511.22033.JBB DMVA Renovate Kingsford Armory- Asbestos & Lead Survey Report.pdf

PDF 7 MB Posted

Attached to
511/22033. JBB; Renovate Kingsford Armory
Solicitation number
RFQ-171-250000000572-2
Issued by
Delta County, Kincheloe CDP, Michigan

About this file

This document is an Asbestos Survey and Lead-Based Paint Sampling Report prepared by U.P. Engineers & Architects, Inc. for the Kingsford Armory Renovations located at 401 S. Carpenter Ave. in Kingsford, Michigan. The survey was conducted on April 3rd, 2025, by Sam Genter, a State of Michigan licensed Asbestos Building Inspector and Lead Inspector, to identify asbestos-containing materials (ACM), presumed asbestos-containing materials (PACM), and lead-based paint in areas planned for renovation. The investigation involved a comprehensive building walkthrough, identification of suspect materials, collection and analysis of 28 bulk samples comprising 38 layers of suspect ACM, and 11 paint samples for lead and cadmium content.

The survey revealed several areas with regulated asbestos-containing and lead-containing materials. Asbestos was detected in pipe insulation on multiple floors, including the hallway, weight room, supply room, conference room, and attic, with materials ranging from beige and gray pipe insulation to black bituminous tar under the drill floor. Lead-based paint was found on the side of an exterior door in the kitchen (53,200 mg/kg) and on the shooting range wall (22,600 mg/kg), both significantly exceeding the federal lead paint statute limit of 5,000 mg/kg. The report emphasizes the need for proper handling and disposal of ACM and PACM by trained personnel, with recommendations for careful management during the planned renovations to ensure worker and environmental safety.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KINGSFORD ARMORY RENOVATIONS

401 S. CARPENTER AVE.

KINGSFORD, MI 49938

ASBESTOS SURVEY & LEAD

BASED PAINT

SAMPLING REPORT

Prepared for:

Kingsford Armory 401 S. Carpenter Ave.

Kingsford, MI 49802

Prepared By:

U.P. ENGINEERS & ARCHITECTS, INC.

100 Portage Street Houghton, Michigan 49931

April 2025

TABLE OF CONTENTS

Page

I. PURPOSE AND SCOPE

II. ASBESTOS CONTAINING MATERIAL SURVEY

III. LEAD CONTAINING PAINT SAMPLING

IV. CONCLUSIONS AND RECOMMENDATION

V. LIMITATIONS

VI. SIGNATURE OF CERTIFIED INSPECTOR………………………………………………….4

LIST OF APPENDICES

APPENDIX A INSPECTOR ACCREDITATION

APPENDIX B BUILDING FLOOR PLANS

APPENDIX C ANALYTICAL RESULTS - ASBESTOS

APPENDIX D ANALYTICAL RESULTS – LEAD & CADMIUM CONTAINING PAINT

APPENDIX E LABORATORY ACCREDITATION

1 UPEA

I. PURPOSE AND SCOPE

The purpose of this project was to conduct an asbestos survey and lead containing paint sampling for the sections of the Kingsford Armory that are going to be renovated. The survey and sampling will identify asbestos containing material (ACM), presumed ACM (PACM), and lead and cadmium containing paint throughout the planned renovation areas. This survey occurred in preparation for the planned renovations for the armory.

The survey and sampling data should be referred to by staff and personnel during demolition operations. Material or items not comprised of ACM or PACM may be removed, repaired, or replaced by general maintenance staff or contractors. However, ACM or PACM items must be handled and disposed of by properly trained personnel.

Lead containing paint may be disposed of as demolition debris if the proper procedures are followed.

The scope of this project includes:

1. Building walk through

2. Identification of suspect ACM and LBP

3. Collection and analysis of bulk samples of suspect ACM

4. Collection of suspect Lead Containing Paint Samples

5. Quantification of ACM and PACM

6. Assess current condition of ACM and PACM and identify the potential for disturbance of ACM and PACM.

II. ASBESTOS CONTAINING MATERIAL SURVEY

An asbestos survey was conducted for parts of the Kingsford Armory in anticipation of planned renovations. The asbestos survey was performed by Sam Genter, a State of Michigan accredited Asbestos Building Inspector (License # A63169) on April 3rd, 2025.

The asbestos survey consisted of five phases: 1) conduct a visual inspection of the building; 2) identify homogeneous areas; 3) collect samples of suspect ACM from different homogeneous areas; 4) quantify ACM and PACM; 5) assess current conditions of sampled suspect ACM and the potential for disturbance of the ACM identified.

Prior to collecting any samples, a sampling strategy was developed based on the layout of the building and the construction periods associated with each section of the building.

Locations were sampled based on the location of the planned demolition and associated renovation. Based on the sampling strategy, the building was divided into different homogeneous areas, from which samples would be collected. A homogeneous area can be described as one or more areas of material that are similar in appearance and that have the same construction/installation date and function. Bulk samples of identified suspect asbestos containing material (ACM) were collected in individual containers and sent to a National Voluntary Lab Accreditation Program (NVLAP)/American Industrial Hygiene Association (AIHA) accredited laboratory for analysis. The number of samples collected from each homogeneous area may vary depending on the professional judgment of the inspector and the type of material present.

Twenty-eight (28) samples consisting of thirty-eight (38) layers of suspect ACM were collected from the areas of the armory that are planned to be renovated and analyzed by Polarized Light Microscopy (PLM). Table 1 shows any confirmed ACMs. Table 3

2 UPEA

presents the sample analysis results. The confirmed ACMs are reported in bold text.

Appendix B contains a copy of the building floor plans and the location of samples.

Copies of the analytical results are included in Appendix C. Appendix E contains a copy of the laboratory accreditation.

These asbestos surveys were completed with limited destructive testing. Therefore, hidden materials may be discovered in walls or ceiling that contain asbestos. If such materials are encountered, all work shall stop immediately until proper testing is conducted to determine the content of the material.

TABLE 1

CONFIRMED ASBESTOS CONTAINING MATERIALS

FLOOR LOCATION MATERIAL EST

QUANTITY

FRIABLE

2 Hallway Beige Pipe Insulation

(Exterior is white)

10 LF Y

Drill Floor (under floorboards) Black, Bituminous Tar 3,200 SF N

Weight Room

Adjacent to Drill Floor

Gray Pipe Insulation 20 LF Y

0 Supply Room Thin Pipe Elbow

Insulation

30 LF Y

Club Conference

Room Thick Pipe Insulation 20 LF Y

Attic Attic Gray Pipe Elbow

Insulation

25 LF Y

III. LEAD CONTAINING PAINT SAMPLING

Eleven (11) paint samples of suspect lead and cadmium containing paint from the areas planned to be renovated in the Kingsford Armory were collected by Sam Genter, a State of Michigan licensed lead Inspector (License # P-009865) on April 3rd, 2025 and submitted for analysis by an accredited laboratory. Table 2 shows any confirmed lead-based or cadmium containing paint. Table 4 presents the sample analysis results. The confirmed lead-containing paint samples are reported in bold text. Copies of the lead analytical results are included in Appendix D.

TABLE 2

CONFIRMED LEAD & CADMIUM CONTAINING MATERIALS

FLOOR LOCATION COLOR LEAD CONC.

1 Side of Exterior

Door – Kitchen Green 53,200 mg/kg

0 Shooting Range Wall

White 22,600 mg/kg

3 UPEA

IV. CONCLUSIONS AND RECOMMENDATIONS

Asbestos:

The results of the asbestos survey conducted on 4/3/2025 for the areas of the Kingsford Armory planned to be renovated at 401 S. Carpenter Ave. in Kingsford, MI indicate that the building DOES contain regulated asbestos containing materials.

Basement:

The thin pipe elbow insulation in the supply room adjacent to the shooting range contained asbestos fibers. This thin insulation, along with any encountered similar insulation, should be treated as ACM. The thicker pipe insulation in the ceiling above the conference room tested positive for asbestos fibers. This pipe wrap, along with any encountered similar insulation, should be treated as ACM.

1st Floor:

The black, bituminous tar under the hardwood in the drill floor contained asbestos fibers.

The pipe insulation in the corner of the weight room, adjacent to the drill floor, also tested positive for asbestos fibers. Anywhere this type of insulation is encountered, the insulation should be treated as ACM.

2nd Floor:

The hallway in the second floor had exposed pipe insulation near the ceiling that had been painted white. A core of this material tested positive for asbestos containing fibers.

This and similar pipe insulation should be treated as ACM.

Attic:

The gray/brown pipe elbow insulation contained asbestos fibers. All similar pipe insulation should be treated as asbestos containing material.

Material or items not comprised of ACM or PACM may be removed, repaired, or replaced by general maintenance staff or contractors. However, ACM or PACM items must be handled and disposed of by properly trained personnel. Subcontractors and employees working in the building should be instructed to report any hidden suspect ACM immediately upon discovery.

Lead-Containing Paint:

The results of the lead-containing paint sampling conducted on 4/3/2025 for the areas of the Kingsford Armory planned to be renovated at 401 S. Carpenter Ave. in Kingsford, MI indicate that the areas planned for renovation DO contain regulated lead-containing or cadmium-containing paint. The kitchen on the first floor has an exterior door on the west side, painted white, with deteriorating paint that had lead levels above the regulatory limit. The shooting range wall in the basement was mostly intact but tested positive for lead at a concentration above regulatory limits.

V. LIMITATIONS

Identification and testing of PACM was conducted by a trained professional licensed in the State of Michigan. Professional judgment was used in the selection of materials to be tested and the number of samples of each homogeneous material tested.

4 UPEA

This report documents testing of ACM or PACM based on sampling strategies and priorities as described herein, and on the dates and at locations identified in this report.

Modifications to the building or its interior through renovations, remodeling, building additions or changes to fixtures, facilities or furnishings that occur subsequent to the date of this report may add or remove ACM or PACM not identified in this report.

This report was completed to aid the building Owner, general contractors, and potential asbestos abatement contractors in locating ACM. Under no circumstances should this report be utilized as a bidding document or as a project specification document.

VI. SIGNATURE OF CERTIFIED INSPECTOR

4/15/2025 Sam Genter, Asbestos Inspector (#A63169) Date Lead Inspector (#P-009865)

Second Floor Hallway Pipe InsulaƟon (ACM)

Kingsford Armory Planned RenovaƟons

Kitchen Side Of Exterior Door

(LBP)

Thin Pipe Elbow in Supply Room (ACM)

Thick Pipe Wrap Above Club Con-ference Room (ACM)

APPENDIX A

INSPECTOR ACCREDITATION

2 UPEA

APPENDIX B

BUILDING FLOOR PLANS

& SAMPLE LOCATIONS

UP

9' - 6"

3 13/16"1' - 0"

13' - 1"

VAULT

EXTG

SIM

9' - 11"

UNEXCAVATED

EXTG

LOCKER

S301

S301

P L

U R

I B

U E

S U

N U

M

C I

R C

U M

S P

I C

E

S I

Q U

E R E I S

P E N I N S U L A M

A M

OE

N A

M

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

PR

EL

IM

IN

AR

Y

C O

N

ST

R U

C

TI

O N

FI

N

AL

R

EC

O

R D

D

AT

E

IS

SU

ED

F O

R

IN

D

EX

C

O D

E

D M

VA

P

R O

JE

C

T #2

6B

ID

EN

TI

FI

C

AT

IO

N

N O

SH

EE

T

DE

SI

GN

ED

DR

AW

N

CH

EC

KE

D

AP

PR

OV

ED

ST

AT

E O

F M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

TE

C

H N

O

LO

G Y, M

AN

AG

EM

EN

T

AN

D

B U

D G

ET

FA

C

IL

IT

IE

S

AN

D B

U

SI

N

ES

S

SE

R

VI

C

ES

A D

M

IN

IS

TR

AT

IO

N

AD

AM

L

AC

H , R

A, D

IR

EC

TO

R w w w .u pe a.

co m

UP

EA

P

RO

JE

CT

KI

N

G

SF

O R

D , M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

M

IL

IT

AR

Y

AN

D V

ET

ER

AN

S

AF

FA

IR

S

D

TM

B

FI

LE

/2

.J

BB

4-

-2

BA

SE

ME

NT

EX

IST

IN

G

PL

AN

TE

ST

IN

G

AT

M1 2-0

R

EN

O

VA

TE

K

IN

G

SF

O

R D

A R

M O

R Y

JH

R

JH

R

C he ck er

A pp ro ve r

1/8" = 1'-0"1 EXISTING BASEMENT PLAN

N

Sam Genter Text Box A19, A20

Sam Genter Text Box L8

Sam Genter Text Box L9

Sam Genter Text Box A21, A22

Sam Genter Text Box L11

Sam Genter Text Box A24

Sam Genter Text Box A23

Sam Genter Text Box L10

UP DN

/8

22' - 0"

9'

/1

6"

26' - 5 7/8"

25' - 11"

EXTG

RECRUITING

EXTG OFFICE

EXTG

WEIGHT

ROOM AND

KITCHEN

STORAGE

EXTG DRILL

HALL (GYM)

EXTG

KITCHEN

EXTG

WOMEN

S301

S301

P L

U R

I B

U E

S U

N U

M

C I

R C

U M

S P

I C

E

S I

Q U

E R E I S

P E N I N S U L A M

A M

OE

N A

M

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

PR

EL

IM

IN

AR

Y

C O

N

ST

R U

C

TI

O N

FI

N

AL

R

EC

O

R D

D

AT

E

IS

SU

ED

F O

R

IN

D

EX

C

O D

E

D M

VA

P

R O

JE

C

T #2

6B

ID

EN

TI

FI

C

AT

IO

N

N O

SH

EE

T

DE

SI

GN

ED

DR

AW

N

CH

EC

KE

D

AP

PR

OV

ED

ST

AT

E O

F M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

TE

C

H N

O

LO

G Y, M

AN

AG

EM

EN

T

AN

D

B U

D G

ET

FA

C

IL

IT

IE

S

AN

D B

U

SI

N

ES

S

SE

R

VI

C

ES

A D

M

IN

IS

TR

AT

IO

N

AD

AM

L

AC

H , R

A, D

IR

EC

TO

R w w w .u pe a.

co m

UP

EA

P

RO

JE

CT

KI

N

G

SF

O R

D , M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

M

IL

IT

AR

Y

AN

D V

ET

ER

AN

S

AF

FA

IR

S

D

TM

B

FI

LE

/2

.J

BB

4-

-2

FIR

ST

FL

OO

R

EX

IST

IN

G

PL

AN

TE

ST

IN

G

AT

M1 2-0

R

EN

O

VA

TE

K

IN

G

SF

O

R D

A R

M O

R Y

JH

R

JH

R

C he ck er

A pp ro ve r

N

1/8" = 1'-0"1 EXISTING FIRST FLOOR PLAN

Sam Genter Text Box A13-1

Sam Genter Text Box A9, A10

Sam Genter Text Box A11

Sam Genter Text Box A19-1

Sam Genter Text Box A13, A14, A15

Sam Genter Text Box L6

Sam Genter Text Box L7

Sam Genter Text Box A16

Sam Genter Text Box A18

Sam Genter Text Box A17

Sam Genter

A12

DN

EXTG

OFFICES

EXTG BUNK

EXTG BUNK

EXTG

WOMEN

EXTG

LACTATION

P L

U R

I B

U E

S U

N U

M

C I

R C

U M

S P

I C

E

S I

Q U

E R E I S

P E N I N S U L A M

A M

OE

N A

M

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

PR

EL

IM

IN

AR

Y

C O

N

ST

R U

C

TI

O N

FI

N

AL

R

EC

O

R D

D

AT

E

IS

SU

ED

F O

R

IN

D

EX

C

O D

E

D M

VA

P

R O

JE

C

T #2

6B

ID

EN

TI

FI

C

AT

IO

N

N O

SH

EE

T

DE

SI

GN

ED

DR

AW

N

CH

EC

KE

D

AP

PR

OV

ED

ST

AT

E O

F M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

TE

C

H N

O

LO

G Y, M

AN

AG

EM

EN

T

AN

D

B U

D G

ET

FA

C

IL

IT

IE

S

AN

D B

U

SI

N

ES

S

SE

R

VI

C

ES

A D

M

IN

IS

TR

AT

IO

N

AD

AM

L

AC

H , R

A, D

IR

EC

TO

R w w w .u pe a.

co m

UP

EA

P

RO

JE

CT

KI

N

G

SF

O R

D , M

IC

H

IG

AN

D

EP

AR

TM

EN

T

O F

M

IL

IT

AR

Y

AN

D V

ET

ER

AN

S

AF

FA

IR

S

D

TM

B

FI

LE

/2

.J

BB

4-

-2

SE

CO

ND

FL

OO

R

EX

IST

IN

G

PL

AN

TE

ST

IN

G

AT

M1 2-0

R

EN

O

VA

TE

K

IN

G

SF

O

R D

A R

M O

R Y

JH

R

JH

R

C he ck er

A pp ro ve r

N

1/8" = 1'-0"1 EXISTING SECOND FLOOR PLAN

Sam Genter Line

Sam Genter Line

Sam Genter Text Box A1

Sam Genter Text Box A2

Sam Genter Text Box L2

Sam Genter Text Box L1

Sam Genter Text Box A9-1

Sam Genter Text Box A3, A4

Sam Genter Text Box A5

Sam Genter Text Box L3, L4

Sam Genter Text Box A6, A7

Sam Genter Text Box L5

Sam Genter

A8

APPENDIX C

ANALYTICAL RESULTS - ASBESTOS

Attn:

Address: 100 Portage St Order #: 615344

Houghton, MI 49931

UP Engineers & Architects (2820)Customer:

Received 04/09/25

Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475

04/14/25Analyzed

04/14/25Reported

Analysis Report

PLM Analysis

Cust. IDSample ID LocationCollected Asbestos Fibers Other Materials

EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:

Project: Kingsford Armory Renovations

M12-05209Number:

Location: 401 S. Carpenter Ave

Office 201/20204/03/25 A1615344-001

White, Powdery

DrywallLayer 1: No Asbestos Detected CELLULOSE FIBER8%

NON FIBROUS MATERIAL92%

401 Carpenter Ave04/03/25 A2615344-002

Black, Rubbery

BaseboardLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%

Yellow, Soft

MasticLayer 2: No Asbestos Detected NON FIBROUS MATERIAL100%

401 Carpenter Ave04/03/25 A3615344-003

Brown, Brittle

MasticLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%

2nd Floor Locker Room04/03/25 A4615344-004

White, Powdery

DrywallLayer 1: No Asbestos Detected CELLULOSE FIBER8%

NON FIBROUS MATERIAL92%

2nd Floor Locker Room04/03/25 A5615344-005

Gray, Granular

PlasterLayer 1: No Asbestos Detected CELLULOSE FIBER2%

NON FIBROUS MATERIAL98%

White, Granular

Skim CoatLayer 2: No Asbestos Detected NON FIBROUS MATERIAL100%

Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the laboratory. The test results apply to the sample as received.

PLM Analysis

Cust. IDSample ID LocationCollected Asbestos Fibers Other Materials

EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:

Project: Kingsford Armory Renovations

M12-05209Number:

Location: 401 S. Carpenter Ave

2nd Floor Bathroom Floor04/03/25 A6615344-006

Blue/White, Hard

No mastic found.

Floor TileLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%

2nd Floor Bathroom Floor04/03/25 A7615344-007

Tan, Granular

GroutLayer 1: No Asbestos Detected CELLULOSE FIBER2%

NON FIBROUS MATERIAL98%

401 Carpenter Ave04/03/25 A8615344-008

Gray/Tan, Hard/Granular

ConcreteLayer 1: No Asbestos Detected CELLULOSE FIBER2%

NON FIBROUS MATERIAL98%

2nd Floor Hallway04/03/25 A9-1615344-009

Beige, Fibrous

Pipe InsulationLayer 1: CELLULOSE FIBER10%

MINERAL/GLASS WOOL30%

NON FIBROUS MATERIAL20%

40% CHRYSOTILE

401 Carpenter Ave04/03/25 A9615344-010

Black, Bituminous

TarLayer 1: NON FIBROUS MATERIAL96%4% CHRYSOTILE

Black, Fibrous/Bituminous

FeltLayer 2: No Asbestos Detected CELLULOSE FIBER70%

NON FIBROUS MATERIAL30%

401 Carpenter Ave04/03/25 A10615344-011

Black, Bituminous

TarLayer 1: NON FIBROUS MATERIAL96%4% CHRYSOTILE

Black, Fibrous/Bituminous

FeltLayer 2: No Asbestos Detected CELLULOSE FIBER70%

NON FIBROUS MATERIAL30%

Gym Floor04/03/25 A11615344-012

Black, Bituminous

Bituminous MaterialLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%

Beige, Soft

No cement found.

Soft MaterialLayer 2: No Asbestos Detected NON FIBROUS MATERIAL100%

Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the

EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:

Project: Kingsford Armory Renovations

M12-05209Number:

Location: 401 S. Carpenter Ave

401 Carpenter Ave04/03/25 A12615344-013

Black, Bituminous

MasticLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%

401 Carpenter Ave04/03/25 A13-1615344-014

White, Powdery

DrywallLayer 1: No Asbestos Detected CELLULOSE FIBER8%

NON FIBROUS MATERIAL92%

401 Carpenter Ave04/03/25 A13615344-015

Tan, Fibrous

InsulationLayer 1: No Asbestos Detected MINERAL/GLASS WOOL95%

NON FIBROUS MATERIAL5%

401 Carpenter Ave04/03/25 A14615344-016

Gray, Fibrous

InsulationLayer 1: No Asbestos Detected MINERAL/GLASS WOOL90%

NON FIBROUS MATERIAL10%

Ceiling04/03/25 A15615344-017

White, Granular

Ceiling PlasterLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%

401 Carpenter Ave04/03/25 A16615344-018

Gray, Soft

Window CaulkLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%

401 Carpenter Ave04/03/25 A17615344-019

Beige, Organically Bound

Vinyl FlooringLayer 1: No Asbestos Detected CELLULOSE FIBER2%

NON FIBROUS MATERIAL98%

Black/Yellow, Bituminous/Soft

MasticsLayer 2: No Asbestos Detected

Unable to separate individual layers.

NON FIBROUS MATERIAL100%

Under Sink04/03/25 A18615344-020

Yellow, Fibrous

InsulationLayer 1: No Asbestos Detected MINERAL/GLASS WOOL95%

NON FIBROUS MATERIAL5%

401 Carpenter Ave04/03/25 A19-1615344-021

Gray, Fibrous

Pipe InsulationLayer 1: CELLULOSE FIBER10%

MINERAL/GLASS WOOL30%

NON FIBROUS MATERIAL20%

40% CHRYSOTILE

Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the

EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:

Project: Kingsford Armory Renovations

M12-05209Number:

Location: 401 S. Carpenter Ave

401 Carpenter Ave04/03/25 A19615344-022

Beige, Fibrous

Pipe ElbowLayer 1: CELLULOSE FIBER10%

MINERAL/GLASS WOOL30%

NON FIBROUS MATERIAL20%

40% CHRYSOTILE

401 Carpenter Ave04/03/25 A20615344-023

Yellow, Fibrous

Pipe WrapLayer 1: No Asbestos Detected MINERAL/GLASS WOOL95%

NON FIBROUS MATERIAL5%

401 Carpenter Ave04/03/25 A21615344-024

Yellow, Fibrous

Pipe InsulationLayer 1: No Asbestos Detected MINERAL/GLASS WOOL95%

NON FIBROUS MATERIAL5%

401 Carpenter Ave04/03/25 A22615344-025

Gray, Fibrous

Pipe InsulationLayer 1: No Asbestos Detected CELLULOSE FIBER80%

NON FIBROUS MATERIAL10%

SYNTHETIC FIBER10%

Off White, Fibrous

Pipe InsulationLayer 2: CELLULOSE FIBER40%

MINERAL/GLASS WOOL20%

NON FIBROUS MATERIAL20%

20% CHRYSOTILE

401 Carpenter Ave04/03/25 A23615344-026

Brown, Fibrous

Pipe WrapLayer 1: No Asbestos Detected CELLULOSE FIBER20%

MINERAL/GLASS WOOL70%

NON FIBROUS MATERIAL10%

401 Carpenter Ave04/03/25 A24615344-027

Black/White, Soft/Fibrous/Bituminous

Pipe WrapLayer 1: No Asbestos Detected

Sample was inhomogenous, subsamples of each component were analyzed separately.

CELLULOSE FIBER60%

MINERAL/GLASS WOOL10%

NON FIBROUS MATERIAL30%

Bathroom Kitchen04/03/25 A25615344-028

Beige, Hard

No mastic found.

TileLayer 1: No Asbestos Detected NON FIBROUS MATERIAL100%

401 Carpenter Ave04/03/25 A26615344-029

Gray, Fibrous

No mud found.

Pipe ElbowLayer 1: CELLULOSE FIBER10%

MINERAL/GLASS WOOL30%

NON FIBROUS MATERIAL20%

40% CHRYSOTILE

Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the

EPA 600/R-93/116 & 40 CFR App. E Sub. E Pt. 763Method:

Project: Kingsford Armory Renovations

M12-05209Number:

Location: 401 S. Carpenter Ave

401 Carpenter Ave04/03/25 A27615344-030

Brown, Fibrous

Pipe WrapLayer 1: No Asbestos Detected CELLULOSE FIBER20%

MINERAL/GLASS WOOL70%

NON FIBROUS MATERIAL10%

401 Carpenter Ave04/03/25 A28615344-031

White, Powdery

DrywallLayer 1: No Asbestos Detected CELLULOSE FIBER8%

NON FIBROUS MATERIAL92%

Analyst

Reviewed By: Michael Alers

Total layers analyzed on order: 38 615344-04/14/25 05:31 PM

EPA Regulatory Limit: 1%

Analyst Eisen Zhao

Reporting Limit: 1% Gravimetrically Reduced Reporting Limit: 0.01% PLM analysis is based on Visual Estimation and NESHAP recommends that any friable sample with an asbestos content less than 10 percent be verified by Point Count or TEM Analysis. The EPA recommends that any attic loose fill vermiculite should be treated as asbestos containing material. This report must not be reproduced except in full with the approval of the

APPENDIX D

ANALYTICAL RESULTS - LEAD

Order #: 615345

Houghton, MI 49931

Project: Kingsford Armory Renovations

UP Engineers & Architects (2820)Customer:

M12-05209Number: PO Number:

Received 04/09/25

Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475

Location: 401 S. Carpenter Ave

04/14/25Reported

Analysis Report

Cust. Sample ID

Parameter

Sample ID Location

UnitsRL* AnalystAnalysis DateResultMethod

Matrix Bulk, Paint

615345-001 L1 White Wall Paint

Metals Analysis

Cadmium mg/kg DM04/11/259.90<9.90EPA 6010D / 3050B

615345-002 L2 White Off Wall Paint

Metals Analysis

Cadmium mg/kg DM04/11/2520.4<20.4EPA 6010D / 3050B

615345-003 L3 Bedroom White Plaster

Metals Analysis

Cadmium mg/kg DM04/11/255.88<5.89EPA 6010D / 3050B

615345-004 L4 Bathroom Pipe Paint

Metals Analysis

Cadmium mg/kg DM04/11/2513.0<13.0EPA 6010D / 3050B

615345-005 L5 Blue/Gray Concrete Paint

Metals Analysis

Cadmium mg/kg DM04/11/254.21<4.21EPA 6010D / 3050B

615345-006 L6 White Ceiling Paint

Metals Analysis

Cadmium mg/kg DM04/11/255.99<5.99EPA 6010D / 3050B

615345-007 L7 Side of Door Paint

Metals Analysis

Cadmium mg/kg DM04/11/256.1010.8EPA 6010D / 3050B

615345-008 L8 White Wall Paint

Metals Analysis

Cadmium mg/kg DM04/11/256.15<6.16EPA 6010D / 3050B

615345-009 L9 White Wood Panel

Metals Analysis

Cadmium mg/kg DM04/11/255.99<5.99EPA 6010D / 3050B

615345-010 L10 Water Pipe White Paint

Metals Analysis

Cadmium mg/kg DM04/11/2522.723.4EPA 6010D / 3050B

All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results apply to the sample as received.

Order #: 615345

Houghton, MI 49931

Project: Kingsford Armory Renovations

UP Engineers & Architects (2820)Customer:

M12-05209Number: PO Number:

Received 04/09/25

Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475

Location: 401 S. Carpenter Ave

04/14/25Reported

Analysis Report

Cust. Sample ID

Parameter

Sample ID Location

UnitsRL* AnalystAnalysis DateResultMethod

Matrix Bulk, Paint

615345-011 L11 Bathroom Water Pipe Paint

Metals Analysis

Cadmium mg/kg DM04/11/257.02<7.02EPA 6010D / 3050B

615345-04/14/25 03:48 PM

Manager

Reviewed By: Kelly Muncy

Method Parameter Michigan Virginia

State Certifications

Cadmium No state cert. necessary VELAP CertifiedEPA 6010D

State Certificate Number

Virginia VELAP 12761

All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results apply to the sample as received.

Weight

Address: 100 Portage St Order #: 615345

Houghton, MI 49931

Project: Kingsford Armory Renovations

UP Engineers & Architects (2820)Customer:

M12-05209Number: PO Number:

Received 04/09/25

Matrix Bulk, Paint

% / Wt. RL*Total µg

Cust. Sample ID

Parameter

Sample ID Location

Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475

04/09/25

Location: 401 S. Carpenter Ave

Analyzed

04/14/25Reported

Sample Date

Conc.Method

Analysis Report

White Wall Paint 04/03/25L1615345-001 202 mg

<0.00396 % 39.6 mg/kg<8.00 µgEPA 7000B <39.6 mg/kgLead

White Off Wall Paint 04/03/25L2615345-002 98.0 mg

0.168 % 81.6 mg/kg165 µgEPA 7000B

Sample weight below methods guidelines; results are accurate for weight provided.

1680 mg/kgLead

Bedroom White Plaster 04/03/25L3615345-003 340 mg

0.00405 % 23.5 mg/kg13.8 µgEPA 7000B 40.5 mg/kgLead

Bathroom Pipe Paint 04/03/25L4615345-004 154 mg

0.0102 % 51.9 mg/kg15.6 µgEPA 7000B

Sample weight below methods guidelines; results are accurate for weight provided.

102 mg/kgLead

Blue/Gray Concrete Paint 04/03/25L5615345-005 475 mg

0.00486 % 16.8 mg/kg23.1 µgEPA 7000B 48.6 mg/kgLead

White Ceiling Paint 04/03/25L6615345-006 334 mg

0.0236 % 24.0 mg/kg78.9 µgEPA 7000B 236 mg/kgLead

Side of Door Paint 04/03/25L7615345-007 328 mg

5.32 % 1220 mg/kg17400 µgEPA 7000B 53200 mg/kgLead

White Wall Paint 04/03/25L8615345-008 325 mg

2.26 % 492 mg/kg7350 µgEPA 7000B 22600 mg/kgLead

White Wood Panel 04/03/25L9615345-009 334 mg

0.00245 % 24.0 mg/kg8.19 µgEPA 7000B 24.5 mg/kgLead

Water Pipe White Paint 04/03/25L10615345-010 88.0 mg

0.0220 % 90.9 mg/kg19.4 µgEPA 7000B

Sample weight below methods guidelines; results are accurate for weight provided.

220 mg/kgLead

Bathroom Water Pipe Paint 04/03/25L11615345-011 285 mg

0.0349 % 28.1 mg/kg99.4 µgEPA 7000B 349 mg/kgLead

Lead Minimum Reporting Limit (*RL): 8.0 µg. All internal QC parameters were met. Unusual sample conditions, if any, are described. Do not reproduce this report except in full. Concentration and Reporting Limit (*RL) based on customer supplied information. The test results apply to the sample as received. PPM = mg/kg | PPB = µg/kg. Values are reported to three significant figures. AIHA LAP, LLC accredited for Lead (Lab ID 100527).

Weight

Address: 100 Portage St Order #: 615345

Houghton, MI 49931

Project: Kingsford Armory Renovations

UP Engineers & Architects (2820)Customer:

M12-05209Number: PO Number:

Received 04/09/25

Matrix Bulk, Paint

% / Wt. RL*Total µg

Cust. Sample ID

Parameter

Sample ID Location

Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475

04/09/25

Location: 401 S. Carpenter Ave

Analyzed

04/14/25Reported

Sample Date

Conc.Method

Analysis Report

Analyst: SAJ

615345-04/14/25 03:48 PM

Manager

Reviewed By: Kelly Muncy

Federal Lead Paint Statute as of 8/1/24

Location UnitLevel

Lead in paint by wt. 0.50 %

Lead in paint PPM 5000 mg/kg

Lead Minimum Reporting Limit (*RL): 8.0 µg. All internal QC parameters were met. Unusual sample conditions, if any, are described. Do not reproduce this report except in full. Concentration and Reporting Limit (*RL) based on customer supplied information. The test results apply to the sample as received. PPM = mg/kg | PPB = µg/kg. Values are reported to three significant figures. AIHA LAP, LLC accredited for Lead (Lab ID 100527).

5 UPEA

APPENDIX E

LABORATORY ACCREDITATION

United States Department of Commerce National Institute of Standards and Technology

Certificate of Accreditation to ISO/IEC 17025:2017

NVLAP LAB CODE: 101150-0

Schneider Laboratories Global, Inc.

Richmond, VA is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:

Asbestos Fiber Analysis

2024-04-01 through 2025-03-31 Effective Dates For the National Voluntary Laboratory Accreditation Program

This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.

This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2017

For the National Voluntary Laboratory Accreditation Program

Effective

National Voluntary Laboratory Accreditation Program

2024-04-01 through 2025-03-31

Schneider Laboratories Global, Inc.

2512 W. Cary Street

Richmond, VA 23220-5117 Ms. Jennifer Lee

Phone: 804-353-6778 X14 Email: jlee@slabinc.com http://www.slabinc.com

ASBESTOS FIBER ANALYSIS NVLAP LAB CODE 101150-0

Bulk Asbestos Analysis Code Description 18/A01 EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of

Asbestos in Bulk Insulation Samples

18/A03 EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials

AIHA Laboratory Accreditation Programs, LLC acknowledges that

Schneider Laboratories Global 2512 West Cary Street, Richmond, VA 23220-5117

Laboratory ID: LAP-100527 along with all premises from which key activities are performed, as listed above, has fulfilled the requirements of the AIHA Laboratory Accreditation Programs, LLC (AIHA LAP) accreditation to the ISO/IEC 17025:2017 international standard, General Requirements for the Competence of Testing and Calibration Laboratories in the following:

LABORATORY ACCREDITATION PROGRAMS

INDUSTRIAL HYGIENE Accreditation Expires: August 01, 2025

ENVIRONMENTAL LEAD Accreditation Expires: August 01, 2025

ENVIRONMENTAL MICROBIOLOGY Accreditation Expires: August 01, 2025

FOOD Accreditation Expires:

UNIQUE SCOPES Accreditation Expires:

BE FIELD/MOBILE Accreditation Expires:

Specific Field(s) of Testing/Method(s) within each Accreditation Program for which the above named laboratory maintains accreditation is outlined on the attached Scope of Accreditation. Continued accreditation is contingent upon successful on-going compliance with ISO/IEC 17025:2017 and AIHA LAP requirements. This certificate is not valid without the attached Scope of Accreditation. Please review the AIHA LAP website (www.aihaaccreditedlabs.org) for the most current Scope.

Revision21: 10/24/2023

Cheryl O Morton Managing Director, AIHA Laboratory Accreditation Programs, LLC

Date Issued: 08/01/2023