This solicitation is for a Building 5 Pharmacy Cleanroom Installation project located at the W. G. Hefner VAMC in Salisbury, North Carolina. The Department of Veterans Affairs requires a contractor to provide all labor, material, equipment and supervision to construct a pre-manufactured ISO class 7 cleanroom and separate compounding areas in accordance with USP chapters 797 and 800 for non-hazardous and hazardous sterile compounding. A site visit will take place on February 9th and questions are due by February 18th. Bids for this 100% SDVOSB set-aside are due on March 4th and will be publicly opened virtually on March 10th. The construction cost is estimated between $500,000 and $1 million. The NAICS code is 236220 for commercial and institutional building construction with a size standard of $39.5 million.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
NOTE:
WIRE SIZE FOR ALL 277V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 170 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 280 FT
AND GREATER THAN OR EQUAL TO 170 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 440 FT
AND GREATER THAN OR EQUAL TO 280 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 700 FT
AND GREATER THAN OR EQUAL TO 440 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
WIRE SIZE FOR ALL 120V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 75 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 125 FT
AND GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 190 FT
AND GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 300 FT
AND GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
EXISTING EQUIPMENT
NEW OR RELOCATED EQUIPMENT
HATCH INDICATES EQUIPMENT TO BE DEMOLISHED
ELECTRICAL GENERAL NOTES:
1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:
A. NFPA 70-2020 (NATIONAL ELECTRICAL CODE)
B. ANSI C2-2017 (NATIONAL ELECTRICAL SAFETY CODE)
C. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.
D. PG-18-10 VA ELECTRICAL DESIGN MANUAL
2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS
REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL.
3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER
TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE
RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL
EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND CORRECT
ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG
NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL DESCRIPTIONS
INDICATED.
5. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON
ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND
ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE
BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO
BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE
COUNTERTOP.
6. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE
ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION SHALL
BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL HAVE ONE
COMMON FACE PLATE.
7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED
GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS
SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT
AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL
CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN
ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
8. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR LOCATIONS
WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS
AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY EXACT LOCATIONS OF
MOTORS AND EQUIPMENT BEFORE ROUGHING-IN.
9. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS
INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER,
LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED,
DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR
REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND
SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE
DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE
RESTORED TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE
RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE
REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED SHALL BE
INCLUDED IN THE CONTRACT AND NO EXTRA COMPENSATION WILL BE
GRANTED.
10. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM
MANNER, SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST
EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS
SHOWN IN NEW WORK AT VARIANCE FROM THE EXISTING SHALL BE
REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.
11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR
CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
12. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE
WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO
STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER
EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO
MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE
DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
13. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE
WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE
CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS,
REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE
WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF
DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.
14. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS
ALUMINUM.
15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,
DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY MATERIALS
AND DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.
16. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT
SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE
SOURCE PANEL & CIRCUIT(S). TEXT SHALL BE BLACK, 1/8” IN HEIGHT
PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED
EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH
CAN BE HANDWRITTEN WITH AN INDELIBLE MARKER.
17. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL
EXTEND 2 ” BEYOND THE FOOTPRINT OF THE EQUIPMENT.
18. EMT SHALL COMPLY WITH ANSI C80.3 AND UL 797. ALL EMT SHALL BE
FACTORY PAINTED.
19. ALL JUNCTION BOXES, ELECTRICAL DEVICES, AND FACEPLATES SHALL BE
SEALED FOR AIR LEAKAGE USING APPROVED SEALANT.
ELECTRICAL ABBREVIATIONS
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CHILLER
CHILLED WATER PUMP
CIRCUIT
COMMUNICATIONS MANHOLE
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT TRACKING
HEATING/VENTILATING UNIT
HWRP
HWSP
HWUH
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NL
NO
NTS
P
PA
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
XFMR
Z
HOT WATER RECIRCULATION PUMP
HOT WATER UNIT HEATER
HERTZ
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
TRANSFORMER
IMPEDANCE
1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS
PROJECT.
2. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.
ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,
DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT
IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF
EACH:
TELECOMMUNICATIONS MAIN GROUNDING
BUSBAR
VAV TERMINAL UNIT WITH PARALLEL OR
SERIES FAN (PRIMARY INDUCTION UNIT)
NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
HEATING WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CHILLED WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
CHILLED WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
DUCTLESS SPLIT CONDENSING UNIT (POWERS
THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE
DSS INDOOR UNIT)
GOVERNMENT FURNISHED GOVERNMENT
INSTALLED
HEAT PUMP (OUTDOOR PORTION OF SPLIT
SYSTEM HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR UNIT)
HEATING WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY
SYSTEM
FFU FAN FILTER UNIT
LED LIGHT EMITTING DIODE
POE POWER OVER ETHERNET
IES ILLUMINATING ENGINEERING SOCIETY
WAP WIRELESS ACCESS POINT
ES ELECTRONIC STRIKE
CR CARD READER
AV AUDIO/VISUAL
TV TELEVISION
T-STAT THERMOSTAT
PB PANIC BUTTON
E-001A
2 DIGIT DISCIPLINE
DESIGNATOR
G GENERAL
A ARCHITECTURAL
S STRUCTURAL
F FIRE PROTECTION
E ELECTRICAL
ED ELECTRICAL DEMOLITION
M MECHANICAL
MD MECHANICAL DEMOLITION
MH MECHANICAL HVAC
P PLUMBING
1 DIGIT SHEET TYPE
DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT SEQUENTIAL # (01-99)
1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR
ONLY USED WHEN
PLANS ARE SUBDIVIDED
INTO AREAS.)
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
E-001
GENERAL ELECTRICAL
NOTES AND ABBREVIATIONS1
1/2
B
W
SB
M
M
2/60/40/1
60/40/3/3R
40/3/3RCB
T
M
EM
J J
PB
G
G4
A
AE
M
X X
C
D a b
LUMINAIRES
LUMINAIRE AND OUTLET BOX. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
LUMINAIRE AND OUTLET BOX WIRED FOR
MULTILEVEL SWITCHING, LOWER CASE LETTER
INDICATES SWITCHLEG DESTINATION.
LUMINAIRE AND OUTLET BOX, WITH PROVISIONS
FOR EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED EXIT SIGN AND
OUTLET BOX. PROVIDE NUMBER OF ARROWS
AND FACES INDICATED. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNT AT 96" ABOVE FINISHED FLOOR.
RECESSED OR PENDANT MOUNTED LUMINAIRE
AND OUTLET BOX. LETTER INDICATES LUMINAIRE
TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED LUMINAIRE AND
OUTLET BOX WITH PROVISIONS FOR
EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
EMERGENCY LIGHT UNIT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
REMOTE HEAD OR FLOOD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
WALL WASH DOWNLIGHT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POLE MOUNTED LUMINAIRE. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POST-TOP OR BOLLARD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
EQUIPMENT
MOTOR, HORSEPOWER AS INDICATED
MOTORIZED DAMPER
3-POLE COMBINATION MAGNETIC MOTOR
STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/
NEMA ENCLOSURE) NF = NONFUSED
DISCONNECT SWITCH, (SWITCH AMPS/ FUSE
SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-
FUSED
INDIVIDUALLY MOUNTED CIRCUIT BREAKER,
(CIRCUIT BREAKER SIZE/ POLES/ NEMA
ENCLOSURE)
DRY TYPE TRANSFORMER, KVA AS INDICATED
METER
ELECTRONIC METER
PANELBOARD, SEE SCHEDULES
DISTRIBUTION PANELBOARD, SEE SCHEDULES
EQUIPMENT AS INDICATED
CEILING OR WALL MOUNTED JUNCTION BOX
PULL BOX
CEILING MOUNTED BLUE LIGHT SYSTEM
ROTATING BEACON
WHITE NOISE PLENUM SPEAKER; MOUNT ABOVE
DROP CEILING
BLUE LIGHT LOCAL CONTROL SWITCH; MOUNT
48" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
WHITE NOISE ROTARY VOLUME CONTROL;
MOUNT 48" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE.
LA-1,3,5
WIRING DEVICES
LOW VOLTAGE ON/OFF WALL SWITCH, WALL
MOUNT 48" ABOVE FINISHED FLOOR. PROVIDE
DIMMER CONTROL WITH DIMMABLE FIXTURES
INTEGRAL WITH SWITCH.
CEILING MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR
CEILING MOUNTED DUAL TECHNOLOGY
VACANCY SENSOR
CEILING MOUNTED DAYLIGHT SENSOR
PHOTOELECTRIC CELL
WIRING
CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5
ADJACENT TO ARROW INDICATES HOMERUN OF
CIRCUITS, 1,3,5 TO PANEL LA. MARKS ACROSS
RACEWAY INDICATE THE NUMBER OF PHASE
CONDUCTORS AND NEUTRAL IN RACEWAY.
GROUND CONDUCTORS ARE INDICATED BY
LONGER HASHMARKS. NO MARKS ACROSS
RACEWAY INDICATES 2#12 CONDUCTORS AND 1
#12 GROUND CONDUCTOR. CONDUCTOR SIZE #
12 UNLESS INDICATED OTHERWISE. MINIMUM
RACEWAY SIZE SHALL BE 3/4"
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR
ABOVE FINISHED CEILING
UNDERGROUND RACEWAY, LOCATED BELOW
GRADE OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
PLUG-IN BUSWAY, UNLESS INDICATED
OTHERWISE
SURFACE METAL RACEWAY OR MULTIOUTLET
ASSEMBLY AS INDICATED
LADDER TYPE CABLE TRAY (SIZE AS INDICATED
ON PLAN)
DUCTBANK, TEXT INDICATES QUANTITY AND
SIZE OF DUCTS (I.E. 2W4" = TWO 4" DUCTS)
LIGHTNING PROTECTION
3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG
GROUND ROD TEST WELL
BARE COPPER GROUND CONDUCTOR, 1/0
UNLESS INDICATED OTHERWISE.
4/0 BARE COPPER GROUND CONDUCTOR
LIGHTNING PROTECTION SYSTEM AIR TERMINAL
LIGHTNING PROTECTION ROOF CONDUCTOR
ELECTRICAL CONNECTION
SITE
ELECTRICAL MANHOLE
ELECTRICAL HANDHOLE
PAD MOUNTED TRANSFORMER
POWER POLE
DOWN GUY AND ANCHOR (QUANTITY AS
INDICATED)
2W4"
WIRING DEVICES
SIMPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE.
DUPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT 48"
ABOVE FINISHED FLOOR OR ABOVE COUNTER
TOP/BACKSPLASH
DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT
18" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT
48" ABOVE FINISHED FLOOR OR ABOVE
COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 48" ABOVE FINISHED FLOOR OR ABOVE
COUNTER TOP/BACKSPLASH
SWITCHED DUPLEX GFI RECEPTACLE NEMA
5-20R, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
SWITCHED DUPLEX GFI RECEPTACLE NEMA
5-20R, MOUNT 48" ABOVE FINISHED FLOOR OR
ABOVE COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX GFI RECEPTACLE, NEMA
5-20R, MOUNTED CONCEALED BEHIND ELECTRIC
WATER COOLER
FLOOR BOX WITH DUPLEX RECEPTACLE NEMA
5-20R. PROVIDE FIRE RATED POKE THRU
DEVICES ON ALL FLOORS ABOVE GROUND
LEVEL.
SPECIAL RECEPTACLE, NEMA TYPE AS
INDICATED, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
CEILING BOX WITH DUPLEX RECEPTACLE, NEMA
5-20R
RECEPTACLE WP = IN-USE WEATHER PROOF
SUBSCRIPTS TR = TAMPER RESISTANT
TV = TELEVISION, MOUNT AT 60" ABOVE
FINISHED FLOOR
AFCI = ARC FAULT CIRCUIT INTERRUPTER
FLOOR BOX SUITABLE FOR CONCRETE FLOOR
POUR; TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE
WITH HINGED ACCESS TO RECEPTACLES AND
JACKS RECESSED BELOW COVER IN FLOOR
BOX. PROVIDE 8" FIRE RATED POKE THRU
ABOVE GROUND FLOOR.
WALL SWITCH, AC TYPE, SPST, MOUNT 48"
ABOVE FINISHED FLOOR
WALL SWITCH, AC TYPE, DPDT, MOUNT 48"
ABOVE FINISHED FLOOR
3-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
4-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
SLIDE DIMMER, MOUNT 48" ABOVE FINISHED
FLOOR
MOTOR RATED DISCONNECT SWITCH WITH
THERMAL OVERLOADS, SINGLE POLE SINGLE
THROW, MOUNT ON UNIT, UNLESS INDICATED
OTHERWISE.
WALL MOUNTED, DUAL TECHNOLOGY VACANCY
SWITCH, MOUNT 48" ABOVE FINISHED FLOOR
WALL MOUNTED, DUAL TECHNOLOGY
OCCUPANCY SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
ELECTRICAL LEGEND
D
M
V
O
LV
OS
DS
PE
5-30R
EWC
SW
S
S
S
S
S
S
S
S
S
VS
D
F
G
H
P
J
LP
TV
COMMUNICATIONS
COAXIAL CABLE TELEVISION OUTLET WALL MOUNTED
60" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
COMMUNICATIONS COMBINATION VOICE/DATA OUTLET
(TWO VOICE & TWO DATA JACKS) MOUNT 18" ABOVE
FINISHED FLOOR, UNLESS INDICATED OTHERWISE
COMMUNICATIONS VOICE OUTLET MOUNT 48" ABOVE
FINISHED FLOOR, UNLESS INDICATED OTHERWISE
COMMUNICATIONS DATA OUTLET, MOUNT 18" ABOVE
FINISHED FLOOR, UNLESS INDICATED OTHERWISE
FLOOR BOX SUITABLE FOR CONCRETE FLOOR POUR;
TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE WITH
HINGED ACCESS TO RECEPTACLES AND JACKS
RECESSED BELOW COVER IN FLOOR BOX. PROVIDE 8"
FIRE RATED POKE THRU ABOVE GROUND FLOOR.
CEILING MOUNTED PA SPEAKER, ONE WAY TYPE
WALL MOUNTED PA SPEAKER, ONE WAY TYPE; MOUNT
120" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
CLOSED CIRCUIT TELEVISION CAMERA
CONTROL STATION
NOTE: NOT ALL SYMBOLS WILL BE USED DURING THIS PROJECT
FIRE PROTECTION
FACP
BATT
ANN
SIMPLEX 4100ES FIRE ALARM CONTROL PANEL
BATTERY CABINET
FIRE ALARM ANNUNCIATOR
FIRE ALARM CLEAR VISUAL STROBE AND
SPEAKER. WALL MOUNT AT 80" AFF TO BOTTOM
OF LENS OR 6" BELOW CEILING, WHICHEVER IS
LOWER AND NOT GREATER THAN 96".
WP FIRE ALARM CLEAR VISUAL STROBE. WALL
MOUNT AT 80" AFF TO BOTTOM OF LENS OR 6"
BELOW CEILING, WHICHEVER IS LOWER AND NOT
GREATER THAN 96". WP=WEATHER PROOF
F
MANUAL FIRE ALARM PULL STATION,
MOUNT 42" - 48" AFF TO TOP OF
HANDLE
AC
DC
S
CR
EL
EH
M
IDS
ACS
IR
KP
ML
DR
BR
HSS
EPT
ELECTRONIC SECURITY
ACCESS CONTROL JUNCTION BOX
BALANCED MAGNETIC DOOR CONTACT
ELECTRIC STRIKE
SEISMIC VIBRATION SENSOR
CARD READER
ELECTRIC LOCKSET
ELECTRIC HINGE
MOTION DETECTION SENSOR
INTRUSION DETECTION SYSTEM PANEL
ACCESS CONTROL SYSTEM PANEL
INFRARED REQUEST TO EXIT
IDS KEYPAD
MAGLOCK
DOOR RELEASE
BIOMETRIC READER
HIGH SECURITY SWITCH
ELECTRIC POWER TRANSFER
S
FIRE ALARM DUCT MOUNTED SMOKE
DETECTOR
PA
PA
KEYED REMOTE TEST SWITCH FOR DUCT MOUNTED
SMOKE DETECTOR, MOUNT 48" ABOVE FINISHED
FLOOR UNLESS INDICATED OTHERWISE
DDS
CEILING MOUNTED FIRE ALARM
CLEAR VISUAL STROBE
COAXIAL CABLE TELEVISION OUTLET CEILING MOUNTED
WAP WIRELESS ACCESS POINT
ES
PB PANIC BUTTON
2 WAY COMMUNICATION CAMERA 1
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
E-002
GENERAL ELECTRICAL
SYMBOL LEGEND1
VENDING
DARK RM
CORRIDOR
1021E
OFFICE
CLOSET
CLOSET
BIOMED SHOP
CLOSET
CORRIDOR
STAIRS
OFFICE
MOP
RECEIV. VEST.
CART CHAR.
WASH RM
GARB. REFR
SUPPLY REFRIG
DRY STORAGE
REFRIG
VEG PREP
1021B
OFFICE
1021C
OFFICE
CLOSET
TOILET
OFFICE
OFFICE
CLOSET
TOILET
1012A
TELE. ROOM
FAC
STAIRS
MEN'S TOILET
WOMEN'S TOILET
CLOSET
M/F TOILET
TRAVEL
AGENT CASH
CORRIDOR
WAITING
STORAGE
STORAGE
MEDICAL MEDIA
MECH. ROOM
MECH. ROOM
FREEZOR
REFRIG
STORAGE
PROJECT AREA PANEL 5F
PANEL 5D
PANEL 5DA
1062 1061
1055 1056
GYNECOLOGY CLINIC
WAITING ROOM
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
E-003
GENERAL ELECTRICAL KEY PLAN
SCALE: 1/16" = 1'-0"A FIRST FLOOR KEY PLAN
PROJECT NORTH
A. PRIOR TO SUBMITTING A PROPOSAL THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND CAREFULLY INVESTIGATE THE EXISTING AREAS AFFECTED BY THIS WORK IN ORDER TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND THE DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THIS WORK. THE CONTRACTOR SHALL BASE HIS BID ACCORDINGLY.
SUBMISSION OF PROPOSAL WILL BE CONSTRUED AS CONFIRMATION THAT A THOROUGH EXAMINATION OF THE SITE HAS BEEN MADE BY THE CONTRACTOR. LATER CLAIMS FOR UNFORESEEN EXTRA LABOR, EQUIPMENT, OR MATERIALS WILL NOT BE ACCEPTED IF SAID CLAIMS COULD HAVE BEEN FORESEEN DURING THE SITE INVESTIGATION.
B. CONTRACTORS WORK SHALL COMPLY WITH ALL SAFETY RELATED WORK PRACTICES DETAILED IN THE LASTEST EDITION OF
NFPA 70E.
C. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF ALL ELECTRICAL FACILITIES RENDERED INACTIVE OR OBSOLETE BY THE SCOPE OF THE ARCHITECTURAL, MECHANICAL, AND PLUMBING DEMOLITION WORK. THE CONTRACT IS ALTERED THAT SUCH ELECTRICAL FACILITIES MAY NOT BE EXPLICITLY SHOWN ON THE ARCHITECTURAL DEMOLITION DRAWINGS. THE CONTRACTOR SHALL VISIT THE SITE, REFER TO THE ARCHITECTURAL MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS, AND COORDINATE WITH THE GENERAL, MECHANICAL, PLUMBING CONTRACTORS. THE CONTRACT INCLUDES ALL ELECTRICAL DEMOLITION WORK, HOWEVER NOT NECESSARILY LIMITED TO, THE COMPLETE ELECTRICAL AND CONTROL WIRE, CONDUIT, JUNCTION BOXES, ENCLOSURE, AND RACEWAY SUPPORT SYSTEM, DISCONNECT SWITCHES, CIRCUIT BREAKERS, ETC INTENDED FOR REMOVAL AS REQUIRED TO COMPLETE THE WORK.
D. THE INTENT OF THE DEMOLITION WORK REQUIREMENTS INCLUDE ALL LABOR AND EQUIPMENT REQUIRED TO ATTAIN THE FINAL CONDITION AS SHOWN ON THE ARCHITECTURAL , MECHANICAL, PLUMBING, STRUCTURAL, AND ELECTRICAL NEW WORK PLANS. THE CONTRACTOR SHALL REVIEW ALL OTHER TRADE DRAWINGS, AND COORDINATE WITH ALL OTHER TRADE
CONTRACTORS, AND BASE HIS BID ACCORDINGLY.
E. WHERE THE REMOVAL OF EXISTING FACILITIES RESULT IN THE DE-ENERGIZATION OF EXISTING REMAINING FACILITIES, THE CONTRACTOR SHALL INSTALL JUNCTION BOXES AND OR OTHER DEVICES, PROVIDE BYPASS CONNECTIONS NECESSARY TO MAKE THE EFFECTED CIRCUITS CONTINUOUS AND READY FOR OPERATION OR AS OTHERWISE INDICATED OR INTENDED.
F. THE CONTRACTOR SHALL REMOVE AND/OR RELOCATE ALL EXISTING ELECTRICAL FACILITIES THAT INTERFERE WITH THE NEW ARCHITECTURAL, MECHANICAL, PLUMBING, STRUCTURAL, ELECTRICAL LAYOUTS AND SCHEMES. REFER TO THE ARCHITECTURAL, MECHANICAL, PLUMBING, STRUCTURAL, AND ELECTRICAL DRAWINGS AND COORDINATE WITH THE
GENERAL, MECHANICAL, PLUMBING, STRUCTURAL CONTRACTORS.
G. PRIOR TO THE COMMENCEMENT OF WORK, ELECTRICAL POWER SHALL BE DISCONNECTED AND OR SWITCHED OFF AS REQUIRED. TEMPORARY LIGHTING AND POWER FOR ALL TRADES, REMAINING BUILDING OCCUPANTS, AND CRITICAL BUILDING SERVICES SHALL BE PROVIDED AS REQUIRED WITHOUT EXCEPTION. UNDER NO CIRCUMSTANCES SHALL POWER BE INTERRUPTED TO ANY AREA WITHOUT PRIOR WRITTEN APPROVAL FROM BUILDING MANAGEMENT.
H. TEMPORARY LIGHT STRINGERS WHERE SPLICED ARE TO EMPLOY COMPRESSION TYPE FITTINGS OR SOLDERED
CONNECTIONS AND MADE UP NEATLY AND SAFELY AS REQUIRED.
I. MAINTAIN CONTINUOUS ELECTRICAL SERVICE TO ALL ACTIVE AREAS AT ALL TIMES EXCEPT WHERE GIVEN WRITTEN PERMISSION BY BUILDING PROPERTY MANAGEMENT FOR A SCHEDULED OUTAGE FOR A DECLARED OUTAGE DURATION.
J. REMOVE EXPOSED CONDUITS, WIREWAYS, OUTLET BOXES, HANGERS, SUPPORTS, AND DEVICES MADE OBSOLETE BY THIS WORK UNLESS BEING REUTILIZED FOR THE NEW INSTALLATION. THE REUTILIZATION OF EXISTING FACILITIES BY THE CONTRACTOR SHALL RENDER A FINISHED INSTALLATION IN STRICT ACCORDANCE WITH THE NEC WITHOUT EXCEPTION.
K. ALL ADJACENT FACILITIES IMPACTED OR TEMPORARILY DISCONNECTED TO FACILITATE DEMOLITION WORK SHALL BE RECONNECTED AND RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINALLY FOUND PRIOR TO THE COMMENCEMENT OF WORK. WHERE EXISTING CONDITIONS DO NOT MEET NEC REQUIREMENTS, THE CONTRACTOR SHALL
NOTIFY THE CONSTRUCTION MANAGER PRIOR TO THE COMMENCEMENT OF WORK.
L. PRIOR TO THE COMMENCEMENT OF WORK THE CONTRACTOR SHALL TRACE EXISTING CIRCUITS AND CONFIRM OR IDENTIFY
TYPE AND LOCATION OF LOAD SERVED.
M. WHERE EXISTING ELECTRICAL PANELS ARE CALLED FOR REMOVAL AND OR REPLACEMENT, THE CONTRACTOR SHALL REMOVE ALL SERVING FEEDER WIRE AND CONDUIT BACK TO ITS RESPECTIVE SOURCE OF POWER OR AS OTHERWISE
INDICATED.
N. ALL OPEN FLOOR OUTLETS SHALL BE PLUGGED. ANY AND ALL PANEL ENCLOSURE OR EQUIPMENT TERMINAL BOX COMPARTMENTS WITH UNOCCUPIED KNOCKOUTS, RACEWAY OR CABLE ASSEMBLY PENETRATIONS SHALL BE PLUGGED WITH A LISTED DEVICE. ANY AND ALL UNOCCUPIED BREAKER SPACES IN EXISTING AND OR NEW PANELS SHALL BE PLUGGED WITH A LISTED DEVICE OR FURNISHED WITH A SPARE, OPERABLE CIRCUIT BREAKER LISTED FOR USE IN THE PANEL. PROVIDE
LISTED PLATES ON ALL UNUSED OUTLET AND JUNCTION BOXES.
O. ELECTRICAL PANEL COVERS ARE NOT TO BE LEFT OFF AT ANY TIME UNLESS MEN ARE WORKING ON, ADEQUATELY PROTECTING AND BARRICADING THEM AS REQUIRED. COVERS SHALL BE REPLACED EACH NIGHT BEFORE LEAVING JOB SITE.
P. REMOVE AND PROPERLY DISPOSE OF ALL REMOVALS IN ACCORDANCE WITH APPLICABLE LAWS AND ENVIRONMENTAL RESTRICTIONS UNLESS OTHERWISE REQUESTED OR DIRECTED BY THE BUILDING PROPERTY MANAGER.
Q. THE REMOVAL AND OR RELOCATION OF ALL FIRE ALARM COMMUNICATIONS, DATA AND SECURITY EQUIPMENT AND ASSOCIATED CABLING SHALL BE COORDINATED WITH BUILDING OPERATIONAL PERSONNEL. EXISTING BASE BUILDING FIRE ALARM SYSTEM (AND FLOOR SECURITY SYSTEM WHERE APPLICABLE) INTEGRITY SHALL BE MAINTAINED AT ALL TIMES
BEFORE, DURING, AND AFTER DEMOLITION.
R. CONTRACTOR SHALL PERFORM THE FOLLOWING PRIOR TO START ANY TRADES DEMOLITION:
R.A. TRACE ALL INCOMING AND OUTGOING FEEDS (LOW VOLTAGE AND HIGH VOLTAGE) AS WELL AS LIGHTING CIRCUITS BACK
TO THEIR ORIGINAL SOURCE OF POWER (I.E. SWITCHBOARDS, PANELBOARDS, ETC.)
R.B. IDENTIFY ALL CONDUITS, CABLES, ETC. WITH CLEARLY IDENTIFIABLE MARKINGS. IDENTIFICATION SHALL BE PROVIDED
FROM EACH LOAD TO THE MOST UPSTREAM SOURCE PANEL. IDENTIFICATION SHALL BE PROVIDED AT ALL JUNCTION
AND PULL BOXES, TERMINATIONS/SPLICES AND PANEL LOCATIONS AS REQUIRED.
R.C. REVIEW LOCATIONS, CONFIGURATION, AND SERVICE LOCATIONS OF ALL FEEDER AND BRANCH CIRCUIT SOURCES WITH CONSTRUCTION MANAGER/GENERAL CONTRACTOR SO AS TO ENSURE SERVICES WILL REMAIN SERVICES OR INTERRUPTED AS ANTICIPATED. REFER TO EXISTING BUILDING RECORD DRAWINGS PRIOR TO COMMENCEMENT OF
WORK.
R.D. COORDINATE ALL WORK WITH BUILDING PROPERTY MANAGEMENT.
R.E. EXISTING ELECTRICAL EQUIPMENT FACILITIES WHEN REUSED, SHALL BE THOROUGHLY CLEANED AND REFURBISHED
PRIOR TO RE-USE. ANY AND ALL EXISTING RE-USED SET SCREW TYPE CONDUIT CONNECTORS SHALL BE THOROUGHLY
TIGHTENED.
ELECTRICAL DEMOLITION NOTES:
PANEL 5D
SS
S S
1TYP.
TYP.
2TYP.
1 TYP.
PANEL 5DA
4WAP
J
S1
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
ED101
ELECTRICAL DEMOLITION PLAN
SCALE: 1/8" = 1'-0"1 ELECTRICAL DEMOLITION PLAN
PROJECT NORTH
1. THESE DRAWINGS SHOW THE INTENT OF THE
DEMOLITION AND THE NEW CIRCUITING DESIGN FOR THE
AREAS INDICATED. IT IS THE ELECTRICAL CONTRACTOR'S
RESPONSIBILITY TO FOLLOW THIS INTENT WHILE
ADAPTING TO THE EXISTING CONDITIONS FOUND IN THE
FIELD.
2. DURING EACH PHASE OF CONSTRUCTION, THE ELECTRICAL
CONTRACTOR SHALL TAKE CARE TO MAINTAIN
CONTINUITY TO ALL CIRCUITS NOT PART OF THE PHASE
INDICATED OR THE FINAL CONSTRUCTION.
3. IF OUTAGES ARE REQUIRED IN AREAS NOT BEING
RENOVATED, THE CONTRACTOR SHALL COORDINATE WITH
THE COR AND PROVIDE AT LEAST 72 HOUR NOTICE
BEFORE THE OUTAGE TAKES PLACE. SHOULD AN
UNPLANNED OUTAGE OCCUR, RESTORING POWER WILL
BE THE PRIORITY.
4. CARE MUST BE TAKEN TO ASSURE EMERGENCY LIGHTING
AND/OR SYSTEMS ARE MAINTAINED THROUGHOUT
CONSTRUCTION.
5. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING
PANEL CAPACITY PRIOR TO INSTALLATION OF NEW LOADS.
DO NOT EXCEED 80% OF MAIN CIRCUIT BREAKER
AMPACITY RATING. PROVIDE NEW WIRING, ACCESSORIES,
AND CIRCUIT BREAKERS NECESSARY FOR COMPLETE
INSTALLATION.
6. ELECTRICAL CONTRACTOR SHALL PROVIDE UPDATED
PANEL DIRECTORIES FOR ALL PANELS AFFECTED DURING
CONSTRUCTION.
7. ELECTRICAL CONTRACTOR SHALL CIRCUIT ELECTRICAL
DEVICES TO SPARE CIRCUIT BREAKERS & CIRCUITS THAT
BECOME AVAILABLE DURING DEMOLITION.
8. FIRE ALARM RELATED WORK SHALL BE PERFORMED BY A
LICENSED FIRE ALARM CONTRACTOR.
1. DISCONNECT AND REMOVE EXISTING ELECTRICAL DEVICE.
PULLBACK ALL CONDUCTORS TO THE NEAREST JUNCTION
BOX WHERE CIRCUIT ENTERS THE ROOM. MODIFY
EXISTING WIRING TO MAINTAIN CONTINUITY OF ANY
ADJACENT DEVICES AS REQUIRED.
2. DISCONNECT AND REMOVE EXISTING LIGHTING FIXTURE.
PULLBACK ALL CONDUCTORS TO THE NEAREST JUNCTION
BOX INSIDE CEILING. MODIFY EXISTING WIRING TO
MAINTAIN CONTINUITY OF ANY ADJACENT DEVICES AS
REQUIRED.
3. DISCONNECT AND REMOVE EXISTING JUNCTION BOX.
MODIFY EXISTING WIRING TO MAINTAIN CONTINUITY OF
ANY ADJACENT DEVICES AS REQUIRED.
4. DISCONNECT AND REMOVE EXISTING FIRE ALARM STROBE
DEVICE. PULL BACK ALL CONDUCTORS TO THE NEAREST
JUNCTION BOX AND FEED TO NEW FIRE ALARM DEVICES
AS SHOWN ON NEW ELECTRICAL WORK PLAN.
5. EXISTING WIRELESS ACCESS POINT SHALL BE
DISCONNECTED AND REMOVED DURING DEMOLITION
AND RECONNECTED AFTER CONSTRUCTION. SEE NEW
ELECTRICAL CEILING PLAN FOR NEW LOCATION (E-102).
ELECTRICAL CONTRACTOR SHALL STORE AND PROTECT
WAP IN A SECURE LOCATION DURING CONSTRUCTION.
ENSURE WAP IS IN GOOD WORKING CONDITION AFTER
REINSTALLATION.
GENERAL NOTES
KEY NOTES
PANEL 5D
5F-42
J
J
5F-41
5D-41
5F-41
5F-6
5D-45
5D-36
J 5D-45
5D-32
5F-41
5F-41
5D-47
5D-47
5D-47
J 5D-36
5F-42
5F-42
5F-6
2SDD
CR
5D-34
PANEL 5DA
TYP.
TYP.
TYP.
TYP.
J 5D-36
TYP.
J
ES
F
1TYP.
1TYP.
5D-39
5F-41
5D-36
5D-36
5F-41
5F-42
5F-42
5F-42
5F-6
5F-6
5F-6
5F-6
5F-6
PB
8 TYP.
1. THESE DRAWINGS SHOW THE INTENT OF THE
DEMOLITION AND THE NEW CIRCUITING DESIGN FOR THE
AREAS INDICATED. IT IS THE ELECTRICAL CONTRACTOR'S
RESPONSIBILITY TO FOLLOW THIS INTENT WHILE
ADAPTING TO THE EXISTING CONDITIONS FOUND IN THE
FIELD.
2. DURING EACH PHASE OF CONSTRUCTION, THE ELECTRICAL
CONTRACTOR SHALL TAKE CARE TO MAINTAIN
CONTINUITY TO ALL CIRCUITS NOT PART OF THE PHASE
INDICATED OR THE FINAL CONSTRUCTION.
3. IF OUTAGES ARE REQUIRED IN AREAS NOT BEING
RENOVATED, THE CONTRACTOR SHALL COORDINATE WITH
THE COR AND PROVIDE AT LEAST 72 HOUR NOTICE
BEFORE THE OUTAGE TAKES PLACE. SHOULD AN
UNPLANNED OUTAGE OCCUR, RESTORING POWER WILL
BE THE PRIORITY.
4. CARE MUST BE TAKEN TO ASSURE EMERGENCY LIGHTING
AND/OR SYSTEMS ARE MAINTAINED THROUGHOUT
CONSTRUCTION.
5. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING
PANEL CAPACITY PRIOR TO INSTALLATION OF NEW LOADS.
DO NOT EXCEED 80% OF MAIN CIRCUIT BREAKER
AMPACITY RATING. PROVIDE NEW WIRING, ACCESSORIES,
AND CIRCUIT BREAKERS NECESSARY FOR COMPLETE
INSTALLATION.
6. ELECTRICAL CONTRACTOR SHALL PROVIDE UPDATED
PANEL DIRECTORIES FOR ALL PANELS AFFECTED DURING
CONSTRUCTION.
7. ELECTRICAL CONTRACTOR SHALL CIRCUIT ELECTRICAL
DEVICES TO SPARE CIRCUIT BREAKERS & CIRCUITS THAT
BECOME AVAILABLE DURING DEMOLITION.
8. FIRE ALARM RELATED WORK SHALL BE PERFORMED BY A
LICENSED FIRE ALARM CONTRACTOR.
GENERAL NOTES
KEY NOTES
1. INSTALL NEW CLEAN ROOM GRADE JUNCTION BOX AND
DUPLEX RECEPTACLE. TYPICAL FOR ALL RECEPTACLES. SEE
E-501 - DETAIL 1 & DETAIL 4.
2. INSTALL NEW CLEAN ROOM GRADE JUNCTION BOX AND
DUPLEX RECEPTACLE FOR HOOD/WORKSTATION OR
REFRIGERATOR AND CIRCUIT BACK TO PANEL. SEE E-501 -
DETAIL 1 & DETAIL 4.
3. INSTALL THREE NEW DUPLEX RECEPTACLES FOR QAS OR
EQUAL REAL TIME MONITORING SYSTEM AND CIRCUIT
BACK TO PANEL. SEE E-501 - DETAIL 1 AND DETAIL 4.
4. INSTALL NEW WALL MOUNTED CLEAN ROOM GRADE
JUNCTION BOX WITH STAINLESS STEEL COVER PLATE FOR
HARD WIRED CONNECTION TO LAVATORY. CIRCUIT TO GFI
RECEPTACLE (LINE-SIDE) AND BACK TO PANEL. SEE E-501 -
DETAIL 4.
5. INSTALL NEW SECURITY CARD READER AND FAIL-SECURE
ELECTRONIC STRIKE AND TIE INTO EXISTING PHYSICAL
ACCESS CONTROL SYSTEM. REFER TO ARCHITECTURAL
SHEET A-002 FOR DOOR HARDWARE SPECIFICATIONS.
6. INSTALL NEW JUNCTION BOX IN CEILING FOR HARD WIRED
CONNECTION TO MOTORIZED AUTOMATIC DOOR
OPERATOR AND MOTION SENSOR. SEE E-501 - DETAIL 4.
REFER TO ARCHITECTURAL SHEET A-002 FOR DOOR
HARDWARE SPECIFICATIONS.
7. INSTALL NEW CLEAN ROOM GRADE TELEPHONE & DATA
COMBINATION OUTLET AND PROVIDE 3 4" CONDUIT TO
CEILING SPACE. SEE E-501 - DETAIL 3.
8. INSTALL NEW TWO WAY COMMUNICATION CAMERA AND
TIE INTO EXISTING COMMUNICATION SYSTEM.
COORDINATE INSTALLATION AND FINAL LOCATION WITH
COR.
9. INSTALL NEW CCTV SURVEILLANCE CAMERA AND TIE INTO
EXISTING CCTV VIDEO SURVEILLANCE SYSTEM.
COORDINATE INSTALLATION AND FINAL LOCATION WITH
COR.
10. INSTALL NEW FIRE ALARM PULL HANDLE AND TIE INTO
EXISTING FIRE ALARM CONTROL PANEL NOTIFICATION
CIRCUIT. INSTALL NEW PANIC BUTTON AND TIE INTO
EXISTING SECURITY NOTIFICATION SYSTEM.
11. INSTALL NEW FIRE ALARM SPEAKER AND/OR STROBE
DEVICE AND TIE INTO EXISTING FIRE ALARM CONTROL
PANEL NOTIFICATION CIRCUIT.
12. INSTALL NEW SMOKE DUCT DETECTOR (SEE MECHANICAL
SHEET MH101 FOR LOCATION) AND KEYED REMOTE TEST
SWITCH AND TIE INTO EXISTING FIRE ALARM CONTROL
PANEL NOTIFICATION CIRCUIT.
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
E-101SCALE: 1/4" = 1'-0"2 ELECTRICAL FLOOR PLAN
NEW ELECTRICAL FLOOR PLAN
PROJECT NORTH
LEDLED
LED
LED
LED
5D-37
PANEL 5D
C
PA
PA
PANEL 5DA
WAP
RELOCATED WAP
SEE ED101 - KEY NOTE 5
OS
OS
SD
a aS3 a
FFU
LED
LED
5D-38 dB
5D-37 dB
5D-37
7TYP.
5TYP.
3TYP.
LED
SD
b bB
5D-37 aA
5D-37 aA
5D-37 aA
5D-37 aA
5D-37 aA
5D-37 a
OS
d
SD
cOS c
OS
e
TYP.
TYP.
TYP.
TYP.
7TYP.
5TYP.
5TYP.
5 TYP.
5D-37 C
5D-37 C
SD
e
SD
d
TYP.
FFU
5D-42
LED
bB
5D-37
OS
b
FFU
5D-38
FFU
5D-42
FFU
5D-38
FFU
5D-38
LED
dB
5D-37
LED
dB
5D-37
FFU
5D-38
FFU
5D-42
FFU
5D-42
FFU
5D-42
LED
cB
5D-37
LED
cB
5D-37
LED
cB
5D-37
FFU
5D-40
FFU
5D-40
FFU
5D-40
FFU
5D-40
LED
eB
5D-37
LED
eB
5D-37
LED
eB
5D-37
LED
eB
5D-37
LED
eB
5D-37
1. THESE DRAWINGS SHOW THE INTENT OF THE
DEMOLITION AND THE NEW CIRCUITING DESIGN FOR THE
AREAS INDICATED. IT IS THE ELECTRICAL CONTRACTOR'S
RESPONSIBILITY TO FOLLOW THIS INTENT WHILE
ADAPTING TO THE EXISTING CONDITIONS FOUND IN THE
FIELD.
2. DURING EACH PHASE OF CONSTRUCTION, THE ELECTRICAL
CONTRACTOR SHALL TAKE CARE TO MAINTAIN
CONTINUITY TO ALL CIRCUITS NOT PART OF THE PHASE
INDICATED OR THE FINAL CONSTRUCTION.
3. IF OUTAGES ARE REQUIRED IN AREAS NOT BEING
RENOVATED, THE CONTRACTOR SHALL COORDINATE WITH
THE COR AND PROVIDE AT LEAST 72 HOUR NOTICE
BEFORE THE OUTAGE TAKES PLACE. SHOULD AN
UNPLANNED OUTAGE OCCUR, RESTORING POWER WILL
BE THE PRIORITY.
4. CARE MUST BE TAKEN TO ASSURE EMERGENCY LIGHTING
AND/OR SYSTEMS ARE MAINTAINED THROUGHOUT
CONSTRUCTION.
5. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING
PANEL CAPACITY PRIOR TO INSTALLATION OF NEW LOADS.
DO NOT EXCEED 80% OF MAIN CIRCUIT BREAKER
AMPACITY RATING. PROVIDE NEW WIRING, ACCESSORIES,
AND CIRCUIT BREAKERS NECESSARY FOR COMPLETE
INSTALLATION.
6. ELECTRICAL CONTRACTOR SHALL PROVIDE UPDATED
PANEL DIRECTORIES FOR ALL PANELS AFFECTED DURING
CONSTRUCTION.
7. ELECTRICAL CONTRACTOR SHALL CIRCUIT ELECTRICAL
DEVICES TO SPARE CIRCUIT BREAKERS & CIRCUITS THAT
BECOME AVAILABLE DURING DEMOLITION.
8. FIRE ALARM RELATED WORK SHALL BE PERFORMED BY A
LICENSED FIRE ALARM CONTRACTOR.
GENERAL NOTES
KEY NOTES
1. INSTALL NEW 2' X 2' LAY-IN PA SPEAKER AND TIE INTO
EXISTING PUBLIC ADDRESS SYSTEM.
2. INSTALL NEW CLEAN ROOM GRADE JUNCTION BOX AND
WALL MOUNTED SWITCH WITH STAINLESS STEEL COVER
PLATE AND CIRCUIT TO NEW LIGHT FIXTURES AND
OCCUPANCY SENSORS AS DESIGNATED. SEE E-501 - DETAIL
2 AND DETAIL 4.
3. INSTALL NEW CEILING MOUNTED OCCUPANCY SENSOR
SWITCH AND CIRCUIT TO NEW LIGHT FIXTURES AS
DESIGNATED.
4. INSTALL NEW 2' X 2' LAY-IN TROFFER LED. SEE E-601 -
LUMINAIRE SCHEDULE AND E-501 - DETAIL 5.
5. CIRCUIT NEW 2' X 2' LAY-IN TROFFER LED (PROVIDED AND
INSTALLED BY OTHERS) AS DESIGNATED. SEE E-601 -
LUMINAIRE SCHEDULE.
6. INSTALL NEW WALL OR CEILING MOUNTED LED EXIT SIGN.
SEE E-601 - LUMINAIRE SCHEDULE AND E-501 - DETAIL 6.
7. CIRCUIT NEW FAN FILTER UNIT (PROVIDED AND INSTALLED
BY OTHERS) AS DESIGNATED.
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
E-102SCALE: 1/4" = 1'-0"3 ELECTRICAL CEILING PLAN
NEW ELECTRICAL CEILING PLAN
PROJECT NORTH
AHU-49
BMEF-1
30/NF/3/3R
30/NF/3/3R5D- 31, 33, 35
5D- 44, 46, 48
EXISTING TO REMAIN
1 1
1. THESE DRAWINGS SHOW THE INTENT OF THE
DEMOLITION AND THE NEW CIRCUITING DESIGN FOR THE
AREAS INDICATED. IT IS THE ELECTRICAL CONTRACTOR'S
RESPONSIBILITY TO FOLLOW THIS INTENT WHILE
ADAPTING TO THE EXISTING CONDITIONS FOUND IN THE
FIELD.
2. DURING EACH PHASE OF CONSTRUCTION, THE ELECTRICAL
CONTRACTOR SHALL TAKE CARE TO MAINTAIN
CONTINUITY TO ALL CIRCUITS NOT PART OF THE PHASE
INDICATED OR THE FINAL CONSTRUCTION.
3. IF OUTAGES ARE REQUIRED IN AREAS NOT BEING
RENOVATED, THE CONTRACTOR SHALL COORDINATE WITH
THE COR AND PROVIDE AT LEAST 72 HOUR NOTICE
BEFORE THE OUTAGE TAKES PLACE. SHOULD AN
UNPLANNED OUTAGE OCCUR, RESTORING POWER WILL
BE THE PRIORITY.
4. CARE MUST BE TAKEN TO ASSURE EMERGENCY LIGHTING
AND/OR SYSTEMS ARE MAINTAINED THROUGHOUT
CONSTRUCTION.
5. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING
PANEL CAPACITY PRIOR TO INSTALLATION OF NEW LOADS.
DO NOT EXCEED 80% OF MAIN CIRCUIT BREAKER
AMPACITY RATING. PROVIDE NEW WIRING, ACCESSORIES,
AND CIRCUIT BREAKERS NECESSARY FOR COMPLETE
INSTALLATION.
6. ELECTRICAL CONTRACTOR SHALL PROVIDE UPDATED
PANEL DIRECTORIES FOR ALL PANELS AFFECTED DURING
CONSTRUCTION.
7. ELECTRICAL CONTRACTOR SHALL CIRCUIT ELECTRICAL
DEVICES TO SPARE CIRCUIT BREAKERS & CIRCUITS THAT
BECOME AVAILABLE DURING DEMOLITION.
8. FIRE ALARM RELATED WORK SHALL BE PERFORMED BY A
LICENSED FIRE ALARM CONTRACTOR.
GENERAL NOTES
KEY NOTES
1. INSTALL NEW 3Φ, 208V, 30A, NON-FUSED ELECTRICAL
DISCONNECT WITH NEMA 3R RATED ENCLOSURE FOR
NEW HVAC EQUIPMENT SPECIFIED ON MECHANICAL
DRAWINGS.
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
E-103SCALE: 1/4" = 1'-0"4 ELECTRICAL ROOF PLAN
NEW ELECTRICAL ROOF PLAN
PROJECT NORTH
EXIT SIGN REQUIREMENTS:
1. HOUSING - DIE-CAST ALUMINUM, STEEL, OR HIGH-IMPACT, UV-STABILIZED,
INJECTION- MOLDED THERMOPLASTIC. SINGLE OR DOUBLE-FACED AS
INDICATED.
2. FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT
FINISH OPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE,
BLACK, OR BLACK WITH BRUSHED ALUMINUM FACE.
3. LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. RED OR GREEN
LETTERS AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT,
RIGHT OR BOTH DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT
THROUGH HOUSING AS REQUIRED.
4. MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR
END-OF-FIXTURE MOUNTING.
5. ILLUMINATION - PROVIDED BY RED, GREEN OR WHITE HIGH-OUTPUT LEDS
INSIDE OF FIXTURE HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR
INDICATED WITH FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM
LED LIGHT OUTPUT.
6. CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.
7. FIXTURE TYPE: C
NOTE: SEE SPECIFICATION 26 51 00 - INTERIOR LIGHTING
FOR ADDITIONAL LUMINAIRE REQUIREMENTS.
WHERE DRAWINGS AND SPECIFICATIONS CONFLICT, THE MOST STRINGENT
REQUIREMENT SHALL GOVERN.
LUMINAIRE REQUIREMENTS:
1. HOUSING & FINISH - 2’ X 2’ TROFFER BODY TO HAVE SMOOTH HEMMED SIDES
AND SMOOTH INWARD FORMED END FLANGES.
2. REFLECTORS - HIGHLY TRANSMISSIVE ACRYLIC PATTERN #12 (.125") LENS
DIFFUSE TO ELIMINATE LED IMAGE FROM BELOW.
3. LAMPS - LED LAMP TO HAVE 3500K KELVIN COLOR TEMPERATURE OF LIGHT
WITH A CRI OF 80 AND AN L70 OF 50,000 HOURS OR GREATER.
4. DRIVER - LED DRIVER TO BE AUTOSENSING 120-277 VOLT AND MUST BE
ACCESSIBLE FROM BELOW THE CEILING. FIXTURE IS TO BE DIMMABLE DOWN
TO 1 PERCENT USING 0 TO 10 VOLT DRIVER BEING FLICKER FREE DURING
DIMMING PROCESS. PROVIDE DIGITALLY ADDRESSABLE DRIVER OR LOW
VOLTAGE DIGITAL ADDRESSABLE CONTROL DEVICE.
5. CERTIFICATION - FIXTURE MUST BE DLC QUALIFIED (DESIGN LIGHT
CONSORTIUM) AND UL LISTED. FIXTURE PERFORMANCE SPECIFICATIONS
MUST MEET OR EXCEED LINE 2 AS TESTED BY DLC.
6. WARRANTY - PROVIDE A MINIMUM 5-YEAR WARRANTY BY MANUFACTURER.
PROVIDE IES FILE AND PROVIDE SPECIFICATION SHEET FOR REVIEW.
7. FIXTURE TYPE: A
NOTE: SEE SPECIFICATION 26 51 00 - INTERIOR LIGHTING
FOR ADDITIONAL LUMINAIRE REQUIREMENTS.
WHERE DRAWINGS AND SPECIFICATIONS CONFLICT, THE MOST STRINGENT
REQUIREMENT SHALL GOVERN.
13" NOMINAL
8" NOMINAL
PNL-CKT
NOTE: REFER TO SPECIFICATION 26 27 26 - WIRING DEVICES
FOR ADDITIONAL LIGHT SWITCH REQUIREMENTS
INSTALL APPROVED
MACHINE SCREWS.
BOND LIGHT SWITCH TO
BOX WITH GREEN
GROUNDING SCREW.
STAINLESS STEEL
FACEPLATE
PROVIDE DURABLE
WIRE MARKERS OR
TAGS INSIDE THE
OUTLET BOX.
WHITE LABEL TAPE WITH
TYPED, BLACK LETTERING
DESIGNATING PANEL AND
CIRCUIT NUMBER.
PROVIDE LIGHT SWITCH IN
WHITE COLOR.
SEAL FACEPLATE AND LIGHT
SWITCH FOR AIR TIGHTNESS
WITH SEALANT.
PNL-CKT
NOTE: REFER TO SPECIFICATION 26 27 26 - WIRING DEVICES
FOR ADDITIONAL RECEPTACLE REQUIREMENTS
INSTALL GROUND
PIN ON TOP.
INSTALL APPROVED
MACHINE SCREWS.
BOND RECEPTACLE TO
BOX WITH GREEN
GROUNDING SCREW
STAINLESS STEEL
FACEPLATE
PROVIDE DURABLE
WIRE MARKERS OR
TAGS INSIDE THE
OUTLET BOX.
WHITE LABEL TAPE WITH
TYPED, BLACK LETTERING
DESIGNATING PANEL AND
CIRCUIT NUMBER.
PROVIDE RECEPTACLES IN
THE FOLLOWING COLORS:
• WHITE: NORMAL POWER
• RED: EMERGENCY POWER
SEAL FACEPLATE AND
RECEPTACLE FOR AIR
TIGHTNESS WITH
SEALANT.
SWITCH-PORT
NOTE: REFER TO SPECIFICATION 27 15 00 - COMMUNICATIONS STRUCTURED CABLING
FOR ADDITIONAL DATA/VOICE OUTLET REQUIREMENTS
INSTALL APPROVED
MACHINE SCREWS.
STAINLESS STEEL
FACEPLATE
PROVIDE 3 4" CONDUIT
TO CEILING SPACE.
COORDINATE CABLING
WITH COR..
WHITE LABEL TAPE WITH
TYPED, BLACK LETTERING
DESIGNATING WORKSTATION
AND PATCH PANEL #.
COORINATE LABELING WITH
COR.
PROVIDE TWO RJ-45 CAT5E
DATA OUTLETS AND TWO
RJ-11 VOICE TELEPHONE
COMMUNICATION OUTLETS.
SEAL FACEPLATE AND
OUTLET FOR AIR
TIGHTNESS WITH
SEALANT.
SEAL ALL UNUSED KNOCKOUTS AND
OPENINGS FOR AIR TIGHTNESS.
PROVIDE STAINLESS STEEL
CLEANROOM GRADE JUNCTION BOX.
NOT TO EXCEED BOX FILL
CALCULATIONS PER NEC 314.16(B).
INSTALL APPROVED MACHINE
SCREWS AND GREEN GROUNDING
SCREWS AS REQUIRED. BOND ALL
METAL BOXES AND ELECTRICAL
DEVICES.
NOTE: REFER TO SPECIFICATION 26 05 33 - RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
FOR ADDITIONAL BOX REQUIREMENTS
TV
TV TV
�6"
MAX.
�6"
MAX.
AV
�12"
MAX.
FI
R
E
FI
R
E
�12"
MAX.
T-STAT
T $
�6"
MAX.
�12"
MAX.
�18"
MAX.
P
�5'-0" MAX.
(EITHER SIDE OF DOOR)
" M
EA
SU
R
ED
T O
H
AN
D
LE
" M
IN
" A
FF
M
IN
BO
TT
O
M O
F
LE
N S
" A
FF
M
AX
TO
P
O F
LE
N
S
FIRE ALARM
PULL STATION
LIGHT
SWITCH
VOICE
OUTLET
PROJECTOR
MOMENTARY
TOGGLE
SWITCH
DATA
OUTLET
DUPLEX
RECEPTACLE
DOUBLE DUPLEX
RECEPTACLE
FIRE
ALARM
M
AR
KE
R
BO
AR
D 6"
MAX.
6"
MAX.
6"
MAX.
6"
MAX.
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
E-501
ELECTRICAL DETAILS
NO SCALE1
RECEPTACLE DETAIL (TYP.)
NO SCALE2
LIGHT SWITCH DETAIL (TYP.)
NO SCALE5
2' X 2' LED LAY-IN TROFFER (TYP.)
NO SCALE6
LED EXIT LIGHT FIXTURE (TYP.)
NO SCALE3
COMM. OUTLET DETAIL (TYP.)
NO SCALE4
JUNCTION BOX DETAIL (TYP.)
NOT TO SCALE7 ELECTRICAL MOUNTING HEIGHT DETAIL
DOCUMENTS ARE PROPERTY OF THE U.S. GOVERNMENT.
Phone: (804) 726-9540 https//raymond.global
1601 Summit Avenue Richmond, VA 23230
DATE DESCRIPTION
PROJECT NO.: RVA1033.003
OWNER:
WG HEFNER VAMC
BUILDING 5
PHARMACY CLEAN ROOM
1601 BRENNER AVE
SALISBURY, NC, 28144
SENSITIVE UNCLASSIFIED
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUES / REVISIONS
09/15/20 15% SD SUBMISSION
10/29/20 35% SD SUBMISSION
DATE VA COR SIGN OFF
09/15/20 ANDRE L. NOBS
SUB
15% SD
11/18/20 ANDRE L. NOBS35% SD
12/19/20 65% DD SUBMISSION
02/25/21 95% DD SUBMISSION
2/2/21 ERIC STEWART65% DD
3/12/21 ERIC STEWART95% DD
03/26/21 100% DD SUBMISSION
05/09/21 FINAL BID DOCUMENTS
4/16/21 ANDRE HAYLES100% DD
09/29/21 DILANDRO COMMENTS1
ADRIAN LOZA
ADRIAN LOZA
FLOYD KEELS
E-601
ELECTRICAL SCHEDULES
1. ELECTRICAL CONTRACTOR SHALL FIELD VERIFY EXISTING
PANEL CAPACITY PRIOR TO INSTALLATION OF NEW LOADS.
DO NOT EXCEED 80% OF MAIN CIRCUIT BREAKER
AMPACITY RATING. PROVIDE NEW WIRING, ACCESSORIES,
AND CIRCUIT BREAKERS NECESSARY FOR COMPLETE
INSTALLATION. PROVIDE NEW PANELBOARD AND CIRCUIT
BREAKERS SIZED AS NEEDED FOR THE COMPLETE
INSTALLATION OF NEW LOADS AND REFEEDING OF
EXISTING LOADS.
2. ELECTRICAL CONTRACTOR SHALL PROVIDE UPDATED
PANEL DIRECTORIES, TYPED AND PRINTED, FOR ALL
PANELS AFFECTED DURING CONSTRUCTION.
3. ELECTRICAL CONTRACTOR SHALL CIRCUIT ELECTRICAL
DEVICES TO SPARE CIRCUIT BREAKERS & CIRCUITS THAT
BECOME AVAILABLE DURING DEMOLITION.
GENERAL NOTES
LUMINAIRE SCHEDULE
TYPE MANUFACTURER DESCRIPTION LAMP TYPE VOLTAGE INPUT WATTS LOCATION
A KENALL
OR EQUAL
2' X 2' RECESSED MOUNTED LED SIMPLESEAL FIXTURE
LED 120 V 72 W STAGING AREA
CSEDO-22-67L-35K8-DIM1-DV-2F-2H-SYM-AMF
B
QAS
OR EQUIAL
2' X 2' RECESSED MOUNTED LED FIXTURE
LED 120 V 60 W CLEANROOM
PROVIDED BY CLEANROOM MANUFACTURER
C COOPER
LIGHTING OR EQUAL
SURE-LITES WALL MOUNTED LED EXIT SIGN
LED 120 V 1 W CLEANROOM
SLX7
EXISTING PANELBOARD SCHEDULE 5D
LOCATION: BUILDING 5 MAINS RATING: 225A
SUPPLY FROM: 5X VOLTAGE 208/120 Y
MOUNTING: SURFACE PHASES: 3
ENCLOSURE: NEMA 1 WIRES: 4
CONNECTED LOAD (VA)
CKT CIRCUIT DESCRIPTION: TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT
1 EXISTING LOAD - - - - - - EXISTING LOAD 2
3 EXISTING LOAD - - - - - - EXISTING LOAD 4
5 EXISTING LOAD - - - - - - EXISTING LOAD 6
7 EXISTING LOAD - - - - - - EXISTING LOAD 8
9 EXISTING LOAD - - - - - - EXISTING LOAD 10
11 EXISTING LOAD - - - - - - EXISTING LOAD 12
13 EXISTING LOAD - - - - - - EXISTING LOAD 14
15 EXISTING LOAD - - - - - - EXISTING LOAD 16
17 EXISTING LOAD - - - - - - EXISTING LOAD 18
19 EXISTING LOAD - - - - - - EXISTING LOAD 20
21 EXISTING LOAD - - - - - - EXISTING LOAD 22
23 EXISTING LOAD - - - - - - EXISTING LOAD 24
25 EXISTING LOAD - - - - - - EXISTING LOAD 26
27 EXISTING LOAD - - - - - - EXISTING LOAD 28
29 EXISTING LOAD - - - - - - EXISTING LOAD 30
AHU-49 15 A 3
888 1000 1 20 A HAZ. STORAGE FRIDGE 32
33 888 1000 1 20 A PHARM. STAGING FRIDGE 34
35 888 1000 1 20 A CLEAN ROOM DOORS 36
37 CLEAN ROOM LTG. 20 A 1 1500 1680 1 20 A HAZ. COMP. ROOM FFU 38
39 BIOSAFE HOOD 20 A 1 1500 1344 1 20 A COMP. ROOM FFU 40
41 LAMINAR WORKSTATION 20 A 1 1500 1680 1 20 A ANTEROOM, STORAGE, HAZ. COMP ROOM FFU 42
43 EXISTING LOAD - - - 1272
3 30 A BMEF-1
45 ANTEROOM SINK 20 A 1 195…