589A4-20-155-Final Drawings 072121 VOL 2 - 60 Pages.pdf

PDF 8 MB Posted

Attached to
Z2DA--Complete Unfinished Specialty Clinic P/N: 589A4-20-155
Solicitation number
36C25521R0106
Issued by

About this file

This presolicitation notice announces an upcoming solicitation for a construction project to renovate approximately 12,780 square feet of unfinished space at the VA Harry S. Truman Memorial Hospital in Columbia, Missouri into a state-of-the-art outpatient specialty clinic and pharmacy. The scope of work includes demolishing and building new interior walls, ceilings, flooring, electrical and mechanical systems, and finishes on the third floor and basement level. The project value is estimated between $2-5 million. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and use the Lowest Price Technically Acceptable source selection process. The North American Industry Classification Code is 236220 and the small business size standard is $39.5 million. Interested parties should monitor the SAM website for the solicitation release on or around July 16th, with proposals due on August 18th. An organized site visit will be scheduled upon solicitation issuance.

View the file

Other files

File Type Posted
36C25521R0106 0003 Amendment 3.pdf PDF
QH101 - BASEMENT EQUIPMENT PLAN.pdf PDF
Amendment 3 Narrative.docx DOCX document
QH102 - THIRD FLOOR EQUIPMENT PLAN.pdf PDF
36C25521R0106 0002 Amendment 2.pdf PDF
Amendment 2-ATTENDANCE ROSTER- Complete Unfinished Specialty Clinic_08032021.xlsx XLSX spreadsheet
090600 Schedule for Finishes_amendment 1.pdf PDF
066060 Plastic Fabrications amendment 1.pdf PDF
077100 Roof Specialties_amendment 1.pdf PDF
072200 Roof and Deck Insulation amendment 1.pdf PDF
077200 Roof Accessories_amendment 1.pdf PDF
083459 Vaults and Day Gates_amendment 1.pdf PDF
111736 Package Transfer Units_amendment 1.pdf PDF
076000 Flashing and Sheet Metal_amendment 1.pdf PDF
Revised Columbia USC Amendment 1 - Combined Drawings.pdf PDF
075423 Thermoplastic Polyolefin -TPO- Roofing_amendment 1.pdf PDF
36C25521R0106 0001- Amendment 1.pdf PDF
072727 Fluid-Applied Membrane Air Barrier- Vapor amendment 1.pdf PDF
224000 Plumbing Fixtures amendment 1.pdf PDF
096723_20 Resinous with Vinyl Chip Broadcast_amendment 1.pdf PDF
149200 Pneumatic Tube System amendment 1.pdf PDF
Complete Unfinished Specialty Clinics Specifications VOL 1- 486 pages.pdf PDF
589A4-20-155-Final Drawings 072121 VOL 1 - 47 pages.pdf PDF
Complete Unfinished Specialty Clinics-589A4-20-155 Specifications VOL 2-742 pages.pdf PDF
36C25521R0106.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HVAC GENERAL NOTES

DUCTWORK SYMBOLSMECHANICAL SYMBOLS

PIPING SYMBOLS

GENERAL DEMOLITION NOTES MECHANICAL GENERAL NOTES

DRAWING SYMBOLS

RATED WALL LEGEND

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A

FURRED CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR

INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES,

TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE

FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS.

COORDINATE LOCATION WITH MECHANICAL INSTALLATION AND DEMONSTRATE

ACCESS TO EQUIPMENT SERVED.

4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM,

TERMINAL UNITS, FILTERS, COILS, ETC. LOSS FOR FILTERS SHALL BE FOR FILTERS AT

50% LOADING.

5. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.

6. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO

PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF

CEILING DIFFUSERS, REGISTERS, AND GRILLES.

LIMIT OF DEMOLITION

SUPPLY DIFFUSER/GRILLE (CEILING, SQUARE 4-WAY)

SEE NOTES 1, 2, 3.

CONNECT NEW DUCT TO EXISTING DUCT

D

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

R

FC

10"x8"SA

FLEXIBLE CONNECTION (FC) - EQUIPMENT,

VIBRATION, OR SEISMIC

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS. VANE SYMBOL ARE NOT

SHOWN ON PLANS)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

DUCT LABELING NOTE:

• INSIDE DIMENSIONS: WIDTH x DEPTH

• SA = SUPPLY AIR

• RA = RETURN AIR

• OA = OUTSIDE AIR SUPPLY

• EA = EXHAUST AIR

EXISTING DUCT TO REMAIN

MANUAL VOLUME DAMPER

EXISTING DUCT TO BE REMOVED

10"x8"SA(EX)

10"x8"

NEW DUCT

EXHAUST GRILLE

SEE NOTES 1, 2, 3.

SD-14

270 CFM

SUPPLY DUCT UP ("X")

EXHAUST DUCT UP ("Y")

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING REGISTER OR

GRILLE BELOW DUCT

EXHAUST OR RETURN BOTTOM

REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN REGISTER OR

TOP GRILLE (WALL TYPE)

RETURN DUCT UP ("/")

SUPPLY DIFFUSER WITH BLANK-OFF (CEILING,

SQUARE 3-WAY) SEE NOTES 1, 2, 3.

SUPPLY DUCT DOWN ("X")

EXHAUST DUCT DOWN ("Y")

RETURN DUCT DOWN ("/")

(ROUND) (RECT.)

EG-21

80 CFM

NOTES:

1. AIR TERMINAL LABEL:

AIR TERMINAL TYPE

BALANCED FLOW RATE

2. AIR TERMINAL TYPE:

Sx = SUPPLY, Rx = RETURN, Ex = EXHAUST xD = DIFFUSER xG = GRILLE xR = REGISTER (WITH INTEGRATED VOLUME DAMPER)

(EX. SG-14 = SUPPLY GRILLE)

3. REFER TO AIR DEVICE SCHEDULE FOR DETAILS.

SD-14

270 CFM

RETURN GRILLE (CEILING)

SEE NOTES 1, 2, 3.

RG-24

270 CFM

TERMINAL UNIT WITHOUT REHEAT COIL

EXISTING TEMINAL UNIT - DEMOLITION

TERMINAL UNIT WITH REHEAT COIL

NOTE 2 (TYP)

AIR VOLUME CONTROL VALVE

(ARROW INDICATED DIRECTION OF FLOW)

NOTE 1 (TYP)

NOTES:

1. DEVICE CONTROL/CONNECTION PANEL.

2. MANUFACTURER'S RECOMMENDED MAINTENANCE/OPERATIONAL CLEARANCE.

KEEP THIS AREA CLEAR AND ACCESSIBLE FOR COIL AND PANEL MAINTENANCE AND

REPAIR.

3. HATCHED AREA INDICATES NEC REQIRED 36" WORKING SPACE - MUST BE KEPT

CLEAR.

4. DISPERSION TUBE WITHIN DUCT.

5. AIR VOLUME CONTROL VALVE.

6. REHEAT COIL WITH DUCT TRANSITION.

DUCT MOUNTED STEAM HUMIDIFIER

NOTE 4

NOTE 3

AIR VOLUME CONTROL VALVE (SUPPLY)

WITH ASSOCIATED REHEAT COIL

NOTE 6

NOTE 5

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE CONNECTION

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN)

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

PIPE UP

PIPE DOWN

NEW PIPE

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN (?=SIZE/TYPE, EX=EXISTING)

CHILLED WATER SUPPLYCHS

CHILLED WATER RETURNCHR

?" (EX)

DRAIN LINED

HOT WATER HEATING SUPPLYHHWS

HOT WATER HEATING RETURNHHWR

1. ALL PIPING AND DUCTWORK IS SHOWN SCHEMATICALLY BASED ON EXISTING PLANS.

CONTRACTORS SHALL BE RESPONSIBLE FOR COORDINATION OF VERIFYING ROUTES

OF ALL EXISTING CONDITIONS AND EXISTING UTILITIES PRIOR TO BIDDING AND

STARTING OF WORK. IF CONDITIONS DIFFER GREATLY CONTACT ENGINEER.

2. CONDUCT A PRECONSTRUCTION AIR AND WATER FLOW TEST OF EXISTING SYSTEMS

AND MAINS SERVING EACH AREA AND FLOOR BEFORE STARTING ANY DEMOLITION

WORK. SUBMIT REPORT OF FLOWS AND FINDINGS TO ENGINEER AND OWNER.

3. COORDINATE SCHEDULE OF WORK WITH OWNER AND PROVIDE SUFFICIENT NOTICE

BEFORE ANY SHUTDOWNS, TO MINIMIZE DISRUPTIONS TO ANY CONCURRENT

OPERATIONS.

4. COMPLY WITH SITE SAFETY PROCEDURES OF OWNER, GENERAL CONTRACTOR, AND

OSHA.

5. DEMOLISH MATERIALS, EQUIPMENT, AND ASSOCIATED SYSTEMS AS SHOWN WITHIN

SCOPE OF WORK AREA AS DESIGNATED/NOTED. DEMOLISH ALL BRANCH DUCT AND

PIPE, SUPPORTS, ACCESSORIES, EQUIPMENT, TERMINAL DEVICES, CONTROLS,

WIRING, CONDUITS, AND ASSOCIATED ITEMS BACK TO RESPECTIVE MAINS. THEN

CAP, SEAL, REPAIR, REINSULATE MAIN CONNECTIONS AS REQUIRED. NOTHING

SHALL BE ABANDONED IN PLACE UNLESS NOTED OTHERWISE. REMOVE ALL

DEMOLISHED ITEMS FROM SITE AND DISPOSE PROPERLY PER LOCAL LAWS.

6. HATCHED OR GRAYED OUT AREAS ARE NOT WITHIN CONTRACT BOUNDARY.

COORDINATE WITH OWNER IF SUCH AREAS REQUIRE ACCESS TO COMPLETE SCOPE

OF WORK, SUCH AS REMOVING A BRANCH MAIN BACK TO LARGER MAIN TO

ELIMINATE DEAD LEGS.

7. INFILL AND REPAIR TO MATCH EXISTING CONDITIONS ALL WALL, FLOOR, AND CEILING

PENETRATIONS RESULTING FROM DEMOLISHED ITEMS, AND INSTALLATION OF NEW

SYSTEMS. COORDINATE WITH GENERAL CONTRACTOR FOR COVERAGE OF THIS

SCOPE.

8. SAVE NOTED ITEMS FOR REUSE OR OWNERS SALVAGE. STORE NOTED ITEMS AND

OTHER ITEMS IDENTIFIED BY OWNER IN OWNER’S DESIGNATED STORAGE AREA.

9. PROTECT EXISTING TO REMAIN EQUIPMENT, MATERIALS, AND SURROUND SITE FROM

DAMAGE DURING DEMOLITION. REPAIRS AND REPLACEMENT OF EXISTING TO

REMAIN CONDITIONS SHALL BE THE CONTRACTOR’S RESPONSIBILITY.

10. REFER TO SPECIFICATION MANUAL FOR FURTHER DETAILS.

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE DEPARTMENT OF

VETERANS AFFAIRS (VA) STANDARDS.

2. ALL WORK SHALL BE IN CONFORMANCE WITH THE INTERNATIONAL MECHANICAL CODE -

LATEST EDITION ADOPTED BY THE VA. THE VA SERVES AS AUTHORITY HAVING JURISDICTION.

3. THESE DOCUMENTS ARE INTENDED TO COMPLY WITH APPLICABLE CODES. WHERE

DISCREPANCIES OCCUR, NOTIFY THE ENGINEER/ARCHITECT IN WRITING FOR

INTERPRETATION. CORRECT ANY INSTALLATION THAT FAILS TO COMPLY WITH THE CODES

AND STANDARDS AT NO ADDITIONAL COST TO THE OWNER.

CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY INCLUDING ALL LABOR, MATERIALS,

PERMITS, TAXES, FEES, INSPECTIONS, HARDWARE, AND COST FOR INSTALLATION FOR A

COMPLETE AND OPERATIONAL SYSTEM.

4. ALL MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE NEW, COMPLETE WITH

MANUFACTURER’S GUARANTEE OR WARRANTY AND SHALL BE LISTED BY A NATIONALLY

RECOGNIZED TESTING LABORATORY.

5. PENETRATIONS THROUGH FIRE RATED WALLS BY DIVISION 23 CONTRACTOR SHALL BE

SEALED WITH APPROPRIATE FIRE PROOFING MATERIAL TO RESTORE FIRE RATING. REFER TO

ARCHITECTURAL DRAWINGS FOR FIRE RATED WALLS.

6. CONTRACTOR SHALL KEEP THE WORK AREA CLEAN OF ALL DEBRIS ON A DAILY BASIS. ALL

NEW MATERIALS AWAITING INSTALLATION SHALL BE KEPT IN AREAS DESIGNATED BY THE

OWNER.

7. DRAWINGS SHALL NOT BE SCALED TO OBTAIN DIMENSIONS. REFER TO DIMENSIONED

ARCHITECTURAL FLOOR PLANS. IF THE DIMENSIONS CANNOT BE DETERMINED BY THE

INFORMATION GIVEN, CONTRACTOR SHALL CONTACT THE ENGINEER FOR ADDITIONAL

INFORMATION.

8. PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY FOR THE PURPOSE OF

DETERMINING IF THE WORK OF THE CONTRACTOR IS PROCEEDING IN ACCORDANCE WITH

THE CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION SHOULD NOT BE

CONSTRUED AS EXHAUSTIVE OR CONTINUOUS TO CHECK THE QUALITY OR QUANTITY OF

THE WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARD THE OWNER AGAINST DEFECTS

OR DEFICIENCIES IN THE WORK OF THE CONTRACTOR.

9. INFORMATION CONTAINED ON THE MECHANICAL DRAWINGS IS IN ITSELF INCOMPLETE AND

VOID UNLESS USED IN CONJUNCTION WITH ALL OTHER DISCIPLINE DRAWINGS, THE

SPECIFICATIONS, TRADE PRACTICES, OR APPLICABLE STANDARDS, CODES, ETC., AND SHALL

BE CONSIDERED THE CONTRACT DOCUMENTS AND WITH ALL THEREIN BY REFERENCE,

WHICH THE CONTRACTOR CERTIFIES KNOWLEDGE OF BY SIGNING THE CONTRACT.

10. CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY, UNRELIEVED BY REVIEW OF SHOP

DRAWINGS OR PERIODIC OBSERVATION OF CONSTRUCTION, FOR COMPLIANCE WITH THE

CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE CONFIRMED AND CORRELATED ON THE

JOB SITE AND BETWEEN INDIVIDUAL DRAWINGS OR SETS OF DRAWINGS FOR FABRICATION

PROCESSES AND CONSTRUCTION TECHNIQUES (INCLUDING EXCAVATION, SHORING,

SCAFFOLDING, BRACING, ERECTION, FORM WORK, ETC.), FOR COORDINATION OF THE

VARIOUS TRADES, AND FOR SAFE CONDITIONS ON THE JOB SITE. VARIATIONS IN FIELD

CONDITIONS RELATIVE TO THE CONTRACT DOCUMENTS SHALL BE REPORTED TO THE

ENGINEER AS SOON AS THEY ARE FOUND. WORK SHALL NOT PROGRESS UNTIL WRITTEN

PERMISSION FROM THE ENGINEER IS OBTAINED.

11. PROVIDE VOLUME BALANCING DAMPERS FOR ALL SUPPLY DIFFUSERS, RETURN AND

EXHAUST GRILLES AND AT EACH INDIVIDUAL BRANCH VENTILATION SUPPLY, RETURN AND

RELIEF DUCT.

12. PLACE DIFFUSERS AS CLOSE TO PLAN LOCATION AS POSSIBLE WITHOUT INTERFERING WITH

OTHER CEILING DEVICES.

13. ALL NEW EQUIPMENT AND ACCESSORIES SHALL BE INSTALLED SO AS TO BE EASILY

ACCESSIBLE. ALL CLEARANCES FOR EQUIPMENT PER MANUFACTURERS GUIDELINES AND

CODE COMPLIANCE SHALL BE REQUIRED.

14. PROVIDE ACCESS PANELS FOR VALVES, ETC. THAT ARE LOCATED IN CONCEALED AREAS.

COORDINATE WITH GENERAL CONTRACTOR FOR EXACT LOCATION AND WITH

ARCHITECTURAL PLANS FOR FINISHES.

15. ALL COMPONENTS OF SYSTEMS SHALL BE PROVIDED FOR A COMPLETELY OPERATIONAL,

UNDERSTANDABLE, SAFE, AND CLEAN SYSTEM; INCLUDING BUT NOT LIMITED TO

EXTRANEOUS FIXTURE TRIM AS SPECIFIED, SERVICE AND COMMISSIONING INTO OPERATION,

LABELS, TESTING AND CLEANING, FIRE AND LIFE SAFETY REQUIREMENTS, AND CONSIDERING

THE REQUESTS OF OWNERS PERSONNEL.

16. ELECTRICAL PANELS SHOWN FOR REFERENCE. DO NOT ROUTE ANY COMPONENTS ABOVE

OR IN FRONT OF ELECTRICAL EQUIPMENT. MAINTAIN CODE REQUIRED CLEARANCES.

17. ALL DUCTWORK SIZES SHOWN ON DRAWINGS ARE CLEAR INTERIOR DIMENSIONS.

18. THERMOSTATS SHALL BE MOUNTED 4'-0" ABOVE FINISHED FLOOR AND COORDINATED WITH

ARCHITECTURAL PLANS. IF THERMOSTATS ARE INSTALLED ADJACENT TO A LIGHT SWITCH

ALIGN MOUNTING HEIGHT WITH LIGHT SWITCH.

19. PROVIDE CONCEALING FLANGES AT ALL VISIBLE DUCT PENETRATIONS THROUGH WALLS.

20. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL INTERCONNECTING CONTROL WIRING.

21. PLANS ARE DIAGRAMMATIC AND INTENDED TO CONVEY SCOPE OF WORK AND GENERAL

LOCATIONS OF EQUIPMENT, MATERIALS, ETC. CONTRACTOR SHALL FIELD VERIFY ALL

DIMENSIONS AND LAYOUT OWN WORK ACCORDINGLY AND IS RESPONSIBLE FOR

DETERMINING EXACT LOCATIONS FOR EQUIPMENT, MATERIALS, ETC.

22. THE EXISTING MECHANICAL SYSTEMS SHALL BE MODIFIED PER SPECIFIED PLANS AND

SPECIFICATIONS. FIELD VERIFY EXISTING MECHANICAL SYSTEMS REQUIREMENTS PRIOR TO

BIDDING.

23. COORDINATE SCOPE OF WORK WITH THE WORK OF OTHER TRADES PRIOR TO

INSTALLATION. ISSUES DUE TO LACK OF COORDINATION EFFORT WILL BE CORRECTED AT NO

ADDITIONAL COST TO THE OWNER.

COORDINATE LOCATION OF SYSTEM COMPONENTS WITHIN LIMITS OF STRUCTURE AND

OTHER ENGINEERED SYSTEMS. ROUTE ALL MECHANICAL SYSTEMS IN CONCEALED SPACES

AND INSTALL COMPONENTS AS HIGH AS POSSIBLE. OFFSET SYSTEMS ROUTING AS

REQUIRED, PROVIDING REQUIRED MATERIALS. PIPE SHALL NOT BE ROUTED IN EXTERIOR

WALLS UNLESS NOTED. COORDINATE ROUTING OF MECHANICAL SYSTEMS TO MAINTAIN

REQUIRED SERVICE CLEARANCES AROUND ANY EQUIPMENT AND ELECTRICAL ITEMS.

24. INFILL AND REPAIR TO MATCH EXISTING CONDITIONS ALL WALL, FLOOR, AND CEILING

PENETRATIONS RESULTING FROM DEMOLISHED ITEMS, AND INSTALLATION OF NEW

SYSTEMS. COORDINATE WITH GENERAL CONTRACTOR FOR COVERAGE OF THIS SCOPE.

25. ALL ELEMENTS OF CONSTRUCTION SHALL BE INSTALLED BY SKILLED TRADESMEN OF THERE

PARTICULAR TRADE, AND INSTALLED IN A NEAT WORKMANLIKE MANNER KEEPING WITH THE

HIGHEST STANDARDS OF THE TRADE.

26. COORDINATE SCOPE OF WORK WITH PROJECT SCHEDULES AGREED UPON BY OWNER AND

ALL CONTRACTORS.

27. REFER TO SPECIFICATION MANUAL FOR FURTHER DETAILS ABOUT DESIGN STANDARDS,

PRODUCTS, DRAWINGS, SUBMITTALS, DOCUMENTATION, COORDINATION, AND INSTALLATION.

28. PROVIDE DIRECT-DIGITAL CONTROL SYSTEM(S) AS INDICATED ON THE PROJECT

DOCUMENTS, POINT LIST, INTEROPERABILITY TABLES, DRAWINGS AND AS DESCRIBED IN

THESE SPECIFICATIONS. INCLUDE A COMPLETE AND WORKING DIRECT-DIGITAL CONTROL

SYSTEM. PROVIDE ALL ENGINEERING, PROGRAMMING, CONFIGURATION/SETUP HARDWARE

AND SOFTWARE, OPEN LICENSES, CONTROLS AND INSTALLATION MATERIALS, INSTALLATION

LABOR, COMMISSIONING AND START-UP, TRAINING, FINAL PROJECT DOCUMENTATION AND

WARRANTY. COORDINATE WITH VA TECHNOLOGY STAFF FOR INTEGRATION OF REQUIRED

SITE NETWORK SECURITY INTEGRATION.

29. CONTROLS SHALL BE AN EXTENSION OF THE EXISTING OWNER PROVIDED TEMPERATURE

CONTROL SYSTEM. PROVIDE A COMPLETE AND FUNCTIONAL EXPANDED CONTROL SYSTEM

TO ADD ON TO THE EXISTING SYSTEM TO CONTROL ALL EQUIPMENT PROVIDED UNDER THIS

CONTRACT. PROVIDE COMPONENTS AND PROGRAMMING THAT MATCH EXISTING SYSTEM

AND ARE COMPATIBLE WITH THE EXISTING SYSTEM, INCLUDING BUT NOT LIMITED TO

CONTROL BOARDS, THERMOSTATS, WIRING, AND ACCESSORIES. FIELD VERIFY EXISTING

PROGRAMMING FOR REUSE AND/OR UPDATING. ALL NEW BUILDING CONTROLLERS SHALL

BE NATIVE BACNET. ALL NEW BACNET CONTROLLERS, DEVICES AND COMPONENTS SHALL

BE LISTED BY BACNET TESTING LABORATORIES.

30. SEQUENCES INCLUDED IN THE SUBMITTAL MUST REFLECT WHAT IS ACTUALLY GOING TO BE

PROGRAMMED, INCLUDING SUGGESTED CHANGES TO THE PLANS. COPIED SEQUENCES

FROM THE PLANS WILL NOT BE ACCEPTED. INCLUDE SYSTEM GRAPHICS INDICATING

MONITORED SYSTEMS, DATA (CONNECTED AND CALCULATED) POINT ADDRESSES,

OPERATOR NOTATIONS, NETWORK CONFIGURATION, ETC.

31. ALL SOFTWARE WORK INVOLVING THIS INTEGRATION PROCESS IS THE RESPONSIBILITY OF

THE TEMPERATURE CONTROL CONTRACTOR AND MUST BE COMPLETED BY A TECHNICIAN

CERTIFIED WITH THE EXISTING SYSTEM. THE TCC MUST SUBMIT A COPY OF THE

CERTIFICATION DOCUMENTATION FOR THE SYSTEM PROGRAMMER PRIOR TO COMPLETING

ANY WORK IN ORDER TO INSURE THE INTEGRITY OF THE SYSTEM.

32. THE TCC IS ALSO RESPONSIBLE FOR PROVIDING AND INSTALLING ALL ROUTERS, SWITCHES, JACE’S, SOFTWARE LICENSES, DRIVERS, ETC, AS NEEDED FOR A COMPLETE INSTALLATION

INCLUDING FULL INTEGRATION. THE TCC IS RESPONSIBLE FOR ALL GRAPHICS GENERATION

AND POINT MAPPING OF POINTS TO BE ADDED IN THE PROJECT. THE TCC SHALL UTILIZE THE

EXISTING DATABASE AS AN EXAMPLE FOR ALL PROGRAMMING, GRAPHICS, ANIMATIONS, AND

POINT MAPPING FOR WORK DONE ON THE PROJECT IN ORDER TO MAINTAIN CONSISTENCY

WITHIN THE BAS.

H4

H7

A

26-SF 3

26-TU-I-I

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

SUPPLY FAN NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (SUPPLY FAN)

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT SHOWN)

SERVED BY AIR HANDLER UNIT NO. 1

DRAWING NUMBER WHERE DRAWN

BUILDING NO. WHERE EQUIPMENT IS LOCATED

WALL

2 HOUR FIRE/SMOKE BARRIER

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:2

A

M

AW DAW

589A4-20-155

M-001

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

MECHANICAL LEGEND, SCHEDULES AND

ABBREVIATIONS

100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

XFER TRANSFER

VHA VETERANS HEALTH ADMINISTRATION

UTIL UTILITY

UPC UNIVERSAL PLUMBING CODE

UL UNDERWRITER'S LABORATORY

TEMP TEMPERATURE

TYP TYPICAL

SPEC SPECIFICATION

SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL...

SI INTERNATIONAL SYSTEM OF UNITS

SHT SHEET

SEN SENSIBLE HEAT

SCI SPINAL CODE INJURY

SA SUPPLY AIR

RM ROOM

RO REVERSE OSMOSIS

RDS ROOM DATA SHEETS

REQD REQUIRED

RA RETURN AIR

R/E RETURN OR EXHAUST

PSS PRIMARY SECONDARY SYSTEM

PGW PROPYLENE GLYCOL-WATER SOLUTION

OR OPERATING ROOM

OD OUTSIDE DIAMETER

OC ON CENTER

OA OUTSIDE AIR

NTS NOT TO SCALE

NSPC NATIONAL STANDARD PLUMBING CODE

NOM NOMINAL

NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION

NO NORMALLY OPEN

NIC NOT IN CONTRACT

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEC NATIONAL ELECTRICAL CODE

NC NORMALLY CLOSED

NA NOT APPLICABLE (ALSO N/A)

MRI MAGNETIC RESONANCE IMAGING

MER MECHANICAL EQUIPMENT ROOM

MIN MINIMUM

MAX MAXIMUM

LPG LIQUID PROPANE GAS

IPC INTERNATIONAL PLUMBING CODE

ID INSIDE DIAMETER

ICU INTENSIVE CARE UNIT

I/O INPUT/OUTPUT

HAC HOUSEKEEPING AIDE’S CLOSET

EX EXISTING (OR EXIST)

EL ELEVATION

ESMT EASEMENT

ETO ETHYLENE OXIDE

EA EXHAUST AIR

DWG DRAWING

CO2 CARBON DIOXIDE

CENT CENTRIFUGAL

BMT BONE MARROW TRANSPLANT

BLDG BUILDING

ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

ASHRAE

AMERICAN SOCIETY OF HEATING REFRIGERATION AIR CONDITIONING

ENGINEERS

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AMB AMBIENT

AFG ABOVE FINISHED GRADE

AFF ABOVE FINISHED FLOOR

A/E ARCHITECTS AND ENGINEERS

GENERAL ABBREVIATIONS

YR YEAR

WPD WATER SIDE PRESSURE DROP

WG WATER GAGE

WB WET-BULB (TEMPERATURE)

W WATTS

TSP TOTAL STATIC PRESSURE

TD TEMPERATURE DIFFERENCE

SQ M SQUARE METER

SQ FT SQUARE FOOT (FEET)

SP GR SPECIFIC GRAVITY

SCFM STANDARD CUBIC FEET PER MINUTE

SAT SUPPLY AIR TEMPERATURE

SI SQUARE INCHES

RPM REVOLUTIONS PER MINUTE

RLA RUN LOAD AMPERE

RAT RETURN AIR TEMPERATURE

RAF RADIO-FREQUENCY

PSIG POUNDS PER SQUARE INCH-GAGE

PSIA POUNDS PER SQUARE INCH ATMOSPHERE

PSI POUNDS PER SQUARE INCH

PPM PARTS PER MILLION

PA PASCAL

NPLV NON-STANDARD PART LOAD VALUE

Nm NEWTON-METER

NC NOISE CRITERIA

MTD MEAN TEMPERATURE DIFFERENCE

M/S METERS PER SECOND

MM MILLIMETER

MIN MINIMUM

MHP MOTOR HORSEPOWER

MERV MINIMUM EFFICIENCY REPORTING VALUE

MCA MULTICHANNEL ANALYZER

MCA MAXIMUM CURRENT AMPACITY

MBH 1000 BTUH

MAX MAXIMUM

M METER

LWT LEAVING WATER TEMPERATURE

LVG LEAVING

LH LATENT HEAT

LGT LEAVING GLYCOL TEMPERATURE

LF LINEAR FOOT (FEET)

LBS/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

L/S LITERS PER SECOND

L/M LITERS PER MINUTE

L/H LITERS PER HOUR

L LITER

kWH KILOWATT HOUR kW KILOWATT kPA KILO PASCAL

KG/HR KILOGRAM PER HOUR

KG KILOGRAM

IPLV INTEGRATED PART LOAD VALUE

IN-LB INCH-POUND

IN WG INCH WATER GAUGE

IN HG INCHES OF MERCURY

IN INCHES

HZ HERTZ

HP HORSEPOWER

GPM GALLONS PER MINUTE

GPH GALLONS PER HOUR

GPD GALLONS PER DAY

GAL GALLONS

GA GAUGE

FT-WC FEET OF WATER COLUMN

FT-LB FOOT-POUND

FT FEET

FPS FEET PER SECOND

FPM FEET PER MINUTE

F FAHRENHEIT

EWT ENTERING WATER TEMPERATURE

ESP EXTERNAL STATIC PRESSURE

ENT ENTERING

EGT ENTERING GLYCOL TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EAT ENTERING AIR TEMPERATURE

DP DEWPOINT

DIA DIAMETER

DEG DEGREE

dB DECIBEL

DB DRY-BULB TEMPERATURE

COP COEFFICIENT OF PERFORMANCE

CM/S CENTIMETER PER SECOND

CM CUBIC METER

CFT CUBIC FEET

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

C CENTIGRADE (CELSIUS)

BTUH BRITISH THERMAL UNIT PER HOUR

BTU BRITISH THERMAL UNIT

BHP BRAKE HORSE POWER

APD AIR SIDE PRESSURE DROP

UNITS OF MEASURE

Revisions: Date:

P

RO

FESSIONAL ENGIN

EE

R

ST

ATE OF MISSOURIArlo G.

Wieczorek

NUMBER

PE-2018026248

7/20/2021

SCOPE OF WORK

KEYED NOTES:

98 10 11

D

C

B

A

1 1

1 1 1

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:2

A

M

AW DAW

589A4-20-155

MD101

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

BASEMENT PLAN - HVAC DEMOLITION 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

BASEMENT PLAN - HVAC DEMOLITION

1 DEMOLISH EXISTING TERMINAL UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES,

CONTROLS, HANGERS SERVING EXISTING TERMINAL UNIT.

2 DEMOLISH EXISTING DUCT CAP AND PREPARE FOR NEW CONNECTION.

3 DEMOLISH EXISTING EA DUCT UP TO THIS APPROXIMATE LOCATION. COORDINATE

WITH COR IF THE VA WANTS ENTIRE EA RUN TO EF IN AREA WELL AT WEST END OF

THE MECHANICAL ROOM TO ALSO BE DEMOLISHED OR JSUT ABANDONED IN PLACE.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

CORRIDOR

F394

OUTDOOR

GARDEN

F370

ELEVATOR

LOBBY

STAFF

TOILET

E309

STAFF

TOILET

E307

STAFF

LOCKERS

E306

STAFF

LOCKERS

E308

ELEC

ROOM

E304

BIOMED

E343

CORRIDOR

F394

KEYED NOTES:

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

H

G

F

E

VAV-149(EX)

/2 MD131 /2 MD131

VAV-163(EX)

VAV-160(EX)

1 1

"x

E X

AD

AD

AD

FSD

FSD

FSD

AD

FSD

AD

FSD

D

C

VAV-147(EX)

VAV-152(EX)

VAV-145(EX)

/1 MD131 /1 MD131

1 7

AD

FSD

AD

FSD

AD

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

B

A

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:2

A

M

AW DAW

589A4-20-155

MD131

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

LEVEL 03 PLAN - HVAC DEMOLITION 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

LEVEL 03 PLAN - HVAC DEMOLITION - PART A

1/4" = 1'-0"

LEVEL 03 PLAN - HVAC DEMOLITION - PART B

1 DEMOLISH EXISTING TERMINAL UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES,

CONTROLS, HANGERS SERVING EXISTING TERMINAL UNIT.

2 DEMOLISH EXISTING DUCT CAP AND PREPARE FOR NEW CONNECTION.

3 EXISTING 12"Ø MRI QUENCH DUCT RUNNING FROM FLOOR BELOW THROUGH ROOF

TO REMAIN.

4 EXISTING 14"x14" CHEMO DUCT RUNNING FROM FLOOR BELOW THROUGH ROOF TO

REMAIN.

5 DEMOLISH EXISTING CAPPED RETURN DUCT AND PREPARE FOR NEW CONNECTION.

6 DEMOLISH EXISTING TERMINAL UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES,

CONTROLS, HANGERS SERVING EXISTING TERMINAL UNIT. THIS TERMINAL UNIT'S

SUPPLY DUCT PASSES THROUGH AN EXISTING 2-HR RATED SMOKE/FIRE BARRIER.

CAREFULLY REMOVE EXISTING FIRE/SMOKE DAMPER AS IT SHALL BE REUSED IN

NEW CONSTRUCTION AT DOORWAY LEADING TO CORRIDOR F358, TO SERVE

EXHAUST DUCT PENETRATION THE 2-HR FIRE/SMOKE BARRIER. PATCH ALL

REMOVED PENTRATIONS WITH APPROVED MATERIALS TO MAINTAIN THE EXISTING

2-HR SMOKE/FRIRE RATING.

7 DEMOLISH EXISTING TERMINAL UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES,

CONTROLS, HANGERS SERVING EXISTING TERMINAL UNIT. THIS TERMINAL UNIT'S

SUPPLY DUCT PASSES THROUGH AN EXISTING 2-HR RATED SMOKE/FIRE BARRIER.

EXISTING DUCT AND FIRE/SMOKE DAMPER SHALL REMAIN AND BE REUSED FOR

CONNECTION OF NEW TERMINAL UNIT.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

98 10 11

D

C

B

A

3"ø HHWR (EX)

3"ø HHWS (EX)

"ø

H H

W R

E

X

3"ø HHWS (EX)

1 1/2"ø HHWR (EX)

1 1/2"ø HHWS (EX)

1 1/2"ø HHWR (EX)

1 1/2"ø HHWS (EX)

/2 "ø

H H

W S

E

X )1

/2 "ø

H H

W R

E

X

1 1 1 1

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:2

A

M

AW DAW

589A4-20-155

MD201

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

BASEMENT PLAN - PIPING DEMOLITION 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

BASEMENT PLAN - PIPING DEMOLITION

1 DEMOLISH EXISTING TERMINAL UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES,

CONTROLS, HANGERS SERVING EXISTING TERMINAL UNIT.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

CORRIDOR

F394

OUTDOOR

GARDEN

F370

ELEVATOR

LOBBY

STAFF

TOILET

E309

STAFF

TOILET

E307

STAFF

LOCKERS

E306

STAFF

LOCKERS

E308

ELEC

ROOM

E304

BIOMED

E343

CORRIDOR

F394

KEYED NOTES:

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

H

G

F

E

/2 MD231 /2 MD231

1 1/2"ø HHWR (EX)

1 1/2"ø HHWS (EX)

1"ø HHWR (EX)

1"ø HHWS (EX)

VAV-149(EX)

VAV-160(EX) VAV-163(EX)

1 1

2"ø HHWS (EX)

2"ø HHWR (EX)

2"ø HHWS (EX)

2"ø HHWR (EX)

2"ø CD (EX) 2"ø CD (EX)2"ø CD (EX)

1 1/4"ø CD (EX)

1 1/2"ø HHWR (EX)

1 1/2"ø HHWS (EX)

D

C

/1 MD231 /1 MD231

VAV-145(EX)

VAV-147(EX) VAV-152(EX)

1 2 3

2"ø HHWS (EX)

2"ø HHWR (EX)

2"ø HHWS (EX)

2"ø HHWR (EX)

2"ø CD (EX) 2"ø CD (EX)

1 1/2"ø HHWR (EX)

1 1/2"ø HHWS (EX)

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

B

A

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:2

A

M

AW DAW

589A4-20-155

MD231

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

LEVEL 03 PLAN - PIPING DEMOLITION 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

LEVEL 03 PLAN - PIPING DEMOLITION - PART A

1/4" = 1'-0"

LEVEL 03 PLAN - PIPING DEMOLITION - PART B

1 DEMOLISH EXISTING TERMINAL UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES,

CONTROLS, HANGERS SERVING EXISTING TERMINAL UNIT.

2 DEMOLISH EXISTING TERMINAL UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES,

CONTROLS, HANGERS SERVING EXISTING TERMINAL UNIT. THIS TERMINAL UNIT'S

SUPPLY DUCT PASSES THROUGH AN EXISTING 2-HR RATED SMOKE/FIRE BARRIER.

CAREFULLY REMOVE EXISTING FIRE/SMOKE DAMPER AS IT SHALL BE REUSED IN NEW

CONSTRUCTION AT DOORWAY LEADING TO CORRIDOR F358, TO SERVE EXHAUST

DUCT PENETRATION THE 2-HR FIRE/SMOKE BARRIER. PATCH ALL REMOVED

PENTRATIONS WITH APPROVED MATERIALS TO MAINTAIN THE EXISTING 2-HR

SMOKE/FRIRE RATING.

3 DEMOLISH EXISTING TERMINAL UNIT AND ALL ASSOCIATED PIPING, ACCESSORIES,

CONTROLS, HANGERS SERVING EXISTING TERMINAL UNIT. THIS TERMINAL UNIT'S

SUPPLY DUCT PASSES THROUGH AN EXISTING 2-HR RATED SMOKE/FIRE BARRIER.

EXISTING DUCT AND FIRE/SMOKE DAMPER SHALL REMAIN AND BE REUSED FOR

CONNECTION OF NEW TERMINAL UNIT.

4 EXISTING CAP-TERMINATED EQUIPMENT CONDENSATE DRAIN TO REMAIN.

5 DEMOLISH EXISTING HEATING WATER MAINS AS SHOWN AND PREPARE FOR NEW

CONNECTION.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

987 10 11

D

C

B

A

1-1-AFCV-1

1-1-AFCV-2

1-1-AFCV-3

1-1-AFCV-4

1-1-AFCV-6

1-1-AFCV-7

1-1-TU-1

1- 1-

TU

-3

1-1-TU-2

1- 1-

TU

-4

1-1-TU-6

1- 1-

TU

-7

1-1-TU-8 1-1-TU-9

1-1-TU-10

1-1-TU-11

1- 1-

TU

-5

E001G

STORAGE

E001

PHARMACY FILLING &

ASSEMBLY

E001K

NEG HD STORAGE

CBE2

EXISTING CORRIDOR

E009

EXIST. ELEC

E001A

EXISTING NARCOTIC

VAULT

E001B

OFFICE 2

E001C

OFFICE 1

E001D

TEAM WORK AREA

E001F

STORAGE

E001L

POS ISO ANTEROOM

E001E

SECURED DISPENSING /

STORAGE, INPATIENT

E002K

EXISTING OFFICE

28"x10" SA

8"ø SA

E001J

NEG ISO HAZ BUFFER

SD-670

385 CFM

(TYP 2)

ER-512

210 CFM

(TYP 2)

ER-512

160 CFM

(TYP 2)

ER-512

170 CFM

(TYP 2)

ER-512

200 CFM

(TYP 2)

ER-512

205 CFM

(TYP 2)

10"ø EA

12"x8" EA

"x

E A

14"x12"

10"x10" RA

"ø

S A

10"x10" SA

"x

S A

SD-670

475 CFM

(TYP 2)

ER-512

205 CFM

ER-512

205 CFM

(TYP 2)

"ø S

A

12"ø EA

16"x10" RA

14"ø EA

SD-13

260 CFM

RG-25

385 CFM

(TYP 2)

SD-12

120 CFM

SD-12

70 CFM

RG-21

70 CFM

RG-21

70 CFM

RG-21

70 CFM

RG-21

80 CFM

SD-12

70 CFM

SD-12

130 CFM

SD-13

300 CFM

1-1-AFCV-5

SD-13

300 CFM

RG-25

445 CFM

(TYP 2)

RG-25

445 CFM

(TYP 2)

SD-13

300 CFM

RG-24

300 CFM

RG-21

40 CFM

SD-12

90 CFM

RG-24

300 CFM

SD-13

300 CFM

SD-13

300 CFM

"x

E A

10"x10" RA

"x

S A

ER-512

130 CFM

ER-512

125 CFM

ER-512

125 CFM

14"x14" EA

14"x12" SA

"ø S

A1

"ø E

A

12"ø EA

"x

R

A

"x

"x

"x

E A

12"x12" RA

10"x10" SA

10"x10" RA

"x

R

A

24"x16" SA

"x

R

A

24"x16" EA

16"x10" EA

16"x10" EA

16"x10" EA

16"ø SA

20"x10" SA

"x

E A

SD-14

405 CFM

(TYP 2)

"x

E A

14"x12" EA

14"x12" SA

10"x10" RA

"ø S

A

1-SH4

1-SH2

1-SH3

1-SH4

1-SH5

SD-13

270 CFM

SD-670

555 CFM

(TYP 2)

30"x16" SA 3

"x

S A

"x

R A

(E X

114"x42" RA(EX)

24"x16" EA

16"x10" EA

"x

S A

8"x8" SA

"x

16"x10"

1-EF3

22"x18" RA

"x

R

A

22"x18" RA

"x

R

A

18"x14" RA

"x

R

A

"ø S

A

"x

S A

10"ø SA14"x10" SA

10"ø SA

"ø S

A

"ø S

A

12"x10" RA

"ø R

A

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:3

A

M

AW DAW

589A4-20-155

MH101

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

BASEMENT PLAN - HVAC 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

BASEMENT PLAN - HVAC

1 NON-DUCTED FUME HOOD.

2 DUCTED FUME HOOD.

3 COORDINATE WITH HOOD MANUFACTURER FOR PROPER CONNECTIONS, AIRFLOW

BALANCING, AND CONTROLS INTEGRATION. HOOD VARIABLE FLOW CANOPY COLLAR

CONNECTION DIAMETER 10 INCHES. ROUTE 14 INCH DIAMETER DUCT TO HOOD WITH

TRANSITIONS AS NEEDED. DUCT TO PROVIDE FOR AIR GAP AROUND HOOD COLLAR

PER MANUFACTURERS DETAILS. BALANCE EXHAUST FAN AND AIR VALVES TO

ENSURE PROPER PRESURIZATION FOR ROOM CERTIFICATION. INTEGRATE HOOD

CONTROLS VIA DRY CONTACTS INTO THE BUILDING AUTOMATION SYSTEM FOR

MONITORING AND ALARMING OF SYSTEM PERFORMANCE.

4 BASEMENT PHARMACY DEDICATED FUME HOOD EXHAUST. 16"x10" UP.

5 BASEMENT PHARMACY ROOM EXHAUST. 24"x16" UP.

6 LOW MOUNTED EXHAUST REGISTER MOUNTED 12" AFF. SEE 1/MH301 FOR MOUNTING

AND DUCT ROUTING DETAIL.

7 LOCATE HUMIDIFIER IN ACCORDANCE WITH NEC REQUIRED 36" WORKING SPACE

CLEARANCE IN FRONT OF PANEL - MUST BE KEPT CLEAR.

8 CAP ABANDONED EA DUCT.

9 HEPA FILTERS AND CONTAINMENT BOXES.

10 PREFILTER CONTAINMENT BOX.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

987 10 11

D

C

B

A

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:3

A

M

AW DAW

589A4-20-155

MH111

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

LEVEL 01 PLAN - HVAC 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1 BASEMENT PHARMACY DEDICATED FUME HOOD EXHAUST. 16"x10" UP.

2 BASEMENT PHARMACY DEDICATED FUME HOOD EXHAUST. 16"x10" DOWN.

3 BASEMENT PHARMACY ROOM EXHAUST. 24"x16" UP.

4 BASEMENT PHARMACY ROOM EXHAUST. 24"x16" DOWN.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

987 10 11

D

C

B

A

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:3

A

M

AW DAW

589A4-20-155

MH121

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

LEVEL 02 PLAN - HVAC 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1 BASEMENT PHARMACY DEDICATED FUME HOOD EXHAUST. 16"x10" UP AND DOWN.

2 BASEMENT PHARMACY ROOM EXHAUST. 24"x16" UP AND DOWN.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

987 10 11

D

C

B

A

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:3

A

M

AW DAW

589A4-20-155

MH125

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

INTERSTITIAL PLAN - HVAC 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1 BASEMENT PHARMACY DEDICATED FUME HOOD EXHAUST. 16"x10" UP AND DOWN.

2 BASEMENT PHARMACY ROOM EXHAUST. 24"x16" UP AND DOWN.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

H

G

F

E

34"x24" SA(EX) 26"x20" SA(EX)

3- 8-

TU

-4

3-8-TU-5

3-8-TU-6

3-8-TU-73-8-TU-8

3- 8-

TU

-9

3-8-TU-10

3-8-TU-11

3- 8-

TU

-1

3-8-TU-13

3-8-TU-14 3-8-TU-15

3-8-TU-16

3-8-TU-17

3-8-TU-18

3-8-TU-19

3-8-TU-20

3-8-TU-21

F361

NON-HAZARDOUS IV PREP

F360

HAZARDOUS IV

PREP/STORAGE

F364

MED. ROOM

F363

SOILED DISPATCH

F365

TOILET

F374

NURSE STATION

F386

INFUSION BAY

F372

INFUSION BAY

F371

INFUSION BAY

F369

INFUSION BAY

F375

INFUSION BAY

F376

INFUSION BAY

F377

INFUSION BAY

F380

PRIVATE INFUSION

F381

PRIVATE INFUSION

F382

TOILET

F389

EXAM ROOM

F391

EXAM ROOM

F392

EXAM ROOM

F385

PATIENT TOILET

F383

NOURISH

F373

CORRIDOR

F

C O

R R

ID

O

R

F357

WORK ROOM

F367

INFUSION BAY

F368

INFUSION BAY

F379

EQUIPMENT ALCOVE

F394

EXISTING CORRIDOR

F395

EXISTING CORRIDOR

3-8-AFCV-2

3-8-AFCV-3

3-8-AFCV-4

3-8-AFCV-5

3-8-AFCV-1

34"x14"(EX)

"x

S A

(E X

20"x16" SA(EX)

RG-22

140 CFM

SD-12

140 CFM

RG-22

180 CFM

SD-12

180 CFM

RG-22

180 CFM

SD-12

180 CFM

RG-22

170 CFM

SD-12

170 CFM

RG-22

190 CFM

SD-12

190 CFM

SD-12

280 CFM

RG-22

100 CFM

SD-12

100 CFM

SD-12

170 CFM

SD-12

100 CFM

SD-12

110 CFM

RG-22

110 CFM

F370

EXISTING OUTDOOR

GARDEN

F378

INFUSION BAY

F358

CORRIDOR

16"x10" SA

"x

S A

12"x10" SA

10"x6" SA

10"x10" SA

"x

S A

SD-12

210 CFM

SD-12

260 CFM

SD-670

540 CFM

SD-15

435 CFM

(TYP 2)

RG-23

225 CFM

SD-12

120 CFM

SD-12

150 CFM

SD-12

80 CFM

RG-23

200 CFM

RG-22

100 CFM

SD-12

100 CFM

SD-12

100 CFM

SD-12

110 CFM

RG-22

110 CFM

SD-12

110 CFM

RG-22

110 CFM

RG-22

120 CFM

SD-12

120 CFM

F388

EXAM ROOM

F362

CLEAN DISPATCH ER-512

285 CFM

(TYP 2)

ER-512

690 CFM

8"ø SA

"ø

S A

RG-22

100 CFM

EG-58

320 CFM

/2 MH131 /2 MH131

F359

ANTEROOM

"ø E

A

"ø E

A

"ø

E A 1

"ø

S A

10"ø

SD-670

12"ø / 385 CFM

(TYP 2)

ER-512

24"x12" / 190 CFM

(TYP 3)

16"x10" EA

"ø S

A

"ø S

A

12"ø EA

"ø

S A

SD-12

150 CFM

16"x10" SA

14"x12" SA

SD-12

140 CFM

EG-51

150 CFM

EG-51

150 CFM

SD-12

150 CFM

SD-12

150 CFM

18"x12" SA20"x14" SA20"x16" SA

RG-23

200 CFM

3-8-TU-22

12"ø SA

"ø E

A

14"x14" EA

12"ø EA

14"x12" SA

8"ø SA10"x8" SA

10"x8" EA

10"x10" RA14"x12" RA

32"x24" SA(EX)

"x

S A

"ø

S A

EG-51

150 CFM

18"x10" RA18"x10" RA

F366

INFUSION BAY

SD-12

150 CFM

"x

R A

(E X

EG-23

230 CFM

12"x10" RA

"ø

R A

"x

R

A

12"x10" SA

"x

E A

"x

E A

8"x6" EA

RG-23

275 CFM

16"x10" RA

12"x10" RA

16"x12" SA

16"x12" SA

AD

AD

AD

FSD

FSD

FSD

"x

R

A

"x

"ø

20"x12"

"x

"x

R

A

18"x16" SA(EX)

AD

FSD

AD

FSD

8"ø EA

"x

E A

8"ø SA

8"ø RA

10"ø RA

AD

FSD

8"x6" EA

8"x6" EA

3-SH2

3-SH3

3-SH1

F393

EXAM ROOM

10"x8" RA

8"x8" SA

8"ø SA

RG-22

95 CFM

12"x12" EA

SD-12

250 CFM

12"x10" SA

D

C

34"x24" SA(EX) 26"x20" SA(EX)

18"x14" RA(EX)36"x22" RA(EX)

3-8-TU-1

3-8-TU-23

3-8-TU-24

E303

WORK AREA

E302

RECEPTION

E301

HEM/ONC WAITING

F394

EXISTING CORRIDOR

SD-12

110 CFM

RG-22

110 CFM

SD-12

110 CFM

SD-12

100 CFM

RG-22

110 CFM

RG-21

100 CFM

E310

INTAKE

E311

CONSULT ROOM

14"x14" SA

SD-12

100 CFM

"x

R

A

3-8-TU-3

/1 MH131 /1 MH131

SD-15

480 CFM

(TYP 2)

RG-25

480 CFM

(TYP 2)

3-8-TU-2

8"x8" SA

AD

AD

FSD

18"x16" SA(EX)

AD

14"x14" RA

"x

S A

"ø

E A

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

B

A

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:4

A

M

AW DAW

589A4-20-155

MH131

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

LEVEL 03 PLAN - HVAC 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

LEVEL 03 PLAN - HVAC - PART A

1/4" = 1'-0"

LEVEL 03 PLAN - HVAC - PART B

1 BASEMENT PHARMACY DEDICATED FUME HOOD EXHAUST ROUTED TO ROOF.

TRANSISTION TO 16"x16" BEFORE PENETRATING ROOF ABOVE.

2 EXISTING 8" STORM DRAIN LINES RUN THROUGHT THIS AREA. COORDINATE ALL

DUCT BELOW THESE STORM DRAIN LINES.

3 16" x 16" EXHAUST UP. TRANSISTION TO 22"x22" BEFORE PENETRATING ROOF AND

CONNECTING TO EXHAUST FAN.

4 12" x 12" EXHAUST UP THROUGH ROOF.

5 18" x 18" EXHAUST UP THROUGH ROOF.

6 NON-DUCTED FUME HOOD.

7 DUCTED FUME HOOD.

8 COORDINATE WITH HOOD MANUFACTURER FOR PROPER CONNECTIONS, AIRFLOW

BALANCING, AND CONTROLS INTEGRATION. HOOD VARIABLE FLOW CANOPY COLLAR

CONNECTION DIAMETER 10 INCHES. ROUTE 14 INCH DIAMETER DUCT TO HOOD WITH

TRANSITIONS AS NEEDED. DUCT TO PROVIDE FOR AIR GAP AROUND HOOD COLLAR

PER MANUFACTURERS DETAILS. BALANCE EXHAUST FAN AND AIR VALVES TO

ENSURE PROPER PRESURIZATION FOR ROOM CERTIFICATION. INTEGRATE HOOD

CONTROLS VIA DRY CONTACTS INTO THE BUILDING AUTOMATION SYSTEM FOR

MONITORING AND ALARMING OF SYSTEM PERFORMANCE.

9 LOW MOUNTED EXHAUST REGISTER. SEE 1/MH301 FOR MOUNTING AND DUCT

ROUTING DETAIL.

10 BASEMENT PHARMACY ROOM EXHAUST ROUTED TO ROOF. TRANSISTION TO 22"x22"

BEFORE PENETRATING ROOF ABOVE.

11 EXISTING 12"Ø MRI QUENCH DUCT RUNNING FROM FLOOR BELOW THROUGH ROOF

TO REMAIN.

12 EXISTING 14"x14" CHEMO DUCT RUNNING FROM FLOOR BELOW THROUGH ROOF TO

REMAIN.

13 REUSED FIRE/SMOKE BARRIER. SEE KEYNOTE 6 ON SHEET MD131 FOR MORE

INFORMATION.

14 LOCATE HUMIDIFIER IN ACCORDANCE WITH NEC REQUIRED 36" WORKING SPACE

CLEARANCE IN FRONT OF PANEL - MUST BE KEPT CLEAR.

15 CONNECT TERMINAL UNIT TO EXISTING SUPPLY DUCT AND FIRE DAMPER.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

H

G

F

E

/2 MH141 /2 MH141

3-EF-3

3-EF-1

3-EF-2

1 111

2 3

3-EF-1

3-EF-1

"ø E

A

"ø E

A

EF-CHEMO

EX EF-12/13EX EF-8 EX EF-14/15

NO SCOPE OF WORK ASSOCIATED IN SHADED AREA

D

C

/1 MH141 /1 MH141

22"ø EA

16"ø EA

"ø E

A

"ø E

A

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

(BLDG 01)

AMB.

CARE

ADD.

B

A

KEYPLAN

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:4

A

M

AW DAW

589A4-20-155

MH141

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

ROOF PLAN - HVAC 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

ROOF PLAN - HVAC - PART A

1/4" = 1'-0"

ROOF PLAN - HVAC - PART B

1 EXISTING 14"x14" CHEMO EXHAUST DUCT AND FAN TO REMAIN.

2 EXISTING 12"Ø MRI QUENCH EXHAUST GOOSENECK TO REMAIN.

3 18"x16" THIRD FLOOR PHARMACEUTICAL AREA EXHAUST DUCT DOWN.

4 14"Ø THIRD FLOOR DEDICATED FUME HOOD EXHAUST DUCT DOWN.

5 14"Ø BASEMENT DEDICATED FUME HOOD EXHAUST DUCT DOWN.

6 22"Ø BASEMENT PHARMACEUTICAL AREA EXHAUST DUCT DOWN.

7 FIELD VERIFY STRUCTURAL CONDITIONS AND PROVIDE ADEQUATE STRUCTURAL

REINFORCEMENT BELOW DECK FOR SUPPORT OF EXHAUST FAN AND ROOF CURB.

Revisions: Date:

P

RO

FESSIONAL ENGIN

Wieczorek

NUMBER

NOTES:

1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED

BY SMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE

TYPE REGARDLESS OF W DIMENSION.

3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL

BE DOUBLE VANE TYPE.

W

W1

VANE

VANE

NOTES:

1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS

ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS

RECOMMENDED BY SMACNA.

R SHALL EQUAL

OR BE GREATER

THAN W.

R SHALL EQUAL

OR BE GREATER

THAN 1/3W.

W

R

R

2/3W

/3

W R SHALL EQUAL OR

BE GREATER THAN

1/6W.

STANDARD RADIUS

OR LONG RADIUS

ELBOW

SHORT RADIUS

ELBOW WITH ONE

VANE

SHORT RADIUS

ELBOW WITH TWO

VANES

W W

1/2W

/3

W

1/6W

R

AIR SPLIT DUCT

TAKE-OFF PLAN VIEW

BRANCH DUCT TAKE-OFF PLAN

VIEW

SUPPLY REGISTER

TAKE-OFF PLAN VIEW

A

IR

F L O

W

SUPPLY REGISTER OR

BRANCH DUCT

TURNING VANES

MAIN SUPPLY

DUCT

NOTES:

1. SEE FLOOR PLAN FOR SPLIT DIMENSION.

PROVIDE VOLUME

DAMPER (TYP)

PROVIDE VOLUME

DAMPER

ADJUSTABLE METAL

ROD OR LINKAGE

TOP OF REGISTER

MAIN SUPPLY

DUCT

1/4 W OR 4" [100mm] MIN. MAIN SUPPLY

DUCT

W

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO

CFM NOTED ON FLOOR PLANS

AIRFLOW

AIRFLOW

SMACNA FIGURE 4-6 45°

LEED IN RIGID DUCT TO

AIR TERMINAL UNIT

MAIN SUPPLY

PLAN VIEW

AIRFLOW

A

IR

F L O

W

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR FLOW

W

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" [100mm] MIN.

BRANCH DUCT

NOTES:

1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION

(SEE SPECIFICATIONS)

DAMPER BLADE

1/8" [6mm]

CLEARANCE ALL

AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION

STAND-OFF

1/2" [15mm] ROUND

ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE

ELEVATION

SECTION

SECTION

"A - A"

B B

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15.

ACCESS PANEL

ACCESS DOOR

CASING

GASKET

HANDLE

INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCHSECTION

"B - B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

A

A

PLAN VIEW

(TOP OF DUCT)

ELEVATION

(SIDE OF DUCT)

HOUSING WELDED

TO DUCT SECTION

ROUND OR FLAT

OVAL DUCT SECTION

COVER WITH HANDLE AND

CHAIN RETAINER GASKETED

AND PRESSURE SEALED

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED CONNECTION

ON FAN SIDE

WASHER

NOTES:

1. 1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL TAUT.

2. FLEXIBLE MATERIAL AS INDICATED IN SPECIFICATIONS.

3. SHEET METAL AS SPECIFIED FOR DUCTWORK.

NOTE 2

1"x1/8" [25x3mm]

DRAW BAND (TYP)

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS ON

12" [300mm] CENTERS

RIVET ON 4" [100mm]

CENTERS

NOTE 3

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEM

ALTERNATE POSITION OF BOLT

1 1/2" [40mm]

POCKET SLIP

1/2" [15mm]

1/2" [15mm]

1 1/2" [40mm]

NOTE 1

FLANGED CONNECTION

ON FAN SIDE

WASHER

NOTE 2

NOTE 1

NOTE 3

DUCT

NOTES:

1. A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW

DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR

SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR

FLOOR AND NOT OUTSIDE THE PENETRATION.

2. GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER

FRAME AND TO PERIMETER ANGLES.

3. PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1-1/2"x1-1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

4. BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA. ACCESS

PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

5. PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH

ROCK WOOL FIRESTOP FIBER.

6. ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND

MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH CONCRETE CURB

AROUND OPENING FOR DUCT.

SLEEVE

(NOTE 2)

DUCT

CONNECTION

(NOTE 4)

DAMPER

(NOTE 1)

DAMPER COLLAR

EXTENSION INTEGRAL

PART OF SLEEVE

SLEEVE (NOTE 2)

NOTE 6FIRE BARRIER PARTITION

OR CHASE

TYPICAL DUCT

INSULATION

PERIMETER ANGLE, NOTE 3 (NOTE

FASTENED TO PARTITION)

ACCESS

PANEL

(NOTE 5)

[2 m m

420 [190]ONE 1 [25] x 18 GA STRAP36 [900]

ONE 1 [25] x 16 GA STRAP50 [1250] 700 [317]

ONE 1 [25] x 22 GA STRAP

QUANTITY/SIZE

IN. [mm]

MAX. DUCT ∅

IN. [mm]

26 [650]

HANGER STRAPS OR RODS

MAX. LOAD

LBS. [kg]

260 [119]

144 [3600]

MAX.

SPACING

IN. [mm]

NOTES:

1. FOR DUCT DIA. LESS THAN 50" [1,250mm].

2. TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING AND

INSULATION, BUT NO EXTERNAL LOAD.

BAND OF SAME SIZE

AS HANGER STRAP

LOAD RATED

FASTENERS (TYP)

DUCT

NOTES:

1. SEE SPECIFICATIONS FOR CLAMPS AND SEALANT (TYP).

2. FLEXIBLE DUCT SIZE SAME AS DIFFUSER INLET: 5'-0" [1,52m] MAX. LENGTH.

3. USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°

TYPICAL DIFFUSER OR

REGISTER IN LAY-IN

CEILING

THERMAL INSULATION

(SEE SPECIFICATIONS)

SUPPORT SADDLE

FROM STRUCTURE

NOTE 2

NOTE 3

SHEET METAL

SADDLE

VOLUME DAMPER

w/LOCKING QUAD

CONICAL OUTLET

BRANCH

DUCT

CEILING

12" [300mm]

NOTE 1

NOTES:

1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF

INLET.

2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0" [900mm].

3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED

THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3

METERS). FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m].

4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO

DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION

GREATER THAN 45°.

5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION WITH VAPOR

BARRIER FOR CONNECTING DUCT SECTIONS.

6. USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE DEDICATED AHU

SERVING THE SURGICAL SUITE.

7. SEE SPECIFICATIONS FOR CLAMPS AND SEALANT (TYP).

AIR TERMINAL UNIT

(CV OR VAV)

REHEAT COIL

SOUND ATTENUATOR

(SEE EQUIPMENT SCHEDULE)

FLEXIBLE AIR DUCT

CONNECTOR. SEE 13/MH200

FOR DETAIL.

DIFFUSER (TYP)

NOTE 7

NOTE 5

N O

T E

NOTE 3

NOTE 2

NOTE 1

D U

C T

M A

IN

A

IR

F

L O

W

NOTE 5

VOLUME DAMPER (TYP)

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

NOT TO SCALE

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia

C o m p le te

U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia

U n fi n is h e d S p e c ia lt y C lin ic

M E

P

V

.r v t

/2

/2

:4

:5

A

M

AW DAW

589A4-20-155

MH300

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

HVAC DETAILS 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

NTS

DUCTWORK SQUARE VANE ELBOWS DETAIL

NTS

DUCTWORK RADIUS ELBOWS DETAIL

NTS

SUPPLY DUCTWORK TAKE-OFFS DETAIL

NTS

ALTERNATE SUPPLY DUCT…