_657-23-115JB_100_Drawings_Book_3_Electrical.pdf

PDF 9 MB Posted

Attached to
Z1DA--657-23-115JB Correct Campus Steam System Failures, JB Federal contract opportunity
Solicitation number
36C25524R0096
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document is a set of construction drawings related to a federal contract opportunity for the Department of Veterans Affairs (VA) to correct campus steam system failures at the Jefferson Barracks Division of the St. Louis VA Medical Center.

The key details are:

  • The project is titled "Correct Campus Steam System Failures, JB" with solicitation number 36C25524R0096 and project number 657-23-115JB.
  • The work includes construction to improve steam and condensate system functionality, manhole access, safety, remote valve operation, monitoring of manhole components, and compliance with VA and industry standards.
  • The scope of work includes architectural, mechanical, and electrical construction such as upgrading manholes, replacing compensators, steam valves, condensate pumps, sump pumps, and providing electrical controls and monitoring.
  • The period of performance is estimated to be 180 days and includes mobilization, construction, inspection, closeout, and documentation.
  • The contract is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--657-23-115JB Correct Campus Steam System Failures, JB, newest first.
File Type Posted
_657-23-115JB_ADD1_Drawings_Book_4_Electrical.pdf PDF
Follow Up Responses REV1 20240802.xlsx XLSX spreadsheet
ADD1_-_BOD_COMBINED_-_657-23-115JB_UPDATED_8.1.24.pdf PDF
_657-23-115JB_ADD1_Drawings_Book_3_Electrical-reduced.pdf PDF
36C25524R0096 0002.docx DOCX document
RFI 021 Response - Manhole Concrete Repairs.pdf PDF
_657-23-115JB_ADD1_Drawings_Book_2_Electrical.pdf PDF
_657-23-115JB_ADD1_Drawings_Book_1_General_and_Mechanical.pdf PDF
PreProposal Conference Site Visit Agenda 657-23-115JB.pdf PDF
Pre-Construction Conference Sign-in Sheet 657-23-115.doc DOC document
100 BOD COMBINED - 657-23-115JB UPDATED 7.23.24.pdf PDF
Contractor Pre-Bid RFI Log - 657-23-115JB - REV1.3.xlsx XLSX spreadsheet
36C25524R0096 0001.docx DOCX document
_657-23-115JB_100_Drawings_Book_2_Electrical.pdf PDF
Directions to Prebid Meeting --- Bldg 1-1st Flr-FLOOR PLAN.pdf PDF
_657-23-115JB_100_Drawings_Book_4_Electrical.pdf PDF
_657-23-115JB_100 _Drawings_Book_1_General_and_Mechanical.pdf PDF
S02 ATTACMENT 3 Past Performance Questionnaire 36C25524R0096 Project 657-23-115JB.pdf PDF
36C25524R0096.docx DOCX document
_657-23-115JB_100Percent _Specs_Conformed 20240612.pdf PDF
Project_Work_Overview.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

AREA SHOWN

MANHOLE

"MH-7B"

MANHOLE

"MH-7A"

SP-7

STEAM TRAP SENSOR

(TYP)

ACTUATED VALVE (TYP)

(E) 14" COMPENSATOR

S

TS

S

TS

A V

A V

E-504

E-504

MANHOLE

"MH-7B"

SP-6A,B

LSHH

LSH

LSL

LEVEL SWITCH (TYP)

MANHOLE

"MH-7A"

TYP.

A V

C-1

P-1

C-3

C-2

C-3

P-1 P-2

C-2

C-3

MH-7A AND MH-7B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:2 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-7A' AND 'MH-7B'

ENLARGED ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP406

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

2'0 4' 6'

PROJECT

NORTH

3/8" = 1'-0"ES101

1 MANHOLE 'MH-7A' AND 'MH-7B' ENLARGED DEMO ELECTRICAL PLANS

3/8" = 1'-0"ES101

2 MANHOLE 'MH-7A' AND 'MH-7B' ENLARGED REVISED ELECTRICAL PLANS

2'0 4' 6'

PROJECT

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-7" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-7" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO

PROVIDE LEAK-PROOF INSTALLATION.

Revisions: Date:

(E) 14" COMPENSATOR

"MH-8"

MANHOLE

SP-8

(E) 14" COMPENSATOR

SP-7A,B

"MH-8"

MANHOLE

LSL

LSH

LSHH

LEVEL SWITCH (TYP)

E-504

E-504

STEAM TRAP

SENSOR

STS

P-1

C-1

C-2

P-2

P-1

MH-8

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:3 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-8' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP407

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

3/8" = 1'-0"ES101

1 MANHOLE 'MH-8' ENLARGED DEMO ELECTRICAL PLANS

3/8" = 1'-0"ES101

2 MANHOLE 'MH-8' ENLARGED REVISED ELECTRICAL PLANS2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS-STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-8" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-8" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO

VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-

BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING

CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE

SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.

Revisions: Date:

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO

PROVIDE LEAK-PROOF INSTALLATION.

MH-9

(E) 14" COMPENSATOR

SP-9

MANHOLE

"MH-9"

(E) 14" COMPENSATOR

STEAM TRAP SENSOR

MANHOLE

"MH-9"

LSHH

LSH

LSL

LEVEL SWITCH

(TYP)

STS

E-504

E-504

SP-8A,B

P-1

C-1

C-2

P-2

P-1

AREA SHOWN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:4 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-9' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP408

KEY NOTES

KEY PLAN

GENERAL NOTES

2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

3/8" = 1'-0"ES101

1 MANHOLE 'MH-9' ENLARGED DEMO ELECTRICAL PLANS

3/8" = 1'-0"ES101

2 MANHOLE 'MH-9' ENLARGED REVISED ELECTRICAL PLANS

TRUE

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE

VAULT(S) TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S),

UNLESS OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-9" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-9" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO

PROVIDE LEAK-PROOF INSTALLATION.

(E) 14" COMPENSATOR

SP-10

MANHOLE

"MH-10"

(E) 14" COMPENSATOR

SP-9A,B

MANHOLE

"MH-10"

STEAM TRAP SENSOR

LSHH

LSH

LSL

LEVEL SWITCH (TYP)

S T S

E-504

E-504

P-1

P-1

C-2

P-2

C-1

E-504

MH-10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:5 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-10' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP409

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

3/8" = 1'-0"ES101

1 MANHOLE 'MH-10' ENLARGED DEMO ELECTRICAL PLANS 2'0 4' 6'

PROJECT

NORTH

3/8" = 1'-0"ES101

2 MANHOLE 'MH-10' ENLARGED REVISED ELECTRICAL PLANS 2'0 4' 6'

PROJECT

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS-STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-10" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-10" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

CONCRETE BOLLARD. COORDINATE EXACT LOCATIONS WITH VA.

Revisions: Date:

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

ACTUATED

VALVE (TYP)

STEAM TRAP SENSOR (TYP)

SP-10A,B

MANHOLE

"MH-12A"

MANHOLE

"MH-12B"

S T S

S T

S

LSHH

LSH

LSL

E-504

E-504

LEVEL SWITCH

AV

A V

A V

P-1

C-1

C-3

C-3

C-3

C-2

C-2

P-1 P-2

SP-12

MANHOLE

"MH-12A"

MANHOLE

"MH-12B"

MH-12A AND MH-12B

AREA SHOWN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:0 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-12A' AND 'MH-12B'

ENLARGED ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP410

KEY PLAN

GENERAL NOTES

1/4" = 1'-0"ES101

2 MANHOLE 'MH-12A' AND 'MH-12B' ENLARGED REVISED ELECTRICAL PLANS

1/4" = 1'-0"ES101

1 MANHOLE 'MH-12A' AND 'MH-12B' ENLARGED DEMO ELECTRICAL PLANS

BASED ON FIELD INVESTIGATION

NO VOLTAGE/POWER WAS OBSERVED

IN EXISTING VAULT

2'0 4' 8'

PROJECT

NORTH

2'0 4' 8'

PROJECT

NORTH

TRUE

NORTH

Revisions: Date:

KEY NOTES

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE TO BE DEMOLISHED AND REPLACED WITH JUNCTION BOX.

EXISTING CONDUCTORS TO BE PRESERVED AND PROTECTED FOR REUSE.

PROVIDE STAINLESS-STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-12" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-12" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO

VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-

BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING

CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE

SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO

J

J

AREA SHOWN

SP-13

MANHOLE

"MH-13B"

MANHOLE

"MH-13A"

MINI-POWER ZONE

STEAM TRAP SENSOR (TYP)

ACTUATED VALVE (TYP)

MANHOLE

"MH-13A”

MANHOLE

“MH-13B”

STS

AV

E-504

A V

AV

SP-11A,B

LSL

LSH

LSHH

LEVEL SWITCH (TYP)

A V

STS

STS

C-1

C-3

P-1

C-2

C-3C-3

C-2

C-3

P-1

C-2

MINI-POWER ZONE

P-2

MH-13A AND MH-13B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:1 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-13A AND MH-13B'

ENLARGED ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP411

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

2'0 4' 6'

PROJECT

NORTH

3/8" = 1'-0"ES101

1 MANHOLE 'MH-13A' AND 'MH-13B' ENLARGED DEMO ELECTRICAL PLANS

3/8" = 1'-0"ES101

2 MANHOLE 'MH-13A' AND 'MH-13B' ENLARGED REVISED ELECTRICAL PLANS

2'0 4' 6'

PROJECT

NORTH

BASED ON FIELD INVESTIGATION

NO VOLTAGE/POWER WAS OBSERVED

IN EXISTING VAULT

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLES BELOW MINI-POWER ZONE TO REMAIN.

EXISTING JUNCTION BOX TO BE DEMOLISHED AND REPLACED. EXISTING

CONDUCTORS TO BE PRESERVED AND PROTECTED FOR REUSE.

PROVIDE CONTROL PANEL "CP-MH-13" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO

VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-

BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING

CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE

SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.

PROVIDE STAINLESS-STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-13" AS INDICATED.

JUNCTION BOX SHALL BE LOCATED HIGH WITHIN MANHOLE TO AVOID FLOODING.

Revisions: Date:

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO

J J

MANHOLE

"MH-15"

SP-15

MANHOLE

"MH-15"

SP-12A,B

LSHH

LSH

LSL

LEVEL SWITCH (TYP)

E-504

E-504

S

TS

STEAM TRAP

SENSOR

P-1

C-1

C-2

P-1

P-2

MH-15

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:2 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-15' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP412

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

2'0 4' 8'

PROJECT

NORTH

- 1/2" = 1'-0"

1 MANHOLE 'MH-15' ENLARGED DEMO ELECTRICAL PLANS

1/2" = 1'-0"ES101

2 MANHOLE 'MH-15' ENLARGED REVISED ELECTRICAL PLANS

BASED ON FIELD INVESTIGATION

NO VOLTAGE/POWER WAS OBSERVED

IN EXISTING VAULT

2'0 4' 8'

PROJECT

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

EXISTING JUNCTION BOX TO BE DEMOLISHED AND REPLACED. EXISTING

CONDUCTORS TO BE PRESERVED AND PROTECTED FOR REUSE.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-15" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-15" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO

VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-

BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING

CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE

SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO

PROVIDE LEAK-PROOF INSTALLATION.

SP-16

(E) 14" COMPENSATOR

MANHOLE

"MH-16"

SP-13A,B

(E) 14" COMPENSATOR

STEAM TRAP SENSOR

MANHOLE

"MH-16"

LSHH

LSH

LSL

LEVEL SWITCH

(TYP)

STS

E-504 1

E-504

P-1

C-1

C-2

P-2

P-1

MH-16

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:3 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-16' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP413

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

3/8" = 1'-0"ES101

1 MANHOLE 'MH-16' ENLARGED DEMO ELECTRICAL PLAN

3/8" = 1'-0"ES101

2 MANHOLE 'MH-16' ENLARGED ELECTRICAL PLAN2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO

PROVIDE LEAK-PROOF INSTALLATION.

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-16" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-16" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

333333

J J

MANHOLE

"MH-18AA"

SP-14

MANHOLE

"MH-18AB"

MANHOLE

"MH-18AA"

S T S

S T S

SP-14A,B

A V

A V

ACTUATED VALVE

(TYP)

STEAM TRAP SENSOR

(TYP)

E-504

E-504

MANHOLE

"MH-18AB"

LSHH

LSH

LSL

C-1

P-2

P-1

P-1

C-2

C-2

C-3

C-3

AREA SHOWN

MH-18A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:3 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-18A' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP414

1/4" = 1'-0"ES101

1 MANHOLE 'MH-18A' ENLARGED DEMO ELECTRICAL PLANS

BASED ON FIELD INVESTIGATION

NO VOLTAGE/POWER WAS OBSERVED

IN EXISTING VAULT

1/4" = 1'-0"ES101

2 MANHOLE 'MH-18A' ENLARGED REVISED ELECTRICAL PLANS

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-18A" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-18A" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO

VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-

BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING

CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE

SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.

Revisions: Date:

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

MH-18B

SP-18

MANHOLE

"MH-18B"

SP-15A,B

MANHOLE

"MH-18B"

LSHH

LSH

LSL

LEVEL SWITCH (TYP)

STEAM TRAP

SENSOR

STS

E-504

E-504

C-1

C-2

P-2 P-1

P-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:4 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-18B' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP415

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-18B" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-18B" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO

VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-

BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING

CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE

SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.

1/2" = 1'-0"ES101

1 MANHOLE 'MH-18B' ENLARGED DEMO ELECTRICAL PLANS

1/2" = 1'-0"ES101

2 MANHOLE 'MH-18B' ENLARGED REVISED ELECTRICAL PLANS1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

Revisions: Date:

BASED ON FIELD INVESTIGATION

NO VOLTAGE/POWER WAS OBSERVED

IN EXISTING VAULT

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

MANHOLE

"MH-19"

SP-19

SP-16A,B

ACTUATED VALVE

MANHOLE

"MH-19"

STEAM TRAP SENSOR (TYP)

LSHH

LSH

LS

STS

STS

STS

STS

LEVEL SWITCH (TYP)

E-504

E-504

AV

AV

AV

AV

C-3C-3

C-3

C-3

P-2

C-2

C-2

P-1

P-1

C-1

C-2

C-2

MH-19

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:5 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-19' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP416

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

3/8" = 1'-0"ES101

1 MANHOLE 'MH-19' ENLARGED DEMO ELECTRICAL PLANS

3/8" = 1'-0"ES101

2 MANHOLE 'MH-19' ENLARGED REVISED ELECTRICAL PLANS 2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-19" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-19" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

Revisions: Date:

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

"MH-20"

MANHOLE

SP-20

SP-17A,B

"MH-20"

MANHOLE

ACTUATED VALVE

STEAM TRAP SENSOR (TYP)

LSHH

LSH

LSL

LEVEL SWITCH (TYP)

STS

STS

STS

E-504

E-504

AV

AV

A V

P-1 P-1

P-2

C-2

C-2

C-2

C-3

C-3

C-3

C-1

MH-20

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:0 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'MH-20' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP417

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

3/8" = 1'-0"ES101

1 MANHOLE 'MH-20' ENLARGED DEMO ELECTRICAL PLANS

3/8" = 1'-0"ES101

2 MANHOLE 'MH-20' ENLARGED REVISED ELECTRICAL PLANS2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-20" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-MH-20" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

333333

Revisions: Date:

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

OLD MH-5

STS

STS

STS

STS

LSHH

LSH

LSL

AV

AV

AV

E-504

E-504

SP-18A,B

C-3

C-3

C-3

C-2

C-2

C-2

C-2

P-1

P-1

C-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:1 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE 'OMH-5' ENLARGED

ELECTRICAL PLANS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

EP418

Revisions: Date:

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

2'0 4' 6'

PROJECT

NORTH

2'0 4' 6'

PROJECT

NORTH

EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)

TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS

OTHERWISE NOTED.

EXISTING RECEPTACLE TO BE DEMOLISHED AND REPLACED WITH JUNCTION

BOX. EXISTING CONDUCTORS TO BE PRESERVED AND PROTECTED FOR REUSE.

PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE

EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE

RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-OMH-5" AS INDICATED.

JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.

PROVIDE CONTROL PANEL "CP-OMH-5" AS INDICATED. FINAL LOCATION OF CONTROL

PANEL TO BE COORDINATED WITH VA.

CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO

VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-

BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING

CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE

SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.

3/8" = 1'-0"ES101

1 MANHOLE 'OLD MH-5' ENLARGED DEMO ELECTRICAL PLANS

3/8" = 1'-0"ES101

2 MANHOLE 'OLD MH-5' ENLARGED REVISED ELECTRICAL PLANS

BASED ON FIELD INVESTIGATION

NO VOLTAGE/POWER WAS OBSERVED

IN EXISTING VAULT

1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR

SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH

EXISTING SITE CONDITIONS.

2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE

MANNER.

3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND

ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;

COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.

4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.

COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.

6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO

INSTALLATION.

7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND

CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.

8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO

MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO

FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,

SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN

MANHOLE(S).

9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO

PROVIDE LEAK-PROOF INSTALLATION.

NORTH

WEST EAST

SOUTH

PIPE

PIPE

PIPE

PIPE

PIPE

PIPE3/4

12 1

NORTH

WEST EAST

SOUTH

PIPE

PIPE

PIPE

PIPE

3/4

2 1 1

NORTH

WEST EAST

SOUTH

PIPE PIPE

3/4

NORTH

WEST EAST

SOUTH

PIPE PIPE

3/4

1 1

NORTH

WEST

SOUTH

PIPE PIPE

PIPE

PIPE

EAST

3/4

1 1

NORTH

WEST

SOUTH

PIPE

PIPEPIPE

PIPE PIPE

PIPE

EASTPIPE

PIPE

PIPE

PIPE 3/4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:1 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE ELECTRICAL

BUTTERFLY DETAILS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

E-501

GENERAL NOTES

NTS

MANHOLE "MH-10" BUTTERFLY DETAIL

EP409

NTS

MANHOLE "MH-3" BUTTERFLY DETAIL

EP402

NTS

MANHOLE "MH-4" BUTTERFLY DETAIL

EP403

NTS

MANHOLE "MH-5" BUTTERFLY DETAIL

EP404

NTS

MANHOLE "MH-6A"

A

NTS

MANHOLE "MH-6B"

B

NTS

MANHOLE "MH-7A"

A

NTS

MANHOLE "MH-7B"

B

NTS

MANHOLE "MH-6A" AND "MH-6B" BUTTERFLY DETAIL

EP405

NTS

MANHOLE "MH-7A" AND "MH-7B" BUTTERFLY DETAIL

EP406

1. BUTTERFLY DETAILS SHOWN FOR VAULT PENETRATION

COORDINATION. NUMBER INSIDE PENETRATION CIRCLE

INDICATES RACEWAY DIAMETER IN INCHES. EXACT

LOCATIONS OF PENETRATIONS AND VAULT

DIMENSIONS/LAYOUT ARE DIAGRAMMATICAL; CONTRACTOR

FIELD VERIFICATION AND COORDINATION SHALL BE

REQUIRED. AFTER CONSTRUCTION IS COMPLETE,

CONTRACTOR SHALL PROVIDE REDLINE DRAWINGS TO

FULLY AS-BUILD MANHOLES.

2. COORDINATE WITH THE MECHANICAL SET REGARDING

EXACT SIZING OF THE PIPES AND EXACT LOCATIONS OF

THE PIPE PENETRATIONS.

3. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE

GROUTED AND SEALED TO PROVIDE LEAK-PROOF

INSTALLATION.

SOUTH

PIPE

PIPE

PIPE

PIPE3/4

NORTH

WEST EAST

SOUTH

PIPE

PIPE

PIPE

PIPE

3/4

WEST

PIPEPIPE

PIPE

NORTH

WEST

SOUTH

PIPEPIPE

EAST

PIPEPIPE

PIPEPIPE

NORTH

SOUTH

WEST

PIPEPIPE

PIPEPIPE

PIPEPIPE

1 1

EAST

PIPEPIPE

PIPE

PIPEPIPE

NORTH

EAST

SOUTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:2 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE ELECTRICAL

BUTTERFLY DETAILS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

E-502

GENERAL NOTES

NTS

MANHOLE "MH-8" BUTTERFLY DETAIL

EP407

NTS

MANHOLE "MH-9" BUTTERFLY DETAIL

EP408

- NTS

A MANHOLE "MH-2A"

NTS

MANHOLE "MH-12A"

A

NTS

MANHOLE "MH-12B"

B

NTS

MANHOLE "MH-13A"

A

NTS

MANHOLE "MH-13B"

B

NTS

MANHOLE "MH-12A" AND "MH-12B" BUTTERFLY DETAIL

EP410

NTS

MANHOLE "MH-13A" AND "MH-13B" BUTTERFLY DETAIL

EP411

- NTS

B MANHOLE "MH-2B"

NTS

MANHOLE "MH-2A" AND "MH-2B" BUTTERFLY DETAIL

EP401

Revisions: Date:

1. BUTTERFLY DETAILS SHOWN FOR VAULT PENETRATION

COORDINATION. NUMBER INSIDE PENETRATION CIRCLE

INDICATES RACEWAY DIAMETER IN INCHES. EXACT

LOCATIONS OF PENETRATIONS AND VAULT

DIMENSIONS/LAYOUT ARE DIAGRAMMATICAL; CONTRACTOR

FIELD VERIFICATION AND COORDINATION SHALL BE

REQUIRED. AFTER CONSTRUCTION IS COMPLETE,

CONTRACTOR SHALL PROVIDE REDLINE DRAWINGS TO

FULLY AS-BUILD MANHOLES.

2. COORDINATE WITH THE MECHANICAL SET REGARDING

EXACT SIZING OF THE PIPES AND EXACT LOCATIONS OF

THE PIPE PENETRATIONS.

3. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE

GROUTED AND SEALED TO PROVIDE LEAK-PROOF

SOUTH

PIPEPIPE

PIPEPIPE

3/4

3/4

NORTH

WEST EAST

SOUTH

PIPEPIPE

PIPEPIPE

3/4

NORTH

WEST EAST

SOUTH

PIPE

PIPE

3/4

PIPE

PIPE

TUNNEL

NORTH

WEST EAST

SOUTH

PIPE

PIPE

PIPE

PIPE

PIPE

PIPE

PIPE

TUNNEL

3/4

NORTH

WEST EAST

SOUTH

PIPE

PIPE

3/4

PIPE

PIPE

NORTH

WEST

SOUTH

PIPE PIPE

PIPE PIPE

3/4

EAST

PIPE PIPE

PIPE PIPE

NORTH

WEST EAST

SOUTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:2 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

MANHOLE ELECTRICAL

BUTTERFLY DETAILS -

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

E-503

GENERAL NOTES

NTS

MANHOLE "MH-15" BUTTERFLY DETAIL

EP412

NTS

MANHOLE "MH-16" DETAIL

EP413

NTS

MANHOLE "MH-18B" DETAIL

EP415

NTS

MANHOLE "MH-19" DETAIL

EP416

NTS

MANHOLE "MH-20" DETAIL

EP417

NTS

MANHOLE "MH-18AA" AND MANHOLE "MH-18AB" BUTTERFLY DETAIL

EP414

- NTS

A MANHOLE "MH-18AA"

Revisions: Date:

- NTS

B MANHOLE "MH-18AB"

NTS

MANHOLE "OMH-5" DETAIL

EP418

1. BUTTERFLY DETAILS SHOWN FOR VAULT PENETRATION

COORDINATION. NUMBER INSIDE PENETRATION CIRCLE

INDICATES RACEWAY DIAMETER IN INCHES. EXACT

LOCATIONS OF PENETRATIONS AND VAULT

DIMENSIONS/LAYOUT ARE DIAGRAMMATICAL; CONTRACTOR

FIELD VERIFICATION AND COORDINATION SHALL BE

REQUIRED. AFTER CONSTRUCTION IS COMPLETE,

CONTRACTOR SHALL PROVIDE REDLINE DRAWINGS TO

FULLY AS-BUILD MANHOLES.

2. COORDINATE WITH THE MECHANICAL SET REGARDING

EXACT SIZING OF THE PIPES AND EXACT LOCATIONS OF

THE PIPE PENETRATIONS.

3. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE

GROUTED AND SEALED TO PROVIDE LEAK-PROOF

AUDIO-VISUAL OR VISUAL ONLY ALARM,

COORDINATE WITH VA FOR EACH CONTROL

PANEL LOCATION TO PROVIDE ALARM

DEVICE AS REQUIRED.

60"

GFCI DUPLEX RECEPTACLE,

20A, 120V, WITH

WEATHERPROOF WHILE-IN-

USE COVER. BOX AND

COVER SHALL BE DIE-CAST

ALUMINUM, AND LOCKABLE.

SUMP PUMP CONTROL PANEL

VERTICAL AND HORIZONTAL

RACK SUPPORTS, SLOTTED

CHANNEL STRUT,

STAINLESS STEEL,

1-5/8" x 1-5/8" (MIN), LENGTH

AS REQUIRED

BACKBOARD SHALL BE 3/8"

STAINLESS STEEL. COLOR AS

CHOSEN BY VA.

CONDUIT, TYPICAL

CONDUIT STRAP, TYPICAL

ANCHOR BOLTS,

1/4"-DIA x 12" L (MIN.), STAINLESS STEEL

FINISHED GRADE

CONCRETE FOOTING WITH

CHAMFERED EDGE, 3000-PSI,

12"-DIA x 36" L (MIN.)

DETAIL NOTES:

1. ALL FASTENING HARDWARE SHALL BE STAINLESS STEEL.

2. MINIMUM RACEWAY SIZE SHALL BE 3/4".

3. NOT ALL CONDUITS MAY BE SHOWN FOR CLARITY.

REFERENCE ENLARGED PLANS FOR ADDITIONAL

INFORMATION.

2kVA TRANSFORMER, NEMA 3R, 208-120/240V, 3PH, 4W

E-505C-4

P-5

P-4

P-3

RESURFACE IN

ACCORDANCE WITH FINAL

REQUIREMENTS-SOD IN

LAWN AREAS, ASPHALT OR

CONCRETE IN

PAVED AREAS. SEE CIVIL

OR SPECIFICATIONS FOR

PATCHING IN ASPHALT

AREAS.

INSTALL RED PLASTIC IDENTIFICATION STRIP

AT 12" DEEP THE FULL LENGTH, WITH

METALLIC TRACER WIRE THE FULL LENGTH,

LABLED "DANGER BURIED ELECTRICAL"

6" OR MORE OF CLEAN SAND

OR APPROVED EXCAVATED

MATERIAL

36" MINIMUM BURIAL DEPTH

FOR UTILITIES

INCLUDING POWER,

DATA AND

TELEPHONE OR AS

AMENDED BY THE

SERVING UTILITY. 24" MINIMUM

BURIAL DEPTH FOR SITE

LIGHTING/POWER

BACKFILL 95%

COMPACTION

CONDUIT TYPE, SIZE, AND

QUANTITY AS SPECIFIED

7-1/2" 7-1/2"

FINISHED GRADE

AUDIBLE-VISUAL ALARM

GFCI DUPLEX RECEPTACLE, 20A,

120V, WITH WEATHERPROOF

WHILE-IN-USE COVER. BOX AND

COVER SHALL BE DIE-CAST

ALUMINUM, AND LOCKABLE.

SUMP PUMP CONTROL PANEL

CONDUIT, TYPICAL

CONDUIT STRAP, TYPICAL

FINISHED GRADE

DETAIL NOTES:

1. UTILIZE STAINLESS STEEL FASTENING HARDWARE AND

ANCHORS TO ATTACH EQUIPMENT TO WALL AS REQUIRED.

2. MINIMUM RACEWAY SIZE SHALL BE 3/4".

3. NOT ALL CONDUITS MAY BE SHOWN FOR CLARITY. REFERENCE

ENLARGED PLANS FOR ADDITIONAL INFORMATION.

2kVA TRANSFORMER, NEMA 3R, 208-120/240V, 3PH, 4W

E-505

SLOTTED CHANNEL STRUT,

STAINLESS STEEL,

1-5/8" x 1-5/8" (MIN), LENGTH

AS REQUIRED, TYPICAL

C-4

P-5

P-4

P-3

FINISHED PAVING

UNDISTURBED SOIL OR SELECT

BACKFILL COMPACTED

(4) NO 6 REBAR

48"

24" MIN

8" DIAMETER GALVANIZED

STEEL PIPE FILLED WITH 3,500-PSI CONCRETE.

APPLY (2) COATS YELLOW PAINT.

CONCRETE CAP

36"

DETAIL NOTES:

1. PROVIDE CEME-TUBE BOLLARD, OR APPROVED

EQUAL.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/0

/2

:4

:3 a m

B

IM

/6

-2

-1

J B

V A

M O

J B

S te a m

F a ilu re s /V

A J B

S

F E

L

S D

B .r v t

TYPICAL ELECTRICAL DETAILS

WM/MM JBB/JFO

100% CONSTRUCTION

DOCUMENTS

04/24/2024

657-23-115JBCorrect Campus Steam Failure - St.

Louis, MO (Jefferson Barracks

Division)

ST. LOUIS COUNTY, MISSOURI

E-504

- 1" = 1'-0"

2 TYPICAL SUMP PUMP CONTROL PANEL INSTALLATION DETAIL (RACK MOUNTED)

- NTS

1 TYPICAL TRENCHING DETAIL

GENERAL NOTES

KEY NOTES

Revisions: Date:

- 1" = 1'-0"

3 TYPICAL SUMP PUMP CONTROL PANEL INSTALLATION DETAIL (WALL MOUNTED)

1. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR SHALL

PROVIDE DETAILED AND DIMENSIONED SHOP DRAWINGS

INDICATING PROPOSED ELECTRICAL EQUIPMENT LAYOUT FOR ALL

ELECTRICAL EQUIPMENT INSTALLATIONS DURING THE SUBMITTAL

PRO…

This is the start of the file's text. The full file is on GovTribe.