511.22033.JBB DMVA Renovate Kingsford Armory- Asbestos & Lead Survey Report.pdf
PDF 7 MB Posted
- Attached to
- 511/22033. JBB; Renovate Kingsford Armory
- Solicitation number
- RFQ-171-250000000572-2
- Issued by
- Delta County, Kincheloe CDP, Michigan
About this file
This document is an Asbestos Survey and Lead-Based Paint Sampling Report prepared by U.P. Engineers & Architects, Inc. for the Kingsford Armory Renovations located at 401 S. Carpenter Ave. in Kingsford, Michigan. The survey was conducted on April 3rd, 2025, by Sam Genter, a State of Michigan licensed Asbestos Building Inspector and Lead Inspector, to identify asbestos-containing materials (ACM), presumed asbestos-containing materials (PACM), and lead-based paint in areas planned for renovation. The investigation involved a comprehensive building walkthrough, identification of suspect materials, collection and analysis of 28 bulk samples comprising 38 layers of suspect ACM, and 11 paint samples for lead and cadmium content.
The survey revealed several areas with regulated asbestos-containing and lead-containing materials. Asbestos was detected in pipe insulation on multiple floors, including the hallway, weight room, supply room, conference room, and attic, with materials ranging from beige and gray pipe insulation to black bituminous tar under the drill floor. Lead-based paint was found on the side of an exterior door in the kitchen (53,200 mg/kg) and on the shooting range wall (22,600 mg/kg), both significantly exceeding the federal lead paint statute limit of 5,000 mg/kg. The report emphasizes the need for proper handling and disposal of ACM and PACM by trained personnel, with recommendations for careful management during the planned renovations to ensure worker and environmental safety.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KINGSFORD ARMORY RENOVATIONS
401 S. CARPENTER AVE.
KINGSFORD, MI 49938
ASBESTOS SURVEY & LEAD
BASED PAINT
SAMPLING REPORT
Prepared for:
Kingsford Armory 401 S. Carpenter Ave.
Kingsford, MI 49802
Prepared By:
U.P. ENGINEERS & ARCHITECTS, INC.
100 Portage Street Houghton, Michigan 49931
April 2025
TABLE OF CONTENTS
Page
I. PURPOSE AND SCOPE
II. ASBESTOS CONTAINING MATERIAL SURVEY
III. LEAD CONTAINING PAINT SAMPLING
IV. CONCLUSIONS AND RECOMMENDATION
V. LIMITATIONS
VI. SIGNATURE OF CERTIFIED INSPECTOR………………………………………………….4
LIST OF APPENDICES
APPENDIX A INSPECTOR ACCREDITATION
APPENDIX B BUILDING FLOOR PLANS
APPENDIX C ANALYTICAL RESULTS - ASBESTOS
APPENDIX D ANALYTICAL RESULTS – LEAD & CADMIUM CONTAINING PAINT
APPENDIX E LABORATORY ACCREDITATION
1 UPEA
I. PURPOSE AND SCOPE
The purpose of this project was to conduct an asbestos survey and lead containing paint sampling for the sections of the Kingsford Armory that are going to be renovated. The survey and sampling will identify asbestos containing material (ACM), presumed ACM (PACM), and lead and cadmium containing paint throughout the planned renovation areas. This survey occurred in preparation for the planned renovations for the armory.
The survey and sampling data should be referred to by staff and personnel during demolition operations. Material or items not comprised of ACM or PACM may be removed, repaired, or replaced by general maintenance staff or contractors. However, ACM or PACM items must be handled and disposed of by properly trained personnel.
Lead containing paint may be disposed of as demolition debris if the proper procedures are followed.
The scope of this project includes:
1. Building walk through
2. Identification of suspect ACM and LBP
3. Collection and analysis of bulk samples of suspect ACM
4. Collection of suspect Lead Containing Paint Samples
5. Quantification of ACM and PACM
6. Assess current condition of ACM and PACM and identify the potential for disturbance of ACM and PACM.
II. ASBESTOS CONTAINING MATERIAL SURVEY
An asbestos survey was conducted for parts of the Kingsford Armory in anticipation of planned renovations. The asbestos survey was performed by Sam Genter, a State of Michigan accredited Asbestos Building Inspector (License # A63169) on April 3rd, 2025.
The asbestos survey consisted of five phases: 1) conduct a visual inspection of the building; 2) identify homogeneous areas; 3) collect samples of suspect ACM from different homogeneous areas; 4) quantify ACM and PACM; 5) assess current conditions of sampled suspect ACM and the potential for disturbance of the ACM identified.
Prior to collecting any samples, a sampling strategy was developed based on the layout of the building and the construction periods associated with each section of the building.
Locations were sampled based on the location of the planned demolition and associated renovation. Based on the sampling strategy, the building was divided into different homogeneous areas, from which samples would be collected. A homogeneous area can be described as one or more areas of material that are similar in appearance and that have the same construction/installation date and function. Bulk samples of identified suspect asbestos containing material (ACM) were collected in individual containers and sent to a National Voluntary Lab Accreditation Program (NVLAP)/American Industrial Hygiene Association (AIHA) accredited laboratory for analysis. The number of samples collected from each homogeneous area may vary depending on the professional judgment of the inspector and the type of material present.
Twenty-eight (28) samples consisting of thirty-eight (38) layers of suspect ACM were collected from the areas of the armory that are planned to be renovated and analyzed by Polarized Light Microscopy (PLM). Table 1 shows any confirmed ACMs. Table 3
2 UPEA
presents the sample analysis results. The confirmed ACMs are reported in bold text.
Appendix B contains a copy of the building floor plans and the location of samples.
Copies of the analytical results are included in Appendix C. Appendix E contains a copy of the laboratory accreditation.
These asbestos surveys were completed with limited destructive testing. Therefore, hidden materials may be discovered in walls or ceiling that contain asbestos. If such materials are encountered, all work shall stop immediately until proper testing is conducted to determine the content of the material.
TABLE 1
CONFIRMED ASBESTOS CONTAINING MATERIALS
FLOOR LOCATION MATERIAL EST
QUANTITY
FRIABLE
2 Hallway Beige Pipe Insulation
(Exterior is white)
10 LF Y
Drill Floor (under floorboards) Black, Bituminous Tar 3,200 SF N
Weight Room
Adjacent to Drill Floor
Gray Pipe Insulation 20 LF Y
0 Supply Room Thin Pipe Elbow
Insulation
30 LF Y
Club Conference
Room Thick Pipe Insulation 20 LF Y
Attic Attic Gray Pipe Elbow
Insulation
25 LF Y
III. LEAD CONTAINING PAINT SAMPLING
Eleven (11) paint samples of suspect lead and cadmium containing paint from the areas planned to be renovated in the Kingsford Armory were collected by Sam Genter, a State of Michigan licensed lead Inspector (License # P-009865) on April 3rd, 2025 and submitted for analysis by an accredited laboratory. Table 2 shows any confirmed lead-based or cadmium containing paint. Table 4 presents the sample analysis results. The confirmed lead-containing paint samples are reported in bold text. Copies of the lead analytical results are included in Appendix D.
TABLE 2
CONFIRMED LEAD & CADMIUM CONTAINING MATERIALS
FLOOR LOCATION COLOR LEAD CONC.
1 Side of Exterior
Door – Kitchen Green 53,200 mg/kg
0 Shooting Range Wall
White 22,600 mg/kg
3 UPEA
IV. CONCLUSIONS AND RECOMMENDATIONS
Asbestos:
The results of the asbestos survey conducted on 4/3/2025 for the areas of the Kingsford Armory planned to be renovated at 401 S. Carpenter Ave. in Kingsford, MI indicate that the building DOES contain regulated asbestos containing materials.
Basement:
The thin pipe elbow insulation in the supply room adjacent to the shooting range contained asbestos fibers. This thin insulation, along with any encountered similar insulation, should be treated as ACM. The thicker pipe insulation in the ceiling above the conference room tested positive for asbestos fibers. This pipe wrap, along with any encountered similar insulation, should be treated as ACM.
1st Floor:
The black, bituminous tar under the hardwood in the drill floor contained asbestos fibers.
The pipe insulation in the corner of the weight room, adjacent to the drill floor, also tested positive for asbestos fibers. Anywhere this type of insulation is encountered, the insulation should be treated as ACM.
2nd Floor:
The hallway in the second floor had exposed pipe insulation near the ceiling that had been painted white. A core of this material tested positive for asbestos containing fibers.
This and similar pipe insulation should be treated as ACM.
Attic:
The gray/brown pipe elbow insulation contained asbestos fibers. All similar pipe insulation should be treated as asbestos containing material.
Material or items not comprised of ACM or PACM may be removed, repaired, or replaced by general maintenance staff or contractors. However, ACM or PACM items must be handled and disposed of by properly trained personnel. Subcontractors and employees working in the building should be instructed to report any hidden suspect ACM immediately upon discovery.
Lead-Containing Paint:
The results of the lead-containing paint sampling conducted on 4/3/2025 for the areas of the Kingsford Armory planned to be renovated at 401 S. Carpenter Ave. in Kingsford, MI indicate that the areas planned for renovation DO contain regulated lead-containing or cadmium-containing paint. The kitchen on the first floor has an exterior door on the west side, painted white, with deteriorating paint that had lead levels above the regulatory limit. The shooting range wall in the basement was mostly intact but tested positive for lead at a concentration above regulatory limits.
V. LIMITATIONS
Identification and testing of PACM was conducted by a trained professional licensed in the State of Michigan. Professional judgment was used in the selection of materials to be tested and the number of samples of each homogeneous material tested.
4 UPEA
This report documents testing of ACM or PACM based on sampling strategies and priorities as described herein, and on the dates and at locations identified in this report.
Modifications to the building or its interior through renovations, remodeling, building additions or changes to fixtures, facilities or furnishings that occur subsequent to the date of this report may add or remove ACM or PACM not identified in this report.
This report was completed to aid the building Owner, general contractors, and potential asbestos abatement contractors in locating ACM. Under no circumstances should this report be utilized as a bidding document or as a project specification document.
VI. SIGNATURE OF CERTIFIED INSPECTOR
4/15/2025 Sam Genter, Asbestos Inspector (#A63169) Date Lead Inspector (#P-009865)
Second Floor Hallway Pipe InsulaƟon (ACM)
Kingsford Armory Planned RenovaƟons
Kitchen Side Of Exterior Door
(LBP)
Thin Pipe Elbow in Supply Room (ACM)
Thick Pipe Wrap Above Club Con-ference Room (ACM)
APPENDIX A
INSPECTOR ACCREDITATION
2 UPEA
APPENDIX B
BUILDING FLOOR PLANS
& SAMPLE LOCATIONS
UP
9' - 6"
3 13/16"1' - 0"
13' - 1"
VAULT
EXTG
SIM
9' - 11"
UNEXCAVATED
EXTG
LOCKER
S301
S301
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R E I S
P E N I N S U L A M
A M
OE
N A
M
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
PR
EL
IM
IN
AR
Y
C O
N
ST
R U
C
TI
O N
FI
N
AL
R
EC
O
R D
D
AT
E
IS
SU
ED
F O
R
IN
D
EX
C
O D
E
D M
VA
P
R O
JE
C
T #2
6B
ID
EN
TI
FI
C
AT
IO
N
N O
SH
EE
T
DE
SI
GN
ED
DR
AW
N
CH
EC
KE
D
AP
PR
OV
ED
ST
AT
E O
F M
IC
H
IG
AN
D
EP
AR
TM
EN
T
O F
TE
C
H N
O
LO
G Y, M
AN
AG
EM
EN
T
AN
D
B U
D G
ET
FA
C
IL
IT
IE
S
AN
D B
U
SI
N
ES
S
SE
R
VI
C
ES
A D
M
IN
IS
TR
AT
IO
N
AD
AM
L
AC
H , R
A, D
IR
EC
TO
R w w w .u pe a.
co m
UP
EA
P
RO
JE
CT
KI
N
G
SF
O R
D , M
IC
H
IG
AN
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
D
TM
B
FI
LE
/2
.J
BB
4-
-2
BA
SE
ME
NT
EX
IST
IN
G
PL
AN
TE
ST
IN
G
AT
M1 2-0
R
EN
O
VA
TE
K
IN
G
SF
O
R D
A R
M O
R Y
JH
R
JH
R
C he ck er
A pp ro ve r
1/8" = 1'-0"1 EXISTING BASEMENT PLAN
N
Sam Genter Text Box A19, A20
Sam Genter Text Box L8
Sam Genter Text Box L9
Sam Genter Text Box A21, A22
Sam Genter Text Box L11
Sam Genter Text Box A24
Sam Genter Text Box A23
Sam Genter Text Box L10
UP DN
/8
22' - 0"
9'
/1
6"
26' - 5 7/8"
25' - 11"
EXTG
RECRUITING
EXTG OFFICE
EXTG
WEIGHT
ROOM AND
KITCHEN
STORAGE
EXTG DRILL
HALL (GYM)
EXTG
KITCHEN
EXTG
WOMEN
S301
S301
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R E I S
P E N I N S U L A M
A M
OE
N A
M
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
PR
EL
IM
IN
AR
Y
C O
N
ST
R U
C
TI
O N
FI
N
AL
R
EC
O
R D
D
AT
E
IS
SU
ED
F O
R
IN
D
EX
C
O D
E
D M
VA
P
R O
JE
C
T #2
6B
ID
EN
TI
FI
C
AT
IO
N
N O
SH
EE
T
DE
SI
GN
ED
DR
AW
N
CH
EC
KE
D
AP
PR
OV
ED
ST
AT
E O
F M
IC
H
IG
AN
D
EP
AR
TM
EN
T
O F
TE
C
H N
O
LO
G Y, M
AN
AG
EM
EN
T
AN
D
B U
D G
ET
FA
C
IL
IT
IE
S
AN
D B
U
SI
N
ES
S
SE
R
VI
C
ES
A D
M
IN
IS
TR
AT
IO
N
AD
AM
L
AC
H , R
A, D
IR
EC
TO
R w w w .u pe a.
co m
UP
EA
P
RO
JE
CT
KI
N
G
SF
O R
D , M
IC
H
IG
AN
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
D
TM
B
FI
LE
/2
.J
BB
4-
-2
FIR
ST
FL
OO
R
EX
IST
IN
G
PL
AN
TE
ST
IN
G
AT
M1 2-0
R
EN
O
VA
TE
K
IN
G
SF
O
R D
A R
M O
R Y
JH
R
JH
R
C he ck er
A pp ro ve r
N
1/8" = 1'-0"1 EXISTING FIRST FLOOR PLAN
Sam Genter Text Box A13-1
Sam Genter Text Box A9, A10
Sam Genter Text Box A11
Sam Genter Text Box A19-1
Sam Genter Text Box A13, A14, A15
Sam Genter Text Box L6
Sam Genter Text Box L7
Sam Genter Text Box A16
Sam Genter Text Box A18
Sam Genter Text Box A17
Sam Genter
A12
DN
EXTG
OFFICES
EXTG BUNK
EXTG BUNK
EXTG
WOMEN
EXTG
LACTATION
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R E I S
P E N I N S U L A M
A M
OE
N A
M
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
PR
EL
IM
IN
AR
Y
C O
N
ST
R U
C
TI
O N
FI
N
AL
R
EC
O
R D
D
AT
E
IS
SU
ED
F O
R
IN
D
EX
C
O D
E
D M
VA
P
R O
JE
C
T #2
6B
ID
EN
TI
FI
C
AT
IO
N
N O
SH
EE
T
DE
SI
GN
ED
DR
AW
N
CH
EC
KE
D
AP
PR
OV
ED
ST
AT
E O
F M
IC
H
IG
AN
D
EP
AR
TM
EN
T
O F
TE
C
H N
O
LO
G Y, M
AN
AG
EM
EN
T
AN
D
B U
D G
ET
FA
C
IL
IT
IE
S
AN
D B
U
SI
N
ES
S
SE
R
VI
C
ES
A D
M
IN
IS
TR
AT
IO
N
AD
AM
L
AC
H , R
A, D
IR
EC
TO
R w w w .u pe a.
co m
UP
EA
P
RO
JE
CT
KI
N
G
SF
O R
D , M
IC
H
IG
AN
D
EP
AR
TM
EN
T
O F
M
IL
IT
AR
Y
AN
D V
ET
ER
AN
S
AF
FA
IR
S
D
TM
B
FI
LE
/2
.J
BB
4-
-2
SE
CO
ND
FL
OO
R
EX
IST
IN
G
PL
AN
TE
ST
IN
G
AT
M1 2-0
R
EN
O
VA
TE
K
IN
G
SF
O
R D
A R
M O
R Y
JH
R
JH
R
C he ck er
A pp ro ve r
N
1/8" = 1'-0"1 EXISTING SECOND FLOOR PLAN
Sam Genter Line
Sam Genter Line
Sam Genter Text Box A1
Sam Genter Text Box A2
Sam Genter Text Box L2
Sam Genter Text Box L1
Sam Genter Text Box A9-1
Sam Genter Text Box A3, A4
Sam Genter Text Box A5
Sam Genter Text Box L3, L4
Sam Genter Text Box A6, A7
Sam Genter Text Box L5
Sam Genter
A8
APPENDIX C
ANALYTICAL RESULTS - ASBESTOS
Attn:
Address: 100 Portage St Order #: 615344
Houghton, MI 49931
UP Engineers & Architects (2820)Customer:
Received 04/09/25
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
04/14/25Analyzed
04/14/25Reported
Analysis Report
PLM Analysis
Cust. IDSample ID LocationCollected Asbestos Fibers Other Materials
EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:
Project: Kingsford Armory Renovations
M12-05209Number:
Location: 401 S. Carpenter Ave
Office 201/20204/03/25 A1615344-001
White, Powdery
DrywallLayer 1: No Asbestos Detected CELLULOSE FIBER8%
NON FIBROUS MATERIAL92%
401 Carpenter Ave04/03/25 A2615344-002
Black, Rubbery
BaseboardLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%
Yellow, Soft
MasticLayer 2: No Asbestos Detected NON FIBROUS MATERIAL100%
401 Carpenter Ave04/03/25 A3615344-003
Brown, Brittle
MasticLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%
2nd Floor Locker Room04/03/25 A4615344-004
White, Powdery
DrywallLayer 1: No Asbestos Detected CELLULOSE FIBER8%
NON FIBROUS MATERIAL92%
2nd Floor Locker Room04/03/25 A5615344-005
Gray, Granular
PlasterLayer 1: No Asbestos Detected CELLULOSE FIBER2%
NON FIBROUS MATERIAL98%
White, Granular
Skim CoatLayer 2: No Asbestos Detected NON FIBROUS MATERIAL100%
Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the laboratory. The test results apply to the sample as received.
PLM Analysis
Cust. IDSample ID LocationCollected Asbestos Fibers Other Materials
EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:
Project: Kingsford Armory Renovations
M12-05209Number:
Location: 401 S. Carpenter Ave
2nd Floor Bathroom Floor04/03/25 A6615344-006
Blue/White, Hard
No mastic found.
Floor TileLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%
2nd Floor Bathroom Floor04/03/25 A7615344-007
Tan, Granular
GroutLayer 1: No Asbestos Detected CELLULOSE FIBER2%
NON FIBROUS MATERIAL98%
401 Carpenter Ave04/03/25 A8615344-008
Gray/Tan, Hard/Granular
ConcreteLayer 1: No Asbestos Detected CELLULOSE FIBER2%
NON FIBROUS MATERIAL98%
2nd Floor Hallway04/03/25 A9-1615344-009
Beige, Fibrous
Pipe InsulationLayer 1: CELLULOSE FIBER10%
MINERAL/GLASS WOOL30%
NON FIBROUS MATERIAL20%
40% CHRYSOTILE
401 Carpenter Ave04/03/25 A9615344-010
Black, Bituminous
TarLayer 1: NON FIBROUS MATERIAL96%4% CHRYSOTILE
Black, Fibrous/Bituminous
FeltLayer 2: No Asbestos Detected CELLULOSE FIBER70%
NON FIBROUS MATERIAL30%
401 Carpenter Ave04/03/25 A10615344-011
Black, Bituminous
TarLayer 1: NON FIBROUS MATERIAL96%4% CHRYSOTILE
Black, Fibrous/Bituminous
FeltLayer 2: No Asbestos Detected CELLULOSE FIBER70%
NON FIBROUS MATERIAL30%
Gym Floor04/03/25 A11615344-012
Black, Bituminous
Bituminous MaterialLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%
Beige, Soft
No cement found.
Soft MaterialLayer 2: No Asbestos Detected NON FIBROUS MATERIAL100%
Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the
EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:
Project: Kingsford Armory Renovations
M12-05209Number:
Location: 401 S. Carpenter Ave
401 Carpenter Ave04/03/25 A12615344-013
Black, Bituminous
MasticLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%
401 Carpenter Ave04/03/25 A13-1615344-014
White, Powdery
DrywallLayer 1: No Asbestos Detected CELLULOSE FIBER8%
NON FIBROUS MATERIAL92%
401 Carpenter Ave04/03/25 A13615344-015
Tan, Fibrous
InsulationLayer 1: No Asbestos Detected MINERAL/GLASS WOOL95%
NON FIBROUS MATERIAL5%
401 Carpenter Ave04/03/25 A14615344-016
Gray, Fibrous
InsulationLayer 1: No Asbestos Detected MINERAL/GLASS WOOL90%
NON FIBROUS MATERIAL10%
Ceiling04/03/25 A15615344-017
White, Granular
Ceiling PlasterLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%
401 Carpenter Ave04/03/25 A16615344-018
Gray, Soft
Window CaulkLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%
401 Carpenter Ave04/03/25 A17615344-019
Beige, Organically Bound
Vinyl FlooringLayer 1: No Asbestos Detected CELLULOSE FIBER2%
NON FIBROUS MATERIAL98%
Black/Yellow, Bituminous/Soft
MasticsLayer 2: No Asbestos Detected
Unable to separate individual layers.
NON FIBROUS MATERIAL100%
Under Sink04/03/25 A18615344-020
Yellow, Fibrous
InsulationLayer 1: No Asbestos Detected MINERAL/GLASS WOOL95%
NON FIBROUS MATERIAL5%
401 Carpenter Ave04/03/25 A19-1615344-021
Gray, Fibrous
Pipe InsulationLayer 1: CELLULOSE FIBER10%
MINERAL/GLASS WOOL30%
NON FIBROUS MATERIAL20%
40% CHRYSOTILE
Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the
EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:
Project: Kingsford Armory Renovations
M12-05209Number:
Location: 401 S. Carpenter Ave
401 Carpenter Ave04/03/25 A19615344-022
Beige, Fibrous
Pipe ElbowLayer 1: CELLULOSE FIBER10%
MINERAL/GLASS WOOL30%
NON FIBROUS MATERIAL20%
40% CHRYSOTILE
401 Carpenter Ave04/03/25 A20615344-023
Yellow, Fibrous
Pipe WrapLayer 1: No Asbestos Detected MINERAL/GLASS WOOL95%
NON FIBROUS MATERIAL5%
401 Carpenter Ave04/03/25 A21615344-024
Yellow, Fibrous
Pipe InsulationLayer 1: No Asbestos Detected MINERAL/GLASS WOOL95%
NON FIBROUS MATERIAL5%
401 Carpenter Ave04/03/25 A22615344-025
Gray, Fibrous
Pipe InsulationLayer 1: No Asbestos Detected CELLULOSE FIBER80%
NON FIBROUS MATERIAL10%
SYNTHETIC FIBER10%
Off White, Fibrous
Pipe InsulationLayer 2: CELLULOSE FIBER40%
MINERAL/GLASS WOOL20%
NON FIBROUS MATERIAL20%
20% CHRYSOTILE
401 Carpenter Ave04/03/25 A23615344-026
Brown, Fibrous
Pipe WrapLayer 1: No Asbestos Detected CELLULOSE FIBER20%
MINERAL/GLASS WOOL70%
NON FIBROUS MATERIAL10%
401 Carpenter Ave04/03/25 A24615344-027
Black/White, Soft/Fibrous/Bituminous
Pipe WrapLayer 1: No Asbestos Detected
Sample was inhomogenous, subsamples of each component were analyzed separately.
CELLULOSE FIBER60%
MINERAL/GLASS WOOL10%
NON FIBROUS MATERIAL30%
Bathroom Kitchen04/03/25 A25615344-028
Beige, Hard
No mastic found.
TileLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%
401 Carpenter Ave04/03/25 A26615344-029
Gray, Fibrous
No mud found.
Pipe ElbowLayer 1: CELLULOSE FIBER10%
MINERAL/GLASS WOOL30%
NON FIBROUS MATERIAL20%
40% CHRYSOTILE
Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the
EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:
Project: Kingsford Armory Renovations
M12-05209Number:
Location: 401 S. Carpenter Ave
401 Carpenter Ave04/03/25 A27615344-030
Brown, Fibrous
Pipe WrapLayer 1: No Asbestos Detected CELLULOSE FIBER20%
MINERAL/GLASS WOOL70%
NON FIBROUS MATERIAL10%
401 Carpenter Ave04/03/25 A28615344-031
White, Powdery
DrywallLayer 1: No Asbestos Detected CELLULOSE FIBER8%
NON FIBROUS MATERIAL92%
Analyst
Reviewed By: Michael Alers
Total layers analyzed on order: 38 615344-04/14/25 05:31 PM
EPA Regulatory Limit: 1%
Analyst Eisen Zhao
Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the
APPENDIX D
ANALYTICAL RESULTS - LEAD
Order #: 615345
Houghton, MI 49931
Project: Kingsford Armory Renovations
UP Engineers & Architects (2820)Customer:
M12-05209Number: PO Number:
Received 04/09/25
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: 401 S. Carpenter Ave
04/14/25Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
Matrix Bulk, Paint
615345-001 L1 White Wall Paint
Metals Analysis
Cadmium mg/kg DM04/11/259.90<9.90EPA 6010D / 3050B
615345-002 L2 White Off Wall Paint
Metals Analysis
Cadmium mg/kg DM04/11/2520.4<20.4EPA 6010D / 3050B
615345-003 L3 Bedroom White Plaster
Metals Analysis
Cadmium mg/kg DM04/11/255.88<5.89EPA 6010D / 3050B
615345-004 L4 Bathroom Pipe Paint
Metals Analysis
Cadmium mg/kg DM04/11/2513.0<13.0EPA 6010D / 3050B
615345-005 L5 Blue/Gray Concrete Paint
Metals Analysis
Cadmium mg/kg DM04/11/254.21<4.21EPA 6010D / 3050B
615345-006 L6 White Ceiling Paint
Metals Analysis
Cadmium mg/kg DM04/11/255.99<5.99EPA 6010D / 3050B
615345-007 L7 Side of Door Paint
Metals Analysis
Cadmium mg/kg DM04/11/256.1010.8EPA 6010D / 3050B
615345-008 L8 White Wall Paint
Metals Analysis
Cadmium mg/kg DM04/11/256.15<6.16EPA 6010D / 3050B
615345-009 L9 White Wood Panel
Metals Analysis
Cadmium mg/kg DM04/11/255.99<5.99EPA 6010D / 3050B
615345-010 L10 Water Pipe White Paint
Metals Analysis
Cadmium mg/kg DM04/11/2522.723.4EPA 6010D / 3050B
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results apply to the sample as received.
Order #: 615345
Houghton, MI 49931
Project: Kingsford Armory Renovations
UP Engineers & Architects (2820)Customer:
M12-05209Number: PO Number:
Received 04/09/25
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: 401 S. Carpenter Ave
04/14/25Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
Matrix Bulk, Paint
615345-011 L11 Bathroom Water Pipe Paint
Metals Analysis
Cadmium mg/kg DM04/11/257.02<7.02EPA 6010D / 3050B
615345-04/14/25 03:48 PM
Manager
Reviewed By: Kelly Muncy
Method Parameter Michigan Virginia
State Certifications
Cadmium No state cert. necessary VELAP CertifiedEPA 6010D
State Certificate Number
Virginia VELAP 12761
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results apply to the sample as received.
Weight
Address: 100 Portage St Order #: 615345
Houghton, MI 49931
Project: Kingsford Armory Renovations
UP Engineers & Architects (2820)Customer:
M12-05209Number: PO Number:
Received 04/09/25
Matrix Bulk, Paint
% / Wt. RL*Total µg
Cust. Sample ID
Parameter
Sample ID Location
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
04/09/25
Location: 401 S. Carpenter Ave
Analyzed
04/14/25Reported
Sample Date
Conc.Method
Analysis Report
White Wall Paint 04/03/25L1615345-001 202 mg
<0.00396 % 39.6 mg/kg<8.00 µgEPA 7000B <39.6 mg/kgLead
White Off Wall Paint 04/03/25L2615345-002 98.0 mg
0.168 % 81.6 mg/kg165 µgEPA 7000B
Sample weight below methods guidelines; results are accurate for weight provided.
1680 mg/kgLead
Bedroom White Plaster 04/03/25L3615345-003 340 mg
0.00405 % 23.5 mg/kg13.8 µgEPA 7000B 40.5 mg/kgLead
Bathroom Pipe Paint 04/03/25L4615345-004 154 mg
0.0102 % 51.9 mg/kg15.6 µgEPA 7000B
Sample weight below methods guidelines; results are accurate for weight provided.
102 mg/kgLead
Blue/Gray Concrete Paint 04/03/25L5615345-005 475 mg
0.00486 % 16.8 mg/kg23.1 µgEPA 7000B 48.6 mg/kgLead
White Ceiling Paint 04/03/25L6615345-006 334 mg
0.0236 % 24.0 mg/kg78.9 µgEPA 7000B 236 mg/kgLead
Side of Door Paint 04/03/25L7615345-007 328 mg
5.32 % 1220 mg/kg17400 µgEPA 7000B 53200 mg/kgLead
White Wall Paint 04/03/25L8615345-008 325 mg
2.26 % 492 mg/kg7350 µgEPA 7000B 22600 mg/kgLead
White Wood Panel 04/03/25L9615345-009 334 mg
0.00245 % 24.0 mg/kg8.19 µgEPA 7000B 24.5 mg/kgLead
Water Pipe White Paint 04/03/25L10615345-010 88.0 mg
0.0220 % 90.9 mg/kg19.4 µgEPA 7000B
Sample weight below methods guidelines; results are accurate for weight provided.
220 mg/kgLead
Bathroom Water Pipe Paint 04/03/25L11615345-011 285 mg
0.0349 % 28.1 mg/kg99.4 µgEPA 7000B 349 mg/kgLead
Lead Minimum Reporting Limit (*RL): 8.0 µg. All internal QC parameters were met. Unusual sample conditions, if any, are described. Do not reproduce this report except in full. Concentration and Reporting Limit (*RL) based on customer supplied information. The test results apply to the sample as received. PPM = mg/kg | PPB = µg/kg. Values are reported to three significant figures. AIHA LAP, LLC accredited for Lead (Lab ID 100527).
Weight
Address: 100 Portage St Order #: 615345
Houghton, MI 49931
Project: Kingsford Armory Renovations
UP Engineers & Architects (2820)Customer:
M12-05209Number: PO Number:
Received 04/09/25
Matrix Bulk, Paint
% / Wt. RL*Total µg
Cust. Sample ID
Parameter
Sample ID Location
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
04/09/25
Location: 401 S. Carpenter Ave
Analyzed
04/14/25Reported
Sample Date
Conc.Method
Analysis Report
Analyst: SAJ
615345-04/14/25 03:48 PM
Manager
Reviewed By: Kelly Muncy
Federal Lead Paint Statute as of 8/1/24
Location UnitLevel
Lead in paint by wt. 0.50 %
Lead in paint PPM 5000 mg/kg
Lead Minimum Reporting Limit (*RL): 8.0 µg. All internal QC parameters were met. Unusual sample conditions, if any, are described. Do not reproduce this report except in full. Concentration and Reporting Limit (*RL) based on customer supplied information. The test results apply to the sample as received. PPM = mg/kg | PPB = µg/kg. Values are reported to three significant figures. AIHA LAP, LLC accredited for Lead (Lab ID 100527).
5 UPEA
APPENDIX E
LABORATORY ACCREDITATION
United States Department of Commerce National Institute of Standards and Technology
Certificate of Accreditation to ISO/IEC 17025:2017
NVLAP LAB CODE: 101150-0
Schneider Laboratories Global, Inc.
Richmond, VA is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:
Asbestos Fiber Analysis
2024-04-01 through 2025-03-31 Effective Dates For the National Voluntary Laboratory Accreditation Program
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.
This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2017
For the National Voluntary Laboratory Accreditation Program
Effective
National Voluntary Laboratory Accreditation Program
2024-04-01 through 2025-03-31
Schneider Laboratories Global, Inc.
2512 W. Cary Street
Richmond, VA 23220-5117 Ms. Jennifer Lee
Phone: 804-353-6778 X14 Email: jlee@slabinc.com http://www.slabinc.com
ASBESTOS FIBER ANALYSIS NVLAP LAB CODE 101150-0
Bulk Asbestos Analysis Code Description 18/A01 EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of
Asbestos in Bulk Insulation Samples
18/A03 EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials
AIHA Laboratory Accreditation Programs, LLC acknowledges that
Schneider Laboratories Global 2512 West Cary Street, Richmond, VA 23220-5117
Laboratory ID: LAP-100527 along with all premises from which key activities are performed, as listed above, has fulfilled the requirements of the AIHA Laboratory Accreditation Programs, LLC (AIHA LAP) accreditation to the ISO/IEC 17025:2017 international standard, General Requirements for the Competence of Testing and Calibration Laboratories in the following:
LABORATORY ACCREDITATION PROGRAMS
INDUSTRIAL HYGIENE Accreditation Expires: August 01, 2025
ENVIRONMENTAL LEAD Accreditation Expires: August 01, 2025
ENVIRONMENTAL MICROBIOLOGY Accreditation Expires: August 01, 2025
FOOD Accreditation Expires:
UNIQUE SCOPES Accreditation Expires:
BE FIELD/MOBILE Accreditation Expires:
Specific Field(s) of Testing/Method(s) within each Accreditation Program for which the above named laboratory maintains accreditation is outlined on the attached Scope of Accreditation. Continued accreditation is contingent upon successful on-going compliance with ISO/IEC 17025:2017 and AIHA LAP requirements. This certificate is not valid without the attached Scope of Accreditation. Please review the AIHA LAP website (www.aihaaccreditedlabs.org) for the most current Scope.
Revision21: 10/24/2023
Cheryl O Morton Managing Director, AIHA Laboratory Accreditation Programs, LLC
Date Issued: 08/01/2023
File details come from the government source that posted it. Updated .