512-23121.JLM Chesterfield - Sidock - Elec Specs.pdf

PDF 573 KB Posted

Attached to
512/23121. JLM; Chesterfield Vet. Home - Maint. Bldg. & Whs.
Solicitation number
RFQ - 171 - 240000000127
Issued by
Macomb County, Chesaning Village, Michigan

About this file

This document contains specifications for a low-voltage electrical power conductors and cables section of the contract for the DTMB Chesterfield Veterans Home Maintenance Building project in Macomb County, Michigan and Chesaning Village, Michigan. The specifications cover requirements for conduit, cable, and wiring systems, including types of conduit, cables, fittings, and accessories to be used. Key details include approved materials and applications, conductor and cable requirements, grounding and bonding, support and attachment methods, and installation procedures. The contract opportunity also includes additional specifications for other electrical work such as grounding and bonding, hangers and supports, boxes, and identification. Bid submissions must be uploaded to the SIGMA VSS system, with questions directed to the project contact. The project location is in Macomb County, Michigan and Chesaning Village, Michigan.

Pricing terms, set-asides, incumbents, funding sources, and other commercial details are not provided in the specifications document. The document focuses on the technical requirements for the electrical work to be performed as part of the overall DTMB Chesterfield Veterans Home Maintenance Building project.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DTMB Chesterfield Veterans Home Maintenance Building

260519 - 1 Low-Voltage Electrical Power

Conductors and Cables

SECTION 260519

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 GENERAL

1.01 SUBMITTALS

A. Product Data: Provide manufacturer's standard catalog pages and data sheets for conductors and cables, including detailed information on materials, construction, ratings, listings, and available sizes, configurations, and stranding.

B. Manufactured Wiring System Shop Drawings: Provide plan views indicating proposed system layout with components identified; indicate branch circuit connections.

C. Field Quality Control Test Reports.

1.02 QUALITY ASSURANCE

A. Comply with requirements of NFPA 70.

PART 2 PRODUCTS

2.01 CONDUCTOR AND CABLE APPLICATIONS

A. Do not use conductors and cables for applications other than as permitted by NFPA 70 and product listing.

B. Provide single conductor building wire installed in suitable raceway unless otherwise indicated, permitted, or required.

1. Exceptions:

a. Use manufactured wiring systems for branch circuits where concealed above accessible ceilings for lighting .

1) Exception: Provide single conductor building wire in raceway for circuit homerun from distribution box to panelboard.

C. Nonmetallic-sheathed cable is not permitted.

D. Underground feeder and branch-circuit cable is permitted only as follows:

1. Where not otherwise restricted, may be used:

a. For damp, wet, or corrosive locations as a substitute for NFPA 70, Type NMC nonmetallic-sheathed cable, when nonmetallic-sheathed cable is permitted.

2. In addition to other applicable restrictions, may not be used:

a. Where exposed to damage.

E. Service entrance cable is permitted only as follows:

1. Where not otherwise restricted, may be used:

a. For underground service entrance, installed in raceway.

2. In addition to other applicable restrictions, may not be used:

a. Where exposed to damage.

F. Armored cable is not permitted.

G. Metal-clad cable is permitted only as follows:

1. Where not otherwise restricted, may be used:

a. Where concealed above accessible ceilings for final connections from junction boxes to luminaires.

1) Maximum Length: 6 feet (1.8 m).

b. Where concealed in hollow stud walls, above accessible ceilings, and under raised floors for branch circuits up to 20 A.

1) Exception: Provide single conductor building wire in raceway for circuit homerun from first outlet to panelboard.

2. In addition to other applicable restrictions, may not be used:

a. Where not approved for use by the authority having jurisdiction.

b. Where exposed to view , except in dedicated electrical, communications, and mechanical rooms where not subject to damage .

c. Where exposed to damage.

260519 - 2 Low-Voltage Electrical Power

Conductors and Cables

d. For damp, wet, or corrosive locations, unless provided with a PVC jacket listed as suitable for those locations.

e. For isolated ground circuits, unless provided with an additional isolated/insulated grounding conductor.

H. Manufactured wiring systems are permitted only as follows:

1. Where not otherwise restricted, may be used:

a. For branch circuits where concealed under raised floors, where concealed above accessible ceilings for lighting, and in open ceiling areas for lighting.

1) Exception: Provide single conductor building wire in raceway for circuit homerun from distribution box to panelboard.

2. In addition to other applicable restrictions, may not be used:

a. Where not approved for use by the authority having jurisdiction.

b. Where exposed to damage.

c. For damp, wet, or corrosive locations.

2.02 CONDUCTOR AND CABLE GENERAL REQUIREMENTS

A. Provide products that comply with requirements of NFPA 70.

B. Provide products listed, classified, and labeled as suitable for the purpose intended.

C. Unless specifically indicated to be excluded, provide all required conduit, boxes, wiring, connectors, etc. as required for a complete operating system.

D. Comply with NEMA WC 70.

E. Thermoplastic-Insulated Conductors and Cables: Listed and labeled as complying with UL 83.

F. Thermoset-Insulated Conductors and Cables: Listed and labeled as complying with UL 44.

G. Conductors for Grounding and Bonding: Also comply with Section 260526.

H. Conductors and Cables Installed Where Exposed to Direct Rays of Sun: Listed and labeled as sunlight resistant.

I. Conductor Material:

1. Provide copper conductors only. Aluminum conductors are not acceptable for this project.

Conductor sizes indicated are based on copper.

2. Copper Conductors: Soft drawn annealed, 98 percent conductivity, uncoated copper conductors complying with ASTM B3, ASTM B8, or ASTM B787/B787M unless otherwise indicated.

3. Tinned Copper Conductors: Comply with ASTM B33.

J. Minimum Conductor Size:

1. Branch Circuits: 12 AWG.

a. Exceptions:

1) 20 A, 120 V circuits longer than 75 feet (23 m): 10 AWG, for voltage drop.

2) 20 A, 120 V circuits longer than 150 feet (46 m): 8 AWG, for voltage drop.

3) 20 A, 277 V circuits longer than 150 feet (46 m): 10 AWG, for voltage drop.

2. Control Circuits: 14 AWG.

K. Where conductor size is not indicated, size to comply with NFPA 70 but not less than applicable minimum size requirements specified.

L. Conductor Color Coding:

1. Color code conductors as indicated unless otherwise required by the authority having jurisdiction. Maintain consistent color coding throughout project.

2. Color Coding Method: Integrally colored insulation.

3. Color Code:

a. 208Y/120 V, 3 Phase, 4 Wire System:

1) Phase A: Black.

2) Phase B: Red.

3) Phase C: Blue.

260519 - 3 Low-Voltage Electrical Power

Conductors and Cables

4) Neutral/Grounded: White.

b. Equipment Ground, All Systems: Green.

c. Isolated Ground, All Systems: Green with yellow stripe.

d. Travelers for 3-Way and 4-Way Switching: Pink.

e. For control circuits, comply with manufacturer's recommended color code.

2.03 SINGLE CONDUCTOR BUILDING WIRE

A. Description: Single conductor insulated wire.

B. Conductor Stranding:

1. Feeders and Branch Circuits:

a. Size 10 AWG and Smaller: Solid.

b. Size 8 AWG and Larger: Stranded.

2. Control Circuits: Stranded.

C. Insulation Voltage Rating: 600 V.

D. Insulation:

1. Copper Building Wire: Type THHN/THWN or THHN/THWN-2, except as indicated below.

a. Size 4 AWG and Larger: Type XHHW-2.

b. Installed Underground: Type XHHW-2.

c. Fixture Wiring Within Luminaires: Type TFFN/TFN for luminaires with labeled maximum temperature of 90 degrees C; Approved suitable type for luminaires with labeled maximum temperature greater than 90 degrees C.

2.04 UNDERGROUND FEEDER AND BRANCH-CIRCUIT CABLE

A. Description: NFPA 70, Type UF multiple-conductor cable listed and labeled as complying with UL 493, Type UF-B.

B. Provide equipment grounding conductor unless otherwise indicated.

C. Conductor Stranding:

1. Size 10 AWG and Smaller: Solid.

2. Size 8 AWG and Larger: Stranded.

D. Insulation Voltage Rating: 600 V.

2.05 SERVICE ENTRANCE CABLE

A. Service Entrance Cable for Underground Use: NFPA 70, Type USE single-conductor cable listed and labeled as complying with UL 854, Type USE-2, and with UL 44 Type RHH/RHW-2.

B. Conductor Stranding: Stranded.

C. Insulation Voltage Rating: 600 V.

2.06 METAL-CLAD CABLE

A. Description: NFPA 70, Type MC cable listed and labeled as complying with UL 1569, and listed for use in classified firestop systems to be used.

B. Conductor Stranding:

1. Size 10 AWG and Smaller: Solid.

2. Size 8 AWG and Larger: Stranded.

C. Insulation Voltage Rating: 600 V.

D. Insulation: Type THHN, THHN/THWN, or THHN/THWN-2.

E. Grounding: Full-size integral equipment grounding conductor.

1. Provide additional isolated/insulated grounding conductor where indicated or required.

F. Armor: Steel, interlocked tape.

G. Provide PVC jacket applied over cable armor where indicated or required for environment of installed location.

260519 - 4 Low-Voltage Electrical Power

Conductors and Cables

2.07 MANUFACTURED WIRING SYSTEMS

A. Description: Manufactured wiring assemblies complying with NFPA 70 Article 604, and listed and labeled as complying with UL 183.

B. Provide components necessary to transition between manufactured wiring system and other wiring methods.

C. Branch Circuit Cables:

1. Conductor Stranding (Size 10 AWG and Smaller): Solid.

2. Insulation Voltage Rating: 600 V.

3. Insulation: Type THHN.

4. Grounding: Full-size integral equipment grounding conductor.

5. Armor: Steel, interlocked tape.

D. Connectors: Keyed and color-coded to prevent interconnection of different voltages.

E. Fixture Leads: Type TFN insulation.

2.08 WIRING CONNECTORS

A. Description: Wiring connectors appropriate for the application, suitable for use with the conductors to be connected, and listed as complying with UL 486A-486B or UL 486C as applicable.

B. Connectors for Grounding and Bonding: Comply with Section 260526.

C. Wiring Connectors for Splices and Taps:

1. Copper Conductors Size 8 AWG and Smaller: Use twist-on insulated spring connectors.

2. Copper Conductors Size 6 AWG and Larger: Use mechanical connectors or compression connectors.

D. Wiring Connectors for Terminations:

1. Provide terminal lugs for connecting conductors to equipment furnished with terminations designed for terminal lugs.

2. Provide compression adapters for connecting conductors to equipment furnished with mechanical lugs when only compression connectors are specified.

3. Where over-sized conductors are larger than the equipment terminations can accommodate, provide connectors suitable for reducing to appropriate size, but not less than required for the rating of the overcurrent protective device.

4. Provide motor pigtail connectors for connecting motor leads in order to facilitate disconnection.

5. Copper Conductors Size 8 AWG and Larger: Use mechanical connectors or compression connectors where connectors are required.

6. Stranded Conductors Size 10 AWG and Smaller: Use crimped terminals for connections to terminal screws.

7. Conductors for Control Circuits: Use crimped terminals for all connections.

E. Do not use insulation-piercing or insulation-displacement connectors designed for use with conductors without stripping insulation.

F. Do not use push-in wire connectors as a substitute for twist-on insulated spring connectors.

G. Twist-on Insulated Spring Connectors: Rated 600 V, 221 degrees F (105 degrees C) for standard applications and 302 degrees F (150 degrees C) for high temperature applications;

pre-filled with sealant and listed as complying with UL 486D for damp and wet locations.

H. Mechanical Connectors: Provide bolted type or set-screw type.

I. Compression Connectors: Provide circumferential type or hex type crimp configuration.

J. Crimped Terminals: Nylon-insulated, with insulation grip and terminal configuration suitable for connection to be made.

2.09 ACCESSORIES

A. Electrical Tape:

260519 - 5 Low-Voltage Electrical Power

Conductors and Cables

1. Vinyl Color Coding Electrical Tape: Integrally colored to match color code indicated; listed as complying with UL 510; minimum thickness of 7 mil (0.18 mm); resistant to abrasion, corrosion, and sunlight; suitable for continuous temperature environment up to 221 degrees F (105 degrees C).

2. Vinyl Insulating Electrical Tape: Complying with ASTM D3005 and listed as complying with UL 510; minimum thickness of 7 mil (0.18 mm); resistant to abrasion, corrosion, and sunlight; conformable for application down to 0 degrees F (-18 degrees C) and suitable for continuous temperature environment up to 221 degrees F (105 degrees C).

3. Rubber Splicing Electrical Tape: Ethylene Propylene Rubber (EPR) tape, complying with ASTM D4388; minimum thickness of 30 mil (0.76 mm); suitable for continuous temperature environment up to 194 degrees F (90 degrees C) and short-term 266 degrees F (130 degrees C) overload service.

4. Electrical Filler Tape: Rubber-based insulating moldable putty, minimum thickness of 125 mil (3.2 mm); suitable for continuous temperature environment up to 176 degrees F (80 degrees C).

5. Varnished Cambric Electrical Tape: Cotton cambric fabric tape, with or without adhesive, oil-primed and coated with high-grade insulating varnish; minimum thickness of 7 mil (0.18 mm); suitable for continuous temperature environment up to 221 degrees F (105 degrees C).

6. Moisture Sealing Electrical Tape: Insulating mastic compound laminated to flexible, all-weather vinyl backing; minimum thickness of 90 mil (2.3 mm).

B. Heat Shrink Tubing: Heavy-wall, split-resistant, with factory-applied adhesive; rated 600 V;

suitable for direct burial applications; listed as complying with UL 486D.

C. Oxide Inhibiting Compound: Listed; suitable for use with the conductors or cables to be installed.

D. Wire Pulling Lubricant:

1. Listed and labeled as complying with UL 267.

2. Suitable for use with conductors/cables and associated insulation/jackets to be installed.

3. Suitable for use at installation temperature.

E. Cable Ties: Material and tensile strength rating suitable for application.

F. Sealing Systems for Roof Penetrations: Premanufactured components and accessories as required to preserve integrity of roofing system and maintain roof warranty; suitable for cables and roofing system to be installed; designed to accommodate existing penetrations where applicable.

1. Products:

a. Menzies Metal Products; Electrical Roof Stack and Cap: www.menzies-metal.com/#sle.

b. Menzies Metal Products; Electrical Retro Box: www.menzies-metal.com/#sle.

c. Substitutions: See Section 016000 - Product Requirements.

G. Firestop Sleeves: Listed; provide as required to preserve fire resistance rating of building elements.

PART 3 EXECUTION

3.01 INSTALLATION

A. Circuiting Requirements:

1. Include circuit lengths required to install connected devices within 10 ft (3.0 m) of location indicated.

2. Maintain separation of Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits in accordance with NFPA 70.

3. Maintain separation of wiring for emergency systems in accordance with NFPA 70.

4. Circuiting Adjustments: Unless otherwise indicated, when branch circuits are indicated as separate, combining them together in a single raceway is permitted, under the following conditions:

260519 - 6 Low-Voltage Electrical Power

Conductors and Cables

a. Provide no more than six current-carrying conductors in a single raceway. Dedicated neutral conductors are considered current-carrying conductors.

b. Increase size of conductors as required to account for ampacity derating.

c. Size raceways, boxes, etc. to accommodate conductors.

5. Common Neutrals: Unless otherwise indicated, sharing of neutral/grounded conductors among up to three single phase branch circuits of different phases installed in the same raceway is not permitted. Provide dedicated neutral/grounded conductor for each individual branch circuit.

B. Install products in accordance with manufacturer's instructions.

C. Perform work in accordance with NECA 1 (general workmanship).

D. Install underground feeder and branch-circuit cable (Type UF-B) in accordance with NECA 121.

E. Install metal-clad cable (Type MC) in accordance with NECA 120.

F. Direct Burial Cable Installation:

1. Provide trenching and backfilling in accordance with Section 312316 - Excavation and

Section 312323 - Fill.

2. Install cable with minimum cover of 24 inches (610 mm) unless otherwise indicated or required.

G. Secure and support conductors and cables in accordance with NFPA 70 using suitable supports and methods approved by the authority having jurisdiction. Provide independent support from building structure. Do not provide support from raceways, piping, ductwork, or other systems.

1. Installation Above Suspended Ceilings: Do not provide support from ceiling support system. Do not provide support from ceiling grid or allow conductors and cables to lay on ceiling tiles.

H. Terminate cables using suitable fittings.

I. Install conductors with a minimum of 12 inches (300 mm) of slack at each outlet.

J. Where conductors are installed in enclosures for future termination by others, provide a minimum of 5 feet (1.5 m) of slack.

K. Make wiring connections using specified wiring connectors.

L. Insulate splices and taps that are made with uninsulated connectors using methods suitable for the application, with insulation and mechanical strength at least equivalent to unspliced conductors.

M. Install firestopping to preserve fire resistance rating of partitions and other elements, using materials and methods specified in Section 078400.

N. Unless specifically indicated to be excluded, provide final connections to all equipment and devices, including those furnished by others, as required for a complete operating system.

END OF SECTION

260526 - 1 Grounding and Bonding for

Electrical Systems

SECTION 260526

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 GENERAL

1.01 SUBMITTALS

A. Product Data: Provide manufacturer's standard catalog pages and data sheets for grounding and bonding system components.

B. Shop Drawings:

1. Indicate proposed arrangement for signal reference grids. Include locations of items to be bonded and methods of connection.

C. Field quality control test reports.

D. Project Record Documents: Record actual locations of grounding electrode system components and connections.

1.02 QUALITY ASSURANCE

A. Comply with requirements of NFPA 70.

PART 2 PRODUCTS

2.01 GROUNDING AND BONDING REQUIREMENTS

A. Do not use products for applications other than as permitted by NFPA 70 and product listing.

B. Unless specifically indicated to be excluded, provide all required components, conductors, connectors, conduit, boxes, fittings, supports, accessories, etc. as necessary for a complete grounding and bonding system.

C. Where conductor size is not indicated, size to comply with NFPA 70 but not less than applicable minimum size requirements specified.

D. Grounding System Resistance:

1. Achieve specified grounding system resistance under normally dry conditions unless otherwise approved by Architect. Precipitation within the previous 48 hours does not constitute normally dry conditions.

2. Grounding Electrode System: Not greater than 5 ohms to ground, when tested according to IEEE 81 using "fall-of-potential" method.

3. Between Grounding Electrode System and Major Electrical Equipment Frames, System Neutral, and Derived Neutral Points: Not greater than 0.5 ohms, when tested using "point-to-point" methods.

E. Grounding Electrode System:

1. Provide connection to required and supplemental grounding electrodes indicated to form grounding electrode system.

a. Provide continuous grounding electrode conductors without splice or joint.

b. Install grounding electrode conductors in raceway where exposed to physical damage. Bond grounding electrode conductor to metallic raceways at each end with bonding jumper.

2. Metal Underground Water Pipe(s):

a. Provide connection to underground metal domestic and fire protection (where present) water service pipe(s) that are in direct contact with earth for at least 10 feet (3.0 m) at an accessible location not more than 5 feet (1.5 m) from the point of entrance to the building.

b. Provide bonding jumper(s) around insulating joints/pipes as required to make pipe electrically continuous.

c. Provide bonding jumper around water meter of sufficient length to permit removal of meter without disconnecting jumper.

3. Concrete-Encased Electrode:

a. Provide connection to concrete-encased electrode consisting of not less than 20 feet

(6.0 m) of either steel reinforcing bars or bare copper conductor not smaller than 4

260526 - 2 Grounding and Bonding for

Electrical Systems

AWG embedded within concrete foundation or footing that is in direct contact with earth in accordance with NFPA 70.

4. Ground Rod Electrode(s):

a. Provide three electrodes in an equilateral triangle configuration unless otherwise indicated or required.

b. Space electrodes not less than 10 feet (3.0 m) from each other and any other ground electrode.

c. Where location is not indicated, locate electrode(s) at least 5 feet (1.5 m) outside building perimeter foundation as near as possible to electrical service entrance;

where possible, locate in softscape (uncovered) area.

d. Provide ground access well for each electrode.

5. Provide additional ground electrode(s) as required to achieve specified grounding electrode system resistance.

6. Ground Bar: Provide ground bar, separate from service equipment enclosure, for common connection point of grounding electrode system bonding jumpers as permitted in NFPA 70. Connect grounding electrode conductor provided for service-supplied system grounding to this ground bar.

a. Ground Bar Size: 1/4 by 2 by 12 inches (6 by 50 by 300 mm) unless otherwise indicated or required.

b. Where ground bar location is not indicated, locate in accessible location as near as possible to service disconnect enclosure.

c. Ground Bar Mounting Height: 18 inches (450 mm) above finished floor unless otherwise indicated.

7. Ground Riser: Provide common grounding electrode conductor not less than 3/0 AWG for tap connections to multiple separately derived systems as permitted in NFPA 70.

F. Service-Supplied System Grounding:

1. For each service disconnect, provide grounding electrode conductor to connect neutral

(grounded) service conductor to grounding electrode system. Unless otherwise indicated, make connection at neutral (grounded) bus in service disconnect enclosure.

2. For each service disconnect, provide main bonding jumper to connect neutral (grounded) bus to equipment ground bus where not factory-installed. Do not make any other connections between neutral (grounded) conductors and ground on load side of service disconnect.

G. Grounding for Separate Building or Structure Supplied by Feeder(s) or Branch Circuits:

1. Provide grounding electrode system for each separate building or structure.

2. Provide equipment grounding conductor routed with supply conductors.

3. For each disconnecting means, provide grounding electrode conductor to connect equipment ground bus to grounding electrode system.

4. Do not make any connections and remove any factory-installed jumpers between neutral

(grounded) conductors and ground.

H. Separately Derived System Grounding:

1. Separately derived systems include, but are not limited to:

a. Transformers (except autotransformers such as buck-boost transformers).

b. Uninterruptible power supplies (UPS), when configured as separately derived systems.

c. Generators, when neutral is switched in the transfer switch.

2. Provide grounding electrode conductor to connect derived system grounded conductor to nearest effectively grounded metal building frame. Unless otherwise indicated, make connection at neutral (grounded) bus in source enclosure.

3. Provide bonding jumper to connect derived system grounded conductor to nearest metal building frame and nearest metal water piping in the area served by the derived system, where not already used as a grounding electrode for the derived system. Make connection at same location as grounding electrode conductor connection.

4. Outdoor Source: Where the source of the separately derived system is located outside the building or structure supplied, provide connection to grounding electrode at source in

260526 - 3 Grounding and Bonding for

Electrical Systems accordance with NFPA 70.

5. Provide system bonding jumper to connect system grounded conductor to equipment ground bus. Make connection at same location as grounding electrode conductor connection. Do not make any other connections between neutral (grounded) conductors and ground on load side of separately derived system disconnect.

6. Where the source and first disconnecting means are in separate enclosures, provide supply-side bonding jumper between source and first disconnecting means.

I. Bonding and Equipment Grounding:

1. Provide bonding for equipment grounding conductors, equipment ground busses, metallic equipment enclosures, metallic raceways and boxes, device grounding terminals, and other normally non-current-carrying conductive materials enclosing electrical conductors/equipment or likely to become energized as indicated and in accordance with

NFPA 70.

2. Provide insulated equipment grounding conductor in each feeder and branch circuit raceway. Do not use raceways as sole equipment grounding conductor.

3. Where circuit conductor sizes are increased for voltage drop, increase size of equipment grounding conductor proportionally in accordance with NFPA 70.

4. Unless otherwise indicated, connect wiring device grounding terminal to branch circuit equipment grounding conductor and to outlet box with bonding jumper.

5. Terminate branch circuit equipment grounding conductors on solidly bonded equipment ground bus only. Do not terminate on neutral (grounded) or isolated/insulated ground bus.

6. Provide bonding jumper across expansion or expansion/deflection fittings provided to accommodate conduit movement.

7. Provide bonding for interior metal piping systems in accordance with NFPA 70. This includes, but is not limited to:

a. Metal water piping where not already effectively bonded to metal underground water pipe used as grounding electrode.

8. Provide bonding for interior metal air ducts.

9. Provide bonding for metal building frame.

10. Provide bonding for metal siding not effectively bonded through attachment to metal building frame.

J. Communications Systems Grounding and Bonding:

1. Provide intersystem bonding termination at service equipment or metering equipment enclosure and at disconnecting means for any additional buildings or structures in accordance with NFPA 70.

2. Provide bonding jumper in raceway from intersystem bonding termination to each communications room or backboard and provide ground bar for termination.

a. Bonding Jumper Size: 6 AWG, unless otherwise indicated or required.

b. Raceway Size: 3/4 inch (21 mm) trade size unless otherwise indicated or required.

c. Ground Bar Size: 1/4 by 2 by 12 inches (6 by 50 by 300 mm) unless otherwise indicated or required.

d. Ground Bar Mounting Height: 18 inches (450 mm) above finished floor unless otherwise indicated.

K. Pole-Mounted Luminaires: Also comply with Section 265600.

2.02 GROUNDING AND BONDING COMPONENTS

A. General Requirements:

1. Provide products listed, classified, and labeled as suitable for the purpose intended.

2. Provide products listed and labeled as complying with UL 467 where applicable.

B. Conductors for Grounding and Bonding, in Addition to Requirements of Section 260526:

1. Use insulated copper conductors unless otherwise indicated.

a. Exceptions:

1) Use bare copper conductors where installed underground in direct contact with earth.

260526 - 4 Grounding and Bonding for

Electrical Systems

2) Use bare copper conductors where directly encased in concrete (not in raceway).

C. Connectors for Grounding and Bonding:

1. Description: Connectors appropriate for the application and suitable for the conductors and items to be connected; listed and labeled as complying with UL 467.

2. Unless otherwise indicated, use exothermic welded connections for underground, concealed and other inaccessible connections.

a. Exceptions:

1) Use mechanical connectors for connections to electrodes at ground access wells.

3. Unless otherwise indicated, use mechanical connectors, compression connectors, or exothermic welded connections for accessible connections.

a. Exceptions:

1) Use exothermic welded connections for connections to metal building frame.

D. Ground Bars:

1. Description: Copper rectangular ground bars with mounting brackets and insulators.

2. Size: As indicated.

3. Holes for Connections: As indicated or as required for connections to be made.

E. Ground Rod Electrodes:

1. Comply with NEMA GR 1.

2. Material: Copper-bonded (copper-clad) steel.

3. Size: 3/4 inch (19 mm) diameter by 10 feet (3.0 m) length, unless otherwise indicated.

F. Ground Plate Electrodes:

1. Material: Copper.

2. Size: 24 by 24 by 1/4 inches (610 by 610 by 6 mm), unless otherwise indicated.

G. Ground Access Wells:

1. Description: Open bottom round or rectangular well with access cover for testing and inspection; suitable for the expected load at the installed location.

2. Size: As required to provide adequate access for testing and inspection, but not less than minimum size requirements specified.

a. Rectangular Wells: Not less than 12 by 12 inches (300 by 300 mm).

3. Depth: As required to extend below frost line to prevent frost upheaval, but not less than 10 inches (250 mm).

4. Cover: Factory-identified by permanent means with word "GROUND".

H. Oxide Inhibiting Compound: Comply with Section 260519.

PART 3 EXECUTION

3.01 INSTALLATION

A. Install products in accordance with manufacturer's instructions.

B. Perform work in accordance with NECA 1 (general workmanship).

C. Ground Rod Electrodes: Unless otherwise indicated, install ground rod electrodes vertically.

Where encountered rock prohibits vertical installation, install at 45 degree angle or bury horizontally in trench at least 30 inches (750 mm) deep in accordance with NFPA 70 or provide ground plates.

1. Outdoor Installations: Unless otherwise indicated, install with top of rod 6 inches (150

mm) below finished grade.

2. Indoor Installations: Unless otherwise indicated, install with 4 inches (100 mm) of top of rod exposed.

D. Ground Plate Electrodes: Unless otherwise indicated, install ground plate electrodes at a depth of not less than 30 inches (750 mm).

E. Make grounding and bonding connections using specified connectors.

260526 - 5 Grounding and Bonding for

Electrical Systems

1. Remove nonconductive paint, enamel, or similar coating at threads, contact points, and contact surfaces.

260529 - 1 Hangers and Supports for

Electrical Systems

SECTION 260529

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Support and attachment requirements and components for equipment, conduit, cable, boxes, and other electrical work.

1.02 RELATED REQUIREMENTS

A. Section 033000 - Cast-in-Place Concrete: Concrete equipment pads.

B. Section 055000 - Metal Fabrications: Materials and requirements for fabricated metal supports.

C. Section 260533.13 - Conduit for Electrical Systems: Additional support and attachment requirements for conduits.

D. Section 260533.16 - Boxes for Electrical Systems: Additional support and attachment requirements for boxes.

E. Section 265100 - Interior Lighting: Additional support and attachment requirements for interior luminaires.

F. Section 265600 - Exterior Lighting: Additional support and attachment requirements for exterior luminaires.

G. Section 270529 - Hangers and Supports for Communications Systems.

1.03 REFERENCE STANDARDS

A. ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products 2017.

B. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware 2016a.

C. ASTM B633 - Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel 2023.

D. MFMA-4 - Metal Framing Standards Publication 2004.

E. NECA 1 - Standard for Good Workmanship in Electrical Construction 2015.

F. NFPA 70 - National Electrical Code Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.

G. NFPA 101 - Life Safety Code Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.

H. UL 5B - Strut-Type Channel Raceways and Fittings Current Edition, Including All Revisions.

1.04 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Coordinate sizes and arrangement of supports and bases with actual equipment and components to be installed.

2. Coordinate work to provide additional framing and materials required for installation.

3. Coordinate compatibility of support and attachment components with mounting surfaces at installed locations.

4. Coordinate arrangement of supports with ductwork, piping, equipment and other potential conflicts.

5. Notify Architect of conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.

B. Sequencing:

1. Do not install products on or provide attachment to concrete surfaces until concrete has cured; see Section 033000.

260529 - 2 Hangers and Supports for

Electrical Systems

1.05 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide manufacturer's standard catalog pages and data sheets for channel/strut framing systems, nonpenetrating rooftop supports, and post-installed concrete/masonry anchors.

C. Shop Drawings: Include details for fabricated hangers and supports where materials or methods other than those indicated are proposed for substitution.

D. Installer's qualification statement.

E. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.

1.06 QUALITY ASSURANCE

A. Maintain at project site one copy of each referenced document that prescribes execution requirements.

B. Installer Qualifications for Powder-Actuated Fasteners: Certified by fastener system manufacturer with current operator's license.

C. Installer Qualifications for Field Welding: See Section 055000.

D. Product Listing Organization Qualifications: Organization recognized by OSHA as Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.

1.07 DELIVERY, STORAGE, AND HANDLING

A. Receive, inspect, handle, and store products in accordance with manufacturer's instructions.

PART 2 PRODUCTS

2.01 SUPPORT AND ATTACHMENT COMPONENTS

A. General Requirements:

1. Comply with the following. Where requirements differ, comply with most stringent.

a. NFPA 70.

b. Requirements of authorities having jurisdiction.

2. Provide required hangers, supports, anchors, fasteners, fittings, accessories, and hardware as necessary for complete installation of electrical work.

3. Provide products listed, classified, and labeled as suitable for purpose intended, where applicable.

4. Where support and attachment component types and sizes are not indicated, select in accordance with manufacturer's application criteria as required for load to be supported .

Include consideration for vibration, equipment operation, and shock loads where applicable.

5. Do not use products for applications other than as permitted by NFPA 70 and product listing.

6. Do not use wire, chain, perforated pipe strap, or wood for permanent supports unless specifically indicated or permitted.

7. Steel Components: Use corrosion-resistant materials suitable for environment where installed.

a. Indoor Dry Locations: Use zinc-plated steel or approved equivalent unless otherwise indicated.

b. Outdoor and Damp or Wet Indoor Locations: Use galvanized steel, stainless steel, or approved equivalent unless otherwise indicated.

c. Zinc-Plated Steel: Electroplated in accordance with ASTM B633.

d. Galvanized Steel: Hot-dip galvanized after fabrication in accordance with ASTM

A123/A123M or ASTM A153/A153M.

B. Materials for Metal Fabricated Supports: See Section 055000.

C. Conduit and Cable Supports: Straps and clamps suitable for conduit or cable to be supported.

260529 - 3 Hangers and Supports for

Electrical Systems

1. Manufacturers:

a. ABB: www.electrification.us.abb.com/#sle.

b. Eaton Corporation: www.eaton.com/#sle.

c. Emerson Electric Co; O-Z/Gedney: www.emerson.com/#sle.

d. HoldRite, a brand of Reliance Worldwide Corporation: www.holdrite.com/#sle.

e. nVent; Caddy: www.nvent.com/#sle.

f. Substitutions: See Section 016000 - Product Requirements.

2. Conduit Straps: One-hole or two-hole type; steel or malleable iron.

3. Conduit Clamps: Bolted type unless otherwise indicated.

4. Products:

a. Gripple, Inc; Universal Bracket: www.gripple.com/#sle.

b. Gripple, Inc; Fast Trak: www.gripple.com/#sle.

c. Gripple, Inc; Universal Clamp (Threaded): www.gripple.com/#sle.

d. Gripple, Inc; Low Profile Bracket Kits: www.gripple.com/#sle.

e. Substitutions: See Section 016000 - Product Requirements.

D. Outlet Box Supports: Hangers and brackets suitable for boxes to be supported.

1. Manufacturers:

a. ABB: www.electrification.us.abb.com/#sle.

b. Eaton Corporation: www.eaton.com/#sle.

c. Emerson Electric Co; O-Z/Gedney: www.emerson.com/#sle.

d. HoldRite, a brand of Reliance Worldwide Corporation: www.holdrite.com/#sle.

e. nVent; Caddy: www.nvent.com/#sle.

f. Substitutions: See Section 016000 - Product Requirements.

E. Metal Channel/Strut Framing Systems:

1. Manufacturers:

a. ABB: www.electrification.us.abb.com/#sle.

b. Atkore International Inc; Unistrut: www.unistrut.us/#sle.

c. Custom Strut and Roll Forming, LLC; _____: www.customstrut.com/#sle.

d. Eaton Corporation: www.eaton.com/#sle.

e. Elgen Manufacturing Company, Inc; _____: www.elgenmfg.com/#sle.

f. Substitutions: See Section 016000 - Product Requirements.

g. Source Limitations: Furnish channel/strut and associated fittings, accessories, and hardware produced by single manufacturer.

2. Description: Factory-fabricated, continuous-slot, metal channel/strut and associated fittings, accessories, and hardware required for field assembly of supports.

3. Comply with MFMA-4.

4. Channel/Strut Used as Raceway, Where Indicated: Listed and labeled as complying with

UL 5B.

5. Channel Material:

a. Indoor Dry Locations: Use painted steel, zinc-plated steel, or galvanized steel.

b. Outdoor and Damp or Wet Indoor Locations: Use galvanized steel.

6. Minimum Channel Thickness: Steel sheet, 12 gauge, 0.1046 inch (2.66 mm).

7. Minimum Channel Dimensions: 1-5/8 inch (41 mm) wide by 13/16 inch (21 mm) high.

F. Hanger Rods: Threaded, zinc-plated steel unless otherwise indicated.

1. Minimum Size, Unless Otherwise Indicated or Required:

a. Equipment Supports: 1/2-inch (13 mm) diameter.

b. Busway Supports: 1/2-inch (13 mm) diameter.

c. Single Conduit up to 1-inch (27 mm) Trade Size: 1/4-inch (6 mm) diameter.

d. Single Conduit Larger than 1-inch (27 mm) Trade Size: 3/8-inch (10 mm) diameter.

e. Trapeze Support for Multiple Conduits: 3/8-inch (10 mm) diameter.

f. Outlet Boxes: 1/4-inch (6 mm) diameter.

g. Luminaires: 1/4-inch (6 mm) diameter.

G. Nonpenetrating Rooftop Supports for Low-Slope Roofs:

260529 - 4 Hangers and Supports for

Electrical Systems

1. Manufacturers:

a. Atkore International Inc; Unistrut: www.unistrut.us/#sle.

b. Eaton Corporation: www.eaton.com/#sle.

c. Green Link, Inc: www.greenlinkengineering.com/#sle.

d. nVent; Caddy: www.nvent.com/#sle.

e. PHP Systems/Design: www.phpsd.com/#sle.

f. Substitutions: See Section 016000 - Product Requirements.

2. Description: Steel pedestals with thermoplastic or rubber bases that rest on top of roofing membrane, not requiring attachment to roof structure and not penetrating roofing assembly, with support fixtures as specified.

3. Base Sizes: As required to distribute load sufficiently to prevent indentation of roofing assembly.

4. Attachment/Support Fixtures: As recommended by manufacturer, same type as indicated for equivalent indoor hangers and supports.

5. Mounting Height: Provide minimum clearance of 6 inches (150 mm) under supported component to top of roofing.

H. Anchors and Fasteners:

1. Manufacturers - Mechanical Anchors:

a. Dewalt: anchors.dewalt.com/#sle.

b. Hilti, Inc: www.hilti.com/#sle.

c. ITW Red Head, a division of Illinois Tool Works, Inc: www.itwredhead.com/#sle.

d. Simpson Strong-Tie Company Inc: www.strongtie.com/#sle.

e. Substitutions: See Section 016000 - Product Requirements.

2. Manufacturers - Powder-Actuated Fastening Systems:

a. Dewalt: anchors.dewalt.com/#sle.

b. Hilti, Inc: www.hilti.com/#sle.

c. ITW Ramset, a division of Illinois Tool Works, Inc: www.ramset.com/#sle.

d. Simpson Strong-Tie Company Inc: www.strongtie.com/#sle.

e. Substitutions: See Section 016000 - Product Requirements.

3. Unless otherwise indicated and where not otherwise restricted, use anchor and fastener types indicated for specified applications.

4. Concrete: Use preset concrete inserts, expansion anchors, or screw anchors.

5. Solid or Grout-Filled Masonry: Use expansion anchors or screw anchors.

6. Hollow Masonry: Use toggle bolts.

7. Hollow Stud Walls: Use toggle bolts.

8. Steel: Use beam clamps, machine bolts, or welded threaded studs.

9. Sheet Metal: Use sheet metal screws.

10. Wood: Use wood screws.

11. Plastic and lead anchors are not permitted.

12. Powder-actuated fasteners are not permitted.

a. Where approved by Architect.

b. Use only threaded studs; do not use pins.

13. Hammer-driven anchors and fasteners are not permitted.

a. Nails are permitted for attachment of nonmetallic boxes to wood frame construction.

14. Preset Concrete Inserts: Continuous metal channel/strut and spot inserts specifically designed to be cast in concrete ceilings, walls, and floors.

a. Manufacturer: Same as manufacturer of metal channel/strut framing system.

b. Comply with MFMA-4.

c. Channel Material: Use galvanized steel.

d. Minimum Channel Thickness: Steel sheet, 12 gauge, 0.1046 inch (2.66 mm) minimum base metal thickness.

15. Post-Installed Concrete and Masonry Anchors: Evaluated and recognized by ICC

Evaluation Service, LLC (ICC-ES) for compliance with applicable building code.

260529 - 5 Hangers and Supports for

Electrical Systems

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that field measurements are as indicated.

B. Verify that mounting surfaces are ready to receive support and attachment components.

C. Verify that conditions are satisfactory for installation prior to starting work.

3.02 INSTALLATION

A. Install products in accordance with manufacturer's instructions.

B. Install hangers and supports in accordance with NECA 1.

C. Install anchors and fasteners in accordance with ICC Evaluation Services, LLC (ICC-ES) evaluation report conditions of use where applicable.

D. Provide independent support from building structure. Do not provide support from piping, ductwork, or other systems.

E. Unless specifically indicated or approved by Architect, do not provide support from suspended ceiling support system or ceiling grid.

F. Unless specifically indicated or approved by Architect, do not provide support from roof deck.

G. Do not penetrate or otherwise notch or cut structural members without approval of Structural Engineer.

H. Field Welding, Where Approved by Architect: See Section 055000.

I. Equipment Support and Attachment:

1. Use metal, fabricated supports or supports assembled from metal channel/strut to support equipment as required.

2. Use metal channel/strut secured to studs to support equipment surface mounted on hollow stud walls when wall strength is not sufficient to resist pull-out.

3. Use metal channel/strut to support surface-mounted equipment in wet or damp locations to provide space between equipment and mounting surface.

4. Unless otherwise indicated, mount floor-mounted equipment on properly sized concrete pad 4 inches (100 mm) in height; see Section 033000 .

5. Securely fasten floor-mounted equipment. Do not install equipment such that it relies on its own weight for support.

J. Conduit Support and Attachment: See Section 260533.13 for additional requirements.

K. Box Support and Attachment: See Section 260533.16 for additional requirements.

L. Interior Luminaire Support and Attachment: See Section 265100 for additional requirements.

M. Exterior Luminaire Support and Attachment: See Section 265600 for additional requirements.

N. Preset Concrete Inserts: Use manufacturer provided closure strips to inhibit concrete seepage during concrete pour.

O. Secure fasteners in accordance with manufacturer's recommended torque settings.

P. Remove temporary supports.

Q. Identify independent electrical component support wires above accessible ceilings, where permitted, with color distinguishable from ceiling support wires in accordance with NFPA 70.

3.03 FIELD QUALITY CONTROL

A. See Section 014000 - Quality Requirements for additional requirements.

B. Inspect support and attachment components for damage and defects.

C. Repair cuts and abrasions in galvanized finishes using zinc-rich paint recommended by manufacturer. Replace components that exhibit signs of corrosion.

D. Correct deficiencies and replace damaged or defective support and attachment components.

260533.13 - 1 Conduit for Electrical Systems

SECTION 260533.13

CONDUIT FOR ELECTRICAL SYSTEMS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Galvanized steel rigid metal conduit (RMC).

B. PVC-coated galvanized steel rigid metal conduit (RMC).

C. Flexible metal conduit (FMC).

D. Liquidtight flexible metal conduit (LFMC).

E. Galvanized steel electrical metallic tubing (EMT).

F. Stainless steel electrical metallic tubing (EMT).

G. Rigid polyvinyl chloride (PVC) conduit.

H. Liquidtight flexible nonmetallic conduit (LFNC).

I. Reinforced thermosetting resin conduit (RTRC).

1.02 RELATED REQUIREMENTS

A. Section 033000 - Cast-in-Place Concrete: Concrete encasement of conduits.

B. Section 078400 - Firestopping.

C. Section 260519 - Low-Voltage Electrical Power Conductors and Cables: Cable assemblies consisting of conductors protected by integral metal armor.

D. Section 260526 - Grounding and Bonding for Electrical Systems.

1. Includes additional requirements for fittings for grounding and bonding.

E. Section 260529 - Hangers and Supports for Electrical Systems.

F. Section 260533.16 - Boxes for Electrical Systems.

G. Section 260533.23 - Surface Raceways for Electrical Systems.

H. Section 260553 - Identification for Electrical Systems: Identification products and requirements.

I. Section 262100 - Low-Voltage Electrical Service Entrance: Additional requirements for electrical service conduits.

J. Section 270533.13 - Conduit for Communications Systems.

K. Section 312316 - Excavation.

L. Section 312316.13 - Trenching: Excavating, bedding, and backfilling.

M. Section 312323 - Fill: Bedding and backfilling.

1.03 REFERENCE STANDARDS

A. ANSI C80.1 - American National Standard for Electrical Rigid Steel Conduit (ERSC) 2020.

B. ANSI C80.3 - American National Standard for Electrical Metallic Tubing -- Steel (EMT-S) 2020.

C. ANSI C80.6 - American National Standard for Electrical Intermediate Metal Conduit 2018.

D. NECA 1 - Standard for Good Workmanship in Electrical Construction 2015.

E. NECA 101 - Standard for Installing Steel Conduits (Rigid, IMC, EMT) 2020.

F. NECA 111 - Standard for Installing Nonmetallic Raceways (RNC, ENT, LFNC) 2017.

G. NEMA FB 1 - Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable 2014.

H. NEMA RN 1 - Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Metal Conduit and Intermediate Metal Conduit 2018.

I. NEMA TC 2 - Electrical Polyvinyl Chloride (PVC) Conduit 2020.

260533.13 - 2 Conduit for Electrical Systems

J. NEMA TC 3 - Polyvinyl Chloride (PVC) Fittings for Use with Rigid PVC Conduit and Tubing 2021.

K. NEMA TC 14 (SERIES) - Reinforced Thermosetting Resin Conduit and Fittings Series 2015.

L. NEMA TC 14.AG - Aboveground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings 2015 (Reaffirmed 2021).

M. NEMA TC 14.BG - Belowground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings 2015 (Reaffirmed 2020).

N. NEMA TC 14.XW - Extra Heavy Wall Aboveground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings 2015 (Reaffirmed 2021).

O. NFPA 70 - National Electrical Code Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.

P. UL 1 - Flexible Metal Conduit Current Edition, Including All Revisions.

Q. UL 6 - Electrical Rigid Metal Conduit-Steel Current Edition, Including All Revisions.

R. UL 360 - Liquid-Tight Flexible Metal Conduit Current Edition, Including All Revisions.

S. UL 514A - Metallic Outlet Boxes Current Edition, Including All Revisions.

T. UL 514B - Conduit, Tubing, and Cable Fittings Current Edition, Including All Revisions.

U. UL 651 - Schedule 40, 80, Type EB and A Rigid PVC Conduit and Fittings Current Edition, Including All Revisions.

V. UL 746C - Polymeric Materials – Use in Electrical Equipment Evaluations Current Edition, Including All Revisions.

W. UL 797 - Electrical Metallic Tubing-Steel Current Edition, Including All Revisions.

X. UL 797A - Electrical Metallic Tubing - Aluminum and Stainless Steel Current Edition, Including All Revisions.

Y. UL 1203 - Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations Current Edition, Including All Revisions.

Z. UL 1242 - Electrical Intermediate Metal Conduit-Steel Current Edition, Including All Revisions.

AA. UL 1653 - Electrical Nonmetallic Tubing Current Edition, Including All Revisions.

BB. UL 1660 - Liquid-Tight Flexible Nonmetallic Conduit Current Edition, Including All Revisions.

CC. UL 2419 - Outline of Investigation for Electrically Conductive Corrosion Resistant Compounds Current Edition, Including All Revisions.

DD. UL 2420 - Belowground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings Current Edition, Including All Revisions.

EE. UL 2515 - Aboveground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings Current Edition, Including All Revisions.

FF. UL 2515A - Standard for Supplemental Requirements for Extra Heavy Wall Reinforced Thermosetting Resin Conduit (RTRC) and Fittings Current Edition, Including All Revisions.

1.04 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Coordinate minimum sizes of conduits with actual type and quantity of conductors to be installed, including adjustments for conductor sizes increased for voltage drop.

2. Coordinate arrangement of conduits with structural members, ductwork, piping, equipment, and other potential conflicts.

3. Verify exact conduit termination locations required for boxes, enclosures, and equipment.

4. Coordinate work to provide roof penetrations that preserve integrity of roofing system and do not void roof warranty.

5. Notify Architect of conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.

260533.13 - 3 Conduit for Electrical Systems

B. Sequencing:

1. Do not begin installation of conductors and cables until installation of conduit between termination points is complete.

1.05 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittals procedures.

B. Product Data: Provide manufacturer's standard catalog pages and data sheets for conduits and fittings.

C. Shop Drawings:

1. Indicate proposed arrangement for conduits to be installed within structural concrete slabs, where…