This document provides specifications for mechanical controls, electrical metering, water detection sensors, and exhaust fan controls for the Project No. 596A4-22-700 Electronic Health Record Modernization Infrastructure Upgrades Construction Project at the Lexington VA Health Care System - Troy Bowling Campus. The specifications require split system air conditioning units with temperature and humidity controls integrated into the BAS. Computer room air handling units must provide rack temperature monitoring and humidity and cooling controls. Electrical panel submetering outputs must communicate with the existing Tririgium BAS. Water sensors in drain pans and underfloor areas must alarm locally and to the BAS. Exhaust fans must interlock with smoke dampers and pressure sensors. Point lists define control strategies and alarm/monitoring points for the BAS.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPLIT SYSTEM AIR CONDITIONING UNITS (AC) & (ACCU):
SYSTEM SHALL BE UTILIZED TO PROVIDE TEMPERATURE CONTROL FOR THE TELECOMMUNICATION ROOMS (TR) AND
ELECTRICAL ROOMS (ER).
CONTROL OF THE SPLIT SYSTEM AIR CONDITIONING UNIT AND THE ASSOCIATED REMOTE AIR COOLED CONDENSING UNIT SHALL BE ACCOMPLISHED LOCALLY BY MANUFACTURER PROVIDED UNIT CONTROLLER. THE SPLIT SYSTEM MANUFACTURER SHALL PROVIDE ALL PROGRAMMING, CONTROLLERS, SENSORS, AND OTHER REQUIRED DEVICES
NECESSARY TO ACHIEVE THE SEQUENCE OF OPERATION AS FOLLOWS.
THE SPLIT SYSTEM CONTROLLER SHALL CYCLE THE OUTDOOR CONDENSING UNIT COMPRESSOR AND CONDENSER FAN TO MAINTAIN SPACE TEMPERATURE SETPOINT OF 72°F (ADJ). CONTROL THE INDOOR FAN IN EITHER LOW, MEDIUM, OR HIGH SPEEDS TO MAINTAIN SETPOINT AND MINIMIZE CYCLING OF THE CONDENSING UNIT.
THE BAS SHALL MONITOR THE NEW SPLIT SYSTEM ALARMS AND TRENDS.
PROVIDE A CONDENSATE PUMP.
PROVIDE A WALL MOUNTED SPACE TEMPERATURE/ HUMIDITY SENSOR FOR TRENDING SPACE TEMPERATURE, MONITORING AND ALARM PURPOSES. INSTALL ONLY (1) SENSOR PER ROOM, SENSOR TO CONTROL MULTIPLE AC
UNITS, IF APPLICABLE.
PROVIDE A BAS ALARM IF SPACE TEMPERATURE RISES ABOVE 85°F (ADJ).
SPLIT SYSTEM CONTROLS - SEQUENCE OF OPERATIONS
SPC-TT
WDS-AS
SPC-TTWALL-MOUNTED
TEMP SENSOR
WITH OVERRIDE
DATA CENTER (CRAC) - SEQUENCE OF OPERATIONS
SYSTEM DESCRIPTION
THE SYSTEM CONSISTS OF THREE COMPUTER ROOM TYPE UNIT WITH DX COOLING COIL, ELECTRIC REHEAT COIL, AND REMOTE AIR COOLED CONDENSING UNIT. INDIVIDUAL UNIT CONTROL SHALL BE PROVIDED BY THE INTERNAL STANDARD MANUFACTURERS TEMPERATURE CONTROLS. THE SYSTEM SHALL BE UNDER THE CONTROL OF THE BAS. THE PLANT IS CONFIGURED FOR N+1 REDUNDANCY, SUCH THAT ANY ONE CRAC UNIT COULD FAIL AND THE OTHER REMAINING UNITS COULD PROVIDE THE COOLING AND
HUMIDIFICATION CONTROL FOR THE COMPUTER ROOM A073.
IN NORMAL CONDITION OPERATION, ALL CRAC UNITS OPERATE CONCURRENTLY, AT THE LOWEST COLLECTIVE ENERGY USE LEVEL
POSSIBLE.
TEMPERATURE AND HUMIDITY MONITORING
THE SPACE TEMPERATURE AND HUMIDITY SHALL BE SENSED BY SPACE SENSORS. THE TEMPERATURE AND HUMIDITY READINGS SHALL BE REPORTED TO THE BAS. THE BAS SHALL BE ABLE TO ADJUST THE SPACE TEMPERATURE AND HUMIDITY SETTINGS.
RACK TEMPERATURE SENSOR MONITORING
A RACK INFRASTRUCTURE MANAGEMENT SYSTEM IS BEING INSTALLED WITH THE RACKS. THE BAS SHALL INTERFACE WITH THIS SYSTEM
(3) LOCATIONS - BOTTOM, MIDDLE, AND TOP) TO MONITOR THE AIR TEMPERATURES AT THE RACKS. AVERAGE RACK-FACE INLET TEMPERATURE SHALL BE DETERMINED AS THE AVERAGE OF THE 3-SENSOR TEMPERATURE MEASUREMENT. THE AVERAGE TEMPERATURE AT THE RACK INLET IS TO BE BETWEEN 72°F AND 80.6°F. ALARM THE BAS IF ANY OF THE AVERAGE RACK INLET
TEMPERATURES INDICATE TEMPERATURES ABOVE 80.6F (ADJ.).
DESIGN CONDITIONS AT THE RACKS SHALL MAINTAIN A 20°F ΔT BETWEEN THE SUPPLY AIR (COLD AISLE) AND THE RETURN AIR
TEMPERATURE AT THE WALL MOUNTED SPACE SENSOR.
THE CONTROL SYSTEM SHALL BE ABLE TO DETERMINE THE OPERATIONAL ΔT, MONITOR THE SUPPLY TEMPERATURES AT THE RACK ENCLOSURES, AND REGULATE THE FAN SPEED AND REFRIGERANT FLOW AT EACH INDIVIDUAL CRAC.
COOLING
THE ACTIVATION AND SEQUENCING OF COMPUTER ROOM AIR CONDITIONING UNITS (CRAC) SHALL BE PERFORMED BY THE BAS.
CONTROL OF EACH CRAC'S INTERNAL OPERATION SHALL BE ACCOMPLISHED LOCALLY AND SHALL BE RESIDENT IN EACH CRAC'S
CONTROL PANEL.
THE CRAC UNIT CONTROLLER SHALL OPERATE EACH CRAC IN TEAMWORK MODE WHICH ENABLES ALL THREE UNITS TO TURN ON AND OFF BASED ON HEAT LOAD AND DYNAMICALLY COORDINATES THE FAN SPEED UP/DOWN TO MEET THE COOLING DEMANDS. AS THE HEAT LOAD SHIFTS DOWN, THE CONTROL SHALL MEET THE NEEDS BY SLOWING THE FAN SPEED DOWN AND CASCADING UNITS BY PUTTING
THEM INTO STANDBY MODE.
IF AN OPERATING CRAC GOES INTO ALARM OR FAILS FOR ANY REASON, THE BAS SHALL IMMEDIATELY SHUT DOWN THE FAILED UNIT, CLOSE THE ASSOCIATED ISOLATION DAMPER, AND SPEED THE FANS UP TO FULL SPEED IN THE TWO CRACS THAT ARE STILL IN OPERATION. PROVIDE FLOAT SWITCH IN CRAC UNIT DRAIN PAN TO CUT POWER TO CRAC UNIT IF DRAIN PAN IS ABOUT TO OVERFLOW.
SWITCH TO CUT POWER TO CRAC UNIT AND ALARM THE BAS.
HUMIDITY CONTROL
THE MANUFACTURER TEMPERATURE CONTROLS SHALL CONTROL THE HUMIDIFICATION CYCLE. ON A CALL FOR HUMIDITY, THE CRAC UNITS WILL ENABLE THE HUMIDIFIERS. ON A CALL FOR DEHUMIDIFICATION, THE UNIT TO OPERATE CONTINUOUSLY IN FULL COOLING WHILE IN DEHUMIDIFICATION MODE, WITH THE ELECTRIC REHEAT MAINTAINING SPACE TEMPERATURES
SMOKE DETECTION
WHEN SMOKE IS DETECTED BY THE SMOKE DETECTOR, THE FANS SHALL BE DE-ENERGIZED AND AN ALARM SENT TO THE BAS AND FIRE
ALARM SYSTEM.
FILTER
MONITOR FILTER PRESSURE DROP. ALARM THE BAS WHEN THE PRESSURE DROP EXCEEDS 0.5" WC (ADJ.)
UNDERFLOOR WATER SENSORS
24 VAC POWERED SOLID STATE SINGLE POLE – DOUBLE THROW CONTACTS THAT CLOSES UPON THE SENSOR’S DETECTION OF WATER AT THE BOTTOM OF PAN, FLOOR ETC. SENSOR DESIGNED TO BE PLACED AT THE BOTTOM OF THE PAN, FLOOR ETC. WHERE IT WILL DETECT MOISTURE. SENSOR DESIGN SHALL INCORPORATE WATER SENSOR ARRAY INSIDE A HYDROPHILIC PAD DESIGNED TO ABSORB AND ALARM WITH ONLY A SMALL AMOUNT OF WATER. CONTACT RATING 4A AT 24 VAC MAXIMUM AND 100 MA AT 5 VDC MINIMUM.
MISCELLANEOUS
BAS TO PROVIDE A DRY CONTACT TO MONITOR THE EPO SWITCH POSITION THAT SHALL SHUT DOWN THE CRAC UNITS WHEN IT IS
ACTIVATED.
RACK-T SPC-HH
TOP
(TYP 4 AT RACKS)
UF-WS (TYP 8)
S U
P P
L Y
A
IR
S T
A R
T E
R
ELEC - HC
CRAC-SS
DP-FLT
EHC-SS
DX
FLTR-CRAC-PD
D P
R S
R L
CONDENSING
UNIT
S D
SMOKE DETECTOR
FURNISHED BY UNIT
MANUFACTURER AND
INSTALLED BY DIV. 26
CRAC-ALM
DP-WS
CU-SS
DATA CENTER - CONTROLS DIAGRAM
R E
T U
R N
A
IR
CRAC UNIT
S U
P P
L Y
A
IR
S T
A R
T E
R
ELEC - HC
CRAC-SS
DP-FLT
EHC-SS
DX
FLTR-CRAC-PD
D P
R S
R L
CONDENSING
UNIT
S D
CRAC-ALM
DP-WS
CU-SS
R E
T U
R N
A
IR
CRAC UNIT
S U
P P
L Y
A
IR
S T
A R
T E
R
ELEC - HC
CRAC-SS
DP-FLT
EHC-SS
DX
FLTR-CRAC-PD
D P
R S
R L
CONDENSING
UNIT
S D
CRAC-ALM
DP-WS
CU-SS
R E
T U
R N
A
IR
CRAC UNIT
RACK TEMP
SENSORS AT (3)
LOCATIONS
MIDDLE
BOTTOM
RACK SENSORS
PROVIDED BY DIV. 23
SMOKE DETECTOR
FURNISHED BY UNIT
MANUFACTURER AND
INSTALLED BY DIV. 26
SMOKE DETECTOR
FURNISHED BY UNIT
MANUFACTURER AND
INSTALLED BY DIV. 26
EA
EXHAUST FAN
EF-X-S
EF-X-DP
EF-X-SS
EF-X-D
EXHAUST FAN (EF-X) SEQUENCE OF OPERATION
SYSTEM DESCRIPTION
THE SYSTEM CONSISTS OF A CONSTANT VOLUME EXHAUST FAN AND AN SMOKE
DAMPER (SEE DAMPER SOO).
EXHAUST FAN
START/STOP: UPON RECEIVING A SIGNAL TO START, AFTER A TIME DELAY TO
ALLOW ALL THE ISOLATION, FIRE/SMOKE AND SMOKE DAMPERS TO OPEN, THE
CLEAN AGENT SYSTEM SHALL START THE SUPPLY FAN.
THE FAN SHALL RUN CONTINUOUSLY.
INSTALL A CURRENT STATUS SWITCH TO PROVE SUPPLY FAN OPERATION. SEND
AN ALARM TO THE OPERATOR'S WORKSTATION UPON FAN FAILURE.
SMOKE DAMPER
PRIOR TO ENABLING EXHAUST FAN, SMOKE DAMPER SHALL OPEN, ONCE PROVEN
OPEN, FAN SHALL BE ENABLED.
WHEN FAN IS DISABLED, AFTER A TIME DELAY TO ALLOW FOR FAN TO RAMP
DOWN, SMOKE DAMPER SHALL CLOSE.
NO
EXHAUST FAN (EF-X) CONTROLS DIAGRAM
EF-X-PS
PS
SMOKE PARTITION
SMOKE DAMPER (N.O.)
PRESSURE SWITCH HIGH TO SHUT
DOWN FAN UPON REACHING HIGH
PRESSURE SETPOINT
DAMPER POSITION
FEEDBACK TO BAS
2 POSITION
BINARY POINT
120V
ELECTRICAL
POWER
TO CLEAN AGENT
SYSTEM
AIRFLOW
AIR
DUCT
SD
AD
DUCT TRANSITION
AS REQUIRED
PSH
ZS M
DAMPER REQUIREMENTS:
A MOTORIZED DAMPER SHALL BE PROVIDED WITH RELAY IF NECESSARY. INTERLINK DAMPER TO A
CONTROL MODULE WITHIN THE CLEAN AGENT PANEL. CLOSE DAMPER UPON THE CLEAN AGENT
SYSTEM ACTIVATION. DAMPER IS NORMALLY OPEN. DISPLAY DAMPER ON FRONT-END GRAPHIC AND
PROVIDE TRENDS.
SMOKE DAMPER (SD) - SEQUENCE OF OPERATIONS
SMOKE DAMPER (SD) - CONTROLS DIAGRAM
Project Number
Building Number
Drawing Number
DrawnCheckedIssue Date
Location
Project TitlePhaseDrawing Title
Approved: Project Director
ARCHITECT OF RECORDCONSULTANT
Revisions: Date:
U.S. Department of Veterans Affairs
Construction and Facilities Management
8718 Botts Lane Phone: (210) 816-4784
San Antonio, Texas 78217 Fax: (210) 881-6808 www.hfscompany.com jbianco@hfscompany.com
FULLY SPRINKLERED
569A4-22-700100% CONSTRUCTION
DOCUMENTS
LEXINGTON-COOPER EHRM
INFRASTRUCTURE DESIGN
1101 VETERANS DRIVE
LEXINGTON, KY 40502
21 3 4 5 6 7 8 9 10
21 3 4 5 6 7 8 9 10
B
A
C
D
E
F
B
A
C
D
E
F
St. Louis
6 South Old Orchard St. Louis, MO 63119 t: +1 800.404.7677 e: hello@introba.com www.introba.com
1 & 1A
M-701
CL
MECHANICAL CONTROLS
SS5/16/23
EXISTING BAS REQUIREMENT:
1. MODIFICATIONS TO THE OWNER'S EXISTING METASYS CONTROLS
SYSTEM AND OPERATOR'S GRAPHIC INTERFACE SHALL BE
INCLUDED AS PART OF THIS CONTRACT. THE REMOVAL OR
MODIFYING OF ANY EXISTING EQUIPMENT WITHIN THE SCOPE OF
THIS PROJECT SHALL BE ADJUSTED. SEE SPECIFICATION 230923
FOR FURTHER CONTROLS SYSTEM INFORMATION.
GENERAL BAS CONTROL NOTE
ELECTRICAL PANEL REQUIREMENT:
1. BAS TO MONITOR ELECTRIC METERS FOR EACH PANELBOARD
SERVING THE TR ROOMS. TOTAL KILOWATT HOURS OF EACH PANEL
TO BE SENT TO THE BAS FOR MONITORING AND REPORTING
PURPOSES.
2. METERS SHALL COMMUNICATE TO EXISTING BUILDING TRIDIUM
SYSTEM. PROVIDE THE REQUIRED COMMUNICATION DEVICES AND
PROGRAMING TO COMMUNICATE DATA TO THE TRIDIUM SYSTEM.
3. PROVIDE A BACNET NETWORK ALLOWING COMMUNICATION FROM
THE METERS’ DATA HEADS TO THE SITE DATA AGGREGATION
DEVICE.
4. PROVIDE DATA HEADS AT EACH METER, CONVERTING ANALOG AND
PULSED INFORMATION TO DIGITAL INFORMATION.
5. THE GRAPHICAL METER SCREEN AT THE BAS SHALL PROVIDE REAL
TIME REPORTING.
6. REFER TO SPEC 251010 FOR ADDITIONAL REQUIREMENTS,
METERING POINTS AND REPORTS.
ELECTRIC METERING NOTE
WATER DETECTOR/ SENSOR REQUIREMENTS:
A DRAIN PAN SHALL BE PROVIDED FOR ALL EXISTING TO REMAIN WET PIPING IN TELECOMMUNICATION ROOMS AND ELECTRICAL ROOMS. PROVIDE A SMALL CONDENSATE PUMP AND WATER DETECTOR SENSOR IN EACH DRAIN PAN
NEAR THE DRAIN OUTLET.
ACTIVATE THE PUMP UPON DETECTION OF WATER.
THE SENSOR SHALL ALARM THE BAS IF STAGNANT WATER OCCURS IN THE PAN.
WATER SENSOR ALARMS AND TRENDS TO BE MONITORED BY THE BAS. SEND AN ALARM TO OPERATOR'S GRAPHIC
INTERFACE WHEN ACTIVATED. RECORD ALARM TRENDS FOR MAINTENANCE REQUIREMENTS.
PROVIDE LOCALIZED AUDIBLE ALARM.
WATER SENSOR CONTROLS - SEQUENCE OF OPERATIONS
DATA CENTER - CONTROL POINTS LIST
CONTROL POINT TAG SYSTEM POINT DESCRIPTION
INPUTS OUTPUTS SOFTWARE ALARM REPORTS
NOTESDI AI DO AO AV BV I
N
T E
G R
A T
E D
H
IG
H \L
O W
L
IM
IT
S A
F E
T Y
M A
IN
T
E N
A N
C E
A B
N O
R M
A L O
N /O
F F
O P
E N
/C L
O S
E
A L A
R M
R U
N T
IM
E
T O
T A
L
IZ
A T
IO
N
T R
E N
D
CRAC-ALM CRAC ALARM ● ● ●
CRAC-SS CRAC START/STOP ● ●
CU-SS CONDENSING UNIT START/STOP ●
DP-FLT DRAIN PAN FLOAT ● ● ● ● ●
DP-WS DRAIN PAN WATER SENSOR ● ●
EHC-SS ELECTRIC HEATING COIL START/STOP ●
FLTR-CRAC-PD CRAC FILTER PRESSURE DROP ● ● ● ●
RACK-T RACK TEMPERATURE ● ● ●
SPC-H SPACE HUMIDITY ● ● ●
SPC-T SPACE TEMPERATURE ● ● ●
UF-WS UNDERFLOOR WATER SENSOR ● ● ●
SPLIT SYSTEM - CONTROL POINTS LIST
CONTROL POINT TAG SYSTEM POINT DESCRIPTION
INPUTS OUTPUTS SOFTWARE ALARM REPORTS
NOTESDI AI DO AO AV BV I
N
T E
G R
A T
E D
H
IG
H \L
O W
L
IM
IT
S A
F E
T Y
M A
IN
T
E N
A N
C E
A B
N O
R M
A L O
N /O
F F
O P
E N
/C L
O
A
R M
R U
N T
IM
E
T O
T A
L
IZ
A T
IO
N
T R
E N
D
SPC-T SPACE TEMPERATURE ● ● ●
WDS-A WATER DETECTOR SENSOR ALARM ● ● ●
EXHAUST FAN (EF-X) POINTS LIST
CONTROL
POINT TAG SYSTEM POINT DESCRIPTION
INPUTS OUTPUTS SOFTWARE ALARM REPORTS
NOTESDI AI DO AO AV BV I
N
T E
G R
A T
E D
H
IG
H \L
O W
L
IM
IT
S A
F E
T Y
M A
IN
T
E N
A N
C E
A B
N O
R M
A L O
N /O
F F
O P
E N
/C L
O
A
R M
R U
N T
IM
E
T O
T A
L
IZ
A T
IO
N
T R
E N
D
EF-X-D EXHAUST AIR DAMPER OPEN/CLOSE ●
EF-X-DP EXHAUST AIR DAMPER POSITION ● ● ● ●
EF-X-PS EXHAUST AIR PRESSURE SENSOR ● ● ●
EF-X-S EXHAUST FAN STATUS ● ● ● ●
EF-X-SS EXHAUST FAN START/STOP ●
1 ESI-001 (PRE-BID #47) 1/8/2024