5-6732 E2.2.1A.pdf
PDF 191 KB Posted
- Solicitation number
- RFP VBI 260000002079 3
- Issued by
- Van Buren County, Michigan
About this file
Summary of 5-6732 E2.2.1A.pdf
This document appears to be a specification or technical exhibit related to the Bert Goens Learning Center Pool Improvements project administered by a Michigan state or local government entity. The file contains detailed technical requirements and specifications for pool improvement work, though the complete scope of services, project timeline, response deadlines, and bidder meeting information cannot be fully determined from the referenced document title and index alone. Standard procurement processes would typically include site visits, a pre-bid meeting or bidders' conference, and a specified submission deadline, with contract award following evaluation of competitive proposals.
Pricing information, contract term details, funding sources, and any applicable set-asides or preferences would be documented in the full RFP package. The project involves improvements to an educational facility's aquatic amenities, which may include upgrades to pool systems, structural components, safety features, or related infrastructure. Prospective bidders should consult the complete RFP documentation for comprehensive information regarding budget allocations, technical specifications, evaluation criteria, and all contractual terms and conditions.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BF BF
BF
BF BF
BF
BF BF
BF BF
BF
BF
C
C
S1
S1
AV
AV
AV
1.
2.
3.
4.
5.
6.
REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.0.01.
REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF
VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE
FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE
CODES.
ALL GENERAL-USE 15- AND 20-AMPERE, 125- AND 250-VOLT NON-LOCKING
RECEPTACLES SHALL BE TAMPER-RESISTANT TYPE; REFER TO NEC 406.12 AND
SPECIFICATION SECTION 26 27 26.
REFER TO LIGHTING CONTROL SCHEDULES, GENERAL NOTES, AND
SPECIFICATIONS FOR AUTOMATIC RECEPTACLE CONTROL REQUIREMENTS.
PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN
ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR
PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS
CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES
INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST
FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.
DESIGNATED CABLING PATHWAYS (CONDUITS, CABLE TRAYS, PENETRATION
SLEEVES, ETC.) SHALL BE RESERVED FOR DIV. 27 COMMUNICATIONS CABLING
AND DIV. 28 SAFETY/SECURITY CABLING ONLY. OTHER CABLING TYPES, SUCH
AS DIV. 23 CONTROLS, DIV. 26 CONTROLS, AND ARCHITECTURAL EQUIPMENT
CABLING SHALL BE SUPPORTED AND SLEEVED BY OTHER INDEPENDENT
PATHWAYS, HANGERS, AND SUPPORTS.
POWER & COMMUNICATION GENERAL NOTES
EX. PANEL 'BPA' EX. SWITCHBOARD 'ESE'
MECHANICAL
STORAGE AND RECEIVING
SEQ-10
SEQ-10SEQ-9
SEQ-8
SEQ-5
SEQ-7
SEQ-6
SEQ-1
SP-1
SEQ-2
UV CTRL
PANEL
SEQ-4
RAIL
HANDRAIL
DOOR FRAME WINDOW FRAME
WINDOW FRAMEDOOR FRAME
LADDER
P01
P06
EX.
PUMP
GFCI
44"
GFCI
GFCI
GFCI
44"
P04
P05
P05
P04
EX. PANEL 'G1'
G1-31,33,35
G1-25
G1-23
G1-34,36
G1-32
G1-27
G1-30
G1-29
P01
P07
P03
GIRLS LOCKER ROOM
BOYS LOCKER ROOM
B133
THERAPY POOL
B132
PLUMB. FIXT. PSU
ABOVE CLG.
P02
P03
E2.2.1A
TYP
MOUNT ON STRUT
G1-28
1D 44"
B132B
B132A
FLOOR GROMMET.
SEE ARCH.
FLOOR GROMMET.
SEE ARCH.
P08
STEEL REINFORCING
SHELL AND DECK
DIVE STAND
BONDING GENERAL NOTE:
PROVIDE A SWIMMING POOL EQUIPOTENTIAL BONDING SYSTEM PER NEC 680.26.
THE POOL AND ALL ASSOCIATED POOL WATER CIRCULATING SYSTEMS/EQUIPMENT
THAT ARE PRESENT SHALL BE BONDED, INCLUDING BUT NOT LIMITED TO:
CONDUCTIVE POOL SHELLS
POOL PERIMETER DECK/SURFACES
METALLIC COMPONENTS OF THE POOL STRUCTURE
UNDERWATER LIGHTING
METAL FITTINGS (CUP ANCHORS, STANCHION POST ANCHORS, WEDGE
ANCHORS OF GRAB RAILS, POOL LIFT ANCHORS, DRAIN FITTINGS, ETC.)
ELECTRICAL EQUIPMENT
FIXED METAL PARTS (CABLE SHEATHS, RACEWAYS, PIPING, AWNINGS, FENCES,
DOOR/WINDOW FRAMES, POOL LIFTS, ETC.)
POOL WATER WHERE NOT IN DIRECT CONNECTION WITH BONDED PARTS
THE BONDING CONDUCTOR SHALL BE MINIMUM #8 AWG BARE SOLID COPPER.
REFER TO NEC FOR FURTHER DETAILS AND EXCEPTIONS.
GRAB RAILS
ELECTRICAL EQUIPMENT
ASSOCIATED WITH POOL OR POOL
WATER CIRCULATING SYSTEM
ANCHORS
POSTS
BONDING CONDUCTOR
LISTED SPLICE PER
SECTION 26 05 26, TYP.
HANDRAILS
JUNCTION BOX
2-GANG BOX
(VERIFY)
2-GANG BOX
(VERIFY)
SINGLE-GANG STAINLESS STEEL COVER PLATE
WITH 1/2" CORD GRIP FITTING FOR CABLE EXIT
THROUGH CENTER OF COVER. LOCATE BOX AS
HIGH AS POSSIBLE UNDER LAVATORY TO
MINIMIZE LENGTH OF EXPOSED POWER CABLE
1/2" CONDUIT STUBBED
ABOVE ACCESSIBLE
CEILING
SHARED POWER TRANSFORMER(S) FOR MULTIPLE PLUMBING FIXTURES
BY SECTION 22 40 00, MOUNTED TO BOX ABOVE ACCESSIBLE CEILING
1/2" CONDUIT STUBBED
ABOVE ACCESSIBLE CEILING
SUSPENDED CEILING
FINISHED FLOOR
120VAC POWER FROM SPECIFIED PANELBOARD BY DIV. 26
CONTROL-VOLTAGE CABLE PER PLUMBING
FIXTURE/VALVE MANUFACTURER BY SECTION 22 40 00
PROJECT NO.
DRAWN
REVIEWED
NO PART OF THIS DRAWING MAY BE
USED OR REPRODUCED IN ANY FORM
OR BY ANY MEANS, OR STORED IN A
DATA BASE OR RETRIEVAL SYSTEM,
WITHOUT PRIOR WRITTEN
PERMISSION OF
ALL RIGHTS RESERVED
c
KEYPLAN
ISSUANCES
GMB COPYRIGHT
Au to de sk
D oc s:
//5
-6
VB
IS
D
B er t G oe ns L ea rn in g
C en te r P oo l I m pr ov em en ts
/5 -6
2E
5.
rv t
6/ 9/
:4
3:
A M
E2.2.1A
5-6732
UNIT 'A' FIRST FLOOR POWER
& COMMUNICATIONS PLAN
JDM
PRH
B E
R T
G O
E N
S L
E A
R N
IN
G
C E
N T
E R
P O
O L
IM
P
R O
V E
M E
N T
S
V A
N B
U R
E N
IN
TE
R M
E D
IA
TE
S C
H O
O L
D
IS
TR
IC
T
LA
W R
E N
C E
M
IC
H
IG
A
N
ELECTRICAL KEYNOTES
P01 POOL EQUIPOTENTIAL BONDING SYSTEM SHOWN IS DIAGRAMATIC.
PROVIDE #8 AWG COPPER GROUND RING. CUT AND PATCH FLOOR AS
NECESSARY TO INSTALL BONDING SYSTEM. THE BONDING SYSTEM IS NOT
REQUIRED TO BE BELOW GRADE IN MECHANICAL 131. REFER TO NEC 680
AND DETAIL 2, THIS SHEET, FOR ADDITIONAL REQUIREMENTS. CONFIRM
ALL BONDING POINTS IN FIELD.
P02 EXTEND THE EXISTING BRANCH CIRCUIT FROM THE DEMOLISHED
ELECTRIC HAND DRYER TO THE PLUMBING FIXTURES PSU. REFER TO
E2.1.1A FOR DEMOLITION KEYNOTES. PSU SHALL SERVE BOTH LOCKER
ROOMS.
P03 EXTEND THE EXISTING BRANCH CIRCUIT FROM THE DEMOLISHED DUPLEX
RECEPTACLE TO THE NEW DUPLEX RECEPTACLES. REFER TO E2.1.1A FOR
DEMOLITION KEYNOTES.
P04 EXTEND THE EXISTING SPEAKER CIRCUIT FROM THE DEMOLISHED PUBLIC
ADDRESS SPEAKER TO THE NEW PUBLIC ADDRESS SPEAKER. REFER TO
E2.1.1A FOR DEMOLITION KEYNOTES.
P05 THE CLOCK SHALL BE OWNER PROVIDED, CONTRACTOR INSTALLED.
PROVIDE DATA OUTLET WITH MALE CONNECTOR AT CLOCK. PROVIDE ALL
NECESSARY HARDWARE AND INFRASTRUCTURE FOR INSTALLATION OF
OWNER-PROVIDED CLOCK. REFER TO KEYPLAN FOR APPROXIMATE
LOCATION OF IDF.
P06 ALL NEW RECEPTACLES SHALL BE GFCI TYPE.
P07 TERMINATE POOL EQUIPOTENTIAL BONDING CONDUCTOR TO GROUND BUS
IN PANELBOARD.
P08 ROUTE TELECOMMUNICATION CABLING IN CHASE AND STUB THROUGH
WALL. MOUNT OUTLET IN TELEPHONE BOX.
1/4" = 1'-0"
UNIT 'A' FIRST FLOOR POWER & COMMUNICATIONS PLAN
NOT TO SCALEE2.2.1A
2 SWIMMING POOL EQUIPOTENTIAL BONDING DETAIL
UNIT A
UNIT B
UNIT C
NOT TO SCALEE2.2.1A
1 TYPICAL PLUMBING FIXTURE ELECTRICAL ROUGH-IN DETAIL
NOTES: PROVIDE NEW CIRCUIT BREAKERS FOR ALL NEW BRANCH CIRCUITS. EXISTING LOADS ARE ASSUMED.
TOTAL CONNECTED CURRENT: 122 A
TOTAL CONNECTED LOAD: 43.9 kVA
PHASE LOAD: 13,102 VA 14,248 VA 16,598 VA
G1-41 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE G1-42
G1-39 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE G1-40
G1-37 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE G1-38
G1-35 2,102 2,496 G1-36 G1-33 2,102 2,496
2 30 A CHLORINE GENERATOR SYSTEM (SEQ-10) (GFCI)
G1-34
G1-31 SP-1
(5HP)
(GFCI)
35 A 3
2,102 1,200 1 20 A REC. - BACKUP CHLORINE FEED SYSTEM (SEQ-9) G1-32
G1-29 REC. - CHLORINE GENERATOR SYSTEM (SEQ-10) 20 A 1 1,200 2,400 1 20 A REC. - CHEM. CTRL (SEQ-5) & H2O LEVEL CTRL (SEQ-7) G1-30 G1-27 REC. - ACID FEED PUMP (SEQ-8) 20 A 1 1,200 1,200 1 20 A REC. - AIR COMPRESSOR (SEQ-2) G1-28 G1-25 REC. - UV FILTER (SEQ-4) & UV CONTROL PANEL 20 A 1 1,350 0 1 20 A SPARE G1-26 G1-23 REC. - POOL FILTER (SEQ-1) 20 A 1 1,200 1,200 1 20 A EX. LOAD - U.V. TREATMENT POWER SUPPPLY G1-24 G1-21 EX. LOAD - UNKNOWN 20 A 1 1,200 1,200 1 20 A EX. LOAD - BOILER #2 PUMP G1-22 G1-19 EX. LOAD - U.V. #8 RM 148 20 A 1 1,200 1,200 1 20 A EX. LOAD - BOILER #1 PUMP G1-20
G1-17 EX. LOAD - U.V. #7 RM 147 20 A 1 1,200 0 G1-18
G1-15 EX. LOAD - U.V. #6 RM 140 20 A 1 1,200 0
2 50 A SPARE
G1-16
G1-13 EX. LOAD - U.V. #5 RM 138 20 A 1 1,200 0 1 20 A SPARE G1-14
G1-11 1,200 1,200 1 20 A EX. LOAD - CHILLER CONTROL - HEATERS G1-12
G1-9 1,200 1,250 G1-10 G1-7
EX. LOAD - SUMP PUMPS 20 A 3
1,200 1,250
2 15 A EX. LOAD - CONTROL TRANSFORMER
G1-8
G1-5 EX. LOAD - DWH-1 20 A 1 1,200 1,200 1 20 A EX. LOAD - CONTROL PANEL SUMP PUMPS G1-6
G1-3 SPARE 20 A 1 0 1,200 1 20 A EX. LOAD - BOILER #1 G1-4
G1-1 EX. LOAD - DWH-1/CIR PUMP H.W. HEATER 20 A 1 1,200 1,200 1 20 A EX. LOAD - BOILER #2 G1-2
CIRCUIT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CIRCUIT
PROVIDE WITH THE FOLLOWING:
SUPPLY FROM:
ENCLOSURE: TYPE 1 CALC'D AVAILABLE FAULT CURRENT:
MOUNTING: SURFACE SCCR: 10 kA MAIN BUS RATING: 225 A LOCATION: MECHANICAL 131 DISTRIBUTION SYSTEM: 208Y/120V 3PH 4W MAINS TYPE: MAIN LUG
PANELBOARD: EX. PANEL 'G1'
05.21.2026 BIDS &
CONSTRUCTION
06.09.2026 ADDENDUM 002
APPROXIMATE LOCATION OF IDF
E2.2.1A - UNIT 'A' FIRST FLOOR POWER & COMMUNICATIONS PLAN
File details come from the government source that posted it. Updated .