630001_SCAT_Vault_Rm_-_Drawings-_PERMIT_SET_5-23.pdf
PDF 14 MB Posted
- Attached to
- Vault Room and Oil Room Project
- Solicitation number
- 262820MKM
- Issued by
- Sarasota County, Florida
About this file
This is a permit set of architectural drawings for the Vault Room and Oil Room Project in Florida. The drawings depict the design specifications for a construction project that involves expanding the vault room from one vault to two vaults through building expansion, performing stucco repairs, completing interior and exterior painting, modifying the oil room, and installing overhead doors. The permit set drawings provide detailed floor plans, elevations, and construction details necessary for the County to solicit competitive bids from qualified contractors. The documentation establishes the technical requirements and specifications that bidders must use to prepare accurate cost estimates and project schedules for the construction work.
The drawings serve as the primary reference documents for contractors to understand the scope of work, site conditions, and construction standards required for this expansion project. Bidders are expected to review these architectural plans in conjunction with the solicitation documents to determine project complexity, material requirements, and labor needs. The permit set establishes baseline design parameters that contractors must follow, ensuring consistency in quality and compliance with applicable building codes and County standards for the vault and oil room modifications.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
SITE
PROJECT
LOCATION
05-10-2024
CONSTRUCTION DOCUMENTS
BREEZE TRANSIT
Wendel Project No. 630001
SERVICE LANE
5303 PINKNEY AVE, SARASOTA, FL 34233
VAULT ROOM IMPROVEMENTS
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
DRAWING INDEX
SHEET
NUMBER SHEET NAME
REVISION
NUMBER DATE
STRUCTURAL
S001 STRUCTURAL NOTES AND
ABBREVIATIONS
0 05-10-2024
S101 FOUNDATION AND FRAMING PLANS 0 05-10-2024
S300 WALL ELEVATIONS AND SECTIONS 0 05-10-2024
S301 TYPICAL DETAILS 0 05-10-2024
ARCHITECTURE
A000 TITLES & SYMBOLS 0 05-10-2024
A001 TITLES & SYMBOLS 0 05-10-2024
A002 ARCHITECTURAL SITE PLAN 0 05-10-2024
A003 EXISTING SITE PLAN & SITE DEMOLITION 0 05-10-2024
A004 CODE PLANS 0 05-10-2024
A100 FLOOR PLAN & DETAIL 0 05-10-2024
A101 ROOF PLAN, DETAILS & 3D VIEW 0 05-10-2024
A400 BUILDING ELEVATIONS & SECTIONS 0 05-10-2024
A401 SECTION DETAILS 0 05-10-2024
A920 DOOR & HARDWARE SCHEDULE & FINISH
SCHEDULE & REFLECTED CEILING PLAN
0 05-10-2024
ELECTRICAL
E001 ELECTRICAL SYMBOLS, ABBREVIATIONS,
& NOTES
0 05-10-2024
E101 GROUND LEVEL - ELECTRICAL WORK 0 05-10-2024
INDICATES ASPHALT PAVEMENT
PLAN VIEW
INDICATES 95% COMPACTED FREE
DRAINING SUB-BASE (STRUCTURAL FILL)
INDICATES NATIVE (EXISTING) SOIL
INDICATES APPROXIMATE FINAL GRADE,
SEE SITE DRAWINGS
INDICATES CONCRETE
SECTION VIEWDESCRIPTION OF MATERIAL
INDICATES CONCRETE MASONRY
INDICATES 98% COMPACTED FREE
DRAINING SUB-BASE (STRUCTURAL FILL)
INDICATES STEEL
INDICATES DEMOLISHED AREA
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO PREPARATION OF SHOP
DRAWINGS.
2. ALL WORK SHALL CONFORM TO THE LATEST EDITIONS OF THE FLORIDA BUILDING CODE, THE AISC CODE, THE ACI BUILDING CODE (ACI 318), THE AMERICAN WELDING SOCIETY CODE (AWS) AND ALL OTHER
APPLICABLE STANDARDS. IN CASES OF CONFLICT, THE MOST STRINGENT SHALL GOVERN.
3. FOR ALL CONSTRUCTION MATERIALS AND METHODS, THE CONTRACTOR IS RESPONSIBLE FOR
TEMPORARY BRACING, BRIDGING, OR SHORING AS REQUIRED FOR SAFETY, STABILITY, AND ALIGNMENT OF THE STRUCTURE. BRACING AND SHORING SHALL BE KEPT IN PLACE UNTIL PERMANENT STRUCTURAL
SUPPORT IS FULLY EFFECTIVE.
4. DELEGATED DESIGN MAY BE REQUIRED FOR A NUMBER OF STRUCTURAL SYSTEMS (I.E. COLD-FORMED METAL FRAMING, TRUSSES, PRECAST CONCRETE, STEEL CONNECTIONS, SOIL SHORING, ETC.). REFER TO
PROJECT SPECIFICATIONS FOR DESIGN CRITERIA AND OTHER PROJECT REQUIREMENTS.
5. REFER TO PROJECT SPECIFICATIONS FOR TESTING, INSPECTION, AND OTHER REQUIREMENTS.
6. A SPECIAL INSPECTION PROGRAM HAS BEEN DEVELOPED IN ACCORDANCE WITH BUILDING CODE
REQUIREMENTS. REFER TO PROJECT SPECIFICATIONS FOR SPECIAL INSPECTION REQUIREMENTS.
1. FOUNDATIONS ARE DESIGNED BASED ON ASSUMED SOIL BEARING CONDITIONS. CONTRACTOR WILL BE RESPONSIBLE TO ENSURE SOIL BEARING CONDITIONS HAVE BEEN ACHIEVED. REFER TO SPECIFICATIONS
FOR SPECIAL INSPECTION REQUIREMENTS.
A. ALLOWABLE SOIL BEARING CAPACITY: 2,000 PSF
B. MODULUS OF SUBGRADE REACTION: 100 PCI
2. EXTERIOR CONSTRUCTION SHALL BE CARRIED DOWN NOT LESS THAN 1 FEET BELOW FINISHED EXTERIOR
GRADE.
3. COMPACT FOUNDATION SUBGRADES TO A MINIMUM OF 98% MODIFIED PROCTOR DENSITY AT OPTIMUM
MOISTURE CONTENT.
4. THE SUB-BASE FOR THE SLABS ON GRADE IS TO BE PLACED AND COMPACTED TO A MINIMUM OF 95%
MODIFIED PROCTOR DENSITY AT OPTIMUM MOISTURE CONTENT.
1. ALL WORK SHALL CONFORM TO THE LATEST EDITION OF THE "BUILDING CODE REQUIREMENTS FOR
CONCRETE MASONRY STRUCTURES" (ACI-530) AND SPECIFICATIONS (ACI 530.1).
2. CONCRETE MASONRY MATERIALS SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES:
A. HOLLOW CONCRETE MASONRY UNITS CONFORMING TO ASTM C90, TYPE I, WITH A MINIMUM
NET COMPRESSIVE STRENGTH OF 2800 PSI.
B. TYPE S MORTAR (ABOVE GRADE) AND TYPE M MORTAR (BELOW GRADE) FOR REINFORCED
MASONRY, IN ACCORDANCE WITH ASTM C270, WITH A MINIMUM 28 DAY COMPRESSIVE
STRENGTH OF 1800 PSI.
C. GROUT FOR REINFORCED MASONRY, IN ACCORDANCE WITH ASTM C476, WITH A MINIMUM 28
DAY COMPRESSIVE STRENGTH OF 3000 PSI. GROUT SOLID ALL BOND BEAMS AND CORES WITH
VERTICAL REINFORCING.
D. THE MASONRY SYSTEM HAS BEEN DESIGNED FOR A MINIMUM 28-DAY COMPRESSIVE
STRENGTH (F’m) OF 2000 PSI.
3. PROVIDE REINFORCING BARS CONFORMING TO ASTM A615, GRADE 60. PROVIDE CONTINUOUS 9-GAGE
HORIZONTAL JOINT REINFORCING AT 16 INCHES VERTICAL SPACING.
4. BRACE THE TOPS OF ALL WALLS TO THE STRUCTURE FOR LATERAL STABILITY.
1. CONCRETE SHALL BE NORMAL WEIGHT (UON) AND HAVE THE FOLLOWING MINIMUM COMPRESSIVE
STRENGTH AT 28 DAYS:
A. FOOTINGS 4000 PSI
B. INTERIOR SLABS ON GRADE 4000 PSI
C. EXTERIOR SLABS ON GRADE 5000 PSI
2. ALL BAR REINFORCEMENT SHALL CONFORM TO ASTM 615, GRADE 60. WELDED WIRE FABRIC
REINFORCEMENT SHALL CONFORM TO ASTM A1065.
3. ALL WORKMANSHIP AND MATERIAL SHALL CONFORM TO THE "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES" (ACI-315), AND BUILDING CODE REQUIREMENTS FOR
REINFORCED CONCRETE (ACI-318).
4. CONDUITS IN CONCRETE SLABS SHALL BE SPACED SUCH THAT THE CENTER TO CENTER DISTANCE BETWEEN CONDUITS IS A MINIMUM OF THREE TIMES THE OUTSIDE DIAMETER OF THE LARGEST CONDUIT.
CONDUITS HAVING OUTSIDE DIAMETER LARGER THAN ONE THIRD OF THE SLAB THICKNESS SHALL NOT BE PERMITTED. CONDUITS THAT CROSS EACH OTHER IN THE SLAB SHALL NOT CONSUME MORE THAN ONE
THIRD OF THE SLAB THICKNESS AT THE POINT OF INTERSECTION.
5. ALUMINUM CONDUITS ARE NOT PERMITTED IN CONCRETE ELEMENTS.
1. DETAIL, FABRICATE AND ERECT STRUCTURAL STEEL IN CONFORMANCE WITH THE AISC SPECIFICATIONS
AND CODES, LATEST EDITIONS.
2. PERFORM ALL WELDING USING QUALIFIED WELDERS AND IN ACCORDANCE WITH THE AWS "STRUCTURAL
WELDING CODE - STEEL", LATEST EDITION.
3. ALL STRUCTURAL STEEL SHALL BE NEW STEEL WHICH CONFORMS TO ASTM WITH THE FOLLOWING MINIMUM FOR YIELD STRESS (Fy):
A. TUBULAR SHAPES 50 KSI, ASTM A500, GRADE C
B. ROUND SHAPES 36 KSI, ASTM A53, GRADE B
C. ALL OTHER STEEL 36 KSI, ASTM A36
D. HIGH STRENGTH BOLTS ASTM A325 OR A490
E. ANCHOR BOLTS 36 KSI OR 55 KSI, ASTM F1554
F. WELDING ELECTRODE E70XX
G. METAL DECK WELDING ELECTRODE E60XX MIN.
4. FOR CONNECTIONS TO THE EXISTING STRUCTURE, THE CONTRACTOR SHALL MAKE ALL NECESSARY MEASUREMENTS AND COORDINATE DETAILS WITH THE EXISTING CONDITIONS, PRIOR TO PREPARATION
OF SHOP DRAWINGS.
1. FABRICATE METAL DECKING FROM STEEL, WHICH CONFORMS TO ASTM A653, HAVING A MINIMUM YIELD STRENGTH OF 33 KSI. HOT DIP GALVANIZE ROOF DECK TO G90 REQUIREMENTS AND ALL OTHER METAL
DECK TO G60 REQUIREMENTS.
2. FASTEN ROOF DECKING AT 12 INCHES MAXIMUM ON CENTER TO THE SUPPORTING STEEL WITH A 5/8-INCH
DIAMETER WELD. WELD SIDE LAPS AT 12 INCHES MAXIMUM ON CENTER.
3. SEE SPECIFICATIONS AND APPROVED SHOP DRAWING FOR ADDITIONAL FLOOR AND ROOF DECK
FASTENING REQUIREMENTS.
1. DELEGATED DESIGN ITEMS SHALL BE DESIGNED, INCLUDING A COMPREHENSIVE ENGINEERING ANALYSIS, BY A QUALIFIED PROFESSIONAL ENGINEER USING PERFORMANCE REQUIREMENTS AND DESIGN CRITERIA
INDICATED IN THE DRAWINGS, PROJECT SPECIFICATIONS, AND APPLICABLE CODES.
2. BUILDING SYSTEMS AND COMPONENTS DESIGNATED AS DELEGATED DESIGN, AS INDICATED IN THE
PROJECT SPECIFICATIONS, INCLUDE BUT ARE NOT LIMITED TO:
A. ROOF PLANK SHORING
B. EXISTING MASONRY WALL SHORING
C. CONNECTIONS AND SUPPORT FOR ALL M.E.P. EQUIPMENT & PROCESSING COMPONENTS. MAJOR
COMPONENTS INCLUDE BUT ARE NOT LIMITED TO:
1. ROOF TOP UNIT CURBS
2. HVAC UNITS
3. EQUIPMENT
WALL COMPONENT AND CLADDING PRESSURES
EFFECTIVE
AREA (SF)
0-10
>500
ZONE: 4 (INTERIOR) ZONE: 5 (CORNER)
POSITIVE NEGATIVE POSITIVE NEGATIVE
44.9 48.7
40.3 44.1
38.3 42.1
36.3 40.1
33.7 37.5
44.9 59.9
40.3 50.7
38.3 46.7
36.3 42.7
33.7 37.5
ROOF COMPONENT AND CLADDING PRESSURES
EFFECTIVE
AREA (SF)
0-10
>500
ZONE: 2 (INTERIOR/EDGE)
POSITIVE NEGATIVE
20.0 103.2
18.7 96.6
17.1 87.8
16.0 81.2
16.0 65.8
ZONE: 3 (CORNER)
POSITIVE NEGATIVE
20.0 140.7
18.7 127.4
17.1 109.8
16.0 96.6
16.0 65.8
ROOF OVERHANG COMPONENT AND CLADDING PRESSURES
NOTES:
1.) ALL PRESSURES SHOWN ARE LRFD/ULTIMATE LEVEL.
MULTIPLY BY 0.6 FOR ASD/SERVICE LEVEL PRESSURES.
2.) MINIMUM PRESSURE = 16 PSF
3.) END ZONE DISTANCE, a = 3FT
EFFECTIVE
AREA (SF)
0-10
>500
ZONE: 2o (INTERIOR/EDGE)
POSITIVE NEGATIVE
-- 103.2
-- 94.4
-- 82.7
-- 73.8
-- 53.3
ZONE: 3o (CORNER)
POSITIVE NEGATIVE
-- 140.7
-- 125.2
-- 104.7
-- 89.2
-- 53.3
MASONRY
F'm = 2000 PSI
BAR
SIZE
SPLICE
LENGTH (IN)
4 17
5 23
6 43
7 58
8 87
NOTES
1. REINFORCING BARS ARE CLASSIFIED AS TOP BARS WHEN MORE THAN 12" OF CONCRETE IS CAST BENEATH RESPECTIVE
REINFORCING BAR
2. "SIDE LAP" ALL LAP SPLICES TO PROVIDE MAXIMUM MOMENT CAPACITY
4000 PSI NORMAL WEIGHT CONCRETE
TENSION
BAR
SIZE
DEV.
LENGTH
(IN)
CLASS B
SPLICE
LENGTH
TOP BAR
DEV.
LENGTH
(IN)
TOP BAR
SPLICE
LENGTH
(IN)
3 15 19 25
4 19 25 33
5 24 31 41
6 29 37 49
7 42 54 71
8 48 62 81
9 54 70 91
10 60 78 101
11 66 85 111
5000 PSI NORMAL WEIGHT CONCRETE
TENSION
BAR
SIZE
DEV.
LENGTH
(IN)
CLASS B
SPLICE
LENGTH
TOP BAR
DEV.
LENGTH
(IN)
TOP BAR
SPLICE
LENGTH
(IN)
3 13 17 22
4 17 23 29
5 22 28 36
6 26 34 44
7 38 49 63
8 43 56 72
9 48 63 81
10 54 69 90
11 59 76 99
NOTE:
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN,
AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF THE
ARCHITECT AND ENGINEER AND IS NOT TO BE USED IN WHOLE OR IN PART,
FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF THE
ARCHITECT AND ENGINEER. UNAUTHORIZED ALTERATION OR ADDITION TO
ANY SURVEY DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IS
PROHIBITED IN ACCORDANCE WITH STATE LAW, CODE AND RULES.
Wendel WD Architecture, Engineering, Surveying and Landscape Architecture, P.C
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
0 1" 2"
GENERIC SCALE BAR
SCALE BAR SHOWN IS TWO INCHES ON THE ORIGINAL DRAWING.
IF NOT TWO INCHES ON THIS SHEET, ADJUST ACCORDINGLY
DWG. No.
PROJ. No.
SCALE
DATE
DWG. TITLE
DWN. CHK.
NO. REVISIONS DATE
12" = 1'-0"
STRUCTURAL NOTES AND
ABBREVIATIONS
S001
05/10/24
DJP / MAW
630001
MAW / JDM
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
MATERIAL LEGEND
DESIGN LOADS
DESIGN CODE
2023 FLORIDA BUILDING CODE, BUILDING, EIGHTH EDITION
2023 FLORIDA BUILDING CODE, EXISTING BUILDING, EIGHTH
EDITION
BUILDING RISK CATEGORY II
DEAD LOADS
ROOFING MATERIALS 10 PSF
MATERIAL SELF-WEIGHT VARIES
LIVE LOADS
ROOF LIVE LOAD 20 PSF
GROUND FLOOR 150 PSF
WIND LOAD
ULTIMATE BASIC WIND SPEED (Vult) 150 MPH
ALLOWABLE BASIC WIND SPEED (Vasd) 117 MPH
EXPOSURE CATEGORY C
ULTIMATE STRUCTURAL SYSTEM PRESSURE 50 PSF
ULTIMATE COMPONENT & CLADDING PRESSURE VARIES
SEISMIC LOAD
SEISMIC IMPORTANCE FACTOR (Ie) 1.0
PROJECT LOCATION ZIP CODE 34233
SHORT PERIOD MAPPED ACCELERATION (SS) 0.048
1 SECOND PERIOD MAPPED ACCELERATION (S1) 0.026
SITE CLASS D
SHORT PERIOD DESIGN ACCELERATION (SDS) 0.051
1 SECOND PERIOD DESIGN ACCELERATION (SD1) 0.042
SEISMIC DESIGN CATEGORY A
GENERAL NOTES
FOUNDATION NOTES
CONCRETE MASONRY
CONCRETE & REINFORCING
STRUCTURAL STEEL
METAL DECK
DELEGATED DESIGN
CONCRETE COVER REQUIREMENTS
LOCATION MIN. COVER
CONCRETE CAST AGAINST SOIL 3"
OTHER CONCRETE BELOW GROUND 2"
EXTERIOR EXPOSED CONCRETE SURFACES 2"
INTERIOR EXPOSED CONCRETE SURFACES 1"
COMPONENTS AND CLADDING LOADS
STRUCTURAL COLUMN SCHEDULE
MARK SIZE
ANCHOR ROD BASEPLATE
REMARKSQTY DIA EMBED ASTM No. LENGTH THICK WIDTH ASTM No. DETAIL C-01 HSS8x6x1/2 4 1" 1' - 0" F1554 GR36 1' - 2" 1" 12" A36
COLUMN / POST FOOTING SCHEDULE
MARK
DIMENSIONS
REINFORCING (BOT UON) REMARKSLENGTH WIDTH DEPTH
F-6.0x6.4 6' - 0" 6' - 4" 2' - 0" (7)-#6 EW (T&B)
F-8.0x16.0 16' - 0" 8' - 0" 2' - 0" #6 @ 8" o.c. T&B (SHORT); #6 @ 12" o.c. T&B (LONG)
ABBREVIATIONS
A
A/E Architect/Engineer
AB Anchor Bolt
ACI American Concrete Institute
ADDL Additional
ADH Adhesive
ADJ Adjustable
AFF Above Finished Floor
AIA American Institute Of Architects
AISC American Institute Of Steel Construction
ALT Alternate
ALUM Aluminum
APA American Plywood Association
APPROX Approximate
ARCH Architect / Architectural
ASCE American Society Of Civil Engineers
ASD Allowable Strength Design
ASI Architect's Supplemental Instruction
ASPH Asphalt
ASTM American Society For Testing And Materials
AVG Average
AWPA American Wood Preservers' Association
AWS American Welding Society
B
B PL Base Plate
B/ Bottom Of
B/B Back To Back
BC Bottom Chord
BEV Bevel
BF Braced Frame
BLK Block
BM Bench Mark
BOC Beginning of Curve
BOT Bottom
BRG Bearing
BRG PL Bearing Plate
BTWN Between
C
CANTIL Cantilever
CB Catch Basin
CFMF Cold-Formed Metal Framing
CI Cast Iron
CIP Cast-In-Place
CJ Construction Joint
CJP Complete Joint Penetration
CL Center / Column Line
CLG Ceiling
CLR Clear
CM Construction Manager
CMU Concrete Masonry Unit
CO Cleanout
COL Column
CONC Concrete
CONN. Connection
CONSTR Construction
CONT Continuous
COORD Coordinate
COV Cover
CRSI Concrete Reinforcing Steel Institute
CSI Construction Specifications Institute
CTR Center
CW Concrete Wall
D
DBL Double
DEMO Demolition
DET Detail
DEV Development
DIA Diameter
DIM Dimension
ABBREVIATIONS
L
L Angle
LAD Ladder
LB Pound
LBF/FT Pound-Force Per Foot
LBF/SF Pound-Force Per Square Foot
LBF/SI Pound-Force Per Square Inch
LDFC Low Density Foam Concrete Fill
LF Linear Feet (Foot)
LL Live Load
LLH Long Leg Horizontal
LLV Long Leg Vertical
LOC Location
LONG Longitudinal
LRFD Load and Resistance Factor Design
LSH Long Side Horizontal
LSV Long Side Vertical
LVL Laminated Veneer Lumber
M
MAS Masonry
MATL Material
MAX Maximum
MECH Mechanical
MEP Mechanical / Electrical / Plumbing
MF Moment Frame
MFR Manufacturer
MIN Minimum
MIRR Mirror
MISC Miscellaneous
MO Masonry Opening
MTL Metal
N
N/A Not Applicable
NAVD North American Vertical Datum
NF Near Face
NIC Not In Contract
NS Near Side
NTS Not To Scale
O
O.F. Outside Face
OC On Center
OD Outside Diameter
OH Overhang
OPNG Opening
OPP Opposite
P
PCC PRECAST CONCRETE
PCF Pounds Per Cubic Foot
PCI Precast/Prestressed Concrete Institute
PERF Perforated
PERP Perpendicular
PJP Partial Joint Penetration
PL Plate
PLAT Platform
PLBG Plumbing
PLF Pounds Per Linear Foot
PLYWD Plywood
POI Point of Interconnection
POLY Polyethylene (Plastic)
POT Point of Tangent
PRCST Precast
PRELIM Preliminary
PROJ Projection
PROP Property
PSF Pounds Per Square Foot
PSI Pounds Per Square Inch
PSL Parallel Strand Lumber
PT Pressure Treated
PT CONC Post-Tensioned Concrete
ABBREVIATIONS
DL Dead Load
DP Drilled Pier
DWG Drawing
DWL Dowel
E
EA Each
EE Each End
EF Each Face
EJ Expansion Joint
EL Elevation
ELEC Electric
ELEV Elevator
ENGR Engineer
EOD Edge Of Deck
EOP Edge Of Plate
EOR Engineer Of Record
EOS Edge Of Slab
EQ Equal
EQUIP Equipment
ES Each Side
EST Estimate
EW Each Way
EX Existing
EXP Expansion
EXT Exterior
F
FAB Fabrication
FDN Foundation
FF EL Finish Floor Elevation
FIN Finish
FIN FLR Finish Floor
FLR Floor
FRMG Framing
FRP Fiberglass Reinforced Plastic
FS Far Side
FT Foot / Feet
FTG Footing
G
GA Gage / Gauge
GAL Gallon
GALV Galvanized
GC General Contractor
GLU LAM Glued Laminated Wood
GR BM Grade Beam
H
HCPP Hollow Core Precast Plank
HM Hollow Metal
HORIZ Horizontal
HSS Hollow Structural Steel
HT Height
I
I.F. Inside Face
ID Inside Diameter
INCL Included
INFO Information
INSUL Insulation
INT Interior
INV Invert
J
JT Joint
K
K Kip
KB Knee Brace
KSF Kip Per Square Foot
KSI Kips Per Square Inch
ABBREVIATIONS
PTN Partition
PVC Polyvinyl Chloride (Plastic)
PVMT Pavement
Q
QA Quality Assurance
QC Quality Control
QTY Quantity
R
R Radius
RD Roof Drain
REBAR Reinforcing Steel Bars
REF Reference
REINF Reinforce
REPL Replace
REQD Required
REV Revision
RH Roof Hatch
RO Rough Opening
ROW Right Of Way
RT Right
RTU Roof Top Unit
RV Roof Vent
S
S South
SCHED Schedule
SDI Steel Deck Institute
SECT Section
SF Square Foot (Feet)
SHT Sheet
SIM Similar
SJ Sawcut Joint
SJI Steel Joist Institute
SPEC Specification
SQ Square
SST Stainless Steel
STD. Standard
STIF Stiffener
STL Steel
STRUCT Structural
SURV Survey
SYMM Symmetrical
T
T Tread
T&B Top and Bottom
T/ Top of
T/CONC Top of Concrete
T/FDN Top of Foundation
T/FTG Top of Concrete Footing
T/MAS Top of Masonry
T/STEEL Top of Steel
T/WALL Top of Wall
TBD To Be Determined
TEMP Temporary
THK Thick / Thickness
TYP Typical
U
UL Underwriters Laboratories
UNO Unless Noted Otherwise
V
VAR Varies
VOL Volume
W w/ With
WD Wood
WF Wide Flange
WP Working Point
WT Weight
WWR Welded Wire Reinforcement
STRUCTURAL DRAWING LIST
DWG No. DRAWING TITLE
S001 STRUCTURAL NOTES AND ABBREVIATIONS
S101 FOUNDATION AND FRAMING PLANS
S300 WALL ELEVATIONS AND SECTIONS
S301 TYPICAL DETAILS
CMU REINF. SPLICE LENGTHCONCRETE REINF. BAR SPLICE LENGTH
0 ISSUED FOR PERMIT 05-10-2024
Jacob Mullen Snapshot
A
S300
S300
B
C
D
E.8
E.7
E.6
E.5
5'-7 1/2"
/8
24'-0" ±
C-0
C-0
24'-0" ±
'-0
'-0
'-0
F-8.0x16.0
6" SLAB ON GRADE
6x6 / W2.9xW2.9 W.W.R.
C-0
/4
S300
'-5
/8
'-7
3'-5" ± 3'-3" ±
S300
C-0
F-6.0x6.4
F-6.0x6.4
4 1/2"
S300
SIM
S301
TYP
EXISTING 24" SQ MASONRY COLUMN AND
8'-0"±x5'-0"± x2'-0"± THICK CONCRETE
FOOTING. TYPICAL OF 5 LOCATIONS
S J
SJ
SJ
S J
S J
S J
SJ
S301
S301
(2)-#4 ADD'L REINF
@ DOORS TYPICAL
2-#4x4'-0" RE-ENTRANT
BAR TYPICAL @ RE-
ENTRANT CORNERS
S J
SJ
S J
SJ
S J
SJ
SJ
SJ
S301
S301
EXISTING 8" CMU
WALL WITH CONC
FOOTING
6" SLAB-ON-GRADE w/ 6x6 / W2.9xW2.9 W.W.R., COORD
DIMENSIONS AND GRADING
w/ ARCH DWGs
6" SLAB-ON-GRADE w/ 6x6 / W2.9xW2.9 W.W.R., COORD
DIMENSIONS AND GRADING
w/ ARCH DWGs
C O
O R
D w
/ A R
C H
'L
5' - 4 1/2"
A
S300
S300
B
C
D
E.8
E.7
E.6
E.5
H S
S x6 x1
/2 H
S S x6 x1 /2
H S
S x6 x1
/2
HSS8x6x1/2
HSS8x6x1/2
5'-7 1/2"
/8
24'-0" ±
24'-0" ±
'-0
'-0
'-0
RD-01
HSS8x6x1/2
HSS8x6x1/2
S300 eW -0 eW-08 eW -0 eW-08
5'-7 1/2"
H S
S x6 x1
/2
H S
S x6 x1
/2 H
S S x6 x1 /2
H S
S x6 x1
/2 H
S S x6 x1 /2
H S
S x6 x1
/2
EQ EQ
S300
S300
E O
D
/2
EOD
4 1/2"
/2 "E
O D
C O
O R
D w
/ A R
C H
'L
4 1/2"
EOD
4"
1. TOP OF SLAB ELEVATION = +0'-6"; MATCH EXISTING SLAB-ON-GRADE ELEVATIONS.
UNLESS OTHERWISE NOTED AS T/SLAB:+ OR - FROM TOP OF SLAB ELEVATION.
COORDINATE w/ ARCH DRAWINGS FOR EXTERIOR SLAB DIMENSIONS AND SLOPES.
TOP FOOTINGS = -1'-4" BELOW TOP OF SLAB ELEVATION UNLESS OTHERWISE NOTED.
UNLESS OTHERWISE NOTED AS T/FTG +/- FROM TOP OF SLAB ELEVATION.
SEE PLAN AND SCHEDULES FOR SIZE, LOCATION AND REINFORCING.
2. ALL SLAB AS INDICATED ON PLAN
SJ INDICATES SAWCUT JOINT, SEE DETAIL XXX
FJ INDICATES FORMED JOINT, SEE DETAIL XXX
CONTRACTOR IS TO DETERMINE LOCATION OF ALL FORMED JOINTS.
3. COORDINATE ALL DOOR LOCATIONS AND SIZES w/ ARCH DRAWINGS AND DETAIL XXX .
4. COORDINATE w/ ARCH DRAWINGS FOR EXISTING SLAB DEMOLITION LOCATIONS AND DIMENSIONS. COORDINATE ALL NEW SLAB DIMENSIONS AND GRADING w/ ARCH DRAWINGS AND DETAILS
ON S300 AND S301.
5. INDICATES APPROXIMATE EXTENT OF PAVEMENT REMOVAL AND RESTORATION. VERIFY EXTENTS OF EXISTING PAVEMENT REPAIRS IN THE FIELD AS REQUIRED FOR NEW CONSTRUCTION. MINIMUM REQUIREMENTS FOR ASPHALT AND CONCRETE REPAIRS ARE AS FOLLOWS:
A. STANDARD DUTY PAVEMENT SECTIONS (ASPHALT):
a. 1.5" TYPE SP-9.5 ASPHALTIC CONCRETE STRUCTURAL COURSE.
b. 8" BASE DOUBLE COURSE LIMEROCK BASE (LBR 100) MAX 6" LIFTS w/ 98% COMPACTION DENSITY.
c. 12" STABILIZED SUBGRADE (LBR 40) 98% COMPACTED DENSITY.
B. TYPICAL CONCRETE PAVEMENT SECTION:
a. 8" CONCRETE SLAB-ON-GRADE w/ 4x4 - W4.0xW4.0 W.W.R. AT TOP AND BOTTOM.
b. 12" STABILIZED SUBGRADE (LBR 40) 98% COMPACTED DENSITY.
c. SAWCUT JOINTS AT 12'-0" o.c. MAXIMUM.
2/S301 3/S301
6/S301
1. TOP OF SLAB ELEVATION = +0'-6" = MATCH EXISTING BUILDING TOP OF SLAB ELEVATION.
UNLESS OTHERWISE NOTED AS T/SLAB:+ OR - FROM TOP OF SLAB ELEVATION.
2. TOP OF STEEL ELEVATION = +10'-6" ABOVE FINISHED FLOOR ELEVATION.
UNLESS OTHERWISE NOTED AS (+ OR -) BELOW TOP OF STEEL ELEVATION.
3. INDICATES SPAN DIRECTION OF 1-1/2"x18 GA TYPE B METAL ROOF DECK
SEE SCHEDULE FOR TOTAL DEPTH, REINFORCING AND DECK INFORMATION.
4. INDICATES DECK PENETRATION, SEE DETAIL XXX
5. FOR COLUMN SCHEDULE AND BASEPLATE DETAILS, SEE DWG S001
6. ALL STRUCTURAL STEEL FRAMING AND COMPONENTS TO BE FINISHED WITH A HIGH-PERFORMANCE COATING. SEE SPECIFICATIONS FOR REQUIREMENTS.
RD-01
13/S301
NOTE:
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN,
AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF THE
ARCHITECT AND ENGINEER AND IS NOT TO BE USED IN WHOLE OR IN PART,
FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF THE
ARCHITECT AND ENGINEER. UNAUTHORIZED ALTERATION OR ADDITION TO
ANY SURVEY DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IS
PROHIBITED IN ACCORDANCE WITH STATE LAW, CODE AND RULES.
Wendel WD Architecture, Engineering, Surveying and Landscape Architecture, P.C
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
0 1" 2"
GENERIC SCALE BAR
SCALE BAR SHOWN IS TWO INCHES ON THE ORIGINAL DRAWING.
IF NOT TWO INCHES ON THIS SHEET, ADJUST ACCORDINGLY
DWG. No.
PROJ. No.
SCALE
DATE
DWG. TITLE
DWN. CHK.
NO. REVISIONS DATE
As indicated
FOUNDATION AND FRAMING
PLANS
S101
05/10/24
DJP / MAW
630001
MAW / JDM
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
SCALE: 1/4" = 1'-0"
FOUNDATION PLAN
SCALE: 1/4" = 1'-0"
ROOF FRAMING PLAN
0 ISSUED FOR PERMIT 05-10-2024
DATUM EL.
EL. +0' - 0"±
B/PARAPET
EL. +14' - 0"±
T/PARAPET
EL. +20' - 6"±
T/SLAB
EL. +0' - 6"
T/EXIST FTG
EL. -2' - 4"±
NEW 8" CMU GROUTED SOLID.
TOOTH IN NEW MASONRY WITH
EXISTING TO MAINTAIN
RUNNING BOND, TYP.
EXISTING PARAPET
EXISTING ROOF
PLANK BEYOND
EXISTING FOOTING
w / A
R C
H 'L
C O
O R
D
#6 BAR; BREAK-OUT EXISTING
END SHELL FOR BAR
INSTALLATION. GROUT
EXISTING CELL SOLID
w/ ARCH'L
COORD
2' - 8" MIN.
#6 DOWEL AT EA VERT BAR,
w/ 8" MIN. EMBED ADHESIVE
ANCHOR TO EXISTING
CONCRETE (TYP)
1' - 8" MIN.
STANDARD HOOKS AT
END OF HORIZ BARS
#6 BAR @ 8" o.c. AT
ENDS OF WALL
#6 BAR @ 16" o.c. UNLESS
NOTED OTHERWISE
12' - 4" ±
COORD w/ ARCH'L
DATUM EL.
EL. +0' - 0"±
B/PARAPET
EL. +14' - 0"±
T/PARAPET
EL. +20' - 6"±
PLANK BRG
EL. +16' - 6"±
T/EXIST FTG
EL. -2' - 4"±
EXISTING PARAPET
EXISTING 8" CMU WALL TO
BE DEMOLISHED
TOOTH MASONRY ALONG
EXISTING WALL TO REMAIN
EXISTING ROOF
PLANK BEYOND
12' - 4" ±
COORD w/ ARCH'L
EXISTING FOOTING TO REMAIN
DEMOLISH EXISTING 8"
CMU WALL TO EXISTING
FOOTING, CUT EXISTING
REBAR AS REQ'D
EXISTING
REINFORCEMENT
@32"o.c. ±
1. EXISTING MASONRY WALL IS A LOAD BEARING WALL. PRIOR TO THE START OF DEMOLITION, CONTRACTOR SHALL INSTALL TEMPORARY BRACING AND SHORING AS REQUIRED FOR SAFETY, STABILITY, AND ALIGNMENT OF THE STRUCTURE. CONTRACTOR SHALL ENGAGE A PROFESSIONAL ENGINEER, LICENSED IN THE STATE OF FLORIDA, TO DEVELOP A MASONRY WALL SHORING PLAN.
2. BRACING AND SHORING SHALL BE KEPT IN PLACE UNTIL PERMANENT STRUCTURAL SUPPORT IS FULLY EFFECTIVE. ALL SHORING REQUIREMENTS ARE MEANS AND METHODS, SOLELY RESPONSIBLE BY THE
CONTRACTOR.
3. DEMOLITION AND CONSTRUCTION WORK SHALL BE EXECUTED IN A SAFE, CAREFUL AND ORDERLY MANNER, WITH THE LEAST POSSIBLE NOISE, DUST AND DISTURBANCE TO THE OWNER. CONTRACTOR
SHALL COORDINATE CONSTRUCTION SEQUENCING WITH THE OWNER SO AS NOT TO DISRUPT THE
OWNER’S OPERATIONS.
4. CONTRACTOR SHALL PROTECT EXISTING BUILDING CONSTRUCTION AND EQUIPMENT SCHEDULED TO
REMAIN. COORDINATE DEMOLITION WITH THE DRAWINGS. REMOVE FROM PROJECT SITE ALL
DEMOLISHED MATERIALS NOT INDICATED TO BE SALVAGED. ALL DEMOLISHED MATERIALS BECOME THE
PROPERTY OF THE CONTRACTOR WHO SHALL LEGALLY DISPOSE OF SUCH MATERIALS.
5. FOR ALL REMOVALS, THE CONTRACTOR SHALL PATCH REMAINING SURFACES AS REQUIRED TO MATCH EXISTING ADJACENT SURFACES. CONTRACTORS SHALL PROTECT EXISTING CONDITIONS AND REPAIR
ALL DAMAGED AREAS PROMPTLY TO ITS ORIGINAL CONDITION.
DATUM EL.
EL. +0' - 0"±
T/O STEEL
EL. +10' - 6"
B/PARAPET
EL. +14' - 0"±
T/PARAPET
EL. +20' - 6"±
T/SLAB
EL. +0' - 6"
T/EXIST FTG
EL. -2' - 4"±
S300
S300
T/O NEW FTG
EL. -1' - 4"
S300
DATUM EL.
EL. +0' - 0"±
1 2
T/SLAB
EL. +0' - 6"
T/EXIST FTG
EL. -2' - 4"±
T/O NEW FTG
EL. -1' - 4"
5' - 0"3' - 0"
EXISTING
MASONRY WALL
NEW 8" CMU WALL GROUT SOLID
w/ #6@16"o.c., SEE PLAN
#6 DOWEL, 60"x12" LEGS AT 16" o.c.
EXISTING
FOOTING, V.I.F.
6" SLAB-ON-GRADE,
SEE PLAN
NEW FOUNDATION, SEE PLAN
AND SCHEDULE FOR
REINFORCEMENT
EXISTING SLAB
ON GRADE, V.I.F.
8" DIA., SCH 40 PIPE BOLLARD.
COORD. LOCATIONS w/ ARCH DWGs
SEE S300 DETAILS
T E
N S
IO
N
S P
L
IC
E T
E N
S
IO
N S
P L
IC
E
1' - 0"
THICKENED SLAB
AT SLAB EDGE, TYP
JOINT MATERIAL w/
SEALANT, TYP
EXISTING
FOOTING, V.I.F.
95% COMPACTED
STRUCTURAL FILL
PROOF-ROLLED AND
APPROVED SUBGRADE
AS DETERMINED BY
SOILS TESTING AGENCY
T/O STEEL
EL. +10' - 6"
B/PARAPET
EL. +14' - 0"±
PLANK BRG
EL. +16' - 6"±
EXISTING ROOF
PLANK
EXISTING CONC
PARAPET
1"EXP. JOINT
3/16 3-12
3/16 3-12
1/4" BENT PL
NEW 8" CMU WALL GROUT
SOLID w/ #6@16"o.c., (2) BOND BEAMS AT BOT w/ (2)-#6 CONT
#6 DOWEL @ 16" o.c. w/ 8" MIN
EMBED ADHESIVE ANCHOR
TO EXISTING PARAPET BEAM
BOND BEAM NEAR
TOP w/ (2)-#6 CONT
4" E.O.D.
T E
N S
IO
N
S P
L
IC
E
4 1/2"
T/O STEEL
EL. +10' - 6"
1/4" BENT PL
3/16 3-12
3/16 3-12
METAL ROOF DECK
8" BOND BEAM
w/ (2)-#6 CONT
E.O.D. SEE PLAN
1/2" COMPRESSIBLE
MATERIAL AT TOP OF CMU
AND UNDERSIDE OF METAL
ROOF DECK
8" CMU SOLID GROUT
w/ #6 BAR @ 16" o.c.
9-GAGE HORIZ JOINT
REINF. @ 16" o.c.
1 13
T/SLAB
EL. +0' - 6"
T/EXIST FTG
EL. -2' - 4"±
3' - 0"3' - 4"
FOOTING, SEE SCHEDULE
1/2" JOINT MATERIAL w/
SEALANT AT EXISTING COL
EXISTING COL
BASEPLATE AND ANCHORS,
SEE SCHEDULE
EXISTING FOOTING
6' - 0"
6" EXTERIOR SLAB
ON GRADE, SEE
8" DIA., SCH 40 PIPE BOLLARD.
COORD. LOCATIONS w/ ARCH DWGs
SEE S300 DETAILS 5/ S301
6" EXTERIOR SLAB
ON GRADE, SEE
PROOF-ROLLED AND
APPROVED SUBGRADE
AS DETERMINED BY
SOILS TESTING AGENCY
95% COMPACTED
STRUCTURAL FILL
3/8
MITER CUT
HSS @ 45°
60°
SEE PLAN
5' - 7 1/2"
SEE PLAN
HSS COL, SEE PLAN
HSS BEAM, SEE PLAN (TYP)
1/4" BENT PL. CONT
1 2
HSS CAP
PL. (TYP)
1/4
2-SIDES1-1/2" METAL
ROOF DECK
HSS BEAM
1/4 T&B
CL BM
TYPICAL BEAM TO BEAM
TYPICAL BEAM TO COL
HSS COL w/
CLOSURE PL.
1/4
HSS BEAM
SEE TYPICAL BEAM
TO BEAM DETAIL
SEE TYPICAL BEAM
TO COL DETAIL
NOTE:
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN,
AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF THE
ARCHITECT AND ENGINEER AND IS NOT TO BE USED IN WHOLE OR IN PART,
FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF THE
ARCHITECT AND ENGINEER. UNAUTHORIZED ALTERATION OR ADDITION TO
ANY SURVEY DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IS
PROHIBITED IN ACCORDANCE WITH STATE LAW, CODE AND RULES.
Wendel WD Architecture, Engineering, Surveying and Landscape Architecture, P.C
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
0 1" 2"
GENERIC SCALE BAR
SCALE BAR SHOWN IS TWO INCHES ON THE ORIGINAL DRAWING.
IF NOT TWO INCHES ON THIS SHEET, ADJUST ACCORDINGLY
DWG. No.
PROJ. No.
SCALE
DATE
DWG. TITLE
DWN. CHK.
NO. REVISIONS DATE
As indicated
WALL ELEVATIONS AND
SECTIONS
S300
05/10/24
DJP / MAW
630001
MAW / JDM
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
SCALE: 3/16" = 1'-0"
ELEVATION AT NEW CMU WALL
SCALE: 3/16" = 1'-0"
ELEVATION AT CMU WALL DEMOLITION
DEMOLITION AND SHORING NOTES:
SCALE: 1/4" = 1'-0"
BUILDING SECTION
SCALE: 3/4" = 1'-0"
SECTION AT FOUNDATION
SCALE: 3/4" = 1'-0"
FRAMING SECTION
SCALE: 3/4" = 1'-0"
FRAMING SECTION
SCALE: 3/4" = 1'-0"
FOUNDATION SECTION
SCALE: 3/4" = 1'-0"
TYPICAL CANOPY FRAME DETAILS
0 ISSUED FOR PERMIT 05-10-2024
SLAB SUB BASE
VAPOR RETARDER
WELDED WIRE REINF. (W.W.R.)
IN FLAT SHEETS (12" MIN. LAP)
GEOTEXTILE FABRIC
APPROVED SUBGRADE
M
IN
T H
IC
K
"D
S
LA
B
C V
R "D
NOTES:
1. MAXIMUM JOINT SPACING (FEET) = 3 x "D" ON CENTER
2. SAWCUT JOINT WITHIN 18 HOURS AFTER CONCRETE PLACEMENT
3. SEE TYPICAL SLAB ON GRADE DETAIL FOR ADD'L INFORMATION NOT
SHOWN
WELDED WIRE REINF (W.W.R.)
SAWCUT JOINT, FILL w/
JOINT MATERIAL AND SEALANT
D E
P T
H
"D
JO
IN
T
C V
R "D
T H
IC
K
"D
S
LA
B
WELDED WIRE REINF. (W.W.R.)1/8" CHAMFER, EA. SIDE. FILL w/
JOINT MATERIAL AND SEALANT
3/4" DIA. x 1'-6" LONG, SMOOTH DOWEL @ 12"o.c., GREASE &
WRAP ONE END IN PLASTIC
T H
IC
K
"D
S
LA
B
EQ EQ
"D
NOTES:
1. SEE TYPICAL SLAB ON GRADE DETAIL FOR
ADD'L INFORMATION NOT SHOWN
OPNG
IF LESS THAN 6'-0"
GROUT C.M.U. SOLID
BETWEEN OPNGs
UP TO 8'-0" MAX.
'W'
WALL REINF. WITHIN 8" OF
WALL END, CORNER OF
MOVEMENT JOINT
BOND BEAM SILL w/ REINF
BOND BEAM LINTEL w/ REINF
TYP EA. SIDE OF OPNG
WALL REINF > 32"o.c.
DOUBLE VERT WALL REINF
WALL REINF < 32"o.c.:
TRIPLE VERT REINF
NOTES:
1. FOR BOND BEAM REINF. SIZE AND QTY, SEE TYPICAL BOND BEAM DETAIL
2. GROUT CORES SOLID AT ALL REINFORCING
3. NO CONCENTRATED LOADS WITHIN W/2 ABOVE OPENING
4. COORDINATE ALL OPENING SIZES AND LOCATIONS WITH ALL OTHER DISCIPLINE DRAWINGS
5. COORDINATE LOCATION OF ALL WALL JOINTS WITH ARCHITECTURAL DRAWINGS.
OPNG
CONT. BOND BEAM AT PARAPET
/ FLOOR LINE / ROOF LINE
DWL's INTO FDN
WALL, MATCH VERT
REINF (TYP)
UPTO 8'-0" MAX.
'W'
L E
N G
T H
S P
L
IC
E
(TYP)
DEV
LENGTH
(T Y
P
D E
V
L E
N G
T H
(TYP)
DEV
LENGTH
HOOKED BAR WHERE DEV
LENGTH NOT ACHIEVED
CORNER BARS TO MATCH
BOND BEAM REINF (TYP)
BOND BEAM REINF
AT MASONRY INTERSECTION AT MASONRY CORNER
PLAN VIEW
SECTIONAL VIEW
NOTE:
COORDINATE w/ PLANS, OPENINGS
AND MASONRY CONTROL JOINTS.
L E
N G
T H
D E
V
STD. HOOK (TYP)
2-#4 CONT "W" = 6"
2-#5 CONT "W" = 8" AND 10"
2-#6 CONT "W" = 12"
GROUT CORES SOLID
PLAN
"W"
SEE
BOND BEAM BLOCK
w/ BREAKOUT WEB
NOTE:
1. FOR LINTELS NOT SPECIFICALLY DETAILED.
2. MASONRY LINTELS SHALL NOT BE INTERRUPTED BY MASONRY CONTROL JOINTS.
3. NO MASONRY CONTROL JOINTS WITHIN 2'-0" OF WALL OPENING
4. SEE PLANS FOR LOCATIONS AND SIZES OF ALL MASONRY OPENINGS, COORD.
WITH ARCH'L DWGs
M A
X
MASONRY
OPNG
DEPTH
"W"
6" 8" 10" 12"
<6'-0" 8" 2-#4 2-#4 2-#5 2-#6
COV
1/2" MIN
"W"
SEE PLAN
G R
O U
T E
D
D E
P T
H F
U L
L Y
"U" SHAPED
MASONRY LINTEL
BLOCK
2' - 0"
1' - 0" 1' - 0"
/2
DOME CONCRETE TOP
8" DIA, SCH 40 PIPE BOLLARD.
FILLED w/ CONC AND PAINTED
"SAFETY YELLOW"
JOINT MATERIAL
w/ SEALANT
CONC SLAB / PVMT
CONC ENCASEMENT
" 1
8" DIA, SCH 40 PIPE BOLLARD.
FILLED w/ CONC AND PAINTED
"SAFETY YELLOW"
DOME CONCRETE TOP
BUILDING FOOTING
3/4" BASE PL. w (4) 3/4" DIA.
ADHESIVE ANCHORS
(6 5/8" MIN. EMBED)
CONC SLAB / PVMT
JOINT MATERIAL w/ SEALANT
CONC ENCASEMENT
T/FOOTING
EL. SEE PLAN
TYPICAL BOLLARD TYPICAL BOLLARD AT BUILDING FOOTING
TAPER CONC
NOTES:
1. GRIND ALL EDGES AND WELDS
SMOOTH
2. GALVANIZE BOLLARDS AFTER
ASSEMBLY
1' - 0"
EQ EQ
E Q
E Q
1/4
TYP
1 1/2"
BOLLARD BASE PLATE
TAPER CONC
1' - 0" 1' - 0"
/2
DRILL AND EPOXY
GROUT #3@18"o.c.
x 18" LG DWL (TYP)
EMBED (TYP)
6" MIN
EXIST CONC SLAB
ON GRADE
E X
IS
T
M A
T C
H
M
IN
NATIVE SOIL
D /2
2-#4 ADD'L.
REINF., SEE PLAN
#4 BENT DWL
@ 12"o.c.
4'-0"
NOTE:
1. COORD. OPENING LOCATIONS & SLAB
REQUIREMENTS / CONNECTIONS w/ ARCH'L DWG's
2-#4 ADD'L
REINF, SEE
PLAN
#4@12"o.c.
x4'-0" LONG
SLAB JOINT AT FOUNDATION WALL
FULL SLAB OVER TOP FOUNDATION WALL
EQ EQ
E M
B E
D
" 2
P
LA
N "D
S
E E
JT MATERIAL
w/ SEALANT
T/ SLAB
EL. SEE PLAN
E M
B E
D
" P
LA
N "D
S
E E
T/ SLAB
EL. SEE PLAN
CL JOINT
DECK PENETRATION (DIM x DIM)
REINFORCING PL.
AS REQ'D.
#10 SCREW, FASTEN
REINF. PL. TO DECK @6"o.c.
MIN.
NOTE:
LIMITED TO ONE PENETRATION PER DECK SHEET/DECK SPAN, A GROUP OF
PENETRATIONS CLOSE TOGETHER REQUIRES A FRAMED OPENING SEE TYPICAL DETAIL.
METAL DECK PENETRATION SCHEDULE
DIM <6" NO REINFORCING
6" < DIM < 13"
DIM >13"
16ga. PL. (MIN.)
SEE DETAIL
6" M
IN
1 RIB
MIN.
SIZE OPNG REINFORCING
CL
CL
CL
PERIMETER
SUPPORT
STEEL
INTERIOR
SUPPORT
STEEL
INTERIOR
SUPPORT
STEEL
DECK PANEL
3'-0" WIDE
D E
C K
S
P A
N
NOTES:
1. FASTEN DECK EDGES AT 6" o.c. ALONG PERIMETER SUPPORT STEEL
2. FASTEN DECK AT 12"o.c. ALONG INTERIOR SUPPORT STEEL
3. FASTEN DECK SIDELAPS AT 12"o.c.
4. SEE SPECIFICATIONS FOR DECK AND FASTENER REQUIREMENTS
SEE NOTE 3
SEE NOTE 2
SEE NOTE 1
6'-0" MAX.
STRUCT. MEMBERS
6'-0" MAX.
STRUCT. MEMBERS
2'-0" MAX
'-0
M A
X
'-0
M
A X
L4x4x1/4
L4x4x1/4
L4 x4 x1 /4
L4 x4 x1 /4
SPAN OF DECK
L4x4x3/8
L4x4x3/8
L4 x4 x3 /8
L4 x4 x3 /8
STRUCT. MEMBER
WF BEAM OR JOIST
SEAT ANGLE
L4x4x3/8
(TYP)
FOR OPENINGS
2'-0" SQUARE MAXIMUM
FOR OPENINGS
2'-0" UP TO 6'-0" MAXIMUM
NOTE:
COORDINATE EXACT OPENING SIZE AND LOCATION WITH ACTUAL EQUIPMENT USED AND
WITH ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND CONTRACTORS
SPAN OF DECK
/8
1/8
1/8 3/16
MASONRY
OPENING
(M.O.) 4" WALL
3'-0" L3-1/2x3-1/2x1/4
4'-0" L4x3-1/2x1/4
6'-0" L5x3-1/2x5/16
MASONRY WALL THICKNESS
NOTES:
1. FOR LINTELS NOT SPECIFICALLY DETAILED IN EXISTING WALLS.
2. LINTELS IN EXTERIOR WALLS SHALL BE HOT-DIPPED GALVANIZED.
3. ANGLES SHALL BE LONG LEG VERTICAL UNLESS NOTED OTHERWISE
4. BEARING LENGTH AT EACH END SHALL BE 8" MINIMUM.
5. LINTELS IN EXTERIOR WALLS SHALL HAVE A MINIMUM THICKNESS OF 5/16".
6. COORDINATE EXACT SIZE, LOCATION AND QUANTITY WITH ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DWG's.
8" WALL
(2) L3-1/2x3-1/2x1/4
(2) L4x3-1/2x1/4
(2) L5x3-1/2x5/16
1/2" RADIUS
SITE PAVEMENT
1/2" JOINT MATERIAL
w/ SEALANT
6" CONCRETE SITE-SLAB w/ 6x6- W2.9xW2.9 WWR, COORD w/ ARCH
FOR LOCATIONS
#4 @ 16" o.c.
12"
24"
(2)-#4 CONT.
V A
R
IE
S
M
A X
M
IN
95% COMPACTED
STRUCTURAL FILL
NOTE: REFER TO ARCHITECTURAL PLANS FOR
SLAB LOCATIONS, GRADING, AND DIMENSIONS
NATIVE SOILS
L
W
EQ EQ
TYP
1 1/2"
T Y
P
/2
3/8" LEVELING PLATE
ON 1 1/8" MIN NON-
SHRINK GROUT
COLUMN, SEE
SCHEDULE FOR SIZE
TOP OF PIER / FTG.
HEAVY HEX HEADED ANCHOR
RODS (TYP), SEE SCHED. FOR
QUANTITY AND SIZE
PLAN VIEW
SECTIONAL VIEW
CL COL. & BASE
PL.
CL COL. & BASE
PL.
5/16
L E
N G
T H
E M
B E
D
WELDED PL. WASHER
NOTE:
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN,
AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF THE
ARCHITECT AND ENGINEER AND IS NOT TO BE USED IN WHOLE OR IN PART,
FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF THE
ARCHITECT AND ENGINEER. UNAUTHORIZED ALTERATION OR ADDITION TO
ANY SURVEY DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IS
PROHIBITED IN ACCORDANCE WITH STATE LAW, CODE AND RULES.
Wendel WD Architecture, Engineering, Surveying and Landscape Architecture, P.C
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
0 1" 2"
GENERIC SCALE BAR
SCALE BAR SHOWN IS TWO INCHES ON THE ORIGINAL DRAWING.
IF NOT TWO INCHES ON THIS SHEET, ADJUST ACCORDINGLY
DWG. No.
PROJ. No.
SCALE
DATE
DWG. TITLE
DWN. CHK.
NO. REVISIONS DATE
As indicated
TYPICAL DETAILS
S301
05/10/24
DJP / MAW
630001
MAW / JDM
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
NOT TO SCALE
TYPICAL SLAB DETAIL
NOT TO SCALE
TYPICAL SAWCUT JOINT (SJ)
NOT TO SCALE
TYPICAL FORMED JOINT (FJ)
NOT TO SCALE
ADDITIONAL CMU WALL REINFORCING
NOT TO SCALE
TYPICAL BOND BEAM
NOT TO SCALE
TYPICAL MASONRY LINTEL
SCALE: 3/8" = 1'-0"
BOLLARD DETAILS
SCALE: 3/4" = 1'-0"
NEW TO EXISTING SLAB CONNECTION
SCALE: 1/2" = 1'-0"
TYPICAL MASONRY WALL AT DOOR OPENING
SCALE: 3/4" = 1'-0"
METAL DECK PENETRATION
SCALE: 3/16" = 1'-0"
ROOF DECK FASTENER PATTERN
SCALE: 3/4" = 1'-0"
TYPICAL METAL DECK PENETRATION AT ROOF DECK
SCALE: 3/4" = 1'-0"
LOOSE LINTEL SCHEDULE
SCALE: 3/4" = 1'-0"
SECTION AT SIDEWALK CURB
NOT TO SCALE
TYPICAL SLAB DETAIL
0 ISSUED FOR PERMIT 05-10-2024
TYP FIXTURE MOUNTING HEIGHTS:
HAND
DRYER
(HD)
PAPER
TOWEL
DISPENSER
(PTD)
SOAP
DISPENSER
(SD)MIRROR
LAV.
M A
X
R
IM
M A
X
C O
N T
R O
LS
/3
"M
A X
"M A
X
/3
2"
GRAB
BAR(GB)
M
A X
COAT HOOK
(CH)
FINISHED FLOOR
SEAT WALL
3"MAXMAX
1 1/2"
30"MIN
TOWEL
PIN (TP)
60"MIN
GRAB
BARS
(GB)
*SEE PLAN FOR ACTUAL DIMENSIONS
CONTROL WALL
2 1/2" MAX
ROLL- IN SHOWER ACCESSORIES
GRAB
BARS
(GB)
SIDE WALL
30"MIN
FOLDING
SHOWER
SEAT (FSS)
FOLDING
SHOWER SEAT
(FSS)M
IN
16"MIN
27"MAX
"M
IN
"M A
X
CONTROLS,
FAUCETS AND
SHOWER
SPRAY
M
A X
"M
IN
4" MAX
M
IN
"M
A X
3"
-3 6"
6"MAX
ALIGN GB W/
EDGE OF FSS
15"-16 1/8"
6"MAX
SHELVING
ACCESSIBLE AND AMBULATORY WATER CLOSET*
*REAR WALL GRAB BAR NOT REQUIRED IN AMBULATORY COMPARTMENT
TRANSFER
SIDE
GRAB
BARS
(GB)
MIN
36"
MIN
24"
MIN
12"
C H
IL
D
16"-18"
A D
U L
T
GRAB
BARS
(GB)
TOILET PAPER
HOLDER (TPH)MAX
12"
MIN
42"
M
IN
/2
A D
U L
T
A D
U L
T
7" -1
9"
C H
IL
D
ADULT
39"- 41" CL
A D
U L
T
27"HX30"W MIN KNEE CLEARANCE
AT FRONT EDGE
9"HX11"D MIN KNEE CLEARANCE
DEPTH, FRONT OF LAV TO TRAP
(8"H WHEN 27"D MIN) THE DIP OF
THE OVERFLOW SHALL NOT BE
CONSIDERED
24"HX30"W MIN KNEE CLEARANCE
AT FRONT EDGE
KEYNOTES:
1. DIMENSIONS FROM THE
FINISHED FLOOR SHALL BE
TAKEN FROM THE LEADING
EDGE/FACE SHOWN TO
ACCOUNT FOR SLOPE IN FLOOR
2. WATER CLOSET HEIGHT IS TO
BE MEASURED FROM TOP OF
SEAT, SEATS SHALL NOT BE
SPRUNG TO RETURN TO THE
LIFTED POSITION
GENERAL NOTES:
M
A X
11" MAX
CL
KNEE CLEARANCE
"M
IN
MIN.
8"
MIN.
11"
MAX.
6"
M
IN
/3
"M
A X
WALL HUNG
ELEMENT
KNEE
CLEARANCE
17"-25"
DRINKING
FOUNTAIN
(DF)
SPOUT
HT
A D
U L
T
M
A X
FINISHED FLOOR
C H
IL
D
M
A X
A D
U L
T
C H
IL
D
DRINKING
FOUNTAIN
(DF)
STANDING USE
DRINKING FOUNTAIN
WHEELCHAIR USE
DRINKING FOUNTAIN
MAX
5"
SPOUT
HT
MIRROR
M
A X
AT TOILET OR
BATHING ROOMS
LOCATED OTHER
THAN ABOVE
COUNTERS OR
LAVATORIES
LAVATORY DRINKING FOUNTAIN
VARING DEPENDING
ON THE MAX. REACH
DEPTH
17"-19"
ACCESIBLE
WATER CLOSET
AMBULATORY
ACCESIBLE
WATER CLOSET
12"-18"
CHILD
A D
U L
T
CHILD
34"-36"
C H
IL
D
C H
IL
D
C H
IL
D
C H
IL
D
MAX
6"
M
IN
" 5
6"
CL
CL
CL
CL
AI PHONE
ROOM
WIZARD
CARD
READER
DOOR SIGNS , OUTLETS AND SWITCHES
ELECTRICAL DEVICE
VOICE AND DATA
DOOR KNOB
SWITCH
THERMOSTAT
FIRE STROBE
6" 6"
CL CL
CL
CL
CL
M
A X
FIRE EXTINGUISHER
CABINET
SEAT
COVER
DISPENSER
(SCD)
SANITARY
NAPKIN
DISPOSAL
UNIT
(SNDU)
0"
ACCESSIBLE
URINAL
M A
X
R
IM
7"
ACCESSORIES
WATER CLOSET
URINAL
A D
U L
T
8" -4
8"
DISPENSER
OUTLET
LOCATION
7"-9"
M
IN
/2
24" MIN
42" MAX
A D
U L
T
M
IN
C H
IL
D
M
IN
C H
IL
D
M
A X
DISPENSER OUTLET
LOCATION
MAX 2 TP ROLLS OF
NOT MORE THAN 5"
DIA. EACH
MIN
13 1/2"
M A
X
R
IM
CL CL
M
A X
DIAPER CHANGING
TABLE
*SEE PLAN FOR ACTUAL DIMENSIONS
TRANSFER SHOWER
SIDE WALL
CL
36" MIN
GRAB
BARS
(GB)
4" MAX
M
IN
"M
A X
3"
-3 6"
M
A X
11" MAX
36" MIN
1 1/2"
CONTROL WALL SIDE WALL
CL
36" MIN
2 1/2" MAX
M A
X
C O
N T
R O
LS
M A
X
C O
N T
R O
LS
CL
CL
ADA REACH RANGE FIGURES:
M
IN
M
A X
20" MAX
M
A X
>20" - 25" MAX
M
A X
10" MAX
4"
8"
4"
6"
10" MAX >10" - 24"MAX
UNOBSTRUCTED FORWARD REACH OBSTRUCTED HIGH FORWARD REACH
UNOBSTRUCTED SIDE REACH OBSTRUCTED HIGH SIDE REACH
5"
8"
1. THE PROJECT SPECIFICATIONS ARE AN INTEGRAL PART OF THE
CONTRACT DOCUMENTS AND WILL BE USED IN CONJUNCTION WITH THE
ARCHITECTURAL DRAWINGS AND GENERAL NOTES. IN CASES, IF ANY,
WHERE REQUIREMENTS INDICATED ON THE ARCHITECTURAL DRAWINGS
DIFFER FROM THE SPECIFICATIONS, NOTIFY THE ARCHITECT.
2. UNLESS OTHERWISE NOTED, DETAILS, SECTIONS AND NOTES CONTAINED
IN THE ARCHITECTURAL CONTRACT DOCUMENTS WILL BE CONSIDERED
TYPICAL FOR ALL SIMILAR CONDITIONS EVEN IF NOT EXPLICITLY
REFERENCED.
3. DEFICIENT WORK AND/OR WORK NOT IN CONFORMANCE WITH THE
CONTRACT DOCUMENTS WILL BE REPAIRED AT THE CONTRACTOR'S
EXPENSE. THE CONTRACTOR WILL REIMBURSE THE PARTIES REQUIRED
FOR PERFORMING THE DESIGN SERVICES ARISING FROM DEFICIENT
WORK, REVIEW OF MODIFICATIONS/CONTRACTOR SUBSTITUTION, OR
EXPEDITING OF SUBMITTALS.
4. COST OF INVESTIGATION AND/OR REDESIGN INCURRED BY THE
ARCHITECT DUE TO CONTRACTOR ERRORS WILL BE AT THE
CONTRACTOR'S EXPENSE.
5. VERIFY IN THE FIELD (VIF) ALL EXISTING JOB CONDITIONS, REVIEW ALL
CONTRACT DRAWINGS, AND VERIFY DIMENSIONS AND ELEVATIONS
NOTED IN THE CONTRACT DOCUMENTS PRIOR TO THE START OF WORK.
6. USE ONLY DIMENSIONS INDICATED ON THE DRAWINGS. DO NOT SCALE
THESE DRAWINGS OR USE DIMENSIONS OBTAINED FROM ELECTRONIC
DRAWING OR MODEL FILES, IF PROVIDED.
GENERAL NOTES: REFERENCE KEYNOTE LEGEND:
02 25 00 . A 01
ROOT
DECIMAL POINT
SUFFIX MODIFIER
SUFFIX
ROOT:
USE SAME SPECIFICATION NUMBER THAT REFERENCES ITEM
DECIMAL POINT:
SEPARATES ROOT FROM SUFFIX
SUFFIX:
USER DEFINED SINGLE ALPHA CHARACTER
(DO NOT USE THE LETTERS "I" OR "O"
SUFFIX MODIFIER:
OPTIONAL USER-DEFINED TWO-DIGIT NUMBER
REFERENCE KEYNOTE MODIFIER:
OPTIONAL TEXT NOTE LOCATED BELOW REFERENCE KEYNOTE. ONLY
APPEARS IN DRAWING BLOCKS, CONTAINED WITHIN PARENTHESIS
(R-VALUE 35)
REFERENCE KEYNOTE MODIFIER
NOTE:
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN,
AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF THE
ARCHITECT AND ENGINEER AND IS NOT TO BE USED IN WHOLE OR IN PART,
FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF THE
ARCHITECT AND ENGINEER. UNAUTHORIZED ALTERATION OR ADDITION TO
ANY SURVEY DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IS
PROHIBITED IN ACCORDANCE WITH STATE LAW, CODE AND RULES.
Wendel WD Architecture, Engineering, Surveying and Landscape Architecture, P.C
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
0 1" 2"
GENERIC SCALE BAR
SCALE BAR SHOWN IS TWO INCHES ON THE ORIGINAL DRAWING.
IF NOT TWO INCHES ON THIS SHEET, ADJUST ACCORDINGLY
DWG. No.
PROJ. No.
SCALE
DATE
DWG. TITLE
DWN. CHK.
NO. REVISIONS DATE
As indicated
TITLES & SYMBOLS
A000
05-10-2024
BMM
630001
JMS
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
0 ISSUED FOR PERMIT 05-10-2024
SS
MATERIALS LEGEND:
FACE BRICK
CONCRETE MASONRY UNIT
FOAM PLASTIC BOARD
INSULATION
BLANKET INSULATION
CONTINUOUS WOOD
SHIM
FINISHED WOOD
GYPSUM BOARD / GROUT
CONCRETE OR
PRECAST CONCRETE
ACOUSTICAL CEILING TILE
OR PANEL
MASONRY IN ELEVATION
PLYWOOD
GRAVEL
FOAMED IN PLACE INSULATION
STEEL
EARTH
SOLID SURFACE / CAST STONE
STONE
DRAWING SYMBOLS:
A101
SIM
A101
SIM
A101
SIM
WALL SECTION REFERENCE
BUILDING SECTION REFERENCE
COLUMN CENTERLINE0
EXISTING COLUMN CENTERLINE0
CENTERLINECL
BREAK LINE
ENLARGED DETAIL REFERENCE
A101
SIM
1-HR FIRE RATING
2-HR FIRE RATING
3-HR FIRE RATING
1-HR FIRE/SMOKE RATING
CONSTRUCTION NOTE
DEMOLITION NOTE
REVISION TAG
ROOM NAME AND NUMBER
VIEW TITLE - DETAIL NUMBER
BUILDING ELEVATION REFERENCE
INTERIOR ELEVATION REFERENCE
DOOR NUMBER
WINDOW / LOUVER NUMBER
MATCHLINE REFERENCE
NEW WALL
EXISTING WALL TO REMAIN
EXISTING WALL TO BE REMOVED
NEW DOOR OPENING
EXISTING DOOR OPENING TO REMAIN
EXISTING DOOR AND FRAME
TO BE REMOVED
ELEVATION REFERENCE
ROOM NAME
View Name
SCALE: 1/8" = 1'-0"
A10
101-1
W1
MATCHLINE
RE: 1/A101
MATCHLINE
RE: 1/A101
Name Elevation
WORKING POINTSIGNAGE TAG
1 A
SIGN TYPE
GRAPHIC TYPE
LEVEL NAME
LEVEL HEIGHT
WP
A101
NOTE:
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN,
AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF THE
ARCHITECT AND ENGINEER AND IS NOT TO BE USED IN WHOLE OR IN PART,
FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF THE
ARCHITECT AND ENGINEER. UNAUTHORIZED ALTERATION OR ADDITION TO
ANY SURVEY DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IS
PROHIBITED IN ACCORDANCE WITH STATE LAW, CODE AND RULES.
Wendel WD Architecture, Engineering, Surveying and Landscape Architecture, P.C
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
0 1" 2"
GENERIC SCALE BAR
SCALE BAR SHOWN IS TWO INCHES ON THE ORIGINAL DRAWING.
IF NOT TWO INCHES ON THIS SHEET, ADJUST ACCORDINGLY
DWG. No.
PROJ. No.
SCALE
DATE
DWG. TITLE
DWN. CHK.
NO. REVISIONS DATE
As indicated
TITLES & SYMBOLS
A001
05-10-2024
BMM
630001
JMS
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
ABBREVIATIONS
A/C AIR CONDITION
ACP ACCOUSTICAL CEILING PANEL
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACCOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJACENT/ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
ANT ANTENNA
AOR AREA OF REFUGE
APPROX APPROXIMATELY
ARCH ARCHITECT
ASSY ASSEMBLY
AV AUDIO VISUAL
BD BOARD
BLD BOLLARD
BLDG BUILDING
BOT BOTTOM
BRG BEARING
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT UP ROOFING
C TO C CENTER TO CENTER
CAB CABINET
CB CATCH BASIN
CDCT CIRCULAR DUCT
CFMF COLD-FORMED METAL FRAMING
CG CORNER GUARD
CGFSU CERAMIC GLAZED STRUCTURAL FACING
UNITS
CH COAT HOOK
CH BD CHALK BOARD
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLO CLOSET
CLOS CLOSURE
CLR CLEAR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONSTR CONSTRUCTION
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CPRS COMPRESSIBLE
CPT CARPET
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CUST CUSTODIAN
D DEEP/DEPTH
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DN DOWN
DPTN DEMOUNTABLE PARTITION
DR DOOR
DS DOWNSPOUT
DWG DRAWING
E EAST
EA EACH
LIN LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LNDSCP LANDSCAPE
LOC LOCATION
LPT LOW POINT
LVT LUXURY VINYL TILE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD BIT MODIFIED BITUMEN
MTD MOUNTED
MTL METAL
MTLP METAL PARTITION
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF/CI OWNER FURNISHED/CONTRACTOR
INSTALLED
OH OVERHANG
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OS OCCUPANCY SENSOR
P PIPE
PCC PRECAST CONCRETE
PEJ PREMOLDED EXPANSION JOINT
PERF PERFORATED
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PORC PORCELAIN
PP POWER POLE
PREF PREFINISH
PREFAB PREFABRICATE
PT PAINT
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE
QT QUARRY TILE
QTY QUANTITY
R RADIUS/RISER/THERMAL RESISTANCE
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RECPT RECEPTACLE
REF REFERENCE/REFRIGERATOR
REINF REINFORCE
REQD REQUIRED
RESIL RESILIENT
RET RETURN
RFG ROOFING
RH ROOF HATCH/RIGHT HAND
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RM ROOM
RO ROUGH OPENING
RR RAILROAD
RTU ROOF TOP UNIT
RV ROOF VENT
S SOUTH
EF EACH FACE
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ENCL ENCLOSURE
EP ELECTRICAL PANEL
EPDM ETHYLENE PROPYLENE DIENE MONOMER
EQ EQUAL
EQUIP EQUIPMENT
ETC ET CETERA
EWC ELECTRIC WATER COOLER
EXH FN EXHAUST FAN
EXP EXPANSION/EXPOSED
EXST EXISTING
EXT EXTERIOR
EXTRU EXTRUSION
F/F FACE TO FACE
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISHED FACE
FHC FIRE HOSE CABINET
FIN FINISH
FIN FLR FINISHED FLOOR
FLASH FLASHING
FLR FLOOR
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FRAME
FRG FIBER REINFORCED GYPSUM
FSS FOLDING SHOWER SEAT
FT FEET/FOOT
FURG FURRING
G NATURAL GAS
GA GAGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GDR GUARD RAIL
GFCI GROUND FAULT CIRCUIT INERRUPTER
GL GLASS
GLZ CMU GLAZED CONCRETE MASONRY UNIT
GSP GUTTER SPLASH BLOCK
GYP GYPSUM
GYP BD GYPSUM WALLBOARD
H HIGH
HB HOSE BIBB
HC HANDICAP
HD HAND DRYER
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HPC HIGH PERFORMANCE COATING
HPT HIGH POINT
HS HOT STACK
HT HEIGHT
HVAC HEATING
HYD HYDRANT
ID INSIDE DIAMETER
IF INSIDE FACE
INCL INCLUDED
INSUL INSULATION
INSUL PNL INSULATED METAL PANEL
INT INTERIOR
JAN JANITOR
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LF LINEAR FEET (FOOT)
LH LEFT HAND
LHR LEFT HAND REVERSE
SA SUPPLY AIR
SC SOLID CORE
SCD SEAT COVER DISPENSER
SCHED SCHEDULE
SD SOAP DISPENSER
SECT SECTION
SF SQUARE FOOT (FEET)
SHR SHOWER
SHT SHEET
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SLNT SEALANT
SND SANITARY NAPKIN DISPENSER
SNDU SANITARY NAPKIN DISPOSAL UNIT
SP STAND PIPE
SP FIN SPECIAL FINISH
SPEC SPECIFICATION
SQ SQUARE
SS STORM SEWER
SSM SOLID SURFACE MATERIAL
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
SUSP SUSPEND
SV SHEET VINYL/SMOKE VENT
SYMM SYMMETRICAL
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TB TOWEL BAR
TD TRENCH DRAIN/TOWEL DISPENSER
TDR TOWEL DISPENSER/RECEPTACLE
TEL TELEPHONE
TER TERRAZZO
THK THICKNESS
TK BD TACK BOARD
TOC TOP OF CURB/TOP OF CONCRETE
TOJ TOP OF JOIST
TOP TOP OF PARAPET
TOS TOP OF STEEL
TOW TOP OF WALL
TP TOWEL PIN
TPH TOILET PAPER HOLDER
TPO THERMOPLASTIC POLYOLEFIN
TPTN TOILET PARTITION
TRTD TREATED
TV TELEVISION
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UNFIN UNFINISH
UNO UNLESS NOTED OTHERWISE
UR URINAL
UTIL UTILITY
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VP VENT PIPE
VS VACANCY SENSOR
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WEST/WIDE
W/ WITH
W/O WITHOUT
WBL WOOD BLOCKING
WC WATER CLOSET
WD WOOD
WH WATER HEATER
WWR WELDED WIRE REINFORCEMENT
A003
Sim
AREA
OF
WORK
NOTE:
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN,
AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF THE
ARCHITECT AND ENGINEER AND IS NOT TO BE USED IN WHOLE OR IN PART,
FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF THE
ARCHITECT AND ENGINEER. UNAUTHORIZED ALTERATION OR ADDITION TO
ANY SURVEY DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IS
PROHIBITED IN ACCORDANCE WITH STATE LAW, CODE AND RULES.
Wendel WD Architecture, Engineering, Surveying and Landscape Architecture, P.C
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
0 1" 2"
GENERIC SCALE BAR
SCALE BAR SHOWN IS TWO INCHES ON THE ORIGINAL DRAWING.
IF NOT TWO INCHES ON THIS SHEET, ADJUST ACCORDINGLY
DWG. No.
PROJ. No.
SCALE
DATE
DWG. TITLE
DWN. CHK.
NO. REVISIONS DATE
1" = 80'-0"
ARCHITECTURAL SITE PLAN
A002
05-10-2024
BMM
630001
JMS
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
SCALE: 1" = 80'-0"
OVERALL EXISTING SITE PLAN
TRUE NORTH
N 0 ISSUED FOR PERMIT 05-10-2024
MINIMUM BUS CLEARANCE
60' - 0"
PROJECT WORK AREA
MAINTENANCE
BUILDING
(EXISTING)
MONEY
COUNTING/
VAULT ROOM
BUILDING
(EXISTING)
PHOTO 1
PHOTO 2
PHOTO 3
PHOTO 5
PHOTO
13 14
E.8
E.7
E.6
V.I.F.
4' - 0"
V .I.
F
V .I.
F
CONCRETE CURB TO BE
REMOVED IN ITS ENTIRETY
REF PHOTO 1
CONCRETE SLAB & CURB
TO BE REMOVED IN ITS
ENTIRETY
REF: PHOTO 1 & 2
CONCRETE SLAB & CURB
TO BE REMOVED IN ITS
ENTIRETY.
REF: PHOTO 2 & 3
CONCRETE
PAVEMENT & CURB
TO BE REMOVED IN
ITS ENTIRETY
REF PHOTO 1 & 2
REF STRUC. DWGS FOR
WALL DEMOLITION
EXTENTS
CONCRETE
COLUMN TO
REMAIN
V.I.F.
21' - 5"+/-
V .I.
F
EXTENTS OF
PAVEMENT TO BE
REMOVED
COORDINATE WITH
STRUC. FOOTINGS
EXISTING
ASPHALT
PAVEMENT
EXISTING
CONCRETE
PAVEMENT
EXISTING
CONCRETE
PAVEMENT
***NOTE: EXISTING UTILITIES TO BE
VERIFIED IN FIELD PRIOR TO
DEMOLITIOIN. PROVIDE
PROTECTION FOR EXISTING
UTILITIES TO REMAIN DURING
CONSTRUCTION
***NOTE: PAVEMENT TO BE
REPAIRED. VERIFY EXTENTS IN
FIELD. REFER TO STRUCTURAL
DWGS FOR DETAILS
SCALE: 1/8" = 1'-0"
ENLARGED EXISTING SITE PLAN
SCALE: 1/8" = 1'-0"
SITE - DEMO PLAN
NOTE:
THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN,
AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF THE
ARCHITECT AND ENGINEER AND IS NOT TO BE USED IN WHOLE OR IN PART,
FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF THE
ARCHITECT AND ENGINEER. UNAUTHORIZED ALTERATION OR ADDITION TO
ANY SURVEY DRAWING, DESIGN, SPECIFICATION, PLAN OR REPORT IS
PROHIBITED IN ACCORDANCE WITH STATE LAW, CODE AND RULES.
Wendel WD Architecture, Engineering, Surveying and Landscape Architecture, P.C
Centerpointe Corporate Park 375 Essjay Road, Suite 200
Williamsville, NY 14221 www.wendelcompanies.com p:716.688.0766 tf:877.293.6335
0 1" 2"
GENERIC SCALE BAR
SCALE BAR SHOWN IS TWO INCHES ON THE ORIGINAL DRAWING.
IF NOT TWO INCHES ON THIS SHEET, ADJUST ACCORDINGLY
DWG. No.
PROJ. No.
SCALE
DATE
DWG. TITLE
DWN. CHK.
NO. REVISIONS DATE
1/8" = 1'-0"
EXISTING SITE PLAN & SITE
DEMOLITION
A003
05-10-2024
BMM
630001
JMS
BREEZE TRANSIT
SERVICE LANE
5303 PINKNEY AVE, SARASOTA,
FL 34233
VAULT ROOM IMPROVEMENTS
CONSTRUCTION DOCUMENTS
TRUE NORTH
N
2 3 4
TRUE NORTH
N
503.1 GENERAL
Except as provided by Sections 302.3, 302.4, or this section, alterations to any building or structure shall comply with the requirements of the Florida Building Code, Building for new construction. Alterations shall be such that the existing building or structure is no less conforming to the provisions of the Florida Building Code, Building than the existing building or structure was prior to the alteration.
603.1 Scope.
Level 2 alterations include the addition or elimination of any door or window, the reconfiguration or extension of any system, or the installation of any additional equipment; and shall apply where the work area is equal to or less than 50 percent of the building area.
603.2 Application.
Level 2 alterations shall comply with the provisions of Chapter 7 for Level 1 alterations as well as the provisions of Chapter 8.
606.1 Scope.
Provisions for additions shall apply where work is classified as an addition as defined in Chapter 2.
606.2 Application.
Additions to existing buildings shall comply with the provisions of Chapter 11.
801.3 Compliance.
All new construction elements, components, systems, and spaces shall comply with the requirements of the Florida…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .