Revised Columbia USC Amendment 1 - Combined Drawings.pdf

PDF 10 MB Posted

Attached to
Z2DA--Complete Unfinished Specialty Clinic P/N: 589A4-20-155
Solicitation number
36C25521R0106
Issued by

About this file

This document provides details for a federal contract solicitation to complete unfinished specialty clinics at a Veterans Affairs medical center. The solicitation seeks to renovate approximately 6,490 square feet of shell space on the third floor and 6,290 square feet of an existing inpatient pharmacy on the basement floor at the VA Harry S. Truman Memorial Hospital in Columbia, Missouri. Renovations include demolishing and constructing new exam rooms, infusion bays, patient toilets, nurse stations, and office spaces on the third floor as well as renovating the pharmacy to comply with compounding guidelines by separating hazardous and non-hazardous materials areas. The solicitation will be available for download on or about July 16, 2021 with proposals due on or about August 18, 2021. The contract is set aside for Service-Disabled Veteran-Owned Small Businesses and award will be made using best value low price technically acceptable source selection. The estimated price range for the project is $2,000,000 to $5,000,000 and work must be completed within 300 calendar days of the notice to proceed.

View the file

Other files

File Type Posted
36C25521R0106 0003 Amendment 3.pdf PDF
QH101 - BASEMENT EQUIPMENT PLAN.pdf PDF
Amendment 3 Narrative.docx DOCX document
QH102 - THIRD FLOOR EQUIPMENT PLAN.pdf PDF
36C25521R0106 0002 Amendment 2.pdf PDF
Amendment 2-ATTENDANCE ROSTER- Complete Unfinished Specialty Clinic_08032021.xlsx XLSX spreadsheet
090600 Schedule for Finishes_amendment 1.pdf PDF
066060 Plastic Fabrications amendment 1.pdf PDF
077100 Roof Specialties_amendment 1.pdf PDF
072200 Roof and Deck Insulation amendment 1.pdf PDF
077200 Roof Accessories_amendment 1.pdf PDF
083459 Vaults and Day Gates_amendment 1.pdf PDF
111736 Package Transfer Units_amendment 1.pdf PDF
076000 Flashing and Sheet Metal_amendment 1.pdf PDF
075423 Thermoplastic Polyolefin -TPO- Roofing_amendment 1.pdf PDF
36C25521R0106 0001- Amendment 1.pdf PDF
072727 Fluid-Applied Membrane Air Barrier- Vapor amendment 1.pdf PDF
224000 Plumbing Fixtures amendment 1.pdf PDF
096723_20 Resinous with Vinyl Chip Broadcast_amendment 1.pdf PDF
149200 Pneumatic Tube System amendment 1.pdf PDF
Complete Unfinished Specialty Clinics Specifications VOL 1- 486 pages.pdf PDF
589A4-20-155-Final Drawings 072121 VOL 1 - 47 pages.pdf PDF
Complete Unfinished Specialty Clinics-589A4-20-155 Specifications VOL 2-742 pages.pdf PDF
36C25521R0106.docx DOCX document
589A4-20-155-Final Drawings 072121 VOL 2 - 60 Pages.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

KEY NOTES

LEGEND

10.6

10.6

11.5

11.5

D D

C C

B B

A A

GRAY AREA NOT IN

PROJECT SCOPE

STORAGE

E001G

OFFICE

E002K

2 3 4

TYP. IN ALL

DEMO AREAS

PHARMACY FILLING & ASSEMBLY

E001

PHARM. SVC.

E002N

CHIEF PHARM. SVC.

E002M

ANTI-COAGULATION OFFICE

E002O

ADMIN. OFFICER PHARM.

E002P

OUTPATIENT PHARM.

E002E

OFFICE

E002L

SUPV. INPATIENT PHARM.

E002F

STAGING RM.

E002D

ANTE RM.

E002C

STER./IV PREP

E002B

CORR.

CBE1

NARCOTIC VAULT

E001A

HALL

E001H

2 3 4

TYP. IN ALL

DEMO AREAS

2 3 4

TYP. IN ALL

DEMO AREAS

BASEMENT FLOOR KEY PLAN

AREA OF

WORK

1. REFER TO ENLARGED FLOOR PLANS, ELEVATIONS

AND DETAILS ON OTHER DRAWING SHEETS FOR

ADDITIONAL DETAILS OF NEW WORK.

2. REFER TO SHEET SERIES FP, P, M, E, T AND V FOR

ADDITIONAL DETAIL OF DEMOLITION AND NEW WORK

RELATED TO THOSE DISCIPLINES.

3. REPAIR ALL WALL CONDITIONS THAT ARE IMPACTED

BY DEMOLITION WITH 5/8" GYPSUM BOARD AND COLD

FORMED METAL FRAMING (MATCH EXISTING DEPTH

AND WALL FINISH). PROVIDE/INSTALL ALL

COMPONENTS AS PREVIOUSLY INDICATED TO

ACHIEVE A CONSISTENT AESTHETIC/FINISH.

4. ALL COMPONENTS INDICATED TO BE REMOVED AND

SALVAGED SHALL BE LABELED AND RETURNED TO

THE OWNER. COORDINATE WITH COR FOR

LOCATIONS.

5. ALL COMPONENTS INDICATED ONLY TO BE REMOVED

SHALL BE DISPOSED OFF-SITE DAILY

6. DEMOLITION PLAN DIMENSIONS SHALL BE FROM

EXISTING FACE OF FINISHED WALL PARTITION

UNLESS NOTED OTHERWISE. ALL DIMENSIONS ARE

APPROXIMATE AND SHALL BE FIELD VERIFIED PRIOR

TO BEGINNING DEMOLITION

7. ALL DEMOLITION SCOPE OF WORK INDICATED ON

THESE DRAWINGS SHALL BE COORDINATED WITH THE

OTHER CONSULTANT/DISCIPLINE DRAWINGS AS WELL

(REFER TO THEIR DRAWINGS FOR ADDITIONAL

DETAILS)

8. DEMOLITION SHALL BE TO THE MAX EXTENT POSSIBLE

IN ORDER TO COMPLETE THE SCOPE OF WORK

(ADVISE THE ARCHITECT OF ANY DISCREPANCIES

BEFORE PROCEEDING WITH THE AFFECTED

DEMOLITION CONDITIONS)

9. THE GENERAL CONTRACTOR (GC) SHALL BE

RESPONSIBLE FOR TAKING ADEQUATE PRECAUTIONS

TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND

EXISTING FINISHES THROUGHOUT ALL PHASES OF

CONSTRUCTION. ANY DAMAGE TO THE EXISTING

COMPONENTS, WHICH HAVE NOT BEEN IDENTIFIED

FOR REMOVAL/DEMOLITION, SHALL BE RESTORED TO

THE ORIGINAL CONDITION AT THE GC'S EXPENSE

10. GC IS RESPONSIBLE FOR KEEPING A CLEAN AND

SAFE ENVIRONMENT THROUGHOUT CONSTRUCTION

11. GENERAL CONTRACTOR (GC) SHALL COMPLY WITH

VA'S ICRA REQUIREMENTS. COORDINATE WITH VA

PRIOR TO COMMENCING ANY DEMOLITION ACTIVITIES

12.ALL WALL PARTITIONS SHALL BE REMOVED DECK TO

DECK.

13.ALL CABLING SHALL BE REMOVED BACK TO POINT OF

ORIGIN (WHICH MAY REQUIRE WORK OUTSIDE THIS

FOOTPRINT).

14.AFTER DEMO, GENERAL CONTRACTOR WILL FIELD

VERIFY MEASUREMENTS AND CONDITIONS PRIOR TO

BEGINNING NEW CONSTRUCTION.

15.GENERAL CONTRACTOR (GC) SHALL PROVIDE

DETAILED DEMO PLAN WHICH CLEARLY SHOWS HOW

ACCESS TO/FROM OCCUPIED AREAS IS MAINTAINED.

16.WORK SHALL BE NIGHTS/WEEKENDS AND

COORDINATED WITH THE COR 2 WEEKS AHEAD OF

TIME.

NO SCOPE OF WORK ASSOCIATED WITH

THIS OCCUPIED AREA

SCOPE OF WORK AREA AS DESIGNATED/NOTED

WITH BLACK BORDER

EXISTING WALL AND ASSOCIATED COMPONENTS

SHALL BE REMOVED - REFER TO DEMOLITION

KEYNOTES FOR ADDITIONAL DETAILS AT SPECIFIC

CONDITIONS.

EXISTING DOOR, FRAME, HARDWARE AND

ASSOCIATED COMPONENTS SHALL BE REMOVED

-REFER TO DEMOLITION KEYNOTES FOR

ADDITIONAL DETAILS AT SPECIFIC CONDITIONS

EXISTING WALL SHALL REMAIN

EXISTING DOOR, FRAME AND HARDWARE

SHALL REMAIN

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:0

:4

P

M

MK LJ

589A4-20-155

AD101

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

BASEMENT DEMOLITION PLAN 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

BASEMENT DEMOLITION PLAN

Note Number Note

1 EXISTING EQUIPMENT AND FIXTURES TO REMAIN. CONTRACTOR TO

COORDINATE PROTECTING EQUIPMENT DURING CONSTRUCTION.

2 REMOVE AND SALVAGE FURNITURE, EQUIPMENT, AND FIXTURES SECURED

TO THE WALL. STORE AT VA DESIGNATED LOCATION.

3 REMOVE CEILING ASSEMBLY AND ASSOCIATED COMPONENTS.

4 REMOVE FLOOR FINISH, FLOOR COVERING, WALL BASE, WALL COVERING,

WALLS, AND ASSOCIATED COMPONENTS.

5 DEMO EXISTING DOOR AND REPLACE WITH NEW DOOR.

7 REMOVE CASEWORK

8 REMOVE SINK

9 DEMO EXISTING DOOR

10 DEMO EXISTING WALL FOR DOOR OPENING

11 DEMO EXISTING GYP. BD.

12 DEMO EXISTING LAYER OF GYP. BD. SOUND BATT INSULATION, AND

FRAMING TO REMAIN.

13 DUMB WAITER IS TO BE DEMOED AND NOT REPLACED. THE TUBE STATION

IS TO BE RELOCATED. AND THE WORK ON THE TUBE STATION RELOCATION

IS NOT ANTICIPATED TO AFFECT THE FLOOR ABOVE.

Revisions: Date:

Addendum #1 8/13/2021

GENERAL NOTES

PLAN LEGEND

KEY NOTES

BARRIER LEGEND

10.6

10.6

11.5

11.5

D D

C C

B B

A A

GRAY AREA NOT IN

PROJECT SCOPE

117 SF

EXISTING NARCOTIC VAULT

E001A

109 SF

OFFICE 2

E001B

109 SF

OFFICE 1

E001C

104 SF

TEAM WORK AREA

E001D

146 SF

POS ISO ANTEROOM

E001L

469 SF

SECURED DISPENSING / STORAGE,

INPATIENT

E001E

2468 SF

PHARMACY FILLING & ASSEMBLY

E001

176 SF

POS ISO NON-HD BUFFER

E001H

147 SF

STORAGE

E001F

122 SF

NEG ISO HAZ BUFFER

E001J

111 SF

NEG HD STORAGE

E001K

REF.

E001G

E001A

E001B

E001D E001C

E001E

E001H

E001K

CBE2

E001

EXISTING CORRIDOR

CBF1

EXISTING CORRIDOR

CBE2

STORAGE

E001G

EXIST. ELEC

E009

EXISTING OFFICE

E002K

AE404

AE404

AE404

AE404

AE404

AE404

18 18

AE404

E002F

CBE2

E001J

E002K

EXISTING ROOM

E002F

HAC

E012

TYP.

AE402

AE6016

AE6017

A1

A2

F351.3

NEW PNUEMATIC

TUBE LOCATION

1. G.C. SHALL VERIFY DIMENSIONS OF OWNER

FURNISHED EQUIPMENT AND COORDINATE

INSTALLATION WITH ALL TRADES WHERE

REQUIRED.

2. REFER TO FINISH SHEETS FOR PARTITION

PROTECTION INFORMATION INCLUDING BUT NOT

LIMITED TO ALL CORNER GUARD TYPES AND

LOCATIONS.

3. G.C. SHALL INSTALL IN-WALL METAL BACKING FOR

ALL PARTITION-MOUNTED EQUIPMENT,

ACCESSORIES, PARTITION STOPS, ETC.

4. G.C. SHALL INSTALL FIRE-RETARDANT WOOD

BLOCKING WITHIN WALLS BASED ON CASEWORK

ELEVATIONS AND ALL INTERIOR PARTITION

ELEVATIONS.

5. ALL INTERIOR WALLS SHALL RECEIVE

5/8" TYPE 'X' GYPSUM BOARD.

6. G.C. SHALL PROVIDE UL APPROVED FIRE-

RESISTIVE PENETRATION SYSTEMS WHERE

PLUMBING IS LOCATED IN A FIRE-RATED

PARTITION ASSEMBLY.

7. ALL EXTERIOR WINDOWS OPEN TO THE INTERIOR

SHALL RECEIVE A SOLID SURFACE WINDOW

STOOL. REFER TO FINISH DRAWINGS FOR

MATERIAL SELECTION.

8. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED

AS NON-RATED SMOKE PARTITIONS.

9. EXTEND ALL RATED WALLS TO DECK PER UL

ASSEMBLY REQUIREMENTS.

AREA WITHIN SCOPE OF WORK

AREA NOT IN CONTRACT

BASEMENT FLOOR KEY PLAN

AREA OF

WORK

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

SB1 = SMOKE BARRIER- 1 HOUR

NON-RATED INTERIOR PARTITION WALL

NON-RATED INTERIOR PARTITION WALL (WITH

INSULATION)

EXISTING WALL TO REMAIN

REFERENCE WALL TYPES SHEET FOR

CONSTRUCTION TYPE

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:0

:4

P

M

MK LJ

589A4-20-155

AE103

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

BASEMENT ENLARGED PLAN 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

BASEMENT ENLARGED PLAN

Note Number Note

1 P-TUBE STATION

INFUSION BAY 3-6 & 7-9 ARE SIMILAR TO BAYS 10, 11, AND 12. REFER TO

INFUSION BAY ELEVATIONS FOR MORE INFORMATION.

PRIVATE INFUSION ROOM F381 IS SIMILAR TO PRIVATE INFUSION ROOM F380.

REFER TO ROOM F380 ELEVATIONS FOR MORE INFORMATION.

12 WINDOWED PASS THROUGH. PASS THROUGH TO BE FIRE RATED.

PAINT EXISTING WALLS TO MATCH NEW WALL PAINT. SEE FINISH MATERIAL

SCHEDULE FOR DETAILS.

14 PATCH CLEAN AND REPAIR WALL AFTER DEMO. TYPICAL IN ALL AREAS

PATCH, CLEAN, AND REPAIR FLOORS WHERE NEEDED AFTER DEMO LEVEL

FLOORS WHERE NEEDED TYPICAL IN ALL AREAS.

PATCH NEW WALLS. SEE FINISH MATERIAL SCHEDULE FOR DETAILS. TYPICAL

IN ALL AREAS

INSTALL NEW CEILING GRID AND CEILING TILES. SEE REFLECTED CEILING

PLAN FOR DETAILS. TYPICAL IN ALL AREAS

18 EXISTING DOOR TO REMAIN

20 INSTALL NEW SOLID SURFACE (SS-1) ACCESSIBLE COUNTERTOP

21 EXISTING COUNTERTOP TO REMAIN

22 NEW STAINLESS STEEL COUNTERTOP

ROOM REPLACEMENT DOOR TO BE INSTALLED. CONTRACTOR TO

COORDINATE INSTALLATION OF NEW DOOR WITH THE DEMO OF THE

EXISTING ROOM DOOR.

24 EXISTING STORM PIPES TO REMAIN

25 NEW GARDEN BALCONY RAILING

CORNER GUARD WALL (FULL HEIGHT) TYP. ALL CORRIDOR CORNERS - REFER

TO FINISH MATERIAL LEGEND AND FINISH SPECIFICATIONS FOR DETAILS.

HANDRAIL AND BUMPER WALL PROTECTION ALONG LENGTH OF WALL -

REFER TO SPEC SECTION 102600 FOR DETAILS. TOP OF HANDRAIL TO BE 34"

A.F.F. TYP.

09 2216 - 60" x 108" TEMPORARY CONSTRUCTION OPENING TO ALLOW

PASSAGE OF EQUIPMENT. COORDINATE SEQUENCING WITH OWNER.

GENERAL NOTES

PLAN LEGEND

KEY NOTES

BARRIER LEGEND

H H

GG

FF

E.1 E.1

E E

106 SF

ANTEROOM

F359

102 SF

NON-HAZARDOUS IV PREP

F361

125 SF

HAZARDOUS IV PREP/STORAGE

F360

74 SF

MED. ROOM

F364

83 SF

CLEAN DISPATCH

F362

110 SF

SOILED DISPATCH

F363

56 SF

TOILET

F365

107 SF

NURSE STATION

F374

61 SF

INFUSION BAY

F386

60 SF

INFUSION BAY

F372

57 SF

INFUSION BAY

F371

58 SF

INFUSION BAY

F369

62 SF

INFUSION BAY

F375

57 SF

INFUSION BAY

F376

55 SF

INFUSION BAY

F377

69 SF

INFUSION BAY

F378

105 SF

PRIVATE INFUSION

F380

105 SF

PRIVATE INFUSION

F381

57 SF

TOILET

F382

116 SF

EXAM ROOM

F389

117 SF

EXAM ROOM

F391

114 SF

EXAM ROOM

F392

111 SF

EXAM ROOM

F393

74 SF

F390

WHEELCHAIR

STORAGE

ALCOVE

64 SF

PATIENT TOILET

F385 31 SF

NOURISH

F383

727 SF

CORRIDOR

F373

668 SF

CORRIDOR

F358

119 SF

EXAM ROOM

F352

113 SF

PROVIDERS ROOM

F353

118 SF

SWAMP

F354

96 SF

PROVIDERS ROOM

F355

144 SF

NURSE NAVIGATOR

F356

201 SF

WORK ROOM

F357

60 SF

INFUSION BAY

F366

62 SF

INFUSION BAY

F367

62 SF

INFUSION BAY

F368

189 SF

EXISTING OUTDOOR GARDEN

F370

14 SF

EQUIPMENT ALCOVE

F379

410 SF

F394

EXISTING

CORRIDOR

F365

F393

F391

F388

F352 F354 F355 F356F353

F381

F374.2

F362b

F364

F382

F374.1

F380

F392

F351.2

F385

F362a

F370

F363a F363b

AE4053

AE405

AE401

AE401

AE401

AE405

61 SF

INFUSION BAY

F398

114 SF

EXAM ROOM

F388

7 7

AE405

15 7

AE405 17

AE405 14

AE405

AE405 2726

F357

F359

F360

AE405

AE40522

AE405

AE405

F389

F361

AE104

Sim

AE104 4

S im

AE403

AE403

AE403

AE405

AE405

AE402

AE403

AE403

26 26

26 26

26 26

F351.1

14 15

TYP.

14 15

TYP.

AE701

Sim

AE701

Sim 8

AE701

Sim

THIRD FLOOR KEY PLAN

AREA OF

WORK

1. G.C. SHALL VERIFY DIMENSIONS OF OWNER

FURNISHED EQUIPMENT AND COORDINATE

INSTALLATION WITH ALL TRADES WHERE

REQUIRED.

2. REFER TO FINISH SHEETS FOR PARTITION

PROTECTION INFORMATION INCLUDING BUT NOT

LIMITED TO ALL CORNER GUARD TYPES AND

LOCATIONS.

3. G.C. SHALL INSTALL IN-WALL METAL BACKING FOR

ALL PARTITION-MOUNTED EQUIPMENT,

ACCESSORIES, PARTITION STOPS, ETC.

4. G.C. SHALL INSTALL FIRE-RETARDANT WOOD

BLOCKING WITHIN WALLS BASED ON CASEWORK

ELEVATIONS AND ALL INTERIOR PARTITION

ELEVATIONS.

5. ALL INTERIOR WALLS SHALL RECEIVE

5/8" TYPE 'X' GYPSUM BOARD.

6. G.C. SHALL PROVIDE UL APPROVED FIRE-

RESISTIVE PENETRATION SYSTEMS WHERE

PLUMBING IS LOCATED IN A FIRE-RATED

PARTITION ASSEMBLY.

7. ALL EXTERIOR WINDOWS OPEN TO THE INTERIOR

SHALL RECEIVE A SOLID SURFACE WINDOW

STOOL. REFER TO FINISH DRAWINGS FOR

MATERIAL SELECTION.

8. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED

AS NON-RATED SMOKE PARTITIONS.

9. EXTEND ALL RATED WALLS TO DECK PER UL

ASSEMBLY REQUIREMENTS.

AREA WITHIN SCOPE OF WORK

AREA NOT IN CONTRACT

D D

C C

93 SF

INTAKE

E310

82 SF

WORK AREA

E303

99 SF

RECEPTION

E302

475 SF

HEM/ONC WAITING

E301

E311

E310

91 SF

CONSULT ROOM

E311

E303

E302

AE405

AE40530

AE405

AE405 31

AE402

14 15

TYP.

AE104

Sim

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

SB1 = SMOKE BARRIER- 1 HOUR

NON-RATED INTERIOR PARTITION WALL

NON-RATED INTERIOR PARTITION WALL (WITH

INSULATION)

EXISTING WALL TO REMAIN

REFERENCE WALL TYPES SHEET FOR

CONSTRUCTION TYPE

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:0

:4

P

M

MK LJ

589A4-20-155

AE104

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

THIRD FLOOR ENLARGED PLAN 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

THIRD FLOOR ENLARGED PLAN

PLAN NORTH

1/4" = 1'-0"

THIRD FLOOR ENLARGED PLAN

Note Number Note

1 P-TUBE STATION

INFUSION BAY 3-6 & 7-9 ARE SIMILAR TO BAYS 10, 11, AND 12. REFER TO

INFUSION BAY ELEVATIONS FOR MORE INFORMATION.

PRIVATE INFUSION ROOM F381 IS SIMILAR TO PRIVATE INFUSION ROOM F380.

REFER TO ROOM F380 ELEVATIONS FOR MORE INFORMATION.

12 WINDOWED PASS THROUGH. PASS THROUGH TO BE FIRE RATED.

PAINT EXISTING WALLS TO MATCH NEW WALL PAINT. SEE FINISH MATERIAL

SCHEDULE FOR DETAILS.

14 PATCH CLEAN AND REPAIR WALL AFTER DEMO. TYPICAL IN ALL AREAS

PATCH, CLEAN, AND REPAIR FLOORS WHERE NEEDED AFTER DEMO LEVEL

FLOORS WHERE NEEDED TYPICAL IN ALL AREAS.

PATCH NEW WALLS. SEE FINISH MATERIAL SCHEDULE FOR DETAILS. TYPICAL

IN ALL AREAS

INSTALL NEW CEILING GRID AND CEILING TILES. SEE REFLECTED CEILING

PLAN FOR DETAILS. TYPICAL IN ALL AREAS

18 EXISTING DOOR TO REMAIN

20 INSTALL NEW SOLID SURFACE (SS-1) ACCESSIBLE COUNTERTOP

21 EXISTING COUNTERTOP TO REMAIN

22 NEW STAINLESS STEEL COUNTERTOP

ROOM REPLACEMENT DOOR TO BE INSTALLED. CONTRACTOR TO

COORDINATE INSTALLATION OF NEW DOOR WITH THE DEMO OF THE

EXISTING ROOM DOOR.

24 EXISTING STORM PIPES TO REMAIN

25 NEW GARDEN BALCONY RAILING

CORNER GUARD WALL (FULL HEIGHT) TYP. ALL CORRIDOR CORNERS - REFER

TO FINISH MATERIAL LEGEND AND FINISH SPECIFICATIONS FOR DETAILS.

HANDRAIL AND BUMPER WALL PROTECTION ALONG LENGTH OF WALL -

REFER TO SPEC SECTION 102600 FOR DETAILS. TOP OF HANDRAIL TO BE 34"

A.F.F. TYP.

09 2216 - 60" x 108" TEMPORARY CONSTRUCTION OPENING TO ALLOW

PASSAGE OF EQUIPMENT. COORDINATE SEQUENCING WITH OWNER.

1 1/2" = 1'-0"

GARDEN BALCONY RAILING SECTION

1 1/2" = 1'-0"

GARDEN BALCONY RAILING ELEVATION

10.6

10.6

11.5

11.5

D D

C C

B B

A A

GRAY AREA NOT IN

PROJECT SCOPE

/8

/1

/8

/8

/8

9' - 11 1/4" 18' - 8 1/8" 8' - 0" 11' - 0 5/8" 11' - 2 7/8" 11' - 2 7/8"

R04

R02

R02

P04

P04

P04

32' - 5 1/2"

R02

R02

R02

R04

R02

/4

/1

P04

A1

A2

BASEMENT FLOOR KEY PLAN

AREA OF

WORK

1. CONTRACTOR TO FIELD VERIFY EXISTING

STRUCTURAL COLUMN SPACING AND OVERALL

BUILDING DIMENSIONS. CONTRACTOR TO NOTIFY

VA AND ARCHITECT IF ANY DISCREPANCIES ARE

FOUND BETWEEN FIELD DIMENSIONS AND

DRAWINGS.

2. G.C. SHALL VERIFY DIMENSIONS OF OWNER

FURNISHED EQUIPMENT AND COORDINATE

INSTALLATION WITH ALL TRADES WHERE

REQUIRED.

3. REFER TO FINISH SHEETS FOR PARTITION

PROTECTION INFORMATION INCLUDING BUT NOT

LIMITED TO ALL CORNER GUARD TYPES AND

LOCATIONS.

4. G.C. SHALL INSTALL IN-WALL 16 GA METAL

BACKING FOR ALL PARTITION-MOUNTED

EQUIPMENT, ACCESSORIES, PARTITION STOPS,

ETC.

5. G.C. SHALL INSTALL FIRE-RETARDANT WOOD

BLOCKING WITHIN WALLS BASED ON CASEWORK

ELEVATIONS AND ALL INTERIOR PARTITION

ELEVATIONS.

6. ALL INTERIOR WALLS SHALL RECEIVE

5/8" TYPE 'X' GYPSUM BOARD.

7. G.C. SHALL PROVIDE UL APPROVED FIRE-

RESISTIVE PENETRATION SYSTEMS AT ALL FIRE-

RATED PARTITION ASSEMBLY.

8. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED

AS NON-RATED SMOKE PARTITIONS.

9. EXTEND ALL WALLS TO UNDERSIDE OF DECK PER

UL ASSEMBLY REQUIREMENTS. REFER TO 1-AF105

FOR INTERIOR PARTITION TYPES & DETAILS.

10. REFER TO SHEET 1-AE705 FOR RATED PARTITION

PRIORITY AND RATED PARTITION INTERSECTIONS.

11. FURNITURE AND EQUIPMENT SHOWN NIC UNLESS

OTHERWISE NOTED.

12. PROVIDE 16 GA STUDS ON WET WALLS IN

RESTROOMS AND FOR THE DRINKING FOUNTAIN

WALL. 20 GA STUDS ON ALL OTHER WALLS.

13. SEAL ALL PENETRATIONS IN SUITE PERIMETER

WALLS.

14. RECESSED ACCESS DOORS LOCATED UNDER

EACH LAVATORY AND SINK LOCATED IN THE

WALL.

Note Number Note

1 EXISTING PLUMBING PIPE TO REMAIN. REFERENCE PLUMBING DRAWINGS.

2 TEMP WALL TO BE DEMO'D.

3 MECHANICAL DUCT TO REMAIN. REF. MECHANICAL DRAWINGS.

4 EXISTING BALCONY TO REMAIN.

5 EXISTING TEMPORARY BALCONY RAILING TO BE REMOVED.

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:0

:0

P

M

MK LJ

589A4-20-155

AE105

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

BASEMENT DIMENSION PLAN 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

BASEMENT DIMENSION PLAN

H H

GG

FF

E.1 E.1

E E

106 SF

ANTEROOM

F359

102 SF

NON-HAZARDOUS IV PREP

F361

125 SF

F360

HAZARDOUS

IV

PREP/STORAGE

74 SF

MED. ROOM

F364

83 SF

F362

CLEAN

DISPATCH

110 SF

SOILED DISPATCH

F363

56 SF

TOILET

F365

107 SF

NURSE STATION

F374

61 SF

INFUSION BAY

F386

60 SF

INFUSION BAY

F372

57 SF

INFUSION BAY

F371

58 SF

INFUSION BAY

F369

62 SF

INFUSION BAY

F375

57 SF

INFUSION BAY

F376

55 SF

INFUSION BAY

F377

69 SF

INFUSION BAY

F378

105 SF

PRIVATE INFUSION

F380

105 SF

PRIVATE INFUSION

F381

57 SF

TOILET

F382

116 SF

EXAM ROOM

F389

117 SF

EXAM ROOM

F391

114 SF

EXAM ROOM

F392

111 SF

EXAM ROOM

F393

74 SF

WHEELCHAIR STORAGE

ALCOVE

F390

64 SF

PATIENT TOILET

F385

31 SF

NOURISH

F383

CORRIDOR

F373

CORRIDOR

F358

119 SF

EXAM ROOM

F352

113 SF

PROVIDERS ROOM

F353

118 SF

SWAMP

F354

96 SF

PROVIDERS ROOM

F355

144 SF

NURSE NAVIGATOR

F356

201 SF

WORK ROOM

F357

60 SF

INFUSION BAY

F366

62 SF

INFUSION BAY

F367

62 SF

INFUSION BAY

F368

EXISTING OUTDOOR

GARDEN

14 SF

EQUIPMENT ALCOVE

F379

EXISTING CORRIDOR

F394

/4

/1

/1

/8

/2

/4

/8

/8

/1

/8

10' - 10 1/8" 2' - 0 1/4" 8' - 4 5/8" 10' - 6 1/2" 2' - 6 3/8" 6' - 6 7/16" 12' - 8 5/16" 9' - 3 1/4" 2' - 0"

/4

/8

/4

/8

/1

/1

/8

/8

3' - 2 1/8" 8' - 0 3/16" 6' - 4 7/8" 8' - 8 5/8" 6' - 4 7/8" 8' - 5 1/8" 4' - 5 7/8" 11' - 8 15/16"

10' - 10 1/8" 14' - 6 11/16" 6' - 0 7/8" 7' - 4 9/16"

2' - 4 9/16"

5' - 9 3/4"

5' - 10"

5' - 10"

3' - 6 15/16" 8' - 6" 10' - 3 3/4" 9' - 8 1/4"

/8

2' - 6"

/1

/1

/8

/8

/8

/8

/1

/1

61 SF

INFUSION BAY

F398

P04

P04

P07

P04

P10

P10

P06

P05

P06

P06

P04

P04

P06

P06

P04

P04

P04

P01

P01

P04

P04

P04

P04

P01

P07

P04

P04

P01

P04 P04

P04

P04

P01

R02

R02

P01

P02

P06R03

P01

P10 P06

P05

P04

EQ EQ

8' - 0"

/4

/1

/1

9' - 4 1/2" 10' - 7 1/4" 16' - 8 7/8" 11' - 3 1/8"

P01 P01

P10

P01 P09

R04R02

R02

R02

P01

P10

P10

P01 P01

P00

P00

P01

P01

D D

C C

93 SF

INTAKE

E310

82 SF

WORK AREA

E303

99 SF

RECEPTION

E302

475 SF

HEM/ONC WAITING

E301

91 SF

CONSULT ROOM

E311

AE700

P01

P01

P04

P02

P04

P04

P04

P04

10' - 7 3/4" 21' - 0 5/8" 10' - 7 1/16"

/1

/1

/8

THIRD FLOOR KEY PLAN

AREA OF

WORK

1. CONTRACTOR TO FIELD VERIFY EXISTING

STRUCTURAL COLUMN SPACING AND OVERALL

BUILDING DIMENSIONS. CONTRACTOR TO NOTIFY

VA AND ARCHITECT IF ANY DISCREPANCIES ARE

FOUND BETWEEN FIELD DIMENSIONS AND

DRAWINGS.

2. G.C. SHALL VERIFY DIMENSIONS OF OWNER

FURNISHED EQUIPMENT AND COORDINATE

INSTALLATION WITH ALL TRADES WHERE

REQUIRED.

3. REFER TO FINISH SHEETS FOR PARTITION

PROTECTION INFORMATION INCLUDING BUT NOT

LIMITED TO ALL CORNER GUARD TYPES AND

LOCATIONS.

4. G.C. SHALL INSTALL IN-WALL 16 GA METAL

BACKING FOR ALL PARTITION-MOUNTED

EQUIPMENT, ACCESSORIES, PARTITION STOPS,

ETC.

5. G.C. SHALL INSTALL FIRE-RETARDANT WOOD

BLOCKING WITHIN WALLS BASED ON CASEWORK

ELEVATIONS AND ALL INTERIOR PARTITION

ELEVATIONS.

6. ALL INTERIOR WALLS SHALL RECEIVE

5/8" TYPE 'X' GYPSUM BOARD.

7. G.C. SHALL PROVIDE UL APPROVED FIRE-

RESISTIVE PENETRATION SYSTEMS AT ALL FIRE-

RATED PARTITION ASSEMBLY.

8. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED

AS NON-RATED SMOKE PARTITIONS.

9. EXTEND ALL WALLS TO UNDERSIDE OF DECK PER

UL ASSEMBLY REQUIREMENTS. REFER TO 1-AF105

FOR INTERIOR PARTITION TYPES & DETAILS.

10. REFER TO SHEET 1-AE705 FOR RATED PARTITION

PRIORITY AND RATED PARTITION INTERSECTIONS.

11. FURNITURE AND EQUIPMENT SHOWN NIC UNLESS

OTHERWISE NOTED.

12. PROVIDE 16 GA STUDS ON WET WALLS IN

RESTROOMS AND FOR THE DRINKING FOUNTAIN

WALL. 20 GA STUDS ON ALL OTHER WALLS.

13. SEAL ALL PENETRATIONS IN SUITE PERIMETER

WALLS.

14. RECESSED ACCESS DOORS LOCATED UNDER

EACH LAVATORY AND SINK LOCATED IN THE

WALL.

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:0

:1

P

M

MK LJ

589A4-20-155

AE106

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

THIRD FLOOR DIMENSION PLAN 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

THIRD FLOOR DIMENSION PLAN

Note Number Note

1 EXISTING PLUMBING PIPE TO REMAIN. REFERENCE PLUMBING DRAWINGS.

2 TEMP WALL TO BE DEMO'D.

3 MECHANICAL DUCT TO REMAIN. REF. MECHANICAL DRAWINGS.

4 EXISTING BALCONY TO REMAIN.

5 EXISTING TEMPORARY BALCONY RAILING TO BE REMOVED.

1/4" = 1'-0"

THIRD FLOOR DIMENSION PLAN

RCP NOTES

RCP LEGEND

S

S

S

F

S

F

F

S

F

F

F

F

F

S

F

F

S

S

S

S

S

1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT

OF ANY DIMENSIONAL DISCREPANCIES

DISCOVERED DURING CONSTRUCTION.

2. REFER TO ELECTRICAL DRAWINGS FOR LOCATION

OF EMERGENCY LIGHTING.

3. CENTER CEILING AND LIGHTS IN ALL SPACES

WHERE POSSIBLE, U.N.O.

4. REFER TO ELECTRICAL DRAWINGS FOR

LOCATIONS OF UNDER-CABINET LIGHT FIXTURES.

5. GYP. BD. SOFFITS ABOVE UPPER CABINETS SHALL

EXTEND TO TOP OF CABINET (7'-0" U.N.O.).

6. THIS SHEET IS FOR LAYOUT ONLY. SEE

ELECTRICAL AND MECHANICAL DRAWINGS FOR

EXACT FIXTURE QUANTITY. ALL SWITCHES,

OUTLETS, LIGHTS, DIFFUSERS, ETC. MUST BE

LOCATED PER ARCHITECTURAL DRAWINGS

WHERE APPLICABLE.

7. PROVIDE ACCESS PANELS IN GYPSUM CEILINGS

WHERE REQUIRED TO ACCESS ABOVE CEILING

EQUIPMENT. (SEE SPECS)

8. ALL CEILINGS SHALL BE 9'-0" AFF U.N.O.

9. REFER TO FINISH DRAWINGS FOR CEILING GRID

AND PANEL TYPE AND SIZE.

10. BOTTOM OF GYP. BD. BULKHEADS SHALL BE 8'-6"

AFF U.N.O.

11. ALL PARTITION WALLS SHALL EXTEND TO

UNDERSIDE OF DECK ABOVE U.N.O.

12. REFER TO SPECS FOR ADDITIONAL GYP. BD.

INFORMATION. GYP. BD. CEILINGS SHALL BE

INSTALLED PER ASTM C840.

13. ALL OFFICES SHALL HAVE DIMMERS.

MECHANICAL SUPPLY DIFFUSER

MECHANICAL RETURN GRILLE

MECHANICAL EXHAUST GRILLE

24" X 48" ACOUSTICAL CEILING

PANEL AND GRID

24" X 24" ACOUSTICAL CEILING

PANEL AND GRID

GYPSUM BOARD CEILING OR

SOFFIT

2' x 4' LED FIXTURE

2' x 2' LED FIXTURE

1' x 4' LED FIXTURE

RECESSED CAN DOWNLIGHT

CEILING ELEVATTION A.F.F.X'-X"

EXIT SIGN

DOWNLIGHT - RECTANGLE

10.6

10.6

11.5

11.5

D D

C C

B B

A A

2468 SF

PHARMACY FILLING & ASSEMBLY

E001

104 SF

TEAM WORK AREA

E001D

109 SF

OFFICE 1

E001C

109 SF

OFFICE 2

E001B

117 SF

EXISTING NARCOTIC VAULT

E001A

469 SF

SECURED DISPENSING / STORAGE,

INPATIENT

E001E

146 SF

POS ISO ANTEROOM

E001L

176 SF

POS ISO NON-HD BUFFER

E001H

147 SF

STORAGE

E001F

122 SF

NEG ISO HAZ BUFFER

E001J

111 SF

NEG HD STORAGE

E001K

8' - 3"A.F.F

8' - 3"A.F.F

8' - 3"A.F.F

8' - 3"A.F.F 8' - 3"A.F.F

E002K

8' - 3"A.F.F

205 SF

STORAGE

E001G

EXISTING CORRIDOR

CBE2

GRAY AREA NOT IN

PROJECT SCOPE

8' - 0"A.F.F

8' - 0"A.F.F

8' - 3"A.F.F

8' - 3"A.F.F

8' - 3"A.F.F

8' - 3"A.F.F

8' - 3"A.F.F

9' - 0"A.F.F

AE503

Sim

8' - 3"A.F.F

8' - 3"A.F.F

BASEMENT FLOOR KEY PLAN

AREA OF

WORK

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:0

:2

P

M

MK LJ

589A4-20-155

AE107

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

BASEMENT REFLECTED CEILING PLAN 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

BASEMENT REFLECTED CEILING PLAN

N

N

CR

S

S

S

S

S

S

S

S

N

N

N

N

N N N

N

N

NN

N N N

N

N

N N

N

N

N

N

N

N

N

N

N

N

S

N

N

CR

C R

CR

C R

S

F

SSS S

S

S

F

S

F

S

F

S

F

S

F

S

F

F

S

F

S

F

S

F

S

S

F

S

F

S

F

S

F

S

F

S

F F

S

S

S

S

S

S

S

S

F

S

S

S

S

F

S S

S

S S

S S

S

RCP NOTES

RCP LEGEND

S

S S

S S

F

S

F

F

KEY NOTES

H H

GG

FF

E.1 E.1

E E

ANTEROOM

F359

F361

NON-HAZARDOUS

IV PREP

F360

HAZARDOUS IV

PREP/STORAGE

MED. ROOM

F364

F362

CLEAN

DISPATCH

SOILED DISPATCH

F363

TOILET

F365

NURSE STATION

F374

INFUSION BAY

F386

INFUSION BAY

F372

INFUSION BAY

F371

INFUSION BAY

F369

INFUSION BAY

F375

INFUSION BAY

F376

INFUSION BAY

F377

INFUSION BAY

F378

F380

PRIVATE

INFUSION

F381

PRIVATE

INFUSION

TOILET

F382

EXAM ROOM

F389

EXAM ROOM

F391

EXAM ROOM

F392

EXAM ROOM

F393

F390

WHEELCHAIR

STORAGE

ALCOVE

PATIENT TOILET

F385

NOURISH

F383

CORRIDOR

F373

CORRIDOR

F358

EXAM ROOM

F352

F353

PROVIDERS

ROOM

SWAMP

F354

F355

PROVIDERS

ROOM

F356

NURSE

NAVIGATOR

WORK ROOM

F357

INFUSION BAY

F366

INFUSION BAY

F367

INFUSION BAY

F368

F370

EXISTING

OUTDOOR

GARDEN

F379

EQUIPMENT

ALCOVE

EXISTING CORRIDOR

F394

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F 9' - 0"A.F.F 9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

2' - 6"

9' - 0"A.F.F

9' - 0"A.F.F 9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F 9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

AE503

AE503

AE503

AE503

AE503

EXISTING CORRIDOR

F395

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

EXAM ROOM

F388

9' - 0"A.F.F

9' - 0"A.F.F

INFUSION BAY

F398

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

PT-2 GYP. BD.

SOFFIT PAINT

COLOR, VERTICAL

AND HORIZONTAL

FACE

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

9' - 0"A.F.F

2 2

1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT

OF ANY DIMENSIONAL DISCREPANCIES

DISCOVERED DURING CONSTRUCTION.

2. REFER TO ELECTRICAL DRAWINGS FOR LOCATION

OF EMERGENCY LIGHTING.

3. CENTER CEILING AND LIGHTS IN ALL SPACES

WHERE POSSIBLE, U.N.O.

4. REFER TO ELECTRICAL DRAWINGS FOR

LOCATIONS OF UNDER-CABINET LIGHT FIXTURES.

5. GYP. BD. SOFFITS ABOVE UPPER CABINETS SHALL

EXTEND TO TOP OF CABINET (7'-0" U.N.O.).

6. THIS SHEET IS FOR LAYOUT ONLY. SEE

ELECTRICAL AND MECHANICAL DRAWINGS FOR

EXACT FIXTURE QUANTITY. ALL SWITCHES,

OUTLETS, LIGHTS, DIFFUSERS, ETC. MUST BE

LOCATED PER ARCHITECTURAL DRAWINGS

WHERE APPLICABLE.

7. PROVIDE ACCESS PANELS IN GYPSUM CEILINGS

WHERE REQUIRED TO ACCESS ABOVE CEILING

EQUIPMENT. (SEE SPECS)

8. ALL CEILINGS SHALL BE 9'-0" AFF U.N.O.

9. REFER TO FINISH DRAWINGS FOR CEILING GRID

AND PANEL TYPE AND SIZE.

10. BOTTOM OF GYP. BD. BULKHEADS SHALL BE 8'-6"

AFF U.N.O.

11. ALL PARTITION WALLS SHALL EXTEND TO

UNDERSIDE OF DECK ABOVE U.N.O.

12. REFER TO SPECS FOR ADDITIONAL GYP. BD.

INFORMATION. GYP. BD. CEILINGS SHALL BE

INSTALLED PER ASTM C840.

13. ALL OFFICES SHALL HAVE DIMMERS.

MECHANICAL SUPPLY DIFFUSER

MECHANICAL RETURN GRILLE

MECHANICAL EXHAUST GRILLE

24" X 48" ACOUSTICAL CEILING

PANEL AND GRID

24" X 24" ACOUSTICAL CEILING

PANEL AND GRID

GYPSUM BOARD CEILING OR

SOFFIT

2' x 4' LED FIXTURE

2' x 2' LED FIXTURE

1' x 4' LED FIXTURE

RECESSED CAN DOWNLIGHT

CEILING ELEVATTION A.F.F.X'-X"

EXIT SIGN

DOWNLIGHT - RECTANGLE

THIRD FLOOR KEY PLAN

AREA OF

WORK

D D

C C

INTAKE

E310

WORK AREA

E303

RECEPTION

E302

HEM/ONC WAITING

E301

EXISTING CORRIDOR

F394

10' - 0"A.F.F

9' - 0"A.F.F

AE503

Sim

EXISTING CORRIDOR

F395

2' - 0" 4' - 4" 4' - 4"

CONSULT ROOM

E311

9' - 0"A.F.F

10' - 0"A.F.F

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:4

:5

P

M

MK LJ

589A4-20-155

AE108

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

THIRD FLOOR REFLECTED CEILING PLAN 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

THIRD FLOOR REFLECTED CEILING PLAN

1/4" = 1'-0"

THIRD FLOOR REFLECTED CEILING PLAN

Note Number Note

1 JSN# A5180 - TRACK, CUBICLE, SURFACE MOUNTED WITH CURTAIN - CC

2 PATIENT LIFT - VC

Revisions: Date:

AE405

F0205

F3025

F0206

M7401

M9025

M3073

A5108

M4100

M4200

A5107

F2000

A5145 A5080A5075

F0340

M1801

A1012

F3200

F392

CURTAIN

MEDICAL

GAS

OUTLETS

114 SF

EXAM ROOM

F392

AE701

Sim

AE405

AE40522

AE405

AE405

AE405

F2017

M4255

A5077

A5080

M3150

F0535

F0535

F2000

A5080 A5077

A5075

F359

F361

F360

F364

M1801

R6200

A5077

A5075

A5077

BSC HOOD

BSC HOOD

X003

60 SF

INFUSION BAY

F366

74 SF

MED. ROOM

F364

125 SF

HAZARDOUS IV PREP/STORAGE

F360

102 SF

NON-HAZARDOUS IV PREP

F361

106 SF

ANTEROOM

F359

X001

X005

NURSE CALL

MEDICAL GAS OUTLETS

PATIENT PRIVACY SCREEN

AE701

Sim

AE701

Sim

END BRACKET TO

STABILIZE PRIVACY

SCREEN TYP.

AE700

Sim

AE4053

F381

F0205

A5077

F0206

M9025

F2017

A5108F0340

A5075

F3200

A1012

M1801

AE701

Sim

F3025

X006

105 SF

PRIVATE INFUSION

F381

MEDICAL

GAS

OUTLETS

AE405 1413

M3072 M3070

F2020

P2000

F363bF363a

110 SF

SOILED DISPATCH

F363

AE405

E0945

F2000

A5077

F362b

F362a

M13150

M13150

M13150

83 SF

CLEAN DISPATCH

F362

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

NORTH

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:5

:0

P

M

MK LJ

589A4-20-155

AE403

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

ENLARGED PLANS 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/2" = 1'-0"

ENLARGED EXAM ROOM

1/2" = 1'-0"

ENLARGED IV PREP STORAGE, MED. ROOM, AND

INFUSION BAY

1/2" = 1'-0"

ENLARGED PRIVATE INFUSION

1/2" = 1'-0"

ENLARGED SOILED DISPATCH F363

1/2" = 1'-0"

ENLARGED CLEAN DISPATCH F362

F2017

A5108

F0340

/2

PT-1

S-2

HPDL-1

WP-2 AT 48"

WITH PT-1

ABOVE

FLASHCOVE

BASE, WSF-2

M9025 A5108

F0340

S-2

HPDL-1

WP-2 AT 48"

WITH EPOXY

PT-4 ACCENT

ABOVE

FLASHCOVE

BASE, WSF-2

M9025

F0206 F0205

A5077

PT-1

FLASHCOVE

BASE, WSF-2

A5077

F0206

PT-1

FLASHCOVE

BASE, WSF-2

F2000

M13150M13150

A5077

FLASHCOVE

BASE, WSF-3

PT-1

WP-2 AT 48" WITH

EPOXY PT-1 ABOVE

E0945

M13150

FLASHCOVE

BASE, WSF-3

WP-2 AT 48" WITH

EPOXY PT-1

ABOVE

F3200

F0206F0205

M7401

M9025 M3073

FLASHCOVE

BASE, WSF-1

PT-1

F3025

A5107

A5108

M7401

M4100

M9025

M3073

FLASHCOVE

BASE, WSF-1

PT-1

A5080 A5075 M1801

F0340 F2000

PT-1

HPDL-1

S-2

WP-2 AT 48"

WITH PT-1

ABOVE

FLASHCOVE

BASE, WSF-1

F3200

F0206

A1012M1801

F2000 F0340

FLASHCOVE

BASE, WSF-1

PT-3 ACCENT

WALL

A5108

A5077

A5075

2' - 6 1/8"2' - 6 1/8"

FLASHCOVE

BASE, WSF-1

S-2

S-1 CAP

HPDL-1

P A

R T

IT

IO

N H

E

IG

H T

P2000 M3070

PT-1 WP-2 TO 48"

A.F.F. WITH

EOPXY PT-1

ABOVE

FLASHCOVE

BASE, WSF-3

F2020M3070WP-2 TO 48" AFF

WITH EPOXY

PT-1 ABOVE

CG-2

FLASHCOVE

BASE, WSF-3

RB-1

HPDL-2

/2

PT-1

HPDL-1

HPDL-1

SHELF BRACKET

RB-1

PT-1

HPDL-2

R6200

3' - 0" 1' - 8" 3' - 1 1/8"

3' - 1" 1' - 8" 2' - 5" 8"

PT-1

HPDL-1

FLASHCOVE

BASE, INT-1

HPDL-1

ICE MACHINE

S-2

5' - 0"

FLASHCOVE

BASE, INT-1

WP-3 AT 48"

WITH EPOXY

PT-1 ABOVE

CG-3

S-2

HPDL-1

M3150

PASS

THROUGH

WP-2 AT 48"

WITH EPOXY

PT-1 ABOVE

S-2

COUNTER

FLASHCOVE

BASE, INT-1

CG-2

PASS THROUGH

PASS THROUGH

S-2 COUNTER

FLASHCOVE

BASE, INT-1

HPDL-1

CG-2

WP-2 BELOW

COUNTERTOP

EPOXY PT-1 ABOVE

8' - 0"

WP-2 AT 48"

WITH PT-1

ABOVE

FLASHCOVE

BASE, WSF-3

S-2 COUNTER

HPDL-1

CG-2

BSC HOOD

FLASHCOVE

BASE, INT-1

WP-3 AT 48"

WITH EPOXY

PT-1 ABOVE

S-2 COUNTER

BSC HOOD

PASS THROUGH

R6200 F0535

WP-3 AT 48"

WITH PT-1

ABOVE

FLASHCOVE

BASE, INT-1

CG-3

S-2 COUNTER

BSC HOOD

PASS THROUGH

F0535 R6200

S-2 COUNTER

FLASHCOVE

BASE, INT-1

WP-3 AT 48" WITH

EPOXY PT-1 ABOVE

BSC HOOD

M1801 A5077

WP-3 AT 48"

WITH PT-1

ABOVE

FLASHCOVE

BASE, INT-1

S-2 COUNTER

CG-3

RB-1

PT-1

CG-2

PT-1

RB-1

M1810

3' - 0"

PT-1

HPDL-1

HPDL-2

RB-1

HPDL-1

HPDL-1

PH-1

VERTICAL

SURFACE

HPDL-2 WORK

SURFACE

S-2

TRANSACTION

TOP

CG-2

PT-1

PT-3 AT VERTICAL FACE &

BOTTOM OF SOFFIT

CG-2

PT-1

PT-3 AT VERTICAL

FACE & BOTTOM OF

SOFFIT

S-2

TRANSACTION

TOP

PH-1

RB-1

CG-2

RB-1

PT-1

PT-1

CG-2

RB-1

4' - 0" 4' - 0"

M4255

INT-1

WP-2 AT 48"

WITH EPOXY

PT-4 ACCENT

ABOVE

PRIVACY

SCREEN

PARTITION

M4255

BENCH

HPDL-2

HPDL-1

HPDL-1

E0954

HPDL-2

HPDL-1

S-2

TRANSACTION

TOP

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:4

:1

P

M

MK LJ

589A4-20-155

AE405

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

THIRD FLOOR INTERIOR ELEVATIONS 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

1/4" = 1'-0"

PRIVATE INFUSION F381 1

1/4" = 1'-0"

PRIVATE INFUSION F381 2

1/4" = 1'-0"

PRIVATE INFUSION F381 3

1/4" = 1'-0"

PRIVATE INFUSION F381 4

1/4" = 1'-0"

CLEAN DISPATCH F362 1

1/4" = 1'-0"

CLEAN DISPATCH F362 2

1/4" = 1'-0"

EXAM ROOM F392 1

1/4" = 1'-0"

EXAM ROOM F392 2

1/4" = 1'-0"

EXAM ROOM F392 3

1/4" = 1'-0"

EXAM ROOM F392 4

1/4" = 1'-0"

INFUSION BAY ALCOVE

1/4" = 1'-0"

SOILED DISPATCH F363 1

1/4" = 1'-0"

SOILED DISPATCH F363 2

1/4" = 1'-0"

SWAMP F354 1 1/4" = 1'-0"

SWAMP F354 2 1/4" = 1'-0"

NOURISH F383

1/4" = 1'-0"

ANTE ROOM

1/4" = 1'-0"

MED. ROOM F364 1

1/4" = 1'-0"

MED. ROOM F364 2

1/4" = 1'-0"

MED. ROOM F364 3

1/4" = 1'-0"

NON-HAZARDOUS IV PREP F361 1

1/4" = 1'-0"

NON-HAZARDOUS IV PREP F361 2

1/4" = 1'-0"

HAZARDOUS IV PREP/STORAGE F360 1

1/4" = 1'-0"

HAZARDOUS IV PREP/STORAGE F360 2

1/4" = 1'-0"

WORK ROOM F357 1

1/4" = 1'-0"

WORK ROOM F357 2

1/4" = 1'-0"

WORK AREA E303

1/4" = 1'-0"

RECEPTION E302

1/4" = 1'-0"

RECEPTION/WAITING

1/4" = 1'-0"

INTAKE ROOM E310 1

1/4" = 1'-0"

INTAKE ROOM E310 2

1/4" = 1'-0"

INFUSION BAY F366 1

1/4" = 1'-0"

INFUSION BAY F366 2

1/4" = 1'-0"

NURSE STATION F374 2

1/4" = 1'-0"

NURSE STATION F374

Revisions: Date:

Addendum #1 8/13/2021

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

TYPE FIRE RATINGSTUD SIZE

P00 NON-RATED7/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

ONE SIDE

CEILING AS

SCHEDULED

LINE OF FLOOR

PROVIDE SOUND PROOF

CAULK WHERE SOUND

ATTENUATION IS CALLED

FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

MTL RUNNER

7/8" HAT CHANNEL

FURRING

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P01 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

PROVIDE SOUND PROOF

CAULK WHERE SOUND

ATTENUATION IS CALLED

FOR ON THE PLANS

MTL RUNNER

5/8" GYP BD ON

ONE SIDE

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

PROVIDE SOUND PROOF

CAULK WHERE SOUND

ATTENUATION IS CALLED

FOR ON THE PLANS

MTL RUNNER

5/8" GYP BD ON

ONE SIDE

TYPE FIRE RATINGSTUD SIZE

P03 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

TYPE FIRE RATINGSTUD SIZE

P02 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

SOUND BATT

INSULATION

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P04 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

PROVIDE SOUND PROOF

CAULK WHERE SOUND

ATTENUATION IS CALLED

FOR ON THE PLANS

MTL RUNNER

5/8" GYP BD ON

ONE SIDE

TYPE FIRE RATINGSTUD SIZE

P05 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

SOUND BATT

INSULATION

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P06 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P07 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON

BOTH SIDES

CEILING AS

SCHEDULED

LINE OF FLOOR

6" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P09 NON-RATED6"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

5/8" GYP BD ON BOTH

SIDES (LEAD LINED ON

EMG/SCI/PROCEDURE

ROOM SIDES ONLY - LEAD

SHIELDING UP TO 7'-0"

A.F.F.)

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

IF TO DECK:

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

SOUND BATT

INSULATION

PROVIDE SOUND PROOF

CAULK BOTH SIDES WHERE

SOUND ATTENUATION IS

CALLED FOR ON THE PLANS

C E

IL

IN

G

A B

O V

E

MTL RUNNER

TYPE FIRE RATINGSTUD SIZE

P08 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

MTL RUNNER

5/8" TYPE "X"

GYP BD ON ONE

SIDE

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

PROVIDE FIRE RATED

CAULK

PROVIDE FIRE RATED

CAULK

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

TYPE FIRE RATINGSTUD SIZE

R02 1 HR3 5/8"

PLACEMENT

INTERIOR

STC

50 MINIMUM

UL

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

MTL RUNNER

5/8" TYPE "X"

GYP BD ON

BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

TYPE FIRE RATINGSTUD SIZE

R01 1 HR3 5/8"

PLACEMENT

INTERIOR

UL

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

TYPE FIRE RATINGSTUD SIZE

R03 1 HR3 5/8"

PLACEMENT

INTERIOR

UL

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

MTL RUNNER

5/8" TYPE "X"

GYP BD ON

BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

STC

50 MINIMUM

64" HIGH WAINSCOT

TILE-SEE ELVATIONS

ON SHEET 1-AE401/AE402

SOUND BATT

INSULATION

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

MTL RUNNER

5/8" TYPE "X"

GYP BD ON ONE

SIDE

PROVIDE FIRE RATED

CAULK

PROVIDE FIRE RATED

CAULK

TYPE FIRE RATINGSTUD SIZE

R04 1 HR3 5/8"

PLACEMENT

INTERIOR

UL

STC

50 MINIMUM

SOUND BATT

INSULATION

PLAN VIEW

SECTION VIEW

LINE OF STRUCTURE

TO DECK

CEILING AS

SCHEDULED

LINE OF FLOOR

STEEL TRACK NESTED

WITHIN DEFLECTION

TRACK WITHOUT

ATTACHMENT

TYPE FIRE RATINGSTUD SIZE

R05 1 HR3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

UL

3 5/8" MTL STUD

MECHANICALLY

FASTENED

DEFLECTION TRACK

MTL RUNNER

5/8" TYPE "X" GYP BD

ON BOTH SIDES

(LEAD LINED ON

PROCEDURE ROOM

SIDE ONLY - LEAD

SHIELDING UP TO

7'-0" A.F.F.)

PROVIDE FIRE RATED

CAULK BOTH SIDES

PROVIDE FIRE RATED

CAULK BOTH SIDES

PLAN VIEW

TYPE FIRE RATINGSTUD SIZE

E00 NON-RATEDN/A

PLACEMENT

EXTERIOR

SECTION VIEW

LINE OF

FLOOR

EXISTING WALL

FIELD VERIFY

CONSTRUCTION

TYPE FIRE RATINGSTUD SIZE

P10 NON-RATED3 5/8"

PLACEMENT

INTERIOR

STC

45 MINIMUM

PLAN VIEW

SECTION VIEW

54" HIGH

PARTITION

LINE OF FLOOR

3 5/8" MTL STUD

WOOD BLOCKING

MTL RUNNER

5/8" GYP BD ON

BOTH SIDE

STEEL TRACK

SOUND BATT

INSULATION

S-1 PARTITION CAP

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:4

:2

P

M

MK LJ

589A4-20-155

AE500

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

PARTITION TYPES 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

SUSPENDED GWB CEILING,

TYP

9/16" SHADOW REVEAL

TRANSITION MOLDING,

TAPED & FINISHED

SEE RCPSEE RCP

VARIES - RE: RCP

APC SYSTEM, TYP.

SEE RCP

SUSPENDED GWB CEILING,

TYP

9/16" SHADOW REVEAL

TRANSITION MOLDING,

TAPED & FINISHED

SEE RCP

APC SYSTEM, TYP.

SEE RCP

5/8" GWB

CORNER BEAD, TYP. AT

ALL CORNERS

3 5/8" MTL. STUD

EDGE MOLDING, TYP.

APC SYSTEM, TYP.

TO DECK ABOVE

SEE RCP

5/8" GYP. BD.

LAY-IN CEILING ON CEILING

SUSPENSION SYSTEM.

CONTINUE STUDS TO DECK.

PROVIDE SLIP CONNECTION

LAY-IN CEILING ON CEILING

SUSPENSION SYSTEM.

5/8" GYP. BD.

CONTINUE GYP. BD. TO

DECK

CONTINUE GYP. BD. TO

DECK

CONTINUE STUDS TO DECK.

PROVIDE SLIP CONNECTION

5/8" GYP. BD.

LAY-IN CEILING ON CEILING

SUSPENSION SYSTEM.

CONTINUE STUDS TO DECK.

PROVIDE SLIP CONNECTION

LAY-IN CEILING ON CEILING

SUSPENSION SYSTEM.

5/8" GYP. BD.

CONTINUE GYP. BD. TO

DECK

CONTINUE GYP. BD. TO

DECK

CONTINUE STUDS TO DECK.

PROVIDE SLIP CONNECTION

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Spinklered

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

C o lu m b ia C o m p le te U n fi n is h e d S p e c ia lt y C lin ic

/C o lu m b ia U n fi n is h e d S p e c C lin ic

V

.r v t

/1

/2

:0

:4

P

M

MK LJ

589A4-20-155

AE503

589A4 - COLUMBIA, MO

JUNE 25, 2021

01-

CEILING DETAILS 100% FINAL CONSTRUCTION

DOCUMENTS

COMPLETE UNFINISHED SPECIALTY

CLINIC

3" = 1'-0"

CEILING DETAIL

3" = 1'-0"

CEILING DETAIL

3" = 1'-0"

CEILING DETAIL

1 1/2" = 1'-0"

CEILING DETAIL AT CORRIDOR

1 1/2" = 1'-0"

CEILING DETAIL

3" = 1'-0"

PATIENT LIFT SUPPORT DETAIL

DOOR LEGEND & ABBREVIATIONS

DOOR PANEL TYPE LEGEND

AA PAIR BOTH ACTIVE

AI PAIR ACTIVE/INACTIVE

DE PAIR DOUBLE EGRESS

OC OVERHEAD COILING DOOR

SG SINGLE DOOR LEAF

SS SINGLE SLIDER

TS TELESCOPIC SLIDER

DOOR ABBREVIATIONS LEGEND

AL ALUMINUM

AP AI PHONE INTERCOM/CAMERA

CR CARD READER

CAL CARD ACCESS LOCKSET

DBL DOUBLE

EXT EXTERIOR

GL GLAZING

HM HOLLOW METAL

AL/GL ALUMINUM W/ GLASS

KP KEYPAD

CR/KP CARD READER/KEYPAD COMBO

MHO MAGNETIC HOLD-OPENS

MOT MOTION SENSOR

OPNG OPENING

PB PUSH BUTTON

PTD PAINTED

RR REMOTE RELEASE

SCWD SOLID-CORE WOOD DOOR

SMOKE SMOKE-TIGHT

THHD THRESHOLD

STL STEEL

DOOR NOTES

1. DOOR 116 MAGLOCK ACTIVATES UPON DOOR LATCHING

OR CARD READER ACTIVATION. DOOR AUTOMATICALLY

UNLOCKS UPON EITHER ACTIVATION OF THE FIRE ALARM

OR DETECTION OF WATERFLOW IN THE SPRINKLER

SYSTEM. CARD READER INSIDE THE ROOM SHALL BE

MOUNTED INSIDE THE WALL WITH A RED DOT PROVIDED

TO INDICATE SCAN AREA. DOOR SHALL BE SELF-LATCHING

APART FROM THE MAGLOCK.

2. CARD READER BOTH SIDES (IN-WALL ON ROOM SIDE)

KEYSWITCH OVERRIDE FOR CARD READER TO TURN 'ON'

AND 'OFF'.

3. KEYSWITCH TO OPERATE OVERHEAD COILING DOOR TO

BE LOCATED OUTSIDE SECURE HOLD EXAM AS SHOWN.

4. CONTRACTOR SHALL FIELD VERIFY WALL THICKNESSES

FOR EACH DOOR HEAD/JAMB

5. DOORS INDICATED TO BE "LEAD-LINED" SHALL BE

MANUFACTURED WITH EQUIVALENT LEAD THICKNESS AS

THE WALL WITHIN WHICH THEY WILL BE INSTALLED.

REFER TO PHYSICIST REPORT FOR SPECIFIC SHIELDING

REQUIREMENTS.

HEAD/JAMB DETAIL

1 LAYER

GYPSUM

WALL BOARD

INSULATION WHERE INDICATED

GYPSUM WALL

BOARD ON METAL

STUD

METAL STUD

FRAME

SEALANT

DOOR

1/2"

DIM.

PARTITION 1/2"

D O

O R

D

IM

PARTITION AS SCHED.

H.M. FRAME

CONT. SEALANT

(BOTH SIDES)

DOOR AS SCHED.

METAL STUD

TRACK - GAUGE TO

MATCH STUDS

+ 1"

PARTITION WIDTH

1/2"

DIM.

PARTITION 1/2"

D O

O R

D

IM

PARTITION AS SCHED.

H.M. FRAME

CONT. SEALANT

(BOTH SIDES)

DOOR AS SCHED.

+ 1"

PARTITION WIDTH

DOUBLE METAL STUDS

AT JAMBS - TYP.

SHIM AS REQUIRED

DOOR AS SCHED.

+ 1"

PARTITION WIDTH

/4

1/8" CLEARANCE ABOVE

THRESHOLD

DOOR

THRESHOLD

DOOR FRAME BEYOND

/4

TYPE CTYPE B

FLUSH PANEL

DOOR

FLUSH PANEL DOOR

W/ VISION PANEL

6"

6"

TYPE G

DOUBLE UNEVEN

PAIR OF FLUSH

PANEL DOORS

V A

R

IE

S

6" 6"

GL

TYPE D

FLUSH PANEL

DOOR W/ GLAZING

F-1

WIDTH AS SCHEDULED2" 2"

H E

IG

H

T A

S S

C H

E D

U L

E D

2" 2"

WIDTH AS SCHEDULED

H E

IG

H

T A

S S

C H

E D

U L

E D

F-2

2" OPEN WIDTH 1' - 8"

F-2

H E

IG

H

T A

S S

C H

E D

U L

E D

5/8" GYP. BD. OVER

MTL. STUD FRAMING

BLOCKING

EXISTING EXTERIOR WALL

EXISTING WINDOW

09 5113 METAL

CEILING TRIM

WINDOW SHADE WHERE

OCCURS.

5/8" GYP. BD.

OVER 3 5/8" MTL.

STUD

CEILING

9'-0"

NOTE: CONTRACTOR TO PROVIDE AND INSTALL BLINDS

/8

4 11/16" 4 5/16"

2"

WINDOW WIDTH

4' - 4"

F L

O O

R T

O S

IL

L

H E

IG

H

T

W

IN

D O

W H

E

IG

H T

F L

O O

R T

O S

IL

L

H E

IG

H

T

W

IN

D O

W H

E

IG

H T

WINDOW WIDTH

3' - 0"

EXISTING ALUMINUM

STOREFRONT

EXISTING EXTERIOR WALL

5/8" GYP. BD. OVER

EXISTING 3 5/8" MTL. STUD

GYP. ALUM. REGLET

EXISTING SOLID

SURFACE WINDOW

SILL

A-601 - DOOR SCHEDULE

LOCATION DOOR SLAB FRAME DETAILS

HARDWARE ACCESS CONTROL NOTES / REMARKSDOOR NUMBER

SIZE

TYPE RATING MATL. FINISH MATL. TYPE HEAD JAMB SILLWIDTH HEIGHT THK

BASEMENT

CBE2 5' - 0" 7' - 0" 1 3/4" G WD F-2 HM 2/AE601 3/AE601 4/AE601 HW-SH-9-MOD CR CARD READER POWER OPERATED

E001 4' - 0" 7' - 0" 1 3/4" EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING

E001A 3' - 6" 7' - 0" 1 3/4"

E001B 3' - 6" 7' - 0" 1 3/4" C WD GL-1 F-1 HM 2/AE601 3/AE601 4/AE601 HW-3E

E001C 3' - 6" 7' - 0" 1 3/4" C WD GL-1 F-1 HM 2/AE601 3/AE601 4/AE601 HW-3E

E001D 3' - 6" 7' - 0" 1 3/4" C WD GL-1 F-1 HM 2/AE601 3/AE601 4/AE601 HW-3E

E001E 5' - 0" 7' - 0" 1 3/4" G WD F-2 HM 2/AE601 3/AE601 4/AE601 HW-10D-MOD 3'-6" LEAF WIDTH

E001G 4' - 0" 7' - 0" 1 3/4" EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING

E001H 3' - 6" 7' - 0" 1 3/4" C 1 HOUR WD GL-2 F-1 HM 2/AE601 3/AE601 4/AE601 HW-SH-3-MOD CR CARD READER POWER OPERATED

E001J 3' - 6" 7' - 0" 1 3/4" C 1 HOUR WD GL-2 F-1 HM 2/AE601 3/AE601 4/AE601 HW-SH-3-MOD CR CARD READER POWER OPERATED

E001K 3' - 6" 7' - 0" 1 3/4" C 1 HOUR WD GL-2 F-1 HM 2/AE601 3/AE601 4/AE601 HW-SH-3

E002F 3' - 6" 7' - 0" 1 3/4" C WD GL-1 F-1 HM 2/AE601 3/AE601 4/AE601 HW-3E

E002K 3' - 6" 7' - 0" 1 3/4" C 1 HOUR WD GL-2 F-1 HM 2/AE601 3/AE601 4/AE601 HW-3E

E002L 3' - 6" 7' - 0" 1 3/4" C WD GL-1 F-1 HM 2/AE601 3/AE601 4/AE601 HW-SH-3-MOD CR CARD READER POWER OPERATED

F351.3 3' - 6" 7' - 0" 1 3/4" EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING

F351.4 3' - 6" 7' - 0" 1 3/4" B WD F-1 HM 2/AE601 3/AE601 4/AE601 HW-3E

LEVEL 03

E302 3' - 6" 7' - 0" 0" F-1 HM 2/AE601 3/AE601 4/AE601

E3…