6-Addenda 1 - 2026-09-02.pdf
PDF 4 MB Posted
- Attached to
- PC MARC Locker Room Renovation
- Solicitation number
- PCMC27013-REC
- Issued by
- Summit County, Utah
About this file
This is Addendum #1 to the Park City Municipal Athletic Recreation Complex (PC MARC) Locker Room Renovation project, issued by WHW Engineering, LLC on August 31, 2026, and addressed to VCBO in Salt Lake City, Utah. The addendum documents mechanical and plumbing modifications to reduce project costs and minimize ceiling modifications. Key changes include retaining all previously scheduled exhaust fan demolition (reverting to existing equipment), reusing existing exhaust duct mains in areas where ceilings remain unchanged, and adding new exhaust duct branches in front of the infrared sauna room. Plumbing modifications involve retaining existing piping where feasible and updating shower domestic hot and cold water piping configurations. The trench drain in front of the men's and women's restrooms will not be replaced as part of this project. Updated schedules for exhaust fans, diffusers, and grilles have been incorporated into revised mechanical plans (ME101, ME501) and enlarged plumbing plans (PE404), with pipe sizing modifications detailed on the affected sheets.
The addendum reflects cost-reduction strategies through material reuse and selective ceiling retention rather than comprehensive replacement. Specific mechanical equipment includes two roof-mounted exhaust fans serving the men's and women's locker rooms at 2,100 CFM each with 0.90 in-wg ESP, belt-drive configuration, and 0.75 hp motors. Supply and exhaust grilles are detailed with CFM ratings ranging from 180 to 1,500 CFM. Plumbing modifications involve the replacement of copper piping with PEX in shower areas, including within CMU walls, coordinated with architectural plans. Field verification is required for all connection points, duct locations, and removal areas. The document indicates that pricing adjustments associated with these modifications were part of a pricing package dated July 6, 2026.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WHW ENGINEERING, LLC.
MECHANICAL
& PLUMBING
E N G I N E E R I N G
WHW ENGINEERING LLC
733 West 9000 South - Sandy, Utah - 84070
p. 801.466.4021
August 31, 2026
VCBO
Salt Lake City, Utah
ATTN: Mark Finlinson RE: Park City MARC Locker Room Renovation - Addendum #1
Dear Mark, Please see below for mechanical modifications to the project listed above included in Addendum #1.
I. CHANGES/CLARIFICATIONS TO DRAWINGS:
a. MD101: All the demoed exhaust fan are changed back to existing. Couple of exhaust grilles to be demoed. See sheet MD101.
b. ME101: In an effort to reduce cost and reduce ceiling modifications, the plans have been updated to re-use the exhaust duct mains in areas where the ceilings are indicated to remain. See updated plans showing to re-use these existing exhaust ducts. A couple of new exhaust duct branches have been added in front of the infrared sauna room where the ceilings are still being replaced. Some exhaust cfm requirements have been updated based on what the existing ductwork can accommodate.
See ME101.
c. ME501: Exhaust fan schedule has been updated. Diffuser and Grille schedule has been updated. See ME501.
d. PD101: Some plumbing piping was updated to keep the existing pipe and reduce ceiling replacement. See PD101.
e. PE101: All shower domestic cold and hot water piping has been modified.
Trench drain in front of the men’s and women’s restroom will not be replaced as part of this project. See PE101.
f. PE404: Pipe sizing has been modified at the showers. See PE404.
We appreciate the opportunity to work with you on this project. If you need additional information or have any questions, please do not hesitate to contact our office. Thank you.
Sincerely, Saroj Sapkota WHW Engineering
A
B
B.1
C
C.1
D
D.1
21.21.11
NOT IN SCOPE
N O
T I N
S C
O P
E
4 4
A
B
B.1
C
C.1
D
D.1
21.21.11
S E
F O
R P
H
ATUFOETA
T S
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
SALT LAKE CITY - HQ
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
REV DATE DESCRIPTION
ST. GEORGE
20 N. MAIN ST. #103
ST. GEORGE, UT 84770
435.522.7070
VCBO.COM
04-02-2026 PRICING PACKAGE
07/06/2026
9/1/2026 8:44:07 AM
MD101
MECHANICAL DEMO PLANS
P A
R K
C
IT
Y M
A R
C L
O C
K E
R R
O O
M
R E
N O
V A
T
IO
N
B
ID
D O
C U
M E
N T
S
L
IT
T
L E
K A
T E
R D
P
A R
K C
IT
Y
U
T
VCBO NUMBER: 23220.01
CLIENT NUMBER: 00000
DATE: 2025 JANUARY 06
1/4" = 1'-0"
LEVEL 1 MECHANICAL DEMO
SHEET NOTES
1 EXISTING DUCTWORK SHALL REMAIN IN THIS
APPROXIMATE LOCATON. FIELD VERIFY.
2 REMOVE AND REPLACE THE EXISTING EXHAUST FAN
LOCATED IN THIS APPROXIMATE LOCATION. FIELD
VERIFY.
3 REMOVE AND REPLACE THE SUPPLY GRILLE
LOCATED IN THIS APPROXIMATE LOCATION. FIELD
VERIFY.
4 REMOVE AND REPLACE THE EXHAUST GRILLE IN THIS
APPROXIMATE LOCATION. FIELD VERIFY THE EXACT
POINT OF REMOVAL.
KEY PLAN
1/4" = 1'-0"
ROOF MECHANICAL DEMO
1 09/01/26 ADD#1
B.1
C
C.1
D
D.1
21.21.11
EG-1
EG-1
EG-1
MEN'S
RESTROOM
183 SF
WOMEN'S
SHOWER/LOCKER
752 SF
INFRARED
SAUNA
84 SF
WOMEN'S
RESTROOM
204 SF
CHASE
FAMILY
FAMILY
CHASE
INFRARED
SUANA
83 SF
MEN'S
SHOWER/LOCKER
LOCKER
HALL
NOT IN SCOPE
N
O T
I N
S C
O P
E
2 D-1
D-1
4"ø EA (E)
EG-1
EG-1
EG-1
4 4
EG-1
EG-2
8"x6" EA
VD
EG-2
VD
8"x6" EA
EG-1
22"x12" EA (E)
24"x12" EA (E)
12"ø EA
A
B
B.1
C
C.1
D
D.1
21.21.11
EF
EF
S E
F O
R P
H
ATUFOETA
T S
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
SALT LAKE CITY - HQ
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
REV DATE DESCRIPTION
ST. GEORGE
20 N. MAIN ST. #103
ST. GEORGE, UT 84770
435.522.7070
VCBO.COM
04-02-2026 PRICING PACKAGE
07/06/2026
9/1/2026 8:44:13 AM
ME101
MECHANICAL PLANS
P A
R K
C
IT
Y M
A R
C L
O C
K E
R R
O O
M
R E
N O
V A
T
IO
N
B
ID
D O
C U
M E
N T
S
L
IT
T
L E
K A
T E
R D
P
A R
K C
IT
Y
U
T
VCBO NUMBER: 23220.01
CLIENT NUMBER: 00000
DATE: 2025 JANUARY 06
1/4" = 1'-0"
LEVEL 1 MECHANICAL
SHEET NOTES
1 PROVIDE NEW EXHAUST FAN IN THIS APPROXIMATE
LOCATION. TIE INTO UTAH YAMAS BAS FOR A
DEDICATED SCHEDULE PER FAN. FIELD VERIFY.
2 EXISTING DUCTWORK SHALL REMAIN IN THIS
APPROXIMATE LOCATON. FIELD VERIFY.
3 PROVIDE NEW SUPPLY GRILLE IN THIS APPROXIMATE
LOCATION AND TIE IT IN THE DUCT. REBALANCE WITH
THE CFM SHOWN. FIELD VERIFY.
4 PROVIDE NEW EXHAUST GRILLE IN THIS
APPROXIMATE LOCATION. BALANCE NEW GRILLE
WITH THE CFM SHOWN. FIELD VERIFY EXACT POINT
OF CONNECTION.
5 EXISTING EXHAUST DUCT SHALL REMAIN. TIE IT INTO
THE INFRARED SAUNA FAN. FIELD VERIFY.
KEY PLAN
1/4" = 1'-0"
ROOF MECHANICAL
1" MIN
BACKDRAFT
DAMPER
DUCT TRANSITION FROM
CEILING GRILLE SIZE TO
DAMPER SIZE.
SEAL
RUN FLASHING UP
UNDER FAN BASE
SEAL
ANCHOR FAN TO CURB
EXHAUST FAN
BIRD SCREEN
ROOF CURB
ROOFING
SCALE: NONE
HANGERS MUST NOT DEFORM DUCT SHAPE
SCALE: NONE
BAND ONE HALF -
ROUND MAY BE
USED IF DUCT
SHAPE IS
MAINTAINED
HANGER RODS, WIRES
OR STRAPS
10" DIA.
MAX.
24" DIA.
MAX.
SCALE: NONE
BAND OF
SAME SIZE AS
HANGER
STRAP
36" DIA.
MAX.
LOAD RATED
FASTENERS
HANGER
SECURE
WIRE
60" MAX
SCALE: NONE
HANGER STRAPS
SCREWS
SCREWS MAY BE
OMITTED IF HANGER
LOOPS.
HANGER STRAPS
TRAPEZE HANGERS
SCALE: NONE
STRAP
SIZE BOLT(S) FOR LOAD
ROD
STRAP OR
ANGLE
C5
ROOF MOUNTED EXHAUST FAN DETAIL
DUCT SUPPORTS
D3 DUCT SUPPORTS
D4 D5
DUCT SUPPORTS DUCT SUPPORTS
D6
1. TIE INTO UTAH YAMAS BAS FOR A DEDICATED SCHEDULE PER FAN.
1. SHALL BE PRICE SPD OR APPROVED EQUAL.
2. SHALL BE PRICE 535 OR APPROVED EQUAL.
3. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.
4. FINISH SHALL BE SPECIFIED BY ARCHITECT.
S E
F O
R P
H
ATUFOETA
T S
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
SALT LAKE CITY - HQ
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
REV DATE DESCRIPTION
ST. GEORGE
20 N. MAIN ST. #103
ST. GEORGE, UT 84770
435.522.7070
VCBO.COM
04-02-2026 PRICING PACKAGE
07/06/2026
9/1/2026 8:44:13 AM
ME501
MECHANICAL DETAILS AND
SCHEDULES
P A
R K
C
IT
Y M
A R
C L
O C
K E
R R
O O
M
R E
N O
V A
T
IO
N
B
ID
D O
C U
M E
N T
S
L
IT
T
L E
K A
T E
R D
P
A R
K C
IT
Y
U
T
VCBO NUMBER: 23220.01
CLIENT NUMBER: 00000
DATE: 2025 JANUARY 06
EXHAUST FAN SCHEDULE
TAG
AREA SERVED CFM ESP DRIVE TYPE MOUNTING
ELECTRICAL DIMENSIONS
MANUF. AND MODEL
SCHEDULE
NOTESTYPE NUMBER V PH HZ RPM HP
VFD BY
DIV 26
VFD
INTEG
L W H WT SONES
EF 1
MENS LOCKER
ROOM
2,100 CFM 0.90 in-wg BELT ROOF 120 V 1 60 Hz 1725 0.75 hp No Yes 33" 33" 29" 93 lb 15.2 COOK 150 ACEB 1
EF 2
WOMENS LOCKER
ROOM
2,100 CFM 0.90 in-wg BELT ROOF 120 V 1 60 Hz 1725 0.75 hp No Yes 33" 33" 29" 93 lb 15.2 COOK 150 ACEB 1
1 09/01/26 ADD#1
DIFFUSER AND GRILLE SCHEDULE
TYPE
GRD
SERVICE
MAX CFM
FACE DIMENSIONS NECK DIMENSIONS
GRD TYPE
CEILING
TYPE
DISCHARGE
PATTERN
THROW 50
FPM
MAX NC MANUF. AND MODEL
SCHEDULE
NOTESDIAMETER L W DIAMETER L W
D-1 SUPPLY 1,500 CFM 0" 2' - 0" 2' - 0" 1' - 0" 0" 0" CEILING HARD 4 WAY 12' 25 PRICE SPD 1,3,4
EG-1 EXHAUST 700 CFM 0" 1' - 0" 1' - 0" 1' - 0" 0" 0" CEILING HARD N/A 0' 25 PRICE 535 2,3,4
EG-2 EXHAUST 180 CFM 0" 8" 8" 0" 8" 8" CEILING HARD N/A 0' 25 PRICE 535 2,3,4
B.1
C
C.1
D
D.1
21.21.11
S E
F O
R P
H
ATUFOETA
T S
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
SALT LAKE CITY - HQ
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
REV DATE DESCRIPTION
ST. GEORGE
20 N. MAIN ST. #103
ST. GEORGE, UT 84770
435.522.7070
VCBO.COM
04-02-2026 PRICING PACKAGE
07/06/2026
9/1/2026 8:44:16 AM
PD101
PLUMBING DEMO PLAN
P A
R K
C
IT
Y M
A R
C L
O C
K E
R R
O O
M
R E
N O
V A
T
IO
N
B
ID
D O
C U
M E
N T
S
L
IT
T
L E
K A
T E
R D
P
A R
K C
IT
Y
U
T
VCBO NUMBER: 23220.01
CLIENT NUMBER: 00000
DATE: 2025 JANUARY 06
1/4" = 1'-0"
LEVEL 1 PLUMBING WATER DEMO
SHEET NOTES
1 REMOVE ALL WASTE AND VENT PIPING IN THIS AREA.
FIELD VERIFY.
2 REMOVE ALL DOMESTIC WATER PIPING TO THIS
APPROXIMATE LOCATION. FIELD VERIFY. IN SHOWER
AREAS, INCLUDING IN CMU WALLS TO SHOWERS.
3 POINT OF REMOVAL OF DOMESTIC HOT AND COLD
WATER PIPE. FIELD VERIFY.
4 POINT OF REMOVAL FOR EXISTING SANITARY AND
VENT PIPING. FIELD VERIFY.
KEY PLAN
B.1
C
C.1
D
D.1
21.21.11
WOMEN'S
SHOWER/LOCKER
INFRARED
SAUNA
149 WOMEN'S
RESTROOM
CHASE
FAMILY
FAMILY
CHASE
INFRARED
SUANA
MEN'S
RESTROOM
MEN'S
SHOWER/LOCKER
LOCKER
HALL
NOT IN SCOPE
N
O T
I N
S C
O P
E
PE401
PE402
PE403
PE404
2 1/2"ø CW (E) 1 1/2"ø HW (E)
6 7
6 7
A
B
B.1
C
C.1
D
D.1
21.21.11
FCO
FCO
FCO
WOMEN'S
SHOWER/LOCKER
INFRARED
SAUNA
WOMEN'S
RESTROOM
CHASE
FAMILY
FAMILY
CHASE
INFRARED
SUANA
MEN'S
RESTROOM
MEN'S
SHOWER/LOCKER
LOCKER
HALL
NOT IN SCOPE
N O
T I N
S C
O P
E
PE401
PE402
PE403
PE404
3"ø V
S E
F O
R P
H
ATUFOETA
T S
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
SALT LAKE CITY - HQ
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
REV DATE DESCRIPTION
ST. GEORGE
20 N. MAIN ST. #103
ST. GEORGE, UT 84770
435.522.7070
VCBO.COM
04-02-2026 PRICING PACKAGE
07/06/2026
9/1/2026 8:44:19 AM
PE101
PLUMBING PLANS
P A
R K
C
IT
Y M
A R
C L
O C
K E
R R
O O
M
R E
N O
V A
T
IO
N
B
ID
D O
C U
M E
N T
S
L
IT
T
L E
K A
T E
R D
P
A R
K C
IT
Y
U
T
VCBO NUMBER: 23220.01
CLIENT NUMBER: 00000
DATE: 2025 JANUARY 06
KEY PLAN
1/4" = 1'-0"
LEVEL 1 DOMESTIC PLUMBING PLAN
SHEET NOTES
1 REPAIR DRAIN IN CMU WALL AT SWIM SUIT WATER
EXTRACTOR. FIELD VERIFY. PATCH, REPAIR, AND
PAINT CMU.
2 SEE SHEET PE401.
3 SEE SHEET PE402.
4 SEE SHEET PE403.
5 SEE SHEET PE404.
6 TIE NEW DOMESTIC HOT WATER LINE INTO THE
EXISTING LINE IN THIS APPROXIMATE LOCATION.
FIELD VERIFY EXACT POINT OF CONNECTION.
7 TIE NEW DOMESTIC COLD WATER LINE INTO THE
EXISTING LINE IN THIS APPROXIMATE LOCATION.
FIELD VERIFY EXACT POINT OF CONNECTION.
8 POINT OF CONNECTION FOR NEW SANITARY AND
VENT PIPING. FIELD VERIFY.
1/4" = 1'-0"
LEVEL 1 WASTE AND VENT
1 09/01/26 ADD#1
D
D.1
SH-1
SH-1
SH-1
SH-1
SH-1
SH-1
SH-11
1"ø HW 1"ø CW
1/2"ø HW
1/2"ø CW
1/2"ø HW
1/2"ø CW
1/2"ø HW
1/2"ø CW
1/2"ø CW 1/2"ø HW
1/2"ø HW 1/2"ø CW
3/4"ø HW
3/4"ø CW
3/4"ø HW 3/4"ø CW
D
D.1
TD-1
SD-1
SD-1
SD-1
SD-1 SD-1
SD-1
SD-1
3"ø SS
2"ø SS
4"ø SS
3"ø V
2"ø SS
2"ø SS
2"ø SS
2"ø SS
4"ø SS
2"ø SS
3"ø SS
3"ø SS
3"ø SS
3"ø V
S E
F O
R P
H
ATUFOETA
T S
R E
E
NI
GNELANOIS
WINWARD M.
PACKER
No. 375080
SALT LAKE CITY - HQ
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
REV DATE DESCRIPTION
ST. GEORGE
20 N. MAIN ST. #103
ST. GEORGE, UT 84770
435.522.7070
VCBO.COM
04-02-2026 PRICING PACKAGE
07/06/2026
9/1/2026 8:44:21 AM
PE404
ENLARGED PLUMBING
PLANS
P A
R K
C
IT
Y M
A R
C L
O C
K E
R R
O O
M
R E
N O
V A
T
IO
N
B
ID
D O
C U
M E
N T
S
L
IT
T
L E
K A
T E
R D
P
A R
K C
IT
Y
U
T
VCBO NUMBER: 23220.01
CLIENT NUMBER: 00000
DATE: 2025 JANUARY 06
1/2" = 1'-0"
LEVEL 1 DOMESTIC PLUMBING PLAN -
Callout 4
1/2" = 1'-0"
LEVEL 1 DOMESTIC PLUMBING PLAN -
Callout 7
SHEET NOTES
1 REPLACE COPPER PIPING IN SHOWER AREAS WITH
PEX, INCLUDING THE PIPING IN THE CMU WALLS TO
THE SHOWERS. COORDINATE WITH ARCHITECTURAL
PLANS.
File details come from the government source that posted it. Updated .