This is a Mechanical General Information drawing sheet for the Bert Goens Learning Center Pool Improvements project located in Lawrence, Michigan, prepared for the Van Buren Intermediate School District. The document serves as a schematic design plan detailing HVAC systems, mechanical demolition requirements, and installation guidelines for Unit B of the pool facility. The drawing includes comprehensive symbol legends for HVAC components, valve types, ductwork configurations, and piping instruments, along with detailed notes regarding equipment installation, coordination requirements, and field verification responsibilities. Key dates noted include a bid and construction start date of May 21, 2026, with an addendum issued on June 8, 2026. The drawing emphasizes that contractors are responsible for field-verifying existing conditions, determining the full extent of demolition work, and coordinating with architectural and engineering teams where discrepancies exist between design drawings and actual site conditions.
The document specifies general mechanical demolition notes and installation requirements, including contractor responsibilities for investigating building conditions, protecting existing utilities and structures, and properly disposing of removed materials and equipment. The owner reserves right of first refusal on equipment items and materials removed from the building. Specific demolition keynotes direct contractors to temporarily support existing grilles and diffusers during ceiling removal and reinstall them within new ceiling grids, and to remove existing return grilles as required. The contractor bears responsibility for any damages incurred during demolition work, storage losses, and patch repairs to wall, floor, ceiling, and roof openings unless assigned to other trades. The document also notes that if asbestos-containing materials are encountered, such removal or encapsulation will be performed by the owner under a separate contract.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SD
SD
F/S
F/S
SD
M
H
T S
T R
CO2
S
PI
SD
FS
PS
PI
TW
F
TI
PT
T
T
T
BF
BF
HVAC SYMBOLS
THERMOSTAT / SENSOR
RADIANT FLOOR THERMOSTAT
HUMIDISTAT
CARBON DIOXIDE SENSOR
OPPOSED BLADE DAMPER
MOTOR OPERATED DAMPER
VOLUME DAMPER
FIRE DAMPER (THRU FLOOR)
FIRE DAMPER (THRU WALL)
SMOKE DAMPER (THRU FLOOR)
SMOKE DAMPER (THRU WALL)
PARALLEL BLADE DAMPER
COMBINATION FIRE/SMOKE DAMPER
(THRU FLOOR)
DUCT SMOKE DETECTOR
COMBINATION FIRE/SMOKE DAMPER
(THRU WALL)
CONNECT TO EXISTING
VALVE SYMBOLS
GATE VALVE
BALL VALVE
GLOBE VALVE
BUTTERFLY VALVE
SWING CHECK VALVE
TRIPLE-DUTY VALVE
PLUG VALVE
DIAPHRAGM VALVE
NEEDLE VALVE
ANGLE VALVE
PRESSURE REDUCING VALVE, SELF-
CONTAINED
EXT. PRESSURE REDUCING VALVE
CHECK VALVE
RELIEF / SAFETY VALVE
SOLENOID VALVE
HOSE BIBB
CALIBRATED BALANCING VALVE
TEMPERATURE CONTROL VALVE
CONTROL VALVE, 3-WAY
BACKFLOW PREVENTER
WITH DRIP PAN
INDICATES VALVE IS FLANGED (TYP)
CONNECT TO EXISTING
AUTOMATIC FLOW CONTROL VALVE
AFF
BOD
BOG
BOS
BOP
CUH
CONV
CO
EA
EF
OA
RA
SA
TOD
TOG
TOP
VD
VTR
UNO
ABOVE FINISHED FLOOR
BOTTOM OF DUCT
BOTTOM OF GRILLE
BOTTOM OF PIPE
BOTTOM OF STRUCTURE
CABINET UNIT HEATER
CONVECTOR
CLEAN-OUT
EXHAUST AIR
EXHAUST FAN
OUTSIDE AIR
RETURN AIR
SUPPLY AIR
TOP OF DUCT
TOP OF GRILLE
TOP OF PIPE
VOLUME DAMPER
VENT THRU ROOF
UNLESS NOTED OTHERWISE
TOS TOP OF STRUCTURE
CLG CEILING
CONN CONNECTION
CONT CONTINUATION
DN DOWN
DWG DRAWING
ETR EXISTING TO REMAIN
EX. EXISTING
FLR FLOOR
TYP TYPICAL
MAU MAKE-UP AIR UNIT
AHU AIR HANDLING UNIT
ERU ENERGY RECOVERY UNIT
MECHANICAL ABBREVIATIONS
SPECS. SPECIFICATIONS
UH UNIT HEATER
MAX MAXIMUM
MIN MINIMUM
MFR MANUFACTURER
ET EXPANSION TANK
RTU ROOF TOP UNIT
DW DOUBLE WALL
BCU BLOWER COIL UNIT
FCU FAN COIL UNIT
ECM ELECTRONICALLY COMMUTATED MOTOR
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ALL DRAWINGS ARE DIAGRAMMATIC IN NATURE, AND ARE INTENDED TO SHOW
THE GENERAL LAYOUT OF SYSTEMS AND EQUIPMENT. THE EXACT LOCATIONS
OF EQUIPMENT AND THE FINAL DUCTWORK LAYOUTS ARE THE
RESPONSIBILITY OF THE CONTRACTOR, AND SHALL BE FIELD-DETERMINED.
COORDINATE WITH THE BUILDING ARCHITECTURE AND STRUCTURE, AND
WITH NEW AND EXISTING MECHANICAL AND ELECTRICAL SYSTEMS. WHERE
THE LAYOUT DIFFERS SIGNIFICANTLY FROM DESIGN, COORDINATE WITH THE
ARCHITECT/ENGINEER. RECORD ALL DIFFERENCES ON RECORD DRAWINGS.
COORDINATE LOCATIONS OF REGISTERS, DIFFUSERS AND GRILLES WITH THE
REFLECTED CEILING PLANS. COORDINATE ANY DISCREPANCIES WITH THE
ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
INSTALL ALL THERMOSTATS/SPACE TEMPERATURE SENSORS AT 48 INCHES
ABOVE FINISHED FLOOR (TO TOP OF SENSOR). WHERE APPLICABLE, ALIGN
WITH LIGHT SWITCHES.
ALL THERMOSTATS AND SENSORS LOCATED ON EXTERIOR WALLS SHALL
HAVE INSULATED BACKPLATES.
WHERE INTERNALLY LINED OR DOUBLE-WALL DUCTWORK IS SHOWN, THE
DIMENSIONS SHOWN INDICATE THE REQUIRED INSIDE FREE AREA
DIMENSIONS.
THE CONTRACTOR SHALL EXAMINE THE CONDITION OF ALL EQUIPMENT PRIOR
TO INSTALLATION. DO NOT INSTALL DAMAGED EQUIPMENT.
WHERE CONNECTING NEW DUCTWORK TO EXISTING, SEAL JOINTS AIRTIGHT
AND REPAIR DAMAGED INSULATION TO MATCH NEW.
WHERE DUCTWORK IS EXPOSED, ROUTE AS HIGH AS PRACTICAL IN THE
SPACE UNLESS INDICATED OTHERWISE.
REFER TO ARCHITECTURAL CODE COMPLIANCE PLANS FOR THE LOCATIONS
OF FIRE/SMOKE RATED ASSEMBLIES.
PAINT VISIBLE INTERIOR SURFACES OF DUCTS AT REGISTERS, GRILLES,
DIFFUSERS AND LOUVERS FLAT BLACK.
WHERE POSSIBLE, INSTALL EQUIPMENT AND DEVICES REQUIRING SERVICE
OR MAINTENANCE IN ACCESSIBLE LOCATIONS. WHERE NOT POSSIBLE,
PROVIDE ACCESS DOORS, SIZED SUITABLY FOR THE REQUIRED PURPOSE.
COORDINATE ACCESS DOOR LOCATIONS AND SIZES WITH THE
ARCHITECT/ENGINEER.
PROVIDE MANUFACTURERS' RECOMMENDED CLEARANCES FOR AIR FLOW,
ELECTRICAL AND MAINTENANCE AROUND EQUIPMENT. WHERE CLEARANCES
ARE ALSO SHOWN ON THE DRAWINGS, PROVIDE THE MORE STRINGENT OF
THE REQUIRED CLEARANCES.
FLEXIBLE DUCTWORK CONNECTIONS TO RIGID DUCTWORK, TO AIR TERMINAL
UNITS AND TO REGISTERS, GRILLES AND DIFFUSERS SHALL BE CLAMPED AND
TAPED. ROUND CONNECTIONS SHALL HAVE VINYL DRAWBANDS AND TAPE.
TAPE SHALL MEET THE REQUIREMENTS OF U.L. 181B-FX.
FLEXIBLE DUCTWORK SHALL NOT BE USED ON RETURN AIR OR EXHAUST AIR
DUCT SYSTEMS EXCEPT WHERE EXPLICITLY SHOWN ON DRAWINGS.
GENERAL HVAC NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
THE OWNER RESERVES THE RIGHT OF FIRST REFUSAL IN OWNERSHIP OF ANY EQUIPMENT
ITEMS AND MATERIALS TO BE REMOVED FROM THE BUILDING AND SITE.
ALL MATERIALS AND EQUIPMENT REMOVED AND NOT SALVAGED OR RE-USED SHALL BECOME
THE PROPERTY OF THE CONTRACTOR, AND SHALL BE REMOVED FROM THE OWNER ’S
PROPERTY AND DISPOSED OF PROPERLY.
THE DRAWINGS ARE DIAGRAMMATIC IN NATURE, AND ARE BASED ON THE REVIEW OF
PREVIOUS DESIGN DRAWINGS (WHERE AVAILABLE) AND ON LIMITED FIELD INVESTIGATION.
THE CONTRACTOR IS RESPONSIBLE TO INVESTIGATE THE BUILDING AND SITE TO DETERMINE
THE FULL EXTENT OF DEMOLITION WORK REQUIRED. THE CONTRACTOR SHALL FIELD-VERIFY
THE ACTUAL LOCATIONS AND SIZES OF EXISTING DUCTWORK, PIPING AND EQUIPMENT.
WHERE DISCREPANCIES BETWEEN THE DRAWINGS AND THE EXISTING CONDITIONS RESULT IN
AN UNCLEAR DEMOLITION SCOPE, COORDINATE WITH THE ARCHITECT/ENGINEER.
WHERE DEMOLITION OF MATERIALS OR EQUIPMENT IS REQUIRED, REMOVE ALL RELATED
SUPPORTS, ACCESSORIES, LOW-VOLTAGE WIRING, PNEUMATIC TUBING AND CONTROLS
(CONCEALED OR EXPOSED). REMOVE WIRING TO THE NEAREST JUNCTION BOX, AND
PNEUMATIC TUBING TO THE NEAREST MAIN. WHERE A PNEUMATIC CONTROL SYSTEM IS TO
REMAIN ACTIVE, CAP AND SEAL TUBING AT MAINS.
ALL PIPING, DUCTWORK AND EQUIPMENT SHOWN CROSS-HATCHED OR BOLD DASHED SHALL
BE REMOVED OR RELOCATED UNLESS OTHERWISE NOTED.
VERIFY LOCATION AND PROTECT EXISTING WORK AND UTILITIES WHICH ARE TO REMAIN IN
PLACE WITH TEMPORARY COVERS, SHORING, BRACING AND SUPPORTS.
ALL MATERIALS AND EQUIPMENT REQUIRING REMOVAL AND REINSTALLATION FOR RE-USE
SHALL BE CAREFULLY REMOVED AND STORED TO PREVENT DAMAGE. THE CONTRACTOR IS
RESPONSIBLE FOR LOSS OF OR DAMAGE TO STORED MATERIALS AND EQUIPMENT.
WHERE ON-SITE STORAGE OF MATERIAL AND EQUIPMENT IS PERMITTED, COORDINATE
STORAGE LOCATION(S) WITH THE OWNER.
PROTECT THE BUILDING STRUCTURE AND FINISHES AND ALL BUILDING SYSTEMS DURING
DEMOLITION. THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGES INCURRED AS A RESULT
OF DEMOLITION WORK.
UNLESS ASSIGNED TO ANOTHER TRADE, PATCH AND REPAIR ALL WALL, FLOOR AND CEILING
OPENINGS DUE TO DEMOLITION WHICH ARE NOT TO BE RE-USED. MATCH EXISTING
SURROUNDING CONSTRUCTION, FINISHES, COLORS AND FIRE/SMOKE RATINGS.
UNLESS ASSIGNED TO ANOTHER TRADE, PATCH AND REPAIR ROOF IN A MANNER WHICH WILL
MAINTAIN THE WATER-TIGHT INTEGRITY OF THE ROOF. WHERE A ROOF WARRANTY EXISTS,
PERFORM THE WORK IN A MANNER WHICH WILL MAINTAIN THE WARRANTY.
IF MATERIALS SUSPECTED OF CONTAINING ASBESTOS ARE ENCOUNTERED, NOTIFY THE
OWNER IMMEDIATELY. WHERE REMOVAL OR ENCAPSULATION IS REQUIRED, SUCH WORK
WILL BE PERFORMED BY THE OWNER UNDER A SEPARATE CONTRACT.
GENERAL MECHANICAL DEMOLITION NOTES: HVAC SHEETMETAL SYMBOLS
MITERED ELBOW (RECTANGULAR, ROUND & OVAL)
TURNING VANES REQUIRED PER SPECIFICATIONS
RECTANGULAR DUCTWORK RISE
RECTANGULAR DUCTWORK
ROUND DUCTWORK
OVAL DUCTWORK
LINED DUCTWORK
FLEXIBLE DUCTWORK (SUPPLY)
SUPPLY DIFFUSER (S-X)
RETURN GRILLE (R-X)
EXHAUST GRILLE (E-X)
LINEAR SLOT DIFFUSER (S-X)
RECTANGULAR OR ROUND MANUAL DAMPER
SIDEWALL DIFFUSER OR GRILLE
RECTANGULAR OR ROUND MOTORIZED DAMPER
RECTANGULAR OR ROUND FIRE / SMOKE DAMPER
RECTANGULAR OR ROUND FIRE DAMPER
M
F/S
DUCTWORK / DIFFUSER DEMOLITION
X"xX" SA
X"ø SA
X"/X"ø SA
X"xX" LINED SA
RECTANGULAR DUCTWORK DROP
ROUND DUCTWORK RISE
ROUND DUCTWORK DROP
OR
R DUCTWORK RISE SYMBOL
D DUCTWORK DROP SYMBOL
VAV TERMINAL BOX
DOUBLE WALL DUCTWORKX"xX" DW SA
PIPING & INSTR. SYMBOLS
ECCENTRIC REDUCER
CONCENTRIC REDUCER
SUCTION DIFFUSER
UNION
CAP
"Y" STRAINER W/ BLOWDOWN
COMPRESSED AIR
COMB. FILTER, REG. & OILER
FLOW SWITCH
PRESSURE SWITCH
PRESSURE TAP
THERMOWELL
FLEXIBLE CONNECTOR
PRESSURE GAUGE & SHUT OFF
THERMOMETER
PRESSURE GAUGE W/ SIPHON
EMERGENCY EYE WASH / SHOWER
ANCHOR
GUIDE
GENERAL / THERMODYNAMIC TRAP
INVERTED BUCKET TRAP
FLOAT & THERMOSTATIC TRAP
BLIND FLANGE
AIR VENT
HIGH CAPACITY AIR VENT
THERAPY POOL
B132
D12
D12
D12
D13
D12
D12
D12
D12
D12
EX. 20"x20" SA
EX. 20"x20" RA
PROJECT NO.
DRAWN
REVIEWED
NO PART OF THIS DRAWING MAY BE
USED OR REPRODUCED IN ANY FORM
OR BY ANY MEANS, OR STORED IN A
DATA BASE OR RETRIEVAL SYSTEM,
WITHOUT PRIOR WRITTEN
PERMISSION OF
ALL RIGHTS RESERVED
c
KEYPLAN
ISSUANCES
GMB COPYRIGHT
Au to de sk
D oc s:
//5
-6
VB
IS
D
B er t G oe ns L ea rn in g
C en te r P oo l I m pr ov em en ts
/5 -6
2M
5.
rv t
6/ 8/
:0
4:
P M
M0.0.01
5-6732
MECHANICAL GENERAL
INFORMATION
RTF
JMW
B E
R T
G O
E N
S L
E A
R N
IN
G
C E
N T
E R
P O
O L
IM
P
R O
V E
M E
N T
S
V A
N B
U R
E N
IN
TE
R M
E D
IA
TE
S C
H O
O L
D
IS
TR
IC
T
LA
W R
E N
C E
M
IC
H
IG
A
N
1/16" = 1'-0"
UNIT 'B' MECHANICAL DEMOLITION PLAN
MECHANICAL DEMO KEYNOTE LEGEND
D12 TEMPORARILY SUPPORT EXISTING GRILLE/DIFFUSER AS
REQUIRED FOR CEILING REMOVAL. CLEAN AND REINSTALL
EXISTING DIFFUSER/GRILLE WITHIN NEW CEILING GRID.
D13 REMOVE EXISTING RETURN GRILLE.
UNIT A
UNIT B
UNIT C
05.21.2026 BIDS &
CONSTRUCTION
06.08.2026 ADDENDUM 002
M0.0.01 - MECHANICAL GENERAL INFORMATION