANCE
WITH NFPA 70. PANEL MOUNTING HEIGHT SHALL ADHERE TO NFPA 72,
STIPULATING THAT OPERATOR CONTROLS SHOULD BE POSITIONED
BETWEEN THIRTY-SIX (36) AND SEVENTY-TWO (72) INCHES ABOVE THE
FINISHED FLOOR.
5. RISER DIAGRAM FOR OVERVIEW: THE FIRE ALARM RISER DIAGRAM
SERVES AS AN OVERVIEW OF THE INSTALLATION AND WIRING
REQUIREMENTS, NOT AS A REPRESENTATION OF DEVICE QUANTITY.
6. QUALITY AND COMPLIANCE STANDARDS: ALL SYSTEM COMPONENTS
MUST CARRY UL LISTING AND FM APPROVAL. THEIR INSTALLATION
SHOULD COMPLY WITH RELEVANT CODES, STANDARDS, MANUFACTURER
INSTRUCTIONS, AND LISTING REQUIREMENTS.
7. NETWORKED SYSTEM REDUNDANCY: FOR NETWORKED SYSTEMS, EACH
DISTRIBUTED FIRE ALARM CONTROL UNIT SHOULD INCLUDE ALL
ESSENTIAL COMPONENTS TO OPERATE INDEPENDENTLY IN THE EVENT OF
A NETWORK COMMUNICATION FAILURE. THESE COMPONENTS
ENCOMPASS AMPLIFIERS, POWER SUPPLIES, AND MORE.
8. CONDUCTOR SIZE AND LOADING: PLEASE REFER TO SPECIFICATIONS,
MANUFACTURER CUTSHEETS, AND UL LISTINGS/FM APPROVALS FOR
GUIDANCE ON CONDUCTOR SIZE, ACCOUNTING FOR VOLTAGE DROP, AND
CIRCUIT LOADING REQUIREMENTS.
9. SMOKE DETECTOR PLACEMENT: CEILING-MOUNTED SMOKE DETECTORS
MUST MAINTAIN A MINIMUM DISTANCE OF 3 FEET FROM AIR SUPPLY
DIFFUSERS.
1. PRIMARY POWER SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR
TO EACH FIRE ALARM CONTROL UNIT, NOTIFICATION APPLIANCE CIRCUIT
POWER EXTENDER, AND SUPERVISING STATION TRANSMITTING
EQUIPMENT. POWER SHALL BE PROVIDED VIA A DEDICATED 120V CIRCUIT
WITH A RED-LOCKABLE BREAKER WITH ALL ELECTRICAL WORK BEING IN
ACCORDANCE WITH NFPA 72. THE FIRE ALARM AND ELECTRICAL
CONTRACTOR SHALL COORDINATE THE REQUIRED NUMBER AND
LOCATION OF NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDERS
AND OTHER EQUIPMENT REQUIRING 120V AC POWER.
2. SECONDARY POWER SHALL BE PROVIDED BY VIA STORAGE BATTERIES
DEDICATED TO THE SYSTEM. THE CONTRACTOR SHALL PROVIDE
BATTERY CALCULATIONS SHOWING THAT THE END CONDITION OF THE
SYSTEM MEETS THE FOLLOWING CRITERIA:
A. BATTERY CALCULATIONS SHALL INCLUDE A 20% SAFETY MARGIN TO
ACCOUNT FOR FUTURE SYSTEM EXPANSION.
B. BATTERIES SHALL BE CAPABLE OF OPERATING THE SYSTEM UNDER
QUIESCENT LOAD FOR A MINIMUM OF 24 HOURS AND, AT THE END OF
THAT PERIOD, SHALL BE CAPABLE OF OPERATING THE SYSTEM
DURING A FIRE OR OTHER EMERGENCY FOR A PERIOD OF 15 MINUTES
IF ANY AHJ HAS MORE STRICT REQUIREMENTS, THOSE
REQUIREMENTS SHALL APPLY.
C. THE BATTERY CALCULATIONS MUST INCLUDE ALL LOADS INCLUDING
ANY LOADS CONNECTED TO AUXILIARY POWER CIRCUITS.
3. COORDINATION OF REQUIRED SMOKE DETECTION COVERAGE. A
PHOTOELECTRIC SMOKE DETECTOR SHALL BE PROVIDED WITHIN 21 FEET
OF ALL FIRE ALARM CONTROL UNITS, NOTIFICATION APPLIANCE CIRCUIT
POWER EXTENDERS, SUPERVISING STATION TRANSMITTING EQUIPMENT,
AND EMERGENCY RESPONDER RADIO COMMUNICATION SYSTEMS,
WHETHER INDICATED ON PLANS OR NOT.
1. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING 120VAC
NORMAL ELECTRICAL POWER TO ALL FIRE ALARM SYSTEM COMPONENTS
THAT REQUIRE IT.
1. PATHWAY SURVIVABILITY SHALL BE LEVEL 1 UNLESS NOTED OTHERWISE.
2. FIRE ALARM WIRING SHALL BE:
A. TYPE FPLR: PERMITTED FOR USE IN CONDUIT.
3. ALL FIRE ALARM WIRING SHALL BE ROUTED IN EMT CONDUIT.
4. PATHWAY CLASS DESIGNATIONS SHALL BE AS FOLLOWS. REFERENCE
FIRE ALARM RISER AND DETAILS FOR ADDITIONAL INFORMATION.
A. NOTIFICATION APPLIANCE CIRCUITS: MATCH EXISTING
B. SPEAKER CIRCUIT: MATCH EXISTING
C. SIGNALING LINE CIRCUITS: MATCH EXISTING
D. AUXILLARY POWER CIRCUIT: MATCH EXISTING
E. FIBER OPTIC NETWORKING CIRCUITS: CLASS X
5. CLASS A CIRCUITS UTILIZING PHYSICAL CONDUCTORS SHALL BE
INSTALLED SO THE OUTGOING AND RETURN CONDUCTORS SEPARATION
COMPLIES WITH NFPA 72 §12.3.8.
6. EMERGENCY CONTROL FUNCTION INTERFACE DEVICES SHALL BE
LOCATED WITHIN THREE (3) FEET OF THE COMPONENT CONTROLLING
THE EMERGENCY CONTROL FUNCTION. THE INSTALLATION WIRING
BETWEEN THE FIRE ALARM CONTROL UNIT AND THE EMERGENCY
CONTROL FUNCTION INTERFACE DEVICE SHALL BE OF A PATHWAY
CLASSIFICATION AS SPECIFIED ON THE FIRE ALARM RISER.
7. A SINGLE FAULT ON A PATHWAY CONNECTED TO THE ADDRESSABLE
DEVICES SHALL NOT CAUSE THE LOSS OF THE DEVICES IN MORE THAN
ONE ZONE PER NFPA 72 §23.6.1.
8. ALL TERMINATIONS SHALL BE MADE ON TERMINAL BLOCKS OR
TERMINALS THAT ARE AN INTEGRAL PART OF THE DEVICE / APPLIANCE.
SPLICING OF CABLES IS PROHIBITED.
9. COVER PLATES FOR ALL JUNCTION BOXES SHALL BE PAINTED RED. LABEL
CIRCUITS IN ACCORDANCE WITH SPECIFICATIONS.
F
BRIGHTNESS
WATTAGE
SHEET LIST
GENERAL NOTES WIRING
POWER SUPPLY
SUBMITTALS / CLOSEOUT
TRADE COORDINATION
ABC
EQUIPMENT DESIGNATOR
"FACU" - FIRE ALARM CONTROL UNIT
"MIC" - VOICE EVACUATION MICROPHONE
"RMIC" - REMOTE VOICE EVACUATION MICROPHONE
"AMP" - AMPLIFIER
"FAA" - FIRE ALARM ANNUNCIATOR
"NAC" - NOTIFICATION APPLIANCE CIRCUIT POWER EXT
SYMBOLS
FIRE ALARM EQUIPMENT
INITIATING DEVICES
X
PULL STATION TYPE
"F" - MANUAL PULL STATION
X
SPRINKLER INTERFACE DEVICE TYPE
"FS" - FLOW SWITCH
"P" - HIGH/LOW PRESSURE SWITCH
"TS" - VALVE SUPERVISORY SWITCH
SMOKE DETECTOR TYPE DESIGNATOR
"SC" - SMOKE / CO COMBINATION
OPTIONAL TYPE DESIGNATOR (SMOKE DETECTION)
"BLANK" - NO OPTION
"120V" - SMOKE ALARM (NON SYSTEM TYPE)
"SB" - LOW FREQUENCY SOUNDER BASE
X S
X
HEAT DETECTOR TYPE DESIGNATOR
"F" - FIXED TEMPERATURE
NOTIFICATION APPLIANCES
WATTAGE
BRIGHTNESS
MISCELLANEOUS
DOOR HOLDER
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
ISOLATION MODULE
END OF LINE RESISTOR
AIM
AOM
ISO
ELR
DH
FIRE ALARM OFF PREMISES COMMUNICATORX
"C" - DIGITAL DIALER
"K" - KELTRON LS NET9000 TRANSCIEVER
ADDRESSABLE ZONE INTERFACE MODULEAZM
x H
DESIGN NARRATIVE
J JUNCTION BOX
A. THE PROPOSED PROJECT CONSISTS OF A FIRE ALARM SYSTEM UPGRADE TO ADDRESS
NETWORK COMMUNICATION FAILURES AND OBSOLETE EQUIPMENT WHILE MAINTAINING
EXISTING BUILDING FIRE ALARM COVERAGE. THE EXISTING SYSTEM INCLUDES THREE
NETWORKED FIRE ALARM CONTROL PANELS (FACPS), SEVERAL REMOTE POWER
SUPPLIES, AND AUDIO AMPLIFIERS CONNECTED VIA A COPPER NETWORK.
THE BASIS OF DESIGN INCLUDES REPLACEMENT OF THE EXISTING FACPS WITH NEW
ADDRESSABLE FIRE ALARM CONTROL UNITS ON A ONE-FOR-ONE BASIS. THE EXISTING
COPPER NETWORK WILL BE FULLY REPLACED WITH FIBER AND NEW NETWORK
INTERFACE CARDS WILL BE PROVIDED AT EACH NETWORK NODE (FACPS AND AUDIO
AMPLIFIER NODES) TO ENSURE RELIABLE SYSTEM COMMUNICATION. EXISTING
INITIATING DEVICES, NOTIFICATION APPLIANCES, AND FIELD WIRING WILL BE REUSED TO
THE MAXIMUM EXTENT PRACTICABLE.
THE INSTALLING CONTRACTOR SHALL VERIFY VOLTAGE DROP, BATTERY CAPACITY, AND
PATHWAY SURVIVABILITY IN ACCORDANCE WITH NFPA 72. ADDITIONAL REMOTE POWER
SUPPLIES, AMPLIFIERS, OR BATTERIES SHALL BE PROVIDED AS REQUIRED TO MEET
MINIMUM STANDBY AND ALARM DURATION REQUIREMENTS.
THE SCOPE OF WORK IS LIMITED TO SYSTEM REPLACEMENT AND COMMUNICATION
RELIABILITY IMPROVEMENTS; INTELLIGIBILITY TESTING AND SOUND PRESSURE LEVEL
MEASUREMENTS ARE NOT INCLUDED. SFC ENGINEERING DID NOT VALIDATE EXISTING
SYSTEM LAYOUT OR DEVICE PLACEMENT. THIS ENGINEERING SEAL IS LIMITED TO THE
CPU-REPLACEMENT ASPECT OF THE SYSTEM.
SYSTEM ACCEPTANCE TESTING SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 72,
INCLUDING FULL FUNCTIONAL TESTING, DOCUMENTATION, AND RECORD DRAWINGS.
B. ADD ALTERNATES:
A. ADD ALTERNATE 1: REPLACE ALL EXISTING ADDRESSABLE SMOKE AND HEAT
DETECTORS IN KIND WITH EQUIVALENT NEW ADDRESSABLE SMOKE AND HEAT
DETECTION DEVICES.
B. ADD ALTERNATE 2: PREPLACE EXISTING DIALER WITH KELTRON LS NET9000
TRANSCEIVER. PROVIDE ALL REQUIRED CONNECTIONS TO FACP (SERIAL AND DRY
CONTACTS, AS APPLICABLE), ONE (1) DATA DROP AT FACP (COORDINATE WITH
OWNER), NETWORK CONFIGURATION, AND UPS FOR COMMUNICATION EQUIPMENT.
COORDINATE PROGRAMMING, INTEGRATION, AND POINT MAPPING WITH KELTRON.
PERFORM FULL END-TO-END TESTING TO CENTRAL MONITORING STATION IN
ACCORDANCE WITH NFPA 72.
C. ADD ALTERNATE 3: PROVIDE UNIT PRICING FOR THE FOLLOWING:
a. 2A: INITIATING DEVICES THAT FAIL DURING TESTING
b. 2B: NOTIFICATION APPLIANCES THAT FAIL DURING TESTING
c. 2C: ADDITIONAL NAC BOOSTERS, IF REQUIRED DUE TO CALCULATIONS
d. 2D: NAC BOOSTER BATTERIES REQUIRING REPLACEMENT
C. THE NEW FIRE ALARM SYSTEM WILL BE INSTALLED IN ACCORDANCE WITH THE
FOLLOWING CODES AND STANDARDS:
A. NFPA 101 - 2021 EDITION
B. NFPA 1 - 2021 EDITION
C. IBC - 2021 EDITION
D. NFPA 72 - 2019 EDITION
E. NFPA 70 - 2020 EDITION
REFERENCE THE FIRE ALARM RISER DIAGRAM FOR A DETAILED DESCRIPTION OF THE NEW
FIRE ALARM SYSTEM.
WEATHER PROOF SPEAKER / STROBE
BRIGHTNESS
WATTAGE
WP
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
12" = 1'-0"
/2
/2
1:
3:
A M
FA-001
FIRE ALARM LEGEND AND
NOTES
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM SHEET LIST
NUMBER NAME
FA-001 FIRE ALARM LEGEND AND NOTES
FA-100 FIRE ALARM DEMO BASEMENT PLAN
FA-101 FIRE ALARM DEMO LEVEL 1 PLAN
FA-101A FIRE ALARM DEMO LEVEL 1 PART PLANS
FA-102 FIRE ALARM DEMO LEVEL 2 PLAN
FA-102A FIRE ALARM DEMO LEVEL 2 PART PLANS
FA-103 FIRE ALARM DEMO LEVEL 3 PLAN
FA-103A FIRE ALARM DEMO LEVEL 3 PART PLAN
FA-104 FIRE ALARM DEMO LEVEL 4 PLAN
FA-201 FIRE ALARM LEVEL 1 PLAN
FA-201A FIRE ALARM - PART PLANS - LEVEL 1
FA-202 FIRE ALARM LEVEL 2 PLAN
FA-202A FIRE ALARM - PART PLANS - LEVEL 2
FA-203 FIRE ALARM LEVEL 3 PLAN
FA-203A FIRE ALARM - PART PLANS - LEVEL 3
FA-900 FIRE ALARM RISER DIAGRAM
FA-901 FIRE ALARM DETAILS AND MATRIX
No. Description Date
03/03/2026
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
UNEXCAVATED
ACCESS FROM
ROOM CORRIDOR
W100CRF ABOVE
SB10A
SB10
SB00STA
SB00CRA
SB03SB04
SB02
SB00ESA
SB25
WB36
UNEXCAVATED
UP
NIC
NIC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/16" = 1'-0"
/2
/2
1:
3:
A M
FA-100
FIRE ALARM DEMO
BASEMENT PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM GENERAL NOTES
1. NO FIRE ALARM CONTROL EQUIPMENT (E.G., FACP, BOOSTER
PANELS, AMPLIFIERS, ETC.) IS LOCATED IN THE BASEMENT. THIS
PLAN IS PROVIDED FOR OVERALL BUILDING CONTEXT AND
COORDINATION ONLY
F A
C P
N A
C
F A
C P
F A
C P
IN
C
C
IN
X
IN
X
IN
X
IN
X
N100CRH
N100LBB
N100STE
N100STF
N100VSD
N100VSE
N101
N101A
N104 N110
N111
N111A
N111B
N111CN111D
N113
N116
N118
N121
N124
N124A
N124B
N124C
N129
N130
N130A
N133
N134
N137
N138 N140
N141
N142
S100CRA
S100CRB
S100CRC
S100CRJ
S100ESA
S100LBA
S100STAS100STB
S100VSA
S100VSB
S101 S103
S105 S106
S107
S108
S109 S109A
S111 S113S115
S120
S120A
S120B
S123
S124
S124A
S124B S124C
S124CA
S124CB
S125
S130
S132
S136
S138
S140
S142
S145
S145A
S145B
S161
S161A
S162
S166
S166A
S168
S171
S172
S173
S174
S175S175A
S178
W100CRD
W100CRE
W100CRF
W100CRG
W100ESB
W100ESC
W100STC
W100VSC
W101
W101A
W105
W107
W108
W110
W111
W113
W114
W115
W117
W119
W121
W123 W124 W126
W131 W132
W133
W135
W136
W137
W138
W139
W141
W142
W159
W161
W163
W165
W167
W171
W173
W175
W177
W181
W183
W183A W183B
W183C
W189
W190
MORSE
200CRZ
DN
UP
UP
DN
UP
DN
UP
DN
UP
UP
IN
XIN
X
N A
C N
A C
N A
C N
A C
NAC
FA
A
F A
A
FA-101A
FA-101A
FA-101A
NIC
NIC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/16" = 1'-0"
/2
/2
1:
3:
A M
FA-101
FIRE ALARM DEMO LEVEL 1
PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM GENERAL NOTES
1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS
OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO
THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA
WHERE WORK IS OCCURRING.
F
C P
N A
C
IN
C
C
IN
X
IN
X
S100CRC
S100STB
S130
S132
S136
S138
S140
S142
N A
C N
A C
N A
C N
A C
F A
C P
W100CRD
W121
W123 W124 W126
IN
X
IN
X
F A
C P
IN
X
IN
X
N116
N118
N124
N124A
N124B
N124C
NAC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/4" = 1'-0"
/2
/2
1:
4:
A M
FA-101A
FIRE ALARM DEMO LEVEL 1
PART PLANS
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
1/4" = 1'-0"
Fire Alarm - Level 1 Demo - Part Plan- Building A
1/4" = 1'-0"
Fire Alarm - Level 1 Demo - Part Plan - Building B
1/4" = 1'-0"
Fire Alarm - Level 1 Demo - Part Plan - Building C
KEYNOTES
1 REPLACE THE EXISTING 7100 FACP WITH NEW S3 FIRE ALARM
CONTROL UNITS.TURN OVER EXISTING CPU TO UNH.
2 REPLACE THE EXISTING E3 FACU 1ST GENERATION ILI-MB-E3
MODULE WITH THE 2ND GENERATION ILI-MB-E3 MODULE. TURN
OVER EXISTING CPU TO UNH.
3 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS
SETS 1 – 5 SERVING BUILDING A
4 EXISTING INX VOICE AMPLIFIER PANELS (NODES 3 AND 4) SERVING
SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS B AND E.
REPLACE THE EXISTING SECOND-GENERATION INI-VGX MODULES
WITH THIRD-GENERATION INI-VGX MODULES.
5 EXISTING INX VOICE AMPLIFIER PANELS (NODES 9 AND 10) SERVING
SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS C AND D.
REPLACE THE EXISTING SECOND-GENERATION INI-VGX MODULES
WITH THIRD-GENERATION INI-VGX MODULE.
6 EXISTING INX VOICE AMPLIFIER PANELS (NODES 3 AND 4) SERVING
SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS A. REPLACE THE
EXISTING SECOND-GENERATION INI-VGX MODULES WITH
THIRD-GENERATION INI-VGX MODULES.
7 EXISTING INCC PANEL WITH MICROPHONE HANDSET SERVING THE
ENTIRE SPEAKER NOTIFICATION SYSTEM. REPLACE THE EXISTING
SECOND-GENERATION INI-VGC MODULE WITH THIRD-GENERATION
INI-VGC MODULE.
8 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS
SETS - 1 SERVING BUILDING C AND D
N200CRDN200LBB
N200STE
N200STF
N200ZOA
N203
N204
N207 N209
N210
N211
N212
N215
N215A N215B N215C N215D
N216 N218
N221
N221A N221B N221C
N221D
N224
N224A
N224B
N224C
N226
N229
N229A
N229B
N230
N233
N233A
N234
N235
N235A N235B
N235C
N238 N240
N241
N241A N241B
N242
S200CLA
S200CRA
S200CRE
S200ESA
S200STAS200STB
S200STH
S200STJ
S200ZOA
S200ZOB
S200ZOC
S203
S210
S211
S212
S215
S216S220
S221
S222
S223
S223A
S224
S225
S226S226A
S227
S230 S232
S234
S236
S236A S236B
S236C
S236D
S236F
S236LS236MS236NS236P
S236Q
S236T
S238
S240
S242
S245S247
S250S252S254S256
W200CRB
W200CRC
W200ESB
W200ESC
W200STC
W200STG
W201
W201A
W205
W207
W208
W211
W213
W214W215
W217
W219 W220
W220A
W220B
W221
W222
W223 W224
W226
W231
W233
W235
W236
W237
W239
W240
W241 W242
W243
W244
W247
W248
W250
W251
W253 W254
W255
W257
W283
W283A
W283B
W283C
W283D
W283E
W288
W289
W289A
W290
HATCH ACCESS
FROM ROOM S205
BELOW
UP
DN
DN
UP
UP
DN
UP
UP
DN
UP
DN
UP
UP
N A
C
NAC
N A
C N
A C
N A
C
FA-102A
FA-102A
NIC
NIC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/16" = 1'-0"
/2
/2
1:
4:
A M
FA-102
FIRE ALARM DEMO LEVEL 2
PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM GENERAL NOTES
1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS
OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO
THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA
WHERE WORK IS OCCURRING.
W220A
W221
W222
W223 W224
W226 N
A C
N A
C N
A C
N A
C
N200CRD
N218
N224
N224A
N224B
N224C
NAC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/4" = 1'-0"
/2
/2
1:
4:
A M
FA-102A
FIRE ALARM DEMO LEVEL 2
PART PLANS
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
1/4" = 1'-0"
Fire Alarm - Level 2 Demo - Part Plan - Building B
1/4" = 1'-0"
Fire Alarm - Level 2 Demo - Part Plan - Building C
KEYNOTES
1 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS
SETS 1 – 4 SERVING BUILDING B & E
2 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS
SETS 2 SERVING BUILDING C & D
N300CRD
N300LBB
N300STE
N300STF
N309
N309A
N309B N309C N309D N309E
N310 N314
N315
N315A N315B N315C N315D
N316 N318
N321
N321A N321B N321C N321D
N324
N324A
N324B
N324C
N328
N329
N330
N333
N333A
N333B N333C
N333D
N334 N338 N340
N341
N342
N343
N345
S300CRA
S300ESA
S300STAS300STB
S300STJ
S310
S311
S312
S315
S316
S319
S320
S321
S322
S323
S324
S325
S326
S332 S332A
S332B
S333S335
S336
S338
S340
S341
S342
S344
S344A
S344B
S360
S360B
W300CRB
W300CRC
W300ESB
W300ESC
W300STC
W300STG
W301
W301A
W305
W307
W308
W311
W313
W314W315
W317
W318
W319
W320
W321
W322
W323
W324
W325 W326
W331
W333
W334
W334A
W334B
W335 W336
W338
W338A
W338BW339
W341
W342 W343
W344
W345
W347
W348
W350
W351
W353 W354
W355
W381
W383
W383B
W385
W387
W388
W389
W390
ROOF
ROOF
ROOF
ROOF
ROOF
UP
DN
UP
DN
UP
DN
DN
UP
DN
UP
DN
NAC
FA-103A
NIC
NIC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/16" = 1'-0"
/2
/2
1:
4:
A M
FA-103
FIRE ALARM DEMO LEVEL 3
PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM GENERAL NOTES
1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS
OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO
THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA
WHERE WORK IS OCCURRING.
N318
N324
N324A
N324B
N324C
NAC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/4" = 1'-0"
/2
/2
1:
4:
A M
FA-103A
FIRE ALARM DEMO LEVEL 3
PART PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
1/4" = 1'-0"
Fire Alarm - Level 3 Demo - Part Plan - Building C
KEYNOTES
1 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS
SET 3 SERVING BUILDING C & D
EQ009403
(Above)
EQ009404
(Above)
EQ009405
(Above)
EQ006171
EQ006172
EQ014261
EQ014565EQ014566
EQ014233
EQ014234
EQ014235
EQ014236
EQ014260
EQ004057
EQ014228
EQ006167 EQ006166
EQ011799
(Above)
EQ014229EQ014227
EQ014538EQ014541
EQ014239
EQ014238
EQ014237
EQ006168
EQ006169
EQ006170
EQ014540
EQ014542
EQ014262
EQ014539
EQ014537
EQ005759
EQ014331
EQ014529
ELEV C
OVERIDE
DUCT
ENCLOSURE
DUCT
ENCLOSURE
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
1,778sf
5,027sf
187sf
3,133sf
239sf
408sf
131sf
1,111sf
7,057sf
556sf
237sf
426sf
102sf
201sf
53sf
132sf
W410
N410
N400STF
N400ZOA
N400ZOB
S400STB
W400STC
W400
S410
S400CRA
S400STA
S401
S400ESA
S403
S402
N400ZOC
W410
N410
N400STF
N400ZOA
N400ZOB
S400STB
W400STC
W400
S410
S400CRA
S400STA
S401
S400ESA
S403
S402
N400ZOC
DNDN
DNDN
DN
DN
NIC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/16" = 1'-0"
/2
/2
1:
4:
A M
FA-104
FIRE ALARM DEMO LEVEL 4
PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM GENERAL NOTES
1. NO FIRE ALARM CONTROL EQUIPMENT (E.G., FACP, BOOSTER
PANELS, AMPLIFIERS, ETC.) IS LOCATED IN THE BASEMENT. THIS
PLAN IS PROVIDED FOR OVERALL BUILDING CONTEXT AND
COORDINATION ONLY
N
C
N100CRH
N100LBB
N100STE
N100STF
N100VSD
N100VSE
N101
N101A
N104 N110
N111
N111A
N111B
N111CN111D
N113
N116
N118
N121
N124
N124A
N124B
N124C
N129
N130
N130A
N133
N134
N137
N138 N140
N141
N142
S100CRA
S100CRB
S100CRC
S100CRJ
S100ESA
S100LBA
S100STAS100STB
S100VSA
S100VSB
S101 S103
S105 S106
S107
S108
S109 S109A
S111 S113S115
S120
S120A
S120B
S123
S124
S124A
S124B S124C
S124CA
S124CB
S125
S130
S132
S136
S138
S140
S142
S145
S145A
S145B
S161
S161A
S162
S166
S166A
S168
S171
S172
S173
S174
S175S175A
S178
W100CRD
W100CRE
W100CRF
W100CRG
W100ESB
W100ESC
W100STC
W100VSC
W101
W101A
W105
W107
W108
W110
W111
W113
W114
W115
W117
W119
W121
W123 W124 W126
W131 W132
W133
W135
W136
W137
W138
W139
W141
W142
W159
W161
W163
W165
W167
W171
W173
W175
W177
W181
W183
W183A W183B
W183C
W189
W190
MORSE
200CRZ
DN
UP
UP
DN
UP
DN
UP
DN
UP
UP
N A
C N
A C
N A
C N
A C
NAC
F A
C P
F A
C P
F A
C P
IN
C
C
IN
X
IN
X
IN
XIN
X
IN
X
IN
X
S
S
S
S
FA
A
F A
A
FA-201A
FA-201A
FA-201A
NIC
NIC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/16" = 1'-0"
/2
/2
1:
4:
A M
FA-201
FIRE ALARM LEVEL 1 PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM GENERAL NOTES
1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS
OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO
THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA
WHERE WORK IS OCCURRING.
N
C
S100CRC
S100STB
S130
S132
S136
S138
S140
S142
N A
C N
A C
N A
C N
A C
F A
C P
IN
C
C
IN
X
IN
X
S
S
W100CRD
W121
W123 W124 W126F
A C
P
IN
X
IN
X
S
N116
N118
N124
N124A
N124B
N124C
NAC
F A
C P
IN
X
IN
X
S
K
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/4" = 1'-0"
/2
/2
1:
4:
A M
FA-201A
FIRE ALARM - PART PLANS
- LEVEL 1
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
1/4" = 1'-0" 1 Fire Alarm - Level 1 - Part Plan- Building A
1/4" = 1'-0" 2 Fire Alarm - Level 1 - Part Plan - Building B
1/4" = 1'-0" 3 Fire Alarm - Level 1 - Part Plan - Building C
KEYNOTES
1 PROVIDE A NEW S3 FIRE ALARM CONTROL PANEL. PROVIDE THE
FSL-E3 FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC
NETWORK. CONTRACTOR SHALL OWN REPROGRAMMING AND
REWIRING TO FACILITATE THE UPGRADE OF THE FIRE ALARM
CONTROL PANEL.
2 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS
SETS 1 – 5 SERVING BUILDING A
3 EXISTING INX VOICE AMPLIFIER PANELS (NODES 3 AND 4) SERVING
SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS B AND E.
PROVIDE WITH NEW 3RD GENERATION INI-VGX MODULE. PROVIDE
THE FSL-E3 FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC
NETWORK.
4 EXISTING INX VOICE AMPLIFIER PANELS (NODES 9 AND 10) SERVING
SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS C AND D.
PROVIDE WITH NEW 3RD GENERATION INI-VGX MODULE. PROVIDE
THE FSL-E3 FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC
NETWORK.
5 EXISTING INX VOICE AMPLIFIER PANELS (NODES 3 AND 4) SERVING
SPEAKER NOTIFICATION APPLIANCES IN BUILDINGS A. PROVIDE
WITH NEW 3RD GENERATION INI-VGX MODULE. PROVIDE THE FSL-E3
FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC NETWORK.
6 EXISTING INCC PANEL WITH MICROPHONE HANDSET SERVING THE
ENTIRE SPEAKER NOTIFICATION SYSTEM. PROVIDE WITH 3RD
GENERATION INI-VGC MODULE. PROVIDE THE FSL-E3 FIBER MODULE
TO CONNECT TO THE NEW FIBER OPTIC NETWORK.
7 EXISTING TO REMAIN NOTIFICATION APPLIANCE BOOSTER PANELS
SETS - 1 SERVING BUILDING C AND D
8 FOR THE EXISTING E3 FACU, PROVIDE AND INSTALL NEW
SECOND-GENERATION COMMUNICATION MODULES, INCLUDING
ILI-MB-E3, RPT-E3-UTP, AND FSL-E3 FIBER MODULES. CONTRACTOR
SHALL OWN REPROGRAMMING AND REWIRING TO FACILITATE THE
UPGRADE OF THE FIRE ALARM CONTROL PANEL.
9 ADD ALTERNATE NO. 2 - REPLACE EXISTING DIALER WITH KELTRON
LS NET9000 TRANSCEIVER. PROVIDE ALL REQUIRED CONNECTIONS
TO FACP (SERIAL AND DRY CONTACTS, AS APPLICABLE), ONE (1)
DATA DROP AT FACP (COORDINATE WITH OWNER), NETWORK
CONFIGURATION, AND UPS FOR COMMUNICATION EQUIPMENT.
COORDINATE PROGRAMMING, INTEGRATION, AND POINT MAPPING
WITH KELTRON. PERFORM FULL END-TO-END TESTING TO CENTRAL
MONITORING STATION IN ACCORDANCE WITH NFPA 72.
N200CRDN200LBB
N200STE
N200STF
N200ZOA
N203
N204
N207 N209
N210
N211
N212
N215
N215A N215B N215C N215D
N216 N218
N221
N221A N221B N221C
N221D
N224
N224A
N224B
N224C
N226
N229
N229A
N229B
N230
N233
N233A
N234
N235
N235A N235B
N235C
N238 N240
N241
N241A N241B
N242
S200CLA
S200CRA
S200CRE
S200ESA
S200STAS200STB
S200STH
S200STJ
S200ZOA
S200ZOB
S200ZOC
S203
S210
S211
S212
S215
S216S220
S221
S222
S223
S223A
S224
S225
S226S226A
S227
S230 S232
S234
S236
S236A S236B
S236C
S236D
S236F
S236LS236MS236NS236P
S236Q
S236T
S238
S240
S242
S245S247
S250S252S254S256
W200CRB
W200CRC
W200ESB
W200ESC
W200STC
W200STG
W201
W201A
W205
W207
W208
W211
W213
W214W215
W217
W219 W220
W220A
W220B
W221
W222
W223 W224
W226
W231
W233
W235
W236
W237
W239
W240
W241 W242
W243
W244
W247
W248
W250
W251
W253 W254
W255
W257
W283
W283A
W283B
W283C
W283D
W283E
W288
W289
W289A
W290
HATCH ACCESS
FROM ROOM S205
BELOW
UP
DN
DN
UP
UP
DN
UP
UP
DN
UP
DN
UP
UP
N A
C
NAC
N A
C N
A C
N A
C
S
S
FA-202A
FA-202A
NIC
NIC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/16" = 1'-0"
/2
/2
1:
4:
A M
FA-202
FIRE ALARM LEVEL 2 PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM GENERAL NOTES
1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS
OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO
THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA
WHERE WORK IS OCCURRING.
W220A
W221
W222
W223 W224
W226
N A
C N
A C
N A
C N
A C
S
N200CRD
N218
N224
N224A
N224B
N224C
NAC
S
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/4" = 1'-0"
/2
/2
1:
4:
A M
FA-202A
FIRE ALARM - PART PLANS
- LEVEL 2
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
1/4" = 1'-0" 2 Fire Alarm - Level 2 - Part Plan - Building B
1/4" = 1'-0" 3 Fire Alarm - Level 2 - Part Plan - Building C
KEYNOTES
1 EXISTING NOTIFICATION APPLIANCE BOOSTER PANELS SETS 1 – 4
SERVING BUILDING B & E
2 EXISTING NOTIFICATION APPLIANCE BOOSTER PANELS SETS 2
SERVING BUILDING C & D
N300CRD
N300LBB
N300STE
N300STF
N309
N309A
N309B N309C N309D N309E
N310 N314
N315
N315A N315B N315C N315D
N316 N318
N321
N321A N321B N321C N321D
N324
N324A
N324B
N324C
N328
N329
N330
N333
N333A
N333B N333C
N333D
N334 N338 N340
N341
N342
N343
N345
S300CRA
S300ESA
S300STAS300STB
S300STJ
S310
S311
S312
S315
S316
S319
S320
S321
S322
S323
S324
S325
S326
S332 S332A
S332B
S333S335
S336
S338
S340
S341
S342
S344
S344A
S344B
S360
S360B
W300CRB
W300CRC
W300ESB
W300ESC
W300STC
W300STG
W301
W301A
W305
W307
W308
W311
W313
W314W315
W317
W318
W319
W320
W321
W322
W323
W324
W325 W326
W331
W333
W334
W334A
W334B
W335 W336
W338
W338A
W338BW339
W341
W342 W343
W344
W345
W347
W348
W350
W351
W353 W354
W355
W381
W383
W383B
W385
W387
W388
W389
W390
ROOF
ROOF
ROOF
ROOF
ROOF
UP
DN
UP
DN
UP
DN
DN
UP
DN
UP
DN
NAC
S
FA-203A
NIC
NIC
NIC
NIC
NIC
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/16" = 1'-0"
/2
/2
1:
4:
A M
FA-203
FIRE ALARM LEVEL 3 PLAN
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
FIRE ALARM GENERAL NOTES
1. THIS OVERALL FLOOR PLAN INDICATES THE GENERAL LOCATIONS
OF FIRE ALARM CONTROL EQUIPMENT TO BE REPLACED. REFER TO
THE SHEET CALLOUTS FOR DETAILED LAYOUTS OF EACH AREA
WHERE WORK IS OCCURRING.
N318
N324
N324A
N324B
N324C
NAC
S
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
1/4" = 1'-0"
/2
/2
1:
4:
A M
FA-203A
FIRE ALARM - PART PLANS
- LEVEL 3
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
1/4" = 1'-0" 3 Fire Alarm - Level 3 - Part Plan - Building C
KEYNOTES
1 EXISTING NOTIFICATION APPLIANCE BOOSTER PANELS SET 3
SERVING BUILDING C & D
(E) E3 SERIES
FACP
NODE #1
120 VAC
(E) INX AUDIO
PANEL
NODE #3
120 VAC
(E) INX AUDIO
PANEL
NODE #4
120 VAC
(E) INCC FCC
PANEL WITH
MICROPHONE
120 VAC
NEW S3 FACP
NODE #5
120 VAC
(E) INX AUDIO
PANEL
NODE #6
120 VAC
NEW S3 FACP
NODE #8
120 VAC
(E) INX AUDIO
PANEL
NODE #9
120 VAC
LEVEL 1
LEVEL 2
LEVEL 3
LEVEL 4
(E) NAC
BOOSTER
PANEL
120 VAC
(E) INX AUDIO
PANEL
NODE #7
120 VAC
(E) INX AUDIO
PANEL
NODE #10
120 VAC
TOTAL OF (5) NAC
BOOSTER PANELS
LOCATED IN RM S130
NEW FIBER OPTIC
NETWORK CIRCUIT
NEW FIBER OPTIC
NETWORK CIRCUIT
(E) NAC
BOOSTER
PANEL
120 VAC
TOTAL OF (1) NAC BOOSTER
PANELS LOCATED IN RM
N124A
(E) NAC
BOOSTER
PANEL
120 VAC
TOTAL OF (1) NAC
BOOSTER PANELS
LOCATED IN RM N224A
(E) NAC
BOOSTER
PANEL
120 VAC
TOTAL OF (1) NAC BOOSTER
PANELS LOCATED IN RM
N324A
(E) NAC
BOOSTER
PANEL
120 VAC
TOTAL OF (4) NAC
BOOSTER PANELS
LOCATED IN RM W224
BUILDING A BUILDING B BUILDING C
1. THE INTENT OF THIS RISER DIAGRAM IS TO ILLUSTRATE THE GENERAL DESIGN INTENT OF THE FIRE ALARM SYSTEM. IT IS NOT
INTENDED TO DEPICT ALL DEVICES, MODULES, OR WIRING.
EXISTING SYSTEM DESCRIPTION:
• THE BUILDING IS CURRENTLY SERVED BY THREE NETWORKED FIRE ALARM CONTROL PANELS (FACPS). THESE PANELS INCLUDE AN FCI E3 SERIES PANEL LOCATED IN THE FIRE ALARM COMMAND CENTER (ROOM S142), AN FCI 7100 PANEL IN ELECTRICAL ROOM N124A, AND ANOTHER FCI 7100 PANEL IN ELECTRICAL ROOM W124. THE THREE FACPS ARE INTERCONNECTED THROUGH AN RPT-
E3-UTP NETWORK REPEATER CARD USING CLASS A, 14 AWG TWISTED, NON-SHIELDED WIRING.
• CURRENTLY THERE IS A NETWORKING ISSUE BETWEEN THE FACPS. WHEN ONE PANEL GOES INTO ALARM, THE OTHER PANELS DO NOT ACTIVATE OR INITIATE THE BUILDING’S NOTIFICATION APPLIANCES. THIS ISSUE IS THE MAIN REASON THAT A SYSTEM UPGRADE IS BEING PROPOSED. THE 7100 SERIES PANELS ARE ALSO DISCONTINUED, WHICH ADDS TO THE NEED FOR REPLACEMENT. BASED ON THE EXISTING TEST REPORTS, THE NETWORK COMMUNICATION ISSUE APPEARS TO BE THE ONLY ONGOING PROBLEM WITH
THE KINGSBURY HALL FIRE ALARM SYSTEM.
FIRE ALARM CONTROL UNIT AND POWER SUPPLIES:
• KINGSBURY HALL WILL BE SERVED BY A NEW CPU BACKBONE CONSISTING OF THREE NEW NETWORKED ADDRESSABLE FIRE ALARM CONTROL PANELS. THE BASIS OF DESIGN IS THE GAMEWELL-FCI S3 SERIES FIRE ALARM CONTROL UNIT. THE S3 SERIES FACP’S ARE INTENDED TO BE THE DIRECT UPGRADE FOR THE OLDER 7100 FACP’S. THREE NEW S3 FACPS WILL BE PROVIDED TO REPLACE THE EXISTING 7100 FACP’S AND E3 FACP ON A ONE-FOR-ONE BASIS. THE INTENT OF THE UPGRADE IS TO REPLACE THE EXISTING CPUS AND UPGRADE THE SYSTEM WHILE REUSING THE EXISTING WIRING, INITIATING DEVICES, AND NOTIFICATION
APPLIANCES TO THE MAXIMUM EXTENT PRACTICAL.
• THE NEW S3 FACPS WILL BE LOCATED IN THE FOLLOWING ROOMS:
1. FIRE ALARM COMMAND CENTER ROOM S142
2. ELECTRICAL ROOM N124A
3. ELECTRICAL ROOM W124
• EXISTING REMOTE POWER SUPPLIES AND AMPLIFIERS SHOULD BE REUSED WHERE POSSIBLE. THE CONTRACTOR MUST PERFORM VOLTAGE DROP CALCULATIONS ON THE EXISTING CIRCUITS TO CONFIRM THAT THE REMOTE POWER SUPPLIES ARE WITHIN THE ALLOWABLE VOLTAGE DROP LIMITS. NEW REMOTE POWER SUPPLIES AND AMPLIFIERS MUST BE ADDED AS NEEDED BASED ON THE RESULTS OF THE VOLTAGE DROP AND BATTERY CAPACITY CALCULATIONS PERFORMED BY THE CONTRACTOR.
• A SMOKE DETECTOR SHALL BE INSTALLED IN THE VICINITY OF EACH FIRE ALARM CONTROL UNIT, REMOTE POWER SUPPLY, AND
AMPLIFIER IN ACCORDANCE WITH NFPA 72.
• EACH FACP, REMOTE POWER SUPPLY, AND AUDIO DIGITAL AMPLIFIER SHALL HAVE A SECONDARY POWER SUPPLY CAPABLE OF OPERATING THE SYSTEM FOR A MINIMUM OF 24 HOURS IN STANDBY AND 15 MINUTES IN ALARM. THE INSTALLING CONTRACTOR SHALL VERIFY THE ADEQUACY OF THE EXISTING BATTERY CAPACITY THROUGH BATTERY CALCULATIONS. NEW BATTERIES SHALL BE PROVIDED AS NECESSARY TO ENSURE COMPLIANCE WITH THE REQUIRED MINIMUM OPERATING DURATIONS.
FIRE ALARM RISER DIAGRAM GENERAL NOTES
C
BUILDING E BUILDING D
SLC
LOOP #1
SLC LOOP #2
SLC
LOOP #1
SLC LOOP #2
SLC
LOOP #1
FIRE ALARM RISER LEGEND
= EXISTING SIGNILING LINE CIRCUIT (SLC)
= EXISTING SPEAKER CIRCUIT
= EXISTING VISUAL CIRCUIT
= NEW FIBER OPTIC NETWORK CIRCUIT
333444444 444 444 444 444
NOTIFICATION:
• AN IN-BUILDING EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM (EVACS) IS CURRENTLY INSTALLED THROUGHOUT KINGSBURY HALL. THE INTENT OF THIS PROJECT IS TO RETAIN THE EXISTING NOTIFICATION APPLIANCES AND TO CONTINUE UTILIZING THE EXISTING AMPLIFIERS AND REMOTE POWER SUPPLIES TO SERVE THE EXISTING NOTIFICATION APPLIANCES. SFC ENGINEERING DID NOT VALIDATE EXISTING SYSTEM LAYOUT OR DEVICE PLACEMENT. THIS ENGINEERING
SEAL IS LIMITED TO THE CPU-REPLACEMENT ASPECT OF THE SYSTEM.
• INTELLIGIBILITY AND SOUND PRESSURE LEVEL MEASUREMENTS WERE NOT EVALUATED AS PART OF THIS ENGINEERING EFFORT. SINCE THE PRIMARY ISSUE IDENTIFIED INVOLVES COMMUNICATION BETWEEN NETWORKED NODES, THE PROPOSED UPGRADE FOCUSES ON RESOLVING THIS ISSUE AND MAINTAINING
PROPER OPERATION OF THE EXISTING NOTIFICATION SYSTEM.
• AN EXISTING MICROPHONE HANDSET IS PROVIDED AT THE FIRE COMMAND CENTER. THE INX AUDIO AMPLIFIER NODES ARE NETWORKED WITH THE FACU'S VIA A CLASS A, 14 AWG TWISTED, NON-SHIELDED PAIR. AS PART OF THIS PROJECT, THE EXISTING CLASS A, 14 AWG TWISTED UNSHIELDED COPPER NETWORK WIRING SHALL BE REPLACED WITH A CLASS A SINGLE-MODE FIBER OPTIC NETWORK. PROVIDE AND REPLACE ALL REQUIRED NETWORK INTERFACE CARDS, FIBER MODULES, AND ASSOCIATED HARDWARE NECESSARY TO SUPPORT THE NEW FIBER NETWORK. THE INX AUDIO AMPLIFIER NODES ARE LOCATED IN THE
FOLLOWING ROOMS:
1. FIRE ALARM COMMAND CENTER ROOM S142
2. ELECTRICAL ROOM N124A
3. ELECTRICAL ROOM W124
PATHWAY SURVIVIBILITY:
• FIBER OPTIC NETWORK CABLE - LEVEL 1
• NOTIFICIATION APPLIANCE CIRCUIT (NAC) - LEVEL 1
• SPEAKER CIRCUIT - LEVEL 1
• SIGNILING LINE CIRCUIT (SLC) - LEVEL 1
• AUXILIARY POWER - LEVEL 1
SYSTEM ACCEPTANCE:
• THE FIRE ALARM EQUIPMENT SHALL UNDERGO A 100% ACCEPTANCE TEST PERFORMED BY THE INSTALLING CONTRACTOR AND APPROVED TESTING COMPANY.
THE FIRE ALARM SYSTEM WILL BE TESTED IN ACCORDANCE WITH NFPA 72. THE FOLLOWING DOCUMENTS SHALL BE REQUIRED AT PROJECT CLOSEOUT:
1. A RECORD OF COMPLETION REPORT
2. A RECORD OF INSPECTION AND TESTING REPORT. TESTING RESULTS SHALL BE DOCUMENTED IN ACCORDANCE WITH NFPA 72.
3. AS-BUILT DRAWINGS
• CONTRACTOR SHALL INCLUDE UNIT PRICING IN THEIR BID FOR REPLACEMENT OF NOTIFICATION APPLIANCES, MODULES, AND INITIATING DEVICES IN THE EVENT
ANY DEVICE FAILS ACCEPTANCE TESTING.
BASEMENT
E
SYNC
SYNC
SYNC
SYNC
FROM NAC ON
1ST FLR
FROM SPEAKER
CKT ON 1ST FLR
SYNC
SYNC = EXISTING SYNC MODULE SERVING NAC'S
= NEW WORK
(E) FAA (E) FAA
(E) FAA = EXISTING REMOTE ANNUNCIATOR
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
12" = 1'-0"
/2
/2
1:
4:
A M
FA-900
FIRE ALARM RISER
DIAGRAM
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
KEYNOTES
1 REMOVE THE EXISTING RPT-E3-UTP NETWORK REPEATER CARD
AND ASSOCIATED CLASS A, 14 AWG TWISTED, UNSHIELDED COPPER
NETWORK WIRING INTERCONNECTING THE NODES. PROVIDE NEW
RPT-E3-UTP NETWORK REPEATER ASSEMBLIES EQUIPPED WITH
FSL-E3 SINGLE-MODE FIBER OPTIC MODULES AT EACH NETWORK
NODE. INSTALL NEW SINGLE-MODE FIBER OPTIC CABLING BETWEEN
ALL NODES TO ESTABLISH THE COMPLETE FIRE ALARM NETWORK.
COORDINATE FINAL NETWORK CONFIGURATION AND TERMINATIONS
WITH THE FIRE ALARM MANUFACTURER’S REQUIREMENTS.
2 REPLACE THE EXISTING 7100 FACU'S WITH NEW S3 FIRE ALARM
CONTROL UNITS.
3 THE CURRENT INCC COMMAND CENTER IS UTILIZING THE SECOND
GENERATION INI-VGC CARD. THE INTENT IS TO UPGRADE THE
INI-VGC CARD TO 3RD GENERATION. PROVIDE THE FSL-E3 FIBER
MODULE TO CONNECT TO THE NEW FIBER OPTIC NETWORK.
4 THE CURRENT INI-VGX CARDS ARE SECOND GENERATION. THE
INTENT IS TO UPGRADE EACH INI-VGX CARD WITH A 3RD
GENERATION MODEL DUE TO UPGRADING THE FIRE ALARM
CONTROL PANEL. EACH INI-VGX SHALL BE PROVIDED WITH THE
FSL-E3 FIBER MODULE TO CONNECT TO THE NEW FIBER OPTIC
NETWORK.
5 FOR THE EXISTING E3 FACU, PROVIDE AND INSTALL NEW
SECOND-GENERATION COMMUNICATION MODULES, INCLUDING
ILI-MB-E3, RPT-E3-UTP, AND FSL-E3 FIBER MODULES.
No. Description Date
CLASS X
CLASS X
SUPPLY DIFFUSER
3 FEET MIN
MOUNT AT 66" AFF
TO TOP OF
ENCLOSURE MOUNT AT 60"
AFF. TO TOP OF
ENCLOSURE
CEILING MOUNTED SMOKE /
HEAT DETECTOR
WALL MOUNTED SMOKE /
HEAT DETECTOR
FINISHED FLOOR
4"
M A
X
5' MAX
SYCHRONIZE MORE THAN
TWO VISUAL APPLIANCES IN
ANY FIELD OF VIEW
4"
DO NOT MOUNT
DEVICE HERE
FACU
1. IN NON-SLEEPING AREAS WALL MOUNT VISIBLE
NOTIFICATION APPLIANCES SHALL BE INSTALLED
SUCH THAT THE ENTIRE LENS IS NOT LESS THAN
80 INCHES AND NOT GREATER THAN 90 INCHES
ABOVE THE FINISHED FLOOR. WHERE LOW
CEILING HEIGHTS DO NOT PERMIT MOUNTING AT A
MINIMUM OF 80 INCHES,VISIBLE APPLIANCES
SHALL BE MOUNTED WITHIN 6 INCHES OF THE
CEILING.
2. WALL-MOUNTED AUDIBLE APPLIANCE SHALL HAVE
THEIR TOPS NOT LESS THAN 90 IN. ABOVE THE
FLOOR AND NOT LESS THAN 6 IN. BELOW THE
CEILING.
FAA
PULL DOWN
FIRE ALARM
REMOTE
INDICATOR LIGHT
Scale
Date
Drawn By
Checked By
Project Number
SFC ENGINEERING
183 Rockingham Rd Unit 3 East, Windham, NH 03087 603-647-8700
NOT FOR CONSTRUCTION
NTS
/2
/2
1:
4:
A M
FA-901
FIRE ALARM DETAILS AND
MATRIX
UNIVERSITY OF NEW
HAMPSHIRE
KINGSBURY HALL FIRE
ALARM UPGRADE
SJS
ARC
03/04/2026
670070
NTS
FIRE ALARM DEVICE MOUNTING
ELEVATIONS
File details come from the government source that posted it. Updated .