596A4-22-700 Drawings 08 - Tech 1.pdf

PDF 5 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades Construction Lexington-Cooper, KY 596A4-22-700
Solicitation number
36C77623B0069
Issued by

About this file

This document package includes construction drawings and specifications for infrastructure upgrades at the Lexington-Cooper VA Medical Center in Lexington, Kentucky. The scope of work involves upgrading telecommunications cabling and equipment throughout five buildings, including installing new category 6A cabling and related connectivity components. The project also requires upgrades to cable tray, conduit, and cable support systems, as well as relocating some wall-mounted devices. Construction is to follow all noted standards and be completed by the specified response date. The Department of Veterans Affairs is the contracting agency overseeing this project.

View the file

Other files

File Type Posted
596A4-22-700 Responses to Tech Questions - 1-25-24.pdf PDF
36C77623B0069 0008.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-22-24.pdf PDF
36C77623B0069 0007.pdf PDF
36C77623B0069 0006.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-18-24.pdf PDF
36C77623B0069 0005.pdf PDF
596A4-22-700 Responses to Tech Questions - 1-12-24.pdf PDF
36C77623B0069 0004.pdf PDF
596A4-22-700 Security Requirements.pdf PDF
DBA Wage Rates - Fayette County - 01-05-24.pdf PDF
596A4-22-700 Smoke Shack.pdf PDF
596A4-22-700 Handrail Submittal.pdf PDF
596A4-22-700 Drawing M-701 - Mechanical Controls.pdf PDF
596A4-22-700 Specification 23 09 23 - DDC for HVAC.pdf PDF
DBA Wage Rates - Fayette County - 12-22-23.pdf PDF
36C77623B0069 0003.pdf PDF
36C77623B0069 0002.pdf PDF
596A4-22-700 Site Visit Sign-in Sheet - 11-28-23.pdf PDF
36C77623B0069 0001.pdf PDF
596A4-22-700 Drawings 01 - General.pdf PDF
596A4-22-700 Drawings 12 - Security.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
596A4-22-700 Drawings 03 - Arch.pdf PDF
596A4-22-700 Drawings 06 - Mechanical.pdf PDF
596A4-22-700 Specifications.pdf PDF
596A4-22-700 Drawings 07 - Electrical.pdf PDF
596A4-22-700 Drawings 05 - Plumbing.pdf PDF
596A4-22-700 Drawings 09 - Tech 2.pdf PDF
596A4-22-700 Drawings 10 - Tech 3.pdf PDF
596A4-22-700 Drawings 04 - Fire Protection.pdf PDF
DBA Wage Rates - Fayette County - 09-08-23.pdf PDF
596A4-22-700 Asbestos Inspection Report.pdf PDF
596A4-22-700 Drawings 11 - Tech 4.pdf PDF
596A4-22-700 Brand Name Justification.pdf PDF
IFB 36C77623B0069.docx DOCX document
596A4-22-700 Drawings 02 - Asbestos.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AC ABOVE COUNTER

A.F.F. ABOVE FINISHED FLOOR

A.F.G. ABOVE FINISHED GRADE

AER AERIAL

A.W.G. AMERICAN WIRE GAUGE

CC CONTRACTOR FURNISHED AND INSTALLED

CER CABLE ENTRANCE ROOM (ER NOT USED IN HEALTHCARE)

CLG ABOVE CEILING

CMP COMMUNICATIONS MULTIPURPOSE CABLE, PLENUM

CMR COMMUNICATIONS MULTIPURPOSE CABLE, RISER

C.O.R. CONTRACT OFFICER REPRESENTATIVE

DEMARC DEMARCATION POINT

DEMO DEMOLITION

DIAG DIAGRAM

DISTR DISTRIBUTION

(E) EXISTING

EMT ELECTRIC METAL TUBING

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATION

EMER EMERGENCY

F.O.C. FIBER OPTIC CABLE

GFE GOVERNMENT FURNISHED EQUIPMENT

GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED (VC)

GFGI GOVERNMENT FURNISHED AND INSTALLED (VV)

GIP GALVANIZED IRON PIPE

GTB GROUND TERMINAL BOX

HE HEAD-END (PA, INTERCOM)

HDPE HIGH DENSITY POLYETHYLENE

IMC INTERMEDIATE METAL CONDUIT

ISP INSIDE CABLE PLANT

IDF INTERMEDIATE DISTRIBUTION FRAME (NOT USED)

-BOX JUNCTION BOX

MDF MAIN DISTRIBUTION FRAME (NOT USED)

MH MAINTENANCE HOLE (FORMERLY MANHOLE)

MM MULTI MODE

N/A NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

N NEUTRAL

N.I.C. NOT IN CONTRACT

N.T.S. NOT TO SCALE

OFCP OPTICAL FIBER CONDUCTIVE, PLENUM

OFCR OPTICAL FIBER CONDUCTIVE, RISER

OFNP OPTICAL FIBER NONCONDUCTIVE, PLENUM

OFNR OPTICAL FIBER NONCONDUCTIVE, RISER

OSP OUTSIDE CABLE PLANT

PB PULL BOX

PR PAIR

PVC POLYVINYL CHLORIDE

RSC RIGID STEEL CONDUIT

SM SINGLE MODE

SP SERVICE PROVIDER

STD STANDARD

STP SHIELDED TWISTED PAIR

TB TERMINAL BLOCK

TR TELECOMMUNICATIONS ROOM

TYP TYPICAL

TZ TELECOMMUNICATIONS ZONE

UG UNDERGROUND

UGC UNDERGROUND COMMUNICATIONS CABLE

UON UNLESS OTHERWISE NOTED

UTP UNSHIELDED TWISTED PAIR

VC GOVERNMENT FURNISHED, CONTRACTOR INSTALLED (GFCI)

VV GOVERNMENT FURNISHED AND INSTALLED (GFGI)

WP WEATHERPROOF

1. GENERAL CONSTRUCTION

1.1. DEMOLITION

1.1.1. THE CONTRACTOR SHALL COORDINATE WITH THE C.O.R. TO MAKE SAFE ALL

THAT WILL NOT BE REMOVED DURING DEMOLITION.

1.1.2. EXISTING CABLES, MODULAR JACKS, FACEPLATES, AND PATCH CABLES MAY

NOT BE REMOVED UNTIL AFTER CUT-OVER TO THE NEW CABLE SYSTEM IS

COMPLETE. CUT-OVER MAY BE BY ZONE, FLOOR, BUILDING, ETC. AND SHALL BE

COORDINATED WITH THE C.O.R. PRIOR TO WORK BEING PERFORMED.

1.1.3. EXISTING PATCH PANELS, PATCH CABLES, EQUIPMENT RACKS, ETC., MAY BE

"FLOATED" DURING CONSTRUCTION AND REMOVED AFTER CUT-OVER IS

COMPLETE.

1.2. CONSTRUCTION

1.1.1. CONTRACTOR SHALL INSTALL AND "BUILD-OUT" TR EQUIPMENT RACKS, CABLE

TRAYS, AND FITTINGS TO THE EXTENT POSSIBLE. FINAL INSTALLATION MAY NOT

BE COMPLETE UNTIL AFTER FINAL CUT-OVER OF THE CONSTRUCTION AREA IS

COMPLETE.

1.1.2. INSTALL FIBER OPTIC BACKBONE RISER CABLES TO THE TR(S) IN

CONSTRUCTION AREA.

1.1.3. INSTALL HORIZONTAL CATEGORY 6A CABLES FROM WORK AREAS TO THE TR(S)

IN THE CONSTRUCTION AREA.

1.1.4. CONTRACTOR SHALL TEST AND CERTIFY 100% OF INSTALLED HORIZONTAL

CABLES.

2. DATA CENTER CONSTRUCTION

2.1. DEMOLITION

2.1.1. REMOVAL OF EXISTING CABINETS AND ABANDONED CABLING WILL FOLLOW

CUT-OVER TO NEW CABLE SYSTEMS AND RELOCATION OF EQUIPMENTS TO NEW

CABINETS.

2.1.2. CONTRACTOR WILL REMOVE "OLD CABINETS" AS THEY ARE EMPTIED.

2.1.3. "OLD" CABINETS WILL BE MOVED TO A STAGING AREA FOR DISPOSAL. THE

CONTRACTOR SHALL COORDINATE WITH THE C.O.R. PRIOR TO BEGINNING

WORK.

2.2. CONSTRUCTION

2.2.1. CONTRACTOR SHALL INSTALL CABINETS, EQUIPMENT RACKS, CABLE TRAYS

AND FITTINGS.

2.2.2. CONTRACTOR SHALL INSTALL BACKBONE CABLES FROM THE TR(S).

2.2.3. CONTRACTOR SHALL TEST AND CERTIFY 100% OF BACKBONE CABLE.

2.2.4. CONTRACTOR SHALL PROVIDE FIBER OPTIC PATCH CABLES PRIOR TO MOVING

EQUIPMENT TO NEW CABINETS.

3. CLOSEOUT (COMMISSIONING)

3.0.1. CONTRACTOR SHALL PERFORM TESTING AND CERTIFICATION IN ACCORDANCE

WITH SPECIFICATION 27 08 00.

3.0.2. CONTRACTOR SHALL PROVIDE TEST DOCUMENTATION AND AS-BUILT DRAWINGS

AS SPECIFIED.

1. THE CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS INCLUDING THE DRAWINGS AND SPECIFICATIONS.

2. THE CONTRACTOR SHALL COMPLETE ALL WORK INCLUDED IN THE CONTRACT DOCUMENTS.

3. THE CONTRACTOR SHALL PHYSICALLY SURVEY AND VERIFY EXISTING CONDITIONS PRIOR TO STARTING CONSTRUCTION TO MINIMIZE UNFORESEEN CONDITIONS.

4. THE SCALE OF DRAWINGS IS PROVIDED AS A REFERENCE. THE CONTRACTOR IS RESPONSIBLE FOR CABLE LENGTHS, PATHWAY SIZING, DIMENSIONS, MEASUREMENTS, QUANTITIES, ETC.

5. THE CONTRACTOR SHALL COORDINATE AND VERIFY ALL ITEMS OF CASEWORK, CEILINGS, AND MILLWORK.

6. CONDUIT, CABLE TRAY, J-HOOKS, AND OTHER CABLE SUPPORTS ARE SHOWN IN APPROXIMATE LOCATIONS. CONTRACTOR SHALL COORDINATE WITH OTHER TRADES PRIOR TO INSTALLATION.

7. DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS AND SPECIFICATIONS SHALL BE CALLED TO THE ATTENTION OF THE DESIGN TEAM. DISCREPANCIES OR CONFLICTS BETWEEN THE DRAWINGS AND SPECIFICATIONS NOT CALLED TO THE ATTENTION OF THE DESIGN TEAM SHALL BE DEEMED TO HAVE BEEN RESOLVED WITHIN THE BID OR PROPOSAL AND THE CONTRACTOR SHALL PERFORM THE WORK IN THE MANNER, GREATER QUANTITY, BETTER QUALITY, IN ACCORDANCE WITH THE DESIGN TEAM'S INTERPRETATION.

GENERAL NOTES

TECHNOLOGY - GENERAL INFORMATION

ABBREVATIONS PHASING PLAN

LEGEND

DATA OUTLET; LETTER INDICATES AS FOLLOWS:

N = JACK QUANTITY

COMBINED VOICE&DATA OUTLET; LETTER INDICATES AS FOLLOWS:

N = JACK QUANTITY

FLOOR BOX - OVER-COUNTER; LETTER INDICATES AS FOLLOWS:

N = JACK QUANTITY

DATA OUTLET - CEILING MOUNTED; LETTER INDICATES AS FOLLOWS:

N = JACK QUANTITY

WIRELESS ACCESS POINT

EZ PATH FIRESTOP PENETRATION

ELECTRICAL PANEL BOARD.

TMGB - TELECOM MAIN GROUND BUS BAR

BASKET CABLE TRAY

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER TOP

NURSE CALL TERMINAL CABINET

NURSE CALL STATION.

2= DUPLICATE FACILITIES FOR TWO BEDS.

D= DUTY STATION.

E= MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF FOR TUB LOCATION,

MTD 3'-0" AFF FOR TOILET LOCATION.

P= PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH.

S= AUDIO VISUAL MALL STATION MTD 5'-0" AFF UNLESS OTHERWISE NOTED.

U= UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED.

NURSE CALL STATION.

2= NURSE'S CALL DOME LIGHT. MTD 6" ABOVE DOOR.

D= CORRIDOR DOME LIGHT.

I= AUXILIARY INTERSECTIONAL DOME LIGHT.

TELEPHONE TERMINAL CABINET

TELEPHONE BACKBOARD (WALL MOUNTED)

N

N

N

N

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

T-001

TECHNOLOGY

GENERAL INFORMATION

VV

RESPONSIBILITY MATRIX CF/CI - DIV

CF/CI - DIV

28 **

CF/CI -

DIV 26 GFE/CI GF/GI GO/GRI GC

CATV N/A

Intercom System N/A

Neutral Host - Distributed Antenna System Antennas (DAS) N/A

Nurse Call System N/A

Neon Coding N/A

Patient Wandering System Devices N/A

Public Address/Overhead Paging Speakers N/A

Physical Security - Acess Controls (EXISTING) X

Physical Security - Acess Controls (NEW) X

RTLS (CenTraK) N/A

Telecommunications Infrastructure Plant (TIP) X

Telecom Room Equipment Fittings X

Telecom Room Electrical & Lighting X

Telecommunications Equipment Backboard - fire retardant plywood, fire retardant paint X

Telecommunications Pathway - cable tray, conduits, bushings, back-boxes, fittings X

Telecommunications Room Equipment Bonding X

Telecommunications Grounding & Bonding - bus bars, ground conductor, backbone conductor X

TV Monitors N/A

Video Surveillance Cameras X

Wireless Network - VA Internal WLAN (WAPs) X

Wireless Network - Patient Network WLAN (WAPs) X

GC = General Contractor Furnished/General Contractor Installed

CF/CI = Contractor Furnished/Contractor Installed

GFE/CI = Government Furnished Equipment/Contractor Installed

GF/GI = Government Furnished/Government Installed

GO/GRI = Government Owned (Existing)/Government Removed and Installed

X = Responsible

NIC = Not In Contract

N/A = Not Applicable to this scope of work or no systems currently installed, unless otherwise noted.

** Refer to Division 28 Security sheets

PREFERRED PRODUCTS SCHEDULE

LINE DESCRIPTION MANUFACTURER PART NUMBER LINE DESCRIPTION MANUFACTURER PART NUMBER

01 Copper Connectivity 45 Pathways 02 Cable, U/UTP, CMP-LP (0.5A), Category 6A, 23AWG, 4-pair, white Berk-Tek 10137384 46 Cable tray, wire mesh, 12"x4" - actual dimension TBD Hubbell HBT0412S 03 Cable, U/UTP,CMP-LP (0.5A), Category 6A, 23AWG, 4-pair, blue Berk-Tek 10130484 47 Adaptor, conduit to tray Hubbell HBTCA3 04 Cable, U/UTP, CMP-LP (0.5A), Category 6A, 23AWG, 4-pair, green Berk-Tek 10137694 48 Ground lug, split bolt Hubbell HBTSPLITBOLTPK1 05 Cable, U/UTP, CMP-LP (0.5A), Category 6A, 23AWG, 4-pair, purple Berk-Tek 10140145 49 Splice bolt assembly Hubbell HBTSK 06 Cable, U/UTP,CMP-LP (0.5A), Category 6A, 23AWG, 4-pair, orange Berk-Tek 10138767 50 Support strut, 12" tray, pre-galvanized - actual dimension TBD Hubbell HBTNSCLGS12 07 Cable, U/UTP, CMP-LP (0.5A), Category 6A, 23AWG, 4-pair, pink Berk-Tek 10140144 51 Radius drop, black, 12" tray - actual dimension TBD Hubbell HBTRD12BK 08 Patch cable, UTP, CMP, Category 6, 4-pair, white, 7 ft. Leviton 6AS10-07W 52 Threaded rod, 3/8"x6' Chatsworth 40153-020 09 Patch cable, UTP, CMP, Category 6A, 4-pair, green, 7 ft. Leviton 6AS10-07G 53 Cable support, steel, J-hook, 4"x3", integrated retainer clip, galvanzied MonoSystems H-433-S 10 Patch cable, UTP, CMP, Category 6A, 4-pair, blue, 7 ft. Leviton 6AS10-07L 54 Cable support, steel, J-hook, 2"x3", integrated retainer clip, galvanzied MonoSystems H-433-AB 11 Patch cable, UTP, CMP, Category 6, 4-pair, white, 10 ft. Leviton 6AS10-10W 55 Center hanger bracket, steel, galvanized MonoSystems H-433-AC 12 Patch cable, UTP, CMP, Category 6A, 4-pair, green, 10 ft. Leviton 6AS10-10G 56 12" cable support extender MonoSystems H-CSE-12 13 Patch cable, UTP, CMP, Category 6A, 4-pair, blue, 10 ft. Leviton 6AS10-10L 57 Cable guide, fiber optic, 4"x12", yellow - actual dimension TBD CommScope FGS-MSHS-F 14 Modular jack, Category 6A, 8P/8C, white Leviton 6110G-RW6 58 Cable guide fittings, joints CommScope FGS-JUNC-F 15 Modular jack, Category 6A, 8P/8C, green Leviton 6110G-RV6 59 Cable guide fittings, drop section CommScope FGS-MDRT-F 16 Modular jack, Category 6A, 8P/8C, orange Leviton 6110G-RO6 60 Cable guide fitting, support kit CommScope FGS-HETP 17 Modular jack, Category 6A, 8P/8C, blue Leviton 6110G-RL6 61 Fiber Channel, 4" x 6", yelow CommScope FGS-MSHS-B 18 Modular jack, Category 6A, 8P/8C, black Leviton 6110G-RE6 62 Fiber Channel, 4" x 6", yelow - Various fittings. CommScope TBD BY

CONTRACTOR

19 Modular jack, Category 6A, 8P/8C, red Leviton 6110G-RC6 63 Grounding & Bonding 20 Plug, Category 6A, F/FTP, S/FTP, F/UTP, UTP, solid conductor 22-26AWG, plenum Hubbell SP6A 64 Ground busbar, TMGB, 2"x20" Chatsworth 40153-020 21 Faceplate, wall phone, stainless steel, 1-P, 1-gang Leviton 4108W-1SP 65 Ground busbar, TGB, 2"x12" Chatsworth 13622-212 22 Faceplate, QuickPort, white, 2-P, 1-gang Leviton 42080-2WS 66 Rack Bonding Busbar, 19" rack, 2 -lugs EATON SBHB119K 23 Faceplate, QuickPort, white, 4-P, 1-gang Leviton 42080-4WS 67 Ground terminal block, 1-mounting hole Chatsworth 08009-001 24 Faceplate, QuickPort, stainless steel, 8-P, 2-gang Leviton 43080-2L8 68 Ground lug connector, compression type, #6 gauge Burndy YGA6C2TC38E2G1 25 Surface mount box, QuickPort, white, 2-P Leviton 41089-2WP 69 Copper-to-Copper Antioxidant Joint Compound Chatsworth 40168-801 26 Patch panel, angled, universal, high-density, 48-port, 1U Leviton E2X1A-S48 70 Aluminum-toCopper Antioxidant Joint Compound Chatsworth 40166-101

27 Rear cable manager Leviton E2XHD-CMB 71 Telecom Room & Data Center Fittings

28 Angled panel cover Leviton E2XHD-COV 72 Equipment rack, Mighty Mo 20® Channel Racks with Hexguard cable passage, white

Legrand/Great Lakes MM20730-W /

CMRX-45U30-W-1224

29 Double-Sided Horizontal Cable Manager, 2U. CHATSWORTH 30530-X19 73 Vertical manager with door, 6.5"W x 10.25"D x7', white Legrand/Great Lakes MM20VMD706-W /

VCM-45U-0612FO-W

30 CPI Patch Panel Wire Management Bar CHATSWORTH 12176-X01 74 Concrete floor anchors Legrand CA-93 31 Trunk cable assembly, Category 6A, UTP, CMP, bundle of 6, T568B, ATLAS-X1

E2XHD, blue- actual dimension TBD Leviton CTA-UASP06L010F-CLNXA24N-CL

NXA24N-SB10E

75 Wire mesh cable tray mounting bracket, 6" elevation, white Legrand MM20CTB6H16-W

32 Trunk cable assembly, Category 6A, UTP, CMP, bundle of 6, T568B, ATLAS-X1 E2XHD, yellow - actual dimension TBD Leviton CTA-UASP06L010F-CYNXA24N-C

YNXA24N-SB10E

76 Wire mesh cable tray, 4"x18", pre-valvanized Hubbell HBT0418S

33 Fiber Optic Connectivity 77 Wire mesh cable tray support, 18" tray, pre-galvanized Hubbell HBTNSCLGS18 34 Cable, fiber optic, OFNP, 9/125, SM OS2, 12-strand, yellow Berk-Tek PDP012AB0707 78 Wire mesh cable tray 4x4 cable dropout, black Hubbell HBTCD4X4BK

Cable, fiber optic, OFNP, 50/125, MM OM4, 24-strand, aqua Berk-Tek PDP024FB010/F5 79 Network cabinet, 45Ux40"(W)x43.3"(D), front air dams, square punched rails, perforated door, side panels, brush entry, white Chatsworth/Great Lakes

NF8N-115C-E42-1 /

GL840ES-4042-Q0532

Patch cable, fiber optic, OFNP, 9/125, SM OS-2, duplex LC, type A/A, yellow * Leviton PCF-S2PR2VV-0010MAA

80 Server cabinet, (45Ux23.4"(W)x43.3"(D), front air dams, square punched rails, perforated door, side panels, brush entry, white

Chatsworth/Great Lakes

CP3203504 /

GL840ES-2448-Q0532

37 Patch cable, fiber optic, OFNP, 9/125, SM OS-2, duplex LC, type A/B, yellow * Leviton PCF-S2PR2VV-0010MAB 81 Fire-rated Pathway 38 Patch cable, fiber optic, OFNP, 50/125, MM OM-4, duplex LC, type A/A, aqua * Leviton PCF-M4PR2VV-0010MAA 82 Through-wall penetration, single pathway, Series 44 kit STI EZDP44S2 39 Patch cable, fiber optic, OFNP, 50/125, MM OM-4, duplex LC, type A/B, aqua * Leviton PCF-M4PR2VV-0010MAB 83 Multi-gang bracket, up to 5 Series 44 pathways STI EZP544W 40 Cassette, 12-fiber, 9/125, single mode OS-2, fusion splice pigtail, LC, blue Leviton SPLCH-12L 84 Through-wall penetration, single pathway, Series 33 kit STI EZDP33FWS 41 Cassette, 12-fiber, 50/125, multi mode OM-4, fusion splice pigtail, LC, aqua Leviton SPLCH-12A 85 Three-gang bracket, Series 33 STI EZDP333W 42 Patch panel, angled, fiber optic, UHDX, 1RU Leviton HDX1A-144 86 Two-gang bracket, Seriess 33 STI EZDP233W 43 Rear cable manager with management rings Leviton E2XHD-CMB 87 Through-wall penetration, single pathway, Series 22 kit STI EZD22

44 Universal Opt-X clamp kit, multiple cable grommet Leviton 5RCMP-KT2 88 Firestop Retrofit Fire Rated Devices STI EZDR400

1 RESPONSIBILITY MATRIX

SCALE: N.T.S.

2 PREFERRED PRODUCTS MATRIX

SCALE: N.T.S.

SHEET NOTES:

1. MATERIALS SHOWN IN THE "PREFERRED PRODUCTS SCHEDULE ARE THE BASIS OF DESIGN AND ARE COMPATIBLE WITH EXISTING CONDITIONS.

EQUIVALENT PRODUCTS MAY BE SUBMITTED FOR APPROVAL.

2. CONTRACTOR IS RESPONSIBLE FOR DETERMINING QUANTITIES, LENGTH, DISTANCES, COLOR, AND OTHER DETAILS NECESSARY FOR A COMPLETE

WORKING SYSTEM.

3 CABLE SCHEDULE

SCALE: N.T.S.

CABLE SCHEDULE

DESCRIPTION CABLE TYPE UL LISTING PERFORMANCE CABLE COLOR STRANDS/PAIRS CABLE CONFIG. OUTLET COLOR

VOICE (EXISTING) UTP CMP EXISTING WHITE 4-PAIR WHITE

DATA U/UTP CMP CATEGORY 6A BLUE 4-PAIR BLUE/ORANGE

WIRELESS LAN U/UTP CMP CATEGORY 6A GREEN 4-PAIR ORANGE

SECURITY (EXISTING) UTP CMP EXISTING PURPLE (VIOLET) 4-PAIR ORANGE

GET WELL (EXISTING) UTP CMP EXISTING ORANGE 4-PAIR ORANGE

GUEST WIFI (EXISTING) UTP CMP EXISTING PINK 4-PAIR ORANGE

MM - DATA BACKBONE 50/125 OFNP* MULTI MODE - OM4 AQUA 24-STRAND TIGHT BUFFER AQUA-DUPLEX LC

SM - DATA BACKBONE 9/125 OFNP* SINGLE MODE - OS1 YELLOW 12-STRAND TIGHT BUFFER BLACK-DUPLEX LC

SM - DATA BACKBONE - OSP 9/125 OFNR** SINGLE MODE - OS2 BLACK 24-STRAND LOOSE TUBE BLACK-DUPLEX LC

* DIELECTRIC, NON-CONDUCTING CABLE, UL LISTED OFNP FOR USE IN PLENUM SPACES.

** ALL DIELECTRIC, NON-CONDUCTING, INDOOR/OUTDOOR CABLE, UL LISTED OFNR FOR USE IN NON-PLENUM, RISER AND OSP SPACES.

SCHEDULE NOTES:

1. CABLE CONNECTORS, FACEPLATES, MODULAR JACKS, PATCH CABLES, AND PATCH PANELS SHALL BE A SINGLE MANUFACTURER, SUCH AS HUBBELL OR PANDUIT.

2. CATEOGORY 6A TELECOMMUNICATIONS OUTLETS AND PATCH PANELS OUTLETS TO BE TERMINATED T568B

3. PREFERRED CABLE AND CONNECTIVITY MANUFACTURER IS LEVITON/BERK-TEK

4. EXISTING CABLES NOT REMOVED DURING DEMOLITION SHALL BE RE-TERMINATED ON NEW PATCH PANEL. COORIDINATE WITH COR FOR PLACEMENT.

5. OS-2 SINGLE MODE FIBER OPTIC CABLE MAY BE USED IN PLACE OF OS-1 SINGLE MODE FIBER OPTIC CABLE.

4 TR ZONE SCHEDULE

SCALE: N.T.S.

TR ZONE TR ROOM NO. BLDG. FLOOR/LEVEL

1 D007D 1A GROUND

2 A002C 1 GROUND

3 C121 1A 1st Floor

4 A104 1 1st Floor

5 C222 1A 2nd Floor

6 A243 1 2nd Floor

7 C333 1A 3rd Floor

8 A345 1 3rd Floor

9 CU411 1A 4th Floor

10 A450 1 4th Floor

11 C580 1A 5th Floor

12 AU547 1 5th Floor

13 A627 1A 6th Floor

14 CNTRL ROM 4

* CONTRACTOR SHALL DETERMINE PART NUMBER BASED ON LENGTH REQUIRED FOR EACH ITEM PRIOR TO ORDERING.

TBD CONTRACTOR SHALL DETERMINE LENGTH, WIDTH, AND NECESSARY COMPONENTS FOR A COMPLETE WORKING SYSTEM.

T-002

TECHNOLOGY SCHEDULES

RMJr

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

UP

UP DN

UP

MECH RM

D-B038

EMERGENCY

GENERATOR

D003

TRANSFORMERS

& SWITCHGEAR

D003A

CORRIDOR

DH001

STAIR

PAS06

STAIR

PAS07

ELECTRICAL

D001

TD

D002

CORRIDOR

DH002

MECH RM

D004

EMS

D005

STOR

D005A

STORAGE

D006

ELEVATOR

S6

ELEVATOR

S7

C O

R R

ID

O

R D

H

PAINT

SHOP

D007C

CORRIDOR

DH003 SIGNAL

CLOSET

D008

STORAGE

PA08

PARKING

LEVEL A

PA01

CORRIDOR

DH004

CARPENTER

SHOP

D007

STORAGE

AREA

PA06

CHIEF

D007A

LOCKSMITH

D007B

CORRIDOR

DH005 CHIEF

ELECTRICIA

B014B

M&O

FORMA

B013

CORRIDOR

BH002

STAIR

PAS08

M

EC

H

AN

IC

AL

B0

F

EMERGENCY

POWER

PA06B

NORMAL

POWER

PA06A

TR

D007D

UP

UP DN

UP

MECH RM

D-B038

EMERGENCY

GENERATOR

D003

TRANSFORMERS

& SWITCHGEAR

D003A

CORRIDOR

DH001

STAIR

PAS06

STAIR

PAS07

ELECTRICAL

D001

TD

D002

CORRIDOR

DH002

MECH RM

D004

EMS

D005

STOR

D005A

STORAGE

D006

ELEVATOR

S6

ELEVATOR

S7

C O

R R

ID

O

R D

H

PAINT

SHOP

D007C

CORRIDOR

DH003 SIGNAL

CLOSET

D008

STORAGE

PA08

PARKING

LEVEL A

PA01

CORRIDOR

DH004

CARPENTER

SHOP

D007

STORAGE

AREA

PA06

CHIEF

D007A

LOCKSMITH

D007B

CORRIDOR

DH005 CHIEF

ELECTRICIA

B014B

M&O

FORMA

B013

CORRIDOR

BH002

STAIR

PAS08

M

EC

H

AN

IC

AL

B0

F

EMERGENCY

POWER

PA06B

NORMAL

POWER

PA06A

TR

D007D c c c

G

2 2 c c

1 DEMO FLOOR PLAN - PARKING GARAGE - LEVEL C & AREA D

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-100-1A.G

DEMO PLAN - BLDG. 1A

PARKING GARAGE - LEVEL A

VV

1A

RMJr

KEY PLAN

PA

D

B

A

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

DATA AND ELECTRICAL OUTLETS WHERE NOTED.

COORDINATE WITH COR FOR NEW LOCATION.

TRUE

NORTH

PLAN

NORTH

1 / TD-400-1-1A.G

MOTOR

CYCLE PARKING

WHEEL

CHAIR PARKING

PARKING

LEVEL A

PA01

STAIRWELL

PAS05

ELEVATOR

PAE04

ELEVATOR

PAE05

ELEVATOR

LOBBY

PA02

STORAGE

PA07

OTHER

SPACE

PAM03

M

EC

H B0 C

O R

R

ID

O R

BH

STORAGE

A008

FOOD

STORAG

A006A

STAIRWELL

PAS04

MOTOR

CYCLE PARKING

WHEEL

CHAIR PARKING

PARKING

LEVEL A

PA01

STAIRWELL

PAS05

ELEVATOR

PAE04

ELEVATOR

PAE05

ELEVATOR

LOBBY

PA02

STORAGE

PA07

OTHER

SPACE

PAM03

M

EC

H B0 C

O R

R

ID

O R

BH

STORAGE

A008

FOOD

STORAG

A006A

STAIRWELL

PAS04

c

G c c c c c

G G

1 DEMO FLOOR PLAN - PARKING GARAGE - LEVEL A

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-101-1A.G

DEMO PLAN - BLDG. 1A

PARKING GARAGE - LEVEL A

VV

1A

RMJr

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

DATA AND ELECTRICAL OUTLETS WHERE NOTED.

COORDINATE WITH COR FOR NEW LOCATION.

HANDICAPPEDHANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING PARKING

LEVEL B

FAN RM

PB04

STAIRWELL

PBS06

TC

PB06

EC

PB05

OTHER SPACE

PB07

UTILITY TUNNEL

OTHER SPACE

PB09

PARKING

PB01

CHASE

PB03

HANDICAPPEDHANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING PARKING

LEVEL B

FAN RM

PB04

STAIRWELL

PBS06

TC

PB06

EC

PB05

OTHER SPACE

PB07

UTILITY TUNNEL

OTHER SPACE

PB09

PARKING

PB01

CHASE

PB03

c c c c c

G

1 DEMO FLOOR PLAN - PARKING GARAGE - LEVEL B

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-102-1A.G

DEMO PLAN - BLDG. 1A

PARKING GARAGE - LEVEL B

VV

1A

TRUE

NORTH

PLAN

NORTH

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

DATA AND ELECTRICAL OUTLETS WHERE NOTED.

COORDINATE WITH COR FOR NEW LOCATION.

KEY PLAN

PA

D

B

A

WHEEL CHAIR PARK

HANDICAPPED

PARKING

HANDICAPPED

HANDICAPPED

PARKING PARKING

HANDICAPPED

PARKING

HANDICAPPED HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

DOWN

UP

DOWN

UP

CHASE

PB03

STAIRWELL

PBS05

ELEVATOR

P4

ELEVATOR

P5

ELEV

VESTIBULE

PB02

STORAGE

PB10

PUMP RM

0-C-1

STAIRWELL

PBS04

OTHER SPACE

PB11

WHEEL CHAIR PARK

HANDICAPPED

PARKING

HANDICAPPED

HANDICAPPED

PARKING PARKING

HANDICAPPED

PARKING

HANDICAPPED HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING

HANDICAPPED

PARKING PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

VOLUNTEER

PARKING

DOWN

UP

DOWN

UP

CHASE

PB03

STAIRWELL

PBS05

ELEVATOR

P4

ELEVATOR

P5

ELEV

VESTIBULE

PB02

STORAGE

PB10

PUMP RM

0-C-1

STAIRWELL

PBS04

OTHER SPACE

PB11

c c c c

G

G

1 DEMO FLOOR PLAN - PARKING GARAGE - LEVEL B

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-103-1A.G

DEMO PLAN - BLDG. 1A

PARKING GARAGE - LEVEL B

VV

1A

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

FF:CONCRETE

FF:CONCRETE

FF:VCT

FF:CONCRETE FF:CONCRETE

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FAN RM

00-D-1

STAIR

PCS06

EC

00-D-2

TC

00-D-3

MECH RM

PC10

STORAGE

PC09

OTHER SPACE

PCM11

PARKING

PC01

STORAGE

PC05

STAIR

SUMP

00-C-3

FF:CONCRETE

FF:CONCRETE

FF:VCT

FF:CONCRETE FF:CONCRETE

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FAN RM

00-D-1

STAIR

PCS06

EC

00-D-2

TC

00-D-3

MECH RM

PC10

STORAGE

PC09

OTHER SPACE

PCM11

PARKING

PC01

STORAGE

PC05

STAIR

SUMP

00-C-3 c c c c c c

G

G

G

1 DEMO FLOOR PLAN - PARKING GARAGE - LEVEL C

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-104-1A.G

DEMO PLAN - BLDG. 1A

PARKING GARAGE - LEVEL C

VV

1A

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

DOWN

MOTORCYCLE

MOTORCYCLE

FF:VCT

FF:VCT

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FF:CONCRETE

FF:VCT

STORAGE

PC05

STAIR

PCS05

ELEV

EQUIP

00-C-1

ELEVATOR

PCE04

ELEVATOR

PCE05

ELEVATOR

LOBBY

PC02

STORAGE

PC16

MECH

RM

PC15

STORAGE

00C6

STORAGE

PC14

STAIRWELL

PCS04

SUMP

00-C-3

FAN RM

00-C-2

OTHER SPACE

PCM17

DOWN

UP

MOTORCYCLE

MOTORCYCLE

FF:VCT

FF:VCT

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:VCT

FF:VCT

FF:CONCRETE

FF:CONCRETE

FF:CONCRETE

FF:VCT

STORAGE

PC05

STAIR

PCS05

ELEV

EQUIP

00-C-1

ELEVATOR

PCE04

ELEVATOR

PCE05

ELEVATOR

LOBBY

PC02

STORAGE

PC16

MECH

RM

PC15

STORAGE

00C6

STORAGE

PC14

STAIRWELL

PCS04

SUMP

00-C-3

FAN RM

00-C-2

OTHER SPACE

PCM17

c c c

G

G

1 DEMO FLOOR PLAN - PARKING GARAGE - LEVEL C

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-105-1A.G

DEMO PLAN - BLDG. 1A

PARKING GARAGE - LEVEL C

VV

1A

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

ELECTRICAL

CORRIDOR

AH010

STERILE AND

NON-STERILE

STORAGE

A001A

A005C

GAS CYL

STORAGE

B005D

CLEAN

RECEIVING

B007

CORRIDOR

AH003

GE

RETAIL

STORE

A009

C O

R R

ID

O

R

AH

ASST

CHIEF

A012

CLERK

TYPIST

A011

CHIEF

A010

OFFICE

CANTEEN

A007

REFR

WALK IN

A006B

PREFAB

REFRIG

A006C

FOOD

STORAGE

A006A

LL

KITCHEN

A006

HAC

A006F

AU008 AU007 AU006

CORRIDOR

AH001

STAIR

AS002 STORAGE

A004

CAFETERIA

A004A

FOOD

SERVICING

A006D

SERVING

LINE

A005

SURGICAL

PACK

B045C

MAIN

KITCHEN

B036

EQUIP

STORAGE

AREA

B001

ELECTRIC

CLOSET

BU003

EMS

A001B

DUMB

ELEVATOR

OFFICE

A019

ELEVATOR

LOBBY

A001

OFFICE

ASST

CHIEF

A003

ELEV

AE004

ELEV

AE005

BREAK

RM

A021

ELEVATOR

LOBBY

A000

DISH

WASHING

A020

ELECTRIC

CLOSET

AU004

EMS

A023

CORRIDOR

AH004

DIETICIANS

OFFICE

A025

ASST

CHIEF

A027

DIETICIANS

OFFICE

A025A

SECY

A028

CORRIDOR

AH005

CONFERENCE M

A029

CORRIDOR

BH006

SUPV

OFFICE

B045

BREAK

RM

B045A

ELECTRICAL

AU003

ELECTRICAL

AU002CORRIDOR

AH004 AU001

ELECTRIC

CLOSET

AU005

EMS

A004B

STORAGE

A004A

VCS

OFFICE

A004A

CHIEF

VCS

OFFICE

A004E

LOCKERS

FEMALE

A002A

LOUNGE

A002

IT

CLOSET

A002C

ELEV

P3

ELEV

P2

ELEV

P1

TOILET &

SHOWERS

A002B

TELEPHONE

EQUIP RM

A022

TOILET

A024 EMS

A026

LOCKERS

A026B

OT

CLINIC

A044

A026A

TOILET &

SHOWERS

A046

TOILET

FEMALE

A045

C O

R R

ID

O

R

AH

CORRIDOR

AH007

OT

OFFICE

A043

OT

OFFICE

A043A

OFFICE

A070RECEIVING

A071

SVC MGR

A072

CORRIDOR

AH009

OFFICE

A069

DATA

CENTER

A073

PGM MGR

A068

SOFTWARE

APPL

SUPPORT

A067

APPLICATION

SUPPORT

A066

SYSTEMS

MGR

A065

NETWORKING

MGR

A064

PROG MGR

SYST &

NETWORKING

A063ADP

WORKSHOP

A062

STAIRWELL

AS004

TELECOMM

SVCS

A061

TELECOMM

SVCS

A060

SUPPORT

A059

APPLICATION

SUPPORT

A058

APPLICATION

SUPPORT

A057

CONFERENCE

RM

A055

C O

R R

ID

O

R

AH

PGMMING

& INFO

A054

PGMMING

& INFO

A053

PGM

SPECIALISTS

A052

OFFICE

A051

RECEPTION

AREA

A050

TRACTION

A039

PROVIDER

A038

EXAM

A040

EXAM

A041

CORRIDOR

A030A

EXAM/

EMG

A037

WAITING

AREA A042

STAIRWELL

AS001

WAITING

AREA

A036

PHYSICAL

THERAPY

WORK

ROOM

RECEPTION

A030

THERAPY

A034A

THERAPY

A034

PHYSICAL

THERAPY

A035

STORAGE

A033

PM&RS

CHIEF'S

OFFICE

A032A

SECY

OFFICE

A032B

RESIDENTS

OFFICE

A032C

HALL

A032

CONFERENCE

RM

A032D CHARTING

A032E

ELECTRICAL

CORRIDOR

AH010

STERILE AND

NON-STERILE

STORAGE

A001A

A005C

GAS CYL

STORAGE

B005D

CLEAN

RECEIVING

B007

CORRIDOR

AH003

GE

RETAIL

STORE

A009

C O

R R

ID

O

R

AH

ASST

CHIEF

A012

CLERK

TYPIST

A011

CHIEF

A010

OFFICE

CANTEEN

A007

REFR

WALK IN

A006B

PREFAB

REFRIG

A006C

FOOD

STORAGE

A006A

LL

KITCHEN

A006

HAC

A006F

AU008 AU007 AU006

CORRIDOR

AH001

STAIR

AS002 STORAGE

A004

CAFETERIA

A004A

FOOD

SERVICING

A006D

SERVING

LINE

A005

SURGICAL

PACK

B045C

MAIN

KITCHEN

B036

EQUIP

STORAGE

AREA

B001

ELECTRIC

CLOSET

BU003

EMS

A001B

DUMB

ELEVATOR

OFFICE

A019

ELEVATOR

LOBBY

A001

OFFICE

ASST

CHIEF

A003

ELEV

AE004

ELEV

AE005

BREAK

RM

A021

ELEVATOR

LOBBY

A000

DISH

WASHING

A020

ELECTRIC

CLOSET

AU004

EMS

A023

CORRIDOR

AH004

DIETICIANS

OFFICE

A025

ASST

CHIEF

A027

DIETICIANS

OFFICE

A025A

SECY

A028

CORRIDOR

AH005

CONFERENCE M

A029

CORRIDOR

BH006

SUPV

OFFICE

B045

BREAK

RM

B045A

ELECTRICAL

AU003

ELECTRICAL

AU002CORRIDOR

AH004 AU001

ELECTRIC

CLOSET

AU005

EMS

A004B

STORAGE

A004A

VCS

OFFICE

A004A

CHIEF

VCS

OFFICE

A004E

LOCKERS

FEMALE

A002A

LOUNGE

A002

IT

CLOSET

A002C

ELEV

P3

ELEV

P2

ELEV

P1

TOILET &

SHOWERS

A002B

TELEPHONE

EQUIP RM

A022

TOILET

A024 EMS

A026

LOCKERS

A026B

OT

CLINIC

A044

A026A

TOILET &

SHOWERS

A046

TOILET

FEMALE

A045

C O

R R

ID

O

R

AH

CORRIDOR

AH007

OT

OFFICE

A043

OT

OFFICE

A043A

OFFICE

A070RECEIVING

A071

SVC MGR

A072

CORRIDOR

AH009

OFFICE

A069

DATA

CENTER

A073

PGM MGR

A068

SOFTWARE

APPL

SUPPORT

A067

APPLICATION

SUPPORT

A066

SYSTEMS

MGR

A065

NETWORKING

MGR

A064

PROG MGR

SYST &

NETWORKING

A063ADP

WORKSHOP

A062

STAIRWELL

AS004

TELECOMM

SVCS

A061

TELECOMM

SVCS

A060

SUPPORT

A059

APPLICATION

SUPPORT

A058

APPLICATION

SUPPORT

A057

CONFERENCE

RM

A055

C O

R R

ID

O

R

AH

PGMMING

& INFO

A054

PGMMING

& INFO

A053

PGM

SPECIALISTS

A052

OFFICE

A051

RECEPTION

AREA

A050

TRACTION

A039

PROVIDER

A038

EXAM

A040

EXAM

A041

CORRIDOR

A030A

EXAM/

EMG

A037

WAITING

AREA A042

STAIRWELL

AS001

WAITING

AREA

A036

PHYSICAL

THERAPY

WORK

ROOM

RECEPTION

A030

THERAPY

A034A

THERAPY

A034

PHYSICAL

THERAPY

A035

STORAGE

A033

PM&RS

CHIEF'S

OFFICE

A032A

SECY

OFFICE

A032B

RESIDENTS

OFFICE

A032C

HALL

A032

CONFERENCE

RM

A032D CHARTING

A032E

2 2

2 2 2 2 2

2 2

2 2 2 2

2 2 2 2

2 2

G

G

G

2 2

2 2 c c cc c

G c c cc

G

G

2 2

2 2

2 2

2 2

2 2

2 2

POST

POST

POST

POST

c c c

1 DEMO FLOOR PLAN - GROUND FLOOR - AREA A

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-107-1.G

DEMO PLAN - BLDG. 1

GROUND FLOOR - AREA A

VV

RMJr

KEY PLAN

PA

D

B

A

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRACTOR SHALL REMOVE NON-CATEGORY

6/6A FACE PLATES, MODULAR JACKS, AND

PATCH PANELS AFTER CUT OVER TO NEW

CATEGORY 6A CABLE PLANT.

11.CONTRACTOR SHALL PRESERVE CABLE

SUPPORTS, SUCH AS CABLE TRAYS OR J-HOOKS

FOR REUSE, UNLESS OTHERWISE INDICATED.

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLE SUPPORTS.

12.NURSE CALL SYSTEM TO BE MAINTAINED IN TR

ROOM. CONTRACTOR SHALL COORDINATE NEW

EQUIPMENT LOCATION WITH THE COR PRIOR TO

MOVING THE NURSE CALL SYSTEM OR BEFORE

WALL DEMOLITION BEGINS.

13.CONTRACTOR SHALL RELOCATE WALL

MOUNTED TV AND PROVIDE NEW CATEGORY 6A

DATA AND ELECTRICAL OUTLETS WHERE NOTED.

COORDINATE WITH COR FOR NEW LOCATION.

TRUE

NORTH

PLAN

2 / TD-400-1-1A.G

DN

DN

OR CHIEF

ELECTRICIAN

B014B

M&O

FORMAN

B013

ELECTRONIC

B014

ELECTRIC

SHOP

B014C

STAFF

TOILET

B015A

OFFICE

B017

STORAGE

FLAMMABLE

B016

STORAGE

GENERAL

B020

WAREHOUSE

B015

MAIL RM

B015B

EMS

EQUIP

B021 SOILED

UTILITY

B022A OFFICE

B022D

OFFICE

B022E

C O

R R

ID

O

R

BH

TOILET

FEMALE

B019

TOILET

MALE

B018

MENS

TOILET

B003

HALL

B004

STORAGE

B009A

SOILED RECEIVING

DECONTAMINATION

AREA

B005

LOGISTICS

BREAKDOWN

B006B

HALL

B006A

ELEC.

B009

ELECTRIC

CLOSET

BU002

CORRIDOR

BH003

UNION

OFFICE

B011A

LOGISTICS

STORAGE

B011

OFFICE

B012A

PROSTHETICS

STORAGE

B015C

MORGUE

B015A

CORRIDOR

BH002

AC

PLUMBING

MACH

B012

BULK

STORAGE

B010

CORRIDOR

OX101

PREPARATION

STERILIZATION

WORK RM

A005C

GAS CYL

STORAGE

B005D

CLEAN

RECEIVING

B007

CORRIDOR

AH003

LOGISTICS SVC

INVENTORY MGMT

B022

WOMENS

TOILET

B002

CORRIDOR

BH004

OFFICE

B022C

OFFICE

B022B

OFFICE

B022A

C O

R R

ID

O

R

BH

EMERGENCY

GENERATOR RM

B037

C O

R R

ID

O

R

BH

FEMALE

TOILET

B040

MENS

TOILET

B041

EMS

B036C

LINEN

B036D

CANTEEN

STORAGE

B036B

MAIN

KITCHEN

B036

ENVIRONMENTAL

MGMT SUPPLY

B045D

SURGICAL

PACK

B045C

STORAGE

B045B

MAIN

KITCHEN

B036

OFFICE

SUPVS

B036F

DAIRY &

EGG

REFRIG

B036G

STORAGE

B035A

OFFICE

B035

STORAGE &

ISSUE

B034

STAIRWELL

BS003

EMS

B005A

MANUAL

CART

WASH

B005B

EQUIP

STORAGE

AREA

B001

ELECTRIC

CLOSET

BU003

SUPV

OFFICE

B045

BREAK

RM

B045A

PM&RS

CHIEF'S

OFFICE

A032A

SECY

OFFICE

A032B

RESIDENTS

OFFICE

A032C

HALL

A032

CONFERENCE

RM

A032D CHARTING

A032E

IT

B046

HAS

B044

TOILET

B044AEMS

B043

ELECTRIC

CLOSET

B043A

EMS

CHECK IN

B042B

EMS

OFFICE

B042A HAS

B044B

HAS

B044C

SVC RM

B039

SECY/

RECEPTIONIST

B-042

OFFICE ASST

CHIEF WORK

RM

B-042C

CORRIDOR

BH004

ELECTRICAL

DISTRIBUTION

RM

B037B

A/C

REFRIGERATION

EQUIP RM

B038

TRANSFORMER

RM

B037A

UP

DN

DN

OR CHIEF

ELECTRICIAN

B014B

M&O

FORMAN

B013

ELECTRONIC

B014

ELECTRIC

SHOP

B014C

STAFF

TOILET

B015A

OFFICE

B017

STORAGE

FLAMMABLE

B016

STORAGE

GENERAL

B020

WAREHOUSE

B015

MAIL RM

B015B

EMS

EQUIP

B021 SOILED

UTILITY

B022A OFFICE

B022D

OFFICE

B022E

C O

R R

ID

O

R

BH

TOILET

FEMALE

B019

TOILET

MALE

B018

MENS

TOILET

B003

HALL

B004

STORAGE

B009A

SOILED RECEIVING

DECONTAMINATION

AREA

B005

LOGISTICS

BREAKDOWN

B006B

HALL

B006A

ELEC.

B009

ELECTRIC

CLOSET

BU002

CORRIDOR

BH003

UNION

OFFICE

B011A

LOGISTICS

STORAGE

B011

OFFICE

B012A

PROSTHETICS

STORAGE

B015C

MORGUE

B015A

CORRIDOR

BH002

AC

PLUMBING

MACH

B012

BULK

STORAGE

B010

CORRIDOR

OX101

PREPARATION

STERILIZATION

WORK RM

A005C

GAS CYL

STORAGE

B005D

CLEAN

RECEIVING

B007

CORRIDOR

AH003

LOGISTICS SVC

INVENTORY MGMT

B022

WOMENS

TOILET

B002

CORRIDOR

BH004

OFFICE

B022C

OFFICE

B022B

OFFICE

B022A

C O

R R

ID

O

R

BH

EMERGENCY

GENERATOR RM

B037

C O

R R

ID

O

R

BH

FEMALE

TOILET

B040

MENS

TOILET

B041

EMS

B036C

LINEN

B036D

CANTEEN

STORAGE

B036B

MAIN

KITCHEN

B036

ENVIRONMENTAL

MGMT SUPPLY

B045D

SURGICAL

PACK

B045C

STORAGE

B045B

MAIN

KITCHEN

B036

OFFICE

SUPVS

B036F

DAIRY &

EGG

REFRIG

B036G

STORAGE

B035A

OFFICE

B035

STORAGE &

ISSUE

B034

STAIRWELL

BS003

EMS

B005A

MANUAL

CART

WASH

B005B

EQUIP

STORAGE

AREA

B001

ELECTRIC

CLOSET

BU003

SUPV

OFFICE

B045

BREAK

RM

B045A

PM&RS

CHIEF'S

OFFICE

A032A

SECY

OFFICE

A032B

RESIDENTS

OFFICE

A032C

HALL

A032

CONFERENCE

RM

A032D CHARTING

A032E

IT

B046

HAS

B044

TOILET

B044AEMS

B043

ELECTRIC

CLOSET

B043A

EMS

CHECK IN

B042B

EMS

OFFICE

B042A HAS

B044B

HAS

B044C

SVC RM

B039

SECY/

RECEPTIONIST

B-042

OFFICE ASST

CHIEF WORK

RM

B-042C

CORRIDOR

BH004

ELECTRICAL

DISTRIBUTION

RM

B037B

A/C

REFRIGERATION

EQUIP RM

B038

TRANSFORMER

RM

B037A

2 2

2 2

2 2

2 2

2 2

2 2 c c c c c c c

2 2

2 2 2

22 2 222 c c trash compator c

IT

B046

1 DEMO FLOOR PLAN - GROUND FLOOR - AREA B

SCALE: 1/8" = 1'-0"

Project Number

Building Number

Drawing Number

DrawnCheckedIssue Date

Location

Project Title

21 3 4 5 6 7 8 9 10

21 3 4 5 6 7 8 9 10

B

A

C

D

E

F

B

A

C

D

E

F

PhaseDrawing Title

Approved: Project Director

ARCHITECT OF RECORDCONSULTANTRevisions: Date:

U.S. Department of Veterans Affairs

Construction and Facilities Management

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

FULLY SPRINKLERED

569A4-22-700

16-MAY-23

100% CONSTRUCTION

DOCUMENTS

LEXINGTON-COOPER EHRM

INFRASTRUCTURE DESIGN

1101 VETERANS DRIVE

LEXINGTON, KY 40502

8718 Botts Lane Phone: (210) 816-4784 San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com

RMJr

09-MAY-23

TD-108-1.G

DEMO PLAN - BLDG. 1

GROUND FLOOR - AREA B

VV

KEY PLAN

PA

D

B

A

TRUE

NORTH

PLAN

NORTH

DEMO NOTES

1. EXISTING CABLE TRAYS SHALL BE RE-USED

UNLESS OTHERWISE NOTED. REFER TO TN-300

SERIES - PATHWAY FOR DETAILS.

2. EXISTING J-HOOKS SHALL BE RE-USED UNLESS

OTHERWISE NOTED.

3. EXISTING TELECOMMUNICATIONS ROOM.

CONTRACTOR SHALL DEMO ALL PATCH PANELS

AND CABLING RELATED TO THIS PROJECT.

CONTRACTOR SHALL REMOVE ALL DATA CABLES

FROM THE DEVICE TO THE SOURCE.

CONTRACTOR SHALL COORDINATE WITH THE

COR PRIOR TO BEGINNING WORK IN EACH

TELECOM ROOM (TR).

4. DO NOT REMOVE ANY WALL MOUNTED

EQUIPMENT, ELECTRICAL CABLES AND

EQUIPMENT, OR ANY CABLING OR DEVICE THAT

IS NOT DATA RELATED. COORDINATE WITH COR

PRIOR TO REMOVING CABLING FROM WALL

FIELDS OR FROM WALL MOUNTED EQUIPMENT.

5. BUILDING AUTOMATION SYSTEMS (BAS) OR

ELECTRONIC SECURITY SYSTEMS CABLES

SHALL NOT BE REMOVED. COORDINATE WITH

COR TO IDENTIFY BAS OR SECURITY CABLES.

6. EXISTING TELECOMMUNICATIONS OUTLET.

CONTRACTOR SHALL REMOVE ALL DEVICE

FACEPLATES AND MODULAR JACKS. EXISTING

OUTLET BOXES AND CONDUITS SHALL BE

PRESERVED FOR REUSE.

7. CONTRACTOR SHALL REMOVE ALL DATA CABLES

EXCEPT CATEGORY 6/6A OR UNLESS

OTHERWISE NOTED. CONTRACTOR SHALL

COORDINATE WITH THE COR PRIOR TO

REMOVING CABLES, OUTLETS, FACE PLATES,

PATCH PANELS, AND PATCH CABLES.

8. CABLES SHALL NOT BE ABANDONED IN PLACE

WITHOUT PRIOR APPROVAL OF THE COR.

9. WHERE CABLES ARE TO BE REMOVED,

CONTRACTOR SHALL COMPLETELY REMOVE THE

CABLE FROM OUTLET TO PATCH PANEL.

10.CONTRAC…