5-6732 E2.2.1A.pdf

PDF 191 KB Posted

Attached to
RFP - Bert Goens Learning Center Pool Improvements
Solicitation number
RFP VBI 260000002079 3
Issued by
Van Buren County, Michigan

About this file

Summary of 5-6732 E2.2.1A.pdf

This document appears to be a specification or technical exhibit related to the Bert Goens Learning Center Pool Improvements project administered by a Michigan state or local government entity. The file contains detailed technical requirements and specifications for pool improvement work, though the complete scope of services, project timeline, response deadlines, and bidder meeting information cannot be fully determined from the referenced document title and index alone. Standard procurement processes would typically include site visits, a pre-bid meeting or bidders' conference, and a specified submission deadline, with contract award following evaluation of competitive proposals.

Pricing information, contract term details, funding sources, and any applicable set-asides or preferences would be documented in the full RFP package. The project involves improvements to an educational facility's aquatic amenities, which may include upgrades to pool systems, structural components, safety features, or related infrastructure. Prospective bidders should consult the complete RFP documentation for comprehensive information regarding budget allocations, technical specifications, evaluation criteria, and all contractual terms and conditions.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BF BF

BF

BF BF

BF

BF BF

BF BF

BF

BF

C

C

S1

S1

AV

AV

AV

1.

2.

3.

4.

5.

6.

REFER TO ELECTRICAL GENERAL NOTES ON SHEET E0.0.01.

REFER TO CODE COMPLIANCE PLAN FOR LOCATIONS AND RATINGS OF

VERTICAL AND HORIZONTAL BUILDING ASSEMBLIES. PROVIDE APPROPRIATE

FIRESTOPPING SYSTEMS PER SPECIFICATIONS TO MEET ALL APPLICABLE

CODES.

ALL GENERAL-USE 15- AND 20-AMPERE, 125- AND 250-VOLT NON-LOCKING

RECEPTACLES SHALL BE TAMPER-RESISTANT TYPE; REFER TO NEC 406.12 AND

SPECIFICATION SECTION 26 27 26.

REFER TO LIGHTING CONTROL SCHEDULES, GENERAL NOTES, AND

SPECIFICATIONS FOR AUTOMATIC RECEPTACLE CONTROL REQUIREMENTS.

PROVIDE BOX-COVER FUSIBLE DISCONNECT SWITCH (ON BUILDING INTERIOR IN

ACCESSIBLE LOCATION) FOR EACH SMALL (< 1/2 HP) MECHANICAL AND/OR

PLUMBING EQUIPMENT MOTOR LOAD WHERE MORE THAN ONE UNIT IS

CONNECTED TO A COMMON BRANCH CIRCUIT. TYPICAL EQUIPMENT TYPES

INCLUDE BUT ARE NOT LIMITED TO CABINET HEATERS, DAMPERS, EXHAUST

FANS, FAN COIL UNITS, PUMPS, UNIT HEATERS, VAV BOXES, ETC.

DESIGNATED CABLING PATHWAYS (CONDUITS, CABLE TRAYS, PENETRATION

SLEEVES, ETC.) SHALL BE RESERVED FOR DIV. 27 COMMUNICATIONS CABLING

AND DIV. 28 SAFETY/SECURITY CABLING ONLY. OTHER CABLING TYPES, SUCH

AS DIV. 23 CONTROLS, DIV. 26 CONTROLS, AND ARCHITECTURAL EQUIPMENT

CABLING SHALL BE SUPPORTED AND SLEEVED BY OTHER INDEPENDENT

PATHWAYS, HANGERS, AND SUPPORTS.

POWER & COMMUNICATION GENERAL NOTES

EX. PANEL 'BPA' EX. SWITCHBOARD 'ESE'

MECHANICAL

STORAGE AND RECEIVING

SEQ-10

SEQ-10SEQ-9

SEQ-8

SEQ-5

SEQ-7

SEQ-6

SEQ-1

SP-1

SEQ-2

UV CTRL

PANEL

SEQ-4

RAIL

HANDRAIL

DOOR FRAME WINDOW FRAME

WINDOW FRAMEDOOR FRAME

LADDER

P01

P06

EX.

PUMP

GFCI

44"

GFCI

GFCI

GFCI

44"

P04

P05

P05

P04

EX. PANEL 'G1'

G1-31,33,35

G1-25

G1-23

G1-34,36

G1-32

G1-27

G1-30

G1-29

P01

P07

P03

GIRLS LOCKER ROOM

BOYS LOCKER ROOM

B133

THERAPY POOL

B132

PLUMB. FIXT. PSU

ABOVE CLG.

P02

P03

E2.2.1A

TYP

MOUNT ON STRUT

G1-28

1D 44"

B132B

B132A

FLOOR GROMMET.

SEE ARCH.

FLOOR GROMMET.

SEE ARCH.

P08

STEEL REINFORCING

SHELL AND DECK

DIVE STAND

BONDING GENERAL NOTE:

PROVIDE A SWIMMING POOL EQUIPOTENTIAL BONDING SYSTEM PER NEC 680.26.

THE POOL AND ALL ASSOCIATED POOL WATER CIRCULATING SYSTEMS/EQUIPMENT

THAT ARE PRESENT SHALL BE BONDED, INCLUDING BUT NOT LIMITED TO:

CONDUCTIVE POOL SHELLS

POOL PERIMETER DECK/SURFACES

METALLIC COMPONENTS OF THE POOL STRUCTURE

UNDERWATER LIGHTING

METAL FITTINGS (CUP ANCHORS, STANCHION POST ANCHORS, WEDGE

ANCHORS OF GRAB RAILS, POOL LIFT ANCHORS, DRAIN FITTINGS, ETC.)

ELECTRICAL EQUIPMENT

FIXED METAL PARTS (CABLE SHEATHS, RACEWAYS, PIPING, AWNINGS, FENCES,

DOOR/WINDOW FRAMES, POOL LIFTS, ETC.)

POOL WATER WHERE NOT IN DIRECT CONNECTION WITH BONDED PARTS

THE BONDING CONDUCTOR SHALL BE MINIMUM #8 AWG BARE SOLID COPPER.

REFER TO NEC FOR FURTHER DETAILS AND EXCEPTIONS.

GRAB RAILS

ELECTRICAL EQUIPMENT

ASSOCIATED WITH POOL OR POOL

WATER CIRCULATING SYSTEM

ANCHORS

POSTS

BONDING CONDUCTOR

LISTED SPLICE PER

SECTION 26 05 26, TYP.

HANDRAILS

JUNCTION BOX

2-GANG BOX

(VERIFY)

2-GANG BOX

(VERIFY)

SINGLE-GANG STAINLESS STEEL COVER PLATE

WITH 1/2" CORD GRIP FITTING FOR CABLE EXIT

THROUGH CENTER OF COVER. LOCATE BOX AS

HIGH AS POSSIBLE UNDER LAVATORY TO

MINIMIZE LENGTH OF EXPOSED POWER CABLE

1/2" CONDUIT STUBBED

ABOVE ACCESSIBLE

CEILING

SHARED POWER TRANSFORMER(S) FOR MULTIPLE PLUMBING FIXTURES

BY SECTION 22 40 00, MOUNTED TO BOX ABOVE ACCESSIBLE CEILING

1/2" CONDUIT STUBBED

ABOVE ACCESSIBLE CEILING

SUSPENDED CEILING

FINISHED FLOOR

120VAC POWER FROM SPECIFIED PANELBOARD BY DIV. 26

CONTROL-VOLTAGE CABLE PER PLUMBING

FIXTURE/VALVE MANUFACTURER BY SECTION 22 40 00

PROJECT NO.

DRAWN

REVIEWED

NO PART OF THIS DRAWING MAY BE

USED OR REPRODUCED IN ANY FORM

OR BY ANY MEANS, OR STORED IN A

DATA BASE OR RETRIEVAL SYSTEM,

WITHOUT PRIOR WRITTEN

PERMISSION OF

ALL RIGHTS RESERVED

c

KEYPLAN

ISSUANCES

GMB COPYRIGHT

Au to de sk

D oc s:

//5

-6

VB

IS

D

B er t G oe ns L ea rn in g

C en te r P oo l I m pr ov em en ts

/5 -6

2E

5.

rv t

6/ 9/

:4

3:

A M

E2.2.1A

5-6732

UNIT 'A' FIRST FLOOR POWER

& COMMUNICATIONS PLAN

JDM

PRH

B E

R T

G O

E N

S L

E A

R N

IN

G

C E

N T

E R

P O

O L

IM

P

R O

V E

M E

N T

S

V A

N B

U R

E N

IN

TE

R M

E D

IA

TE

S C

H O

O L

D

IS

TR

IC

T

LA

W R

E N

C E

M

IC

H

IG

A

N

ELECTRICAL KEYNOTES

P01 POOL EQUIPOTENTIAL BONDING SYSTEM SHOWN IS DIAGRAMATIC.

PROVIDE #8 AWG COPPER GROUND RING. CUT AND PATCH FLOOR AS

NECESSARY TO INSTALL BONDING SYSTEM. THE BONDING SYSTEM IS NOT

REQUIRED TO BE BELOW GRADE IN MECHANICAL 131. REFER TO NEC 680

AND DETAIL 2, THIS SHEET, FOR ADDITIONAL REQUIREMENTS. CONFIRM

ALL BONDING POINTS IN FIELD.

P02 EXTEND THE EXISTING BRANCH CIRCUIT FROM THE DEMOLISHED

ELECTRIC HAND DRYER TO THE PLUMBING FIXTURES PSU. REFER TO

E2.1.1A FOR DEMOLITION KEYNOTES. PSU SHALL SERVE BOTH LOCKER

ROOMS.

P03 EXTEND THE EXISTING BRANCH CIRCUIT FROM THE DEMOLISHED DUPLEX

RECEPTACLE TO THE NEW DUPLEX RECEPTACLES. REFER TO E2.1.1A FOR

DEMOLITION KEYNOTES.

P04 EXTEND THE EXISTING SPEAKER CIRCUIT FROM THE DEMOLISHED PUBLIC

ADDRESS SPEAKER TO THE NEW PUBLIC ADDRESS SPEAKER. REFER TO

E2.1.1A FOR DEMOLITION KEYNOTES.

P05 THE CLOCK SHALL BE OWNER PROVIDED, CONTRACTOR INSTALLED.

PROVIDE DATA OUTLET WITH MALE CONNECTOR AT CLOCK. PROVIDE ALL

NECESSARY HARDWARE AND INFRASTRUCTURE FOR INSTALLATION OF

OWNER-PROVIDED CLOCK. REFER TO KEYPLAN FOR APPROXIMATE

LOCATION OF IDF.

P06 ALL NEW RECEPTACLES SHALL BE GFCI TYPE.

P07 TERMINATE POOL EQUIPOTENTIAL BONDING CONDUCTOR TO GROUND BUS

IN PANELBOARD.

P08 ROUTE TELECOMMUNICATION CABLING IN CHASE AND STUB THROUGH

WALL. MOUNT OUTLET IN TELEPHONE BOX.

1/4" = 1'-0"

UNIT 'A' FIRST FLOOR POWER & COMMUNICATIONS PLAN

NOT TO SCALEE2.2.1A

2 SWIMMING POOL EQUIPOTENTIAL BONDING DETAIL

UNIT A

UNIT B

UNIT C

NOT TO SCALEE2.2.1A

1 TYPICAL PLUMBING FIXTURE ELECTRICAL ROUGH-IN DETAIL

NOTES: PROVIDE NEW CIRCUIT BREAKERS FOR ALL NEW BRANCH CIRCUITS. EXISTING LOADS ARE ASSUMED.

TOTAL CONNECTED CURRENT: 122 A

TOTAL CONNECTED LOAD: 43.9 kVA

PHASE LOAD: 13,102 VA 14,248 VA 16,598 VA

G1-41 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE G1-42

G1-39 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE G1-40

G1-37 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE G1-38

G1-35 2,102 2,496 G1-36 G1-33 2,102 2,496

2 30 A CHLORINE GENERATOR SYSTEM (SEQ-10) (GFCI)

G1-34

G1-31 SP-1

(5HP)

(GFCI)

35 A 3

2,102 1,200 1 20 A REC. - BACKUP CHLORINE FEED SYSTEM (SEQ-9) G1-32

G1-29 REC. - CHLORINE GENERATOR SYSTEM (SEQ-10) 20 A 1 1,200 2,400 1 20 A REC. - CHEM. CTRL (SEQ-5) & H2O LEVEL CTRL (SEQ-7) G1-30 G1-27 REC. - ACID FEED PUMP (SEQ-8) 20 A 1 1,200 1,200 1 20 A REC. - AIR COMPRESSOR (SEQ-2) G1-28 G1-25 REC. - UV FILTER (SEQ-4) & UV CONTROL PANEL 20 A 1 1,350 0 1 20 A SPARE G1-26 G1-23 REC. - POOL FILTER (SEQ-1) 20 A 1 1,200 1,200 1 20 A EX. LOAD - U.V. TREATMENT POWER SUPPPLY G1-24 G1-21 EX. LOAD - UNKNOWN 20 A 1 1,200 1,200 1 20 A EX. LOAD - BOILER #2 PUMP G1-22 G1-19 EX. LOAD - U.V. #8 RM 148 20 A 1 1,200 1,200 1 20 A EX. LOAD - BOILER #1 PUMP G1-20

G1-17 EX. LOAD - U.V. #7 RM 147 20 A 1 1,200 0 G1-18

G1-15 EX. LOAD - U.V. #6 RM 140 20 A 1 1,200 0

2 50 A SPARE

G1-16

G1-13 EX. LOAD - U.V. #5 RM 138 20 A 1 1,200 0 1 20 A SPARE G1-14

G1-11 1,200 1,200 1 20 A EX. LOAD - CHILLER CONTROL - HEATERS G1-12

G1-9 1,200 1,250 G1-10 G1-7

EX. LOAD - SUMP PUMPS 20 A 3

1,200 1,250

2 15 A EX. LOAD - CONTROL TRANSFORMER

G1-8

G1-5 EX. LOAD - DWH-1 20 A 1 1,200 1,200 1 20 A EX. LOAD - CONTROL PANEL SUMP PUMPS G1-6

G1-3 SPARE 20 A 1 0 1,200 1 20 A EX. LOAD - BOILER #1 G1-4

G1-1 EX. LOAD - DWH-1/CIR PUMP H.W. HEATER 20 A 1 1,200 1,200 1 20 A EX. LOAD - BOILER #2 G1-2

CIRCUIT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CIRCUIT

PROVIDE WITH THE FOLLOWING:

SUPPLY FROM:

ENCLOSURE: TYPE 1 CALC'D AVAILABLE FAULT CURRENT:

MOUNTING: SURFACE SCCR: 10 kA MAIN BUS RATING: 225 A LOCATION: MECHANICAL 131 DISTRIBUTION SYSTEM: 208Y/120V 3PH 4W MAINS TYPE: MAIN LUG

PANELBOARD: EX. PANEL 'G1'

05.21.2026 BIDS &

CONSTRUCTION

06.09.2026 ADDENDUM 002

APPROXIMATE LOCATION OF IDF

E2.2.1A - UNIT 'A' FIRST FLOOR POWER & COMMUNICATIONS PLAN