089000 - Louvers and Vents - Edited.pdf
PDF 124 KB Posted
- Attached to
- Z2DA--542-25-105 | Replace Pitched Roof Building 1 | NCO 4 Construction East (VA-25-00008811)
- Solicitation number
- 36C24425B0003
About this file
This technical specification document (Section 08 90 00) details requirements for louvers and vents for the Replace Pitched Roof Building 1 project at the Coatesville VAMC in Pennsylvania. The specification covers fixed and operable wall louvers, door louvers, and wall vents, with comprehensive requirements for materials, fabrication, performance, and installation.
Key technical specifications include aluminum and stainless steel louver construction with specific material standards (ASTM B221, A240/A240M), minimum thickness requirements (2mm for frames), and performance criteria such as weather resistance and blast resistance. The document mandates wire guards for exterior louvers, specifies finish options including anodized and organic coatings, and provides detailed installation instructions. Notably, the louvers must meet blast resistance standards for Life Safety Protected facilities, with specific deformation and pressure resistance requirements. Installation must be precise, with louvers set plumb, level, and properly anchored, and all components must be cleaned and adjusted to operate without binding.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| INSTRUCTIONS to bidders.docx | DOCX document | |
| 36C24425B0003 0004.docx | DOCX document | |
| Sign in sheet Replace roof building 1 4 March 2025.pdf | ||
| 542-25-105 - Contractor Questions and Answers Site Visit No. 2 10 April 2025.docx | DOCX document | |
| 36C24425B0003 0003.docx | DOCX document | |
| Sign in sheet Replace roof building 1 10 April 2025.pdf | ||
| PA VA DORMER DRAWINGS.pdf | ||
| Building 1 Roof - 2.pdf | ||
| Building 1 Roof - 1.pdf | ||
| 542-25-105 - Contractor Questions and Answers updated.docx | DOCX document | |
| 099100 - Painting - Edited.pdf | ||
| 36C24425B0003 0002.docx | DOCX document | |
| Sign in sheet for Replace Roof building 1 2.pdf | ||
| 36C24425B0003 0001.docx | DOCX document | |
| Attachment 5 - GEMS Contractor training.doc | DOC document | |
| Attachment 6 - Bldg 1 Roof - Construction Safety Standards.pdf | ||
| 542-25-105 Specifications.pdf | ||
| 542-25-105 Replace Pitched Roof Building 1 - Drawings - Updated.pdf | ||
| 36C24425B0003_1.docx | DOCX document | |
| 542-25-105 Additional Specs.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Replace Pitched Roof Building 1 Bid Documents Coatesville VAMC | Coatesville, PA
03-27-25
08 90 00 - 1
SECTION 08 90 00
LOUVERS AND VENTS
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies fixed and operable wall louvers, door louvers and wall vents.
1.2 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Shop Drawings:
1. Each type, showing material, finish, size of members, method of assembly, and installation and anchorage details.
C. Manufacturer's Literature and Data:
1. Each type of louver and vent.
D. Color samples.
1.3 APPLICABLE PUBLICATIONS:
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. The Master Painters Institute (MPI):
Approved Product List – Updated Monthly
C. ASTM International (ASTM):
A240/A240M-20...........Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
A653/A653M-20...........Steel Sheet Zinc-Coated (Galvanized) or Zinc-
Iron Alloy Coated (Galvannealed) by the Hot Dip
Process
A1008/A1008M-20.........Steel, Sheet, Carbon, Cold Rolled, Structural, and High Strength Low-Alloy with Improved
Formability
B209-14.................Aluminum and Aluminum Alloy, Sheet and Plate
B209M-14................Aluminum and Aluminum Alloy, Sheet and Plate
(Metric)
B221-14.................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes
Coatesville VAMC | Coatesville, PA
03-27-25
08 90 00 - 2
B221M-13................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric)
D1187/D1187M-97(2018)...Asphalt-Base Emulsions for Use as Protective
Coatings for Metal
D. National Association of Architectural Metal Manufacturers (NAAMM):
AMP 500-06..............Metal Finishes Manual
E. National Fire Protection Association (NFPA):
90A-15..................Installation of Air Conditioning and
Ventilating Systems
F. American Architectural Manufacturers Association (AAMA):
2605-13.................High Performance Organic Coatings on
Architectural Extrusions and Panels
G. Air Movement and Control Association, Inc. (AMCA):
500-L-07 Testing Louvers
I. Protective Design Center PDC-TR-08 Single Degree of Freedom Structural Response Limits for
Antiterrorism Design
PART 2 - PRODUCTS
2.1 MATERIALS:
A. Aluminum, Extruded: ASTM B221M (B221).
B. Stainless Steel: ASTM A240/A240M, Type 302B.
C. Galvanized Steel Sheet: ASTM A653/A653M; G90 min.
D. Carbon Steel and Sheet: ASTM A1008/A1008M (interior use louvers only).
E. Aluminum, Plate and Sheet: ASTM B209M (B209); alloy 3003 or 5005 with temper as required for forming.
F. Fasteners: Fasteners for securing louvers and wall vents to adjoining construction, except as otherwise specified or indicated in construction documents, to be toggle or expansion bolts of size and type as required for each specific type of installation and service condition.
1. Where type, size, or spacing of fasteners is not shown or specified, submit shop drawings showing proposed fasteners, and method of installation.
2. Fasteners for louvers, louver frames, and wire guards to be of stainless steel or aluminum with same finish as louvers.
3. Fasteners for louvers, louver frames and wire guards within mental health areas to be non-removable/tamper-proof type.
Coatesville VAMC | Coatesville, PA
03-27-25
08 90 00 - 3
G. Inorganic Zinc Primer: MPI No. 19.
H. Bituminous Coating: ASTM D1187/D1187M; cold applied asphalt mastic emulsion.
2.2 EXTERIOR WALL LOUVERS:
A. General:
1. Provide fixed and operable type louvers of size and design shown.
2. Heads, sills and jamb sections are to have formed caulking slots or be designed to retain caulking. Head sections are to have exterior drip lip, and sill sections an integral water stop.
3. Furnish louvers with sill extension or separate sill as shown.
4. Frame is to be mechanically fastened or welded construction with welds dressed smooth and flush.
B. Performance Characteristics:
1. Weather louvers are to have a minimum of 50 percent free area and to pass 5 mm/s (10 fpm) free area velocity at a pressure drop not exceeding 2 mm (1.5 inch) water gauge and carry not more than 50 g
(2 ounces) of water per square meter (6 square foot) of free area for 15 minutes when tested per AMCA Standard 500-L.
2. Louvers are to bear AMCA certified rating seals for air performance and water penetration ratings.
3. Blast Resistance:
A. Louvers in exterior walls shall be blast resistant and meet the following criteria per the VA Physical Security Design Manual for
Life Safety Protected Facilities January 2015:
1. Standoff Distance: 25 feet (Life Safety Protected)
a. Design Threat W1 at the standoff distance not to exceed pressure and impulse associated with GP1 threat for Life
Safety Protected Buildings.
b. Deformation not to exceed those defined by B3 response per the Protective Design Center document PDC-TR-08 while experiencing design level pressures.
C. Aluminum Louvers:
1. General: Frames, blades, and mullions (sliding interlocking type); 2 mm (0.078-inch) thick extruded 6063-T5 or –T52 aluminum. Blades to be standard type and have reinforcing bosses.
2. Louvers, fixed: Make frame sizes 13 mm (1/2-inch) smaller than openings. Single louvers frames are not to exceed 1676 mm (66
Coatesville VAMC | Coatesville, PA
03-27-25
08 90 00 - 4 inches) wide. When openings exceed 1676 mm (66 inches), provide twin louvers separated by mullion members.
3. Louvers are to withstand the effects or gravity loads and the following wind loads and stresses within limits and under conditions indicated without permanent deformation of louver components, noise or metal fatigue caused by louver-blade rattle or flutter, or permanent damage to fasteners and anchors.
a. Wind load acting inward or outward of not less than 1436 Pa (30 pound per square foot.).
4. Louvers, operable: Louver frame opening sizes, single louver sizes and mullion requirements are to be as specified for fixed louvers.
a. Blades: Attach blades to frame with aluminum pivot pins through nylon bearings. Fasten each blade to stainless steel operation arms that are connected to minimum 3 mm (1/8-inch) thick stainless steel operating bar arranged for simultaneous operation of blades.
D. Stainless Steel Louvers: Form stainless steel louvers using 1.6 mm (0.063-inch) thick sheet for frames, blades, sills, and mullions.
1. Provide louver with fixed 45-degree standard blades with water baffle. Make overall frame size 13 mm (1/2-inch) less than opening, unless otherwise indicated in construction documents.
2. Single louver sections are not to exceed 1676 mm (66 inches) in width. For openings larger than 1676 mm (66 inches) wide, provide multiple sections not larger than 1676 mm (66 inches) wide separated by mullions.
E. Formed Steel Louvers: Form galvanized louvers using 1.5 mm (0.059-inch) thick sheet for frames, blades, sills, and mullions.
1. Provide louver with fixed 45-degree standard blades with water baffle. Make overall frame size 13 mm (1/2-inch) less than opening, unless otherwise indicated in construction documents.
2. Single louver sections are not to exceed 1676 mm (66 inches) in width. For openings larger than 1676 mm (66 inches) wide, provide multiple sections not larger than 1676 mm (66 inches) side separated by mullions.
2.3 CLOSURE ANGLES AND CLOSURE PLATES:
A. Fabricate from 2 mm (0.078-inch) thick stainless steel or aluminum.
Coatesville VAMC | Coatesville, PA
03-27-25
08 90 00 - 5
B. Provide continuous closure angles and closure plates on inside head, jambs and sill of exterior wall louvers.
C. Secure angles and plates to louver frames with screws, and to masonry or concrete with fasteners as indicated in construction documents.
2.4 WIRE GUARDS:
A. Provide wire guards on outside of all exterior louvers, except on exhaust air louvers.
B. Fabricate frames from 2 mm (0.078-inch) thick extruded or sheet aluminum designed to retain wire mesh.
C. Wire mesh to be woven from not less than 1.6 mm (0.063-inch) diameter aluminum wire in 13 mm (1/2-inch) square mesh.
D. Miter corners and join by concealed corner clips or locks extending not less than 57 mm (2-1/4 inches) into rails and stiles. Equip wire guards over 1219 mm (4 feet) in height with a mid-rail constructed as specified for frame components.
E. Fasten frames to outside of louvers with aluminum or stainless-steel devices of same finish as louvers designed to allow removal and replacement without damage to the wire guard or the louver.
2.5 EXTERIOR DOOR LOUVERS:
A. Fabricate of 1.6 mm (0.063-inch) thick extruded aluminum. Miter frames at corners and join by concealed corner brackets. Louvers are to be weather resistant type.
B. Equip louvers on outside with wire guards, except omit wire guards for louvers in doors located completely below enclosed areaways.
2.6 FINISH:
A. In accordance with NAAMM Metal Finishes Manual: AMP 500-505 B. Aluminum Louvers, Air Intake Vents, Wire Guards, and Blank Off Panels:
1. Anodized finish
a. AA-M1X, Mill finish, as fabricated.
2. Organic Finish: AAMA 2605 (Fluorocarbon coating) with total dry film thickness of not less than 0.03 mm (1.2 mil).
A. Aluminum Wall Vents and Brick Vents: Sand blasted satin finish.
B. Stainless Steel: Mechanical finish No. 4 in accordance with NAAMM
Metal Finishes Manual.
C. Galvanized Sheet Steel: Two-coat baked-enamel or powder-coat finish consisting of prime coat and thermosetting topcoat, with a minimum dry film thickness of 0.05 mm (2 mils).
Coatesville VAMC | Coatesville, PA
03-27-25
08 90 00 - 6
1. Paint interior surfaces of lightproof louvers with two (2) additional finish shop coats of baked-on flat black enamel.
2. Finish painting of exposed surfaces of shop primed louvers is specified in Section 09 91 00, PAINTING.
D. Steel: Surfaces of steel work, for which no other finish is specified, are to be cleaned free from scale, rust, oil, and grease, and then given a light-colored prime paint after fabrication, except ferrous metals concealed in finished work. Paint all contact surfaces of assembled work (except welded contact surfaces) with an additional shop coat of similar paint.
2.7 PROTECTION:
A. Provide protection for aluminum against galvanic action wherever dissimilar materials are in contact, by painting the contact surfaces of the dissimilar material with a heavy coat of bituminous coating
(complete coverage), or by separating the contact surfaces with a performed synthetic rubber tape having pressure sensitive adhesive coating on one side.
B. Isolate the aluminum from plaster, concrete and masonry by coating aluminum with zinc-chromate primer.
C. Protect finished surfaces from damage during fabrication, erection, and after completion of the work. Strippable plastic coating on colored anodized finish is not approved.
PART 3 - EXECUTION
3.1 INSTALLATION:
A. Set work accurately, in alignment and where indicated in construction documents. Install plumb, level, free of rack and twist, and set parallel or perpendicular as required to line and plane of surface.
B. Furnish setting drawings and instructions for installation of anchors and for the positioning of items having anchors to be built into masonry construction. Provide temporary bracing for such items until masonry is set.
C. Provide anchoring devices and fasteners as shown and as necessary for securing louvers and vent to building construction as specified. Power actuated drive pins may be used, except for removal items and where members would be deformed or substrate damaged by their use.
D. Set wall louvers and vent in masonry walls during progress of the work.
If wall louvers and vents are not delivered to job in time for
Coatesville VAMC | Coatesville, PA
03-27-25
08 90 00 - 7 installation in prepared openings, make provision for later installation. Set in cast-in-place concrete in prepared openings.
3.2 CLEANING AND ADJUSTING:
A. After installation, all exposed prefinished and plated items and all items fabricated from stainless steel and aluminum are to be cleaned as recommended by the manufacturer and protected from damage until completion of the project.
B. All movable parts, including hardware, are to be cleaned and adjusted to operate as designed without binding or deformation of the members, so as to be centered in the opening of frame, and where applicable, to have all contact surfaces fit tight and even without forcing or warping the components.
C. Restore louvers and vents damaged during installation and construction so no evidence remains of corrective work. If results of restoration are unsuccessful, as determined by Contracting Officer
Representative (COR) damaged units and replace with new units.
- - - E N D - - -
| SECTION 08 90 00 LOUVERS AND VENTS |
| PART 1 - GENERAL |
| 1.1 DESCRIPTION |
| 1.2 SUBMITTALS |
| 1.3 APPLICABLE PUBLICATIONS: |
| PART 2 - PRODUCTS |
| 2.1 MATERIALS: |
| 2.2 EXTERIOR WALL LOUVERS: |
| 2.3 CLOSURE ANGLES AND CLOSURE PLATES: |
| 2.4 WIRE GUARDS: |
| 2.5 EXTERIOR DOOR LOUVERS: |
| 2.6 FINISH: |
| 2.7 PROTECTION: |
| PART 3 - EXECUTION |
| 3.1 INSTALLATION: |
| 3.2 CLEANING AND ADJUSTING: |
File details come from the government source that posted it. Updated .