This is Addendum #1 to the Park City Municipal Athletic Recreation Complex (PC MARC) Locker Room Renovation project, issued by WHW Engineering, LLC on August 31, 2026, and addressed to VCBO in Salt Lake City, Utah. The addendum documents mechanical and plumbing modifications to reduce project costs and minimize ceiling modifications. Key changes include retaining all previously scheduled exhaust fan demolition (reverting to existing equipment), reusing existing exhaust duct mains in areas where ceilings remain unchanged, and adding new exhaust duct branches in front of the infrared sauna room. Plumbing modifications involve retaining existing piping where feasible and updating shower domestic hot and cold water piping configurations. The trench drain in front of the men's and women's restrooms will not be replaced as part of this project. Updated schedules for exhaust fans, diffusers, and grilles have been incorporated into revised mechanical plans (ME101, ME501) and enlarged plumbing plans (PE404), with pipe sizing modifications detailed on the affected sheets.

The addendum reflects cost-reduction strategies through material reuse and selective ceiling retention rather than comprehensive replacement. Specific mechanical equipment includes two roof-mounted exhaust fans serving the men's and women's locker rooms at 2,100 CFM each with 0.90 in-wg ESP, belt-drive configuration, and 0.75 hp motors. Supply and exhaust grilles are detailed with CFM ratings ranging from 180 to 1,500 CFM. Plumbing modifications involve the replacement of copper piping with PEX in shower areas, including within CMU walls, coordinated with architectural plans. Field verification is required for all connection points, duct locations, and removal areas. The document indicates that pricing adjustments associated with these modifications were part of a pricing package dated July 6, 2026.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WHW ENGINEERING, LLC.

MECHANICAL

& PLUMBING

E N G I N E E R I N G

WHW ENGINEERING LLC

733 West 9000 South - Sandy, Utah - 84070

p. 801.466.4021

August 31, 2026

VCBO

Salt Lake City, Utah

ATTN: Mark Finlinson RE: Park City MARC Locker Room Renovation - Addendum #1

Dear Mark, Please see below for mechanical modifications to the project listed above included in Addendum #1.

I. CHANGES/CLARIFICATIONS TO DRAWINGS:

a. MD101: All the demoed exhaust fan are changed back to existing. Couple of exhaust grilles to be demoed. See sheet MD101.

b. ME101: In an effort to reduce cost and reduce ceiling modifications, the plans have been updated to re-use the exhaust duct mains in areas where the ceilings are indicated to remain. See updated plans showing to re-use these existing exhaust ducts. A couple of new exhaust duct branches have been added in front of the infrared sauna room where the ceilings are still being replaced. Some exhaust cfm requirements have been updated based on what the existing ductwork can accommodate.

See ME101.

c. ME501: Exhaust fan schedule has been updated. Diffuser and Grille schedule has been updated. See ME501.

d. PD101: Some plumbing piping was updated to keep the existing pipe and reduce ceiling replacement. See PD101.

e. PE101: All shower domestic cold and hot water piping has been modified.

Trench drain in front of the men’s and women’s restroom will not be replaced as part of this project. See PE101.

f. PE404: Pipe sizing has been modified at the showers. See PE404.

We appreciate the opportunity to work with you on this project. If you need additional information or have any questions, please do not hesitate to contact our office. Thank you.

Sincerely, Saroj Sapkota WHW Engineering

A

B

B.1

C

C.1

D

D.1

21.21.11

NOT IN SCOPE

N O

T I N

S C

O P

E

4 4

A

B

B.1

C

C.1

D

D.1

21.21.11

S E

F O

R P

H

ATUFOETA

T S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

SALT LAKE CITY - HQ

524 SOUTH 600 EAST

SALT LAKE CITY, UT 84102

801.575.8800

E

1 2 3 4 5

E

C

A

B

D D

C

B

A

1 2 3 4 5 6

REV DATE DESCRIPTION

ST. GEORGE

20 N. MAIN ST. #103

ST. GEORGE, UT 84770

435.522.7070

VCBO.COM

04-02-2026 PRICING PACKAGE

07/06/2026

9/1/2026 8:44:07 AM

MD101

MECHANICAL DEMO PLANS

P A

R K

C

IT

Y M

A R

C L

O C

K E

R R

O O

M

R E

N O

V A

T

IO

N

B

ID

D O

C U

M E

N T

S

L

IT

T

L E

K A

T E

R D

P

A R

K C

IT

Y

U

T

VCBO NUMBER: 23220.01

CLIENT NUMBER: 00000

DATE: 2025 JANUARY 06

1/4" = 1'-0"

LEVEL 1 MECHANICAL DEMO

SHEET NOTES

1 EXISTING DUCTWORK SHALL REMAIN IN THIS

APPROXIMATE LOCATON. FIELD VERIFY.

2 REMOVE AND REPLACE THE EXISTING EXHAUST FAN

LOCATED IN THIS APPROXIMATE LOCATION. FIELD

VERIFY.

3 REMOVE AND REPLACE THE SUPPLY GRILLE

LOCATED IN THIS APPROXIMATE LOCATION. FIELD

VERIFY.

4 REMOVE AND REPLACE THE EXHAUST GRILLE IN THIS

APPROXIMATE LOCATION. FIELD VERIFY THE EXACT

POINT OF REMOVAL.

KEY PLAN

1/4" = 1'-0"

ROOF MECHANICAL DEMO

1 09/01/26 ADD#1

B.1

C

C.1

D

D.1

21.21.11

EG-1

EG-1

EG-1

MEN'S

RESTROOM

183 SF

WOMEN'S

SHOWER/LOCKER

752 SF

INFRARED

SAUNA

84 SF

WOMEN'S

RESTROOM

204 SF

CHASE

FAMILY

FAMILY

CHASE

INFRARED

SUANA

83 SF

MEN'S

SHOWER/LOCKER

LOCKER

HALL

NOT IN SCOPE

N

O T

I N

S C

O P

E

2 D-1

D-1

4"ø EA (E)

EG-1

EG-1

EG-1

4 4

EG-1

EG-2

8"x6" EA

VD

EG-2

VD

8"x6" EA

EG-1

22"x12" EA (E)

24"x12" EA (E)

12"ø EA

A

B

B.1

C

C.1

D

D.1

21.21.11

EF

EF

S E

F O

R P

H

ATUFOETA

T S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

SALT LAKE CITY - HQ

524 SOUTH 600 EAST

SALT LAKE CITY, UT 84102

801.575.8800

E

1 2 3 4 5

E

C

A

B

D D

C

B

A

1 2 3 4 5 6

REV DATE DESCRIPTION

ST. GEORGE

20 N. MAIN ST. #103

ST. GEORGE, UT 84770

435.522.7070

VCBO.COM

04-02-2026 PRICING PACKAGE

07/06/2026

9/1/2026 8:44:13 AM

ME101

MECHANICAL PLANS

P A

R K

C

IT

Y M

A R

C L

O C

K E

R R

O O

M

R E

N O

V A

T

IO

N

B

ID

D O

C U

M E

N T

S

L

IT

T

L E

K A

T E

R D

P

A R

K C

IT

Y

U

T

VCBO NUMBER: 23220.01

CLIENT NUMBER: 00000

DATE: 2025 JANUARY 06

1/4" = 1'-0"

LEVEL 1 MECHANICAL

SHEET NOTES

1 PROVIDE NEW EXHAUST FAN IN THIS APPROXIMATE

LOCATION. TIE INTO UTAH YAMAS BAS FOR A

DEDICATED SCHEDULE PER FAN. FIELD VERIFY.

2 EXISTING DUCTWORK SHALL REMAIN IN THIS

APPROXIMATE LOCATON. FIELD VERIFY.

3 PROVIDE NEW SUPPLY GRILLE IN THIS APPROXIMATE

LOCATION AND TIE IT IN THE DUCT. REBALANCE WITH

THE CFM SHOWN. FIELD VERIFY.

4 PROVIDE NEW EXHAUST GRILLE IN THIS

APPROXIMATE LOCATION. BALANCE NEW GRILLE

WITH THE CFM SHOWN. FIELD VERIFY EXACT POINT

OF CONNECTION.

5 EXISTING EXHAUST DUCT SHALL REMAIN. TIE IT INTO

THE INFRARED SAUNA FAN. FIELD VERIFY.

KEY PLAN

1/4" = 1'-0"

ROOF MECHANICAL

1" MIN

BACKDRAFT

DAMPER

DUCT TRANSITION FROM

CEILING GRILLE SIZE TO

DAMPER SIZE.

SEAL

RUN FLASHING UP

UNDER FAN BASE

SEAL

ANCHOR FAN TO CURB

EXHAUST FAN

BIRD SCREEN

ROOF CURB

ROOFING

SCALE: NONE

HANGERS MUST NOT DEFORM DUCT SHAPE

SCALE: NONE

BAND ONE HALF -

ROUND MAY BE

USED IF DUCT

SHAPE IS

MAINTAINED

HANGER RODS, WIRES

OR STRAPS

10" DIA.

MAX.

24" DIA.

MAX.

SCALE: NONE

BAND OF

SAME SIZE AS

HANGER

STRAP

36" DIA.

MAX.

LOAD RATED

FASTENERS

HANGER

SECURE

WIRE

60" MAX

SCALE: NONE

HANGER STRAPS

SCREWS

SCREWS MAY BE

OMITTED IF HANGER

LOOPS.

HANGER STRAPS

TRAPEZE HANGERS

SCALE: NONE

STRAP

SIZE BOLT(S) FOR LOAD

ROD

STRAP OR

ANGLE

C5

ROOF MOUNTED EXHAUST FAN DETAIL

DUCT SUPPORTS

D3 DUCT SUPPORTS

D4 D5

DUCT SUPPORTS DUCT SUPPORTS

D6

1. TIE INTO UTAH YAMAS BAS FOR A DEDICATED SCHEDULE PER FAN.

1. SHALL BE PRICE SPD OR APPROVED EQUAL.

2. SHALL BE PRICE 535 OR APPROVED EQUAL.

3. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.

4. FINISH SHALL BE SPECIFIED BY ARCHITECT.

S E

F O

R P

H

ATUFOETA

T S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

SALT LAKE CITY - HQ

524 SOUTH 600 EAST

SALT LAKE CITY, UT 84102

801.575.8800

E

1 2 3 4 5

E

C

A

B

D D

C

B

A

1 2 3 4 5 6

REV DATE DESCRIPTION

ST. GEORGE

20 N. MAIN ST. #103

ST. GEORGE, UT 84770

435.522.7070

VCBO.COM

04-02-2026 PRICING PACKAGE

07/06/2026

9/1/2026 8:44:13 AM

ME501

MECHANICAL DETAILS AND

SCHEDULES

P A

R K

C

IT

Y M

A R

C L

O C

K E

R R

O O

M

R E

N O

V A

T

IO

N

B

ID

D O

C U

M E

N T

S

L

IT

T

L E

K A

T E

R D

P

A R

K C

IT

Y

U

T

VCBO NUMBER: 23220.01

CLIENT NUMBER: 00000

DATE: 2025 JANUARY 06

EXHAUST FAN SCHEDULE

TAG

AREA SERVED CFM ESP DRIVE TYPE MOUNTING

ELECTRICAL DIMENSIONS

MANUF. AND MODEL

SCHEDULE

NOTESTYPE NUMBER V PH HZ RPM HP

VFD BY

DIV 26

VFD

INTEG

L W H WT SONES

EF 1

MENS LOCKER

ROOM

2,100 CFM 0.90 in-wg BELT ROOF 120 V 1 60 Hz 1725 0.75 hp No Yes 33" 33" 29" 93 lb 15.2 COOK 150 ACEB 1

EF 2

WOMENS LOCKER

ROOM

2,100 CFM 0.90 in-wg BELT ROOF 120 V 1 60 Hz 1725 0.75 hp No Yes 33" 33" 29" 93 lb 15.2 COOK 150 ACEB 1

1 09/01/26 ADD#1

DIFFUSER AND GRILLE SCHEDULE

TYPE

GRD

SERVICE

MAX CFM

FACE DIMENSIONS NECK DIMENSIONS

GRD TYPE

CEILING

TYPE

DISCHARGE

PATTERN

THROW 50

FPM

MAX NC MANUF. AND MODEL

SCHEDULE

NOTESDIAMETER L W DIAMETER L W

D-1 SUPPLY 1,500 CFM 0" 2' - 0" 2' - 0" 1' - 0" 0" 0" CEILING HARD 4 WAY 12' 25 PRICE SPD 1,3,4

EG-1 EXHAUST 700 CFM 0" 1' - 0" 1' - 0" 1' - 0" 0" 0" CEILING HARD N/A 0' 25 PRICE 535 2,3,4

EG-2 EXHAUST 180 CFM 0" 8" 8" 0" 8" 8" CEILING HARD N/A 0' 25 PRICE 535 2,3,4

B.1

C

C.1

D

D.1

21.21.11

S E

F O

R P

H

ATUFOETA

T S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

SALT LAKE CITY - HQ

524 SOUTH 600 EAST

SALT LAKE CITY, UT 84102

801.575.8800

E

1 2 3 4 5

E

C

A

B

D D

C

B

A

1 2 3 4 5 6

REV DATE DESCRIPTION

ST. GEORGE

20 N. MAIN ST. #103

ST. GEORGE, UT 84770

435.522.7070

VCBO.COM

04-02-2026 PRICING PACKAGE

07/06/2026

9/1/2026 8:44:16 AM

PD101

PLUMBING DEMO PLAN

P A

R K

C

IT

Y M

A R

C L

O C

K E

R R

O O

M

R E

N O

V A

T

IO

N

B

ID

D O

C U

M E

N T

S

L

IT

T

L E

K A

T E

R D

P

A R

K C

IT

Y

U

T

VCBO NUMBER: 23220.01

CLIENT NUMBER: 00000

DATE: 2025 JANUARY 06

1/4" = 1'-0"

LEVEL 1 PLUMBING WATER DEMO

SHEET NOTES

1 REMOVE ALL WASTE AND VENT PIPING IN THIS AREA.

FIELD VERIFY.

2 REMOVE ALL DOMESTIC WATER PIPING TO THIS

APPROXIMATE LOCATION. FIELD VERIFY. IN SHOWER

AREAS, INCLUDING IN CMU WALLS TO SHOWERS.

3 POINT OF REMOVAL OF DOMESTIC HOT AND COLD

WATER PIPE. FIELD VERIFY.

4 POINT OF REMOVAL FOR EXISTING SANITARY AND

VENT PIPING. FIELD VERIFY.

KEY PLAN

B.1

C

C.1

D

D.1

21.21.11

WOMEN'S

SHOWER/LOCKER

INFRARED

SAUNA

149 WOMEN'S

RESTROOM

CHASE

FAMILY

FAMILY

CHASE

INFRARED

SUANA

MEN'S

RESTROOM

MEN'S

SHOWER/LOCKER

LOCKER

HALL

NOT IN SCOPE

N

O T

I N

S C

O P

E

PE401

PE402

PE403

PE404

2 1/2"ø CW (E) 1 1/2"ø HW (E)

6 7

6 7

A

B

B.1

C

C.1

D

D.1

21.21.11

FCO

FCO

FCO

WOMEN'S

SHOWER/LOCKER

INFRARED

SAUNA

WOMEN'S

RESTROOM

CHASE

FAMILY

FAMILY

CHASE

INFRARED

SUANA

MEN'S

RESTROOM

MEN'S

SHOWER/LOCKER

LOCKER

HALL

NOT IN SCOPE

N O

T I N

S C

O P

E

PE401

PE402

PE403

PE404

3"ø V

S E

F O

R P

H

ATUFOETA

T S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

SALT LAKE CITY - HQ

524 SOUTH 600 EAST

SALT LAKE CITY, UT 84102

801.575.8800

E

1 2 3 4 5

E

C

A

B

D D

C

B

A

1 2 3 4 5 6

REV DATE DESCRIPTION

ST. GEORGE

20 N. MAIN ST. #103

ST. GEORGE, UT 84770

435.522.7070

VCBO.COM

04-02-2026 PRICING PACKAGE

07/06/2026

9/1/2026 8:44:19 AM

PE101

PLUMBING PLANS

P A

R K

C

IT

Y M

A R

C L

O C

K E

R R

O O

M

R E

N O

V A

T

IO

N

B

ID

D O

C U

M E

N T

S

L

IT

T

L E

K A

T E

R D

P

A R

K C

IT

Y

U

T

VCBO NUMBER: 23220.01

CLIENT NUMBER: 00000

DATE: 2025 JANUARY 06

KEY PLAN

1/4" = 1'-0"

LEVEL 1 DOMESTIC PLUMBING PLAN

SHEET NOTES

1 REPAIR DRAIN IN CMU WALL AT SWIM SUIT WATER

EXTRACTOR. FIELD VERIFY. PATCH, REPAIR, AND

PAINT CMU.

2 SEE SHEET PE401.

3 SEE SHEET PE402.

4 SEE SHEET PE403.

5 SEE SHEET PE404.

6 TIE NEW DOMESTIC HOT WATER LINE INTO THE

EXISTING LINE IN THIS APPROXIMATE LOCATION.

FIELD VERIFY EXACT POINT OF CONNECTION.

7 TIE NEW DOMESTIC COLD WATER LINE INTO THE

EXISTING LINE IN THIS APPROXIMATE LOCATION.

FIELD VERIFY EXACT POINT OF CONNECTION.

8 POINT OF CONNECTION FOR NEW SANITARY AND

VENT PIPING. FIELD VERIFY.

1/4" = 1'-0"

LEVEL 1 WASTE AND VENT

1 09/01/26 ADD#1

D

D.1

SH-1

SH-1

SH-1

SH-1

SH-1

SH-1

SH-11

1"ø HW 1"ø CW

1/2"ø HW

1/2"ø CW

1/2"ø HW

1/2"ø CW

1/2"ø HW

1/2"ø CW

1/2"ø CW 1/2"ø HW

1/2"ø HW 1/2"ø CW

3/4"ø HW

3/4"ø CW

3/4"ø HW 3/4"ø CW

D

D.1

TD-1

SD-1

SD-1

SD-1

SD-1 SD-1

SD-1

SD-1

3"ø SS

2"ø SS

4"ø SS

3"ø V

2"ø SS

2"ø SS

2"ø SS

2"ø SS

4"ø SS

2"ø SS

3"ø SS

3"ø SS

3"ø SS

3"ø V

S E

F O

R P

H

ATUFOETA

T S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

SALT LAKE CITY - HQ

524 SOUTH 600 EAST

SALT LAKE CITY, UT 84102

801.575.8800

E

1 2 3 4 5

E

C

A

B

D D

C

B

A

1 2 3 4 5 6

REV DATE DESCRIPTION

ST. GEORGE

20 N. MAIN ST. #103

ST. GEORGE, UT 84770

435.522.7070

VCBO.COM

04-02-2026 PRICING PACKAGE

07/06/2026

9/1/2026 8:44:21 AM

PE404

ENLARGED PLUMBING

PLANS

P A

R K

C

IT

Y M

A R

C L

O C

K E

R R

O O

M

R E

N O

V A

T

IO

N

B

ID

D O

C U

M E

N T

S

L

IT

T

L E

K A

T E

R D

P

A R

K C

IT

Y

U

T

VCBO NUMBER: 23220.01

CLIENT NUMBER: 00000

DATE: 2025 JANUARY 06

1/2" = 1'-0"

LEVEL 1 DOMESTIC PLUMBING PLAN -

Callout 4

1/2" = 1'-0"

LEVEL 1 DOMESTIC PLUMBING PLAN -

Callout 7

SHEET NOTES

1 REPLACE COPPER PIPING IN SHOWER AREAS WITH

PEX, INCLUDING THE PIPING IN THE CMU WALLS TO

THE SHOWERS. COORDINATE WITH ARCHITECTURAL

PLANS.

File details come from the government source that posted it. Updated .