542-25-105 Additional Specs.pdf
PDF 1 MB Posted
- Attached to
- Z2DA--542-25-105 | Replace Pitched Roof Building 1 | NCO 4 Construction East (VA-25-00008811)
- Solicitation number
- 36C24425B0003
About this file
This is a technical specification section (07 56 00) for fluid-applied roofing to be used on Building 1 at the Coatesville VA Medical Center. The specification details requirements for a fluid-applied roofing system consisting of multiple layers of neoprene and chlorosulfonated polyethylene (CSPE) to be used specifically for repairing and relining the existing integral gutter system on all roofs of the buildings in this project.
The basis of design is the Sika Corporation Sikalastic-641 Lo-VOC Roofing System, which requires a 4-layer application including primer coat, base coat, reinforcement layer, and top coat. Key requirements include: installer must have 3 years experience and manufacturer approval; all products must be from a single manufacturer; samples and certifications must be submitted; weather conditions must be suitable with surfaces dry and temperature above 40°F; and manufacturer must provide a minimum 10-year warranty. The specification includes detailed requirements for surface preparation, application methods, joint treatments, and protection/clean-up procedures. The system uses Sika Reemat or Sika Fleece reinforcement materials and requires specific mil thicknesses for each coat depending on the warranty term selected (10, 15, 20 or 25 years).
View the file
Other files
| File | Type | Posted |
|---|---|---|
| INSTRUCTIONS to bidders.docx | DOCX document | |
| 36C24425B0003 0004.docx | DOCX document | |
| Sign in sheet Replace roof building 1 4 March 2025.pdf | ||
| 542-25-105 - Contractor Questions and Answers Site Visit No. 2 10 April 2025.docx | DOCX document | |
| 36C24425B0003 0003.docx | DOCX document | |
| Sign in sheet Replace roof building 1 10 April 2025.pdf | ||
| PA VA DORMER DRAWINGS.pdf | ||
| Building 1 Roof - 2.pdf | ||
| Building 1 Roof - 1.pdf | ||
| 089000 - Louvers and Vents - Edited.pdf | ||
| 542-25-105 - Contractor Questions and Answers updated.docx | DOCX document | |
| 099100 - Painting - Edited.pdf | ||
| 36C24425B0003 0002.docx | DOCX document | |
| Sign in sheet for Replace Roof building 1 2.pdf | ||
| 36C24425B0003 0001.docx | DOCX document | |
| Attachment 5 - GEMS Contractor training.doc | DOC document | |
| Attachment 6 - Bldg 1 Roof - Construction Safety Standards.pdf | ||
| 542-25-105 Specifications.pdf | ||
| 542-25-105 Replace Pitched Roof Building 1 - Drawings - Updated.pdf | ||
| 36C24425B0003_1.docx | DOCX document |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Coatesville VAMC Replace Pitched Roof Building 1 Coatesville, PA
January 7, 2025
VA #542-25-105
07 56 00 - 1
SECTION 07 56 00
FLUID-APPLIED ROOFING
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies a fluid applied roofing system consisting of a fluid application of multiple layers of neoprene and chlorosulfonated polyethylene (CSPE).
B. The Fluid Applied Roofing system is specified for the repair and relining of the existing integral gutter system installed on all roofs of all buildings in this project.
C. The BASIS OF DESIGN for this fluid applied roof system is the Sika
Corporation system Sikalastic – 641 Lo-VOC Roofing System. The system shall employ 4 layers – Primer Coat, Base Coat, Reinforcement layer, and top coat.
1.2 QUALITY ASSURANCE
A. Manufacturer’s Qualifications: Obtain products from single manufacturer or from sources recommended by manufacturer for use with fluid applied roofing and incorporated in manufacturer’s warranty.
B. Installers Qualifications: Work is to be performed by installer having three (3) years’ experience for work relating to this section and approved in writing by fluid applied roofing manufacturer.
C. The Contractor shall use one manufacturer for all products for the gutter repair including sealant and membrane. Entire system shall be covered under one warranty.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Samples:
1. 150 mm (6 inch) square cured sheet of roofing system without backing, showing color, and texture.
2. System proposed for flashing and reinforcing.
C. Manufacturer's Certificates:
1. Installer approval.
2. Certificate stating that material utilized on the job will be of the same formulation as materials covered by the test report.
Coatesville, PA
January 7, 2025
VA #542-25-105
07 56 00 - 2
D. Manufacturer's Literature and Data:
1. Roofing system materials giving physical properties, wet mil thickness in relation to dry mil thickness, and other related information.
2. Manufacturer's printed instructions for application of roofing materials to be installed.
E. Test Reports: Test report from an independent commercial testing laboratory showing that neoprene and CSPE materials meet specified requirements.
F. Manufacturer warranty.
1.4 PRODUCT DELIVERY, STORAGE AND HANDLING
A. Deliver materials to job site in manufacturer's original factory sealed containers labeled to identify product, manufacturer and point of manufacture.
B. Observe precautions appropriate to flammable materials and "safety notes" included in roofing material manufacturer's printed instructions to installer before, during, and immediately following application of these materials.
1.5 JOB CONDITIONS
A. Install fluid applied roofing only on dry surfaces free of water, surface condensation, rain, snow, ice, frost, dirt and debris.
B. Exposed gutter surfaces shall be lightly sanded to remove any patina that has built up on the copper surface. 60-80 grit sandpaper with a sanding block or orbital sander should be used.
C. Do not proceed when temperature of surfaces to receive roofing and flashing, is lower than 5 degrees C (40 degrees F).
D. Complete work on roof deck and install penetrations and projections through roof deck before roofing and flashing work is applied.
1.6 WARRANTY
A. Construction Warranty: Comply with FAR clause 52.246-21 “Warranty of
Construction”.
B. Manufacturer Warranty: Manufacturer shall warranty their fluid applied roofing for a minimum of ten (10) years from date of installation and final acceptance by the Government. Submit manufacturer warranty.
January 7, 2025
VA #542-25-105
07 56 00 - 3
Coatesville VAMC Replace Pitched Roof Building 1 Coatesville, PA
1.7 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. ASTM International (ASTM):
D3468/D3468M-99(2020)...Liquid-Applied Neoprene and Chlorosulfonated
Polyethylene Used In Roofing and Waterproofing
D412-16.................Vulcanized Rubber and Thermoplastic Elastomers-
Tension
D750-12(2017)...........Rubber Deterioration in Carbon-Arc Weathering
Apparatus
D1149-07(2012)..........Rubber Deterioration-Surface Ozone Cracking in a Chamber
E96/E96M-16.............Water Vapor Transmission of Materials
PART 2 - PRODUCTS
2.1 FLUID APPLIED MEMBRANE WATERPROOFING SYSTEM FOR INTREGAL GUTTERS
A. Fluid applied system consisting of primer coat, base coat, mesh reinforcing, and a continuous finish(top) coat is to be installed in all existing integral gutter installed on the roofs as indicated in the
Contract Documents.
B. Contractor shall use one manufacturer’s complete system for all integral gutter on all buildings in this project scope.
C. Basis of design Sika Corporation – Sikalastic 641 Lo-VOC Roofing
System.
D. GC to perform an on-site test application in a 5’-0” length of gutter to confirm final color. (GC to confirm with VA COR before ordering product)
2.2 CAULKING COMPOUND
A. A non-staining, cold setting, flexible sealant having a polychloroprene or chlorosulfonated polyethylene base with added plasticizers, curing agents, pigments and which contains no volatile oils or other ingredients that will stain applied CSPE roofing.
2.3 REINFORCING TAPE
A. Unwoven glass mat with nominal 0.46 mm (18 mils) film bonded with neoprene; or a 0.38 mm (15 mils) neoprene impregnated inorganic felt;
Coatesville, PA
January 7, 2025
VA #542-25-105
07 56 00 - 4 or an untreated woven glass fiber tape, plain weave, weight 200 grams per square meter (6 ounces per square yard), thread count 42 by 32.
B. In lieu of reinforcing tape, loose glass fibers embedded in liquid neoprene are as the reinforcing medium.
2.4 SOLVENT
A. For use in job site preparation of neoprene primer, for cleanup and other related work, furnish a commercial grade xylene (xylol) or commercial grade toluene (toluol).
2.5 UNDERLAYMENT
A. Provide level coat and underlayment materials compatible with and as recommended by manufacturer of roofing materials.
B. Provide level coat and underlayment materials when necessary to provide a suitable base for application of the roofing materials.
PART 3 - EXECUTION
3.1 PREPARATION OF SURFACE
A. Verify that surfaces to receive roofing and flashing are in sound condition and free of projections, depressions, grease, oil, asphalt, tar, paint, wax, dust, or other debris that may prevent proper application of roofing.
B. Allow concrete surfaces to cure a minimum of 28 days and clean free of waterproofing agents, form release agents, and curing agents that might act as bond breakers. Proceed only when maximum moisture content of the substrate as measured with a moisture meter is 16 percent.
C. Report adverse roof deck conditions of any type in writing to
Contracting Officer Representative (COR)before material is applied.
Commencement of work constitutes acceptance of roof surfaces by installer as satisfactory for application of roofing and flashing.
3.2 CLEANING
A. Broom-clean surfaces to remove all dust, dirt, loose aggregate, and other foreign particles. Remove excessive alkaline efflorescence on concrete by flushing with 10 percent muriatic acid solution, then rinsing, and allowing to dry.
3.3 APPLICATION
A. Install roofing with tools and equipment approved by roofing material manufacturer. Wet film thickness of roofing materials to be as recommended by roofing material manufacturer to obtain the specified
Coatesville, PA
January 7, 2025
VA #542-25-105
07 56 00 - 5 dry film thickness. Check wet film thickness frequently by use of a wet mil thickness gauge. Control application of fluid-applied material by maintaining careful balance at all times between material consumption and area covered. Apply quantity of coats to achieve minimum dry film thickness of neoprene and CSPE materials.
B. Joint Treatment:
1. Treat hairline cracks or other openings up to 2 mm (1/16 inch) in width with a brush coat of neoprene base fibered sealer.
2. Openings larger than 2 mm (1/16 inch) but less than 6 mm (1/4 inch) fill and treat with a reinforcing tape as specified.
3. Cracks 6 mm (1/4 inch) and over treat as specified for expansion joints.
C. Drains: Cut elastic base sheet to fit around drains/downspouts and extend the same sheet horizontally in gutter a minimum the manufacturers installation instructions from edge of all drains. Do not clamp rings or strainers until 48 hours after entire roofing application is complete.
D. Priming: Immediately after substrate has been thoroughly cleaned and ready for application of the roof, prime concrete surfaces to receive roofing and flashing with neoprene or chlorinated rubber based primer.
E. Finish coat per manufacturers installation instructions; Basis of design Sika Corporation – Sikalastic 641 Lo-VOC-Roofing System.
3.4 PROTECTION AND CLEAN UP
A. Keep completed roofing system free of non-essential traffic and unrelated work until at least 48 hours after completion of roofing application.
B. Provide temporary support, such as insulation board, for materials and equipment stored on roof during application.
C. Protect adjacent construction from disfiguration by run, spillage or overspray, and repair work defaced in this manner.
D. Remove tools, equipment and surplus materials and clear roof area of debris on completion of work.
3.5 REPAIRS
A. Repair damage to roofing and flashing before work is complete. Patch breaks in surface with neoprene-based base course and CSPE-base weather course application to insure a continuous waterproof membrane complying with these specifications.
- - - E N D - -
Coatesville, PA
January 7, 2025
VA #542-25-105
07 56 00 - 6
---INTENTIONALLY BLANK---
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12 020915909000000012
SYSTEM DATA SHEET
Sikalastic®-641 Lo-VOC Roofing System Liquid applied single component fully reinforced Lo-VOC, low-odor roofing system with fiberglass or polyester reinforcement
PRODUCT DESCRIPTION
Sikalastic®-641 Lo-VOC Roofing System combines cold applied, aliphatic, single component, moisture-triggered polyurethane resin with fiberglass mat or polyester fleece reinforcement to create a seamless membrane and flashing system.
System components are:
Sika® or Sikalastic® Primer: Select primer per substrate material in accordance with Priming Guide Sikalastic®-641 Lo-VOC: Resin used for all systems with Sika Reemat or Sika Fleece reinforcements Sika® Reemat: Chopped strand fiberglass mat Sika® Fleece 120, 140, 170: Non-woven, needle-punched polyester fleece in various weights
USES
Sikalastic®-641 Lo-VOC roofing/waterproofing systems may only be used by experience professionals.
Sikalastic® RoofPro 10, 15, 20 and 25 year systems, including Sikalastic® RoofPro Built Up, Direct, Plaza Deck/PMA, and Vegetated systems for both new construction and refurbishment
Ideal for roofs displaying complex details and geometry or when accessibility is limited
Effective and cost efficient life cycle extension of existing roofs
Highly reflective Sikalastic®-641 Lo-VOC in White suitable for cool roofs and solar roof assemblies
Suitable for use for applications such as balconies, terraces, walkways, plazas, and similar applications exposed to foot traffic when provided with a supplemental aggregated surfacing
CHARACTERISTICS / ADVANTAGES
Proven technology with over 30 year track record▪ Single component - no mixing and ready to use▪ Fully reinforced with highly conformable Sika Reemat or Sika Fleece
Moisture triggered chemistry that is rapidly weatherproof after application
Resistant to ponding water▪ Low VOC formula - low Odor▪ Highly elastic and crack bridging▪ Seamless and fully adhered▪ Vapor permeable▪ UV resistant and non-yellowing▪ Abrasion and chemical resistant▪ Adheres to most common construction materials when suitable primer is used
ENVIRONMENTAL INFORMATION
Environmental Product Declaration (EPD) - Cradle-to- Grave
APPROVALS / STANDARDS
FM Approval Standard 4470 for Class 1 Roof Covers▪ UL 790 Class A▪ Miami-Dade▪
ASTM D 6083▪
ASTM E 108▪
Florida Building Code▪
1 / 10 jbrooks Text Box FOR REFERENCE ONLY - GC TO SUBMIT FINAL FLUID APPLIED ROOFING SUBMITTAL PER SECTION 01 00 00.
jbrooks Cloud
Steel Gray
Pearl Gray (Made to Order)
Mushroom Copper Green
Sikalastic®-644 Lo-VOC a selection of 3 standard colors are available with no minimum order quantity
Sikalastic®-641 Lo-VOC a selection of 6 standard colors are available with no minimum order quantity
**Custom Colors
• Available as Made to Order
• 5-gal pails only
• 120 pail minimum order
Sikalastic® -621 TC a selection of 3 standard colors are available with no minimum order quantity (can recieve textured and decorative finishes)
Sikalastic® -624 WP a selection of 2 standard colors are available with no minimum order quantity (can recieve textured and decorative finishes)
**Custom Colors
• Available as Made to Order
• 5-gal pails only
• 120 pail minimum order
NOTE:
Colors show approximate tone without any texture. Color of actual product may vary slightly. Gloss level will vary depending on product used. Custom colors available with adequate lead time and minimum batch quantities.
Please consult your Sika® representative for further information and pricing.
*50 Gallon Drums Available
• White
• Standard Gray
**Custom Colors
**Custom Colors
SIKA CORPORATION • ROOFING
East Tel: 888-552-9769 West Tel: 888-509-3350 usa.sika.com
ALL COLORS ARE AVAILABLE IN 5-GAL PAILS UNLESS OTHERWISE NOTED
SIKALASTIC® ROOFPRO COLOR CHART
Steel GrayWhite Pearl Gray
White Pearl Gray
*Standard Gray*White Pearl Gray
*Standard Gray*White
*50 Gallon Drums Available
• White
• Standard Gray
© Sika Corporation /06.3001.5 / 08/2023 bwagner Rectangle
SYSTEM INFORMATION
Sikalastic® RoofPro-641 Lo-VOC System Guide with Sika® RoofPro Metal
RoofPro Metal*
1. Primer See Priming Guide
2. Base Layer: Sikalastic®-641 Lo-VOC 20 mils wet–80 sf/gal.
3. Top Layer: Sikalastic®-641 Lo-VOC 20 mils wet–80 sf/gal.
* Detailing: Sika® Flexitape Heavy or Sika® Joint Tape SA centered over seams, transitions and properly treated cracks and joints.
Sikalastic® RoofPro-641 Lo-VOC System Guide with Sika® Reemat
RoofPro 10** RoofPro 15** RoofPro 20** RoofPro 25**
1. Primer See Priming
Guide See Priming Guide
See Priming Guide
See Priming Guide
2. Base Layer:
Sikalastic®-641 Lo-VOC
30 mils wet 53 sf/gal.
50 mils wet 32 sf/gal.
50 mils wet 32 sf/gal.
50 mils wet 32 sf/gal.
3.
Reinforcement:
Sika® Reemat Standard
Sika® Reemat Premium
Sika® Reemat Premium
Sika® Reemat Premium
4. Top Layer:
Sikalastic®-641 Lo-VOC
30 mils wet 53 sf/gal.
20 mils wet 80 sf/gal.
30 mils wet 53 sf/gal.
23 mils wet 69 sf/gal.
5. Top Layer:
Sikalastic®-641 Lo-VOC
23 mils wet 69 sf/gal.
System Structure
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12 020915909000000012
2 / 10 bwagner Rectangle
Sikalastic® RoofPro 641 Lo-VOC System Guide with Sika® Fleece
RoofPro 15** RoofPro 20** RoofPro 25**
1. Primer See Priming Guide See Priming Guide See Priming Guide
2. Base Layer:
Sikalastic®-641 Lo-
VOC
45 mils wet 35 sf/gal.
50 mils wet 32 sf/gal.
66 mils wet 24 sf/gal.
3. Reinforcement: Sika® Fleece
120 (US)
Sika® Fleece
140 (US)
Sika® Fleece
170 (US)
4. Top Layer:
Sikalastic®-641 Lo-
VOC
25 mils wet 64 sf/gal.
30 mils wet 53 sf/gal.
34 mils wet 47 sf/gal.
** Substrates: Concrete or cementious, metals, woods, single-ply or bituminous, stone. Primer required (see Substrate Priming Guide). Detailing: Sika® Flexitape Heavy or Sika® Joint Tape SA centered over seams, transistions and properly treated cracks and joints.
Note: Coverage rates provided are optimal and are not guaranteed -coverage rates will vary depending on temperature, surface roughness and porosity, aggregate selection and embedment, and application technique.
For example, using Sikalastic®-641 Lo-VOC Roofing System with Sika® Fleece 140 in a RoofPro 20 build up, a potential full system coverage rate for a mod-bit surface could be 14 - 16 sf/gal.. Sikalastic®-641 Lo-VOC Roofing System with Sika Reemat Premium in a RoofPro 15, 20 & 25 build up, a potential base coat coverage rate could be 25 - 28 sf/gal.
Composition Single component, moisture-triggered, aliphatic polyurethane
Color White, Standard Gray, Pearl Gray, Steel Gray, Mushroom, Copper Green;
custom colors available with minimum order quantity
Dry film thickness Sikalastic® RoofPro-641 Lo-VOC System Guide with Sika® RoofPro Metal RoofPro Metal 36 mils dry
Sikalastic® RoofPro-641 Lo-VOC System Guide with Sika® Reemat RoofPro 10 RoofPro 15 RoofPro 20 RoofPro 25 53 mils dry 62 mils dry 71 mils dry 85 mils dry
Sikalastic® RoofPro-641 Lo-VOC System Guide with Sika® Fleece RoofPro 15 RoofPro 20 RoofPro 25 62 mils dry 71 mils dry 89 mils dry
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12 020915909000000012
3 / 10
TECHNICAL INFORMATION
Resistance to Static Puncture Sikalastic® RoofPro 20 with Sika® Reemat Premium
Sikalastic® RoofPro 20 with Sika® Fleece 140
> 55 lbf > 55 lbf
(ASTM D-5602)
Note: Data for other RoofPro assemblies available upon request
Tensile Strength Sikalastic® RoofPro 20 with Sika® Reemat Premium
Sikalastic® RoofPro 20 with Sika® Fleece 140
1030 psi 900 psi
(ASTM D-751 Proc. B)
Note: Data for other RoofPro assemblies available upon request Sikalastic® RoofPro 20 with Sika® Reemat Premium 1030 psi (ASTM D-751 Proc. B)
Sikalastic® RoofPro 20 with Sika® Fleece 140 900 psi (ASTM D-751 Proc. B)
Tear Strength Sikalastic® RoofPro 20 with Sika® Reemat Premium
Sikalastic® RoofPro 20 with Sika® Fleece 140
300 lbf/in 200 lbf/in
(ASTM D-624)
Note: Data for other RoofPro assemblies available upon request
Elongation at Break Sikalastic® RoofPro 20 with Sika® Reemat Premium
Sikalastic® RoofPro 20 with Sika® Fleece 140
21 % 82 %
(ASTM D-751)
Note: Data for other RoofPro assemblies available upon request
External Fire Performance Class A (ASTM E-108)
Chemical Resistance Strong resistance to a wide range of reagents, including paraffin, gasoline, fuel oil, white spirit, acid rain, detergents and moderate solutions of acids and alkalis. Some low molecular weight alcohols can soften the material.
Contact Technical Service for specific recommendations.
Artificial Ageing 5,000 hours under UV light, no cracking or crazing (ASTM C-1442)
Solar Reflectance 86.8 %
57.6 %
37.5 %
12.0 %
56.5 %
(ASTM C-1549) (White) (Pearl Gray)
(Standard Gray) (Steel Gray)
(Mushroom)
Solar Reflectance Index 108 (ASTM E-1980) (White)
Thermal Emittance 0.90 0.91 0.91 0.91 0.91
(ASTM C-1371) (White) (Pearl Gray)
(Standard Gray) (Steel Gray)
(Mushroom)
Service Temperature -22–176 °F (-30–80 °C) intermittent
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12
4 / 10
APPLICATION INFORMATION
Ambient Air Temperature 41 °F (5 °C) min. / 95 °F (35 °C) max
Relative Air Humidity 85 % R.H. max.
Dew Point Beware of condensation.
The substrate and uncured coating must be ≥ 5 °F (3 °C) above dew point.
Substrate Temperature 41 °F (5 °C) min. / 140°F (60°C) max.
Substrate Moisture Content ≤ 4 % moisture content Test method: Sika®-Tramex meter No rising moisture according to ASTM (Polyethylene-sheet)
Waiting / Recoat Times Ambient Conditions Minimum Wait Time To Overcoat +40 °F / 50 % r.h. 18 hours +50 °F / 50 % r.h. 8 hours +70 °F / 50 % r.h. 6 hours
*After 7 days the surface must be cleaned and primed with Sika® Concrete Primer Lo-VOC or Sika® Reactivation Primer before continuing.
Note: Times are approximate and will be affected by changing ambient conditions particularly temperature and relative humidity.
Applied Product Ready for Use Ambient Conditions
Rain Resistant Touch Dry Full Cure
+40 °F / 50 % r.h. 1 hour 12 hours 24 hours +50 °F / 50 % r.h. 1 hour 6 hours 18–24 hours +70 °F / 50 % r.h. 1 hour 4 hours 12–18 hours
Note: Times are approximate and will be affected by changing ambient conditions particularly temperature and relative humidity.
BASIS OF PRODUCT DATA
Results may differ based upon statistical variations depending upon mixing methods and equipment, temperature, application methods, test methods, actual site conditions and curing conditions.
LIMITATIONS
Minimum age of concrete must be 28 days depending on curing and drying conditions
Do not thin with solvents▪ Do not store materials outdoors directly exposed to sunlight and moisture. Cover and protect material with breathable type covers such as canvas tarpaulins to allow venting and protection from weather and moisture. Observe temperature storage and conditioning requirements
Do not apply to substrate surfaces where moisture vapor transmission will occur during application and cure.This condition may be checked using ASTM D 4263 (Polyethylene sheet method)
Substrate must be dry prior to application. Do not apply to a frosted, wet or damp surface. Allow sufficient time for the substrate to dry after rain or inclement weather, as there is the potential for bonding problems On substrates likely to exhibit outgassing apply during falling ambient and substrate temperature. If applied during rising temperature pinholing or blistering may occur
Use sunglasses with UV filter when applying highly reflective Sikalastic®- 641 Lo-VOC White (RAL 9016).
Do not use for indoor applications unless sufficient air flow and ventilation are provided to prevent odors and/or vapors from leaving the immediate work area
Precautions should be taken to prevent odors and/or vapors from entering the building/structure, including but not limited to turning off and sealing air intake vents or other means of ingress for odors and/or vapors into the building/structure during product application and cure
For areas with direct exposure to heavy or frequent foot traffic, an additional wear coat protection with slip resistant aggregate is required. Opening to traffic prior to cure may result in loss of aggregate or permanent staining and subsequent premature failure.
Do not apply cementitious products, such as tile mortar directly onto Sikalastic®- 641 Lo-VOC. See Sikalastic®-624 WP or Sikalastic®-644 Lo VOC Product Data Sheet
Any repairs required to achieve a level surface must be performed prior to application (consult a Sika
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12
5 / 10 representative for guidance on various product solutions). Surface irregularities may reflect through the cured system When applying over existing coatings or membranes compatibility and adhesion testing and subsequent approval by Technical Services is required
Opening to traffic prior to cure may result in permanent staining and subsequent premature failure
On grade concrete decks should not be covered with Sikalastic® RoofPro membrane systems
Unvented metal pan, split/sandwich slab with encapsulated membrane and/or insulation, cinder fill decks, and lightweight insulating concrete deck overlays should not be covered with Sikalastic® RoofPro systems without additional deck evaluation and subsequent approval by Technical Services
Do not subject to continuous immersion, i.e., fountains, ponds, pools, or interior of tanks
Not recommended for use over ceramic tile▪
ENVIRONMENTAL, HEALTH AND SAFETY
For further information and advice regarding transportation, handling, storage and disposal of chemical products, user should refer to the actual Safety Data Sheets containing physical, environmental, toxicological and other safety related data. User must read the current actual Safety Data Sheets before using any products. In case of an emergency, call CHEMTREC at 1-800-424-9300, International 703-527-3887.
APPLICATION INSTRUCTIONS
Substrate Pre-Treatment Refer to Priming Guide to select primer for properly evaluated and prepared substrate. Refer to separate primer Product Data Sheet for application methods, coverage rates, cure times and recoat windows. Always allow primer to cure thoroughly before applying detail or base resin layer.
Sikalastic® RoofPro-641 Lo-VOC Priming Guide
Substrates and Primer Options Concrete *1 Sikalastic® Concrete Primer Lo-VOC Sikalastic® DTE Primer Sikalastic® GDC Primer Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid Lightweight Structural Concrete *1 Sikalastic® Concrete Primer Lo-VOC Sikalastic® DTE Primer Sikalastic® GDC Primer Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid Cement, Gypsum Based Roof Boards Sikalastic® Concrete Primer Lo-VOC Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid
Brick, Stone *3 Sikalastic® Concrete Primer Lo-VOC Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid Bituminous Substrate Asphalt, Bituminous Felts, Bituminous Coatings, Granulated or Smooth SBS & Aged APP Cap Sheets *2,3 Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid Single Ply PVC Membranes *3 Sarnafil, Sikaplan *3 Sikalastic® EP Primer/Sealer Hypalon *3 Sika® Bonding Primer
TPO, EPDM *3
Sikalastic® EPDM Primer Sikalastic® EPDM / TPO Primer Lo-VOC Roof tiles (unglazed) *3,4 Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid Fiberglass *3 Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid Polyurethane Foam - Sprayed or Slab Stock Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid
Metal *3 Aluminium, Galvanized, Cast Iron, Copper, Lead, Brass, Stainless Steel, Steel, Zinc Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid Pre-Coated Metal *3 Paints & Coatings *3 Aluminized Solar Reflective Coatings *3 Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid Wood - Timber & Plywood *5 Sikalastic® EP Primer/Sealer Sikalastic® EP Primer Rapid
* Consult Sika 1 New cementitious substrates must be Portland base and be cured min. 28 days.
2 The presence of volatile bitumen may cause discoloration of Sikalastic® if not properly primed.
3 Surface evaluation and field adhesion testing.
4 Glazed tile consult Sika.
5 Pressure treated lumber consult Sika.
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12
6 / 10
SUBSTRATE PREPARATION
Concrete and Cementitious Substrates New concrete shall be allowed to cure a minimum of 28 days. Concrete shall have a minimum compressive strength of 20.7 MPa (3000 psi) and exhibit a minimum tensile bond strength of 1.4 MPa (200 psi). Moist or sheet curing methods should be used, as opposed to the use of curing compounds, which may interfere with the bond of the membrane. Inspect the concrete, including upstands. All areas should be hammer or chain drag tested. Concrete must be suitably finished, preferably by wood float or steel pan. A power float finish is acceptable where the surface is prepared to avoid laitance (a tamped finish is not acceptable). The surface finish must be uniform and free from defects such as laitance, voids or honeycombing.
Cementitious or mineral based substrates must be prepared mechanically using abrasive blast cleaning or scarifying equipment to remove cement laitance and to achieve an open textured surface (CSP 2-4 per ICRI guidelines). Loose friable material and weak concrete must be completely removed and surface defects such as blowholes and voids must be fully exposed. The amount of embedment coat required may increase over rough or highly porous surfaces.
Repairs to the substrate, filling of joints, blowholes/voids and surface levelling must be carried out. Consult Sika for product recommendations based on project requirements. High spots must be removed by grinding or similar method. Outgassing is a naturally occurring phenomenon of concrete that can produce pinholes in liquid applied materials. The concrete must be carefully assessed for moisture content, air entrapment, and surface finish prior to any roofing/waterproofing work.
Particular requirements for priming must also be considered. Installing the primer and membrane either when the concrete temperature is falling or stable can reduce outgassing. It is generally beneficial to apply the primer and embedment coat in the late afternoon or evening.
Gypsum and Cement Based Sheathing Sheathing boards shall be clean, dry,dust free, and shall be properly secured to the structure. Secure loose boards if in sound condition. Damaged or contaminated boards shall be removed and replaced.
Brick and Stone Mortar joints must be sound and preferably flush pointed. Power wash and use biodegradeable non-sudsing detergent with clean water rinse as required.
Asphalt Asphalt contains volatiles which can cause bleeding and slight non-detrimental staining. The asphalt must be carefully assessed for moisture and/or air entrapment, grade and surface finish. Power wash and use biodegradeable non-sudsing detergent with clean water rinse as required. All major cracks should be sealed to allow continuity of the Sikalastic® RoofPro system.
Bituminous Felt Ensure that bituminous felt is firmly adhered or mechanically fixed to the substrate. Bituminous felt shall not contain badly degraded areas. Power wash and use biodegradeable non-sudsing detergent with clean water rinse as required. Treat blisters by star cutting and removing any underlying water. Allow to dry and re-adhere using suitable adhesive.
Bituminous Coatings Bituminous coatings should not be sticky or mobile.
Volatile mastic coatings, or old coal tar coatings are not acceptible. Remove any loose or degraded coatings.
Metals Metals must be in sound condition. Ferrous metals should be thoroughly cleaned by grinding or blast cleaning prior to priming (SSPC-SP3 to SP11 near-white metal). Non-ferrous metals are prepared by removing any deposits of dust and oxidation and abrading to bright metal. Wire brushing can be used for soft metal such as lead. The surface must be clean and free from grease which, if present, must be removed with a solvent wipe or wash with detergent, rinse and dry.
Stainless Steel must be mechanically abraded or ground to create an appropriate anchor profile.
Wooden Substrates Plywood and timber based roof decks must be in good condition, firmly adhered or mechanically fixed. All plywood should be identified as conforming to PS 1 for construction and industrial plywood by grade, APA (American Plywood Association) trademark, or equivalent. For maximum smoothness, EXT Type APA, Grade A-C should be used, and the “A” side should be positioned to receive the Sikalastic® resin. Plywood decks to receive resin directly shall be at least 1/2'' thick
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12
7 / 10 and attached and supported according to APA guidelines, using only non-rusting screw, spiral or coated nail type fasteners. A good practice would be to recess or counter sink fasteners 1/8 to 1/4'' and fill with Sikaflex® sealant. Suitable edge support to prevent differential deflection between panels shall be provided.
Panel edges shall be tongue and groove or supported on solid blocking. Space panels 1/8 to 3/16'' at panel ends.
Timber and timber based roof decks require additional reinforcement such as the installation of plywood, approved insulation or cover board. Small timber protrusions and suitable decks may be treated directly, provided that the timber is of exterior quality, i.e.
plywood. Fill joints flush with Sikaflex® sealant.
Paints and Coatings Ensure the existing material is sound and firmly adhered. Remove any loose or degraded coatings.
Ensure the surface is clean and free from oxidation, dust, dirt, and debris. Power wash and use biodegradeable non-sudsing detergent with clean water rinse as required.
Existing Sikalastic® RoofPro System The existing Sikalastic® RoofPro System shall be soundly adhered to the substrate. Clean the membrane using a pressure washer at approximately 140bar (2000 psi) and biodegradeable non-sudsing detergent with clean water rinse. Allow to dry.
Sikaplan®/Sarnafil® membranes Clean the membrane using a pressure washer at approximately 140bar (2000 psi) and biodegradeable non-sudsing detergent with clean water rinse. Allow to dry.
MIXING
No mixing necessary
APPLICATION
Detailing
Non-structural Cracks Up To 1/16'' Detail application not necessary. Apply embedment/base resin layer per below. Non-structural cracks between 1/16'' and 1/4''. Rout and seal with Sikaflex® sealant. Apply 40–45 mil resin layer embedded with 3'' Sika Flexitape Heavy or use Sika® Joint Tape SA centered over the crack. Apply embedment/base resin layer per instruction.
Cracks and Joints Between 1/4" and 1'' Rout and seal with Sikaflex® sealant. Apply bond breaker tape sufficient to span width of crack or joint followed by 40-45 mil resin layer embedded with 6'' Sika® Flexitape Heavyor use Sika® Joint Tape SA centered over crack or joint. Apply embedment/base resin layer by terminating Sika® Reemat or Sika® Fleece at edges of crack or joint overlapping Sika® Flexitape Heavy or Sika® Joint Tape SA, a minimum of 2 inches on both sides of the crack or joint.
Joints Greater Than 1'' Treat as expansion joint. Consult Sika for recommendations.
Metal Seams and Plywood/Cover Board Joints Apply 40–45 mil resin layer embedded with 3 or 6'' Sika® Flexitape Heavy centered over seam. Alternativly Sika® Joint Tape SA can be applied centered over seam. Apply embedment resin layer per instruction.
Transitions Between Dissimilar Materials Apply 40–45 mil resin layer embedded with Sika® Flexitape Heavy or use Sika® Joint Tape SA centered over transitions or dissimilar materials. Apply embedment resin layer per instruction.
Embedment/Base Resin Layer With Sika® Reemat Reinforcement Mixing not required. Apply Sikalastic®- 641 Lo-VOC at the coverage rate listed in the RoofPro System Guide using a 1/2'' nap phenolic resin core roller. Material can also be squeegee or spray applied, in which case it should be backrolled prior to embedding Sika® Reemat.
Place Sika® Reemat in wet base resin layer overlapping seams a minimum of 2'' (place frayed edge over cut edge of roll) and apply wet roller to topside to saturate completely. After approximately 5 minutes the binder will begin to dissolve allowing the fiber strands to conform to irregular surfaces. Do not over work once the fibers have conformed to the substrate. Allow to cure 12 hours at 70 °F and 50 % R.H. or until tack free before top resin layer. Keep clean and dry and apply top resin layer within 7 days. If window is exceeded clean with non-sudsing detergent and clean water rinse, and allow to dry prior to application of Sika® Concrete Primer Lo-VOC or Sika® Reactivation Primer.
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12
8 / 10
Top Resin Layer With Sika® Reemat Reinforcement Mixing not required. Apply Sikalastic®- 641 Lo-VOC at the coverage rate listed in the RoofPro System Guide with a 1/2'' nap phenolic resin core roller. Material can also be squeegee or spray applied, in which case it should also be backrolled. In the case of RoofPro 25 allow the first top resin layer to cure 12 hours at 70 °F and 50 % R.H. or until tack free before applying second top resin layer. On top of the complete RoofPro system additional resin layers may be applied with aggregate for slip resistance. Keep clean and dry and apply additional resin layers within 7 days. If window is exceeded clean with non-sudsing detergent and clean water rinse, and allow to dry prior to application of Sika® Concrete Primer Lo-VOC or Sika® Reactivation Primer.
Wet On Wet Application With Sika® Fleece Reinforcement Mixing not required. To primed substrate apply two-thirds of the Sikalastic®- 641 Lo-VOC specified in the RoofPro System Guide with a 1/2'' nap phenolic resin core roller. Immediately place specified Sika® Fleece into wet resin overlapping seams a minimum of 3” along the edge and 6” end-to-end. Apply wet roller to topside with light pressure to saturate fleece from bottom and ensure air pockets are completely removed.
Immediately apply all of remaining one-third of Sikalastic®- 641 Lo-VOC resin specified in the RoofPro System Guide. Ensure there is an even and complete fleece saturation from the topside.
Aggregated Surfacing Supplemental aggregate surfacing is required for all applications that will experience direct foot traffic such as balconies, terraces, walkways, and plazas. It is also recommended for areas that experience maintenance foot traffic. The aggregate surfacing is applied in a supplemental resin layer after the Sikalastic membrane has been installed. Aggregate is not applied into the roofing/waterproofing resin.
Seed and Back Roll Option The Seed and Backroll option is primarily intended for use for maintenance traffic-type applications where enhanced slip resistance is required. Apply Sikalastic®- 641 Lo-VOC resin at 15 mils wet film thickness to the installed, cured membrane system. While the supplemental resin application is still wet seed with kiln dried, iron free aggregate. Back roll the surface to encapsulate the aggregate in the Sikalastic resin.
Full Broadcast and Seal Option The Full Broadcast and Seal option is intended for use for applications where both enhanced slip resistance and physical protection of the roofing membrane is required. Apply Sikalastic®- 641 Lo-VOC resin at 15 mils wet film thickness to the installed, cured membrane system. While the supplemental resin application is still wet broadcast to rejection (full broadcast/beach) with kiln dried, iron free aggregate. Remove excess aggregate after cure. Seal with an additional coat of Sikalastic resin.
Aggregate Selection Use clean, rounded or semiangular, oven dried quartz sand with a minimum hardness of 6.5 per the Moh’s scale. It should be supplied in prepackaged bags and free of metallic or other impurities. The following size gradations are recommended:
16–30 or 20–40 mesh for pedestrian traffic systems▪
CLEANING OF TOOLS
Clean all tools and application equipment with appropriate solvent immediately after use. Hardened and/or cured material can only be removed mechanically.
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12
9 / 10
OTHER RESTRICTIONS
See Legal Disclaimer.
LEGAL DISCLAIMER
• KEEP CONTAINER TIGHTLY CLOSED
• KEEP OUT OF REACH OF CHILDREN
• NOT FOR INTERNAL CONSUMPTION
• FOR INDUSTRIAL USE ONLY
• FOR PROFESSIONAL USE ONLY
Prior to each use of any product of Sika Corporation, its subsidiaries or affiliates (“SIKA”), the user must always read and follow the warnings and instructions on the product’s most current product label, Product Data Sheet and Safety Data Sheet which are available at usa.sika.com or by calling SIKA’s Technical Service Department at 1-800-933-7452. Nothing contained in any SIKA literature or materials relieves the user of the obligation to read and follow the warnings and instructions for each SIKA product as set forth in the current product label, Product Data Sheet and Safety Data Sheet prior to use of the SIKA product.
SIKA warrants this product for one year from date of installation to be free from manufacturing defects and to meet the technical properties on the current Product Data Sheet if used as directed within the product’s shelf life. User determines suitability of product for intended use and assumes all risks. User’s and/or buyer’s sole remedy shall be limited to the purchase price or replacement of this product exclusive of any labor costs.
NO OTHER WARRANTIES EXPRESS OR IMPLIED SHALL
APPLY INCLUDING ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. SIKA SHALL NOT BE LIABLE UNDER ANY LEGAL
THEORY FOR SPECIAL OR CONSEQUENTIAL DAMAGES.
SIKA SHALL NOT BE RESPONSIBLE FOR THE USE OF THIS
PRODUCT IN A MANNER TO INFRINGE ON ANY PATENT
OR ANY OTHER INTELLECTUAL PROPERTY RIGHTS HELD
BY OTHERS.
Sale of SIKA products are subject to the Terms and Conditions of Sale which are available at https://usa.sika.com/en/group/SikaCorp/termsandconditions.html or by calling 1-800-933-7452.
Sika Corporation 201 Polito Avenue Lyndhurst, NJ 07071 Phone: +1-800-933-7452 Fax: +1-201-933-6225 usa.sika.com
Sikalastic-641Lo-VOCRoofingSystem-en-US-(09-2023)-1-12.pdf
System Data Sheet Sikalastic®-641 Lo-VOC Roofing System September 2023, Version 01.12
10 / 10
Safety Data Sheet according to the OSHA Hazard Communication Standard
Sikalastic®-641 Lo-VOC
Revision Date 02/05/2024
Print Date 02/05/2024
1 / 18
SECTION 1. IDENTIFICATION
Product name : Sikalastic®-641 Lo-VOC
Company name : Sika Corporation
201 Polito Avenue Lyndhurst, NJ 07071
USA
www.sikausa.com
Telephone : (201) 933-8800
Telefax : (201) 804-1076
E-mail address : ehs@sika-corp.com
Emergency telephone : CHEMTREC: 800-424-9300
INTERNATIONAL: +1-703-527-3887
Recommended use of the chemical and restrictions on use
: For further information, refer to product data sheet.
SECTION 2. HAZARDS IDENTIFICATION
GHS classification in accordance with the OSHA Hazard Communication Standard (29 CFR 1910.1200) Flammable liquids
: Category 4
Acute toxicity (Inhalation)
: Category 4
Skin irritation
: Category 2
Eye irritation
: Category 2A
Respiratory sensitization
: Category 1
Skin sensitization
: Category 1
Reproductive toxicity
: Category 1B
GHS label elements Hazard pictograms
Signal Word : Danger
2 / 18
Hazard Statements : H227 Combustible liquid.
H315 Causes skin irritation.
H317 May cause an allergic skin reaction.
H319 Causes serious eye irritation.
H332 Harmful if inhaled.
H334 May cause allergy or asthma symptoms or breathing diffi-culties if inhaled.
H360 May damage fertility or the unborn child.
Precautionary Statements : Prevention:
P201 Obtain special instructions before use.
P202 Do not handle until all safety precautions have been read and understood.
P210 Keep away from heat/ sparks/ open flames/ hot surfaces.
No smoking.
P261 Avoid breathing mist or vapors.
P264 Wash skin thoroughly after handling.
P271 Use only outdoors or in a well-ventilated area.
P272 Contaminated work clothing must not be allowed out of the workplace.
P280 Wear protective gloves/ protective clothing/ eye protection/ face protection.
P284 Wear respiratory protection.
Response:
P302 + P352 IF ON SKIN: Wash with plenty of soap and water.
P304 + P340 + P312 IF INHALED: Remove person to fresh air and keep comfortable for breathing. Call a POISON CENTER/ doctor if you feel unwell.
P305 + P351 + P338 IF IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. Continue rinsing.
P308 + P313 IF exposed or concerned: Get medical advice/ attention.
P333 + P313 If skin irritation or rash occurs: Get medical advice/ attention.
P337 + P313 If eye irritation persists: Get medical advice/ atten-tion.
P342 + P311 If experiencing respiratory symptoms: Call a POISON CENTER/ doctor.
P362 + P364 Take off contaminated clothing and wash it before reuse.
P370 + P378 In case of fire: Use dry sand, dry chemical or alco-hol-resistant foam to extinguish.
Storage:
P403 Store in a well-ventilated place.
P405 Store locked up.
Disposal:
P501 Dispose of contents/ container to an approved waste dis-
3 / 18 posal plant.
Additional Labeling There are no ingredients with unknown acute toxicity used in a mixture at a concentration >= 1%.
Other hazards None known.
SECTION 3. COMPOSITION/INFORMATION ON INGREDIENTS
Mixtures
Components Chemical name CAS-No. Classification Concentra-tion (% w/w) 4-chloro-α,α,α-trifluorotoluene 98-56-6 Flam. Liq. 3; H226
Skin Irrit. 2; H315 Eye Irrit. 2A; H319 Skin Sens. 1B; H317
STOT SE 3; H335
>= 10 - < 20 barium sulfate 7727-43-7 >= 5 - < 10 Hardener MTJ (Polyoxypropylene-tri(morpholinoaldimine))
1379822-00-0 Skin Sens. 1B; H317 >= 5 - < 10 triphenyl phosphate 115-86-6 >= 1 - < 5 Hardener MI (Isopho-ronedi(morpholinoaldimine))
1217271-02-7 Skin Irrit. 2; H315 Eye Irrit. 2A; H319 Skin Sens. 1; H317
>= 1 - < 5
Isophorondiisocyanate homopoly-mer
53880-05-0 Skin Sens. 1B; H317
STOT SE 3; H335
>= 1 - < 5
Methyl Acetate Salicylic Acid Blend Not Assigned Flam. Liq. 2; H225 Eye Dam. 1; H318 Repr. 2; H361
STOT SE 3; H336
>= 1 - < 5 tris(methylphenyl) phosphate 1330-78-5 Repr. 2; H361 >= 0.1 - < 1 3-isocyanatomethyl-3,5,5-trimethylcyclohexyl isocyanate
4098-71-9 Acute Tox. 1; H330 Skin Corr. 1C; H314 Eye Dam. 1; H318 Resp. Sens. 1; H334 Skin Sens. 1; H317
STOT SE 3; H335
>= 0.1 - < 1
Pentamethyl piperidylsebacate 41556-26-7 Skin Sens. 1A; H317 Repr. 2; H361
>= 0.1 - < 1
N-methyl-2-pyrrolidone 872-50-4 Skin Irrit. 2; H315 Eye Irrit. 2A; H319 Repr. 1B; H360D
STOT SE 3; H335
>= 0.1 - < 1
4,5-dichloro-2-octyl-2H-isothiazol-3-one (DCOIT)
64359-81-5 Acute Tox. 4; H302 Acute Tox. 2; H330 Skin Corr. 1; H314 Eye Dam. 1; H318
>= 0.1 - < 1
4 / 18
Skin Sens. 1A; H317 Actual concentration is withheld as a trade secret
SECTION 4. FIRST AID MEASURES
General advice : Move out of dangerous area.
Consult a physician.
Show this material safety data sheet to the doctor in attend-ance.
If inhaled : Move to fresh air.
Consult a physician after significant exposure.
In case of skin contact : Take off contaminated clothing and shoes immediately.
Wash off with soap and plenty of water.
If symptoms persist, call a physician.
In case of eye contact : Immediately flush eye(s) with plenty of water.
Remove contact lenses.
Keep eye wide open while rinsing.
If eye irritation persists, consult a specialist.
If swallowed : Clean mouth with water and drink afterwards plenty of water.
Do not induce vomiting without medical advice.
Do not give milk or alcoholic beverages.
Never give anything by mouth to an unconscious person.
Obtain medical attention.
Most important symptoms and effects, both acute and delayed
: irritant effects sensitizing effects toxic effects for reproduction Asthmatic appearance Respiratory disorder Allergic reactions Excessive lachrymation Erythema Headache Dermatitis Causes skin irritation.
May cause an allergic skin reaction.
Causes serious eye irritation.
Harmful if inhaled.
May cause allergy or asthma symptoms or breathing difficul-ties if inhaled.
May damage fertility or the unborn child.
Notes to physician : Treat symptomatically.
SECTION 5. FIRE-FIGHTING MEASURES
5 / 18
Suitable extinguishing media : Carbon dioxide (CO2)
Unsuitable extinguishing media
: Water
Further information : Collect contaminated fire extinguishing water separately. This must not be discharged into drains.
Fire residues and contaminated fire extinguishing water must be disposed of in accordance with local regulations.
Special protective equipment for fire-fighters
: In the event of fire, wear self-contained breathing apparatus.
SECTION 6. ACCIDENTAL RELEASE MEASURES
Personal precautions, protec-tive equipment and emer-gency procedures
: Use personal protective equipment.
Deny access to unprotected persons.
Environmental precautions : Do not flush into surface water or sanitary sewer system.
If the product contaminates rivers and lakes or drains inform respective authorities.
Local authorities should be advised if significant spillages cannot be contained.
Methods and materials for containment and cleaning up
: Soak up with inert absorbent material (e.g. sand, silica gel, acid binder, universal binder, sawdust).
Keep in suitable, closed containers for disposal.
SECTION 7. HANDLING AND STORAGE
Advice on protection against fire and explosion
: Normal measures for preventive fire protection.
Advice on safe handling : Avoid formation of aerosol.
Do not breathe vapors or spray mist.
Avoid exceeding the given occupational exposure limits (see section 8).
Do not get in eyes, on skin, or on clothing.
For personal protection see section 8.
Persons with a history of skin sensitization problems or asth-ma, allergies, chronic or recurrent respiratory disease should not be employed in any process in which this mixture is being used.
Smoking, eating and drinking should be prohibited in the ap-plication area.
Provide sufficient air exchange and/or exhaust in work rooms.
Pregnant women or women of child-bearing age should not be exposed to this product.
Follow standard hygiene measures when handling chemical products.
6 / 18
Precautions should be taken to prevent odors and/or vapors from entering the building/structure, including but not limited to turning off and sealing air intake vents or other means of in-gress for odors and/or vapors into the building/structure during product application and cure.
Avoid formation of aerosol.
Do not breathe vapors or spray mist.
Avoid exceeding the given occupational exposure limits (see section 8).
Do not get in eyes, on skin, or on clothing.
For personal protection see section 8.
Persons with a history of skin sensitization problems or asth-ma, allergies, chronic or recurrent respiratory disease should not be employed in any process in which this mixture is being used.
Smoking, eating and drinking should be prohibited in the ap-plication area.
Provide sufficient air exchange and/or exhaust in work rooms.
Pregnant women or women of child-bearing age should not be exposed to this product.
Follow standard hygiene measures when handling chemical products.
Conditions for safe storage : Store in original container.
Keep in a well-ventilated place.
Containers which are opened must be carefully resealed and kept upright to prevent leakage.
Observe label precautions.
Store in accordance with local regulations.
Materials to avoid : Explosives Oxidizing agents Poisonous gases Poisonous liquids
SECTION 8. EXPOSURE CONTROLS/PERSONAL PROTECTION
Ingredients with workplace control parameters Components CAS-No. Value type
(Form of exposure)
Control parame-ters / Permissible concentration
Basis barium sulfate 7727-43-7 TWA (Inhal-able particu-late matter)
5 mg/m3 ACGIH
TWA (total dust)
15 mg/m3 OSHA Z-1
TWA (respir-able fraction)
5 mg/m3 OSHA Z-1
TWA (Total 10 mg/m3 OSHA P0
7 / 18 dust) TWA (respir-able dust fraction)
5 mg/m3 OSHA P0 triphenyl phosphate 115-86-6 TWA 3 mg/m3 ACGIH TWA 3 mg/m3 OSHA Z-1 TWA 3 mg/m3 OSHA P0
3-isocyanatomethyl-3,5,5-trimethylcyclohexyl isocyanate
4098-71-9 TWA 0.005 ppm OSHA P0
STEL 0.02 ppm OSHA P0
The above constituents are the only constituents of the product which have a PEL, TLV or other rec-ommended exposure limit. At this time, the other constituents have no known exposure limits.
Engineering measures : Use of adequate ventilation should be sufficient to control worker exposure to airborne contaminants. If the use of this product generates dust, fumes, gas, vapor or mist, use pro-cess enclosures, local exhaust ventilation or other engineer-ing controls to keep worker exposure below any recommend-ed or statutory limits.
The engineering controls also need to keep gas, vapor or dust concentrations below any…
This is the start of the file's text. The full file is on GovTribe.