596A4-22-700 Drawings 06 - Mechanical.pdf

PDF 3 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Lexington-Cooper, KY 596A4-22-700
Solicitation number
36C77623B0069
Issued by

About this file

This document outlines the requirements for infrastructure upgrades at the Lexington-Cooper VA Medical Center in Lexington, Kentucky. The scope of work includes mechanical, electrical, and technology improvements to support the expansion and renovation of the Emergency and Hospital Resource Management department. Upgrades are required for HVAC systems, including the installation of new air handling units, variable refrigerant flow units, computer room air conditioners, and associated ductwork and piping. Electrical work includes connecting new systems to the existing building automation system. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center and has an estimated value of $5-10 million. The completion date is scheduled for January 2024.

View the file

Other files

File Type Posted
596A4-22-700 Responses to Tech Questions - 1-25-24.pdf PDF
36C77623B0069 0008.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-22-24.pdf PDF
36C77623B0069 0007.pdf PDF
36C77623B0069 0006.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-18-24.pdf PDF
36C77623B0069 0005.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-12-24.pdf PDF
36C77623B0069 0004.pdf PDF
596A4-22-700 Security Requirements.pdf PDF
DBA Wage Rates - Fayette County - 01-05-24.pdf PDF
596A4-22-700 Smoke Shack.pdf PDF
596A4-22-700 Handrail Submittal.pdf PDF
596A4-22-700 Drawing M-701 - Mechanical Controls.pdf PDF
596A4-22-700 Specification 23 09 23 - DDC for HVAC.pdf PDF
DBA Wage Rates - Fayette County - 12-22-23.pdf PDF
36C77623B0069 0003.pdf PDF
36C77623B0069 0002.pdf PDF
596A4-22-700 Site Visit Sign-in Sheet - 11-28-23.pdf PDF
36C77623B0069 0001.pdf PDF
596A4-22-700 Drawings 01 - General.pdf PDF
596A4-22-700 Drawings 12 - Security.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
596A4-22-700 Drawings 03 - Arch.pdf PDF
596A4-22-700 Specifications.pdf PDF
596A4-22-700 Drawings 07 - Electrical.pdf PDF
596A4-22-700 Drawings 05 - Plumbing.pdf PDF
596A4-22-700 Drawings 09 - Tech 2.pdf PDF
596A4-22-700 Drawings 10 - Tech 3.pdf PDF
596A4-22-700 Drawings 04 - Fire Protection.pdf PDF
DBA Wage Rates - Fayette County - 09-08-23.pdf PDF
596A4-22-700 Asbestos Inspection Report.pdf PDF
596A4-22-700 Drawings 11 - Tech 4.pdf PDF
596A4-22-700 Brand Name Justification.pdf PDF
IFB 36C77623B0069.docx DOCX document
596A4-22-700 Drawings 02 - Asbestos.pdf PDF
596A4-22-700 Drawings 08 - Tech 1.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X

MECHANICAL ABBREVIATIONS

A AIR OR AMP (PER CONTEXT)

ACC ACCESSORIES

AD ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AFS AIR FLOW SWITCH

AHRI AIR CONDITIONING, HEATING, AND

REFRIGERATION INSTITUTE

AI ANALOG SIGNAL INPUT

AMB AMBIENT

AO ANALOG SIGNAL OUTPUT

AP ACCESS PANEL

APD AIR PRESSURE DROP

APLV APPLICATION PART LOAD VALUE

APPROX APPROXIMATE

ARCH ARCHITECTURE/ARCHITECT

AUX AUXILIARY

AV AUTOMATIC VENT

AVG AVERAGE

BDD BACK DRAFT DAMPER

BFC BELOW FINISHED CEILING

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BI BINARY SIGNAL INPUT

BMS BUILDING MANAGEMENT SYSTEM

BO BINARY SIGNAL OUTPUT

BOB BOTTOM OF BEAM

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BS BEAM SPACE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNITS PER HOUR

BWE BAKED WHITE ENAMEL

CAP CAPACITY

CAV CONSTANT AIR VOLUME

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CLG COOLING DUCT (COLD DUCT)

CO CLEAN OUT

COMP COMPRESSOR

CONC CONCRETE

COND CONDENSATE

CONN CONNECTION

CORR CORRIDOR

CV CONTROL VALVE

D DEPTH

DB DRY BULB

DBA A-WEIGHTED DECIBELS

DEFL DEFLECTION

DEG DEGREES

DEG F DEGREES FAHRENHEIT

DES DESIGN

DIA DIAMETER

DIM DIMENSION

DISCH DISCHARGE

DIV DIVISION

DN DOWN

DP DIFFERENTIAL PRESSURE SENSOR

DPS DIFFERENTIAL PRESSURE SWITCH

DPT DIFFERENTIAL PRESSURE TRANSMITTER

DTL DETAIL

DWG(S) DRAWING(S)

EA EXHAUST AIR OR EACH (PER CONTEXT)

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENT RATIO

EFF EFFICIENCY

ELEC ELECTRIC

ELEV ELEVATION

EQ EQUAL

ESP EXTERNAL STATIC PRESSURE

EWB ENTERING AIR WET BULB TEMPERATURE

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST, EX EXISTING

EXT EXTERNAL

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

FC FLEXIBLE CONNECTION

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FIN FINISHED

FLR FLOOR

FPF FINS PER FOOT

FPM FEET PER MINUTE

FS FLOW SWITCH

FT FEET

FT-HD HEAD IN FEET

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GC GENERAL CONTRACTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

H HEIGHT

HD HEAD

HEV HOSE END VALVE

HORIZ HORIZONTAL

HP HORSEPOWER

HR HOUR

HTG HEATING DUCT (HOT DECK)

HVAC HEATING, VENTILATING & AIR

CONDITIONING

HW HOT WATER

HZ HERTZ

IB INVERTED BUCKET

IE INVERT ELEVATION

IN INCH/INCHES

INDIC INDICATOR

IPLV INTEGRATED PART-LOAD VALUE

ISP INTERNAL STATIC PRESSURE

JS JOIST SPACE

KW KILOWATTS

L LENGTH

LAT LEAVING AIR TEMPERATURE

LB(S) POUNDS

LF LINEAR FEET

LRA LOCKED ROTOR AMPS

LS LIGHT SPACE

LVL LEVEL

LWT LEAVING WATER TEMPERATURE

MAN MANUAL

MANU MANUFACTURER

MAX MAXIMUM

MBH THOUSAND BRITISH THERMAL UNITS PER

HOUR

MCA MINIMUM CIRCUIT AMPS

MCC MOTOR CONTROL CENTER

MECH MECHANICAL

MERV MINIMUM EFFICIENCY REPORTING VALUE

(ASHRAE 52.2)

MFR MANUFACTURER

MIN MINIMUM OR MINUTE (PER CONTEXT)

MTD MOUNTED

MTL METAL

MV MANUAL VENT

NC NORMALLY CLOSED OR NOISE CRITERIA

(PER CONTEXT)

NIC NOT IN CONTRACT

NO NORMALLY OPEN OR NUMBER (PER CONTEXT)

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

OC ON CENTER

OD OUTSIDE DIAMETER

OT OIL TRAP

PA PIPE ANCHOR

PBD PARALLEL BLADE DAMPER

PD PRESSURE DROP

PENT PENTHOUSE

PH PHASE

PHC PREHEAT COIL

PLBG PLUMBING

PNEU PNEUMATIC

PPH POUNDS PER HOUR

PRESS PRESSURE

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH ABSOLUTE

PSIG POUNDS PER SQUARE INCH GAUGE

QTY QUANTITY

RA RETURN AIR

RAD RADIATED

RD ROOF DRAIN

REFR REFRIGERANT

REQ REQUIRED

RH RELATIVE HUMIDITY

RLA RUNNING LOAD AMPS

RM ROOM

RND ROUND

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SAN SANITARY

SEC'N SECTION

SEER SEASONAL ENERGY EFFICIENCY RATIO

SENS SENSIBLE

SF SQUARE FOOT

SH SENSIBLE HEAT

SHT SHEET

SND SOUND

SOL SOLENOID

SP STATIC PRESSURE

SPD STATIC PRESSURE DIFFERENTIAL

SPT STATIC PRESSURE TRANSMITTER

SQ SQUARE

SST STAINLESS STEEL

STL STEEL

STM STEAM

T&P TEMPERATURE AND PRESSURE

TC TEMPERATURE CONTROL

TD THERMODYNAMIC OR TEMPERATURE

DIFFERENTIAL (PER CONTEXT)

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TOT TOTAL

TPD TOTAL PRESSURE DROP

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UC UNDERCUT DOOR

UG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

V VOLTS

VAC VACUUM

VD VOLUME DAMPER (MANUAL)

VEL VELOCITY

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

VTR VENT THRU ROOF

W WATT OR WIDTH (PER CONTEXT)

W/ WITH

W/O WITHOUT

WB WET BULB

WC WATER COLUMN

WG WATER GAUGE

WPD WATER PRESSURE DIFFERENTIAL

WT WEIGHT

MECH EQUIPMENT DESIGNATION

MECH EQUIPMENT DESIGNATION

AC AIR CURTAIN

ACC AIR COOLED CONDENSER

ACU AIR CONDITIONING UNIT

ACV AIR CONTROL VALVE

AF AIR FILTER

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

ATU AIR TERMINAL UNIT

B BOILER

BCU BLOWER COIL UNIT

BS BASKET STRAINER

BT BUFFER TANK

CAV CONSTANT AIR VOLUME

CB CHILLED BEAM

CC COOLING COIL

CFP CHEMICAL FEED PUMP

CH CHILLER

CP CONDENSER WATER PUMP

CRAC COMPUTER ROOM AIR CONDITIONING UNIT

CRP CONDENSATE RETURN PUMP

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CTF COOLING TOWER FILTER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CVR CONVECTOR

CWP CHILLED WATER PUMP

DFH DEAERATING FEEDWATER HEATER

DHU DESSICANT DEHUMIDIFICATION UNIT

DMC DUCT MOUNTED COIL

EAV EXHAUST AIR VALVE

EF EXHAUST FAN

EJ EXPANSION JOINT

ERU ENERGY RECOVERY UNIT

ET EXPANSION TANK

EVC EVAPORATIVE COOLER

F FAN

FAV FUME AIR VALVE

FC FLUID COOLER

FCU FAN COIL UNIT

FD FIRE DAMPER

FFU FAN FILTER UNIT

FSD COMBINATION FIRE/SMOKE DAMPER

FT FLASH TANK

FTR FIN-TUBE RADIATION

FTU FAN TERMINAL UNIT

FUR GAS FIRED FURNACE (*NEED APPROVAL)

GMU GLYCOL MAKEUP UNIT (*NEED APPROVAL)

GP GLYCOL PUMP

GV GRAVITY VENTILATOR

H HUMIDIFIER

HC HEATING COIL

HEV HOOD EXHAUST VALVE

HPU HEAT PUMP UNIT

HRU HEAT RECOVERY UNIT

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

L LOUVER

MAU MAKE-UP AIR UNIT

MD MOTORIZED DAMPER

P PUMP

PAC PACKAGED AIR CONDITIONING UNIT

PCWP PRIMARY CHILLED WATER PUMP

PG PIPE GUIDE

PHWP PRIMARY HEATING WATER PUMP

PHX PLATE HEAT EXCHANGER

PRV PRESSURE REGULATING VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

RF RETURN FAN

RHC TERMINAL REHEAT COIL

RP RADIANT PANEL

RTU ROOFTOP UNIT

RV ROOF VENTILATOR (*NEED APPROVAL)

SA SOUND ATTENUATOR

SAV SUPPLY AIR VALVE

SCWP SECONDARY CHILLED WATER PUMP

SD SMOKE DAMPER

SF SUPPLY FAN

SHWP SECONDARY HEATING WATER PUMP

SPP STEAM PRESSURE PUMP

SSCU SPLIT SYSTEM CONDENSING UNIT (*NEED APPROVAL)

SSFU SPLIT SYSTEM FAN/COIL UNIT (*NEED APPROVAL)

ST STEAM TRAP

T TANK

TCP TEMPERATURE CONTROL PANEL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME BOX

VFD VARIABLE FREQUENCY DRIVE

VI VIBRATION ISOLATION

VRF VRF INDOOR UNIT

VRHU VRF HEAT RECOVERY UNIT (*NEED APPROVAL)

WCC WATER COOLED CONDENSER

WSHP WATER SOURCE HEAT PUMP

UNIT NUMBER

EQUIPMENT DESIGNATION

TYPE OF SERVICE: S = SUPPLY

R = RETURN

E = EXHAUST

T = TRANSFER

AIR QUANTITY

IN CFM

SCHEDULED

DEVICE NO

UNIT NUMBER

DAMPER TYPE DESIGNATION

AIRFLOW MEASURING STATION

EXISTING EQUIPMENT DESIGNATION

S-1

FSD

AHU

AHU-1

ID-#

HVAC SENSOR

SENSOR TYPE

OPTIONS

SPECIALTY SENSOR TYPE

I = INSULATED BASE

G= PROVIDE GUARD

CO = CARBON MONOXIDE

CO2= CARBON DIOXIDE

NG = NATURAL GAS

T = TEMPERATURE SENSOR

H = HUMIDITY SENSOR

O = OCCUPANCY SENSOR

R = REFRIGERANT SENSOR

P = PRESSURE SENSOR

MECHANICAL SYMBOLS

ASSOCIATED UNIT

X Y

Z

(UNIT #)

ACCESS PANEL, TOP OR SIDE

TURNING VANES

MOTORIZED DAMPER

GRAVITY BACKDRAFT DAMPER

MANUAL VOLUME DAMPER

FIRE DAMPER

SMOKE DAMPER

FIRE/SMOKE DAMPER

FLOW ARROW DOWNSTREAM OF FAN

FLOW ARROW UPSTREAM OF FAN

SUPPLY DIFFUSER AS SCHEDULED. ARROWS INDICATE

DIRECTION OF AIR DISCHARGE. IF NO ARROWS ARE

SHOWN ON PLAN, DEFAULT IS A 4-WAY THROW

RETURN GRILLE OR REGISTER AS SCHEDULED

EXHAUST GRILLE OR REGISTER AS SCHEDULED

SLOT DIFFUSER AS SCHEDULED. ARROWS INDICATE DIRECTION

OF AIR DISCHARGE. IF NO ARROWS ARE SHOWN ON PLAN,

DEFAULT IS 2-WAY THROW

SIDEWALL DIFFUSER AS SCHEDULED

SIDEWALL RETURN OR EXHAUST AS SCHEDULED

DUCT SYSTEM SYMBOLS

12x12

12ø

12x10ø

FLEXIBLE DUCT

ROUND DUCT SIZE, (ACTUAL SIZE INDICATED)

CHANGE OF ELEVATION - RISE (R) OR DROP (D)

FLEXIBLE DUCT CONNECTION

SUPPLY AND OUTSIDE AIR SECTION UP

RETURN AIR SECTION UP

SPIRAL FLAT-OVAL DUCT SIZE, FIRST FIGURE

IS SIDE SHOWN (ACTUAL SIZE INDICATED)

R

DUCT SIZE, FIRST FIGURE IS SIDE

SHOWN (CLEAR INSIDE, ADJUST FOR

LINER)

SUPPLY AND OUTSIDE AIR SECTION DOWN

RETURN AIR SECTION DOWN

EXHAUST AIR SECTION UP

EXHAUST AIR SECTION DOWN

MECHANICAL PROJECT GENERAL NOTES

1. ALL ELBOWS, FITTINGS, ETC., IN PIPING AND DUCTWORK REQUIRED

TO CLEAR ALL JOB OBSTRUCTIONS ARE NOT NECESSARILY

INDICATED. ALL NECESSARY TRANSITIONS, FITTINGS AND OFFSETS

ARE REQUIRED WHETHER SHOWN OR NOT.

2. BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE

MECHANICAL WORK, COORDINATION BETWEEN THE VARIOUS

TRADES IS OF THE UTMOST IMPORTANCE. SEE SPECIFICATION

230100 FOR REQUIRED COORDINATION DRAWINGS.

3. THE CONTRACTOR SHALL COORDINATE STAGING AND SCHEDULING

WITH THE OWNER'S REPRESENTATIVE.

4. EXISTING CONDITIONS ARE BASED ON INFORMATION OBTAINED

FROM PREVIOUS CONSTRUCTION DOCUMENTS AND INFORMAL

FIELD OBSERVATION AND SHALL NOT BE construed AS "AS BUILT." THE

CONTRACTOR SHALL FIELD-VERIFY EXISTING CONDITIONS BEFORE

THE ONSET OF CONSTRUCTION.

5. DEMOLISH ALL PIPING, DUCTWORK EQUIPMENT, ETC., SHOWN TO BE

REMOVED, IN ITS ENTIRETY, INCLUDING ALL HANGERS AND

SUPPORTS.

6. WHERE CONTRACTOR IS REQUIRED TO CONCEAL NEW WORK,

REMOVE OR MODIFY EXISTING CONSTRUCTION OR EQUIPMENT, OR

ATTACH TO EXISTING CONSTRUCTION, THE CONTRACTOR SHALL

REPAIR OR REPLACE EXISTING CONSTRUCTION AND MATERIALS TO

MATCH CONDITIONS AT THE ONSET OF CONSTRUCTION. IT IS THE

CONTRACTOR'S RESPONSIBILITY TO REMOVE AND REPLACE

EXISTING CEILINGS AND WALLS REQUIRED FOR INSTALLATION OF

MECHANICAL SYSTEMS.

7. THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT

AND MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT

CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE PREMISES

BY THIS CONTRACTOR.

8. CONTRACTOR SHALL PROVIDE SEISMIC BRACING AND MOUNTING OF

EQUIPMENT AND MATERIALS IN COMPLIANCE WITH ALL LOCAL CODE

REQUIREMENTS AND THE REQUIREMENTS OF SPECIFICATION

SECTION SEISMIC PROTECTION.

9. ALL WORK SHALL BE INSTALLED PER THE REFERENCE DETAILS,

REGARDLESS OF WHETHER OR NOT THE DETAILS ARE CALLED OUT

ON THE PLANS.

10. THE CONTRACTOR SHALL VERIFY ALL REFRIGERANT PIPE SIZING

AND ROUTINGS WITH THE EQUIPMENT MANUFACTURER. THE

CONTRACTOR SHALL ALSO PROVIDE ALL REQUIRED REFRIGERANT

ACCESSORIES AS RECOMMENDED BY THE EQUIPMENT

MANUFACTURER FOR COMPLETE AND FULLY FUNCTIONAL SYSTEMS.

11. DO NOT SCALE THE LOCATION OF HVAC CEILING ELEMENTS, SUCH

AS AIR INLETS AND OUTLETS, FROM THE M-SERIES DRAWINGS. SEE

ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT HVAC

CEILING ELEMENT LOCATIONS. REFLECTED CEILING PLANS GOVERN

THE LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES. M-SERIES

DRAWINGS GOVERN TYPE, STYLE, AND SIZE OF DIFFUSERS,

REGISTERS, AND GRILLES.

12. ALL DUCTWORK SHALL COMPLY WITH "HVAC DUCT CONSTRUCTION

STANDARDS - METAL AND FLEXIBLE," MOST RECENT VERSION OF

SMACNA, EXCEPT WHERE MORE RESTRICTIVE REQUIREMENTS ARE

SPECIFIED. ANY PLAN REFERENCES TO "SMACNA FIGURE ---"

REFERS TO THIS STANDARD. SEE SPECIFICATIONS FOR SCHEDULE

OF DUCT PRESSURE CLASS AND SEAL CLASS.

13. IN GENERAL, THE FINAL FLEX DUCT RUNOUT TO EACH DIFFUSER,

REGISTER, OR GRILLE IS NOT SIZED ON PLANS. FLEX DUCT RUNOUT

SIZE SHALL MATCH AIR OUTLET NECK SIZE, UNO.

14. IT IS THE INTENT OF THESE DRAWINGS THAT A MANUAL BALANCING

DAMPER BE PROVIDED AT EVERY INDIVIDUAL DUCTED CONNECTION

TO AN AIR DEVICE, UNLESS A BALANCING DAMPER IS SCHEDULED

TO BE FURNISHED WITH AIR DEVICE. VAV BOXES WITH SINGLE

DIFFUSERS ARE NOT REQUIRED TO HAVE A BALANCING DAMPER.

15. ALL NEW DUCTWORK SIZES SHOWN ON PLANS ARE CLEAR INSIDE

DIMENSIONS. CONTRACTOR SHALL ADJUST SHEET METAL SIZES AS

NECESSARY TO ACCOMMODATE INTERNAL DUCT LINER, IF

SPECIFIED.

16. ALL EXISTING TEMPERATURE CONTROLS THAT ARE BEING

DEMOLISHED OR DISABLED AS WORK OF THIS CONTRACT SHALL BE

COMPLETELY REMOVED FROM BUILDING.

17. THE CONTRACTOR SHALL CONNECT THE NEW HVAC SYSTEM TO THE

OWNER'S EXISTING BUILDING CONTROL SYSTEM. REFER TO THE

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

18. CONTRACTOR SHALL HAVE THE DOCUMENTS REVIEWED

COMPLETELY BY A CERTIFIED BALANCING CONTRACTOR FOR THE

INCLUSION OF THE NECESSARY ADDITIONAL AIR AND HYDRONIC

SYSTEM BALANCING DEVICES NOT SHOWN IN THESE DOCUMENTS

FOR COMPLETE HVAC SYSTEM BALANCING. REFER TO

SPECIFICATION SECTION 230593 FOR CONSTRUCTION DOCUMENT

EXAMINATION REPORT.

19. THESE PLANS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR

SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO THE EXACT

LOCATION OF DUCTWORK, PIPING AND EQUIPMENT FROM THE

LOCATION INDICATED ON THESE DRAWINGS TO FIT ACTUAL JOB

CONDITIONS.

REFRIGERANT VENTRV

CHEMICAL FEEDCF

V VENT

NATURAL GASG

CW COLD WATER, DOMESTIC

CWS

CA

CWR

GLS

CR

CS

GLYCOL SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

CHILLED WATER RETURN

CHILLED WATER SUPPLY

COMPRESSED AIR

CHR

CHS

HWS

HWR

GLR

HG

RS

RL

PC

CHILLED/HOT WATER RETURN

CHILLED/HOT WATER SUPPLY

REFRIGERANT HOT GAS

REFRIGERANT SUCTION

REFRIGERANT LIQUID

PUMPED CONDENSATE

HEATING WATER SUPPLY

HEATING WATER RETURN

GLYCOL RETURN

PUMP DISCHARGE

DRAIND

PD

DOMESTIC HOT WATERHW

MU MAKE-UP WATER (NON-POTABLE)

BLOW DOWNBD

CD CONDENSATE (STEAM) DRAIN

PIPE SYSTEM ABBREVIATIONS PIPE LINE SYMBOLS

SHUT OFF VALVE (SEE

SPECIFICATION FOR TYPE)

GATE VALVE

BALL VALVE

BUTTERFLY VALVE

VALVE IN RISE (SEE SPECIFICATION FOR TYPE)

MULTI-PURPOSE PUMP DISCHARGE VALVE

CHECK VALVE

SOLENOID VALVE

CALIBRATED - ORIFICE BALANCING VALVE

ACTIVE FLOW-LIMITING VALVE

PLUG VALVE

IN-LINE PUMP

Y-PATTERN STRAINER

Y-PATTERN STRAINER W/ BLOWDOWN VALVE

UNION

PRESSURE AND TEMPERATURE TEST PORT

THERMOMETER

PRESSURE GAGE WITH COCK

FLEX PIPE COUPLING

PIPE ANCHOR

PIPE GUIDE

PITCH DOWN IN DIRECTION OF ARROW

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

GLOBE VALVE

COMMON PIPING SYMBOLS

DIRECTION OF FLOW

BRANCH CONNECTION, BOTTOM

BRANCH CONNECTION, TOP

ELBOW, TURNED DOWN

ELBOW TURNED UP

PIPING CAP

PLAN MARK

EQUIPMENT NUMBER

SHEET NUMBER

LINE TYPE LEGEND

DRAWING REFERENCES

NEW WORK BY THIS CONTRACTOR

(DARK, SOLID LINE)

EXISTING TO REMAIN OR NEW WORK BY OTHERS

(LIGHT, SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR

(DARK, DASHED LINE, DEMOLITION PLANS)

NORTH ARROW

PLAN DETAIL REFERENCE TITLE

KEYED NOTE DESIGNATION

PLAN MARK

EQUIPMENT NUMBER

EQUIPMENT DESIGNATION REFER TO MEP

SCHEDULE FOR CIRCUITING AND DEVICE

REQUIREMENTS AND FLOOR PLANS FOR

LOCATIONS

ENLARGED PLAN REFERENCE

PLAN MARK

SHEET NUMBER

A101

SIM

AHU

TITLE

SCALE

PLAN

NORTH

TRUE

NORTH

INTERFACE, EXISTING TO NEW

EXTENT OF DEMOLITION

SECTION

MATCHLINE

1 REVISION TAG

AD888

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-000

CL

MECHANICAL SYMBOLS AND ABBREVIATIONS

SS5/16/23

UP

UP DN

UP

M-400A-1A.G

M-400A-1A.G

M-400B-1A.G

M-400B-1A.G

ACCU-D007

ACCU

PA06A

AC

PA06A

AC

PA06B

ACCU

PA06B

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

1A

M-100-1A.G

CL

OVERALL GROUND FLOOR - AREA D -

MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1/8" = 1'-0"

OVERALL GROUND FLOOR - AREA D - MECHANICAL

UP

DN

DN

M-402-1.G

M-402-1.G

AC

B046A

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-102-1.G

CL

OVERALL GROUND FLOOR - AREA B -

MECHANICAL

SS5/16/23

NOT TO SCALE

OVERALL GROUND FLOOR - AREA D - MECHANICAL

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

M-403A-1.G

M-403A-1.G

M-403B-1.G

M-403B-1.G

AC

A002.2

AC

A002.1

AC

A022B

AC

A022A

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-103-1.G

CL

OVERALL GROUND FLOOR - AREA A WEST -

MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1/8" = 1'-0"

OVERALL GROUND FLOOR - AREA A WEST - MECHANICAL

M-404B-1.G

M-404B-1.G

M-414-1.1

CRAC

CRAC

CRAC

EF

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-104-1.G

CL

OVERALL GROUND FLOOR - AREA A EAST -

MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1/8" = 1'-0"

OVERALL GROUND FLOOR - AREA A EAST - MECHANICAL

WAITING

C1-5D

WORK RM

D155

M-411-1A.1

M-411-1A.1

AC

C121.1AC

C121.2

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

1A

M-111-1A.1

CL

OVERALL FIRST FLOOR - AREA C - MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C

E

B

A

D

1/8" = 1'-0"

OVERALL FIRST FLOOR - AREA C - MECHANICAL

DN UP

M-412-1.1

M-412-1.1

AC

B125

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-112-1.1

CL

OVERALL FIRST FLOOR - AREA B - MECHANICAL

SS5/16/23

NOT TO SCALE

OVERALL FIRST FLOOR - AREA C - MECHANICAL

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

M-413-1.1

M-413-1.1

AC

A104.1

AC

A104.2

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-113-1.1

CL

OVERALL FIRST FLOOR - AREA A WEST -

MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C

E

B

A

D

1/8" = 1'-0"

OVERALL FIRST FLOOR - AREA A WEST - MECHANICAL

CHECK OUT

FF:VCT

FF:VCT

FF:VCT

FF:VCT

FF:VCT

FF:VCT

FF:CERAMIC TILE

CARD CATALOG

R E

F E

R E

N C

E

UP

DN

UP

DN

UP

M-421-1A.2

M-421-1A.2

AC

C222.1

AC

C222.2

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

1A

M-121-1A.2

CL

OVERALL SECOND FLOOR - AREA C -

MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C

B

A

D

1/8" = 1'-0"

OVERALL SECOND FLOOR - AREA C - MECHANICAL

1. NOTE THAT AS OF APRIL, 2023, DAVID KNAPP OF THE

VA INFORMED OUR TEAM THAT THE SECOND FLOOR

CARDIOLOGY PROJECT IS CURRENTLY APPROVED AND

SCHEDULED FOR CONSTRUCTION IN JANUARY,

2024. THIS CARDIOLOGY PROJECT HAS A NEW 200SF

DATA ROOM A229 SHOWN IN THE NEW LAYOUT WHICH

IS APPROX. 50-FEET SOUTHWEST FROM TR C222 IN THE

EHRM PROJECT. THE VA WILL LIKELY ISSUE A

MODIFICATION REVISION WHERE THE DESIGN TEAMS

WILL KEEP ONE OF THE IT ROOMS AND ENSURE THAT

IT CAN SATISFY BOTH THE EHRM TR ROOM

REQUIREMENTS AS WELL AS THE CARDIOLOGY

PROJECT REQUIREMENTS. IT IS IMPORTANT THAT THIS

FINAL TR ROOM SATISFIES ALL THE EHRM DESIGN

REQUIREMENTS FOR THE MECHANICAL, ELECTRICAL,

PLUMBING, FIRE PROTECTION, SECURITY, AND DATA

SYSTEMS.

SHEET KEY NOTES#

PNEUMATIC TUBE

FF:VCTFF:VCT

FF:VCT

FF:CONCRETE

FF:VCT FF:VCT

FF:VCT

FF:VCT

FF:VCT

FF:VCT

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FF:CERAMIC TILE

S

S D

W

D

W

DN

M-423-1.2

M-423-1.2

AC

A243.1

AC

A243.2

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-123-1.2

CL

OVERALL SECOND FLOOR - AREA A -

MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C

B

A

D

1/8" = 1'-0"

OVERALL SECOND FLOOR - AREA A - MECHANICAL

ROOF OF SECOND FLOOR

M-431-1A.3

M-431-1A.3

ACCU

C121

ACCU

C333

AC

C333.2

AC

C333.1

ACCU

C222

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

1A

M-131-1A.3

CL

OVERALL THIRD FLOOR - AREA C - MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C B

A

D

1/8" = 1'-0"

OVERALL THIRD FLOOR - AREA C - MECHANICAL

L S

L S

LS

LS

L S

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

M-433-1.3

M-433-1.3

AC

A345.1

AC

A345.2

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-133-1.3

CL

OVERALL THIRD FLOOR - AREA A - MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C B

A

D

1/8" = 1'-0"

OVERALL THIRD FLOOR - AREA A - MECHANICAL

M-441-1A.4

M-441-1A.4

AC

CU411.2

AC

CU411.1

ACCU

CU411

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

1A

M-141-1A.4

CL

OVERALL FOURTH FLOOR - AREA C -

MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C

B

A

D

1/8" = 1'-0"

OVERALL FOURTH FLOOR - AREA C - MECHANICAL

X

2FLT

2FLT

X

2FLT

2FLT

WASHERDRYER

M-443-1.4

M-443-1.4

AC

A450.1

AC

A450.2

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-143-1.4

CL

OVERALL FOURTH FLOOR - AREA A -

MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C

B

A

D

1/8" = 1'-0"

OVERALL FOURTH FLOOR - AREA A - MECHANICAL

M-451-1A.5

M-451-1A.5

AC

C580.1

AC

C580.2

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

1A

M-151-1A.5

CL

OVERALL FIFTH FLOOR - AREA C - MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C B

A

1/8" = 1'-0"

OVERALL FIFTH FLOOR - AREA C - MECHANICAL

M-453-1.5

M-453-1.5

AC

AU547.1

AC

AU547.2

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-153-1.5

CL

OVERALL FIFTH FLOOR - AREA A - MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

C B

A

1/8" = 1'-0"

OVERALL FIFTH FLOOR - AREA A - MECHANICAL

FILES

PNEUMATIC TUBE

M-463-1.6

M-463-1.6

AC

A627

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-163-1.6

CL

OVERALL SIXTH FLOOR - AREA A - MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

B

A

1/8" = 1'-0"

OVERALL SIXTH FLOOR - AREA A - MECHANICAL

ACCU-D007

CORRIDOR

DH003

EMS

D005

CORRIDOR

DH003

TR

D007D

EMS

D005

ELEVATOR

S6

ELEVATOR

S7

T

CORRIDOR

DH002

ACCU-D007

CORRIDOR

DH003

COMM EQUIP.

D007D

EMS

D005

ELEVATOR

S6

ELEVATOR

S7

T

CORRIDOR

DH002

A. THE DATA CENTER IS TO REMAIN IN OPERATION. IN

THIS AREA, COORDINATE TIMING OF THE CRAC UNIT

REMOVAL AND NEW ACTIVATION WITH A PHASING

PLAN. REFERENCE TECHNOLOGY AND ELECTRICAL

DRAWINGS FOR THE PHASING.

B. ALL EXISTING PIPES TO REMAIN IN THE NEW TR ROOMS

SHALL HAVE A DRIP PAN BELOW THE ENTIRE LENGTH

OF PIPE, REGARDLESS IF SHOWN OR NOT. SEE

PLUMBING DRAWING PL-000 FOR PAN DETAIL. SEE

WATER SENSOR CONTROLS - SEQUENCE OF

OPERATIONS ON M-701.

C. ALL NEW PIPING PENETRATIONS THROUGH FLOORS OR

ROOFS SHALL BE COORDINATED WITH STRUCTURAL.

PROVIDE A SEAL AROUND NEW PENETRATION.

D. REFRIGERANT LINE SIZES AND LENGTHS TO BE

CONFIRMED BY THE CONTRACTOR. VERIFY

MANUFACTURERS RECOMMENDATION FOR PIPE SIZES.

E. WHERE CONDENSATE PIPING TERMINATES, THE PIPING

IS TO HAVE A 1" MIN AIR-GAP TO DRAIN.

GENERAL SHEET NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

1A

M-400A-1A.G

CL

BUILDING 1A – ENLARGED PLANS - GROUND

FLOOR – MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA D TR D007D - NEW WORK

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA D COMM EQUIP D007D - DEMOLITION

1. EXISTING EQUIPMENT AND ACCESSORIES TO REMAIN.

2. EXISTING PIPING, VALVES, FITTINGS AND ACCESSORIES

TO REMAIN.

3. PROVIDE A TEMPERATURE/ HUMIDITY SENSOR AT THE

NEW LOCATION SHOWN. VERIFY COMMUNICATION

WITH THE BAS FOR MONITORING.

4. CAP DUCT AND SEAL AIR TIGHT AT WALL.

5. CONTRACTOR TO PROVIDE A BACNET GATEWAY FOR

MONITORING WITH OWNER'S EXISTING BAS. SEE THE

SPLIT SYSTEM CONTROL SEQUENCE OF OPERATIONS

(SOO). VERIFY THE UNIT OPERATES PROPERLY,

INCLUDING THE CONDENSATE PUMP.

STORAGE AREA/

GARAGE

PA06

NORMAL POWER

PA06A

EMERGENCY

POWER

PA06B

ACCU

PA06A

AC

PA06A

AC

PA06B

ACCU

PA06B

T T

3/4" CD

3/4" CD

STORAGE AREA/

GARAGE

PA06

A. THE DATA CENTER IS TO REMAIN IN OPERATION. IN

THIS AREA, COORDINATE TIMING OF THE CRAC UNIT

REMOVAL AND NEW ACTIVATION WITH A PHASING

PLAN. REFERENCE TECHNOLOGY AND ELECTRICAL

DRAWINGS FOR THE PHASING.

B. ALL EXISTING PIPES TO REMAIN IN THE NEW TR ROOMS

SHALL HAVE A DRIP PAN BELOW THE ENTIRE LENGTH

OF PIPE, REGARDLESS IF SHOWN OR NOT. SEE

PLUMBING DRAWING PL-000 FOR PAN DETAIL. SEE

WATER SENSOR CONTROLS - SEQUENCE OF

OPERATIONS ON M-701.

C. ALL NEW PIPING PENETRATIONS THROUGH FLOORS OR

ROOFS SHALL BE COORDINATED WITH STRUCTURAL.

PROVIDE A SEAL AROUND NEW PENETRATION.

D. REFRIGERANT LINE SIZES AND LENGTHS TO BE

CONFIRMED BY THE CONTRACTOR. VERIFY

MANUFACTURERS RECOMMENDATION FOR PIPE SIZES.

E. WHERE CONDENSATE PIPING TERMINATES, THE PIPING

IS TO HAVE A 1" MIN AIR-GAP TO DRAIN.

GENERAL SHEET NOTES

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-400B-1A.G

CL

BUILDING 1A – ENLARGED PLANS - GROUND

FLOOR – MECHANICAL

SS5/16/23

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA PA PA06 - DEMOLITION

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA PA PA06A & PA06B - NEW WORK

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1. PROVIDE NEW ACCU UNIT, MOUNT ON WALL BRACKETS

6'-0" ABOVE GARAGE FLOOR. THIS DESIGN SCOPE IS

EXPECTING REMOVAL OF THE STORAGE AREA AND

CONVERTING BACK INTO PARKING SPACES. IF THIS IS

NOT THE CASE AT THE TIME OF INSTALLATION THEN,

LOCATE ACCU UNITS OUTSIDE STORAGE AREA AND

MAINTAIN MANUFACTURER RECOMMENDED

CLEARANCE.

2. PROVIDE NEW AC UNIT, MOUNT ON WALL ABOVE DOOR

AT APPROXIMATELY 8'-0" ABOVE GARAGE FLOOR TO

BOTTOM OF UNIT.

3. PROVIDE 3/4" CD PIPING AND ROUTE ALONG WALL IN

THE DIRECTION TO NEAREST GARAGE FLOOR DRAIN.

4. PROVIDE NEW TEMPERATURE/ HUMIDITY SENSOR AND

CONNECT TO THE BAS FOR MONITORING.

IT

B046

ELECTRIC

CLOSET

B043A

EMS

B043

CORRIDOR

BH006

T

IT

B046

TR

B046A

AC

B046A

3/4" CD

ELECTRIC

CLOSET

B043A

EMS

B043

CORRIDOR

BH006

T

T

REFRIGERANT

PIPING DOWN

A. THE DATA CENTER IS TO REMAIN IN OPERATION. IN

THIS AREA, COORDINATE TIMING OF THE CRAC UNIT

REMOVAL AND NEW ACTIVATION WITH A PHASING

PLAN. REFERENCE TECHNOLOGY AND ELECTRICAL

DRAWINGS FOR THE PHASING.

B. ALL EXISTING PIPES TO REMAIN IN THE NEW TR ROOMS

SHALL HAVE A DRIP PAN BELOW THE ENTIRE LENGTH

OF PIPE, REGARDLESS IF SHOWN OR NOT. SEE

PLUMBING DRAWING PL-000 FOR PAN DETAIL. SEE

WATER SENSOR CONTROLS - SEQUENCE OF

OPERATIONS ON M-701.

C. ALL NEW PIPING PENETRATIONS THROUGH FLOORS OR

ROOFS SHALL BE COORDINATED WITH STRUCTURAL.

PROVIDE A SEAL AROUND NEW PENETRATION.

D. REFRIGERANT LINE SIZES AND LENGTHS TO BE

CONFIRMED BY THE CONTRACTOR. VERIFY

MANUFACTURERS RECOMMENDATION FOR PIPE SIZES.

E. WHERE CONDENSATE PIPING TERMINATES, THE PIPING

IS TO HAVE A 1" MIN AIR-GAP TO DRAIN.

GENERAL SHEET NOTES

REFRIGERANT

PIPING UP

ACCU

B046A

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-402-1.G

CL

BUILDING 1 – ENLARGED PLANS - GROUND

FLOOR – MECHANICAL

SS5/16/23

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA B IT B046 - DEMOLITION

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA B TR B046A - NEW WORK

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1. EXISTING DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES TO REMAIN.

2. EXISTING PIPING, VALVES, FITTINGS AND ACCESSORIES

TO REMAIN.

3. REMOVE DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES.

4. RELOCATE DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES AS SHOWN ON NEW WORK PLAN.

5. REMOVE ABANDONED BRANCH PIPING, VALVES,

FITTINGS AND ACCESSORIES BACK TO MAIN IN

CORRIDOR.

6. RELOCATE EXISTING EQUIPMENT CONTROLS AND

WIRING TO LOCATION SHOWN ON THE NEW WORK

PLAN.

7. PROVIDE CAP COVERING THE DUCT OPENING AND

SEAL AIRTIGHT.

8. PROVIDE PIPE CAP AND SEAL WATERTIGHT.

9. PROVIDE NEW ACCU UNIT IN CRAWL SPACE WITH PAD,

LEVEL. COORDINATE LOCATION WITH OTHER EXISTING

SYSTEMS IN THIS AREA.

10. PROVIDE NEW AC UNIT, MOUNT ON WALL AT

APPROXIMATELY 8'-0" AFF TO BOTTOM OF UNIT.

COORDINATE LOCATION WITH OTHER EXISTING

SYSTEMS IN THIS AREA.

11. PROVIDE 3/4" CD PIPING, ROUTE ALONG WALL AND

TERMINATE JUST ABOVE THE JANITOR'S SINK.

12. PROVIDE NEW TEMPERATURE/ HUMIDITY SENSOR AND

CONNECT TO THE BAS FOR MONITORING.

SHEET KEY NOTES#

NOT TO SCALE

ENLARGED CRAWL SPACE AREA B - NEW WORK

x S

A ø

S A

TR

A002C

LOUNGE

A002

AC

A002.1

EMS

A004B

LOCKERS

FEMALE

A002A

ELEV

P3

ELEVATOR

LOBBY

A000

T

T

8 1" CD

1/4" RL

3/8" RS

3/4" CD

AC

A002.2

7 3/4" CD

x S

A ø

S A

IT CLOSET

A002C

LOUNGE

A002

T

T

EMS

A004B

LOCKERS

FEMALE

A002A

ELEV

P3

ELEVATOR

LOBBY

A000

A. THE DATA CENTER IS TO REMAIN IN OPERATION. IN

THIS AREA, COORDINATE TIMING OF THE CRAC UNIT

REMOVAL AND NEW ACTIVATION WITH A PHASING

PLAN. REFERENCE TECHNOLOGY AND ELECTRICAL

DRAWINGS FOR THE PHASING.

B. ALL EXISTING PIPES TO REMAIN IN THE NEW TR ROOMS

SHALL HAVE A DRIP PAN BELOW THE ENTIRE LENGTH

OF PIPE, REGARDLESS IF SHOWN OR NOT. SEE

PLUMBING DRAWING PL-000 FOR PAN DETAIL. SEE

WATER SENSOR CONTROLS - SEQUENCE OF

OPERATIONS ON M-701.

C. ALL NEW PIPING PENETRATIONS THROUGH FLOORS OR

ROOFS SHALL BE COORDINATED WITH STRUCTURAL.

PROVIDE A SEAL AROUND NEW PENETRATION.

D. REFRIGERANT LINE SIZES AND LENGTHS TO BE

CONFIRMED BY THE CONTRACTOR. VERIFY

MANUFACTURERS RECOMMENDATION FOR PIPE SIZES.

E. WHERE CONDENSATE PIPING TERMINATES, THE PIPING

IS TO HAVE A 1" MIN AIR-GAP TO DRAIN.

GENERAL SHEET NOTES

ELEV

P3

REFRIGERANT

PIPING UP

ACCU

A002

ACCU

A104

ACCU

A243

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-403A-1.G

CL

BUILDING 1 – ENLARGED PLANS - GROUND

FLOOR – MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1. EXISTING DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES TO REMAIN.

2. EXISTING EQUIPMENT, CONTROLS AND ASSOCIATED

HARDWARE TO REMAIN.

3. REMOVE DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES.

4. REMOVE EQUIPMENT, CONTROLS AND ASSOCIATED

HARDWARE.

5. PROVIDE CAP COVERING THE DUCT OPENING AND

SEAL AIRTIGHT.

6. RELOCATE THE EXISTING GREASE DUCT FIRE ALARM

INDICATING CEILING DEVICES INTO THE FEMALE

LOCKER ROOM CEILING, COORDINATE WITH OTHER

EXISTING SYSTEMS IN THE CEILING, ADJUST AS

NECESSARY.

7. PROVIDE NEW AC UNIT, MOUNT ON WALL AT

APPROXIMATELY 8'-0" AFF TO BOTTOM OF UNIT.

COORDINATE LOCATION WITH OTHER EXISTING

SYSTEMS IN THIS AREA.

8. PROVIDE 1" CD PIPING, ROUTE ABOVE CEILING, ALONG

WALL AND TERMINATE JUST ABOVE THE JANITOR'S

SINK.

9. PROVIDE NEW TEMPERATURE/ HUMIDITY SENSOR AND

CONNECT TO THE BAS FOR MONITORING.

10. RISER LOCATIONS ARE APPROXIMATE. COORDINATE

EXACT LOCATIONS WITH EXISTING EQUIPMENT AND

WITH OTHER SYSTEMS BEING INSTALLED.

COORDINATE THIS WORK WITH CONTRACTORS OF

OTHER DISCIPLINES, INCLUDING ELECTRICAL CONDUIT

AND FIBER OPTIC CABLE.

11. PROVIDE NEW ACCU UNIT IN CRAWL SPACE WITH PAD,

LEVEL. COORDINATE LOCATION WITH OTHER EXISTING

SYSTEMS IN THIS AREA.

12. CONTRACTOR TO VERIFY WHICH UNIT IS CONTROLLED

BY THIS STAT, RELOCATE STAT IF NECESSARY.

SHEET KEY NOTES#

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA A TR A002C - NEW WORK

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA A IT CLOSET A002C - DEMOLITION

1/4" = 1'-0"

ENLARGED CRAWL SPACE AREA A - NEW WORK

TELEPHONE

EQUIP RM

A022

FCU

ELEV

P1

ELEVATOR

LOBBY

A000

ELECTRIC

CLOSET

AH004

EMS

A023

TOILET

A024

CORRIDOR

AH004

T

TT

AC

A022A

AC

A022B

TELEPHONE

EQUIP RM

A022

ELEV

P1

ELEVATOR

LOBBY

A000

ELECTRIC

CLOSET

AH004

EMS

A023

TOILET

A024

CORRIDOR

AH004

T

T

T T

3/4" CD DN

3/4" CD DN

NORMAL POWER

A022A

EMERGENCY

POWER

A022B

REFRIGERANT

PIPING DOWN

REFRIGERANT

PIPING DOWN

A. THE DATA CENTER IS TO REMAIN IN OPERATION. IN

THIS AREA, COORDINATE TIMING OF THE CRAC UNIT

REMOVAL AND NEW ACTIVATION WITH A PHASING

PLAN. REFERENCE TECHNOLOGY AND ELECTRICAL

DRAWINGS FOR THE PHASING.

B. ALL EXISTING PIPES TO REMAIN IN THE NEW TR ROOMS

SHALL HAVE A DRIP PAN BELOW THE ENTIRE LENGTH

OF PIPE, REGARDLESS IF SHOWN OR NOT. SEE

PLUMBING DRAWING PL-000 FOR PAN DETAIL. SEE

WATER SENSOR CONTROLS - SEQUENCE OF

OPERATIONS ON M-701.

C. ALL NEW PIPING PENETRATIONS THROUGH FLOORS OR

ROOFS SHALL BE COORDINATED WITH STRUCTURAL.

PROVIDE A SEAL AROUND NEW PENETRATION.

D. REFRIGERANT LINE SIZES AND LENGTHS TO BE

CONFIRMED BY THE CONTRACTOR. VERIFY

MANUFACTURERS RECOMMENDATION FOR PIPE SIZES.

E. WHERE CONDENSATE PIPING TERMINATES, THE PIPING

IS TO HAVE A 1" MIN AIR-GAP TO DRAIN.

GENERAL SHEET NOTES

ACCU-FCU

ELEV

P1

ACCU

A022A

ACCU

A022B

ELEV

P1

3/4" CD UP

3/4" CD UP

3/4" CD

3/4" CD

REFRIGERANT

PIPING UP

REFRIGERANT

PIPING UP

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-403B-1.G

CL

BUILDING 1 – ENLARGED PLANS - GROUND

FLOOR – MECHANICAL

SS5/16/23

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA A TELEPHONE EQUIP RM A022 - DEMOLITION

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA A TELEPHONE EQUIP RM A022 - NEW WORK

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1. EXISTING DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES TO REMAIN.

2. RELOCATE EXISTING EQUIPMENT CONTROLS AND

WIRING TO LOCATION SHOWN ON THE NEW WORK

PLAN.

3. REMOVE DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES.

4. REMOVE PIPING, VALVES, FITTINGS AND ACCESSORIES.

5. REMOVE EQUIPMENT, CONTROLS AND ASSOCIATED

HARDWARE.

6. PROVIDE NEW ACCU UNIT IN CRAWL SPACE WITH PAD,

LEVEL. COORDINATE LOCATION WITH OTHER EXISTING

SYSTEMS IN THIS AREA.

7. PROVIDE NEW AC UNIT, MOUNT ON WALL AT

APPROXIMATELY 8'-0" AFF TO BOTTOM OF UNIT.

COORDINATE LOCATION WITH OTHER EXISTING

SYSTEMS IN THIS AREA.

8. PROVIDE 3/4" CD PIPING. TERMINATE WITH AN INSECT

SCREEN ON THE OUTLET.

9. PROVIDE NEW TEMPERATURE/ HUMIDITY SENSOR AND

CONNECT TO THE BAS FOR MONITORING.

SHEET KEY NOTES#

1/4" = 1'-0"

ENLARGED CRAWL SPACE AREA A - DEMOLITION

1/4" = 1'-0"

ENLARGED CRAWL SPACE AREA A - NEW WORK

CRAC-3

CRAC-2

CRAC-1

DATA CENTER

A073

APP SUPPORT

A057

ELECTRICAL

A056

SVC MGR

A072

CORRIDOR

AH009

RECEIVING

A071

CORRIDOR

AH010

ADP WORKSHOP

A062

AC-1

AC-2

T

T

T

T

4 4

6 6

4 6

REFRIGERANT

PIPING DOWN

G R

O U

N D

L E

V E

L T

U N

N E

L L

E V

E L

T

TT

T

PORTABLE-AC

OFFICE

A069

EXISTING EXHAUST

DUCT UP TO YARD

EXISTING OUTSIDE AIR

DUCT UP TO YARD

A. THE DATA CENTER IS TO REMAIN IN OPERATION. IN

THIS AREA, COORDINATE TIMING OF THE CRAC UNIT

REMOVAL AND NEW ACTIVATION WITH A PHASING

PLAN. REFERENCE TECHNOLOGY AND ELECTRICAL

DRAWINGS FOR THE PHASING.

B. ALL EXISTING PIPES TO REMAIN IN THE NEW TR ROOMS

SHALL HAVE A DRIP PAN BELOW THE ENTIRE LENGTH

OF PIPE, REGARDLESS IF SHOWN OR NOT. SEE

PLUMBING DRAWING PL-000 FOR PAN DETAIL. SEE

WATER SENSOR CONTROLS - SEQUENCE OF

OPERATIONS ON M-701.

C. ALL NEW PIPING PENETRATIONS THROUGH FLOORS OR

ROOFS SHALL BE COORDINATED WITH STRUCTURAL.

PROVIDE A SEAL AROUND NEW PENETRATION.

D. REFRIGERANT LINE SIZES AND LENGTHS TO BE

CONFIRMED BY THE CONTRACTOR. VERIFY

MANUFACTURERS RECOMMENDATION FOR PIPE SIZES.

E. WHERE CONDENSATE PIPING TERMINATES, THE PIPING

IS TO HAVE A 1" MIN AIR-GAP TO DRAIN.

GENERAL SHEET NOTES

REFRIGERANT

PIPING UP

G R

O U

N D

L E

V E

L T

U N

N E

L L

E V

E L

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-404A-1.G

CL

BUILDING 1 – ENLARGED PLANS - GROUND

FLOOR – MECHANICAL

SS5/16/23

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1. EXISTING DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES TO REMAIN.

2. EXISTING PIPING, VALVES, FITTINGS AND ACCESSORIES

TO REMAIN.

3. REMOVE DUCTWORK, GRILLES/ DIFFUSERS, FITTINGS

AND ACCESSORIES.

4. REMOVE PIPING, VALVES, FITTINGS AND ACCESSORIES.

5. REMOVE EQUIPMENT, CONTROLS AND ASSOCIATED

HARDWARE. COORDINATE TIMING OF EQUIPMENT

REMOVAL WITH THE DATA CENTER PDU AND PHASING

PLAN. SEE ELECTRICAL DRAWINGS.

6. PIPING BELOW RAISED FLOOR.

7. RELOCATE EXISTING EQUIPMENT CONTROLS AND

WIRING TO LOCATION SHOWN ON THE NEW WORK

PLAN. VERIFY LOCATION WITH OWNER. OWNER MAY

SELECT A DIFFERENT LOCATION.

SHEET KEY NOTES#

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA A DATA CENTER A073 - DEMOLITION

1/4" = 1'-0"

ENLARGED CRAWL SPACE TUNNEL AREA A - DEMOLITION

DATA CENTER

A073

APP SUPPORT

A057

ELECTRICAL

A056

FIRE PROTECT

A072

CORRIDOR

AH009

RECEIVING

A071

CORRIDOR

AH010

ADP WORKSHOP

A062

CRAC

CRAC

T

G R

O U

N D

L E

V E

L T

U N

N E

L L

E V

E L

REFRIGERANT

PIPING DOWN

REFRIGERANT

PIPING UP

1 1/4" CD 3/4" CD

6(TYP. 12)

T

T

OFFICE

A069

EF

10ø EA

10ø EA ø

10ø EA UP

SDSD

EXISTING EXHAUST

DUCT UP TO YARD

EXISTING OUTSIDE AIR

DUCT UP TO YARD

8ø

10ø EA ø

E A ø

E A

T (RACK)

UPS ENCLOSURE,

SEE ELECTRICAL

DRAWINGS FOR

RELATED WORK

T(RACK)

T (RACK)

T(RACK)

DATA RACKS, SEE TECHNOLOGY

DRAWINGS FOR RELATED WORK

DATA RACKS, SEE TECHNOLOGY

DRAWINGS FOR RELATED WORK

ø

CRAC

UPS ENCLOSURE,

SEE ELECTRICAL

DRAWINGS FOR

RELATED WORK

3/4" CD

1" CD

ø

E A

8ø

19(TYP. 10)

19 (TYP. 10)

6 (TYP. 12)

A. THE DATA CENTER IS TO REMAIN IN OPERATION. IN

THIS AREA, COORDINATE TIMING OF THE CRAC UNIT

REMOVAL AND NEW ACTIVATION WITH A PHASING

PLAN. REFERENCE TECHNOLOGY AND ELECTRICAL

DRAWINGS FOR THE PHASING.

B. ALL EXISTING PIPES TO REMAIN IN THE NEW TR ROOMS

SHALL HAVE A DRIP PAN BELOW THE ENTIRE LENGTH

OF PIPE, REGARDLESS IF SHOWN OR NOT. SEE

PLUMBING DRAWING PL-000 FOR PAN DETAIL. SEE

WATER SENSOR CONTROLS - SEQUENCE OF

OPERATIONS ON M-701.

C. ALL NEW PIPING PENETRATIONS THROUGH FLOORS OR

ROOFS SHALL BE COORDINATED WITH STRUCTURAL.

PROVIDE A SEAL AROUND NEW PENETRATION.

D. REFRIGERANT LINE SIZES AND LENGTHS TO BE

CONFIRMED BY THE CONTRACTOR. VERIFY

MANUFACTURERS RECOMMENDATION FOR PIPE SIZES.

E. WHERE CONDENSATE PIPING TERMINATES, THE PIPING

IS TO HAVE A 1" MIN AIR-GAP TO DRAIN.

GENERAL SHEET NOTES

REFRIGERANT

PIPING UP

1 1/4" CD

G R

O U

N D

L E

V E

L T

U N

N E

L L

E V

E L

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project TitlePhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANT

Revisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784

San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

St. Louis

6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com

M-404B-1.G

CL

BUILDING 1 - ENLARGED PLANS - GROUND

FLOOR - MECHANICAL

SS5/16/23

1/4" = 1'-0"

ENLARGED GROUND FLOOR AREA A DATA CENTER A073 - NEW WORK

PLAN

NORTH

TRUE

NORTH

KEY PLAN

PA

D

B

A

1. INSTALL PIPING BELOW RAISED FLOOR.

2. PROVIDE CAP COVERING THE DUCT OPENING AND

SEAL AIRTIGHT.

3. PROVIDE PIPE CAP AND SEAL WATERTIGHT.

4. ALL REFRIGERANT PIPING SHALL BE MOUNTED

VERTICALLY AGAINST THE WALL. PIPING SHOWN

HORIZONTAL FOR CLARITY.

5. PROVIDE 12"x12" GRILLE ON BOTH SIDES OF WALL AT

ABOUT 8'-0" AFF FOR TRANSFER AIR. SIMILAR TO PRICE

MODEL #535 OR EQUIVALENT.

6. PROVIDE (24) 24"x24" FLOOR ACCESS PERFORATED

TILES. SHALL BE MINIMUM 32% FREE AREA TILES.

SIMILAR TO ASM MODULAR SYSTEM MODEL #AFD320

OR EQUIVALENT. TILES TO MATCH EXISTING FLOOR

SYSTEM. ALL OTHER TILES SHALL BE SOLID. SEE

ACCESS FLOORING SPEC # 096900.

7. RELOCATE EXISTING EQUIPMENT CONTROLS AND

WIRING TO LOCATION SHOWN ON THE NEW WORK

PLAN. VERIFY LOCATION WITH OWNER. OWNER MAY

SELECT A DIFFERENT LOCATION.

8. PROVIDE NEW CRAC UNITS WITH HUMIDIFIER WATER

PIPING, SEE PLUMBING DRAWINGS.

9. SEE PLUMBING DATA CENTER DRAWING FOR THE

UNDER FLOOR WATER SENSOR LOCATIONS.

10. PROVIDE SPACE TEMPERATURE AND HUMIDITY

SENSOR WITH OVERRIDE. SEE CONTROLS DRAWING

M-701 FOR THE RACK SENSOR'S SEQUENCE OF

OPERATIONS.

11. SEE TECHNOLOGY DRAWINGS FOR COLD AISLE AND

RACK LOCATION. REFERENCE THE THERMAL

CONTAINMENT SPEC # 110000 FOR THE COLD AISLE

STRUCTURE.

12. ROUTE DUCT UP TO EXISTING EXHAUST HOOD IN THE

MECHANICAL YARD. CONNECT AND SEAL EXISTING

HOOD FROM LEAKING INTO THE ELECTRICAL ROOM.

13. TRANSITION AS NECESSARY AND DIRECTLY CONNECT

TO THE EXHAUST OPENING ON TOP OF THE BATTERY

SIDE OF THE UPS SYSTEM.

14. PROVIDE 12"x12" SUPPLY AIR GRILLE, SIMILAR TO PRICE

MODEL #535 OR EQUIVALENT. BALANCE DAMPER TO

300 CFM.

15. PROVIDE MOTORIZED SMOKE DAMPER INTERLINKED TO

A CONTROL MODULE WITHIN THE CLEAN AGENT PANEL.

SEE FIRE PROTECTION AND MECHANICAL CONTROLS

DRAWINGS FOR ADDITIONAL INFORMATION.

16. COORDINATE LOCATION OF EXHAUST FAN WITH OTHER

SYSTEMS, REMOVE ABANDONED SYSTEMS IF

NECESSARY.

17. ROUTE 10" EXHAUST DUCTWORK TO AVOID EXISTING

SYSTEMS NOT SHOWN. TRANSITION ABOVE OR BELOW

OTHER SYSTEMS AS NECESSARY.

18. PROVIDE RACK TEMPERATURE SENSORS AT BOTTOM,

MIDDLE AND TOP…