596A4-22-700 Drawings 09 - Tech 2.pdf

PDF 6 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Lexington-Cooper, KY 596A4-22-700
Solicitation number
36C77623B0069
Issued by

About this file

This solicitation is for an EHRM infrastructure upgrade construction project at the Lexington-Cooper VA Medical Center in Lexington, Kentucky. The solicitation number is 36C77623B0069 and was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The project involves upgrading cabling and connectivity components to Category 6A standards throughout multiple buildings. It includes installing new cable trays, j-hooks, patch panels, outlets, and replacing all data cables. The contractor must test all new and re-terminated cables according to specification 27 08 00. The period of performance is 100% construction documents. The anticipated award date is May 23, 2023.

View the file

Other files

File Type Posted
596A4-22-700 Responses to Tech Questions - 1-25-24.pdf PDF
36C77623B0069 0008.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-22-24.pdf PDF
36C77623B0069 0007.pdf PDF
36C77623B0069 0006.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-18-24.pdf PDF
36C77623B0069 0005.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-12-24.pdf PDF
36C77623B0069 0004.pdf PDF
596A4-22-700 Security Requirements.pdf PDF
DBA Wage Rates - Fayette County - 01-05-24.pdf PDF
596A4-22-700 Smoke Shack.pdf PDF
596A4-22-700 Handrail Submittal.pdf PDF
596A4-22-700 Drawing M-701 - Mechanical Controls.pdf PDF
596A4-22-700 Specification 23 09 23 - DDC for HVAC.pdf PDF
DBA Wage Rates - Fayette County - 12-22-23.pdf PDF
36C77623B0069 0003.pdf PDF
36C77623B0069 0002.pdf PDF
596A4-22-700 Site Visit Sign-in Sheet - 11-28-23.pdf PDF
36C77623B0069 0001.pdf PDF
596A4-22-700 Drawings 01 - General.pdf PDF
596A4-22-700 Drawings 12 - Security.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
596A4-22-700 Drawings 03 - Arch.pdf PDF
596A4-22-700 Drawings 06 - Mechanical.pdf PDF
596A4-22-700 Specifications.pdf PDF
596A4-22-700 Drawings 07 - Electrical.pdf PDF
596A4-22-700 Drawings 05 - Plumbing.pdf PDF
596A4-22-700 Drawings 10 - Tech 3.pdf PDF
596A4-22-700 Drawings 04 - Fire Protection.pdf PDF
DBA Wage Rates - Fayette County - 09-08-23.pdf PDF
596A4-22-700 Asbestos Inspection Report.pdf PDF
596A4-22-700 Drawings 11 - Tech 4.pdf PDF
596A4-22-700 Brand Name Justification.pdf PDF
IFB 36C77623B0069.docx DOCX document
596A4-22-700 Drawings 02 - Asbestos.pdf PDF
596A4-22-700 Drawings 08 - Tech 1.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PNEUMATIC TUBE

A604

CORRIDOR

C6A1

A607 OFFICE

A606

A601

ON CALL

BATH

A602

ELEVATOR

AE604

ELEVATOR

AE605

ELEC

B600B

CYLINDER

B600A

CORRIDOR

6A1

C O

R C

HDCP

TELE

FAMILY WAITING

AREA

A657

PUBLIC

TOILET

A657A

LOBBY

A600

ELEVATOR

AE603

ELEVATOR

AE602

ELEVATOR

AE601

DICTATION

A628C

RECOVERY

ROOM

SOILED

UTILITY

A625

CLEAN

UTILITY

A626

FROZEN

SECTION

A606

PNEUMATIC

TUBE

STATION

CORRIDOR

CLEAN

LINEN

A628B

PATIENT

A632

PATIENT

A633

PATIENT

A634

PATIENT

A635

CORRIDOR

6A8

PATIENT

A636

PATIENT

A637

C O

R R

ID

O

R 6A

9 CONTROL

CENTER

A638

MED

PREP

A638A

NOURISHMENT

A638B

CLEAN

SUPPLY

A638C

PA

SS

AG

E

6A

CLEAN

LINEN

A652

SOLID

UTILITY

A651

HAC

A656

NURSE

CALL EQUIP

A655

PATIENT

TOILET

A629

CORRIDOR

6A6

STRETCHER

STORAGE

A630

ANTHERM

A631A

ISOLATION

PATIENT

A631

STAFF LOUNGE/

CONSULTATION

A653

LOCKERS

A654

PATIENT

A639

PATIENT

A640

PATIENT

A641

PATIENT

A642

PATIENT

A643

6A10

A644

STAIR

AS602

WORK RM

A650

STAFF

TOILET

A654A

C

LE

AN

LI

N

EN

TOILET

A646 EQUIP

STORAGE

A648

PATIENT

A645

EQUIP

STORAGE

A647

C O

R R

ID

O

R 6A

6A

ON CALL

RM

A603

EC

AU661

EQUIP

A610A

OR 2

A610

OR 3

A611

SCRUB

A612

EQUIP

A611A

HAC

A613

STAIR

AS601

ELEC

SUB

STERILE

A609

OR 1

A608

ANEST

WORKROOM

A624

STERILIZERS

A607

PROCESSING

A623

SOILED

UTILITY

A621

CLEAN

LINEN

A619

EQUIP

A618 SCRUB

A614

CORRIDOR

6A3

CLEAN

STORAGE

A616

CORRIDOR

6A4

SCRUB

A620

OR 6 GENERAL OR

A622

EQUIP

STORAGE

A622A

OR 5

A617

OR 4

A615

TR

A627

TR

A627

2 2

2 2

222222 2

2 2 2 2

2 2 2 2

2 2 2 2

C

C

C

C

C

1 FLOOR PLAN - SIXTH FLOOR - AREA A

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-160-1.6

DEMO PLAN - BLDG.1

SIXTH FLOOR - AREA A

VV

RMJr

KEY PLAN

B

A

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

DATA AND ELECTRICAL OUTLETS WHERE NOTED.

COORDINATE WITH COR FOR NEW LOCATION.

TRUE

NORTH

PLAN

NORTH

TD-418-1-1A.6

FILES

UROLOGY

PROCEDURE

RM

B615

EQUIP/

SUPPLY

B612A PROCEDURE

RM-9

B612

ANEST

OFFICE

B611

NURSE

MGR

OFFICE

B610

PNEUMATIC

TUBE STATION

C6B4

SUB

STERILE

B609A

LOCKER RM

B617A

MENS TOILET

B617

BIO MED

OFFICE

B614

C6B3 STAIR

BS603

C O

R R

ID

O

R C

6B

LOUNGE

B618

EL

EC

BU

C O

R R

ID

O

R C

6B

STOR

B607

EL

EC

BU

2 AMBULATORY

SURGY

B604 NOURISHMENT

B605

REST RM

B603

NEPTUNE

STOR

B602

REST RM

B601A

B604B603

MED RM

B604A

WOMENS TOILET

B619

HEAD

NURSE

B605A

LOCKER RM

B619A

ANEST

OFFICE

B623 C O

R R

ID

O

R C

6B

1 ELEC

B624A

IMPLANT

CO-ORDR

B624

STOR

B601

CORRIDOR

C6B6

B618

SOILED

UTILITY

B625

ELEVATOR

ELEVATOR

B625A

VACANT

A604

CORRIDOR

C6A1

A607 OFFICE

A606

CONTROL

A605

A601 CORRIDOR

6A1

C O

R R

ID

O

R C

6A

EQUIP

STORAGE

2 22

2 2

2 2 2

C

1 FLOOR PLAN - SIXTH FLOOR - AREA B

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-161-1.6

DEMO PLAN - BLDG. 1

SIXTH FLOOR- AREA B

VV

RMJr

KEY PLAN

B

A

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

DATA AND ELECTRICAL OUTLETS WHERE NOTED.

COORDINATE WITH COR FOR NEW LOCATION.

TRUE

NORTH

PLAN

NORTH

TR

D007D

TR

D007D

1 TR D007D DEMO PLAN

SCALE: 1/2" = 1'-0"

ELEV

P3

A002C

ELEV

P3

A002C

2 TR A002C DEMO PLAN

SCALE: 1/2" = 1'-0"

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO REMAIN

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK - DEMO

5. EXISTING 2-POST RACK - DEMO

6. EXISTING CABLE MANAGER - DEMO

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING CABLE TRAY PATHWAY - TO REMAIN

9. EXISTING SAFE - DEMO. COORDINATE FINAL DISPOSITION OF SAFE SAFE WITH COR.

NOTE: SAFE NOT DRAWN TO SCALE

10. EXISTING 4-POST RACK - DEMO

9 10

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO REMAIN

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK - DEMO

5. EXISTING 2-POST RACK - DEMO

6. EXISTING CABLE MANAGER - DEMO

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING CABLE TRAY PATHWAY - TO REMAIN

9. EXISTING FIBER OPTIC SPLICE - DEMO

TRUE

NORTH

PLAN

NORTH

TRUE

NORTH

PLAN

NORTH

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-400-1-1A-G

BLDGS. 1 & 1A - GROUND FL.

TR DEMO PLAN

VV

1 & 1A

A104A104

1 TR C121 DEMO PLAN

SCALE: 1/2" = 1'-0" 2 TR A104 DEMO PLAN

SCALE: 1/2" = 1'-0"

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO BE RELOCATED

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE

4. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED

5. EXISTING 4-POST RACK - DEMO

6. EXISTING CABLE MANAGER - DEMO

7. EXISTING PLYWOOD BACKBOARD - DEMO

MATV

ACCESS CTL INT

CMAC CTL

BR

G

A

LM

FI

R

E

AL

M

NRS CL

DTR

CM ELV TEL LNS

SPLIT SYSTEM

A/C UNIT

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT

2. EXISTING CABLE TERMINAL

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK

5. EXISTING 2-POST RACK

6. EXISTING CABLE MANAGER

7. EXISTING PLYWOOD BACKBOARD

8. EXISTING CABLE TRAY PATHWAY

9. EXISTING FIREWALL PENETRATION

NOTE: THIS DRAWING DETAIL IS FOR REFERENCE ONLY, UNLESS OTHERWISE NOTED.

6 5

6 5

TRUE

NORTH

PLAN

NORTH

TRUE

NORTH

PLAN

NORTH

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-403-1-1A-1

BLDGS. 1 & 1A - FIRST FLOOR

TR DEMO PLAN

IT

C-222

C222

1 TR C222 DEMO PLAN

SCALE: 1/2" = 1'-0"

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO BE RELOCATED.

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK - DEMO

5. EXISTING 4-POST RACK - DEMO

6. EXISTING CABLE MANAGER - DEMO

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING CABLE TRAY PATHWAY - DEMO

9. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED PRIOR TO DEMO OF WALL.

10. WALL TO BE DEMOED BY OTHERS.

11. EXISTING ENCLOSED CABLE PATHWAY - TO REMAIN

NOTE: EXISTING ELEVATOR LINES WILL BE RELOCATED TO AN ADJACENT WALL. CONTRACTOR WILL COORDINATE WITH THE COR TWO WEEKS PRIOR TO DISCONNECTING, SPLICING, AND RELOCATING

LINES.

OIT

CLOSET

A243 A243

2 TR A243 DEMO PLAN

SCALE: 1/2" = 1'-0"

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO REMAIN

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK - TO REMAIN

5. EXISTING 2-POST RACK - TO REMAIN

6. EXISTING CABLE MANAGER - TO REMAIN

7. EXISTING PLYWOOD BACKBOARD -TO REMAIN

8. EXISTING CABLE TRAY PATHWAY - TO REMAIN

9. EXISTING FIREWALL PENETRATION - TO REMAIN

10. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED PRIOR TO DEMO OF WALL

1 1 2 7

8 4

TRUE

NORTH

PLAN

NORTH

TRUE

NORTH

PLAN

NORTH

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-406-1-1A-2

BLDGS. 1 & 1A - SECOND FL.

TR DEMO PLAN

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO BE RELOCATED.

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO BE RELOCATE BEFORE DEMO OF WALL

4. EXISTING LADDER RACK - DEMO

5. EXISTING 4-POST RACK - DEMO

6. EXISTING CABLE MANAGER - DEMO

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING CABLE TRAY PATHWAY - DEMO

9. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED PRIOR TO DEMO OF WALL.

10. EXISTING WALL TO BE DEMOED BY OTHERS

11. EXISTING ENCLOSED CABLE PATHWAY - TO REMAIN

NOTE: EXISTING ELEVATOR LINES WILL BE RELOCATED TO AN ADJACENT WALL. CONTRACTOR

WILL COORDINATE WITH THE COR TWO WEEKS PRIOR TO DISCONNECTING, SPLICING, AND RELOCATING

LINES.

NOTF:

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO REMAIN

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK - TO REMAIN

5. EXISTING 2-POST RACK - TO REMAIN

6. EXISTING CABLE MANAGER - TO REMAIN

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING CABLE TRAY PATHWAY - TO REMAIN

9. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED PRIOR TO DEMO OF WALL.

10. EXISTING WALL TO BE DEMOED BY OTHERS

11. EXISTING FIREWALL PENETRATION - TO REMAIN

NOTE: EXISTING ELEVATOR LINES WILL BE RELOCATED TO AN ADJACENT WALL. CONTRACTOR

WILL COORDINATE WITH THE COR TWO WEEKS PRIOR TO DISCONNECTING, SPLICING, AND RELOCATING

LINES.

109 3

11 1 32

1 TR C333 DEMO PLAN

SCALE: 1/2" = 1'-0"

TRUE

NORTH

PLAN

NORTH

TRUE

NORTH

PLAN

NORTH

2 TR A345 DEMO PLAN

SCALE: 1/2" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-409-1-1A-3

BLDGS. 1 & 1A - THIRD FLOOR

TR DEMO PLAN

A450

CU411

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO BE RELOCATED.

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK - DEMO

5. EXISTING 4-POST RACK - DEMO

6. EXISTING CABLE MANAGER - DEMO

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING CABLE TRAY PATHWAY - DEMO

9. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED PRIOR TO DEMO OF WALL.

10. EXISTING WALL TO BE DEMOED BY OTHERS

11. EXISTING ENCLOSED CABLE PATHWAY - TO REMAIN

NOTE: EXISTING ELEVATOR LINES WILL BE RELOCATED TO AN ADJACENT WALL. CONTRACTOR

WILL COORDINATE WITH THE COR TWO WEEKS PRIOR TO DISCONNECTING, SPLICING, AND RELOCATING

LINES.

NOTF:

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO BE RELOCATED PRIOR TO DEMO OF WALL

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK - DEMO

5. EXISTING 2-POST RACK - DEMO

6. EXISTING CABLE MANAGER - DEMO

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING CABLE TRAY PATHWAY - DEMO

9. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED PRIOR TO DEMO OF WALL.

10. EXISTING WALL TO BE DEMOED BY OTHERS

11. EXISTING FIREWALL PENETRATION - TO REMAIN

NOTE: EXISTING ELEVATOR LINES WILL BE RELOCATED TO AN ADJACENT WALL. CONTRACTOR

WILL COORDINATE WITH THE COR TWO WEEKS PRIOR TO DISCONNECTING, SPLICING, AND RELOCATING

LINES.

NOTF:

9 3

5 8

1 TR CU411 DEMO PLAN

SCALE: 1/2" = 1'-0"

TRUE

NORTH

PLAN

NORTH

TRUE

NORTH

PLAN

NORTH

2 TR A450 DEMO PLAN

SCALE: 1/2" = 1'-0"

9 1

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-412-1-1A-4

BLDGS. 1 & 1A - FOURTH FL.

TR DEMO PLAN

2. EXISTING CABLE TERMINAL - TO REMAIN

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING LADDER RACK - DEMO

5. EXISTING 2-POST RACK - DEMO

6. EXISTING CABLE MANAGER - DEMO

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED PRIOR TO DEMO OF WALL.

9. EXISTING WALL TO BE DEMOED BY OTHERS

NOTE: EXISTING ELEVATOR LINES SHALL BE RELOCATED TO AN ADJACENT WALL OR AS DIRECTED BY

COR. CONTRACTOR WILL COORDINATE WITH THE COR TWO WEEKS PRIOR TO DISCONNECTING,

SPLICING, AND RELOCATING LINES.

KEYED NOTES:

1. EXISTING WALL MOUNTED EQUIPMENT - TO REMAIN

2. EXISTING CABLE TERMINAL - TO REMAIN

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING CABLE TRAY - TO REMAIN

5. EXISTING 2-POST RACK - TO REMAIN

6. EXISTING LADDER RACK - TO REMAIN

7. EXISTING CABLE MANAGER - TO REMAIN

8. EXISTING PLYWOOD BACKBOARD - TO REMAIN

9. EXISTING WALL TO BE DEMOED BY OTHERS

NOTE: EXISTING ELEVATOR LINES SHALL BE RELOCATED TO AN ADJACENT WALL OR AS DIRECTED BY COR. CONTRACTOR WILL COORDINATE WITH THE COR TWO WEEKS PRIOR TO DISCONNECTING, SPLICING, AND RELOCATING LINES.

1 TR C580 DEMO PLAN

SCALE: 1/2" = 1'-0"

TRUE

NORTH

PLAN

NORTH

TRUE

NORTH

PLAN

NORTH

2 TR AU547 DEMO PLAN

SCALE: 1/2" = 1'-0"

3 2

7 1

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-415-1-1A-5

BLDGS. 1 & 1A - FIFTH FLOOR

TR DEMO PLAN

2. EXISTING CABLE TERMINAL - TO REMAIN

3. EXISTING VERTICAL RISER CONDUIT OR SLEEVE - TO REMAIN

4. EXISTING 2-POST RACK - TO REMAIN

5. EXISTING CABLE MANAGER - TO REMAIN

6. EXISTING CABLE TRAY - TO REMAIN

7. EXISTING PLYWOOD BACKBOARD - TO REMAIN

8. EXISTING WALL MOUNTED EQUIPMENT - TO BE RELOCATED PRIOR TO DEMO OF WALL.

9. EXISTING WALL TO BE DEMOED BY OTHERS

NOTE: EXISTING ELEVATOR LINES SHALL BE RELOCATED TO AN ADJACENT WALL OR AS DIRECTED BY COR. CONTRACTOR WILL COORDINATE WITH THE COR TWO WEEKS PRIOR TO DISCONNECTING, SPLICING, AND RELOCATING LINES.

1 TR A627 DEMO PLAN

SCALE: 1/2" = 1'-0"

TRUE

NORTH

PLAN

NORTH

1 2

TR

A627

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-418-1-1A-6

BLDGS. 1 & 1A - SIXTH FLOOR

TR DEMO PLAN

UP

UP DN

UP

MECH RM

D-B038

EMERGENCY

GENERATOR

D003

TRANSFORMERS

& SWITCHGEAR

D003A

CORRIDOR

DH001

STAIR

PAS06

STAIR

PAS07

ELECTRICAL

D001

TD

D002

CORRIDOR

DH002

MECH RM

D004

EMS

D005

STOR

D005A

STORAGE

D006

ELEVATOR

S6

ELEVATOR

S7

C O

R R

ID

O

R D

H

PAINT

SHOP

D007C

CORRIDOR

DH003 SIGNAL

CLOSET

D008

STORAGE

PA08

PARKING

LEVEL A

PA01

CORRIDOR

DH004

CARPENTER

SHOP

D007

STORAGE

AREA

PA06

CHIEF

D007A

LOCKSMITH

D007B

CORRIDOR

DH005 CHIEF

ELECTRICIA

B014B

M&O

FORMA

B013

CORRIDOR

BH002

STAIR

PAS08

M

EC

H

AN

IC

AL

B0

F

EMERGENCY

POWER

PA06B

NORMAL

POWER

PA06A

TR

D007D

UP

UP DN

UP

MECH RM

D-B038

EMERGENCY

GENERATOR

D003

TRANSFORMERS

& SWITCHGEAR

D003A

CORRIDOR

DH001

STAIR

PAS06

STAIR

PAS07

ELECTRICAL

D001

TD

D002

CORRIDOR

DH002

MECH RM

D004

EMS

D005

STOR

D005A

STORAGE

D006

ELEVATOR

S6

ELEVATOR

S7

C O

R R

ID

O

R D

H

PAINT

SHOP

D007C

CORRIDOR

DH003 SIGNAL

CLOSET

D008

STORAGE

PA08

PARKING

LEVEL A

PA01

CORRIDOR

DH004

CARPENTER

SHOP

D007

STORAGE

AREA

PA06

CHIEF

D007A

LOCKSMITH

D007B

CORRIDOR

DH005 CHIEF

ELECTRICIA

B014B

M&O

FORMA

B013

CORRIDOR

BH002

STAIR

PAS08

M

EC

H

AN

IC

AL

B0

F

EMERGENCY

POWER

PA06B

NORMAL

POWER

PA06A

TR

D007D c c c

G

2 2 c c

1 FLOOR PLAN - GROUND FLOOR - AREAS D & PA

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TN-200-1A.G

FLOOR PLAN - BLDG. 1A

PARKING GARAGE - AREA D

VV

1A

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

TN-402-1A.G

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL NEW CABLE

TRAYS AS INDICATED ON TECHNOLOGY

PATHWAY PLANS.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE EXISTING

COMMUNICATIONS CABLES WITH NEW

CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL

BE OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A CABLES AND CONNECTIVITY COMPONENTS

THAT ARE OF THE SAME MANUFACTURER,

INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND

EXISTING RE-TERMINATED CABLES IN

ACCORDANCE WITH THE SPECIFICATION 27 08

00.

MOTOR

CYCLE PARKING

WHEEL

CHAIR PARKING

PARKING

LEVEL A

PA01

STAIRWELL

PAS05

ELEVATOR

PAE04

ELEVATOR

PAE05

ELEVATOR

LOBBY

PA02

STORAGE

PA07

OTHER

SPACE

PAM03

M

EC

H B0 C

O R

R

ID

O R

BH

STORAGE

A008

FOOD

STORAG

A006A

STAIRWELL

PAS04

MOTOR

CYCLE PARKING

WHEEL

CHAIR PARKING

PARKING

LEVEL A

PA01

STAIRWELL

PAS05

ELEVATOR

PAE04

ELEVATOR

PAE05

ELEVATOR

LOBBY

PA02

STORAGE

PA07

OTHER

SPACE

PAM03

M

EC

H B0 C

O R

R

ID

O R

BH

STORAGE

A008

FOOD

STORAG

A006A

STAIRWELL

PAS04

c

G c c c c c

G G

1 FLOOR PLAN - PARKING GARAGE - LEVEL A

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TN-201-1A.G

FLOOR PLAN - BLDG. 1A

PARKING GARAGE - AREA PA

VV

1A

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL NEW CABLE

TRAYS AS INDICATED ON TECHNOLOGY

PATHWAY PLANS.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE EXISTING

COMMUNICATIONS CABLES WITH NEW

CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL

BE OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A CABLES AND CONNECTIVITY COMPONENTS

THAT ARE OF THE SAME MANUFACTURER,

INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND

EXISTING RE-TERMINATED CABLES IN

HANDICAPPEDHANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING PARKING

LEVEL B

FAN RM

PB04

STAIRWELL

PBS06

TC

PB06

EC

PB05

OTHER SPACE

PB07

UTILITY TUNNEL

OTHER SPACE

PB09

PARKING

PB01

CHASE

PB03

HANDICAPPEDHANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING PARKING

LEVEL B

FAN RM

PB04

STAIRWELL

PBS06

TC

PB06

EC

PB05

OTHER SPACE

PB07

UTILITY TUNNEL

OTHER SPACE

PB09

PARKING

PB01

CHASE

PB03

c c c c c

G

1 FLOOR PLAN - PARKING GARAGE - LEVEL B

SCALE: 1/8" = 1'-0"

TN-202-1A.G

FLOOR PLAN - BLDG. 1A

PARKING GARAGE - LEVEL B

VV

1A

TRUE

NORTH

PLAN

NORTH

KEY PLAN

PA

D

B

A

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL NEW CABLE

TRAYS AS INDICATED ON TECHNOLOGY

PATHWAY PLANS.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE EXISTING

COMMUNICATIONS CABLES WITH NEW

CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL

BE OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A CABLES AND CONNECTIVITY COMPONENTS

THAT ARE OF THE SAME MANUFACTURER,

INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND

EXISTING RE-TERMINATED CABLES IN

ACCORDANCE WITH THE SPECIFICATION 27 08

00.

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

WHEEL CHAIR PARK

HANDICAPPED

PARKING

HANDICAPPED

HANDICAPPED

PARKING PARKING

HANDICAPPED

PARKING

HANDICAPPED HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

DOWN

UP

DOWN

UP

CHASE

PB03

STAIRWELL

PBS05

ELEVATOR

P4

ELEVATOR

P5

ELEV

VESTIBULE

PB02

STORAGE

PB10

PUMP RM

0-C-1

STAIRWELL

PBS04

OTHER SPACE

PB11

WHEEL CHAIR PARK

HANDICAPPED

PARKING

HANDICAPPED

HANDICAPPED

PARKING PARKING

HANDICAPPED

PARKING

HANDICAPPED HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

DOWN

UP

DOWN

UP

CHASE

PB03

STAIRWELL

PBS05

ELEVATOR

P4

ELEVATOR

P5

ELEV

VESTIBULE

PB02

STORAGE

PB10

PUMP RM

0-C-1

STAIRWELL

PBS04

OTHER SPACE

PB11

c c c c

G

G

1 FLOOR PLAN - PARKING GARAGE - LEVEL B

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TN-203-1A.G

FLOOR PLAN - BLDG. 1A

PARKING GARAGE - LEVEL B

VV

1A

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL NEW CABLE

TRAYS AS INDICATED ON TECHNOLOGY

PATHWAY PLANS.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE EXISTING

COMMUNICATIONS CABLES WITH NEW

CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL

BE OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A CABLES AND CONNECTIVITY COMPONENTS

THAT ARE OF THE SAME MANUFACTURER,

INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND

EXISTING RE-TERMINATED CABLES IN

FF:CONCRETE

FF:CONCRETE

FF:VCT

FF:CONCRETE FF:CONCRETE

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FAN RM

00-D-1

STAIR

PCS06

EC

00-D-2

TC

00-D-3

MECH RM

PC10

STORAGE

PC09

OTHER SPACE

PCM11

PARKING

PC01

STORAGE

PC05

STAIR

SUMP

00-C-3

FF:CONCRETE

FF:CONCRETE

FF:VCT

FF:CONCRETE FF:CONCRETE

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FAN RM

00-D-1

STAIR

PCS06

EC

00-D-2

TC

00-D-3

MECH RM

PC10

STORAGE

PC09

OTHER SPACE

PCM11

PARKING

PC01

STORAGE

PC05

STAIR

SUMP

00-C-3 c c c c c c

G

G

G

1 FLOOR PLAN - PARKING GARAGE - LEVEL C

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TN-204-1A.G

FLOOR PLAN - BLDG. 1A

PARKING GARAGE - LEVEL C

VV

1A

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL NEW CABLE

TRAYS AS INDICATED ON TECHNOLOGY

PATHWAY PLANS.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE EXISTING

COMMUNICATIONS CABLES WITH NEW

CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL

BE OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A CABLES AND CONNECTIVITY COMPONENTS

THAT ARE OF THE SAME MANUFACTURER,

INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND

EXISTING RE-TERMINATED CABLES IN

DOWN

MOTORCYCLE

MOTORCYCLE

FF:VCT

FF:VCT

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FF:CONCRETE

FF:VCT

STORAGE

PC05

STAIR

PCS05

ELEV

EQUIP

00-C-1

ELEVATOR

PCE04

ELEVATOR

PCE05

ELEVATOR

LOBBY

PC02

STORAGE

PC16

MECH

RM

PC15

STORAGE

00C6

STORAGE

PC14

STAIRWELL

PCS04

SUMP

00-C-3

FAN RM

00-C-2

OTHER SPACE

PCM17

DOWN

UP

MOTORCYCLE

MOTORCYCLE

FF:VCT

FF:VCT

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FF:CONCRETE

FF:VCT

STORAGE

PC05

STAIR

PCS05

ELEV

EQUIP

00-C-1

ELEVATOR

PCE04

ELEVATOR

PCE05

ELEVATOR

LOBBY

PC02

STORAGE

PC16

MECH

RM

PC15

STORAGE

00C6

STORAGE

PC14

STAIRWELL

PCS04

SUMP

00-C-3

FAN RM

00-C-2

OTHER SPACE

PCM17

c c c

G

G

1 FLOOR PLAN - PARKING GARAGE - LEVEL C

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TN-205-1A.G

FLOOR PLAN - BLDG. 1A

PARKING GARAGE - LEVEL C

VV

1A

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL NEW CABLE

TRAYS AS INDICATED ON TECHNOLOGY

PATHWAY PLANS.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE EXISTING

COMMUNICATIONS CABLES WITH NEW

CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL

BE OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A CABLES AND CONNECTIVITY COMPONENTS

THAT ARE OF THE SAME MANUFACTURER,

INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND

EXISTING RE-TERMINATED CABLES IN

ELECTRICAL

CORRIDOR

AH010

STERILE AND

NON-STERILE

STORAGE

A001A

A005C

GAS CYL

STORAGE

B005D

CLEAN

RECEIVING

B007

CORRIDOR

AH003

GE

RETAIL

STORE

A009

C O

R R

ID

O

R

AH

ASST

CHIEF

A012

CLERK

TYPIST

A011

CHIEF

A010

OFFICE

CANTEEN

A007

REFR

WALK IN

A006B

PREFAB

REFRIG

A006C

FOOD

STORAGE

A006A

LL

KITCHEN

A006

HAC

A006F

AU008 AU007 AU006

CORRIDOR

AH001

STAIR

AS002 STORAGE

A004

CAFETERIA

A004A

FOOD

SERVICING

A006D

SERVING

LINE

A005

SURGICAL

PACK

B045C

MAIN

KITCHEN

B036

EQUIP

STORAGE

AREA

B001

ELECTRIC

CLOSET

BU003

EMS

A001B

DUMB

ELEVATOR

OFFICE

A019

ELEVATOR

LOBBY

A001

OFFICE

ASST

CHIEF

A003

ELEV

AE004

ELEV

AE005

BREAK

RM

A021

ELEVATOR

LOBBY

A000

DISH

WASHING

A020

ELECTRIC

CLOSET

AU004

EMS

A023

CORRIDOR

AH004

DIETICIANS

OFFICE

A025

ASST

CHIEF

A027

DIETICIANS

OFFICE

A025A

SECY

A028

CORRIDOR

AH005

CONFERENCE M

A029

CORRIDOR

BH006

SUPV

OFFICE

B045

BREAK

RM

B045A

ELECTRICAL

AU003

ELECTRICAL

AU002CORRIDOR

AH004 AU001

ELECTRIC

CLOSET

AU005

EMS

A004B

STORAGE

A004A

VCS

OFFICE

A004A

CHIEF

VCS

OFFICE

A004E

LOCKERS

FEMALE

A002A

LOUNGE

A002

ELEV

P3

ELEV

P2

ELEV

P1

TOILET &

SHOWERS

A002B

TELEPHONE

EQUIP RM

A022

TOILET

A024 EMS

A026

LOCKERS

A026B

OT

CLINIC

A044

A026A

TOILET &

SHOWERS

A046

TOILET

FEMALE

A045

C O

R R

ID

O

R

AH

CORRIDOR

AH007

OT

OFFICE

A043

OT

OFFICE

A043A

OFFICE

A070RECEIVING

A071

CORRIDOR

AH009

OFFICE

A069

PGM MGR

A068

SOFTWARE

APPL

SUPPORT

A067

APPLICATION

SUPPORT

A066

SYSTEMS

MGR

A065

NETWORKING

MGR

A064

PROG MGR

SYST &

NETWORKING

A063ADP

WORKSHOP

A062

STAIRWELL

AS004

TELECOMM

SVCS

A061

TELECOMM

SVCS

A060

SUPPORT

A059

APPLICATION

SUPPORT

A058

APPLICATION

SUPPORT

A057

CONFERENCE

RM

A055

C O

R R

ID

O

R

AH

PGMMING

& INFO

A054

PGMMING

& INFO

A053

PGM

SPECIALISTS

A052

OFFICE

A051

RECEPTION

AREA

A050

TRACTION

A039

PROVIDER

A038

EXAM

A040

EXAM

A041

CORRIDOR

A030A

EXAM/

EMG

A037

WAITING

AREA A042

STAIRWELL

AS001

WAITING

AREA

A036

PHYSICAL

THERAPY

WORK

ROOM

RECEPTION

A030

THERAPY

A034A

THERAPY

A034

PHYSICAL

THERAPY

A035

STORAGE

A033

PM&RS

CHIEF'S

OFFICE

A032A

SECY

OFFICE

A032B

RESIDENTS

OFFICE

A032C

HALL

A032

CONFERENCE

RM

A032D CHARTING

A032E

TR

A002C

DATA

CENTER

A073

FIRE

PROTECT

A072

ELECTRICAL

CORRIDOR

AH010

STERILE AND

NON-STERILE

STORAGE

A001A

A005C

GAS CYL

STORAGE

B005D

CLEAN

RECEIVING

B007

CORRIDOR

AH003

GE

RETAIL

STORE

A009

C O

R R

ID

O

R

AH

ASST

CHIEF

A012

CLERK

TYPIST

A011

CHIEF

A010

OFFICE

CANTEEN

A007

REFR

WALK IN

A006B

PREFAB

REFRIG

A006C

FOOD

STORAGE

A006A

LL

KITCHEN

A006

HAC

A006F

AU008 AU007 AU006

CORRIDOR

AH001

STAIR

AS002 STORAGE

A004

CAFETERIA

A004A

FOOD

SERVICING

A006D

SERVING

LINE

A005

SURGICAL

PACK

B045C

MAIN

KITCHEN

B036

EQUIP

STORAGE

AREA

B001

ELECTRIC

CLOSET

BU003

EMS

A001B

DUMB

ELEVATOR

OFFICE

A019

ELEVATOR

LOBBY

A001

OFFICE

ASST

CHIEF

A003

ELEV

AE004

ELEV

AE005

BREAK

RM

A021

ELEVATOR

LOBBY

A000

DISH

WASHING

A020

ELECTRIC

CLOSET

AU004

EMS

A023

CORRIDOR

AH004

DIETICIANS

OFFICE

A025

ASST

CHIEF

A027

DIETICIANS

OFFICE

A025A

SECY

A028

CORRIDOR

AH005

CONFERENCE M

A029

CORRIDOR

BH006

SUPV

OFFICE

B045

BREAK

RM

B045A

ELECTRICAL

AU003

ELECTRICAL

AU002CORRIDOR

AH004 AU001

ELECTRIC

CLOSET

AU005

EMS

A004B

STORAGE

A004A

VCS

OFFICE

A004A

CHIEF

VCS

OFFICE

A004E

LOCKERS

FEMALE

A002A

LOUNGE

A002

ELEV

P3

ELEV

P2

ELEV

P1

TOILET &

SHOWERS

A002B

TELEPHONE

EQUIP RM

A022

TOILET

A024 EMS

A026

LOCKERS

A026B

OT

CLINIC

A044

A026A

TOILET &

SHOWERS

A046

TOILET

FEMALE

A045

C O

R R

ID

O

R

AH

CORRIDOR

AH007

OT

OFFICE

A043

OT

OFFICE

A043A

OFFICE

A070RECEIVING

A071

CORRIDOR

AH009

OFFICE

A069

PGM MGR

A068

SOFTWARE

APPL

SUPPORT

A067

APPLICATION

SUPPORT

A066

SYSTEMS

MGR

A065

NETWORKING

MGR

A064

PROG MGR

SYST &

NETWORKING

A063ADP

WORKSHOP

A062

STAIRWELL

AS004

TELECOMM

SVCS

A061

TELECOMM

SVCS

A060

SUPPORT

A059

APPLICATION

SUPPORT

A058

APPLICATION

SUPPORT

A057

CONFERENCE

RM

A055

C O

R R

ID

O

R

AH

PGMMING

& INFO

A054

PGMMING

& INFO

A053

PGM

SPECIALISTS

A052

OFFICE

A051

RECEPTION

AREA

A050

TRACTION

A039

PROVIDER

A038

EXAM

A040

EXAM

A041

CORRIDOR

A030A

EXAM/

EMG

A037

WAITING

AREA A042

STAIRWELL

AS001

WAITING

AREA

A036

PHYSICAL

THERAPY

WORK

ROOM

RECEPTION

A030

THERAPY

A034A

THERAPY

A034

PHYSICAL

THERAPY

A035

STORAGE

A033

PM&RS

CHIEF'S

OFFICE

A032A

SECY

OFFICE

A032B

RESIDENTS

OFFICE

A032C

HALL

A032

CONFERENCE

RM

A032D CHARTING

A032E

TR

A002C

DATA

CENTER

A073

FIRE

PROTECT

A072

2 2

2 2 2 2 2

2 2

2 2 2 2

2 2 2 2

2 2

G

G

G

2 2

2 2 c c cc c

G c c cc

G

G

2 2

2 2

2 2

2 2

2 2

2 2 c c c

1 FLOOR PLAN - GROUND FLOOR - AREA A

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TN-207-1.G

FLOOR PLAN - BLDG. 1

GROUND FLOOR - AREA A

VV

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

TN-401-1.G

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL NEW CABLE

TRAYS AS INDICATED ON TECHNOLOGY

PATHWAY PLANS.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE EXISTING

COMMUNICATIONS CABLES WITH NEW

CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL

BE OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A CABLES AND CONNECTIVITY COMPONENTS

THAT ARE OF THE SAME MANUFACTURER,

INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND

EXISTING RE-TERMINATED CABLES IN

DN

DN

OR CHIEF

ELECTRICIAN

B014B

M&O

FORMAN

B013

ELECTRONIC

B014

ELECTRIC

SHOP

B014C

STAFF

TOILET

B015A

OFFICE

B017

STORAGE

FLAMMABLE

B016

STORAGE

GENERAL

B020

WAREHOUSE

B015

MAIL RM

B015B

EMS

EQUIP

B021 SOILED

UTILITY

B022A OFFICE

B022D

OFFICE

B022E

C O

R R

ID

O

R

BH

TOILET

FEMALE

B019

TOILET

MALE

B018

MENS

TOILET

B003

HALL

B004

STORAGE

B009A

SOILED RECEIVING

DECONTAMINATION

AREA

B005

LOGISTICS

BREAKDOWN

B006B

HALL

B006A

ELEC.

B009

ELECTRIC

CLOSET

BU002

CORRIDOR

BH003

UNION

OFFICE

B011A

LOGISTICS

STORAGE

B011

OFFICE

B012A

PROSTHETICS

STORAGE

B015C

MORGUE

B015A

CORRIDOR

BH002

AC

PLUMBING

MACH

B012

BULK

STORAGE

B010

CORRIDOR

OX101

PREPARATION

STERILIZATION

WORK RM

A005C

GAS CYL

STORAGE

B005D

CLEAN

RECEIVING

B007

CORRIDOR

AH003

LOGISTICS SVC

INVENTORY MGMT

B022

WOMENS

TOILET

B002

CORRIDOR

BH004

OFFICE

B022C

OFFICE

B022B

OFFICE

B022A

C O

R R

ID

O

R

BH

EMERGENCY

GENERATOR RM

B037

C O

R R

ID

O

R

BH

FEMALE

TOILET

B040

MENS

TOILET

B041

EMS

B036C

LINEN

B036D

CANTEEN

STORAGE

B036B

MAIN

KITCHEN

B036

ENVIRONMENTAL

MGMT SUPPLY

B045D

SURGICAL

PACK

B045C

STORAGE

B045B

MAIN

KITCHEN

B036

OFFICE

SUPVS

B036F

DAIRY &

EGG

REFRIG

B036G

STORAGE

B035A

OFFICE

B035

STORAGE &

ISSUE

B034

STAIRWELL

BS003

EMS

B005A

MANUAL

CART

WASH

B005B

EQUIP

STORAGE

AREA

B001

ELECTRIC

CLOSET

BU003

SUPV

OFFICE

B045

BREAK

RM

B045A

PM&RS

CHIEF'S

OFFICE

A032A

SECY

OFFICE

A032B

RESIDENTS

OFFICE

A032C

HALL

A032

CONFERENCE

RM

A032D CHARTING

A032E

IT

B046

HAS

B044

TOILET

B044AEMS

B043

ELECTRIC

CLOSET

B043A

EMS

CHECK IN

B042B

EMS

OFFICE

B042A HAS

B044B

HAS

B044C

SVC RM

B039

SECY/

RECEPTIONIST

B-042

OFFICE ASST

CHIEF WORK

RM

B-042C

CORRIDOR

BH004

ELECTRICAL

DISTRIBUTION

RM

B037B

A/C

REFRIGERATION

EQUIP RM

B038

TRANSFORMER

RM

B037A

TR

B046A

UP

DN

DN

OR CHIEF

ELECTRICIAN

B014B

M&O

FORMAN

B013

ELECTRONIC

B014

ELECTRIC

SHOP

B014C

STAFF

TOILET

B015A

OFFICE

B017

STORAGE

FLAMMABLE

B016

STORAGE

GENERAL

B020

WAREHOUSE

B015

MAIL RM

B015B

EMS

EQUIP

B021 SOILED

UTILITY

B022A OFFICE

B022D

OFFICE

B022E

C O

R R

ID

O

R

BH

TOILET

FEMALE

B019

TOILET

MALE

B018

MENS

TOILET

B003

HALL

B004

STORAGE

B009A

SOILED RECEIVING

DECONTAMINATION

AREA

B005

LOGISTICS

BREAKDOWN

B006B

HALL

B006A

ELEC.

B009

ELECTRIC

CLOSET

BU002

CORRIDOR

BH003

UNION

OFFICE

B011A

LOGISTICS

STORAGE

B011

OFFICE

B012A

PROSTHETICS

STORAGE

B015C

MORGUE

B015A

CORRIDOR

BH002

AC

PLUMBING

MACH

B012

BULK

STORAGE

B010

CORRIDOR

OX101

PREPARATION

STERILIZATION

WORK RM

A005C

GAS CYL

STORAGE

B005D

CLEAN

RECEIVING

B007

CORRIDOR

AH003

LOGISTICS SVC

INVENTORY MGMT

B022

WOMENS

TOILET

B002

CORRIDOR

BH004

OFFICE

B022C

OFFICE

B022B

OFFICE

B022A

C O

R R

ID

O

R

BH

EMERGENCY

GENERATOR RM

B037

C O

R R

ID

O

R

BH

FEMALE

TOILET

B040

MENS

TOILET

B041

EMS

B036C

LINEN

B036D

CANTEEN

STORAGE

B036B

MAIN

KITCHEN

B036

ENVIRONMENTAL

MGMT SUPPLY

B045D

SURGICAL

PACK

B045C

STORAGE

B045B

MAIN

KITCHEN

B036

OFFICE

SUPVS

B036F

DAIRY &

EGG

REFRIG

B036G

STORAGE

B035A

OFFICE

B035

STORAGE &

ISSUE

B034

STAIRWELL

BS003

EMS

B005A

MANUAL

CART

WASH

B005B

EQUIP

STORAGE

AREA

B001

ELECTRIC

CLOSET

BU003

SUPV

OFFICE

B045

BREAK

RM

B045A

PM&RS

CHIEF'S

OFFICE

A032A

SECY

OFFICE

A032B

RESIDENTS

OFFICE

A032C

HALL

A032

CONFERENCE

RM

A032D CHARTING

A032E

IT

B046

HAS

B044

TOILET

B044AEMS

B043

ELECTRIC

CLOSET

B043A

EMS

CHECK IN

B042B

EMS

OFFICE

B042A HAS

B044B

HAS

B044C

SVC RM

B039

SECY/

RECEPTIONIST

B-042

OFFICE ASST

CHIEF WORK

RM

B-042C

CORRIDOR

BH004

ELECTRICAL

DISTRIBUTION

RM

B037B

A/C

REFRIGERATION

EQUIP RM

B038

TRANSFORMER

RM

B037A

TR

B046A

2 2

2 2

2 2

2 2

2 2

2 2 c c c c c c c

2 2

2 2 2

22 2 222 c c trash compator c

IT

B046

1 FLOOR PLAN - GROUND FLOOR - AREA B

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TN-208-1.G

FLOOR PLAN - BLDG. 1

GROUND FLOOR - AREA B

VV

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

GENERAL NOTES

1. CONTRACTOR SHALL INSTALL NEW CABLE

TRAYS AS INDICATED ON TECHNOLOGY

PATHWAY PLANS.

2. CONTRACTOR SHALL INSTALL NEW J-HOOKS

WHERE THERE IS NO CABLE TRAY OR

COMMUNICATIONS CONDUIT UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A PATCH PANELS IN THE TELECOMMUNICATION

ROOM AS INDICATED ON RACK ELEVATIONS.

4. CONTRACTOR SHALL RE-TERMINATE AND TEST

CABLING REMOVED FROM ANY WALL MOUNT

EQUIPMENT UNLESS OTHERWISE NOTED.

TESTING SHALL BE PERFORMED BY THE

CONTRACTOR DURING COMMISSIONING.

5. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A TELECOMMUNICATIONS/DATA OUTLET AS

INDICATED. EXISTING COMMUNICATION OUTLET

BOXES AND CONDUITS TO BE REUSED.

6. CONTRACTOR SHALL REPLACE ALL DATA CABLE

WITH NEW CATEGORY 6A CABLE UNLESS

OTHERWISE NOTED.

7. CONTRACTOR SHALL TERMINATE EXISTING

COMMUNICATIONS CABLES WITH NEW

CATEGORY MODULAR JACKS TO MATCH THE

COMMUNICATION CABLE PERFORMANCE

SPECIFICATIONS. NEW MODULAR JACKS SHALL

BE OF THE SAME MANUFACTURER AS THE FACE

PLATES, PATCH PANELS, AND PATCH CABLES.

8. CONTRACTOR SHALL INSTALL NEW CATEGORY

6A CABLES AND CONNECTIVITY COMPONENTS

THAT ARE OF THE SAME MANUFACTURER,

INCLUDING CABLE, MODULAR JACKS, PATCH

PANELS, FACEPLATES, AND PATCH CABLES.

9. CONTRACTOR SHALL TEST ALL NEW AND

EXISTING RE-TERMINATED CABLES IN

1 FLOOR PLAN - FIRST FLOOR - AREA A

SCALE: 1/8" = 1'-0"

A-184

S V

A-153

A-185

A-150A

A-184C

AS107

A-152

IN-VITRO

COUNTING

HIGH/LOW

A-166

A-184A A-184B

CORRIDOR

BH106

DRESSING

RM ALCOVE

B146G

EL

EC

BU

EL BU

WAITING

A-150

CORRIDOR

BH101

FILE

RM

A-151A

A-151

BONE

DENSITY

A-159

VACANT

B131

OFFICE

B132A

VIEWING

RM B132

LOUNGE

B133

KITCHEN

B133A

MECH

B133B

STAFF

TOILET

B133A

CORRIDOR

BH102

PHARMACY

WAITING

A-186

C O

R R

ID

O

R

AH

SUPPLY

A-160

BREAK

RM

A-156

READING

RM A-158

EXAM

A-157

MENS

RESTROOM

A-155

WOMENS

RESTROOM

A-154

STORAGE

A-152B

HOT

LAB

A-152A

HOT

LAB

A-152B P

EM

CLOS

B10

ELECT

CLOS

BU1

STAIR

AS102

AS108 AS106

CORRIDOR

AH102

PHARMACY

OFFICE

A-189

OFFICE

NURSE

MGR

A177

PATIENT

ADVOCATE

A102

INPT

PHARMACY

A103

CORRIDOR

A-191

VAULT

A-180

CONFERENCE

RM

A174

TECHNICIAN

OFFICE

A-179

C O

R R

ID

O

R A-

PRE-PACK

A-177a

ANTEROOM

A-190

IV

STORAGE

A-190a

CORRIDOR

AH103

MGR

CMOP

A-178

ACOS

AMB

CARE

A-190C

SUPPORT

UNIT ADMIN

A-190b

ADMIN

ASSIST

A-188

INVESTIGATION

DRUGS SVC

PGME MGR

A164

MED MGMT

SPECIALIST

A-163FORMULARY

MGR

A-165

PHARMACY

OPERATION

MGR

A-166

CLINICAL

PHARMACIST

A-167

JANITOR

A-167A

CORRIDOR

A-162

WOMEN

A-176

MEN

A-175

ASSOCIATE

CHIEF OF

PHARMACY

OFFICE

A-171

CRITICAL

CARE

PHARMACY

SPECIALIST

OFFICE

A-170

PHARMACY

ADAPC

A-169

CHIEF

A-168

DIRECTOR

OFFICE A125

TOILET

A125A

ADMIN

ASST TO

DIRECTOR

A126

FACILITY

PLANNER

OFFICE

A115

ASSOCIATE

NURSE

EXECUTIVE

OFFICE

A127

C O

R R

ID

O

R

AH

8CHIEF OF

REVENUE &

RESOURCES

ANALYSIS

SECY

A114

QUALITY

PERFORMANCE

& PATIENT

SAFETY ADMIN

OFFICE

A113

QUALITY

MGMT

DIRECTOR

A128

PUBLIC

AFFAIRS

A129

ASSOCIATE

NURSE

EXECUTIVE

A130

RECEPTIONIST

A133

CORRIDOR

AH107

COPY

RM

A134FEMALE

TOILET

A141

MALE

TOILET

A142

ELEC

AU101

ELEC

AU102

ELEC

AU103

STAIR

AS101

SVC

A-112PGM

ANALYST

A111

CORRIDOR

AH105

QUALITY

MGMT

A110

MED STAFF

CO-ORDR

A118

EX ASST

COS

OFFICE

A117

CHIEF OF

STAFF

A120

SECY

OFFICE

A121

DEPUTY

CHIEF

A121A

BREAK

RM

A122

CORRIDOR

AH109

ASSOCIATE

DIRECTOR

A123

SEC

OFFICE

A124

CONFERENCE

RM A116

FEMALE

TOILET

A106

QUALITY

MGMT

A109

HEALTH

SYSTEM

SPECIALIST

A119

MALE

TOILET

A107

ST

O

R

AG

E A1

CORRIDOR

AH110

STAFF

TOILET

A105A

DAV

SVC

OFFICE

A105

VFW

SVC

A101

LOBBY

A100

OFFICE

A105B

CORRIDOR

AH101

ELEVATOR

P3

ELEVATOR

P2

ELEVATOR

P1

ELEV

LOBBY

ELEVATOR

S4

ELEVATOR

S5

COPIER/

FAX RM

A145 ELEC

AU104

ELEC

AU-105

BMS

CLOSET

A178

STOCK

RM

A149EMS

A148

SVC ELEV

LOBBY

1B-1

CORRIDOR

AH101

SPECIMEN

TOILET

A140B

STORAGE

A140

ASSOCIATE

DIRECTOR

FOR…