_657-23-115JB_100_Drawings_Book_3_Electrical.pdf
PDF 9 MB Posted
- Attached to
- Z1DA--657-23-115JB Correct Campus Steam System Failures, JB Federal contract opportunity
- Solicitation number
- 36C25524R0096
About this file
This document is a set of construction drawings related to a federal contract opportunity for the Department of Veterans Affairs (VA) to correct campus steam system failures at the Jefferson Barracks Division of the St. Louis VA Medical Center.
The key details are:
- The project is titled "Correct Campus Steam System Failures, JB" with solicitation number 36C25524R0096 and project number 657-23-115JB.
- The work includes construction to improve steam and condensate system functionality, manhole access, safety, remote valve operation, monitoring of manhole components, and compliance with VA and industry standards.
- The scope of work includes architectural, mechanical, and electrical construction such as upgrading manholes, replacing compensators, steam valves, condensate pumps, sump pumps, and providing electrical controls and monitoring.
- The period of performance is estimated to be 180 days and includes mobilization, construction, inspection, closeout, and documentation.
- The contract is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J
AREA SHOWN
MANHOLE
"MH-7B"
MANHOLE
"MH-7A"
SP-7
STEAM TRAP SENSOR
(TYP)
ACTUATED VALVE (TYP)
(E) 14" COMPENSATOR
S
TS
S
TS
A V
A V
E-504
E-504
MANHOLE
"MH-7B"
SP-6A,B
LSHH
LSH
LSL
LEVEL SWITCH (TYP)
MANHOLE
"MH-7A"
TYP.
A V
C-1
P-1
C-3
C-2
C-3
P-1 P-2
C-2
C-3
MH-7A AND MH-7B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:2 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-7A' AND 'MH-7B'
ENLARGED ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP406
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
2'0 4' 6'
PROJECT
NORTH
3/8" = 1'-0"ES101
1 MANHOLE 'MH-7A' AND 'MH-7B' ENLARGED DEMO ELECTRICAL PLANS
3/8" = 1'-0"ES101
2 MANHOLE 'MH-7A' AND 'MH-7B' ENLARGED REVISED ELECTRICAL PLANS
2'0 4' 6'
PROJECT
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-7" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-7" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO
PROVIDE LEAK-PROOF INSTALLATION.
Revisions: Date:
(E) 14" COMPENSATOR
"MH-8"
MANHOLE
SP-8
(E) 14" COMPENSATOR
SP-7A,B
"MH-8"
MANHOLE
LSL
LSH
LSHH
LEVEL SWITCH (TYP)
E-504
E-504
STEAM TRAP
SENSOR
STS
P-1
C-1
C-2
P-2
P-1
MH-8
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:3 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-8' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP407
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
3/8" = 1'-0"ES101
1 MANHOLE 'MH-8' ENLARGED DEMO ELECTRICAL PLANS
3/8" = 1'-0"ES101
2 MANHOLE 'MH-8' ENLARGED REVISED ELECTRICAL PLANS2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS-STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-8" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-8" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO
VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-
BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING
CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE
SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.
Revisions: Date:
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO
PROVIDE LEAK-PROOF INSTALLATION.
MH-9
(E) 14" COMPENSATOR
SP-9
MANHOLE
"MH-9"
(E) 14" COMPENSATOR
STEAM TRAP SENSOR
MANHOLE
"MH-9"
LSHH
LSH
LSL
LEVEL SWITCH
(TYP)
STS
E-504
E-504
SP-8A,B
P-1
C-1
C-2
P-2
P-1
AREA SHOWN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:4 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-9' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP408
KEY NOTES
KEY PLAN
GENERAL NOTES
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
3/8" = 1'-0"ES101
1 MANHOLE 'MH-9' ENLARGED DEMO ELECTRICAL PLANS
3/8" = 1'-0"ES101
2 MANHOLE 'MH-9' ENLARGED REVISED ELECTRICAL PLANS
TRUE
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE
VAULT(S) TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S),
UNLESS OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-9" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-9" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO
PROVIDE LEAK-PROOF INSTALLATION.
(E) 14" COMPENSATOR
SP-10
MANHOLE
"MH-10"
(E) 14" COMPENSATOR
SP-9A,B
MANHOLE
"MH-10"
STEAM TRAP SENSOR
LSHH
LSH
LSL
LEVEL SWITCH (TYP)
S T S
E-504
E-504
P-1
P-1
C-2
P-2
C-1
E-504
MH-10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:5 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-10' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP409
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
3/8" = 1'-0"ES101
1 MANHOLE 'MH-10' ENLARGED DEMO ELECTRICAL PLANS 2'0 4' 6'
PROJECT
NORTH
3/8" = 1'-0"ES101
2 MANHOLE 'MH-10' ENLARGED REVISED ELECTRICAL PLANS 2'0 4' 6'
PROJECT
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS-STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-10" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-10" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
CONCRETE BOLLARD. COORDINATE EXACT LOCATIONS WITH VA.
Revisions: Date:
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
ACTUATED
VALVE (TYP)
STEAM TRAP SENSOR (TYP)
SP-10A,B
MANHOLE
"MH-12A"
MANHOLE
"MH-12B"
S T S
S T
S
LSHH
LSH
LSL
E-504
E-504
LEVEL SWITCH
AV
A V
A V
P-1
C-1
C-3
C-3
C-3
C-2
C-2
P-1 P-2
SP-12
MANHOLE
"MH-12A"
MANHOLE
"MH-12B"
MH-12A AND MH-12B
AREA SHOWN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:0 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-12A' AND 'MH-12B'
ENLARGED ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP410
KEY PLAN
GENERAL NOTES
1/4" = 1'-0"ES101
2 MANHOLE 'MH-12A' AND 'MH-12B' ENLARGED REVISED ELECTRICAL PLANS
1/4" = 1'-0"ES101
1 MANHOLE 'MH-12A' AND 'MH-12B' ENLARGED DEMO ELECTRICAL PLANS
BASED ON FIELD INVESTIGATION
NO VOLTAGE/POWER WAS OBSERVED
IN EXISTING VAULT
2'0 4' 8'
PROJECT
NORTH
2'0 4' 8'
PROJECT
NORTH
TRUE
NORTH
Revisions: Date:
KEY NOTES
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE TO BE DEMOLISHED AND REPLACED WITH JUNCTION BOX.
EXISTING CONDUCTORS TO BE PRESERVED AND PROTECTED FOR REUSE.
PROVIDE STAINLESS-STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-12" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-12" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO
VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-
BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING
CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE
SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO
J
J
AREA SHOWN
SP-13
MANHOLE
"MH-13B"
MANHOLE
"MH-13A"
MINI-POWER ZONE
STEAM TRAP SENSOR (TYP)
ACTUATED VALVE (TYP)
MANHOLE
"MH-13A”
MANHOLE
“MH-13B”
STS
AV
E-504
A V
AV
SP-11A,B
LSL
LSH
LSHH
LEVEL SWITCH (TYP)
A V
STS
STS
C-1
C-3
P-1
C-2
C-3C-3
C-2
C-3
P-1
C-2
MINI-POWER ZONE
P-2
MH-13A AND MH-13B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:1 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-13A AND MH-13B'
ENLARGED ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP411
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
2'0 4' 6'
PROJECT
NORTH
3/8" = 1'-0"ES101
1 MANHOLE 'MH-13A' AND 'MH-13B' ENLARGED DEMO ELECTRICAL PLANS
3/8" = 1'-0"ES101
2 MANHOLE 'MH-13A' AND 'MH-13B' ENLARGED REVISED ELECTRICAL PLANS
2'0 4' 6'
PROJECT
NORTH
BASED ON FIELD INVESTIGATION
NO VOLTAGE/POWER WAS OBSERVED
IN EXISTING VAULT
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLES BELOW MINI-POWER ZONE TO REMAIN.
EXISTING JUNCTION BOX TO BE DEMOLISHED AND REPLACED. EXISTING
CONDUCTORS TO BE PRESERVED AND PROTECTED FOR REUSE.
PROVIDE CONTROL PANEL "CP-MH-13" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO
VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-
BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING
CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE
SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.
PROVIDE STAINLESS-STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-13" AS INDICATED.
JUNCTION BOX SHALL BE LOCATED HIGH WITHIN MANHOLE TO AVOID FLOODING.
Revisions: Date:
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO
J J
MANHOLE
"MH-15"
SP-15
MANHOLE
"MH-15"
SP-12A,B
LSHH
LSH
LSL
LEVEL SWITCH (TYP)
E-504
E-504
S
TS
STEAM TRAP
SENSOR
P-1
C-1
C-2
P-1
P-2
MH-15
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:2 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-15' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP412
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
2'0 4' 8'
PROJECT
NORTH
- 1/2" = 1'-0"
1 MANHOLE 'MH-15' ENLARGED DEMO ELECTRICAL PLANS
1/2" = 1'-0"ES101
2 MANHOLE 'MH-15' ENLARGED REVISED ELECTRICAL PLANS
BASED ON FIELD INVESTIGATION
NO VOLTAGE/POWER WAS OBSERVED
IN EXISTING VAULT
2'0 4' 8'
PROJECT
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
EXISTING JUNCTION BOX TO BE DEMOLISHED AND REPLACED. EXISTING
CONDUCTORS TO BE PRESERVED AND PROTECTED FOR REUSE.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-15" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-15" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO
VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-
BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING
CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE
SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO
PROVIDE LEAK-PROOF INSTALLATION.
SP-16
(E) 14" COMPENSATOR
MANHOLE
"MH-16"
SP-13A,B
(E) 14" COMPENSATOR
STEAM TRAP SENSOR
MANHOLE
"MH-16"
LSHH
LSH
LSL
LEVEL SWITCH
(TYP)
STS
E-504 1
E-504
P-1
C-1
C-2
P-2
P-1
MH-16
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:3 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-16' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP413
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
3/8" = 1'-0"ES101
1 MANHOLE 'MH-16' ENLARGED DEMO ELECTRICAL PLAN
3/8" = 1'-0"ES101
2 MANHOLE 'MH-16' ENLARGED ELECTRICAL PLAN2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO
PROVIDE LEAK-PROOF INSTALLATION.
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-16" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-16" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
333333
J J
MANHOLE
"MH-18AA"
SP-14
MANHOLE
"MH-18AB"
MANHOLE
"MH-18AA"
S T S
S T S
SP-14A,B
A V
A V
ACTUATED VALVE
(TYP)
STEAM TRAP SENSOR
(TYP)
E-504
E-504
MANHOLE
"MH-18AB"
LSHH
LSH
LSL
C-1
P-2
P-1
P-1
C-2
C-2
C-3
C-3
AREA SHOWN
MH-18A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:3 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-18A' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP414
1/4" = 1'-0"ES101
1 MANHOLE 'MH-18A' ENLARGED DEMO ELECTRICAL PLANS
BASED ON FIELD INVESTIGATION
NO VOLTAGE/POWER WAS OBSERVED
IN EXISTING VAULT
1/4" = 1'-0"ES101
2 MANHOLE 'MH-18A' ENLARGED REVISED ELECTRICAL PLANS
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-18A" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-18A" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO
VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-
BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING
CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE
SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.
Revisions: Date:
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
MH-18B
SP-18
MANHOLE
"MH-18B"
SP-15A,B
MANHOLE
"MH-18B"
LSHH
LSH
LSL
LEVEL SWITCH (TYP)
STEAM TRAP
SENSOR
STS
E-504
E-504
C-1
C-2
P-2 P-1
P-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:4 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-18B' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP415
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-18B" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-18B" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO
VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-
BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING
CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE
SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.
1/2" = 1'-0"ES101
1 MANHOLE 'MH-18B' ENLARGED DEMO ELECTRICAL PLANS
1/2" = 1'-0"ES101
2 MANHOLE 'MH-18B' ENLARGED REVISED ELECTRICAL PLANS1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
Revisions: Date:
BASED ON FIELD INVESTIGATION
NO VOLTAGE/POWER WAS OBSERVED
IN EXISTING VAULT
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
MANHOLE
"MH-19"
SP-19
SP-16A,B
ACTUATED VALVE
MANHOLE
"MH-19"
STEAM TRAP SENSOR (TYP)
LSHH
LSH
LS
STS
STS
STS
STS
LEVEL SWITCH (TYP)
E-504
E-504
AV
AV
AV
AV
C-3C-3
C-3
C-3
P-2
C-2
C-2
P-1
P-1
C-1
C-2
C-2
MH-19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:5 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-19' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP416
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
3/8" = 1'-0"ES101
1 MANHOLE 'MH-19' ENLARGED DEMO ELECTRICAL PLANS
3/8" = 1'-0"ES101
2 MANHOLE 'MH-19' ENLARGED REVISED ELECTRICAL PLANS 2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-19" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-19" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
Revisions: Date:
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
"MH-20"
MANHOLE
SP-20
SP-17A,B
"MH-20"
MANHOLE
ACTUATED VALVE
STEAM TRAP SENSOR (TYP)
LSHH
LSH
LSL
LEVEL SWITCH (TYP)
STS
STS
STS
E-504
E-504
AV
AV
A V
P-1 P-1
P-2
C-2
C-2
C-2
C-3
C-3
C-3
C-1
MH-20
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:0 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'MH-20' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP417
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
3/8" = 1'-0"ES101
1 MANHOLE 'MH-20' ENLARGED DEMO ELECTRICAL PLANS
3/8" = 1'-0"ES101
2 MANHOLE 'MH-20' ENLARGED REVISED ELECTRICAL PLANS2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE AND ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-MH-20" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-MH-20" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
333333
Revisions: Date:
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
OLD MH-5
STS
STS
STS
STS
LSHH
LSH
LSL
AV
AV
AV
E-504
E-504
SP-18A,B
C-3
C-3
C-3
C-2
C-2
C-2
C-2
P-1
P-1
C-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:1 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE 'OMH-5' ENLARGED
ELECTRICAL PLANS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
EP418
Revisions: Date:
KEY NOTES
KEY PLAN
GENERAL NOTES
TRUE
NORTH
2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
EXISTING SUMP PUMP AND ASSOCIATED CONDUIT AND WIRING WITHIN THE VAULT(S)
TO BE DEMOLISHED BACK TO POWER POINT OF ENTRY OF VAULT(S), UNLESS
OTHERWISE NOTED.
EXISTING RECEPTACLE TO BE DEMOLISHED AND REPLACED WITH JUNCTION
BOX. EXISTING CONDUCTORS TO BE PRESERVED AND PROTECTED FOR REUSE.
PROVIDE STAINLESS STEEL NEMA 4X JUNCTION BOX (6"Hx6"Wx4"D, MIN.) TO SPLICE
EXISTING CONDUCTORS AND PROVIDE POWER TO CONTROL PANEL. PROVIDE
RACEWAYS AND CONDUCTORS TO CONTROL PANEL "CP-OMH-5" AS INDICATED.
JUNCTION BOX TO BE LOCATED HIGH WITHIN THE MANHOLE TO AVOID FLOODING.
PROVIDE CONTROL PANEL "CP-OMH-5" AS INDICATED. FINAL LOCATION OF CONTROL
PANEL TO BE COORDINATED WITH VA.
CONTRACTOR SHALL PROVIDE CIRCUIT TRACING BACK TO PANELBOARD SOURCE TO
VERIFY EXISTING VAULT POWER FEEDER; CONTRACTOR SHALL DOCUMENT AND AS-
BUILD FINDINGS. CONTRACTOR SHALL REMOVE AND REPLACE EXISTING
CONDUCTORS WHILE MAINTAINING EXISTING RACEWAY; CONDUCTORS SHALL BE
SIZED FOR VOLTAGE DROP PER NEC. COORDINATE WITH VA AS REQUIRED.
3/8" = 1'-0"ES101
1 MANHOLE 'OLD MH-5' ENLARGED DEMO ELECTRICAL PLANS
3/8" = 1'-0"ES101
2 MANHOLE 'OLD MH-5' ENLARGED REVISED ELECTRICAL PLANS
BASED ON FIELD INVESTIGATION
NO VOLTAGE/POWER WAS OBSERVED
IN EXISTING VAULT
1. ALL EXISTING EQUIPMENT WITHIN MANHOLES MAY NOT BE SHOWN. CONTRACTOR
SHALL FIELD VERIFY SITE PRIOR TO BID TO FAMILIARIZE THEMSELVES WITH
EXISTING SITE CONDITIONS.
2. LOCATIONS OF EXISTING UNDERGROUND UTILITIES ARE SHOWN IN AN APPROXIMATE
MANNER.
3. ALL CONDUIT SHALL BE ROUTED TO AVOID ALL OTHER UNDERGROUND PIPING AND
ANY OTHER OBSTRUCTION. NOT ALL UNDERGROUND PIPING IS SHOWN FOR CLARITY;
COORDINATE WITH OTHER DISCIPLINES AND ENGINEERED DRAWINGS AS REQUIRED.
4. ALL ELECTRICAL WORK SHALL BE CLOSELY COORDINATED WITH PROJECT PHASING.
COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
5. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. COORDINATE WITH VA FOR FINAL LOCATIONS OF ALL EQUIPMENT PRIOR TO
INSTALLATION.
7. NOT ALL CONDUIT AND WIRE MAY BE SHOWN. REFERENCE WIRING AND
CONNECTION DIAGRAMS FOR WIRING REQUIREMENTS.
8. EXISTING MANHOLE POWER FEEDER(S) FROM PANELBOARD SOURCE TO
MANHOLE(S) IS UNKNOWN. CONTRACTOR SHALL PROVIDE FIELD INVESTIGATION TO
FULLY AS-BUILD EXISTING FEEDERS [CONDUCTORS AND RACEWAYS (QUANTITY,
SIZE, AND CONDITION)] FROM PANELBOARD SOURCE TO EQUIPMENT LOADS WITHIN
MANHOLE(S).
9. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE GROUTED AND SEALED TO
PROVIDE LEAK-PROOF INSTALLATION.
NORTH
WEST EAST
SOUTH
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE3/4
12 1
NORTH
WEST EAST
SOUTH
PIPE
PIPE
PIPE
PIPE
3/4
2 1 1
NORTH
WEST EAST
SOUTH
PIPE PIPE
3/4
NORTH
WEST EAST
SOUTH
PIPE PIPE
3/4
1 1
NORTH
WEST
SOUTH
PIPE PIPE
PIPE
PIPE
EAST
3/4
1 1
NORTH
WEST
SOUTH
PIPE
PIPEPIPE
PIPE PIPE
PIPE
EASTPIPE
PIPE
PIPE
PIPE 3/4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:1 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE ELECTRICAL
BUTTERFLY DETAILS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
E-501
GENERAL NOTES
NTS
MANHOLE "MH-10" BUTTERFLY DETAIL
EP409
NTS
MANHOLE "MH-3" BUTTERFLY DETAIL
EP402
NTS
MANHOLE "MH-4" BUTTERFLY DETAIL
EP403
NTS
MANHOLE "MH-5" BUTTERFLY DETAIL
EP404
NTS
MANHOLE "MH-6A"
A
NTS
MANHOLE "MH-6B"
B
NTS
MANHOLE "MH-7A"
A
NTS
MANHOLE "MH-7B"
B
NTS
MANHOLE "MH-6A" AND "MH-6B" BUTTERFLY DETAIL
EP405
NTS
MANHOLE "MH-7A" AND "MH-7B" BUTTERFLY DETAIL
EP406
1. BUTTERFLY DETAILS SHOWN FOR VAULT PENETRATION
COORDINATION. NUMBER INSIDE PENETRATION CIRCLE
INDICATES RACEWAY DIAMETER IN INCHES. EXACT
LOCATIONS OF PENETRATIONS AND VAULT
DIMENSIONS/LAYOUT ARE DIAGRAMMATICAL; CONTRACTOR
FIELD VERIFICATION AND COORDINATION SHALL BE
REQUIRED. AFTER CONSTRUCTION IS COMPLETE,
CONTRACTOR SHALL PROVIDE REDLINE DRAWINGS TO
FULLY AS-BUILD MANHOLES.
2. COORDINATE WITH THE MECHANICAL SET REGARDING
EXACT SIZING OF THE PIPES AND EXACT LOCATIONS OF
THE PIPE PENETRATIONS.
3. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE
GROUTED AND SEALED TO PROVIDE LEAK-PROOF
INSTALLATION.
SOUTH
PIPE
PIPE
PIPE
PIPE3/4
NORTH
WEST EAST
SOUTH
PIPE
PIPE
PIPE
PIPE
3/4
WEST
PIPEPIPE
PIPE
NORTH
WEST
SOUTH
PIPEPIPE
EAST
PIPEPIPE
PIPEPIPE
NORTH
SOUTH
WEST
PIPEPIPE
PIPEPIPE
PIPEPIPE
1 1
EAST
PIPEPIPE
PIPE
PIPEPIPE
NORTH
EAST
SOUTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:2 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE ELECTRICAL
BUTTERFLY DETAILS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
E-502
GENERAL NOTES
NTS
MANHOLE "MH-8" BUTTERFLY DETAIL
EP407
NTS
MANHOLE "MH-9" BUTTERFLY DETAIL
EP408
- NTS
A MANHOLE "MH-2A"
NTS
MANHOLE "MH-12A"
A
NTS
MANHOLE "MH-12B"
B
NTS
MANHOLE "MH-13A"
A
NTS
MANHOLE "MH-13B"
B
NTS
MANHOLE "MH-12A" AND "MH-12B" BUTTERFLY DETAIL
EP410
NTS
MANHOLE "MH-13A" AND "MH-13B" BUTTERFLY DETAIL
EP411
- NTS
B MANHOLE "MH-2B"
NTS
MANHOLE "MH-2A" AND "MH-2B" BUTTERFLY DETAIL
EP401
Revisions: Date:
1. BUTTERFLY DETAILS SHOWN FOR VAULT PENETRATION
COORDINATION. NUMBER INSIDE PENETRATION CIRCLE
INDICATES RACEWAY DIAMETER IN INCHES. EXACT
LOCATIONS OF PENETRATIONS AND VAULT
DIMENSIONS/LAYOUT ARE DIAGRAMMATICAL; CONTRACTOR
FIELD VERIFICATION AND COORDINATION SHALL BE
REQUIRED. AFTER CONSTRUCTION IS COMPLETE,
CONTRACTOR SHALL PROVIDE REDLINE DRAWINGS TO
FULLY AS-BUILD MANHOLES.
2. COORDINATE WITH THE MECHANICAL SET REGARDING
EXACT SIZING OF THE PIPES AND EXACT LOCATIONS OF
THE PIPE PENETRATIONS.
3. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE
GROUTED AND SEALED TO PROVIDE LEAK-PROOF
SOUTH
PIPEPIPE
PIPEPIPE
3/4
3/4
NORTH
WEST EAST
SOUTH
PIPEPIPE
PIPEPIPE
3/4
NORTH
WEST EAST
SOUTH
PIPE
PIPE
3/4
PIPE
PIPE
TUNNEL
NORTH
WEST EAST
SOUTH
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
TUNNEL
3/4
NORTH
WEST EAST
SOUTH
PIPE
PIPE
3/4
PIPE
PIPE
NORTH
WEST
SOUTH
PIPE PIPE
PIPE PIPE
3/4
EAST
PIPE PIPE
PIPE PIPE
NORTH
WEST EAST
SOUTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:2 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
MANHOLE ELECTRICAL
BUTTERFLY DETAILS -
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
E-503
GENERAL NOTES
NTS
MANHOLE "MH-15" BUTTERFLY DETAIL
EP412
NTS
MANHOLE "MH-16" DETAIL
EP413
NTS
MANHOLE "MH-18B" DETAIL
EP415
NTS
MANHOLE "MH-19" DETAIL
EP416
NTS
MANHOLE "MH-20" DETAIL
EP417
NTS
MANHOLE "MH-18AA" AND MANHOLE "MH-18AB" BUTTERFLY DETAIL
EP414
- NTS
A MANHOLE "MH-18AA"
Revisions: Date:
- NTS
B MANHOLE "MH-18AB"
NTS
MANHOLE "OMH-5" DETAIL
EP418
1. BUTTERFLY DETAILS SHOWN FOR VAULT PENETRATION
COORDINATION. NUMBER INSIDE PENETRATION CIRCLE
INDICATES RACEWAY DIAMETER IN INCHES. EXACT
LOCATIONS OF PENETRATIONS AND VAULT
DIMENSIONS/LAYOUT ARE DIAGRAMMATICAL; CONTRACTOR
FIELD VERIFICATION AND COORDINATION SHALL BE
REQUIRED. AFTER CONSTRUCTION IS COMPLETE,
CONTRACTOR SHALL PROVIDE REDLINE DRAWINGS TO
FULLY AS-BUILD MANHOLES.
2. COORDINATE WITH THE MECHANICAL SET REGARDING
EXACT SIZING OF THE PIPES AND EXACT LOCATIONS OF
THE PIPE PENETRATIONS.
3. ALL MANHOLE CONDUIT PENETRATIONS SHALL BE
GROUTED AND SEALED TO PROVIDE LEAK-PROOF
AUDIO-VISUAL OR VISUAL ONLY ALARM,
COORDINATE WITH VA FOR EACH CONTROL
PANEL LOCATION TO PROVIDE ALARM
DEVICE AS REQUIRED.
60"
GFCI DUPLEX RECEPTACLE,
20A, 120V, WITH
WEATHERPROOF WHILE-IN-
USE COVER. BOX AND
COVER SHALL BE DIE-CAST
ALUMINUM, AND LOCKABLE.
SUMP PUMP CONTROL PANEL
VERTICAL AND HORIZONTAL
RACK SUPPORTS, SLOTTED
CHANNEL STRUT,
STAINLESS STEEL,
1-5/8" x 1-5/8" (MIN), LENGTH
AS REQUIRED
BACKBOARD SHALL BE 3/8"
STAINLESS STEEL. COLOR AS
CHOSEN BY VA.
CONDUIT, TYPICAL
CONDUIT STRAP, TYPICAL
ANCHOR BOLTS,
1/4"-DIA x 12" L (MIN.), STAINLESS STEEL
FINISHED GRADE
CONCRETE FOOTING WITH
CHAMFERED EDGE, 3000-PSI,
12"-DIA x 36" L (MIN.)
DETAIL NOTES:
1. ALL FASTENING HARDWARE SHALL BE STAINLESS STEEL.
2. MINIMUM RACEWAY SIZE SHALL BE 3/4".
3. NOT ALL CONDUITS MAY BE SHOWN FOR CLARITY.
REFERENCE ENLARGED PLANS FOR ADDITIONAL
INFORMATION.
2kVA TRANSFORMER, NEMA 3R, 208-120/240V, 3PH, 4W
E-505C-4
P-5
P-4
P-3
RESURFACE IN
ACCORDANCE WITH FINAL
REQUIREMENTS-SOD IN
LAWN AREAS, ASPHALT OR
CONCRETE IN
PAVED AREAS. SEE CIVIL
OR SPECIFICATIONS FOR
PATCHING IN ASPHALT
AREAS.
INSTALL RED PLASTIC IDENTIFICATION STRIP
AT 12" DEEP THE FULL LENGTH, WITH
METALLIC TRACER WIRE THE FULL LENGTH,
LABLED "DANGER BURIED ELECTRICAL"
6" OR MORE OF CLEAN SAND
OR APPROVED EXCAVATED
MATERIAL
36" MINIMUM BURIAL DEPTH
FOR UTILITIES
INCLUDING POWER,
DATA AND
TELEPHONE OR AS
AMENDED BY THE
SERVING UTILITY. 24" MINIMUM
BURIAL DEPTH FOR SITE
LIGHTING/POWER
BACKFILL 95%
COMPACTION
CONDUIT TYPE, SIZE, AND
QUANTITY AS SPECIFIED
7-1/2" 7-1/2"
FINISHED GRADE
AUDIBLE-VISUAL ALARM
GFCI DUPLEX RECEPTACLE, 20A,
120V, WITH WEATHERPROOF
WHILE-IN-USE COVER. BOX AND
COVER SHALL BE DIE-CAST
ALUMINUM, AND LOCKABLE.
SUMP PUMP CONTROL PANEL
CONDUIT, TYPICAL
CONDUIT STRAP, TYPICAL
FINISHED GRADE
DETAIL NOTES:
1. UTILIZE STAINLESS STEEL FASTENING HARDWARE AND
ANCHORS TO ATTACH EQUIPMENT TO WALL AS REQUIRED.
2. MINIMUM RACEWAY SIZE SHALL BE 3/4".
3. NOT ALL CONDUITS MAY BE SHOWN FOR CLARITY. REFERENCE
ENLARGED PLANS FOR ADDITIONAL INFORMATION.
2kVA TRANSFORMER, NEMA 3R, 208-120/240V, 3PH, 4W
E-505
SLOTTED CHANNEL STRUT,
STAINLESS STEEL,
1-5/8" x 1-5/8" (MIN), LENGTH
AS REQUIRED, TYPICAL
C-4
P-5
P-4
P-3
FINISHED PAVING
UNDISTURBED SOIL OR SELECT
BACKFILL COMPACTED
(4) NO 6 REBAR
48"
24" MIN
8" DIAMETER GALVANIZED
STEEL PIPE FILLED WITH 3,500-PSI CONCRETE.
APPLY (2) COATS YELLOW PAINT.
CONCRETE CAP
36"
DETAIL NOTES:
1. PROVIDE CEME-TUBE BOLLARD, OR APPROVED
EQUAL.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/0
/2
:4
:3 a m
B
IM
/6
-2
-1
J B
V A
M O
J B
S te a m
F a ilu re s /V
A J B
S
F E
L
S D
B .r v t
TYPICAL ELECTRICAL DETAILS
WM/MM JBB/JFO
100% CONSTRUCTION
DOCUMENTS
04/24/2024
657-23-115JBCorrect Campus Steam Failure - St.
Louis, MO (Jefferson Barracks
Division)
ST. LOUIS COUNTY, MISSOURI
E-504
- 1" = 1'-0"
2 TYPICAL SUMP PUMP CONTROL PANEL INSTALLATION DETAIL (RACK MOUNTED)
- NTS
1 TYPICAL TRENCHING DETAIL
GENERAL NOTES
KEY NOTES
Revisions: Date:
- 1" = 1'-0"
3 TYPICAL SUMP PUMP CONTROL PANEL INSTALLATION DETAIL (WALL MOUNTED)
1. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR SHALL
PROVIDE DETAILED AND DIMENSIONED SHOP DRAWINGS
INDICATING PROPOSED ELECTRICAL EQUIPMENT LAYOUT FOR ALL
ELECTRICAL EQUIPMENT INSTALLATIONS DURING THE SUBMITTAL
PRO…
This is the start of the file's text. The full file is on GovTribe.