568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part2.pdf

PDF 10 MB Posted

Attached to
Z1DA--568A4-21-208, DOM Reno Rooms Bldg 8 (HS) 36C263-25-AP-2561
Solicitation number
36C26325B0018_1
Issued by

About this file

This document is a set of architectural and life safety plans for the renovation of Domiciliary Building 8 at the Hot Springs VA Medical Center. The project involves a comprehensive renovation of a multi-story building with basement, first, and second floors, designed to meet VA construction and life safety code requirements. The building will be fully sprinklered and will have a Type V (111) construction classification, with an existing historic building designation.

The plans detail the renovation of residential board and care spaces, including multiple two-bed and one-bed bedrooms, toilets, storage areas, corridors, and support spaces. The total building area is 14,087 square feet, with each floor measuring approximately 4,475 square feet. Key design features include active fire safety systems such as smoke detectors, emergency lighting, fire alarm systems, and portable extinguishers. The design team includes Stone Group Architects, Albertson Engineering, and West Plains Engineering, with the project being managed by the VA Office of Construction and Facilities Management located in Hot Springs, South Dakota.

View the file

Other files

File Type Posted
568A4-21-208 DOM Reno Rooms Bldg 8 QA 2.docx DOCX document
36C26325B0018 0003.docx DOCX document
36C26325B0018 0002.docx DOCX document
Johnson Controls Single Source Justification_Redacted.pdf PDF
2025.08.22_211921 Hot Springs Dom 8_Add-1.pdf PDF
568A4-21-208 DOM Reno Rooms Bldg 8 QA Final.docx DOCX document
Statement of Work - 568A4-21-208_Revised 8.22.25.pdf PDF
Building 8 Site Visit Sign-in.pdf PDF
36C26325B0018 0001.docx DOCX document
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part4.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part8.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part7.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part13.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part6.pdf PDF
Statement of Work - 568A4-21-208.pdf PDF
Wage Determination SD20250022 01.03.2025.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part11.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part5.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part1.pdf PDF
36C26325B0018.docx DOCX document
TMS 20939 VA Privacy Training.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part12.pdf PDF
Final Specs Combined 6-6-25.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part9.pdf PDF
Safety or Environmental Violations and EMR Information.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part10.pdf PDF
568A4-21-208 HOT SPRINGS VA DOMICILIARY RENO BLDG 9_Part3.pdf PDF
VAAR 852.219-75 Limitations on Subcontracting Cert of Compliance.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT INFORMATION:

1. CONSTRUCTION PURPOSE: RENOVATION

2. REASON FOR SUBMITTAL: RENOVATION

3. I CERTIFY THAT TO THE BEST OF OUR KNOWLEDGE THE SUBMITTED PLANS FOR THE

ABOVE-REFERENCED PROJECT COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING:

NFPA 101-18 (AND ALL REFERENCED DOCUMENTS)

2018 INTERNATIONAL MECHANICAL CODE (IMC)

2015 UNIFORM PLUMBING CODE (UPC)

2017 NATIONAL ELECTRICAL CODE (NFPA-70)

2018 LIFE SAFETY CODE (NFPA-101)

2015 ABA ACCESSIBILITY STANDARDS

BARRIER FREE DESIGN

2018 IBC WITH LOCAL AMENDMENTS

ASHRAE STANDARD 90.1 (2007)

ASHRAE 62.1 (2007)

4. LOCATION OF ANY ANTICIPATED FUTURE ADDITIONS: UNKNOWN

5. OWNER:

DEPARTMENT OF VETERANS AFFAIRS

OFFICE OF CONSTRUCTION AND FACILITIES MANAGEMENT

500 NORTH 5TH STREET

HOT SPRINGS, SD 57747

6. DESIGN TEAM:

STONE GROUP ARCHITECTS - 605-271-1144

600 E 7TH STREET - SIOUX FALLS, SD 57103

CONTACT: TODD STONE - TODD.STONE@STONEGROUPARCH.COM

ALBERTSON ENGINEERDING - 651-343-9606

3202 W MAIN ST, SUITE C - RAPID CITY, SD 57702

CONTACT: DAVID LEPPERT (STRUCTURAL) - DAVID@ALBERTSONENGINEERING.COM

WEST PLAINS ENGINEERING - 605-348-7455

1750 RAND ROAD - RAPID CITY, SD 57702

CONTACT:

MIKE SIGMAN (ELECTRICAL) - MIKE.SIGMAN@WESTPLAINSENGINEERING.COM

MICHAEL HEINRICH (MECHANICAL) - MICHAEL.HEINRICH@WESTPLAINSENGINEERING.COM

7. ARCHITECTS SEAL: SEE STAMP AT BOTTOM

8. FIRE SERVICE: HOT SPRINGS FIRE DEPARTMENT

9. INSPECTION: VISN SAFETY OFFICER

10. OCCUPANCY GROUP TYPE: RESIDENTIAL BOARD AND CARE

BUSINESS

CHANGE OF OCCUPANCY- 1ST AND 2ND FLOOR (NO)

MIXED OCCUPANCIES - PROPOSED NEW CONSTRUCTION (YES)

2ND- RESIDENTIAL BOARD AND CARE

1ST- RESIDENTIAL BOARD AND CARE

BASEMENT- BUSINESS

11. CONSTRUCTION TYPE: TYPE V (111) FULLY SPRINKLERED

HISTORIC BUILDING: YES

A. ALLOWABLE AREA PER FLOOR: NO CHANGE

ACTUAL AREA PER FLOOR

ATTIC - MECHANICAL: 3,900 SF

SECOND FLOOR: 4,475 SF

ARCADE LOBBY UL: 331 SF

FIRST FLOOR: 4,475 SF

ARCADE LOBBY LL: 331 SF

BASEMENT: 4,475 SF

TOTAL: 14,087 SF

B. BUILDING HEIGHT: NO CHANGE

ACTUAL BUILDING HEIGHT: 48'

STORIES: 2 W/ BASEMENT

12. ACTIVE FIRE SAFETY SYSTEMS

(a) SMOKE DETECTORS THROUGHOUT

(b) GENERATOR POWERED EMERGENCY LIGHTING

(c) BATTERY POWERED EXIT LIGHTING

(d) HOOD SUPPRESSION SYSTEM

(e) PORTABLE EXTINGUISHERS

(f) AUTOMATIC AIR-HANDLING SHUT-DOWN

(g) FIRE ALARM SYSTEM

13. WATER SUPPLY: NATURAL SPRING

14. SEWAGE TREATMENT: CITY OF HOT SPRINGS

15. HANDICAP PROVISIONS: ACCESSIBLE ROUTE

LAVATORIES AND SIGNAGE

16. OCCUPATIONAL LOAD:

OUTPATIENT INSTITUTIONAL: 150 SF/PERSON GROSS

EGRESS CAPACITY:

STAIRWAY: .3 IN./PERSON

DOOR: .2 IN./PERSON

CODE INFORMATION

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD

STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE INFORMATION ON THE

TECHNICAL INFORMATION LIBRARY (TIL)

• INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA

DESIGN DOCUMENTS)

• 2018 NFPA 101 LIFE SAFETY CODE

• 2018 IBC

• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

• VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• NATIONAL ELECTRICAL CODE (NEC)

• INTERNATIONAL PLUMBING CODE (IPC)

• ASME BOILER AND PRESSURE VESSEL CODE

• ASME CODE FOR PRESSURE PIPING

• ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA

SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)

• VA FIRE PROTECTION DESIGN MANUAL

NOTE: ALL WORK IS TO BE PERFORMED TO THE LATEST EDITION OF THE FOLLOWING CODES, ORDINANCES, AND LAWS WHICH INCLUDE, BUT ARE NOT LIMITED TO: A. CONTRACTOR IS NOT AUTHORIZED TO SCALE CONSTRUCTION DOCUMENTS. ARCHITECT IS TO BE NOTIFIED IN THE EVENT A DISCREPANCY IS FOUND IN EITHER SPECIFICATIONS OR CONTRACT

DOCUMENTS AT THE EARLIEST PRACTICAL OPPORTUNITY.

B. GENERAL CONTRACTOR SHALL OBSERVE ALL REGULATIONS IMPOSED BY GOVERNING BODIES.

C. CONSTRUCTION SHALL PROCEED IN AN ORDERLY AND CONTINUOUS FASHION IN ACCORDANCE WITH

THE INTERNATIONAL BUILDING CODES AND ALL OTHER APPLICABLE CODES.

D. THE CONTRACTOR SHALL CONTAIN ALL CONSTRUCTION ACTIVITY, INCLUDING STORAGE OF MATERIAL

AND EQUIPMENT, WITHIN THE CONSTRUCTION LIMITS, AT ALL TIMES BEING RESPONSIBLE FOR AND

ABIDING BY RULES AND REGULATIONS OF THE OWNER.

E. GENERAL CONTRACTOR TO BE RESPONSIBLE FOR REPAIRING ANY AND ALL SURFACES DAMAGED BY

HIMSELF OR SUBCONTRACTORS UNDER HIS CONTROL. REPAIRS ARE TO MATCH EXISTING

MATERIALS AND MUST BE ACCEPTABLE TO OWNER.

F. ADEQUATELY PATCH/REPAIR TO MATCH ADJACENT CONSTRUCTION, ALL BUILDING STRUCTURES, COMPONENTS, AND UTILITIES WHICH ARE DISTURBED AND REQUIRE REPAIR AS A RESULT OF WORK

PERFORMED UNDER THIS CONTRACT.

G. ALL FLOOR TRANSITIONS BETWEEN DIFFERENT MATERIALS SHALL BE SMOOTH AND FLUSH (MAXIMUM

SLOPE = 1/8" PER FOOT).

H. GENERAL CONTRACTOR SHALL REMOVE ALL CONSTRUCTION DEBRIS FROM JOBSITE. ALL

CONSTRUCTION DEBRIS SHALL BE CONTAINED INSIDE CONSTRUCTION LIMITS.

I. ALL WALLS WITH ITEMS SUCH AS GRAB BARS, TOILET ACCESSORIES, WOOD TRIM, SHELVING, CASEWORK, ETC. SHALL BE REINFORCED WITH CONCEALED, FIRE TREATED WOOD BLOCKING OR

METAL STUD BLOCKING. (GENERAL CONTRACTOR TO INSTALL BLOCKING TYP.)

J. BUILDING 5 WILL REMAIN OCCUPIED THROUGHOUT THE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL TAKE EVERY NECESSARY PRECAUTION TO ENSURE THE UNINTERRUPTED OPERATION OF THE FACILITY, STAFF, PATIENTS AND VISITORS. DISRUPTION TO ADJACENT DEPARTMENTS AS WELL AS

DEPARTMENTS ON FLOORS ABOVE OR BELOW SHALL BE COORDINATED WITH THE FACILITY

CONTRACT OFFICER. THE CONTRACTOR SHALL COORDINATE ALL WORK, CONSTRUCTION, PATHWAYS, ELEVATOR USAGE, AND UTILITY INTERRUPTION WITH THE OWNER.

K. CONTRACTOR TO EXERCISE ALL PRECAUTIONS TO PROVIDE FOR STAFF, PATIENTS, VISITORS, AND WORKMEN'S SAFETY DURING THE PERFORMANCE OF THIS CONTRACT PER EPA, OSHA, AND OTHER

APPLICABLE CODES, STANDARDS, AND REGULATIONS.

L. THE CONTRACTOR SHALL MAINTAIN & KEEP BARRIER FREE THE EXISTING MEANS OF EGRESS.

M. ALL GYPSUM BOARD TO BE MOISTURE/MOLD RESISTANT TYPE X.

N. THE CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION OF TEMPORARY PARTITIONS AND

TEMPORARY VENTILATION SYSTEMS AS REQUIRED TO PREVENT THE SPREAD OF DUST FROM THE

CONSTRUCTION AREA TO OCCUPIED AREAS OF THE BUILDING. OCCUPIED AREAS SHALL REMAIN DUST FREE THROUGHOUT THE CONSTRUCTION. THE CONTRACTOR SHALL MAINTAIN THE AFFECTED AREAS

OF THE BUILDING (INCLUDING MATERIAL TRANSPORT ROUTES) CLEAN AND DUST FREE.

O. ALL WOOD USED IN WALL CONSTRUCTION SHALL BE FIRE-RETARDANT-TREATED LUMBER.

P. ALL WRITTEN CORRESPONDENCE WILL BE TRANSMITTED FROM SUBCONTRACTOR THROUGH

GENERAL CONTRACTOR THROUGH ARCHITECT TO OWNER. ALL PARTIES CORRESPONDENCE ARE TO

RECEIVE WRITTEN AND SIGNED COPIES OF SUCH. NO VERBAL AGREEMENTS AFFECTING COST OR

ALTERNATIVE CONSTRUCTION METHODS AND ARRANGEMENTS WILL BE CONSIDERED VALID OR

BINDING, AND ARE THEREFORE, DISALLOWED.

Q. GENERAL CONTRACTOR SHALL COMPLY WITH ALL DIRECTIVES OF THE OWNER. IF CONFLICTS

BETWEEN DRAWINGS, SPECIFICATIONS AND REQUIREMENTS OF BUILDING OWNER AND/OR

OPERATORS ARISE, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY.

R. THE HVAC, PLUMBING AND ELECTRICAL CONTRACTORS SHALL COORDINATE THEIR WORK WITH THE

WORK OF OTHER TRADES TO ASSURE THAT THE WORK CAN BE INSTALLED IN A WORKMAN-LIKE

MANNER. EACH CONTRACTOR SHALL BE EXPECTED TO COOPERATE WITH OTHER CONTRACTORS IN

THE PLACEMENT OF WORK TO AVOID CONFLICTS AND MAINTAIN JOB PROGRESS.

S. IT IS THE INTENT OF THESE DRAWINGS THAT A COMPLETE JOB IS TO BE ACCOMPLISHED IN PREPARING THE BID. THE BIDDER SHALL MAKE ALLOWANCES FOR DETAILS WHICH MIGHT HAVE BEEN

INADVERTENTLY OMITTED FROM THE DRAWINGS.

T. ALL EXISTING DUCTWORK, ELECTRICAL OR PIPING IS NOT NECESSARILY SHOWN ON THE DRAWINGS.

U. BEFORE CONTRACTOR(S) BID THE JOB, IT IS IMPERATIVE THEY VISIT THE JOBSITE AND FIELD VERIFY

THE EXACT LOCATION OF ALL EXISTING EQUIPMENT, DUCTWORK, ETC. IT WILL BE PART OF THE CONTRACTOR'S RESPONSIBILITY TO DESIGN AND RELOCATE ANY EXISTING OBSTACLES WHICH WILL INTERFERE WITH THE CONTRACTOR'S ABILITY TO INSTALL ALL NEW OR RELOCATED WORK ON HIS

CONTRACT.

A. ALL EXISTING DUCTWORK, ELECTRICAL OR PIPING IS NOT NECESSARILY SHOWN ON THE DRAWINGS.

B. BEFORE CONTRACTOR(S) BID THE JOB, IT IS IMPERATIVE THEY VISIT THE JOBSITE AND FIELD VERIFY

THE EXACT LOCATION OF ALL EXISTING EQUIPMENT, DUCTWORK, ETC. IT WILL BE PART OF THE CONTRACTOR'S RESPONSIBILITY AND COST TO ENGINEER AND RELOCATE ANY EXISTING OBSTACLES WHICH WILL INTERFERE WITH THE CONTRACTOR'S ABILITY TO INSTALL ALL NEW OR RELOCATED

WORK ON HIS CONTRACT.

C. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN FIELD AND NOTIFY PROJECT ENGINEER OF ALL

DISCREPANCIES IF ANY, FOUND PRIOR TO PLACEMENT OF ANY COMPONENTS

D. THE CONTRACTOR WILL TAKE ALL NECESSARY PRECAUTIONS INCLUDING THE BUILDING AND

MAINTENANCE OF DUST TIGHT PARTITIONS, DAILY VACUUMING, SWEEPING, AND PROVISION OF CLEAN FLOOR MATS AT THE PROJECT ENTRANCES, TO PREVENT THE INFILTRATION OF DIRT AND

DUST FROM THE CONSTRUCTION AREAS INTO THE OWNER OCCUPIED AREAS.

E. PATCH ALL FINISHES WHERE DISTURBED BY THE WORK AND WHERE UNFINISHED SURFACES HAVE

BEEN EXPOSED BY DEMOLITION. PATCHING MUST MATCH ADJACENT MATERIALS, COLORS, AND

FINISHES. WALL SURFACES THAT ARE PATCHED SHALL HAVE THE FINISHES (PAINT, VINYL WALL

COVERING, ETC.) REPLACED FROM CORNER TO CORNER AND FLOOR TO CEILING.

F. UNLESS OTHERWISE INDICATED FINISH ALL NEW FRAMES AND PARTITIONS TO MATCH SURROUNDING.

NEW HOLLOW METAL DOORS SHALL BE PAINTED SAME COLOR AS FRAMES. EXISTING PARTITIONS

RECEIVING NEW DOOR FRAMES THAT HAVE VINYL WALL COVERING (VWC) SHALL HAVE THE VWC

COMPLETELY REMOVED AND REPLACED WITH NEW VWC OF MATCHING TEXTURE AND COLOR

G. PAINT ALL EXPOSED NEW AND EXISTING PIPING, CONDUIT, WIRE MOLD, ELECTRICAL PANELS, ACCESS

PANELS, ETC.,TO MATCH WALL FINISH UNLESS OTHERWISE NOTED.

H. CORRIDOR WALLS AND PLUMBING PARTITIONS SHALL BE CONSIDERED 1 HOUR FIRE RATED WALLS, UON, AND NEW OR EXISTING PENETRATIONS MUST BE SEALED ACCORDINGLY WITH APPROVED

FIRESTOPPING MATERIAL THE SAME DAY THE PENETRATION IS MADE OR DISCOVERED. ALL FLOOR SLABS, VERTICAL SHAFTS AND STAIRWELLS SHALL BE CONSIDERED 2 HOUR RATED PARTITIONS AND BE SEALED ACCORDINGLY IN THE MANNER LISTED HEREIN. PENETRATIONS THROUGH THE EXTERIOR

WALLS SHALL BE SEALED WATERTIGHT.

I. ALL NEW VERTICAL AND HORIZONTAL DUCTS, PIPES, CONDUITS, ETC.,IN FINISHED ROOMS OR AREAS

THROUGHOUT BUILDING, NOT ENCASED IN MASONRY OR CONCRETE CONSTRUCTION, SHALL BE

FURRED IN, THE FURRING FINISHED TO MATCH THE ROOM FINISH.

J. WHENEVER EXISTING EQUIPMENT, PIPING, DUCTS, ETC., ARE REQUIRED TO BE REMOVED, SUCH

REMOVAL SHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS NOTED

OTHERWISE. AFTER REMOVAL; FLOORS, WALLS, AND CEILINGS SHALL BE FINISHED TO MATCH

ADJOINING SURFACES.

K. UTILITY WORK THAT WILL REQUIRE A SHUTDOWN OF EXISTING SERVICE(S) WILL BE DONE AFTER NORMAL WORKING HOURS (NIGHTS, WEEKENDS, HOLIDAYS, ETC.) AT NO ADDITIONAL COST TO THE

GOVERNMENT. WORK MUST BE SCHEDULED WITH THE COR.

L. WORK THAT MUST OCCUR IN OCCUPIED AREAS, SUCH AS PUBLIC CORRIDORS, OF THE MEDICAL CENTER OR DISRUPT A MEDICAL CENTER FUNCTION WILL BE DONE AT TIMES OTHER THAN NORMAL

WORKING HOURS (NIGHTS, WEEKENDS, HOLIDAYS, ETC.) AT NO ADDITIONAL COST TO THE

GOVERNMENT. WORK MUST BE SCHEDULED WITH THE V.A. PROJECT ENGINEER.

M. ALL ELECTRICAL CIRCUITRY TO BE CONCEALED UNLESS OTHERWISE SPECIFIED. CIRCUITING FOR

ELECTRIC DOOR HOLD OPENS IN MASONRY WALLS SHALL BE SURFACE RACEWAY.

N. COORDINATE ALL WORK WITH OTHER TRADES AND EXISTING CONDITIONS TO ELIMINATE CONFLICTS AND/OR INTERFERENCES. THE CONTRACTOR SHALL PROVIDE ALL OFFSETS, FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR A COMPLETE AND FUNCTIONAL SYSTEM.

O. DRAWINGS ARE DIAGRAMMATIC AND SHOW ONLY THE GENERAL ARRANGEMENT OF EACH SYSTEM.

BECAUSE OF SMALL SCALE OF DRAWINGS IT IS NOT POSSIBLE TO SHOW OR INDICATE ALL BRANCHES, OFFSETS, FITTINGS, BOXES, AND ACCESSORIES WHICH MAY BE REQUIRED. CONTRACTOR MUST

CAREFULLY INVESTIGATE STRUCTURAL AND FINISH CONDITIONS AFFECTING ALL WORK, FURNISHING

SUCH FITTINGS, TRAPS, VALVES, BOXES, ACCESSORIES, ETC., AS MAY BE REQUIRED.

P. LOCATIONS OF NEW EQUIPMENT, PIPING, AND ASSOCIATED ITEMS SHOWN ON THE DRAWINGS ARE SCHEMATIC ONLY. THE CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION AND ELEVATION FOR ALL WORK, INCLUDING CONNECTIONS TO EXISTING WORK. ALL OFFSETS, FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR A COMPLETE AND FUNCTIONAL SYSTEM SHALL BE PROVIDED AT

NO ADDITIONAL COST.

Q. ALL EXISTING DUCTWORK, ELECTRICAL OR MECHANICAL PIPING, CABLE TRAYS, ETC., IS NOT NECESSARILY SHOWN ON THE DRAWINGS. BEFORE CONTRACTOR PLACES A BID IT IS IMPERATIVE THEY VISIT THE JOBSITE AND FIELD VERIFY THE EXACT LOCATION OF ALL EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. IT WILL BE PART OF THE CONTRACTOR'S RESPONSIBILITY AND THE CONTRACTOR WILL BEAR THE COST TO ENGINEER AND RELOCATE ANY EXISTING OBSTACLES WHICH WILL INTERFERE WITH THE CONTRACTOR'S ABILITY TO INSTALL ALL NEW OR RELOCATED WORK IN

THIS PROJECT.

R. CONTRACTOR SHALL NOT INSTALL CONDUIT, PIPING, LIGHTING, OR OTHER OBSTRUCTIONS UNDER OR ADJACENT TO HVAC EQUIPMENT THAT WILL ELIMINATE OR OBSTRUCT ACCESS TO COILS, MOTORS, VALVES, SWITCHES, PANELS, ETC.

S. BEFORE THE CONTRACTOR BEGINS WORK HE SHALL RECORD ANY EXISTING SYSTEM INFORMATION

SUCH AS TEMPERATURE, FLOW RATE, PRESSURE, CURRENT, VOLATAGE, OR ANY OTHER

INFORMATION NECESSARY FOR HIM TO RETURN THE AFFECTED SYSTEM TO ORIGINAL OPERATING CONDITION. UNLESS NOTED OTHERWISE IT IS ASSUMED THAT ALL SYSTEMS ( HVAC, ELECTRICAL, PLUMBING, ETC.) ARE WORKING PROPERLY IN EVERY MANNER AT THE BEGINNING OF THE PROJECT.

THE CONTRACTOR'S RECORDED MEASUREMENTS MUST BE SUBMITTED TO THE PROJECT ENGINEER

FOR REVIEW AND ACCEPTANCE BEFORE ANY DEMOLITION OR OTHER RELATED WORK CAN PROCEED.

T. FOR DOORS BEING REPLACED: IF THE EXISTING DOOR HAS SIGNAGE APPLIED TO IT, THIS SIGNAGE SHOULD BE CAREFULLY REMOVED AND REAPPLIED TO THE NEW DOOR. IF THE SIGNAGE IS DAMAGED

DURING REMOVAL OR CANNOT OTHERWISE BE REAPPLIED IT SHOULD BE REPLACED WITH NEW

SIGNAGE OF IDENTICAL TYPE.

U. THE CONTRACTOR WILL BE RESPONSIBLE FOR MAINTAINING ALL EXISTING ACCESS DOORS TO

CONSTRUCTION AREAS, EXISTING MECHANICAL AND ELECTRICAL AREAS, ASSIGNED STORAGE

AREAS, EQUIPMENT ACCESS AREAS, ETC. DOORS MUST BE RESTORED TO THE CONDITION

ENCOUNTERED AT BEGINNING OF PROJECT. THIS INCLUDES DOOR REPLACEMENT, HARDWARE

REPLACEMENT, HARDWARE REPAIR, DOOR REPAIR, ETC.

V. IT IS IMPORTANT THAT ALL REPLACEMENT DOORS HAVE A GAP OF LESS THAN 3/4" BETWEEN THE

BOTTOM OF THE DOOR AND THE FLOOR AT ALL POINTS. CONTRACTOR MUST COORDINATE

INSTALLED DOOR FRAME HEIGHT OR MAKE OTHER NECESSARY MODIFICATIONS0 TO MEET THIS

REQUIREMENT AND KEEP FIRE RATING OF DOOR AND FRAME. BOTTOM SWEEPS ARE NOT

ACCEPTABLE UNLESS SPECIFICALLY STATED ON DRAWING.

W. IF THERE IS ANY WORK TO BE DONE ON EXISTING ROOFS, SUCH AS ROOF PENETRATIONS OR STANDS, OR ANYTHING THAT DAMAGES THE INTEGRITY OF THE ROOF, THIS WORK MUST BE DONE BY A CONTRACTOR LICENSED BY THE ROOFING MEMBRANE MANUFACTURER. HE MUST BE APPROVED BY

THE MEMBRANE MANUFACTURER SO AS TO NOT VOID OR INTERRUPT EXISTING SINGLE PLY

MEMBRANE ROOF WARRANTIES.

X. EXISTING CIRCUITRY (CONDUIT, BOXES, WIRE, ETC.) MAY BE REUSED AT THE CONTRACTOR'S OPTION AS LONG AS IT MEETS THE SAME SPECIFICATIONS REQUIRED FOR NEW CIRCUITRY. ALL WORK, NEW

AND EXISTING, SHALL COMPLY WITH THE LATEST NEC CODE.

Y. WHERE DOOR AND HARDWARE ARE SHOWN TO BE REMOVED, THE DOOR STOPS ARE TO REMAIN AND

BE REUSED UNLESS NOTED OTHERWISE.

CONTRACTOR GENERAL NOTESPROJECT GENERAL NOTESBUILDING CODES, GUIDE AND MANUALS

• BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE

INSTITUTE AND COMMENTARY (ACI 318)

• MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE FACTOR DESIGN

SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL

CONSTRUCTION (AISC)

• DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL,

COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-

RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434, AND 435.

• FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS:

MEMORANDUM OF UNDERSTANDING (MOU)

• EXECUTIVE ORDER 13834

• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL

REQUIRMENTS SECTION 01010 IF THE VA MASTER CONSTRUCTION SPECIFICATION.

• VENTILATION FOR THE ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1 –

2004.

• SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 – 2007.

• ENERGY POLICY ACT OF 2005 (EPACT)

PLUMBING WATER LAVATORIES SHOWER DRINKING SERVICE

FIXTURES FOUNTAINS SINKS

BUSINESS 1 PER 25 1 PER 40 1 PER 100 1 SINK

(FIRST 50) (FIRST 80)

REQUIRED 2 WC 2 LAVS 1 DF 1 SINK

RESIDENTIAL 1 PER UNIT 1 PER UNIT 1 PER UNIT 1 SINK

REQUIRED 14 WC 14 LAVS 14 SHWR 2 SINKS

TOTAL REQUIRED 16 WC 16 LAVS 14 SHWR 1 DF 3 SINKS

TOTAL PROVIDED 18 WC 18 LAVS 14 SHWR 2 DF 3 SINKS

ARRANGEMENT OF MEANS OF EGRESS

BUISNESS OCCUPANCY - FULLY SPRINKLERED

TRAVEL DISTANCE (NFPA 101 39.2.6.3) 300 FT

COMMON PATH OF TRAVEL (NFPA 101 39.2.5.3.1) 100 FT

DEAD END (NFPA 101 39.2.5.2) 50 FT

LARGE RESIDENTIAL BOARD AND CARE - FULLY SPRINKLERED

TRAVEL DISTANCE

WITHIN ROOM TO CORRIDOR (NFPA 101 33.3.2.6.2) 125 FT

CORRIDOR DOOR TO EXIT (NFPA 101 33.3.2.6.3.1) 100 FT

COMMON PATH OF TRAVEL (NFPA 101 33.3.2.5.3) 160 FT

DEAD END (NFPA 101 33.3.2.5.4) 50 FT

MISCELLANEOUS

YES NO

FIRE RESISTIVE CORRIDORS

SMOKE TIGHT CORRIDORS (SMOKE PARTITIONS)

INCIDENTAL USE AREA RATINGS SEE PLANS

INTERIOR FINISHES CLASSIFICATION EXITS A

EXIT ACCESS CORRDORS A

OTHER SPACES B

FIRE-RESISTANCE REQUIREMENTS: CONSTRUCTION TYPE V (111)

STRUCTURAL FRAME:

COLUMNS: EXISTING / 1HR NFPA - A.8.2.1.2

GIRDERS: EXISTING / 1HR NFPA - A.8.2.1.2

TRUSSES: EXISTING / 1HR NFPA - A.8.2.1.2

BEARING WALLS:

EXTERIOR BEARING WALLS: EXISTING / 1 HR NFPA - A.8.2.1.2

BEARING WALLS INTERIOR: EXISTING / 1 HR NFPA - A.8.2.1.2

NON-BEARING WALLS:

EXTERIOR NON-BEARING WALLS: 0 HR NFPA - A.8.2.1.2

INTERIOR NON-BEARING WALLS: SEE LIFE PLANS

FLOOR CONSTRUCTION:

FLOOR AND FLOOR/CEILING: EXISTING / 1HR NFPA - A.8.2.1.2

PRIME & SEC. BEAMS & JOISTS: EXISTING / 0HR NFPA - A.8.2.1.2

ROOF CONSTRUCTION:

ROOF AND ROOF/CEILING: EXISTING / 1HR NFPA - A.8.2.1.2

PRIME & SEC. BEAMS & JOISTS: EXISTING / 0HR NFPA - A.8.2.1.2

OTHER:

SHAFTS & EXIT PASSAGEWAYS: 1HR NFPA - 33.2.3.1.3, 8.6.5

ELEVATOR (ACCESSIBLE EGRESS) 2HR NFPA - 9.4/ASME 17.1

VA FORM 08 - 6231

A

B

C

D

A

B

C

D

2 4 5 61

6"

6"

6"

6"

O N

E E

IG

H

T H

I N

C H

O

N E

F O

O T

1/

8"

'-0

O

N E

Q U

A R

T E

R I

N C

H

O N

E F

O O

T

1/ 4"

'-0

T H

R E

E E

IG

H

T H

S

IN

C H

O

N E

F O

O T

(3 /8

1' -0

O

N E

H A

LF

I

N C

H

O N

E F

O O

T

1/ 2"

'-0

T H

R E

E Q

U A

R T

E R

S

IN

C H

O

N E

F O

O T

3/

4"

'-0

O

N E

I N

C H

O

N E

F O

O T

1"

'-0

O N

E A

N D

O N

E H

A

LF

I N

C H

E S

O

N E

F O

O T

1/ 2"

'-0

T H

R E

E

IN

C H

E S

O

N E

F O

O T

3"

'-0

32 4 5 61

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANTS

STRUCTURAL:

ALBERTSON ENGINEERING, INC.

3202 W. MAIN ST., #C

RAPID CITY, SD 57702

605-343-9606

MEP:

WEST PLAINS ENGINEERING, INC.

1750 RAND ROAD

RAPID CITY, SD 57702

605-348-7455

STEPHEN KILBER MIKE SIGMAN (ELEC)

MICHAEL HEINRICH (MECH)

C :\U se rs

\K .K ue pe r\D oc um en ts \2

D om R en ov

B ui ld in g

_k yl ek 9D

U H

U .rv t 6/

2/

:0 1:

P

M

GI014

CODE REVIEW, PCRA, ICRA, ISLM, GEN NOTES

STONE GROUP ARCHITECTS

600 EAST 7TH ST.

SIOUX FALLS, SD 57103

605-271-1144

TODD STONE

DOM RENOVATION FOR

SEMIPRIVATE ROOMS

HOT SPRINGS, SD

DOUG SPRINKLE

06/03/2025 JM/GB/TM TL/KK

SGA #211921

VA #568A4-21-208

BID DOCUMENTS

ISSUE # DESCRIPTION DATE

1 BID DOCUMENTS 06/03/2025

UP

UP

204 SF

B14

STAFF

LOUNGE

107 SF

B13

MH OFFICE

100 SF

B12

MH OFFICE

100 SF

B11

MH OFFICE

412 SF

B10

MECHANICAL

58 SF

B09

HAC

100 SF

B08

MH OFFICE

62 SF

B15A

STORAGE

76 SF

B16

TOILET,

WOMEN

122 SF

B17

MH OFFICE

128 SF

B18

MH OFFICE

128 SF

B19

MH OFFICE 75 SF

B20

TOILET,

MEN

109 SF

B21

MH OFFICE

331 SF

B05

GYM

204 SF

B07

GROUP

ROOM MH

67 SF

B01

STORAGE

14 SF

B03

ELEC

100 SF

ELEVATOR

65 SF

B05A

ELEVATOR

EQUIPMENT

164 SF

B06

UNASSIGNED

MH

203 SF

B15

GROUP

ROOM MH

1002 SF

B00

BASEMENT

CORRIDOR

LENGTH OF TRAVEL: 69'-7"

LENGTH OF TRAVEL: 97'-1"

FEC

FEC

8.6"

34.0"

1 14

EX

157 SF

B04

UNASSIGNED

MH

125 SF

B02

TR

1 1 1

1 1

75'-0"

75'-0"

TWO-STORY EXIT ENLCLOSURE IS

OPEN TO BASEMENT WITHIN AN

EXISTING BUILDING. COMPLIANT

WITH NFPA 101 PER 7.2.2.5.1.3

B06A

FIRE

SERVICE

B00

BASEMENT

CORRIDOR

8.7"

60.0"

TO B.O. STAIR + 21'-0" (B.O. STAIR TO DOOR ABOVE)

21.9"

38.0"

8.33A

14.01

G A

T E

22.03

0.0"

0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

CODE & EGRESS SYMBOL LEGEND

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

DIRECTION OF EGRESS

DIRECTION OF EGRESSPATH OF TRAVEL

START OF PATH TRAVEL DISTANCE (TD)

TD = X'-X"

FEC

FE

EXITEX

CONSTRUCTION LEGEND

AREA NOT IN CONSTRUCTION BOUNDARIES

EXISTING COMPONENTS

NEW COMPONENTS

GENERAL CODE NOTES

H. SMOKE SEALS TO BE INSTALLED AT ALL RATED DOORS.

I. SMOKE SEALS TO BE INSTALLED AT NON RATED SMOKE PARTITION & BARRIER DOORS UON.

A. ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT & THE OWNER BEFORE

PROCEEDING WITH THE WORK.

B. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

C. CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

D. ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

E. DETAILS SHOWN ARE TYPICAL UON. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

F. SEE STRUCTURAL, MECHANICAL, ELECTRICAL, & PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

G. DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR

GRID UON. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UON.

BUILDING & LIFE SAFETY REQUIREMENT LEGEND

DESCRIPTION

WALL

RATING

PARTITION KEY

NFPA 101-2021

IBC 2023

OPENINGS

RATING REFERENCE

FIRE WALL:

BUILDING SEPARATION

90 MINFIRE BARRIER:

OCCUPANCY/AREA SEPARATION

90 MIN

FIRE BARRIER:

HORIZONTAL EXIT & REFUGE AREA

90 MINNFPA 7.1.3.2

NFPA 8.2.1.3

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

NFPA 8.3.3.2.2

2 HOUR

FIRE BARRIER

VERTICAL EXIT PASSAGEWAY

60 MIN

FIRE BARRIER

HORIZONTAL EXIT PASSAGEWAY

NFPA 7.2.6

NFPA 8.6

NFPA 8.3.3.2.2

NFPA 8.3.3.2.2

FIRE BARRIER

VERTICAL EXIT ENCLOSURE/SHAFT

(2 HR = 4 OR MORE STORIES)

(1 HR = LESS THAN 4 STORIES) 60 MIN

90 MINNFPA 8.6

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

90 MIN

1 HR

2 HR

SMOKE PARTITION

(SPRINKLERED)

HAZARDOUS/INCIDENTAL USE

NR

SMOKE BARRIER

SUBDIVIDING SPACES

20 MIN

SMOKE PARTITION

SLEEPING RM SEPARATION REQ

EXIT ACCESS CORRIDOR

(SPRINKLERED) CORRIDOR WALLS

NR

NFPA 8.5

IBC 716.1

NFPA 8.4.2

NFPA 32.3.3.6

NFPA 8.4.2

IBC 407.3

NFPA 8.4.2

NFPA 8.7.1.2

NFPA 8.3.3.2.2, 19.3.7.8

IBC 716.1

NFPA 8.7.1.2

NFPA 8.3.3.2.2, 8.4

NFPA 32.3.3.6

NFPA 8.4.3

1 HOUR

NR

NR

0.5 HOUR

NR

FIRE BARRIER

45 MINNFPA 8.7.1.1

IBC 716.1

NFPA 8.3.3.2.2, 8.7.1.1

IBC 716.1

1 HOUR

1 HR

2 HR

1 HR

2 HR

60 MIN

90 MIN

NFPA 8.2.1.3

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

DAMPERS

TYPE REFERENCE

FIRE

90 MIN

FIRE

90 MIN

FIRE

90 MIN

NFPA 8.3.4.3, 9.2.1

NFPA 8.3.4.3, 9.2.1

N/A

N/A N/A

SMOKE

90 MIN

NFPA 8.5.5.3

VARIES NFPA 8.4.4

VARIES NFPA 8.4.4, 8.4.6.2

VARIES NFPA 8.4.4, 8.4.6.2

NOT ALLOWED

UNLESS SERVING

STAIR ONLY

N/A

NOT ALLOWED N/A

N/A NFPA 8.6.4

VA FORM 08 - 6231

A

B

C

D

A

B

C

D

2 4 5 61

6"

6"

6"

6"

O N

E E

IG

H

T H

I N

C H

O

N E

F O

O T

1/

8"

'-0

O

N E

Q U

A R

T E

R I

N C

H

O N

E F

O O

T

1/ 4"

'-0

T H

R E

E E

IG

H

T H

S

IN

C H

O

N E

F O

O T

(3 /8

1' -0

O

N E

H A

LF

I

N C

H

O N

E F

O O

T

1/ 2"

'-0

T H

R E

E Q

U A

R T

E R

S

IN

C H

O

N E

F O

O T

3/

4"

'-0

O

N E

I N

C H

O

N E

F O

O T

1"

'-0

O N

E A

N D

O N

E H

A

LF

I N

C H

E S

O

N E

F O

O T

1/ 2"

'-0

T H

R E

E

IN

C H

E S

O

N E

F O

O T

3"

'-0

32 4 5 61

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANTS

STRUCTURAL:

ALBERTSON ENGINEERING, INC.

3202 W. MAIN ST., #C

RAPID CITY, SD 57702

605-343-9606

MEP:

WEST PLAINS ENGINEERING, INC.

1750 RAND ROAD

RAPID CITY, SD 57702

605-348-7455

STEPHEN KILBER MIKE SIGMAN (ELEC)

MICHAEL HEINRICH (MECH)

C :\U se rs

\K .K ue pe r\D oc um en ts \2

D om R en ov

B ui ld in g

_k yl ek 9D

U H

U .rv t 6/

2/

:0 1:

P

M

GI100

LIFE SAFETY PLAN - BASEMENT

STONE GROUP ARCHITECTS

600 EAST 7TH ST.

SIOUX FALLS, SD 57103

605-271-1144

TODD STONE

DOM RENOVATION FOR

SEMIPRIVATE ROOMS

HOT SPRINGS, SD

DOUG SPRINKLE

06/03/2025 JM/GB/TM TL/KK

SGA #211921

VA #568A4-21-208

BID DOCUMENTS

3/16" = 1'-0" D5

LIFE SAFETY PLAN - BASEMENT

TRUE

NORTH

PLAN

NORTH

ISSUE # DESCRIPTION DATE

1 BID DOCUMENTS 06/03/2025

KEYNOTES

KEY VALUE KEYNOTE TEXT

8.33A SMOKE GUARD CURTAIN. INSTALL FLUSH WITH CEILING.

14.01 ELEVATOR.

22.03 BI-LEVEL ADA DRINKING FOUNTAIN W/ BOTTLE FILLING STATION. REF PLUMB & SPECS.

D D

W W

DN

DN

DN UP

UP

0.0"

0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

CODE & EGRESS SYMBOL LEGEND

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

DIRECTION OF EGRESS

DIRECTION OF EGRESSPATH OF TRAVEL

START OF PATH TRAVEL DISTANCE (TD)

TD = X'-X"

FEC

FE

EXITEX

CONSTRUCTION LEGEND

AREA NOT IN CONSTRUCTION BOUNDARIES

EXISTING COMPONENTS

NEW COMPONENTS

GENERAL CODE NOTES

H. SMOKE SEALS TO BE INSTALLED AT ALL RATED DOORS.

I. SMOKE SEALS TO BE INSTALLED AT NON RATED SMOKE PARTITION & BARRIER DOORS UON.

A. ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT & THE OWNER BEFORE

PROCEEDING WITH THE WORK.

B. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

C. CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

D. ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

E. DETAILS SHOWN ARE TYPICAL UON. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

F. SEE STRUCTURAL, MECHANICAL, ELECTRICAL, & PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

G. DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR

GRID UON. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UON.

BUILDING & LIFE SAFETY REQUIREMENT LEGEND

DESCRIPTION

WALL

RATING

PARTITION KEY

NFPA 101-2021

IBC 2023

OPENINGS

RATING REFERENCE

FIRE WALL:

BUILDING SEPARATION

90 MINFIRE BARRIER:

OCCUPANCY/AREA SEPARATION

90 MIN

FIRE BARRIER:

HORIZONTAL EXIT & REFUGE AREA

90 MINNFPA 7.1.3.2

NFPA 8.2.1.3

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

NFPA 8.3.3.2.2

2 HOUR

FIRE BARRIER

VERTICAL EXIT PASSAGEWAY

60 MIN

FIRE BARRIER

HORIZONTAL EXIT PASSAGEWAY

NFPA 7.2.6

NFPA 8.6

NFPA 8.3.3.2.2

NFPA 8.3.3.2.2

FIRE BARRIER

VERTICAL EXIT ENCLOSURE/SHAFT

(2 HR = 4 OR MORE STORIES)

(1 HR = LESS THAN 4 STORIES) 60 MIN

90 MINNFPA 8.6

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

90 MIN

1 HR

2 HR

SMOKE PARTITION

(SPRINKLERED)

HAZARDOUS/INCIDENTAL USE

NR

SMOKE BARRIER

SUBDIVIDING SPACES

20 MIN

SMOKE PARTITION

SLEEPING RM SEPARATION REQ

EXIT ACCESS CORRIDOR

(SPRINKLERED) CORRIDOR WALLS

NR

NFPA 8.5

IBC 716.1

NFPA 8.4.2

NFPA 32.3.3.6

NFPA 8.4.2

IBC 407.3

NFPA 8.4.2

NFPA 8.7.1.2

NFPA 8.3.3.2.2, 19.3.7.8

IBC 716.1

NFPA 8.7.1.2

NFPA 8.3.3.2.2, 8.4

NFPA 32.3.3.6

NFPA 8.4.3

1 HOUR

NR

NR

0.5 HOUR

NR

FIRE BARRIER

45 MINNFPA 8.7.1.1

IBC 716.1

NFPA 8.3.3.2.2, 8.7.1.1

IBC 716.1

1 HOUR

1 HR

2 HR

1 HR

2 HR

60 MIN

90 MIN

NFPA 8.2.1.3

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

DAMPERS

TYPE REFERENCE

FIRE

90 MIN

FIRE

90 MIN

FIRE

90 MIN

NFPA 8.3.4.3, 9.2.1

NFPA 8.3.4.3, 9.2.1

N/A

N/A N/A

SMOKE

90 MIN

NFPA 8.5.5.3

VARIES NFPA 8.4.4

VARIES NFPA 8.4.4, 8.4.6.2

VARIES NFPA 8.4.4, 8.4.6.2

NOT ALLOWED

UNLESS SERVING

STAIR ONLY

N/A

NOT ALLOWED N/A

N/A NFPA 8.6.4

160 SF

LOUNGE

213 SF

BEDROOM

TWO-BED

219 SF

BEDROOM

TWO-BED

215 SF

BEDROOM

TWO-BED

218 SF

BEDROOM

TWO-BED

222 SF

BEDROOM

TWO-BED

206 SF

BARIATRIC

BEDROOM

TWO-BED

124 SF

BEDROOM

ONE-BED

86 SF

116A

TOILET

82 SF

115A

TOILET42 SF

SOILED

UTILITY

1017 SF

FIRST

FLOOR

CORRIDOR

74 SF

114A

TOILET

74 SF

113A

TOILET

81 SF

112A

TOILET

102 SF

111A

BARIATRIC

TOILET

31 SF

HAC

43 SF

TOILET

70 SF

110A

TOILET

112 SF

LAUNDRY

100 SF

ELEVATOR

38 SF

105A

LINEN

87 SF

TR

17 SF

ELEC

226 SF

MULTIPURPOSE

KITCHENETTE

35 SF

STORAGE

28 SF

STORAGE

LENGTH OF TRAVEL: 82'-8"

LENGTH OF TRAVEL: 50'-1"

5.2"

44.0"

7.2"

34.0"

3 3 3 3

4.4"

40.0"

EX

EX

FEC

15 20

1 1

EX

5.8"

34.0"

EX

EX

5.2"

44.0"

75'-0"

75'-0"

FEC

TWO-STORY EXIT ENLCLOSURE IS

OPEN TO BASEMENT WITHIN AN

EXISTING BUILDING. COMPLIANT

WITH NFPA 101 PER 7.2.2.5.1.3

100A

STORAGE

107A

COMPUTER

6.6"

54.0"

STAIRWELL

21.9"

38.0"

73 37

14.01

8.33A 8.33C

22.03

G A

T E

3/16" = 1'-0" D5

LIFE SAFETY PLAN - FIRST FLOOR

VA FORM 08 - 6231

A

B

C

D

A

B

C

D

2 4 5 61

6"

6"

6"

6"

O N

E E

IG

H

T H

I N

C H

O

N E

F O

O T

1/

8"

'-0

O

N E

Q U

A R

T E

R I

N C

H

O N

E F

O O

T

1/ 4"

'-0

T H

R E

E E

IG

H

T H

S

IN

C H

O

N E

F O

O T

(3 /8

1' -0

O

N E

H A

LF

I

N C

H

O N

E F

O O

T

1/ 2"

'-0

T H

R E

E Q

U A

R T

E R

S

IN

C H

O

N E

F O

O T

3/

4"

'-0

O

N E

I N

C H

O

N E

F O

O T

1"

'-0

O N

E A

N D

O N

E H

A

LF

I N

C H

E S

O

N E

F O

O T

1/ 2"

'-0

T H

R E

E

IN

C H

E S

O

N E

F O

O T

3"

'-0

32 4 5 61

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANTS

STRUCTURAL:

ALBERTSON ENGINEERING, INC.

3202 W. MAIN ST., #C

RAPID CITY, SD 57702

605-343-9606

MEP:

WEST PLAINS ENGINEERING, INC.

1750 RAND ROAD

RAPID CITY, SD 57702

605-348-7455

STEPHEN KILBER MIKE SIGMAN (ELEC)

MICHAEL HEINRICH (MECH)

C :\U se rs

\K .K ue pe r\D oc um en ts \2

D om R en ov

B ui ld in g

_k yl ek 9D

U H

U .rv t 6/

2/

:0 1:

P

M

GI101

LIFE SAFETY PLAN - 1ST FLOOR

STONE GROUP ARCHITECTS

600 EAST 7TH ST.

SIOUX FALLS, SD 57103

605-271-1144

TODD STONE

DOM RENOVATION FOR

SEMIPRIVATE ROOMS

HOT SPRINGS, SD

DOUG SPRINKLE

06/03/2025 JM/GB/TM TL/KK

SGA #211921

VA #568A4-21-208

BID DOCUMENTS

TRUE

NORTH

PLAN

NORTH

ISSUE # DESCRIPTION DATE

1 BID DOCUMENTS 06/03/2025

KEYNOTES

KEY VALUE KEYNOTE TEXT

8.33A SMOKE GUARD CURTAIN. INSTALL FLUSH WITH CEILING.

8.33C EXPOSED SMOKE GUARD CURTAIN.

W W

D D

DN

DN

DN

0.0"

0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

CODE & EGRESS SYMBOL LEGEND

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

DIRECTION OF EGRESS

DIRECTION OF EGRESSPATH OF TRAVEL

START OF PATH TRAVEL DISTANCE (TD)

TD = X'-X"

FEC

FE

EXITEX

CONSTRUCTION LEGEND

AREA NOT IN CONSTRUCTION BOUNDARIES

EXISTING COMPONENTS

NEW COMPONENTS

GENERAL CODE NOTES

H. SMOKE SEALS TO BE INSTALLED AT ALL RATED DOORS.

I. SMOKE SEALS TO BE INSTALLED AT NON RATED SMOKE PARTITION & BARRIER DOORS UON.

A. ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT & THE OWNER BEFORE

PROCEEDING WITH THE WORK.

B. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

C. CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

D. ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

E. DETAILS SHOWN ARE TYPICAL UON. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

F. SEE STRUCTURAL, MECHANICAL, ELECTRICAL, & PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

G. DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR

GRID UON. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UON.

BUILDING & LIFE SAFETY REQUIREMENT LEGEND

DESCRIPTION

WALL

RATING

PARTITION KEY

NFPA 101-2021

IBC 2023

OPENINGS

RATING REFERENCE

FIRE WALL:

BUILDING SEPARATION

90 MINFIRE BARRIER:

OCCUPANCY/AREA SEPARATION

90 MIN

FIRE BARRIER:

HORIZONTAL EXIT & REFUGE AREA

90 MINNFPA 7.1.3.2

NFPA 8.2.1.3

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

NFPA 8.3.3.2.2

2 HOUR

FIRE BARRIER

VERTICAL EXIT PASSAGEWAY

60 MIN

FIRE BARRIER

HORIZONTAL EXIT PASSAGEWAY

NFPA 7.2.6

NFPA 8.6

NFPA 8.3.3.2.2

NFPA 8.3.3.2.2

FIRE BARRIER

VERTICAL EXIT ENCLOSURE/SHAFT

(2 HR = 4 OR MORE STORIES)

(1 HR = LESS THAN 4 STORIES) 60 MIN

90 MINNFPA 8.6

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

90 MIN

1 HR

2 HR

SMOKE PARTITION

(SPRINKLERED)

HAZARDOUS/INCIDENTAL USE

NR

SMOKE BARRIER

SUBDIVIDING SPACES

20 MIN

SMOKE PARTITION

SLEEPING RM SEPARATION REQ

EXIT ACCESS CORRIDOR

(SPRINKLERED) CORRIDOR WALLS

NR

NFPA 8.5

IBC 716.1

NFPA 8.4.2

NFPA 32.3.3.6

NFPA 8.4.2

IBC 407.3

NFPA 8.4.2

NFPA 8.7.1.2

NFPA 8.3.3.2.2, 19.3.7.8

IBC 716.1

NFPA 8.7.1.2

NFPA 8.3.3.2.2, 8.4

NFPA 32.3.3.6

NFPA 8.4.3

1 HOUR

NR

NR

0.5 HOUR

NR

FIRE BARRIER

45 MINNFPA 8.7.1.1

IBC 716.1

NFPA 8.3.3.2.2, 8.7.1.1

IBC 716.1

1 HOUR

1 HR

2 HR

1 HR

2 HR

60 MIN

90 MIN

NFPA 8.2.1.3

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

DAMPERS

TYPE REFERENCE

FIRE

90 MIN

FIRE

90 MIN

FIRE

90 MIN

NFPA 8.3.4.3, 9.2.1

NFPA 8.3.4.3, 9.2.1

N/A

N/A N/A

SMOKE

90 MIN

NFPA 8.5.5.3

VARIES NFPA 8.4.4

VARIES NFPA 8.4.4, 8.4.6.2

VARIES NFPA 8.4.4, 8.4.6.2

NOT ALLOWED

UNLESS SERVING

STAIR ONLY

N/A

NOT ALLOWED N/A

N/A NFPA 8.6.4

160 SF

LOUNGE

213 SF

BEDROOM

TWO-BED

219 SF

BEDROOM

TWO-BED

215 SF

BEDROOM

TWO-BED

218 SF

BEDROOM

TWO-BED

222 SF

BEDROOM

TWO-BED

86 SF

216A

TOILET

82 SF

215A

TOILET

74 SF

214A

TOILET

74 SF

213A

TOILET

81 SF

212A

TOILET

102 SF

211A

BARIATRIC

TOILET

124 SF

BEDROOM

ONE-BED

206 SF

BARIATRIC

BEDROOM

TWO-BED

43 SF

TOILET

70 SF

210A

TOILET

112 SF

LAUNDRY

100 SF

ELEVATOR

38 SF

205A

LINEN

101 SF

TR17 SF

ELEC

1024 SF

SECOND

FLOOR

CORRIDOR

42 SF

SOILED

UTILITY

28 SF

STORAGE

37 SF

STORAGE

LENGTH OF TRAVEL: 81'-7"

LENGTH OF TRAVEL: 48'-8"

35 SF

ATTIC

ACCESS

3 3 3 3

15 21

1 1

2.4"

44.0"

7.4"

34.0"

4.6"

40.0"

EX

EX

EX

EX

2.4"

44.0"

FEC

FEC

75'-0"

75'-0"

200A

STORAGE

207A

COMPUTER

FSA

STATION

11.1"

38.0"

'-4

6.9"

54.0"

3' -6

5' -0

/2

1024 SF

SECOND

FLOOR

CORRIDOR

MULTIPURPOSE

KITCHENETTE

8.33C8.33A

14.01

5.42E

22.03

3/16" = 1'-0" D5

LIFE SAFETY PLAN - SECOND FLOOR

VA FORM 08 - 6231

A

B

C

D

A

B

C

D

2 4 5 61

6"

6"

6"

6"

O N

E E

IG

H

T H

I N

C H

O

N E

F O

O T

1/

8"

'-0

O

N E

Q U

A R

T E

R I

N C

H

O N

E F

O O

T

1/ 4"

'-0

T H

R E

E E

IG

H

T H

S

IN

C H

O

N E

F O

O T

(3 /8

1' -0

O

N E

H A

LF

I

N C

H

O N

E F

O O

T

1/ 2"

'-0

T H

R E

E Q

U A

R T

E R

S

IN

C H

O

N E

F O

O T

3/

4"

'-0

O

N E

I N

C H

O

N E

F O

O T

1"

'-0

O N

E A

N D

O N

E H

A

LF

I N

C H

E S

O

N E

F O

O T

1/ 2"

'-0

T H

R E

E

IN

C H

E S

O

N E

F O

O T

3"

'-0

32 4 5 61

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANTS

STRUCTURAL:

ALBERTSON ENGINEERING, INC.

3202 W. MAIN ST., #C

RAPID CITY, SD 57702

605-343-9606

MEP:

WEST PLAINS ENGINEERING, INC.

1750 RAND ROAD

RAPID CITY, SD 57702

605-348-7455

STEPHEN KILBER MIKE SIGMAN (ELEC)

MICHAEL HEINRICH (MECH)

C :\U se rs

\K .K ue pe r\D oc um en ts \2

D om R en ov

B ui ld in g

_k yl ek 9D

U H

U .rv t 6/

2/

:0 1:

P

M

GI102

LIFE SAFETY PLAN - 2ND FLOOR

STONE GROUP ARCHITECTS

600 EAST 7TH ST.

SIOUX FALLS, SD 57103

605-271-1144

TODD STONE

DOM RENOVATION FOR

SEMIPRIVATE ROOMS

HOT SPRINGS, SD

DOUG SPRINKLE

06/03/2025 JM/GB/TM TL/KK

SGA #211921

VA #568A4-21-208

BID DOCUMENTS

TRUE

NORTH

PLAN

NORTH

ISSUE # DESCRIPTION DATE

1 BID DOCUMENTS 06/03/2025

KEYNOTES

KEY VALUE KEYNOTE TEXT

5.42E PAINTED STEEL STAIR W/ ALTERNATING TREADS.

8.33A SMOKE GUARD CURTAIN. INSTALL FLUSH WITH CEILING.

8.33C EXPOSED SMOKE GUARD CURTAIN.

GENERAL SITE NOTES

H. SEE MECHANICAL & ELECTRICAL PLANS FOR LOCATIONS OF HOSE BIBS & EXTERIOR OUTLETS.

I. PROTECT ALL EXISTING UTILITIES UON.

A. ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT & THE OWNER BEFORE

PROCEEDING WITH THE WORK.

B. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

C. CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

D. ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

E. DETAILS SHOWN ARE TYPICAL UON. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

F. SEE STRUCTURAL, MECHANICAL, ELECTRICAL, & PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

G. DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR

GRID UON. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UON.

32.01

32.02

32.02

23.02

23.03

4' -0

4'-6"

32.03

32.03

32.03

32.05

32.05

32.03

32.05

32.03

SEE BASEMENT FLOOR PLAN FOR SIDEWALK CONTINUATION

V E

R

IF

Y W

/ C O

R

'-0

8'

-0

1.02

1.02

1.01

1.04

2.26

2.25

4'-0"

4'-6"

32.04

2.02

2.02A

2.02A

2.02A

SEE BASEMENT FLOOR PLAN FOR SIDEWALK CONTINUATION

GENERAL DEMOLITION NOTES

H. PROTECT ALL EXISTING UTILITIES UON.

I. WHERE APPLICABLE, ROOF PROTECTION IS TO BE PROVIDED FOR EXISTING ROOFS DURING ALL

PHASES OF CONSTRUCTION.

J. PATCH REMAINING EXISTING CONSTRUCTION AFFECTED BY DEMOLITION AS NEEDED.

K. PATCHING AND/OR INFILL TO MATCH EXISTING CONSTRUCTION & FINISHES UON.

L. EXISTING ITEMS TO REMAIN ARE SHOWN IN GRAY.

M. EXISTING ITEMS TO BE DEMOED ARE SHOWN WHITE WITH DASHED LINES.

N. INFILL OF FIRE PARTITION PENETRATIONS/OPENINGS SHALL MAINTAIN THE INTEGRITY OF THE

RATING.

O. CONTRACTOR TO COORDINATE RELOCATION AND/OR STORAGE OF SALVAGED ITEMS WITH THE

OWNER UON.

P. REFERENCE HAZARDOUS MATERIALS, MECHANICAL DEMOLITION, AND/OR PLUMBING DEMOLITION

SHEETS FOR INFORMATION REGARDING DEMOLITION OF HAZARDOUS MATERIALS.

Q. SEE STRUCTURAL DETAILS FOR INFORMATION REGARDING INFILL OF EXISTING STRUCTURAL FLOOR &

ROOF PENETRATIONS.

R. ALL CONSTRUCTION WASTE PRODUCED BY DEMOLITION TO BE PROPERTY OF CONTRACTOR UON.

S. PLUMBING ON BASEMENT LEVEL TO BE REMOVED TO BELOW THE FLOOR AND CAPPED. SEE

STRUCTURAL FOR CONCRETE PATCH DETAILS.

T. EXISTING INTERIOR PAINTED WOOD SURFACES TO BE STRIPPED TO BARE WOOD AND PREPPED FOR

NEW STAIN FINISH. EXISTING EXTERIOR PAINTED WOOD SURFACES TO BE STRIPPED TO BARE WOOD

AND PREPPED FOR NEW PAINT.

U. STRIP EXISTING STAINED WOOD WINDOWS, TRIM, AND SILLS. PREPARE FOR NEW STAIN FINISH.

EXISTING WOOD TRIM AND SILLS TO BE REMOVED AND SALVAGED AS NECESSARY FOR

REINSTALLATION

A. ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT & THE OWNER BEFORE

PROCEEDING WITH THE WORK.

B. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

C. CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

D. ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

E. DETAILS SHOWN ARE TYPICAL UON. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

F. SEE STRUCTURAL, MECHANICAL, ELECTRICAL, & PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

G. DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR

GRID UON. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UON.

1" = 10'-0" D5

SITE PLAN

1" = 10'-0" B5

SITE PLAN - DEMOLITION

VA FORM 08 - 6231

A

B

C

D

A

B

C

D

2 4 5 61

6"

6"

6"

6"

O N

E E

IG

H

T H

I N

C H

O

N E

F O

O T

1/

8"

'-0

O

N E

Q U

A R

T E

R I

N C

H

O N

E F

O O

T

1/ 4"

'-0

T H

R E

E E

IG

H

T H

S

IN

C H

O

N E

F O

O T

(3 /8

1' -0

O

N E

H A

LF

I

N C

H

O N

E F

O O

T

1/ 2"

'-0

T H

R E

E Q

U A

R T

E R

S

IN

C H

O

N E

F O

O T

3/

4"

'-0

O

N E

I N

C H

O

N E

F O

O T

1"

'-0

O N

E A

N D

O N

E H

A

LF

I N

C H

E S

O

N E

F O

O T

1/ 2"

'-0

T H

R E

E

IN

C H

E S

O

N E

F O

O T

3"

'-0

32 4 5 61

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANTS

STRUCTURAL:

ALBERTSON ENGINEERING, INC.

3202 W. MAIN ST., #C

RAPID CITY, SD 57702

605-343-9606

MEP:

WEST PLAINS ENGINEERING, INC.

1750 RAND ROAD

RAPID CITY, SD 57702

605-348-7455

STEPHEN KILBER MIKE SIGMAN (ELEC)

MICHAEL HEINRICH (MECH)

C :\U se rs

\K .K ue pe r\D oc um en ts \2

D om R en ov

B ui ld in g

_k yl ek 9D

U H

U .rv t 6/

2/

:0 1:

P

M

GI121

ARCHITECTURAL SITE PLANS

STONE GROUP ARCHITECTS

600 EAST 7TH ST.

SIOUX FALLS, SD 57103

605-271-1144

TODD STONE

DOM RENOVATION FOR

SEMIPRIVATE ROOMS

HOT SPRINGS, SD

DOUG SPRINKLE

06/03/2025 JM/GB/TM TL/KK

SGA #211921

VA #568A4-21-208

BID DOCUMENTS

TRUE

NORTH

PLAN

NORTH

TRUE

NORTH

PLAN

NORTH

KEYNOTES

KEY VALUE KEYNOTE TEXT

1.01 CONTRACTOR'S ENTRANCE.

1.02 7'-0" CONSTRUCTION FENCE.

1.04 STAIR TO BE REMOVED. MAY RETAIN AS NECESSARY FOR USE DURING

DEMOLITION/CONSTRUCTION. CONFIRM W/ COR.

2.02 REMOVE LANDSCAPE ROCK FOR NEW SIDEWALK.

2.02A EXISTING LANDSCAPE ROCK TO REMAIN.

2.25 REMOVE MECH ELEMENT. CONCRETE SLAB TO REMAIN. SEE MECHANICAL.

2.26 REMOVE MECH ELEMENT, CONCRETE SLAB, CANOPY. SEE MECHANICAL.

23.02 MECH ELEMENT ON NEW CONCRETE PAD. SEE MECHANICAL.

23.03 MECH ELEMENT ON EXISTING CONCRETE PAD. SEE MECHANICAL.

32.01 NEW 4" CONCRETE SIDEWALK OVER GRANULAR SUB-BASE.

32.02 REPAIR/REPLACE LAWN WHERE DISTURBED BY CONSTRUCTION ACTIVITIES.CONFIRM FINAL

GRADING IS AWAY FROM BUILDING.

32.03 REPAIR/REPLACE DAMAGED CONCRETE WALK AND OR PARKING FROM CONSTRUCTION

ACTIVITIES.

32.04 REMOVE DUMPSTER.

32.05 REPAIR LANDSCAPE ROCK DISRUPTED BY CONSTRUCTION.

ISSUE # DESCRIPTION DATE

1 BID DOCUMENTS 06/03/2025

Sheets
GI014 - CODE REVIEW, PCRA, ICRA, ISLM, GEN NOTES
GI100 - LIFE SAFETY PLAN - BASEMENT
GI101 - LIFE SAFETY PLAN - 1ST FLOOR
GI102 - LIFE SAFETY PLAN - 2ND FLOOR
GI121 - ARCHITECTURAL SITE PLANS
HA100 - HAZARDOUS ABATEMENT PLAN - BASEMENT
HA101 - HAZARDOUS ABATEMENT PLAN - 1ST FLOOR
HA102 - HAZARDOUS ABATEMENT PLAN - 2ND FLOOR

File details come from the government source that posted it. Updated .