5-6732 M0.0.01.pdf

PDF 190 KB Posted

Attached to
RFP - Bert Goens Learning Center Pool Improvements
Solicitation number
RFP VBI 260000002079 3
Issued by
Van Buren County, Michigan

About this file

This is a Mechanical General Information drawing sheet for the Bert Goens Learning Center Pool Improvements project located in Lawrence, Michigan, prepared for the Van Buren Intermediate School District. The document serves as a schematic design plan detailing HVAC systems, mechanical demolition requirements, and installation guidelines for Unit B of the pool facility. The drawing includes comprehensive symbol legends for HVAC components, valve types, ductwork configurations, and piping instruments, along with detailed notes regarding equipment installation, coordination requirements, and field verification responsibilities. Key dates noted include a bid and construction start date of May 21, 2026, with an addendum issued on June 8, 2026. The drawing emphasizes that contractors are responsible for field-verifying existing conditions, determining the full extent of demolition work, and coordinating with architectural and engineering teams where discrepancies exist between design drawings and actual site conditions.

The document specifies general mechanical demolition notes and installation requirements, including contractor responsibilities for investigating building conditions, protecting existing utilities and structures, and properly disposing of removed materials and equipment. The owner reserves right of first refusal on equipment items and materials removed from the building. Specific demolition keynotes direct contractors to temporarily support existing grilles and diffusers during ceiling removal and reinstall them within new ceiling grids, and to remove existing return grilles as required. The contractor bears responsibility for any damages incurred during demolition work, storage losses, and patch repairs to wall, floor, ceiling, and roof openings unless assigned to other trades. The document also notes that if asbestos-containing materials are encountered, such removal or encapsulation will be performed by the owner under a separate contract.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SD

SD

F/S

F/S

SD

M

H

T S

T R

CO2

S

PI

SD

FS

PS

PI

TW

F

TI

PT

T

T

T

BF

BF

HVAC SYMBOLS

THERMOSTAT / SENSOR

RADIANT FLOOR THERMOSTAT

HUMIDISTAT

CARBON DIOXIDE SENSOR

OPPOSED BLADE DAMPER

MOTOR OPERATED DAMPER

VOLUME DAMPER

FIRE DAMPER (THRU FLOOR)

FIRE DAMPER (THRU WALL)

SMOKE DAMPER (THRU FLOOR)

SMOKE DAMPER (THRU WALL)

PARALLEL BLADE DAMPER

COMBINATION FIRE/SMOKE DAMPER

(THRU FLOOR)

DUCT SMOKE DETECTOR

COMBINATION FIRE/SMOKE DAMPER

(THRU WALL)

CONNECT TO EXISTING

VALVE SYMBOLS

GATE VALVE

BALL VALVE

GLOBE VALVE

BUTTERFLY VALVE

SWING CHECK VALVE

TRIPLE-DUTY VALVE

PLUG VALVE

DIAPHRAGM VALVE

NEEDLE VALVE

ANGLE VALVE

PRESSURE REDUCING VALVE, SELF-

CONTAINED

EXT. PRESSURE REDUCING VALVE

CHECK VALVE

RELIEF / SAFETY VALVE

SOLENOID VALVE

HOSE BIBB

CALIBRATED BALANCING VALVE

TEMPERATURE CONTROL VALVE

CONTROL VALVE, 3-WAY

BACKFLOW PREVENTER

WITH DRIP PAN

INDICATES VALVE IS FLANGED (TYP)

CONNECT TO EXISTING

AUTOMATIC FLOW CONTROL VALVE

AFF

BOD

BOG

BOS

BOP

CUH

CONV

CO

EA

EF

OA

RA

SA

TOD

TOG

TOP

VD

VTR

UNO

ABOVE FINISHED FLOOR

BOTTOM OF DUCT

BOTTOM OF GRILLE

BOTTOM OF PIPE

BOTTOM OF STRUCTURE

CABINET UNIT HEATER

CONVECTOR

CLEAN-OUT

EXHAUST AIR

EXHAUST FAN

OUTSIDE AIR

RETURN AIR

SUPPLY AIR

TOP OF DUCT

TOP OF GRILLE

TOP OF PIPE

VOLUME DAMPER

VENT THRU ROOF

UNLESS NOTED OTHERWISE

TOS TOP OF STRUCTURE

CLG CEILING

CONN CONNECTION

CONT CONTINUATION

DN DOWN

DWG DRAWING

ETR EXISTING TO REMAIN

EX. EXISTING

FLR FLOOR

TYP TYPICAL

MAU MAKE-UP AIR UNIT

AHU AIR HANDLING UNIT

ERU ENERGY RECOVERY UNIT

MECHANICAL ABBREVIATIONS

SPECS. SPECIFICATIONS

UH UNIT HEATER

MAX MAXIMUM

MIN MINIMUM

MFR MANUFACTURER

ET EXPANSION TANK

RTU ROOF TOP UNIT

DW DOUBLE WALL

BCU BLOWER COIL UNIT

FCU FAN COIL UNIT

ECM ELECTRONICALLY COMMUTATED MOTOR

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

ALL DRAWINGS ARE DIAGRAMMATIC IN NATURE, AND ARE INTENDED TO SHOW

THE GENERAL LAYOUT OF SYSTEMS AND EQUIPMENT. THE EXACT LOCATIONS

OF EQUIPMENT AND THE FINAL DUCTWORK LAYOUTS ARE THE

RESPONSIBILITY OF THE CONTRACTOR, AND SHALL BE FIELD-DETERMINED.

COORDINATE WITH THE BUILDING ARCHITECTURE AND STRUCTURE, AND

WITH NEW AND EXISTING MECHANICAL AND ELECTRICAL SYSTEMS. WHERE

THE LAYOUT DIFFERS SIGNIFICANTLY FROM DESIGN, COORDINATE WITH THE

ARCHITECT/ENGINEER. RECORD ALL DIFFERENCES ON RECORD DRAWINGS.

COORDINATE LOCATIONS OF REGISTERS, DIFFUSERS AND GRILLES WITH THE

REFLECTED CEILING PLANS. COORDINATE ANY DISCREPANCIES WITH THE

ARCHITECT/ENGINEER PRIOR TO INSTALLATION.

INSTALL ALL THERMOSTATS/SPACE TEMPERATURE SENSORS AT 48 INCHES

ABOVE FINISHED FLOOR (TO TOP OF SENSOR). WHERE APPLICABLE, ALIGN

WITH LIGHT SWITCHES.

ALL THERMOSTATS AND SENSORS LOCATED ON EXTERIOR WALLS SHALL

HAVE INSULATED BACKPLATES.

WHERE INTERNALLY LINED OR DOUBLE-WALL DUCTWORK IS SHOWN, THE

DIMENSIONS SHOWN INDICATE THE REQUIRED INSIDE FREE AREA

DIMENSIONS.

THE CONTRACTOR SHALL EXAMINE THE CONDITION OF ALL EQUIPMENT PRIOR

TO INSTALLATION. DO NOT INSTALL DAMAGED EQUIPMENT.

WHERE CONNECTING NEW DUCTWORK TO EXISTING, SEAL JOINTS AIRTIGHT

AND REPAIR DAMAGED INSULATION TO MATCH NEW.

WHERE DUCTWORK IS EXPOSED, ROUTE AS HIGH AS PRACTICAL IN THE

SPACE UNLESS INDICATED OTHERWISE.

REFER TO ARCHITECTURAL CODE COMPLIANCE PLANS FOR THE LOCATIONS

OF FIRE/SMOKE RATED ASSEMBLIES.

PAINT VISIBLE INTERIOR SURFACES OF DUCTS AT REGISTERS, GRILLES,

DIFFUSERS AND LOUVERS FLAT BLACK.

WHERE POSSIBLE, INSTALL EQUIPMENT AND DEVICES REQUIRING SERVICE

OR MAINTENANCE IN ACCESSIBLE LOCATIONS. WHERE NOT POSSIBLE,

PROVIDE ACCESS DOORS, SIZED SUITABLY FOR THE REQUIRED PURPOSE.

COORDINATE ACCESS DOOR LOCATIONS AND SIZES WITH THE

ARCHITECT/ENGINEER.

PROVIDE MANUFACTURERS' RECOMMENDED CLEARANCES FOR AIR FLOW,

ELECTRICAL AND MAINTENANCE AROUND EQUIPMENT. WHERE CLEARANCES

ARE ALSO SHOWN ON THE DRAWINGS, PROVIDE THE MORE STRINGENT OF

THE REQUIRED CLEARANCES.

FLEXIBLE DUCTWORK CONNECTIONS TO RIGID DUCTWORK, TO AIR TERMINAL

UNITS AND TO REGISTERS, GRILLES AND DIFFUSERS SHALL BE CLAMPED AND

TAPED. ROUND CONNECTIONS SHALL HAVE VINYL DRAWBANDS AND TAPE.

TAPE SHALL MEET THE REQUIREMENTS OF U.L. 181B-FX.

FLEXIBLE DUCTWORK SHALL NOT BE USED ON RETURN AIR OR EXHAUST AIR

DUCT SYSTEMS EXCEPT WHERE EXPLICITLY SHOWN ON DRAWINGS.

GENERAL HVAC NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

THE OWNER RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIP OF ANY EQUIPMENT

ITEMS AND MATERIALS TO BE REMOVED FROM THE BUILDING AND SITE.

ALL MATERIALS AND EQUIPMENT REMOVED AND NOT SALVAGED OR RE-USED SHALL BECOME

THE PROPERTY OF THE CONTRACTOR, AND SHALL BE REMOVED FROM THE OWNER ’S

PROPERTY AND DISPOSED OF PROPERLY.

THE DRAWINGS ARE DIAGRAMMATIC IN NATURE, AND ARE BASED ON THE REVIEW OF

PREVIOUS DESIGN DRAWINGS (WHERE AVAILABLE) AND ON LIMITED FIELD INVESTIGATION.

THE CONTRACTOR IS RESPONSIBLE TO INVESTIGATE THE BUILDING AND SITE TO DETERMINE

THE FULL EXTENT OF DEMOLITION WORK REQUIRED. THE CONTRACTOR SHALL FIELD-VERIFY

THE ACTUAL LOCATIONS AND SIZES OF EXISTING DUCTWORK, PIPING AND EQUIPMENT.

WHERE DISCREPANCIES BETWEEN THE DRAWINGS AND THE EXISTING CONDITIONS RESULT IN

AN UNCLEAR DEMOLITION SCOPE, COORDINATE WITH THE ARCHITECT/ENGINEER.

WHERE DEMOLITION OF MATERIALS OR EQUIPMENT IS REQUIRED, REMOVE ALL RELATED

SUPPORTS, ACCESSORIES, LOW-VOLTAGE WIRING, PNEUMATIC TUBING AND CONTROLS

(CONCEALED OR EXPOSED). REMOVE WIRING TO THE NEAREST JUNCTION BOX, AND

PNEUMATIC TUBING TO THE NEAREST MAIN. WHERE A PNEUMATIC CONTROL SYSTEM IS TO

REMAIN ACTIVE, CAP AND SEAL TUBING AT MAINS.

ALL PIPING, DUCTWORK AND EQUIPMENT SHOWN CROSS-HATCHED OR BOLD DASHED SHALL

BE REMOVED OR RELOCATED UNLESS OTHERWISE NOTED.

VERIFY LOCATION AND PROTECT EXISTING WORK AND UTILITIES WHICH ARE TO REMAIN IN

PLACE WITH TEMPORARY COVERS, SHORING, BRACING AND SUPPORTS.

ALL MATERIALS AND EQUIPMENT REQUIRING REMOVAL AND REINSTALLATION FOR RE-USE

SHALL BE CAREFULLY REMOVED AND STORED TO PREVENT DAMAGE. THE CONTRACTOR IS

RESPONSIBLE FOR LOSS OF OR DAMAGE TO STORED MATERIALS AND EQUIPMENT.

WHERE ON-SITE STORAGE OF MATERIAL AND EQUIPMENT IS PERMITTED, COORDINATE

STORAGE LOCATION(S) WITH THE OWNER.

PROTECT THE BUILDING STRUCTURE AND FINISHES AND ALL BUILDING SYSTEMS DURING

DEMOLITION. THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGES INCURRED AS A RESULT

OF DEMOLITION WORK.

UNLESS ASSIGNED TO ANOTHER TRADE, PATCH AND REPAIR ALL WALL, FLOOR AND CEILING

OPENINGS DUE TO DEMOLITION WHICH ARE NOT TO BE RE-USED. MATCH EXISTING

SURROUNDING CONSTRUCTION, FINISHES, COLORS AND FIRE/SMOKE RATINGS.

UNLESS ASSIGNED TO ANOTHER TRADE, PATCH AND REPAIR ROOF IN A MANNER WHICH WILL

MAINTAIN THE WATER-TIGHT INTEGRITY OF THE ROOF. WHERE A ROOF WARRANTY EXISTS,

PERFORM THE WORK IN A MANNER WHICH WILL MAINTAIN THE WARRANTY.

IF MATERIALS SUSPECTED OF CONTAINING ASBESTOS ARE ENCOUNTERED, NOTIFY THE

OWNER IMMEDIATELY. WHERE REMOVAL OR ENCAPSULATION IS REQUIRED, SUCH WORK

WILL BE PERFORMED BY THE OWNER UNDER A SEPARATE CONTRACT.

GENERAL MECHANICAL DEMOLITION NOTES: HVAC SHEETMETAL SYMBOLS

MITERED ELBOW (RECTANGULAR, ROUND & OVAL)

TURNING VANES REQUIRED PER SPECIFICATIONS

RECTANGULAR DUCTWORK RISE

RECTANGULAR DUCTWORK

ROUND DUCTWORK

OVAL DUCTWORK

LINED DUCTWORK

FLEXIBLE DUCTWORK (SUPPLY)

SUPPLY DIFFUSER (S-X)

RETURN GRILLE (R-X)

EXHAUST GRILLE (E-X)

LINEAR SLOT DIFFUSER (S-X)

RECTANGULAR OR ROUND MANUAL DAMPER

SIDEWALL DIFFUSER OR GRILLE

RECTANGULAR OR ROUND MOTORIZED DAMPER

RECTANGULAR OR ROUND FIRE / SMOKE DAMPER

RECTANGULAR OR ROUND FIRE DAMPER

M

F/S

DUCTWORK / DIFFUSER DEMOLITION

X"xX" SA

X"ø SA

X"/X"ø SA

X"xX" LINED SA

RECTANGULAR DUCTWORK DROP

ROUND DUCTWORK RISE

ROUND DUCTWORK DROP

OR

R DUCTWORK RISE SYMBOL

D DUCTWORK DROP SYMBOL

VAV TERMINAL BOX

DOUBLE WALL DUCTWORKX"xX" DW SA

PIPING & INSTR. SYMBOLS

ECCENTRIC REDUCER

CONCENTRIC REDUCER

SUCTION DIFFUSER

UNION

CAP

"Y" STRAINER W/ BLOWDOWN

COMPRESSED AIR

COMB. FILTER, REG. & OILER

FLOW SWITCH

PRESSURE SWITCH

PRESSURE TAP

THERMOWELL

FLEXIBLE CONNECTOR

PRESSURE GAUGE & SHUT OFF

THERMOMETER

PRESSURE GAUGE W/ SIPHON

EMERGENCY EYE WASH / SHOWER

ANCHOR

GUIDE

GENERAL / THERMODYNAMIC TRAP

INVERTED BUCKET TRAP

FLOAT & THERMOSTATIC TRAP

BLIND FLANGE

AIR VENT

HIGH CAPACITY AIR VENT

THERAPY POOL

B132

D12

D12

D12

D13

D12

D12

D12

D12

D12

EX. 20"x20" SA

EX. 20"x20" RA

PROJECT NO.

DRAWN

REVIEWED

NO PART OF THIS DRAWING MAY BE

USED OR REPRODUCED IN ANY FORM

OR BY ANY MEANS, OR STORED IN A

DATA BASE OR RETRIEVAL SYSTEM,

WITHOUT PRIOR WRITTEN

PERMISSION OF

ALL RIGHTS RESERVED

c

KEYPLAN

ISSUANCES

GMB COPYRIGHT

Au to de sk

D oc s:

//5

-6

VB

IS

D

B er t G oe ns L ea rn in g

C en te r P oo l I m pr ov em en ts

/5 -6

2M

5.

rv t

6/ 8/

:0

4:

P M

M0.0.01

5-6732

MECHANICAL GENERAL

INFORMATION

RTF

JMW

B E

R T

G O

E N

S L

E A

R N

IN

G

C E

N T

E R

P O

O L

IM

P

R O

V E

M E

N T

S

V A

N B

U R

E N

IN

TE

R M

E D

IA

TE

S C

H O

O L

D

IS

TR

IC

T

LA

W R

E N

C E

M

IC

H

IG

A

N

1/16" = 1'-0"

UNIT 'B' MECHANICAL DEMOLITION PLAN

MECHANICAL DEMO KEYNOTE LEGEND

D12 TEMPORARILY SUPPORT EXISTING GRILLE/DIFFUSER AS

REQUIRED FOR CEILING REMOVAL. CLEAN AND REINSTALL

EXISTING DIFFUSER/GRILLE WITHIN NEW CEILING GRID.

D13 REMOVE EXISTING RETURN GRILLE.

UNIT A

UNIT B

UNIT C

05.21.2026 BIDS &

CONSTRUCTION

06.08.2026 ADDENDUM 002

M0.0.01 - MECHANICAL GENERAL INFORMATION