This document provides details for a federal construction solicitation for a complete unfinished specialty clinic project. The solicitation seeks to renovate approximately 6,490 square feet for an outpatient hematology/oncology clinic and 6,290 square feet for the main inpatient pharmacy at the Harry S. Truman Memorial VA Hospital in Columbia, Missouri. Renovations include new exam rooms, infusion bays, waiting areas, nurse stations, clean and soiled rooms, and office spaces for the clinic, as well as remodeling pharmacy compounding areas to comply with USP standards. The estimated price range for the project is $2,000,000 to $5,000,000. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and issued on July 16, 2021, with proposals due on August 18, 2021. The contract will be awarded using the Best Value Lowest Price Technical Acceptable source selection process. The duration of the project is up to 300 calendar days from notice to proceed. The Department of Veterans Affairs Veterans Health Administration VISN 15 is the contracting agency.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING LIST
PROJECT INFORMATION
THIS PROJECT WILL CONSTRUCT APPROXIMATELY 6,490 SQUARE FEET OF SPACE ON THE 3RD FLOOR AND APPROXIMATELY 6,290 SQUARE FEET ON THE BASEMENT FLOOR. THE 3RD FLOOR SPACE WILL CONTAIN A HEMATOLOGY / ONCOLOGY CLINIC AND ALL ASSOCIATED SUPPORT AREAS. THE BASEMENT FLOOR SPACE WILL CONTAIN PHARMACY OFFICES AND COMPOUNDING ROOMS
AND INCLUDE ALL ASSOCIATED SUPPORT AREAS.
VICINITY MAPBUILDING SUMMARY
PROJECT NAME: COMPLETE UNFINISHED SPECIALTY CLINIC
PROJECT NUMBER: 589A4-20-155
PROJECT LOCATION: HARRY S. TRUMAN MEMORIAL HOSPITAL
BUILDING AREA:
BASEMENT FLOOR 6,290 GSF
3RD FLOOR 6,490 GSF
1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW ALL DRAWINGS
AND PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.
2. THE GC SHALL VISIT THE SITE TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING PERFORMED BEFORE SUBMITTING
COST QUOTATIONS FOR WORK.
3. NOTIFY THE C.O.R. PROMPTLY OF ANY ERRORS, OMISSIONS, INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT A RESOLUTION CAN BE PROVIDED PRIOR
TO CONTINUING WITH WORK.
4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE ARCHITECT.
5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING SUCH PERMITS AND CERTIFICATES
AND SHALL FURNISH COPIES OF PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.
6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL CONDITION AT THE CONTRACTOR'S EXPENSE.
7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE ON A DAILY BASIS.
8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE C.O.R. IN WRITING AND WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE ADVANTAGEOUS TO THE OWNER WITH RESPECT TO
DELIVERY DATE, QUALITY, OR COST.
9. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S MEANS AND
METHODS OR FOR TEMPORARY STRUCTURES.
10. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL
EMPLOY ENGINEERING EXPERTISE AS NEEDED TO ASSIST IN DEMOLITION.
11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING OSHA REGULATIONS DURING
CONSTRUCTION.
12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD, RESULTING FROM WATER INTRUSION
DURING CONSTRUCTION SHALL BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.
SCOPE OF WORK SUMMARY:
GENERAL NOTES
PROJECT TEAM
AREA OF WORK
VA LEADERSHIP SIGNATURES
MEDICAL CENTER DIRECTOR
ASSOCIATE DIRECTOR
ASSISTANT DIRECTOR
SPECIALTY CARE CHIEF
ASSOCIATE DIRECTOR FOR PATIENT SERVICES
EXECUTIVE OF HIGH RELIABILITY
PHARMACY CHIEF
CHIEF ENGINEER
INFECTION CONTROL PRACTITIONER
SAFETY OFFICER
Romanyk Consulting Focusing on what matters
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
8910 7 6 5 4 3 2 1
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
IM
/V
IS
N
C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic
/C o lu m b ia U n fi n is h e d S p e c C lin ic
V
.r v t
/2
/2
:2
:1
A
M
VA PROJECT NUMBER - 589A4-20-155
COMPLETE UNFINISHED SPECIALTY CLINIC
100% FINAL CONSTRUCTION DOCUMENTS
JUNE 25, 2021
MK LJ
589A4-20-155
GI100
589A4 - COLUMBIA, MO
JUNE 25, 2021
01-
SHEET INDEX & GENERAL INFORMATION 100% FINAL CONSTRUCTION
DOCUMENTS
COMPLETE UNFINISHED SPECIALTY
CLINIC
SHEET # SHEET TITLE
MH111 LEVEL 01 PLAN - HVAC
MH121 LEVEL 02 PLAN - HVAC
MH125 INTERSTITIAL PLAN - HVAC
MH131 LEVEL 03 PLAN - HVAC
MH141 ROOF PLAN - HVAC
MH300 HVAC DETAILS
MH301 HVAC DETAILS
MH400 HVAC SCHEDULES
MH401 HVAC SCHEDULES
MI101 BASEMENT PLAN - MECHANICAL INSTRUMENTATION
MI131 LEVEL 03 PLAN - MECHANICAL INSTRUMENTATION
MP101 BASEMENT PLAN - PIPING
MP131 LEVEL 03 PLAN - PIPING
MP300 PIPING DETAILS
MP400 PIPING SCHEDULES
PLUMBING
PD001 UNDER FLOOR PLAN - PLUMBING DWV DEMOLITION
PP001 UNDER FLOOR PLAN - PLUMBING DWV
P-001 PLUMBING LEGEND, SCHEDULES AND ABBREVIATIONS
PD101 BASEMENT PLAN - PLUMBING DWV DEMOLITION
PD125 INTERSTITIAL PLAN - PLUMBING DWV DEMOLITION
PD131 LEVEL 03 PLAN - PLUMBING DWV DEMOLITION
PD201 BASEMENT PLAN - PLUMBING DISTRISTIBUTION DEMOLITION
PD225 INTERSTITIAL PLAN - PLUMBING DISTRISTIBUTION DEMOLITION
PD231 LEVEL 03 PLAN - PLUMBING DISTRISTIBUTION DEMOLITION
PP101 BASEMENT PLAN - PLUMBING DWV
PP125 INTERSTITIAL PLAN - PLUMBING DWV
PP131 LEVEL 03 PLAN - PLUMBING DWV
PP201 BASEMENT PLAN - PLUMBING DISTRISTIBUTION
PP225 INTERSTITIAL PLAN - PLUMBING DISTRISTIBUTION
PP231 LEVEL 03 PLAN - PLUMBING DISTRISTIBUTION
P-300 PLUMBING RISER DIAGRAM
P-400 PLUMBING DETAILS
ELECTRICAL
EJ102 ELECTRICAL SCHEDULES
E-001 ELECTRICAL LEGEND, SCHEDULES AND ABBREVIATIONS
ED101 BASEMENT PLAN - ELECTRICAL DEMOLITION
ED131 LEVEL 03 PLAN - ELECTRICAL DEMOLITION
EL101 BASEMENT PLAN - LIGHTING
EL131 LEVEL 03 PLAN - LIGHTING
EP101 BASEMENT PLAN - POWER
EP102 BASEMENT PLAN - MECHANICAL POWER
EP131 LEVEL 03 PLAN - POWER
EP132 LEVEL 03 PLAN - MECHANICAL POWER
EP141 ROOF PLAN - POWER
EJ101 ELECTRICAL ENLARGED PLANS
ET101 BASEMENT PLAN - SYSTEMS
ET131 LEVEL 03 PLAN - SYSTEMS
E-400 ELECTRICAL DETAILS
Grand total: 106
SHEET # SHEET TITLE
GENERAL
GI100 SHEET INDEX & GENERAL INFORMATION
GI101 ABBREVIATIONS
GI102 ADA INFORMATION
GI103 BUILDING CODE
GI104 BASEMENT LIFE SAFETY PLAN
GI105 THIRD FLOOR LIFE SAFETY PLAN
GI106 PHASING PLAN
GI107 PHASING PLAN
ARCHITECTURAL
AD101 BASEMENT DEMOLITION PLAN
AD102 THIRD FLOOR DEMOLITION PLAN
AD103 BASEMENT RCP DEMOLITION
AE101 BASEMENT OVERALL PLAN
AE102 THIRD FLOOR OVERALL PLAN
AE103 BASEMENT ENLARGED PLAN
AE104 THIRD FLOOR ENLARGED PLAN
AE105 BASEMENT DIMENSION PLAN
AE106 THIRD FLOOR DIMENSION PLAN
AE107 BASEMENT REFLECTED CEILING PLAN
AE108 THIRD FLOOR REFLECTED CEILING PLAN
AE401 ENLARGED TOILET PLAN AND ELEVATIONS
AE402 ENLARGED PLANS
AE403 ENLARGED PLANS
AE404 BASEMENT INTERIOR ELEVATIONS
AE405 THIRD FLOOR INTERIOR ELEVATIONS
AE500 PARTITION TYPES
AE501 ACCESSIBLE DETAILS
AE502 METAL STUD DETAILS
AE503 CEILING DETAILS
AE504 CEILING DETAILS
AE601 DOOR & WINDOW SCHEDULES
AE700 MILLWORK SECTIONS AND DETAILS
AE701 MILLWORK SECTIONS AND DETAILS
AF100 INTERIOR FINISH NOTES AND DETAILS
AF101 BASEMENT FINISH PLAN
AF102 THIRD FLOOR FINISH PLAN
AF103 THIRD FLOOR HEM/ONC WAITING FINISH PLAN
AW101 BASEMENT SIGNAGE PLAN
AW102 THIRD FLOOR SIGNAGE PLAN
AW103 SIGNAGE PLAN DETAILS
AW104 SIGNAGE PLAN DETAILS
QH101 BASEMENT EQUIPMENT PLAN
QH102 THIRD FLOOR EQUIPMENT PLAN
SPRINKLER
FS001 SPRINKLER SYMBOLS, NOTES, AND ABBREVIATIONS
FD101 BASEMENT PLAN - SPRINKLER DEMOLITION
FD131 LEVEL 03 PLAN - SPRINKLER DEMOLITION
FS101 BASEMENT PLAN - SPRINKLER
FS131 LEVEL 03 PLAN - SPRINKLER
MECHANICAL
MH402 HVAC SCHEDULES
MI301 CAV - HW HEATING
MI302 VAV - HW REHEAT
MI303 VAV - PHARMACY HW REHEAT ROOM PRESSURE CONTROL
MI304 EXHAUST FAN - ON/OFF
MI305 EXHAUST FAN - PHARMACY PRESSURE CONTROL
M-001 MECHANICAL LEGEND, SCHEDULES AND ABBREVIATIONS
MD101 BASEMENT PLAN - HVAC DEMOLITION
MD131 LEVEL 03 PLAN - HVAC DEMOLITION
MD201 BASEMENT PLAN - PIPING DEMOLITION
MD231 LEVEL 03 PLAN - PIPING DEMOLITION
MH101 BASEMENT PLAN - HVAC
OWNER:
Department of Veterans Affairs, Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth KS 66048
Jeanette G. Mathena Jeanette.Mathena@va.gov
913.946.1129
CONTRACTING OFFICER REPRESENTATIVE (COR):
Harry S. Truman Memorial Hospital 800 Hospital Drive Columbia, MO 65201
Daniel P. Schmidt, CMOVAMC Daniel.Schmidt6@va.gov
573-814-6000 x52448
PROJECT ARCHITECT:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Michele M. Kiehl, AIA, LEED AP BD+C Michele.Kiehl@RomanykConsulting.com
855.424.3838 x313
913.908.3280 cell
MECHANICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855-424-3838 x324 319.721.4986
PLUMBING ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com
855-424-3838 x324 319.721.4986
ELECTRICAL ENGINEER:
Romanyk Consulting Corp.
3308 Preston Road, Suite 350-164 Plano, Texas 75093
Jeffrey Koehler Jeffrey.Koehler@RomanykConsulting.com
855.424.3838 x315
262.930.0903 cell
INTERIOR DESIGNER:
Spellman Brady & Company 8251 Maryland Ave STE 300 St. Louis, MO 63105
Melissa Kenney, IIDA, RID, NCIDQ, LEED AP Mkenney@spellmanbrady.com
314.862.0070 x128 314.369.9241
Revisions: Date:
1i
0 GRID / COLUMN LINE DESIGNATOR
EQUIPMENT NUMBER
DOOR NUMBER
Ga5xFB1
WALL TYPE
WINDOW TYPE
ROOM NAME
ROOM NAME / NUMBER
REVISION TAG
NORTH
NORTH ARROW WITH TRUE
NORTH INDICATION
EGRESS ROUTE ID AND
SECTION LENGTH
ROOM
ROOM OCCUPANCY
150 SF
EGRESS : EGRESS ID
Egress Length
ROOM OCCUPANCY & AREA
ELEVATION NUMBER
SECTION
INTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name Elevation
FLOOR LEVEL &
NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
SHEET KEYNOTE
A101
SIM
EXTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
A101
A101
ANNOTATION DRAWING SYMBOLS
INDEX OF DRAWINGS
202-A101
DISCIPLINE:
G - GENERAL
A - ARCHITECTURE
I - INTERIORS
F- FIRE PROTECTION
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
T - TELECOM
V - VENTILATION
SHEET TYPE
DESIGNATOR
BUILDING NUMBER
SHEET NUMBER
WITHIN SERIES
ARCHITECTURAL SYMBOLS
LEGEND
CONCRETE/ PRECAST
CONCRETE
SOIL
SAND, EIFS FINISH COAT,
OR CEMENT PLASTER
BRICK
CMU
STONE
FIBERGLASS BATT
INSULATION
EXPANDED POLYSTYRENE
RIGID INSULATION
EXTRUDED POLYSTYRENE
RIGID INSULATION
POLYISOCYANURATE RIGID
INSULATION
GYPSUM BOARD
EXTERIOR GYPSUM
SHEATHING
EXTERIOR CEMENT
BOARD
COATED GLASS MAT
WATER RESISTANT
GYP BD
PLYWOOD
COVER BOARD
MATERIALS
CEILING SYMBOLS
MECHANICAL SUPPLY DIFFUSER
MECHANICAL RETURN GRILLE
MECHANICAL EXHAUST GRILLE
24" X 24" ACOUSTICAL CEILING
PANEL AND GRID
GYPSUM BOARD CEILING OR
SOFFIT
2' x 2' LED FLUORESCENT
FIXTURE - EMERGENCY NIGHT
LIGHT
RECESSED CAN DOWNLIGHT
CEILING ELEVATION A.F.F.X'-X"
EXIT SIGN
LED LIGHT
1' x 4' LED FLUORESCENT
FIXTURE
2' x 4' LED FLUORESCENT
FIXTURE
INDUSTRIAL LUMINAIRE
EMERGENCY LIGHT
2' x 2' LED FLUORESCENT
FIXTURE
OC
NURSE CALL DOME LIGHT WALL
MOUNTED
A
FIRE ALARM AUDIO/VISUAL
NOTIFICATION DEVICE-CEILING
MOUNTED.
CAM
LS
OCCUPANCY SENSOR
A1 A3
DAYLIGHT LEVEL SENSOR
CLOSED CIRCUIT CAMERA (CCTV)
CEILING MOUNTED
N
S SPEAKER
CLOSED CIRCUIT CAMERA (CCTV)CAM
VC VACANCY SENSOR
WAP CEILING INFORMATION OUTLET
FIRE ALARM VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
V1
WALL CONTROL STATIONSW
NURSE CALL STATIONN
SMOKE,FIRE/SMOKE
DAMPER CONTROLLER
ARD
FIRE ALARM MANUAL PULL
STATION
F
FIRE ALARM SMOKE,
SMOKE DAMPER
SD
SD FIRE ALARM DUCT SMOKE
DETECTOR
D DIMMER LED
A FIRE ALARM AUDIO/VISUAL
NOTIFICATION DEVICE- WALL
MOUNTED.
A1 A3
S SWITCH
{LD}
{LS}
LIGHT DIMMER
LIGHT SENSOR
ARCHITECTURAL DRAWING ABBREVIATIONS
A ---------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALG ALUMINUM AND GLASS
AL ALUMINUM
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AW ARCHITECTURAL WOODWORK
AWT ACOUSTICAL WALL TREATMENT
B ---------------------
B LABEL CLASS B DOOR
BALC BALCONY
BB BASEBOARD
BC BOOKCASE
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BUILDING PAPER
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER) BOARD
CD CONSTRUCTION DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE
COORD COORDINATE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ELEV EQ ELEVATOR EQUIPMENT
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE BOARD (INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GR EXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAS BD FASCIA BOARD
FC BRK FACE BRICK
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
FRTW FIRE RETARDANT TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED INSTALLED BY GOVERNMENT
GFRG GLASS-FIBER-REINFORCED GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GSF GROSS SQUARE FEET
GUT GUTTER
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H ---------------------
HAC HOUSE AID KEEPING CLOSET
HB HOSE BIBB
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
ISO ISOLATION
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBS POUND
LDG LANDING
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WATERPROOFING
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER AND RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REC ROOM RECREATION ROOM
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV ROOF VENT
RVL REVEAL
S --------------------
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHT MTL FLASH SHEET METAL (FLASHING)
SHTHG SHEATHING
SHWR SHOWER
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SKLT SKYLIGHT
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STD STANDARD
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STOR STORAGE
STR STRINGERS
STRB/HRN STROBE/HORN
SUB FL SUBFLOOR
SV SHEET VINYL
SW SIDEWALK
T --------------------
T TREAD
T/S TUB/SHOWER
TC TERRA COTTA
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TFF TOP OF FINISH FLOOR
THK THICKNESS
TK BD TACKBOARD
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TRANS TRANSOM
TRTD TREATED
TV TELEVISION
SEE OTHER DISCIPLINES FOR
ADDITIONAL ABREVIATIONS
NOTE: NOT ALL MAY BE USED
ARCHITECTURAL SYMBOLS
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic
/C o lu m b ia U n fi n is h e d S p e c C lin ic
V
.r v t
/2
/2
:2
:1
A
M
Checker Author
589A4-20-155
GI101
589A4 - COLUMBIA, MO
JUNE 25, 2021
01-
ABBREVIATIONS 100% FINAL CONSTRUCTION
DOCUMENTS
COMPLETE UNFINISHED SPECIALTY
CLINIC
ACCESSIBLE SIGNAGE REQS
LETTER AND NUMBER HEIGHTS
TOILET ACCESSORY LEGEND
NOTES
CHARACTER PROPORTIONS:
LETTERS AND NUMBERS ON SIGNS SHALL HAVE A WIDTH-TO-HEIGHT RATIO
BETWEEN 3:5 AND 1:1 AND A STROKE-WIDTH-TO-HEIGHT RATIO BETWEEN 1:5 AND
1:10, UTILIZING AN UPPER CASE 'X' FOR MEASUREMENT.
CHARACTER HEIGHT:
SEE LETTER AND NUMBER HEIGHT CHART BELOW
*EXCEPTION: CHARACTER HEIGHT SHALL BE 5/8" HIGH MINIMUM FOR BUILDING
DIRECTORIES.
PICTOGRAMS:
WHERE PICTOGRAMS ARE REQUIRED, THEY SHALL HAVE A 6" MINIMUM SIZE
MEASURED AT THE BORDER. WHERE TEXT DESCRIPTORS FOR PICTOGRAMS ARE
REQUIRED, THEY SHALL COMPLY WITH THE TACTILE CHARACTER PROVISIONS OF
RAISED CHARACTERS AND SYMBOLS, BRAILLE, AND LOCATION OF TACTILE
SIGNAGE PORTIONS BELOW.
FINISH AND CONTRAST:
THE CHARACTERS, SYMBOLS AND BACKGROUND OF SIGNS SHALL BE EGGSHELL,
MATTE, OR OTHER NON-GLARE FINISH. CHARACTERS AND BRAILLE, AND LOCATION
OF TACTILE SIGNAGE PORTIONS BELOW. LIGHT BACKGROUND.
RAISED CHARACTERS AND SYMBOLS:
CHARACTERS AND SYMBOLS ON TACTILE SIGNS SHALL BE RAISED 1/32" MINIMUM.
RAISED CHARACTERS AND SYMBOLS SHALL BE IN UPPERCASE CHARACTERS.
RAISED CHARACTERS AND SYMBOLS SHALL BE 5/8" HIGH MINIMUM, AND 2"
MAXIMUM. RAISED CHARACTERS AND SYMBOLS SHALL BE ACCOMPANIED BY
BRAILLE IN ACCORDANCE WITH THE PROVISIONS OUTLINED BELOW.
BRAILLE:
BRAILLE SHALL BE SEPARATED 1/2" MINIMUM FROM THE CORRESPONDING RAISED
CHARACTERS OR SYMBOLS. BRAILLE PROVIDED IN ACCORDANCE WITH THE
REQUIREMENTS FOR ELEVATOR CONTROLS SHALL BE PLACED 3/16" MINIMUM BELOW
THE CORRESPONDING CHARACTERS OR SYMBOLS. BRAILLE SHALL BE GRADE II AND
SHALL CONFORM TO SPECIFICATION #800, NATIONAL LIBRARY SERVICE, LIBRARY OF
CONGRESS.
LOCATION OF TACTILE SIGNAGE:
TACTILE SIGNAGE SHALL BE LOCATED ALONGSIDE THE DOOR ON THE LATCH SIDE
AND SHALL BE MOUNTED AT 60" ABOVE THE ADJACENT FINISHED FLOOR TO THE
CENTERLINE OF THE SIGN. IN LOCATIONS HAVING DOUBLE DOORS, TACTILE SIGNS
SHALL BE MOUNTED TO THE RIGHT OF THE RIGHT HAND DOOR. WHERE THERE IS
NO WALL SPACE ON THE LATCH SIDE OF THE DOOR, INCLUDING DOUBLE LEAF
DOORS, SIGNS SHALL BE RIGHT HAND DOOR. WHERE THERE IS NO WALL SPACE
ON THE LATCH SIDE OF THE DOOR, INCLUDING DOUBLE LEAF DOORS, SIGNS SHALL
BE PLACED ON THE NEAREST ADJACENT WALL.
GENERAL NOTES:
ANY ADDITIONAL TEXT REQUIRED DUE TO LOCAL ORDINANCES (FINES FOR
PARKING IN ACCESSIBLE SPACES, ETC.) SHALL COMPLY WITH THE SIGNAGE
REQUIREMENTS ABOVE.
ALL INTERIOR SIGNAGE WITHIN THE ASC SHALL CONFORM TO THE REQUIREMENTS
OF ADA 2010 AND ANY OTHER STATE OR LOCAL APPLICABLE CODES.
HEIGHT ABOVE FLOOR/ GROUND: MIN. CHARACTER HEIGHT:
GREATER THAN 80" (6'-8") AFF 3"
GREATER THAN 60" (5'-0") AFF BUT LESS THAN 80" (6'-8") AFF 2"
GREATER THAN 48" (4'-0") AFF BUT LESS THAN 60" (5'-0") AFF 1"
A FLOOR MOUNTED TOILET (CFCI)
GB42 42" GRAB BAR (BLOX FURNISHED & INSTALLED)
GB36 36" GRAB BAR (BLOX FURNISHED & INSTALLED)
GB18 18" GRAB BAR (VERTICAL) (BLOX FURNISHED &
INSTALLED)
E MIRROR (BLOX FURNISHED & INSTALLED)
F TOILET PAPER DISPENSER (OFCI)
G ROBE HOOK (CFCI)
H SOAP DISPENSER (OFCI)
H PAPER TOWEL DISPENSER (OFCI)
J SANITARY NAPKIN DISPOSAL (CFCI)
O BABY CHANGING TABLE (CFCI)
P WALL MOUNTED SINK (BLOX FURNISHED &
INSTALLED)
U SURFACE MTD TOILET SEAT COVER DISPENSER
(CFCI)
1. SEE SPECIFICATIONS FOR MANUFACTURERS INFORMATION ON ALL TOILET
ACCESSORIES.
2. ALL SOAP DISPENSERS, PAPER TOWEL DISPENSERS, TOILET PAPER
DISPENSERS & HAND SANITIZER DISPENSERS TO BE OWNER FURNISHED AND
CONTRACTOR INSTALLED. LOCATIONS SHOWN FOR FACILITY.
3. FOR ALL TOILET ROOMS, REFER TO SPECIFICATIONS AND DRAWINGS FOR
PARTITION TYPES & DETAILS AND BLOCKING REQUIREMENTS FOR TOILET
ACCESSORIES.
4. ALL TOILET LOCATIONS, WHETHER NOTED OR NOT, SHALL BE PROVIDED WITH
THE FOLLOWING UNLESS OTHERWISE NOTED:
a) ONE MIRROR
b) ONE TOILET PAPER DISPENSER
c) ONE ROBE HOOK - MOUNTED BEHIND STALL DOORS.
A D
A
T O
H A
N D
L E
MIRROR SOAP DISPENSER PAPER
TOWEL
DISPENSER
TOILET PAPER
DISPENSER
TOILET
PAPER
HOLDER
SANITARY
NAPKIN
DISPOSAL
MIN
1' - 3"
LAVATORY
M
IN
INSULATE EXPOSED
PIPING WITH WHITE
PLASTIC PRE-FITTED
INSULATION
M A
X
MEASURE
TO BOTTOM
OF REFLECTIVE
SURFACE
D
IS
P E
N S
E R
M A
X O
P E
R A
B L E
D
IS
P E
N S
E R
M
A X
T O
O P
E R
A B
L E
M A
X
M
IN
M
IN
FIRE
EXTINGUISHERS
AND CABINETS
7-PEG
COAT RACK
2' - 0"
"MIN
8"
MIN
11"
KNEE AND TOE
CLEARANCES
E
E
SEALANT
PROVIDE ADA
COMPLIANT FAUCET
WITH WRIST BLADE
CONTROLS
M A
X
5" MAX 15" MAX
ACCESS HGT. D.F.
SPOUT LOCATION
M
IN
SPOUT
HEIGHT
STANDING AND
ACCESSIBLE DRINKING
FOUNTAINS
FRONT SIDE
PLAN
ALUM. SEMI-RECESSED CAB.
W/ FULL CLEAR ACRYLIC DOOR
10 LBS
ABC TYPE
BABY CHANGING
TABLE
M A
X
/2
ROBE
HOOK
M A
X
"FIRE EXTINGUISHER" IN
RED LETTERS
G
F
F
(ALT)H
J
C
N O O
P
P
M
IN9
MIN
11"
M
IN
8"
25" MAX
30x48
CLEAR
SPACE
U
M A
X
TOILET
SEAT COVER
DISPENSER
SIGNAGE
(12" BELOW CEILING)
2"
HANDRAIL
PER NFPA 10
PTD (OF/OI)
PUBLIC TLTS
ONLY
SEMI-
RECESSED
WASTE RECP.
S P
O U
T H
G T
S T
A N
D
IN
G H
E
IG
H T
D .F
A C
C E
S S
H
E
IG
H T
D .F
M A
X
NOTE: PROVIDE CANE
DETECTABLE APRON AT
THE STANDING HEIGHT
UNIT
MIN
3' - 6"
MAX
1' - 0"
WATER CLOSET
SIDE WALL
1 1/4" MIN., 2" MAX DIA.
GRAB BAR WITH 1 1/2"
GAP FROM WALL
WATER CLOSET
BACK WALL
TP DISPENSER
MOUNTING AREA
1' - 6"
T .O
G
.B
/2
4' - 6" MIN
MIN
1' - 0"
MIN
2' - 0"
FLUSH CONTROLS
ON OPEN SIDE
M
IN
GB42
GB36
A
A
3' - 4"
/2
GB18
U
CENTER ON
GRAB BAR END
NOTE: GRAB BARS
SHALL BE 33" - 36" TO
TOP OF BAR
MEASURE
TO BOTTOM
OF REFLECTIVE
SURFACE
3' - 0"
6"
6"
8"
MEN WOMEN
NO SMOKING
T O
F
IN
IS
H
E D
F L O
O R
F
IN
IS
H
E D
F L O
O R
T O
T O
F
IN
IS
H
E D
F L O
O R
PROPORTIONS OF THE INTERNATIONAL
SYMBOL OF ACCESSIBILITY
(BRAILLE) (BRAILLE)
INTERIOR SIGNAGE
DOOR FRAME
LATCH SIDE OF
DOOR PANEL
TO TOP OF SIGN
GENERAL NOTES:
PROVIDE INTERIOR SIGNAGE FOR EVERY DOOR/ROOM UNLESS NOTED
OTHERWISE (REFER TO FINISH DRAWINGS).
ALL FINAL ROOM NAMES SHALL BE APPROVED BY ARCHITECT/OWNER PRIOR
TO SIGN FABRIACATION.
AT LOCATIONS WHERE THERE ISN'T AVAILABLE WALL SPACE TO INSTALL THE
INTERIOR SIGNAGE AS INDICATED, OBTAIN ARCHITECT'S INSTRUCTION PRIOR
TO INSTALLATION.
AT LOCATIONS WHERE THERE ISN'T AVAILABLE WALL SPACE, BUT AVAILABLE
WINDOW SPACE, ADHERE INTERIOR SIGNAGE WITH DOUBLE SIDED TAPE TO
PROVIDE A PERMANENT INSTALLATION. PROVIDE A BLANK PANEL OF THE
SAME COLOR, SIZE, AND MATERIAL FOR THE BACK SIDE OF THE SIGN TO BE
INSTALLED ON THE GLASS.
1.
2.
3.
4.
T-SHAPED TURNING SPACE
TURNING RADIUS
ø 5
5' - 0"
2' - 0" 3' - 0"
IF DOOR HAS BOTH
A CLOSER AND LATCH
OTHERWISE THIS = 0"
LATCH APPROACH, PUSH SIDE
Y= 4'-0" MIN IF DOOR HAS
A CLOSER, OTHERWISE Y = 3'-6"
FRONT APPROACH, PUSH SIDE
Y= 4'-6" MIN. IF DOOR HAS
A CLOSER, OTHERWISE
Y = 4'-0" MIN
Y= 4'-0" MIN IF DOOR HAS
BOTH A CLOSER AND LATCH
OTHERWISE Y = 3'-6"
HINGE APPROACH, PUSH SIDE
X= 3'-0" MIN. IF Y= 5'-0"
X= 3'-6" MIN. IF Y= 4'-6"
MIN
2' - 0"
Y M
IN
MIN
1' - 6"
Y X
MIN
2' - 0" Y 1' - 0" Y
1' - 10"
LATCH APPROACH, PULL SIDE FRONT APPROACH, PULL SIDE HINGE APPROACH, PULL SIDE
NTS
TOILET ACCESSORY MOUNTING HEIGHTS
NTS
ACCESSIBLE SIGNAGE DIAGRAMS
NTS
GENERAL - SIGNAGE
NTS
TURNING SPACE
NTS
TYPICAL DOOR APPROACH DETAILS
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic
/C o lu m b ia U n fi n is h e d S p e c C lin ic
V
.r v t
/2
/2
:2
:1
A
M
MK LJ
589A4-20-155
GI102
589A4 - COLUMBIA, MO
JUNE 25, 2021
01-
ADA INFORMATION 100% FINAL CONSTRUCTION
DOCUMENTS
COMPLETE UNFINISHED SPECIALTY
CODE SUMMARYENERGY SUMMARY
PROPERTY LOCATION:
FILL IN INFORMATION WITH BUILDING LOCATION
ZONING:
LAND USE: LAND USE INFORMATION HERE
ZONING DISTRICT: ZONING INFORMATION HERE
RELEVANT CODES:
· 2012 INTERNATIONAL BUILDING CODE, W/ AMENDMENTS
· 2012 INTERNATIONAL PLUMBING CODE, W/ AMENDMENTS
· 2012 INTERNATIONAL MECHANICAL CODE, W/ AMENDMENTS
· 2014 NATIONAL ELECTRICAL CODE, W/ AMENDMENTS
· 2012 INTERNATIONAL ENERGY CONSERVATION CODE, W/ AMENDMENTS
· 2012 INTERNATIONAL FUEL GAS CODE, W/ AMENDMENTS
· FIRE SAFETY CODE: 2012 NFPA 101 LIFE SAFETY CODE, W/ AMENDMENTS
2012 NFPA 1 FIRE CODE, W/ AMENDMENTS
2010 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
· ACCESSIBILITY GUIDELINES:
ICC/ANSI A117.1 - 2009
DEPARTMENT OF JUSTICE 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
· DEPARTMENT OF HEALTH REGULATIONS :
2014 FGI GUIDELINES
USE/OCCUPANCY CLASSIFICATION:
B (BUSINESS) - PER 2012 IBC SECTION 304.1
NEW BUSINESS OCCUPANCY PER 2012 NFPA 101 CHAPTER 38
NEW AMBULATORY HEALTH CARE OCCUPANCY PER 2012 NFPA 101 CHAPTER 20
OCCUPANCY SEPARATION:
ALOWABLE PER 2012 IBC SECTION 422.2: ALLOWABLE PER 2012 NFPA 101
TABLE 6.1.14.4.1(A)
FIRE PARTITION PER SECTION 708 SEPARATING MULTIPLE OCCUPANCY BUSINESS
& AMBULATORY HEALTHCARE
AMB. HEALTHCARE FROM ADJACENT SPACES 1-HOUR SEPARATION REQUIRED
PROVIDED:
1-HOUR SEPARATION @ FLOORPLATES BETWEEN BUSINESS ON FLOORS 1 / 3 AND
AMBULATORY HEALTHCARE ON FLOOR 2
1-HOUR FIRE PARTITION SEPARATING AMBULATORY HEALTHCARE FROM PUBLIC
LOBBY ON FLOOR 2
CONSTRUCTION TYPE:
STEEL STRUCTURAL FRAME; OPEN WEB BAR JOISTS; CONCRETE FLOOR SLAB
OVER METAL
DECK; METAL STUD FRAMED EXTERIOR WALLS AND INTERIOR PARTITIONS
II B - NONCOMBUSTIBLE PER 2012 IBC TABLE 601 / SECTION 602.2
II (000) - NONCOMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIAL PER 2012 NFPA
101 CHAPTER 8.2.1.2
(REF. NFPA 220, TABLE A.4.1.1 / CHAPTER 4.3)
HEIGHT & AREA LIMITATIONS:
ALLOWABLE PER 2012 IBC TABLE 503: ALLOWABLE PER 2012 NFPA 101
CHAPTER 38.1.6.1 & TABLE 20.1.6.1
TYPE II-B CONSTRUCTION, B USE GROUP NO REQUIREMENTS FOR BUSINESS
OCCUPANCY
4 STORIES (PER 504.2 SPRINKLER HEIGHT INCREASE) TYPE II (000),
AMBULATORY HEALTH CARE OCCUPANCY
69,000 SQFT / STORY (PER 506.3 SPRINKLER AREA INCREASE) 2 OR MORE
STORIES PERMITTED WITH SPRINKLERS
PROVIDED:
4 STORIES @ 21,097 SQFT / STORY
LIFE SAFETY SYSTEMS:
FIRE DETECTION, ALARM, AND COMMUNICATION SYSTEM PROVIDED PER 2012
NFPA 101 CHAPTER 9.6
SUPERVISED AUTOMATIC SPRINKLER SYSTEM PROVIDED PER 2012 NFPA 101
CHAPTER 9.7.1
EXIT ACCESS:
ALLOWABLE PER 2012 IBC SECTION 1014.3: ALLOWABLE PER 2012 IBC SECTION
1016.2
100' COMMON PATH (TABLE 1014.3) 300' TRAVEL DISTANCE (TABLE 1016.2)
ALLOWABLE PER 2012 NFPA 101 CHAPTER 38.2.5.3.1: ALLOWABLE PER 2012 NFPA
101 CHAPTER 38.2.6.3:
100' COMMON PATH (TABLE A.7.6) 300' TRAVEL DISTANCE (TABLE A.7.6)
ALLOWABLE PER 2012 NFPA 101 CHAPTER 20.2.6.1: ALLOWABLE PER 2012 NFPA
101 CHAPTER 20.2.6.2:
100' COMMON PATH (TABLE A.7.6) 200' TRAVEL DISTANCE (TABLE A.7.6)
PROVIDED:
LESS THAN 100' @ BOTH FLOORS (CORE & SHELL ONLY)
[TRAVEL DISTANCE PER PHASE 2 - INTERIOR FIT-OUT TO BE DETERMINED]
EXIT ACCESS CORRIDOR WIDTH:
ALLOWABLE PER IBC 2012 SECTION 1005.3.2:
22.2" = 0.15"/PERSON x # PEOPLE @ FLOOR 1 22.2" = 0.15"/PERSON x # PEOPLE @ FLOOR 2
OR 44" MIN. (TABLE 1018.2)
ALLOWABLE PER NFPA 101 2012 CHAPTER 38.2.3.2:
44"
PROVIDED:
NO CORRIDORS PROVIDED FOR PHASE 1 - CORE & SHELL
CORRIDOR WIDTH TO BE IN EXCESS OF 44" FOR PHASE 2 - INTERIOR FIT-OUT
EXIT ACCESS CORRIDOR RATING:
ALLOWABLE PER 2012 IBC TABLE 1018.1
NO RATING REQUIRED W/ SPRINKLER SYSTEM
ALLOWABLE PER 2012 NFPA 101 CHAPTER 20.3.6.1 & CHAPTER 38.3.6.1(3)
NO RATING REQUIRED W/ SPRINKLER SYSTEM
PROVIDED:
NO RATING
ELEVATOR LOBBY:
NOT REQUIRED PER 2012 IBC SECTION 713.14.1 EXCEPTION 4
ELEVATOR LOBBY NOT REQUIRED WITH SPRINKLERS
EXIT SEPARATION DISTANCE:
ALLOWABLE PER 2012 NFPA 101 SECTION 7.5.1.3.3:
234'-6" DIAGONAL X 1/3 MIN. ALLOWABLE = 78'-2" MIN.
PROVIDED:
212'-4"
EXIT STAIR WIDTH:
ALLOWABLE PER 2012 IBC SECTION 1005.3.1:
205 MAX. OCCUPANTS / STORY @ 0.20" PER OCCUPANT = 41" EGRESS WIDTH
41" EGRESS WIDTH DIVIDED BY TWO STAIRWAYS = 20.5" PER STAIRWAY
REQUIRED 44" MIN. (SECTION 1009.4)
ALLOWABLE PER 2012 NFPA 101 TABLE 7.3.3.1:
205 MAX. OCCUPANTS / STORY @ 0.30" PER OCCUPANT = 61.5" EGRESS WIDTH
61.5" EGRESS WIDTH DIVIDED BY TWO STAIRWAYS = 30.75" PER STAIRWAY
REQUIRED 44" MIN. (TABLE 7.2.2.2.1.2(B) FOR LESS THAN 2,000 PERSONS):
PROVIDED:
48" @ BOTH EGRESS STAIRS
EXIT STAIR ENCLOSURE RATING:
ALLOWABLE PER 2012 IBC SECTION 1022.2
2-HOUR CONNECTING FOUR STORIES OR MORE
ALLOWABLE PER 2012 NFPA 101 CHAPTER A.7.1.3.2.1(3)
2-HOUR CONNECTING FOUR STORIES OR MORE
PROVIDED:
2-HOUR
SHAFT ENCLOSURE RATING:
ALLOWABLE PER 2012 IBC SECTION 713.4
2-HOUR CONNECTING FOUR STORIES OR MORE
ALLOWABLE PER 2012 NFPA 101 CHAPTER 8.6.5(1)
2-HOUR CONNECTING FOUR STORIES OR MORE
PROVIDED:
2-HOUR
AREA OF REFUGE / ACCESSIBLE MEANS OF EGRESS:
PROVIDED PER 2012 IBC SECTION 1007.2.1, 1007.3 EXCEPTIONS 1 & 2, 1007.4
PROVIDED PER 2012 NFPA 101 CHAPTER 7.2.12.1.1 & 7.2.12.2.4
PLUMBING FIXTURE REQUIREMENTS:
ALLOWABLE PER 2012 IBC TABLE 2902.1
FLOOR 1 OCCUPANCY = 74 MEN / 74 WOMEN (148 TOTAL)
WATER CLOSETS REQUIRED = 3 MEN / 3 WOMEN
(EACH GENDER: 1 PER 25 FIRST 50; 1 PER 50 REMAINDER)
LAVATORIES REQUIRED = 2 MEN / 2 WOMEN
(EACH GENDER: 1 PER 40 FIRST 80; 1 PER 80 REMAINDER)
DRINKING FOUNTAINS REQUIRED = 2
(1 PER 100)
SERVICE SINKS REQUIRED = 1
FLOOR 2 OCCUPANCY = 74 MEN / 74 WOMEN (148 TOTAL)
WATER CLOSETS REQUIRED = 3 MEN / 3 WOMEN
(EACH GENDER: 1 PER 25 FIRST 50; 1 PER 50 REMAINDER)
LAVATORIES REQUIRED = 2 MEN / 2 WOMEN
(EACH GENDER: 1 PER 40 FIRST 80; 1 PER 80 REMAINDER)
DRINKING FOUNTAINS REQUIRED = 2
(1 PER 100)
SERVICE SINKS REQUIRED = 1
PROVIDED:
FLOOR 1
WATER CLOSETS = 1 MEN / 1 WOMEN (10 UNISEX PER TENANT BUILD-OUT)
LAVATORIES = 1 MEN / 1 WOMEN (10 UNISEX PER TENANT BUILD-OUT)
DRINKING FOUNTAINS = (2 PER TENANT BUILD-OUT)
SERVICE SINKS = 1
FLOOR 2
WATER CLOSETS = 1 MEN / 1 WOMEN (6 UNISEX PER TENANT BUILD-OUT)
LAVATORIES = 1 MEN / 1 WOMEN (6 UNISEX PER TENANT BUILD-OUT)
DRINKING FOUNTAINS = (2 PER TENANT BUILD-OUT)
SERVICE SINKS = 1
SLAB-ON-GRADE FLOOR ASSEMBLY:
REQUIRED PER IECC 2012 AMENDED TABLE C402.2:
UNHEATED SLAB, R-10 EXTENDING 24" BELOW SLAB
PROVIDED:
R-10 EXTRUDED POLYSTYRENE 2" RIGID INSULATION EXTENDING 24"
MIN. BELOW SLAB
EXTERIOR WALL ASSEMBLY:
REQUIRED PER IECC 2012 AMENDED TABLE C402.2:
METAL-FRAMED BUILDING, R-13 + R-7.5 C.I.
PROVIDED:
R-21 FIBERGLASS BATT 51/2" INSUL. IN STUD CAVITY W/ CONTINUOUS MIN. R-10
EXTRUDED POLYSTYRENE 2" MIN. RIGID EXTERIOR INSULATION
ROOF ASSEMBLY:
REQUIRED PER IECC 2012 AMENDED TABLE 402.2:
INSUL. ENTIRELY ABOVE DECK, R-25 C.I.
PROVIDED:
FLAT ROOF - CONTINUOUS R-25 POLYISOCYANURATE 4" MIN. RIGID INSULATION
FENESTRATION:
REQUIRED PER IECC 2012 AMENDED TABLE C402.3:
FIXED FENESTRATION U-0.38 MAX.
ENTRANCE DOORS U-0.77 MAX.
SHGC (ALL COMPONENTS) 0.40 MAX.
PROVIDED:
FIXED WINDOW UNITS U-0.38 MAX.
FIXED CURTAIN WALL SYSTEM U-0.38 MAX.
ENTRANCE DOORS U-0.77 MAX.
SHGC (ALL COMPONENTS) 0.40 MAX.
NOTE: THESE DRAWINGS DO NOT
INCLUDE IBC BUILDING CODE
INFORMATION
CODE NOTES - BASEMENT FLOOR
1. DRAWING PURPOSE : NFPA CODE COMPLIANCE
2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING CODES:
A. 2018 NFPA 101 LIFE SAFETY CODE
a. CHAPTER 4 - GENERAL
b. CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD CONTENTS
c. CHAPTER 7 - MEANS OF EGRESS
d. CHAPTER 19 - EXISTING HEALTHCARE OCCUPANCY
3. OWNER:
HARRY S. TRUMAN MEMORIAL HOSPITAL
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
PH (573) 814-6000
4. ARCHITECT:
ROMANYK CONSULTING
3308 PRESTON ROAD
SUITE 350-164
PLANO, TEXAS
5. ARCHITECT SEAL: SEE STAMP IN TITLEBLOCK
6. FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT
7. INSPECTION: JCHO; CITY OF COLUMBIA
8. OCCUPANCY GROUP TYPE:
a. OCCUPANCY 1/ BUILDING 1/ BASEMENT: EXISTING HEALTHCARE OCCUPANCY
9. CONSTRUCTION TYPE:
CONSTRUCTION TYPE II - NFPA TYPE 222, (TABLE 19.1.6.1)
10. BUILDING 1 - OCCUPANCY 1 GROSS FLOOR AREAS - BASEMENT FLOOR AREA ACTUAL: 158,877 SF (TOTAL FLOOR)
6,920 SF (AREA OF WORK)
11. HEIGHT & AREA LIMITATIONS:
ALLOWABLE AREA: UNLIMITED
HEALTH CARE OCCUPANCY:
ALLOWABLE HEIGHT/ 4 OR MORE
STORIES
ACTUAL HEIGHT/STORIES 7 OCCUPIABLE STORIES
12. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):
CONSTRUCTION TYPE II (222)
HEALTHCARE
OCCUPANCY
BEARING WALLS:
A. EXTERIOR 2 HR
B. INTERIOR 2 HR
C. INT/EXT (ROOF ONLY) 1 HR
NON-BEARING WALLS:
A. EXTERIOR 0 HR
B. INTERIOR NON-COMBUSTIBLE
COLUMNS:
A. SUPPORT FLOORS 2 HR
B. SUPPORT ROOF ONLY 1 HR
BEAMS/GIRDER/TRUSSES:
A. EXTERIOR: 2 HR
B. INTERIOR: 1 HR
FLOOR CONSTRUCTION: 2 HR
ROOF CONSTRUCTION: 1 HR
13. ACTIVE FIRE SAFETY FEATURES:
a. AUTOMATIC SUPPRESSION SYSTEMS:
• SPRINKLER SYSTEM (FULLY SPRINKLED)
• AUTOMATIC AIR-HANDLING SHUT-DOWN
b. FIRE ALARM SYSTEM - SIMPLEX, ADDRESSABLE, AUTO DIAL-UP
c. GENERATOR POWERED EMERGENCY LIGHTING, GENERATOR POWERED
d. EXIT LIGHTING.
e. PORTABLE EXTINGUISHERS
f. SMOKE DETECTORS AT ALL CORRIDORS, ALL SMOKE DOORS AND MISC
AREAS AS REQ'D (ALSO IN SOME DUCTS)
14. WATER SUPPLY: CITY OF COLUMBIA
15. SPRINKLERS: FULLY SPRINKLERED
16. TOTAL OCCUPANTS
TABLE 7.3.1.2 OCCUPANT LOAD FACTOR
USE (FT2 /PERSON)
HEALTHCARE USE
INPATIENT TREATMENT DEPARTMENTS 240
SLEEPING DEPARTMENTS 120
AMBULATORY HEALTH CARE 150
OCCUPANT LOAD = FLOOR AREA/OCCUPANT LOAD FACTOR (TABLE 7.3.1.2)
BUILDING 1
BASEMENT FLOOR (AREA OF WORK): 6,920/150 = 46" (MEANS OF EGRESS WIDTH CANNOT BE LOWER THAN THIS)
17. MEANS OF EGRESS: TWO MEANS OF EGRESS, AS A MINIMUM REQUIRED (4.5.3.1).
ACTUAL MEANS OF EGRESS (BASEMENT FLOOR): 2 MEANS OF EGRESS
18. DOOR OPENINGS IN MEANS OF EGRESS: SHALL BE NO LESS THAN
32" IN CLEAR WIDTH (7.2.1.2.3.2). DOOR OPENINGS IN PROJECT ARE 42".
19. DEAD END CORRIDORS: DEAD END CORRIDORS SHALL NOT EXCEED 30 FEET (TABLE A.7.6)
ACTUAL PROJECT DEAD END CORRIDOR (BASEMENT FLOOR) = 24 FEET.
20. TABLE 7.3.3.1 CAPACITY FACTORS: STAIRWAY (WIDTH/PERSON), HEALTHCARE,
SPRINKLERED = .2 INCHES (LEVEL COMPONENTS AND RAMPS)
21. CORRIDOR WIDTH: AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED
FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE NOT LESS THAN
44 INCHES IN CLEAR AND UNOBSTRUCTED WIDTH (19.2.3.4).
ACTUAL CORRIDOR WIDTH (2ND FLOOR): 72 INCHES (MIN.)
22. NUMBER OF EXITS FOR EACH STORY: NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON
EACH STORY 19.2.4.2). ACTUAL PROJECT EXITS = 2.
23. TRAVEL DISTANCE TO EXITS= THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 150 FEET(19.2.6.2.1). ACTUAL TRAVEL DISTANCE 147 FEET (BASEMENT FLOOR).
24. TABLE A.7.6 COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (BY OCCUPANCY)
TYPE OF OCCUPANCY COMMON PATH LIMIT DEAD END LIMIT TRAVEL DISTANCE LIMIT
(SPRINKLERED) (SPRINKLERED) (SPRINKLERED)
EXISTING HEALTH CARE NO REQUIREMENT 30 FEET 200 FEET
CODE NOTES - 3RD FLOOR
1. DRAWING PURPOSE : NFPA CODE COMPLIANCE
2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING CODES:
A. 2018 NFPA 101 LIFE SAFETY CODE
a. CHAPTER 4 - GENERAL
b. CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD CONTENTS
c. CHAPTER 7 - MEANS OF EGRESS
d. CHAPTER 19 - EXISTING HEALTHCARE OCCUPANCY
3. OWNER:
HARRY S. TRUMAN MEMORIAL HOSPITAL
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
PH (573) 814-6000
4. ARCHITECT:
ROMANYK CONSULTING
3308 PRESTON ROAD
SUITE 350-164
PLANO, TEXAS
5. ARCHITECT SEAL: SEE STAMP AREA IN TITLEBLOCK
6. FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT
7. INSPECTION: TJC; CITY OF COLUMBIA
8. OCCUPANCY GROUP TYPE: OCCUPANCY 1/ BUILDING 1/ THIRD FLOOR: EXISTING HEALTHCARE OCCUPANCY
9. CONSTRUCTION TYPE: CONSTRUCTION TYPE II - NFPA TYPE 222, (TABLE 19.1.6.1)
10. BUILDING GROSS FLOOR AREA: 3RD FLOOR AREA: 26,865 SF (TOTAL FLOOR AREA)
6,490 SF (AREA OF WORK)
11. HEIGHT & AREA LIMITATIONS:
ALLOWABLE AREA: UNLIMITED
HEALTH CARE OCCUPANCY:
ALLOWABLE HEIGHT/ 4 OR MORE
STORIES
ACTUAL HEIGHT/STORIES 7 OCCUPIABLE STORIES
12. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):
HEALTHCARE
OCCUPANCY
CONSTRUCTION TYPE II (222)
BEARING WALLS:
A. EXTERIOR 2 HR
B. INTERIOR 2 HR
C. INT/EXT (ROOF ONLY) 1 HR
NON-BEARING WALLS:
A. EXTERIOR 0 HR
B. INTERIOR NON-COMBUSTIBLE
COLUMNS:
A. SUPPORT FLOORS 2 HR
B. SUPPORT ROOF ONLY 1 HR
BEAMS/GIRDER/TRUSSES:
A. EXTERIOR: 2 HR
B. INTERIOR: 1 HR
FLOOR CONSTRUCTION: 2 HR
ROOF CONSTRUCTION: 1 HR
13. ACTIVE FIRE SAFETY FEATURES:
a. AUTOMATIC SUPPRESSION SYSTEMS:
• SPRINKLER SYSTEM (FULLY SPRINKLED)
• AUTOMATIC AIR-HANDLING SHUT-DOWN
b. FIRE ALARM SYSTEM - SIMPLEX, ADDRESSABLE, AUTO DIAL-UP
c. GENERATOR POWERED EMERGENCY LIGHTING
d. EXIT LIGHTING.
e. PORTABLE EXTINGUISHERS
f. SMOKE DETECTORS AT ALL CORRIDORS, ALL SMOKE DOORS AND
AREAS AS REQ'D.
14. WATER SUPPLY: CITY OF COLUMBIA
15. SPRINKLERS: FULLY SPRINKLERED
16. TOTAL OCCUPANTS
TABLE 7.3.1.2 OCCUPANT LOAD FACTOR
USE (FT2 /PERSON)
HEALTHCARE USE
INPATIENT TREATMENT DEPARTMENTS 240
SLEEPING DEPARTMENTS 120
AMBULATORY HEALTH CARE 150
OCCUPANT LOAD = FLOOR AREA/OCCUPANT LOAD FACTOR (TABLE 7.3.1.2)
BUILDING 1
4TH FLOOR (AREA OF WORK): 6,490/150 = 43 TOTAL OCCUPANTS
17. EXIT WIDTH: TABLE 7.3.3.1 CAPACITY FACTORS
EXIT WIDTH STAIRS: 34 OCCUPANTS X.3 INCHES = 10.2" (SCOPE OF WORK)
EXIT WIDTH LEVEL COMPONENTS: 34 X .2 INCHES = 6.8" (SCOPE OF WORK)
18. MEANS OF EGRESS: MINIMUM REQUIRED TWO MEANS OF EGRESS (4.5.3.1)
ACTUAL MEANS OF EGRESS (3RD FLOOR): 2 MEANS OF EGRESS
19. DOOR OPENINGS IN MEANS OF EGRESS: SHALL BE NO LESS THAN 32" IN CLEAR WIDTH (7.2.1.2.3.2).
DOOR OPENINGS IN PROJECT ARE 42" MINIMUM.
20. DEAD END CORRIDORS: DEAD END CORRIDORS SHALL NOT EXCEED 30 FEET. (TABLE A.7.6)
ACTUAL PROJECT DEAD END CORRIDOR (3RD FLOOR) = 25'
21. TABLE 7.3.3.1 CAPACITY FACTORS: STAIRWAY (WIDTH/PERSON), HEALTHCARE,
SPRINKLERED = .2 INCHES (LEVEL COMPONENTS AND RAMPS)
22. CORRIDOR WIDTH: AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED
FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE NOT LESS THAN
44 INCHES IN CLEAR AND UNOBSTRUCTED WIDTH (19.2.3.4).
ACTUAL CORRIDOR WIDTH (3RD FLOOR): 72"
23. NUMBER OF EXITS FOR EACH STORY: NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON
EACH STORY 19.2.4.2). ACTUAL PROJECT EXITS = 2.
24. TRAVEL DISTANCE TO EXITS: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND
AN EXIT SHALL NOT EXCEED 150 FEET(19.2.6.2.1). 19.2.6.2.2
THE MAXIMUM TRAVEL DISTANCE SPECIFIED IN 19.2.6.2.1
SHALL BE PERMITTED TO INCREASE BY 50 FEET IN BUILDINGS
PROTECTED BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER
SYSTEM IN ACCORDANCE WITH 19.3.5.7.
ACTUAL MAX TRAVEL DISTANCE: 194'- 2" (3RD FLOOR).
25. TABLE A.7.6 COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (BY OCCUPANCY)
TYPE OF OCCUPANCY COMMON PATH LIMIT DEAD END LIMIT TRAVEL DISTANCE LIMIT
(SPRINKLERED) (SPRINKLERED) (SPRINKLERED)
EXISTING NO REQUIREMENT 30 FEET 200 FEET
NOTE: THESE DRAWINGS DO NOT
INCLUDE IBC BUILDING CODE
INFORMATION
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
B
IM
/V
IS
N
C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic
/C o lu m b ia U n fi n is h e d S p e c C lin ic
V
.r v t
/2
/2
:2
:2
A
M
MK LJ
589A4-20-155
GI103
589A4 - COLUMBIA, MO
JUNE 25, 2021
01-
BUILDING CODE 100% FINAL CONSTRUCTION
DOCUMENTS
COMPLETE UNFINISHED SPECIALTY
LIFE SAFETY NOTES
FE
FEC
LIFE SAFETY LEGEND
BASEMENT FLOOR KEY PLAN
AREA OF
WORK
H H
6.3
6.3
5.6
5.6
GG
FF
10.6
10.6
11.5
11.5 E.1
E.1E
E
D D
C C
B B
A A
GRAY AREA NOT IN
PROJECT SCOPE
E001
PHARMACY
FILLING
ASSEMBLY
E001D
TEAM
WORK
AREA
E001C
OFFICE 1
E001B
OFFICE 2
E001A
EXISTING
NARCOTIC
VAULT
SECURED DISPENSING /
STORAGE, INPATIENT
E001E
E001L
POS ISO
ANTEROOM
E001H
POS ISO
NON-HD
BUFFER
E001F
STORAGE
E001J
NEG ISO
HAZ
BUFFER
E001K
NEG HD
STORAGE
E001G
EXISTING
STAIR #11
46"
247/2
24.6"
BLDG 1 - OCCUPANCY 1 - BASEMENT =
158,877 SF (AREA OF WORK)
OCCUPANCY TYPE - BUSINESS
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS = 1060
FULLY SPRINKLERED
2 3/4"5 7/16"
TRAVEL DISTANCE: 105' - 0"
TRAVEL DISTANCE: 127' - 4"
TEMPORARY CONSTRUCTION
BARRIER WITH 3'0" x 7'0" FIRE RATED
PARTITION
TEMPORARY CONSTRUCTION
BARRIER
SMOKE
COMPARTMENT #0-0
17000SF
80"
24.8"
247/2
TRAVEL DISTANCE: 63' - 6"
T R
A V
E L D
IS
T
A N
C E
EXIT
COMPLIANCE NOTES PER NFPA
3.9.3.2.1 & 9.7.1.1 (2)
HAZARDOUS AREAS IN FULLY
SPRINKLERED BUILDINGS ARE NOT
REQUIRED TO BE PROTECTED BY FIRE
BARRIERS.
COMPLIANCE NOTES PER NFPA 7.3.13
BUSINESS OCCUPANCY LOAD FACTOR
150 158,877 / 150 = 1060 OCC.
1. THIS PLAN IS FOR LIFE SAFETY INFORMATION ONLY.
2. BUILDING IS FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13
AND IS PROTECTED WITH A SUPERVISED AUTOMATIC SMOKE
DETECTION SYSTEM.
3. REFER TO THIS DRAWING FOR MEANS OF EGRESS
4. REFER TO THIS DRAWING FOR DOOR CAPACITIES.
5. FINAL LOCATION OF FAAP PANEL TO BE COORDINATED WITH FIRE
MARSHAL.
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FDC
F
L
L
D
MHO
FACP
FAAP
FIRE DEPARTMENT CONNECTION
EXIT
ILLUMINATED EXIT SIGN
FIRE ALARM - MANUAL PULL STATION
FIRE ALARM - STROBE / CHIME
FIRE ALARM - STROBE
SMOKE DETECTOR
MAGNETIC HOLD OPEN
FIRE ALARM CONTROL PANEL
FIRE ALARM ANUNCIATOR PANEL
EXTERIOR EMERGENCY LIGHTING
TRAVEL
PATH
STARTING
LOCATION
TD = XX
TRAVEL DISTANCE
NO. OF OCC./
NO. OF EXITS
ACTUAL
EXIT
WIDTH
OCC.
LOAD
FACTOR
FACP
FSA
FAA
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR ALARM
ANNUNCIATOR PANEL
LIFE SAFETY SYMBOLS
10/1
2"
34"
1:50
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
NEW
PARTITION KEY
NFPA
101-2015
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
(FIRE WALL IN IBC)
2 HR 90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR 90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS (SPRINKLERED)
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
VERT. OPG. (SHAFT)
FIRE BARRIER
60 MIN
[D]
1 HR
2 HR
60 MIN
90 MIN
EXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
8.7
NFPA 6.1.14.4.1
18.1.3.5.1 19.1.3.5.1
NFPA 7.2.A.3.1 (1)
NFPA 18.1.3.8/
19.1.3.8 18.2.2.5/19.2.25 7.1.3.2.1
NFPA 19.3.1.1
NFPA 8.6.2
8.6.5
NFPA 18.3.2.1.2
NFPA 8.4.1.1
19.3.2.1
NFPA 8.4.2 (3)
18.3.2.1.3 19.3.2.1.2
NFPA 8.5.2
18.3.7.3 19.3.7.3
NFPA 8.4.2
18.2.5.7.1.4 19.2.5.7.1.1
NFPA 8.4.2
18.3.6.2 19.3.6.2
21.3.6 39.3.6
NFPA 19.3.1.1
19.2.2.7 8.6.2 8.6.5(3) & 2
NFPA 7.2.6
19.2.2.7 18.2.2.7
NFPA 221
8.2.1.3
EXIST SOL.
CORE WD.
NFPA 7.2.1.4.1
7.2.4.3.7 8.3.4 18.2.2.5.3,4,5,6,7 19.2.2.5,3,4
8.3.4.2 TBL
18.4.4.7.2.2
7.1.3.2.9 (9)
NFPA 8.3.4.2 TBL
19.3.2.1.3,5
NFPA 8.3.4.2 TBL
8.5.4 18.3.7.8
NFPA 8.3.4.2 TBL
8.3.4.2 TBL
8.3.4.2 TBL
NFPA 8.3.4.2 TBL
8.3.4.2 8.4.3 19.3.2.1.4,3,5
8.4.3
8.4.3 18.3.6.4.1 19.3.6.4.1
N/A
FIRE
90 MIN
FIRE
90 MIN
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
NFPA 90
8.3.5.7 9.2.1
NFPA 8.3.5.7
9.2.1 7.2.4.3.5
N/A
8.5.5.2 18.3.7.3(2) 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4.1 8.4.6.2
8.4.4.1 8.4.6.2
8.4.4.1 8.4.6.2 18.3.6.4.1
N/A
WALL
RATING
RATED UL
ASSEMBLIES
2 HR
1 HR
1 HR
NR-
RESIST
SMK
NR
NR-
RESIST
SMK
NR
8.3
UL U412
UL U419
UL U412
UL U419
UL U412
UL U419
UL U412
UL U419
UL U415 (A)
UL U412
UL U419
UL U415 (A)
UL U412
UL U419
UL U412
UL U419
UL U415 (A)
NR
SELF OR AUTO
CLOSING
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR ONLY
NFPA 90
8.3.5.7 9.2.1
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Spinklered
Office of Construction and Facilities Management
NORTH
FULLY SPRINKLERED
B
IM
/V
IS
N
C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic
/C o lu m b ia U n fi n is h e d S p e c C lin ic
V
.r v t
/2
/2
:2
:2
A
M
MK LJ
589A4-20-155
GI104
589A4 - COLUMBIA, MO
JUNE 25, 2021
01-
BASEMENT LIFE SAFETY PLAN 100% FINAL CONSTRUCTION
DOCUMENTS
COMPLETE UNFINISHED SPECIALTY
CLINIC
1" = 10'-0"
BASEMENT OVERALL FLOOR PLAN
LIFE SAFETY NOTES
FE
FEC
LIFE SAFETY LEGEND
DN
DN
1. THIS PLAN IS FOR LIFE SAFETY INFORMATION ONLY.
2. BUILDING IS FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13
AND IS PROTECTED WITH A SUPERVISED AUTOMATIC SMOKE
DETECTION SYSTEM.
3. REFER TO THIS DRAWING FOR MEANS OF EGRESS
4. REFER TO THIS DRAWING FOR DOOR CAPACITIES.
5. FINAL LOCATION OF FAAP PANEL TO BE COORDINATED WITH FIRE
MARSHAL.
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FDC
F
L
L
D
MHO
FACP
FAAP
FIRE DEPARTMENT CONNECTION
EXIT
ILLUMINATED EXIT SIGN
FIRE ALARM - MANUAL PULL STATION
FIRE ALARM - STROBE / CHIME
FIRE ALARM - STROBE
SMOKE DETECTOR
MAGNETIC HOLD OPEN
FIRE ALARM CONTROL PANEL
FIRE ALARM ANUNCIATOR PANEL
EXTERIOR EMERGENCY LIGHTING
THIRD FLOOR KEY PLAN
AREA OF
WORK
H H
6.3
6.3
5.6
5.6
GG
FF
10.6
10.6
11.5
11.5 E.1
E.1E
E
D D
C C
B B
ANTEROOM
F359
NON-HAZARDOUS IV PREP
F361
F360
HAZARDOUS
IV
PREP/STORAGE
F364
MED.
ROOM
F362
CLEAN
DISPATCH
F363
SOILED
DISPATCH
TOILET
F365
F374
NURSE
STATION
F386
INFUSION
BAY
F372
INFUSION
BAY
F371
INFUSION
BAY
F375
INFUSION
BAY
F376
INFUSION
BAY
F377
INFUSION
BAY
F378
INFUSION
BAY
F380
PRIVATE
INFUSION
F381
PRIVATE
INFUSION
TOILET
F382
E310
INTAKE
F389
EXAM
ROOM
F391
EXAM
ROOM
F392
EXAM
ROOM
F393
EXAM
ROOM
WHEELCHAIR STORAGE
ALCOVE
F390
F385
PATIENT
TOILET
NOURISH
F383
CORRIDOR
F373
CORRIDOR
F358
F352
EXAM
ROOM
F353
PROVIDERS
ROOM SWAMP
F354 F355
PROVIDERS
ROOM
F356
NURSE
NAVIGATOR
F357
WORK
ROOM
F366
INFUSION
BAY
F367
INFUSION
BAY
F368
INFUSION
BAY
EXISTING OUTDOOR
GARDEN
F370
F379
EQUIPMENT
ALCOVE
E303
WORK
AREA
RECEPTION
E302
HEM/ONC WAITING
E301
EXISTING CORRIDOR
F394
F369
INFUSION
BAY
GRAY AREA NOT IN PROJECT
SCOPE
EXISTING
SMOKE
COMP 3-7
7219 SF
EXISTING
SMOKE
COMP 3-6
18819 SF
STAIR #11
F395
TEMPORARY CONSTRUCTION
BARRIER
TRAVEL DISTANCE: 105' - 9"
TRAVEL DISTANCE: 194' - 2 "
TRAVEL DISTANCE: 123' - 11"
TEMPORARY CONSTRUCTION
BARRIER
BLDG 1 -…