General Information
Submitted to: Tyrone Dorsey
| Project Name: | Ronald Reagan Building Annual FA ITM 2020-2021 |
| Site: | Ronald Reagan Building |
| Location or Building: | 1300 Pennsylvania Avenue, NW, Washington, DC 20004 |
| Lead Inspector: | Kevin Combs/Joe Woodring |
| Date Inspection Completed: | 3/1/2021-4/30/21 |
Fire Alarm Inspection Reports
Panel Inspection Report
Batteries Inspection Report
Alarm & Supervisory Functions Report
Alarm Devices Report
Fire Phones
A/V's
Deficiencies Report
| Recommendations Report | |
| Report Prepared by: | |
| 11685 Crossroad Circle, Suite L |
Baltimore, MD 21220 P: 410-628-1155 F: 410-828-1148
Device Quantities
| Project: | Ronald Reagan Building Annual FA ITM 2020-2021 |
| Site: | Ronald Reagan Building |
| Location: | 1300 Pennsylvania Avenue, NW, Washington, DC 20004 |
| Inspector: | Kevin Combs/Joe Woodring |
| Date: | 3/1/2021-4/30/21 |
| Device Quantites By Building | |
| << | |
| Device Type | Quantity |
| Manual Pull Stations | 499 |
| Smoke Detectors | 1176 |
| Heat Detectors | 129 |
| Duct Detectors | 453 |
| Beam Detectors | 15 |
| Fire Phones | 356 |
&G
Panel Inspection Node 1
| Project: | Ronald Reagan Building Annual FA ITM 2020-2021 |
| Site: | Ronald Reagan Building |
| Location: | 1300 Pennsylvania Avenue, NW, Washington, DC 20004 |
| Inspector: | Kevin Combs/Joe Woodring |
| Date: | 3/1/2021-4/30/21 |
| Panel Inspection Report Node 1 | |
| << | |
| Panel Information |
Siemens MXL Panel Manufacturer/Model
Fire Command Center Panel Location
Addressable Panel Type
Panel Inspection
Yes x No NA System was normal and clear in operation upon arrival?
| x | Yes | No | NA | Panel and surrounding equipment, conduit and wiring well |
| secured and in good condition? |
x Yes No NA Are all lamps and displays operating correctly?
x Yes No NA Primary power supply operates properly under full load?
x Yes No NA Transient suppressors visually inspected?
x Yes No NA Have all fuses been checked for rating and supervision?
x Yes No NA Are drawings and wiring diagrams available at the panel?
x Yes No NA Are operating instructions posted or available at the panel?
x Yes No NA Are zones labeled and identified?
Central Station Test
Networked Type Transmission
| Yes | No | x | NA | Alarm, Trouble and Supervisory indication tested and verified |
| with the central station? |
Self Monitored Operator Called
Printer x Yes No NA Is the type legible?
x Yes No NA Did the printer work?
&G
Panel Inspection Node 2
| Project: | Ronald Reagan Building Annual FA ITM 2020-2021 |
| Site: | Ronald Reagan Building |
| Location: | 1300 Pennsylvania Avenue, NW, Washington, DC 20004 |
| Inspector: | Kevin Combs/Joe Woodring |
| Date: | 3/1/2021-4/30/21 |
| Panel Inspection Report Node 2 | |
| << | |
| Panel Information |
Siemens MXL Panel Manufacturer/Model
Fire Command Center Panel Location
Addressable Panel Type
Panel Inspection
Yes x No NA System was normal and clear in operation upon arrival?
| x | Yes | No | NA | Panel and surrounding equipment, conduit and wiring well |
| secured and in good condition? |
x Yes No NA Are all lamps and displays operating correctly?
x Yes No NA Primary power supply operates properly under full load?
x Yes No NA Transient suppressors visually inspected?
x Yes No NA Have all fuses been checked for rating and supervision?
x Yes No NA Are drawings and wiring diagrams available at the panel?
x Yes No NA Are operating instructions posted or available at the panel?
x Yes No NA Are zones labeled and identified?
Central Station Test
Networked Type Transmission
| Yes | No | x | NA | Alarm, Trouble and Supervisory indication tested and verified |
| with the central station? |
Self Monitored Operator Called
Printer x Yes No NA Is the type legible?
x Yes No NA Did the printer work?
&G
Panel Inspection Node 3
| Project: | Ronald Reagan Building Annual FA ITM 2020-2021 |
| Site: | Ronald Reagan Building |
| Location: | 1300 Pennsylvania Avenue, NW, Washington, DC 20004 |
| Inspector: | Kevin Combs/Joe Woodring |
| Date: | 3/1/2021-4/30/21 |
| Panel Inspection Report Node 3 | |
| << | |
| Panel Information |
Siemens MXL Panel Manufacturer/Model
Fire Command Center Panel Location
Addressable Panel Type
Panel Inspection x Yes No NA System was normal and clear in operation upon arrival?
| x | Yes | No | NA | Panel and surrounding equipment, conduit and wiring well |
| secured and in good condition? |
x Yes No NA Are all lamps and displays operating correctly?
x Yes No NA Primary power supply operates properly under full load?
x Yes No NA Transient suppressors visually inspected?
x Yes No NA Have all fuses been checked for rating and supervision?
x Yes No NA Are drawings and wiring diagrams available at the panel?
x Yes No NA Are operating instructions posted or available at the panel?
x Yes No NA Are zones labeled and identified?
Central Station Test
Networked Type Transmission
| Yes | No | x | NA | Alarm, Trouble and Supervisory indication tested and verified |
| with the central station? |
Self Monitored Operator Called
Printer x Yes No NA Is the type legible?
x Yes No NA Did the printer work?
&G
Batteries Inspection
| Project: | Ronald Reagan Building Annual FA ITM 2020-2021 | |
| Site: | Tyrone Dorsey | |
| Location: | 1300 Pennsylvania Avenue, NW, Washington, DC 20004 | |
| Inspector: | Kevin Combs/Joe Woodring | |
| Date: | 3/1/2021-4/30/21 | |
| Batteries Inspection Report | ||
| << | ||
| Battery Type | Qty | Size |
Volts
| Amps | Battery Year | Readings | Location/Description | Equipment | |||||||||
| Covered | Physical | ||||||||||||
| Condition | Functional | ||||||||||||
| Test | Connection Type | Date Inspected | Comments | ||||||||||
| Battery 1 AH/Temp | Battery 2 AH/Temp | ||||||||||||
| SLA | 2 | 12V 26AH | 2019 | 100%/ 78.6F | 100%/ 79.3F | FCC Node 3 | FACP NODE 3 | Pass | Pass | F2 | 4/8/21 | ||
| SLA | 2 | 12V 18AH | 2020 | 100%/ 79.5F | 100%/ 78.5F | FCC Node 2 | FACP NODE 2 | Pass | Pass | F2 | 4/8/21 | ||
| SLA | 2 | 12V 18AH | 2020 | 100%/ 79.3F | 100%/ 79.5F | FCC Node 1 | FACP NODE 1 | Pass | Pass | F2 | 4/8/21 | ||
| SLA | 2 | 12V 40AH | 2020 | 100%/ 77.2F | 100%/ 77.4F | South Room M.5B EPA | PWR Panel 1:32-29 | Pass | Pass | NB | 4/8/21 | ||
| SLA | 2 | 12V 18AH | 2019 | 100% 77.3F | 100%/ 77.3F | South Room M.5B EPA | PSR 3:80 | Pass | Pass | F2 | 4/8/21 | ||
| SLA | 2 | 12V 7AH | 2018 | 100%/ 78.6F | 100%/ 78.6F | Mezz. CLDP | Silent Knight NAC | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 40AH | 2020 | 100%/ 78.6F | 100%/ 77.7F | Mezz. CLDP | PWR Panel | Pass | Pass | NB | 3/24/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 100%/ 78.4F | 100%/ 79.7F | Mezz. CLDP | PSR 3:70 | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 38AH | 2020 | 100%/ 98F | 100%/ 80F | Room G.7B | Strobe PWR PNL R | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 40AH | 2017 | 100%/ 98F | 100%/ 80F | Room G.7B | Strobe PWR PNL L | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2020 | 80%/ 79.5F | 70%/ 80.4F | Room G.7B | MXLRV-5.5 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2019 | 100%/ 80.9F | 100%/ 80.7F | Room G.7B | PSR 2-21 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2019 | 100%/ 84.9F | 100%/ 85.2F | Room G.5B | MXLRA-1 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 40AH | 2019 | 100%/ 81.9F | 100%/ 80.4F | Room G.5B | MXLRV-6 | Pass | Pass | NB | 3/15/21 | BATTERY 1 IS STARTING TO SHOW SIGNS OF CORROSION | |
| SLA | 2 | 12V 75AH | 2019 | 100%/ 66.3F | 100%/ 66.5F | Room C.7B | AMP Panel | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2020 | 100%/ 67.6F | 100%/ 69.4F | Room C.7B | PSR 3-47 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 7AH | 2018 | 100%/ 64.9F | 100%/ 66.3F | Room C.7B | PAD-3 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 75AH | 2019 | 100%/ 59.8F | 100%/ 61.3F | Room C.4B | AMP Panel | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2019 | 100%/ 66.7F | 100%/ 68F | Room C.4B | PSR 2-65 | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 65.3F | 100%/ 65.1F | Room C.4B | Booster Con 66:6 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 12AH | 2020 | 100%/ 63.1F | 100%/63.5F | Room C.4B | Booster Con 66:5 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2019 | 100%/ 77.1F | 100%/ 78.4F | Room B1.11 | PSR 2:230 | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 18AH | 2019 | 100%/ 76.4F | 100%/ 77.1 | Room B1.11 | PSR 3:35 | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 80%/ 80.1F | 80%/ 81.1F | Room B1.5 | PSR 2:240 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 35AH | 2020 | 100%/ 79.8F | 100%/ 80.2F | Room B2.1 | PWR PNL 2:244-32 | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 75AH | 2019 | 100%/ 79.8F | 100%/ 80F | Room B2.1 | PSR/AMP Panel 3:40 | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2020 | 100%/ 76.1F | 100%/ 76.5F | Room B3.5-SE | PSR 2:220 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 55AH | 2020 | 100%/ 80.7F | 100%/ 82.4F | Room B4-SE12 | PWR Panel 2:221-14 | Pass | Pass | NB | 3/24/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 100%/ 78.4F | 100%/ 78.4F | Room B4-SE12 | PSR 3:20 | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 40AH | 2020 | 100%/ 68.1F | 100%/ 68.0F | Room B.4-NE11 | PWR Panel 2:212-32 | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2018 | 100%/ 68.9F | 100%/ 69.0F | Room B.4-NE11 | Panel 3-10 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 100% 78.6F | 100%/ 78.9F | Room B2.6 | PSR 3:34 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 55AH | 2018 | 80%/ 78.4F | 80%/ 77F | Room B2.6 | PWR Panel 2:236-38 | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 75AH | 2019 | 100%/ 78.4F | 100%/ 78.8F | Room B2.6 | AMP Panel | Pass | Pass | NB | 3/15/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 100%/ 73.7F | 100%/ 75.7F | Room B2.6 | PWR PNL 2:236-32 | Pass | Pass | F2 | 3/15/21 | ||
| SLA | 2 | 12V 7AH | 2018 | 100%/ 81.5F | 100%/ 81.3F | Room B3-NE09 | SK NAC 2:216-60 | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 18AH | 2020 | 100%/ 78.9F | 100%/ 79.8F | Room B3-NE09 | PSR 2:210 | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 18AH | 2018 | 90%/ 71.4F | 100%/ 72.6F | USAID Telcom 8.10 | PSR | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 100%/ 71.5F | 100%/ 71.8F | USAID Telcom 7.10 | PSR | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 75AH | 2020 | 100%/ 78.2F | 100%/ 78.1F | USAID Telcom 7.10 | AMP Panel 3:130 | Pass | Pass | NB | 4//12/21 | ||
| SLA | 2 | 12V 26AH | 2019 | 100%/ 69.8F | 100%/ 69F | USAID Telcom 7.10 | Bottom PWR PNL | Pass | Pass | 4//12/21 | |||
| SLA | 2 | 12V 38AH | 2017 | 70%/ 69.5F | 70%/ 68.9 | USAID Telcom 7.10 | Top PWR PNL | Pass | Pass | 4//12/21 | |||
| SLA | 2 | 12v 7AH | 2019 | 100%/ 70.5 | 100%/ 72.6 | USAID Telecom 7.10 | PAD 3 top | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 71.6 | 100%/ 72.6 | USAID Telecom 7.10 | PAD 3 Left 3:131-52 | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 7AH | 2016 | 100%/ 72.6 | 100%/ 71.6 | USAID Telecom 7.10 | PAD 3 Right | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 18AH | 2017 | USAID Telcom 6.10 | PSR | F2 | 4//12/21 | Couldn’t get access to room. Card reader not working. | |||||
| SLA | 2 | 12V 35AH | 2018 | 100%/ 72.6F | 100%/ 73.4F | USAID Telcom 5.10 | Strobe PWR PNL 1:72-1 | Pass | Pass | NB | 4//12/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 80%/ 74.6F | 80%/ 75.3F | USAID Telcom 5.10 | PSR | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 18AH | 2019 | USAID Telcom 4.10 | PSR | F2 | 4//12/21 | Couldn't get access. Floor under constructon. | |||||
| SLA | 2 | 12V 38AH | 2020 | 90%/ 73.5F | 90%/ 73.5F | USAID Telcom 3.10 | Bottom PWR PNL | Pass | Pass | NB | 4//12/21 | ||
| SLA | 2 | 12V 26AH | 2019 | 100%/ 74.1F | 100%/ 74.4F | USAID Telcom 3.10 | Top PWR PNL | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 18AH | 2019 | 100%/ 73.7F | 100%/ 74.6F | USAID Telcom 3.10 | PSR | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 75AH | 2017 | 100%/ 73.5F | 100%/ 73.5 | USAID telcom 3.10 | AMP Panel 3:90 | Pass | Pass | NB | 4//12/21 | ||
| SLA | 2 | 12V 12AH | 2020 | 100%/ 74.5F | 100%/ 74.5F | USAID Elec Rm 2.09EA | Nac Panel | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 12AH | 2020 | 100%/ 75.9F | 100%/ 75.8 | USAID Elec Rm | Nac Panel | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 18AH | 2016 | 100%/ 70.3F | 80%/ 71.7 | USAID telcom 2.10 | PSR 1:30 | Pass | Pass | F2 | 4//12/21 | ||
| SLA | 2 | 12V 18AH | 2018 | 70%/ 75.7F | 70%/ 76.2F | Customs telcom 2.5 | PSR-20 | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 75AH | 2020 | 100%/ 69.4F | 100%/ 68.9F | Customs telcom 3.5 | AMP Panel | Pass | Pass | NB | 4/15/21 | ||
| SLA | 2 | 12V 35AH | 2020 | 70%/ 69.4F | 70%/ 69.2F | Customs telcom 3.5 | PWR PNL | Pass | Pass | NB | 4/15/21 | ||
| SLA | 2 | 12V 7AH | 2019 | 100%/ 76.1F | 100%/ 68.9F | Customs telcom 4.5 | PAD 3 | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 18AH | 2020 | FAIL | FAIL | Customs telcom 4.5 | PSR | Fail | Fail | F2 | 4/15/21 | Corrossion | |
| SLA | 2 | 12V 7AH | 2017 | 100%/ 78.2F | 100%/ 77.7F | Customs telcom 5.5 | SK BPS | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 77.5F | 100%/ 76.8F | Customs telcom 5.5 | PAD-4 | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 18AH | 2020 | 100%/ 73.5F | 100%/ 78.6F | Customs telcom 5.5 | PSR-120 | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 55AH | 2020 | 100%/ 76.2F | 100%/ 76.4F | Customs telcom 5.5 | PWR PNL | Pass | Pass | NB | 4/15/21 | ||
| SLA | 2 | 12V 18AH | 2020 | 100%/ 78.8F | 100%/ 79.8F | Customs telcom 6.5 | PSR | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 75AH | 2019 | 100%/ 80.6F | 100%/ 80F | Customs telcom 7.5 | AMP Panel | Pass | Pass | NB | 4/15/21 | ||
| SLA | 2 | 12V 40AH | 2019 | 100%/ 79.5F | 100%/ 79.2F | Customs telcom 7.5 | PWR PNL | Pass | Pass | NB | 4/15/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 90%/ 77.3F | 90%/ 77.7F | Customs telcom 8.5 | PSR | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V18AH | 2017 | 90%/ 84.3F | 90%/ 85.6F | Customs telecom 9.1 | PSR 3:165 | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V18AH | 2018 | 100%/ 81.8F | 100%/ 80.6F | Customs telecom 9.1 | Pwr PNL 1:88-51 | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 100%/ 85.2F | 100%/ 86.3F | Customs telcom 9.1 | PSR 3:160 | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 18AH | 2017 | 90%/ 78.2F | 90%/ 78.3F | Customs telcom 9.5 | AMP Panel | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V18AH | 2020 | 100%/ 78.5F | 100%/ 78.5F | Customs telcom 9.5 | PSR | Pass | Pass | F2 | 4/15/21 | ||
| SLA | 2 | 12V 18AH | 2019 | 100%/ 78.9F | 100%/ 78.9F | 9th Flr 9.6 Mech Rm ZC | PSR 3:155 | Pass | Pass | F2 | 4/8/21 | ||
| SLA | 2 | 12V 18AH | 2013 | 10%/ 78.5F | 10%/ 78.5F | 9th Flr 9.6 Mech Rm ZC | PSR 3:150 | Pass | Fail | F2 | 4/8/21 | Expired | |
| SLA | 2 | 12V 18AH | 2018 | 70%/ 78F | 80%/ 78F | 9th Flr 9.6 Mech Rm ZC | PWR PNL 1:96-1 | Pass | Pass | F2 | 4/8/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 71F | 100%/ 71F | 8th Flr Telcom Rm NTWR | Nac Panel PAD3 | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 71F | 100%/ 72.1F | 8th Flr Telcom Rm NTWR | Nac Panel PAD2 | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 83.1F | 100%/ 83.4F | 7th Flr Telcom Rm NTWR | Nac Panel | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 85.1F | 100%/ 84.3F | 6th Flr Telcom Rm NTWR | Nac Panel | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 80.2F | 100%/ 80.9F | 5th Flr Telcom Rm NTWR | Nac Panel | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 78.1F | 100%/ 78.4F | 4th Flr Telcom Rm NTWR | Nac Panel | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 7AH | 2017 | 100%/ 81.8F | 100%/ 81.8F | 3rd Flr Telcom Rm NTWR | Nac Panel Top | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V 7AH | 2020 | 100%/ 80.4F | 100%/ 78.9F | 3rd Flr Telcom Rm NTWR | Nac Panel Bottom | Pass | Pass | F2 | 3/24/21 | ||
| SLA | 2 | 12V7AH | 2020 | 100%/ 77.9F | 100%/ 77.3F | Market to Market | Nac Panel | Pass | Pass | F2 | 3/24/21 |
&G
Alarm & Supervisory Functions
| Project: | Ronald Reagan Building Annual FA ITM 2020-2021 | |
| Site: | Ronald Reagan Building | |
| Location: | 1300 Pennsylvania Avenue, NW, Washington, DC 20004 | |
| Inspector: | Kevin Combs/Joe Woodring | |
| Date: | 3/1/2021-4/30/21 | |
| Alarm & Supervisory Functions Report | ||
| << | ||
| Function | Description | Test Result |
| Alarm Functions | ||
| Alarm Bells/Horns/Strobes | Evacuation Alarm functions including Bells/Horns/Strobes actuaute properly | No A/V testing done per GSA |
| Alarm Panel Supervisory Functions | ||
| Panel AC Power Loss | Loss of AC power to the alarm panel is detected by the alarm system | Pass |
| Panel Sec Power Loss | Loss of Secondary power to the alarm panel is detected by the alarm system | Pass |
| Open Alarm Circuits | Electrical opens in initiating and indicating circuits are detected | Pass |
| Short Alarm Circuits | Electrical shorts in initiating and indicating circuits are detected | Pass |
| Ground Faults Detected | Ground faults in alarm circuits are detected | Pass |
| Auxiliary Functions | |||
| Remote Annunciator | Remote annunciator shows properly | Pass | |
| Stair Pressurization | Stairwell is pressurized for smoke control by roof fan | Pass | |
| Elevator Recall | Elevators are recalled to primary floor except for primary floor alarm initiation | Not tested yet. | |
| Elevator Recall Primary Fl | Elevators are recalled to Secondary floor for Primary floor alarm initiation | Not tested yet. | |
| HVAC Shutdown | HVAC shutdown upon an alarm condition | Pass | |
| High/Low Air | High or low air pressure switch actuation indicating conditions in the dry sprinkler system is detected by the alarm system | N/A | |
| Building Temp | Temperatures below 40 degress in wet sprinkler areas is detected by the alarm system | Pass | |
| Site Water Temp. | Water Temperature below 40 degrees in a water tank is supervised by the alarm system | N/A | |
| Site Water Level | Site Water Level too high or low in a water tank is supervised by the alarm system | N/A |
| Fire Pump Supervisory Functions | ||
| Fire Pump Power | Fire Pump Power not connected or off is supervised by the alarm system | Pass |
| Fire Pump Running | Fire Pump Running is detected by the alarm system | Pass |
| Fire Pump Phase Reversal | Fire Pump Phase Reversal is detected by the alarm system | Pass |
| Fire Pump Auto Position | Fire Pump Controller in the Automatic Position is supervised by the alarm system | Pass |
| Fir Pump or Pump Controller Trouble | Fire Pump or Pump Controller Trouble is supervised by the alarm system | Pass |
| Generator Supervisory Functions | ||
| Generator in Auto Position | Generator Controller in Auto Position is supervised by the alarm system | Pass |
| Generator or Controller Trouble | Generator or Controller Trouble is supervised by the alarm system | Pass |
| Switch Transfer | Switch Transfer between power sources is supervised by the alarm system | Pass |
&G
Alarm Devices
| Project: | Ronald Reagan Building Annual FA ITM 2020-2021 | ||||||||||
| Site: | Ronald Reagan Building | ||||||||||
| Location: | 1300 Pennsylvania Ave, NW, Washington, DC 20004 | ||||||||||
| Inspector: | Kevin Combs/Joe Woodring | Testing Counts | |||||||||
| Date: | 3/1/2021-4/30/21 | Total Devices | Devices Tested | Devices Not Tested | Percentage Done | ||||||
| Alarm Devices Report | 2272 | 2272 | 0 | 100 | |||||||
| << | Need to update descriptions as tested | ||||||||||
| Device Type | Location/Description | Address | Physical | ||||||||
| Condition | Functional | ||||||||||
| Test | Comments | Date Inspected | |||||||||
| Duct Detector | Mezz Level ZE0404 RF-60S | 1:21:08 | Pass | Pass | Remote LED did not activate | 4/29/21 | |||||
| Duct Detector | Mezz Level ZE ME-0416 | 1:21:09 | DNT | DNT | Did not test inaccessable | 4/29/21 | |||||
| Smoke Detector | Mezz Level ZF Elev Lobby SWG1-3 | 1:21:10 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | Ground Floor Elev Lobby SWP1-6 | 1:21:11 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | Mezz Level Elev Lobby SEG1-3 | 1:21:12 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | Mezz Level Elev Lobby SEF1-2 | 1:21:13 | Pass | Pass | 4/29/21 | ||||||
| Smoke Detector | Ground Floor Elev Lobby SEP1-6 | 1:21:14 | Pass | pass | 4/23/21 | ||||||
| Smoke Detector | Ground Floor Elev Lobby SEP7-9 | 1:21:15 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | Mezz Level ME-0422 | 1:21:16 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0422 | 1:21:17 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0422 | 1:21:18 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0418 | 1:21:19 | Fail | Pass | Smoke is painted | 3/4/21 | |||||
| Smoke Detector | Mezz Level ME-0418 | 1:21:20 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0418 | 1:21:21 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0418 | 1:21:22 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0418 | 1:21:23 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor GR-0420 | 1:21:24 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor GR-0420 | 1:21:25 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor GR-0420 | 1:21:26 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0401 | 1:21:27 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0401 | 1:21:28 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz 14th St Bridge | 1:21:29 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0408 | 1:21:30 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0406 | 1:21:31 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0702 | 1:21:32 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | Mezz Level ME-SE02A | 1:21:33 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | Mezz Level ME-0708 | 1:21:34 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | Mezz Level ME-0712 | 1:21:35 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | Mezz Level ME-0701A | 1:21:36 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | Mezz Level Tele Com Rm EPA | 1:21:37 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | Mezz Level Tele Rm EPA | 1:21:38 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | Mezz Level Elec Closet EPA | 1:21:39 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | Mezz Level ME-0404 | 1:21:40 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level ME-SE02A | 1:21:42 | Pass | Pass | 4/2/21 | ||||||
| Manual Station | Mezz Level ZE Stair 6B EPA | 1:21:43 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | Mezz Level ZE Stair 6B EPA | 1:21:44 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | Mezz Level ZF ME-0702 | 1:21:55 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level EPA | 1:21:58 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | Mezz Level EPA | 1:21:59 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | Mezz Level USAID | 1:22:01 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | Mezz Level Electric Closet EPA | 1:22:02 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | Mezz Level USAID Stair 7C | 1:22:04 | Pass | Pass | No point on NCC | 4/2/21 | |||||
| Duct Detector | Mezz Level ME-0605 RF35 EPA | 1:22:05 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | Mezz Level Tele Com Room EPA | 1:22:06 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | Mezz Level Jan Closet | 1:22:08 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level Stair 6C EPA | 1:22:09 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0422 | 1:22:16 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor GR-0513 | 1:22:17 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0506 | 1:22:18 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ME-0504 | 1:22:19 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor East Atrium | 1:22:20 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor East Atrium | 1:22:21 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor East Atrium High Ceiling | 1:22:22 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZF GR-0518 | 1:22:25 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0518 | 1:22:26 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0518 | 1:22:27 | Pass | Pass | 3/4/21 | ||||||
| Duct Detector | Mezz Level USAID RF-40 | 1:22:32 | Pass | Pass | 3/25/21 | ||||||
| Duct Detector | Mezz Level USAID RF-40 | 1:22:33 | Pass | Pass | 3/25/21 | ||||||
| Duct Detector | Mezz Level USAID RF-76 | 1:22:35 | Pass | Pass | 3/25/21 | ||||||
| Smoke Detector | Mezz Level ZG Tele Com Room | 1:22:36 | Pass | Pass | Need Access USAID | 4/2/21 | |||||
| Smoke Detector | Mezz Level ZG Elec Closet | 1:22:37 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | Mezz Level Elev Lobby EP 1-3 | 1:22:38 | DNT | DNT | Did not test inaccessable | 4/22/21 | |||||
| Manual Station | Mezz Level USAID Stair 7C | 1:22:39 | Pass | Pass | 4/2/21 | ||||||
| Duct Detector | Mezz Level Child Care RF-71 | 1:22:49 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level Elev Lobby CCP-1 | 1:22:50 | Pass | Pass | 4/22/21 | ||||||
| Smoke Detector | Mezz Level Mech Rm 0722 Child Care | 1:22:51 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level Elec Room 0714 Child Care | 1:22:52 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level Child Care | 1:22:53 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level ZE Child Care | 1:22:54 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level ZE EPA | 1:22:55 | Pass | Pass | 4/8/21 | ||||||
| Duct Detector | 2nd Floor ZE RF52 CBP | 1:23:05 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 2nd Floor ZE RF55 CBP | 1:23:06 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 2nd Floor ZE RF60S CBP | 1:23:07 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 2nd Floor RF52 CBP | 1:23:08 | DNT | DNT | Did not test inaccessable | 4/16/21 | |||||
| Duct Detector | 2nd Floor ZE RF53 CBP | 1:23:09 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 2nd Floor ZE RF54 CBP | 1:23:10 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 2nd Floor Elev Lobby SWP1-6 | 1:23:11 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | 2nd Floor ZE 02-SW17 Telecom Rm CBP | 1:23:12 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZE 02-SW14 CBP | 1:23:13 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 2nd Floor ZE 02-SW12 CBP | 1:23:14 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 2nd Floor ZE 02-SW11 Telecom Rm CBP | 1:23:15 | Pass | Pass | No point on NCC | 4/7/21 | |||||
| Smoke Detector | 2nd Floor ZE 02-SW08 CBP | 1:23:16 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 2nd Floor ZE 02-SW09 Telecom Rm 2 CBP | 1:23:17 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZE 02-SW10 CBP | 1:23:18 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | 2nd Floor ZE CBP | 1:23:19 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | 2nd Floor ZE CBP | 1:23:20 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZG USCS Tel Room | 1:23:34 | Pass | Pass | 4/28/21 | ||||||
| Duct Detector | 2nd Floor ZG 02-0000 RF77 CBP | 1:23:35 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 2nd Floor ZG 02-0701 RF42 CBP | 1:23:36 | DNT | DNT | Did not test inaccessable | 4/16/21 | |||||
| Smoke Detector | 2nd Floor ZG Elev Lobby EP 1-3 | 1:23:37 | DNT | DNT | Did not test inaccessable | 4/22/21 | |||||
| Smoke Detector | 2nd Floor ZG 02-0701 | 1:23:38 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZG 02-0701 | 1:23:39 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZG 02-0702 | 1:23:40 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | Ground Floor ZG High Ceiling | 1:23:41 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZG High Ceiling | 1:23:42 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZG High Ceiling | 1:23:43 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZG High Ceiling | 1:23:44 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | 2nd Floor ZG 02-SE18 Telecom Rm CBP | 1:23:45 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZG 02-SE19 CBP | 1:23:46 | Pass | Pass | 4/7/21 | ||||||
| Manual Station | 2nd Floor ZG 02-0000 CBP | 1:23:47 | Pass | Pass | 4/7/21 | ||||||
| Manual Station | 2nd Floor ZG 02-0000 | 1:23:48 | Pass | Pass | 4/7/21 | ||||||
| Manual Station | 2nd Floor ZG 02-0701 | 1:23:49 | Pass | Pass | 4/7/21 | ||||||
| Duct Detector | 2nd Floor ZF 02-000 RF44 USAID | 1:24:05 | Pass | Pass | Wrong Label Should be Zone C | 4/5/21 | |||||
| Duct Detector | 2nd Floor ZF 02-000 RF47 USAID | 1:24:06 | Pass | Pass | Wrong Label Should be Zone C | 4/5/21 | |||||
| Duct Detector | 2nd Floor ZF 02-000 RF56 | 1:24:07 | DNT | DNT | Did not test inaccessable | 4/5/21 | |||||
| Duct Detector | 2nd Floor ZF 02-000 RF53 CBP | 1:24:08 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 2nd Floor ZF 02-000 RF57 CBP Mens Rm 2.5 | 1:24:09 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 2nd Floor ZF Elev Lobby Sep1-6 | 1:24:10 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 2nd Floor ZF Elev Lobby SEF1-2 | 1:24:11 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-SE08 CBP | 1:24:12 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-SE09 Telecom Rm 3 CBP | 1:24:13 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-SE10 CBP | 1:24:14 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-SE11 Telecom Rm CBP | 1:24:15 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-SE14 CBP | 1:24:17 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-SE12 CBP | 1:24:19 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-0503 Telecom Rm 4 CBP | 1:24:20 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-0502 CBP | 1:24:21 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 2nd Floor ZF 02-0501 CBP | 1:24:22 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | Ground Floor ZF East Atrium | 1:24:23 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZF East Atrium | 1:24:24 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | 2nd Floor ZF Bridge East Atrium | 1:24:25 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | 2nd Floor ZF Bridge East Atrium | 1:24:26 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZF East Atrium | 1:24:27 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZF East Atrium | 1:24:28 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZF East Atrium | 1:24:29 | DNT | DNT | need boom lift to test | 3/1/21 | |||||
| Manual Station | 2nd Floor ZF 02-0000 CBP | 1:24:30 | Pass | Pass | 4/7/21 | ||||||
| Manual Station | 2nd Floor ZG 02-SE01 CBP | 1:24:31 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 2nd Floor ZG EMR SEP 7-9 | 1:24:46 | Pass | Pass | 4/23/21 | ||||||
| Duct Detector | 2nd Floor ZF EMR SEP 7-9 SF-94 CBP | 1:24:49 | Pass | Pass | 4/16/21 | ||||||
| Heat Detector | 2nd Floor ZF EMR SEP 7-9 SF-94 | 1:24:50 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 2nd Floor ZG TOS SEP-7 | 1:24:51 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 2nd Floor ZG TOS SEP-8 | 1:24:52 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 2nd Floor ZG TOS SEP-9 | 1:24:53 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 2nd Floor ZG EMR Sep 7-9 | 1:24:54 | Pass | Pass | 4/23/21 | ||||||
| Manual Station | 2nd Floor ZG EMR 0705 | 1:24:55 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | Mezz Level ZB Elev Lobby NG 1-3 | 1:31:11 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | Ground Floor ZB Elev Lobby NP 1-6 | 1:31:12 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | Mezz Level ZB ME-0101 | 1:31:15 | Pass | Pass | 4/28/21 | ||||||
| Manual Station | Mezz Level ZB Stair 1A | 1:31:16 | Pass | Pass | 4/28/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0100 | 1:31:23 | Pass | Pass | 3/4/21 | ||||||
| Duct Detector | Mezz Level ZB Mens Rm RF14 | 1:31:30 | Pass | Pass | 4/29/21 | ||||||
| Smoke Detector | Mezz Level ZB Elec Closet | 1:31:31 | Pass | Pass | 3/24/21 | ||||||
| Smoke Detector | Mezz Level ZB Tele Com Room | 1:31:32 | Pass | Pass | 3/24/21 | ||||||
| Smoke Detector | Con Level ZB CO-0325 | 1:31:33 | DNT | DNT | need boom lift to test | 3/12/21 | |||||
| Smoke Detector | Con Level ZB CO-0325 | 1:31:34 | Pass | Pass | 3/12/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0325 | 1:31:34 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0307 | 1:31:35 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Con Level ZB CO-0307 | 1:31:36 | Pass | Pass | 3/12/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0307 | 1:31:36 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0325 | 1:31:37 | DNT | DNT | inaccessible through grate. | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZB GR-0325 | 1:31:38 | DNT | DNT | inaccessible through grate. | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZB GR-0325 | 1:31:39 | DNT | DNT | inaccessible through grate. | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZB GR-0100 | 1:31:40 | DNT | DNT | inaccessible through grate. | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZB GR-0100 | 1:31:41 | DNT | DNT | inaccessible through grate. | 3/1/21 | |||||
| Smoke Detector | Ground Floor ZB GR-0144 | 1:31:42 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0144 | 1:31:43 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0144 | 1:31:44 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0144 | 1:31:45 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZB GR-0144 | 1:31:46 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level ZB ME-NM01 | 1:31:47 | Pass | Pass | 3/24/21 | ||||||
| Manual Station | Mezz Level ZB ME-0302 | 1:31:48 | Pass | Pass | 3/24/21 | ||||||
| Duct Detector | Mezz Level ZD ME-0206 RF31 | 1:32:05 | Pass | Pass | 3/25/21 | ||||||
| Duct Detector | Mezz Level ZD ME-0203 RF36 | 1:32:06 | Pass | Pass | 3/25/21 | ||||||
| Duct Detector | Mezz Level ZD ME-0208 RF36 | 1:32:07 | Pass | Pass | 3/25/21 | ||||||
| Duct Detector | Mezz Level ZD ME-0200 RF73 | 1:32:08 | Pass | Pass | 3/25/21 | ||||||
| Duct Detector | Mezz Level ZD ME-0200 RF73 | 1:32:09 | Pass | Pass | 3/25/21 | ||||||
| Smoke Detector | Mezz Level ZD ME-0201 Telecom Rm | 1:32:12 | Pass | Pass | 3/24/21 | ||||||
| Smoke Detector | Mezz Level ZD ME-0202 Elec Rm | 1:32:13 | Pass | Pass | 3/24/21 | ||||||
| Smoke Detector | Mezz Level ZD Elec Closet | 1:32:14 | Pass | Pass | 3/24/21 | ||||||
| Smoke Detector | Mezz Level ZD Tele Com Room | 1:32:15 | Pass | Pass | 3/24/21 | ||||||
| Smoke Detector | Mezz Level ZD ME-0307 | 1:32:16 | Pass | Pass | 3/24/21 | ||||||
| Manual Station | Mezz Level ZD ME-0206 | 1:32:17 | Pass | Pass | 3/24/21 | ||||||
| Manual Station | Mezz Level ZD ME-0206 | 1:32:18 | Pass | Pass | 3/24/21 | ||||||
| Manual Station | Mezz Level ZD Commerce Dept | 1:32:19 | Pass | Pass | No point on NCC | 3/24/21 | |||||
| Manual Station | Mezz Level ZD ME-1101 | 1:32:20 | Pass | Pass | No point on NCC | 3/24/21 | |||||
| Manual Station | Mezz Level ZD ME-1113 | 1:32:21 | Pass | Pass | No point on NCC | 3/24/21 | |||||
| Duct Detector | Mezz Level ZF 0405 RF-60N | 1:32:30 | Pass | Pass | 4/29/21 | ||||||
| Smoke Detector | Mezz Level ZF Elev Lobby NWG1-3 | 1:32:31 | Pass | Pass | 4/22/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0421 | 1:32:32 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0421 | 1:32:33 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0419 | 1:32:34 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0419 | 1:32:35 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0419 | 1:32:36 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0419 | 1:32:37 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0419 | 1:32:38 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0419 | 1:32:39 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0419 | 1:32:40 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0421 | 1:32:41 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0421 | 1:32:42 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0421 | 1:32:43 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0407 | 1:32:44 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF Tele Com Room | 1:32:45 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF Electric Room | 1:32:46 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level ZF ME-0405 Stair 4A | 1:32:47 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF Tele Com Room | 1:33:05 | Pass | Pass | 4/9/21 | ||||||
| Smoke Detector | Ground Floor ZD NWP1-6 Elev Lobby | 1:33:06 | Pass | Pass | 4/21/21 | ||||||
| Manual Station | Mezz Level ZD Stair 2B | 1:33:07 | Pass | Pass | 3/24/21 | ||||||
| Manual Station | Mezz Level ZD Stair 2B | 1:33:08 | Pass | Pass | 3/24/21 | ||||||
| Smoke Detector | Mezz ZF Elev Lobby NEG 1-3 | 1:33:18 | Pass | Pass | 4/22/21 | ||||||
| Smoke Detector | Mezz Level ZF Elev Lobby NEF1-2 | 1:33:19 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | Ground Floor Elev Lobby NEP 11-16 | 1:33:20 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | Ground Floor ZF Elev Lobby NEP 1-6 | 1:33:21 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | Mezz Level ZF Elev Lobby FS 1-2 | 1:33:22 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | Ground Floor ZF Elev Lobby NEP 7-10 | 1:33:23 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | Mezz Level ZF Elev Lobby PFP1-2 | 1:33:24 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | Ground Floor ZF East Atrium | 1:33:25 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0503 | 1:33:26 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF ME-0505 | 1:33:27 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0512 | 1:33:28 | Pass | Pass | 3/4/21 | ||||||
| Duct Detector | Mezz Level ZC ME-0507 RF30 | 1:33:29 | Pass | Pass | 3/25/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0327 | 1:33:30 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0327 | 1:33:31 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0326 | 1:33:32 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0326 | 1:33:33 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0326 | 1:33:34 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Ground Floor ZF GR-0326 | 1:33:35 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF Sec Room 0323 | 1:33:36 | Pass | Pass | 4/29/21 | ||||||
| Smoke Detector | Mezz Level ZF Elec Room 0325 | 1:33:37 | Pass | Pass | 4/28/21 | ||||||
| Smoke Detector | Mezz Level ZF over Stair 8A | 1:33:38 | Pass | Pass | 3/4/21 | ||||||
| Smoke Detector | Mezz Level ZF over Stair 8A | 1:33:39 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level ZF Atrium | 1:33:40 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level ZD ME-NE02 | 1:33:41 | Pass | Pass | 3/4/21 | ||||||
| Manual Station | Mezz Level ZF ME-NE02A | 1:33:42 | Pass | Pass | 4/29/21 | ||||||
| Manual Station | Mezz Level ZF ME-0309A | 1:33:43 | Pass | Pass | 4/28/21 | ||||||
| Manual Station | Mezz Level ZC Stair 3D EPA | 1:33:44 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | 2nd Floor ZA Stair 1A NTWR | 1:35:01 | Pass | Pass | 3/19/21 | ||||||
| Duct Detector | 2nd Floor ZA 02-1000 RF-2 NTWR | 1:35:07 | Pass | Pass | 4/14/21 | ||||||
| Duct Detector | 2nd Floor ZA 02-0000 RF-1 NTWR | 1:35:08 | Pass | Pass | 4/14/21 | ||||||
| Smoke Detector | 2nd Floor ZA Elev Lobby NP 1-6 | 1:35:09 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 2nd Floor ZA 02-NA08 NTWR | 1:35:10 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | 2nd Floor ZA 02-NA13 NTWR | 1:35:11 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | 2nd Floor ZA 02-NA16 NTWR | 1:35:12 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | 2nd Floor ZA 02-NA15 NTWR | 1:35:13 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | 2nd Floor ZA Sister Cities NTWR | 1:35:14 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | Con Level ZB Elev Lobby AP-1 | 1:35:15 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | Con Level ZA C0-1000 | 1:35:16 | DNT | DNT | need boom lift to test | 3/12/21 | |||||
| Smoke Detector | Con Level ZA C0-1000 | 1:35:17 | DNT | DNT | need boom lift to test | 3/12/21 | |||||
| Smoke Detector | Con Level ZA C0-1000 | 1:35:18 | DNT | DNT | need boom lift to test | 3/12/21 | |||||
| Smoke Detector | Con Level ZA C0-1000 | 1:35:19 | DNT | DNT | need boom lift to test | 3/12/21 | |||||
| Manual Station | 2nd Floor ZA 02-0000 USAID | 1:35:20 | Pass | Pass | 4/5/21 | ||||||
| Manual Station | 2nd Floor ZA 02-0000 NTWR | 1:35:21 | Pass | Pass | 3/19/21 | ||||||
| Manual Station | 2nd Floor ZA 02-NA09 NTWR | 1:35:22 | Pass | Pass | 3/19/21 | ||||||
| Manual Station | 2nd Floor ZA 02-0000 USAID | 1:35:25 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 2nd Floor ZD 02-0000 RF60N USAID | 1:35:37 | DNT | DNT | Did not test inaccessable | 4/5/21 | |||||
| Duct Detector | 2nd Floor ZD 02-0000 RF46 USAID | 1:35:38 | DNT | DNT | Did not test inaccessable | 4/5/21 | |||||
| Duct Detector | 2nd Floor ZD 02-0000 RF47 USAID | 1:35:39 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 2nd Floor ZD 02-0000 RF46 USAID | 1:35:40 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 2nd Floor ZD 02-0000 RF49 USAID | 1:35:41 | DNT | DNT | Did not test inaccessable | 4/5/21 | |||||
| Duct Detector | 2nd Floor ZD 02-0000 RF48 USAID | 1:35:42 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZD NWP 1-6 ELEV Lobby | 1:35:43 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | 2nd Floor ZD 02-NW-17 USAID Telcom Rm | 1:35:44 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZD 02-NW12 USAID Elec Rm | 1:35:45 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZD 02-NW14 USAID Elec Rm | 1:35:46 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZD 02-NW-11 USAID Telcom Rm | 1:35:47 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZD 02-NW10 USAID Elec Rm | 1:35:48 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZD 02-NW09 USAID Telcom Rm | 1:35:49 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZD 02-NW08 USAID Elec Rm | 1:35:50 | Pass | Pass | 4/5/21 | ||||||
| Manual Station | 2nd Floor ZD 02-0000 USAID Stair 2B | 1:35:51 | Pass | Pass | 4/5/21 | ||||||
| Manual Station | 2nd Floor ZD 02-0000 USAID | 1:35:52 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZB 02-NM14 Tele Rm USAID | 1:36:04 | Pass | Pass | Need access | 4/15/21 | |||||
| Duct Detector | 2nd Floor ZB 02-0000 RF-3 USAID | 1:36:05 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 2nd Floor ZB 02-0000 RF-4 USAID | 1:36:06 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZB 02-NM12 USAID Elec Rm | 1:36:07 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZB 02-NM13 USAID Elec Rm | 1:36:08 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZB 02-NM09 USAID Tele Rm | 1:36:09 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZB 02-NM08 USAID Elec Rm | 1:36:10 | Pass | Pass | 4/5/21 | ||||||
| Manual Station | 2nd Floor ZB 02-NM01 USAID | 1:36:11 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 2nd Floor ZC 02-0000 RF-50 USAID | 1:36:25 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 2nd Floor ZC 02-0000 RF-51 USAID | 1:36:26 | DNT | DNT | Did not test inaccessable | 4/5/21 | |||||
| Duct Detector | 2nd Floor ZC 02-0306 RF39 USAID | 1:36:27 | DNT | DNT | Did not test inaccessable | 4/5/21 | |||||
| Duct Detector | 2nd Floor ZC 02-0000 RF45 USAID | 1:36:28 | DNT | DNT | Did not test inaccessable | 4/5/21 | |||||
| Smoke Detector | 2nd Floor ZC Elev Lobby PFP1-2 | 1:36:29 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 2nd Floor ZC Elev Lobby FS 1-2 | 1:36:30 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 2nd Floor ZC Elev Lobby NEP1-6 | 1:36:31 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | 2nd Floor ZC Elev Lobby NEP9-10 | 1:36:32 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | 2nd Floor ZC Elev Lobby NEP11-16 | 1:36:33 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | 2nd Floor ZC Elev Lobby NEF1-2 | 1:36:34 | Pass | Pass | 4/21/21 | ||||||
| Smoke Detector | 2nd Floor ZC 02-0305 USAID Telcom Rm | 1:36:35 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZC 02-NE09 USAID Telcom Rm | 1:36:36 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZC 02-NE08 USAID Elec Rm | 1:36:37 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZC 02-NE11 USAID Telcom Rm | 1:36:38 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZC 02-NE14 USAID Elec Rm | 1:36:39 | Pass | Pass | No point on NCC | 4/5/21 | |||||
| Smoke Detector | 2nd Floor ZC 02-NE12 USAID Elec Rm | 1:36:40 | Pass | Pass | No point on NCC | 4/5/21 | |||||
| Manual Station | 2nd Floor ZC 02-0000 USAID Stair 3A | 1:36:41 | Pass | Pass | 4/5/21 | ||||||
| Manual Station | 2nd Floor ZC 02-0000 USAID Stair 3A | 1:36:42 | Pass | Pass | 4/5/21 | ||||||
| Manual Station | 2nd Floor ZC 02-0305 USAID Telcom Rm | 1:36:43 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 2nd Floor ZC Pavillion | 1:36:53 | Pass | Pass | No point on NCC | 4/5/21 | |||||
| Beam Detector | Main Atrium ZF | 1:41:01 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | Main Atrium ZF | 1:41:02 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | Main Atrium ZF | 1:41:03 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | Main Atrium ZF | 1:41:04 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Duct Detector | 3rd Floor ZE 03-0000 RF52 CBP | 1:41:11 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 3rd Floor ZE 03-0000 RF55 CBP | 1:41:12 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 3rd Floor ZE 03-0000 RF54 | 1:41:13 | DNT | DNT | Did not test inaccessable | 4/28/21 | |||||
| Duct Detector | 3rd Floor ZE 03-0000 RF52 CBP | 1:41:14 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 3rd Floor ZE 03-0000 RF53 CBP | 1:41:15 | Pass | Pass | No point on NCC | 4/7/21 | |||||
| Duct Detector | 3rd Floor ZE EMR SWG 1-3 SF98 CBP | 1:41:16 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 3rd Floor ZE TOS SWG-1 | 1:41:17 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | 3rd Floor ZE TOS SWG-2 | 1:41:18 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | 3rd Floor ZE TOS SWG-3 | 1:41:19 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | 3rd Floor ZE EMR SWG 1-3 | 1:41:20 | Pass | Pass | 4/26/21 | ||||||
| Heat Detector | 3rd Floor ZE EMR SWG 1-3 | 1:41:21 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | 3rd Floor ZE Elev Lobby SWP1-6 | 1:41:22 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | 3rd Floor ZE 03-SW17 Telecom Rm 1 CBP | 1:41:23 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 3rd Floor ZE 03-SW14 CBP | 1:41:24 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 3rd Floor ZE 03-SW12 CBP | 1:41:25 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 3rd Floor ZE 03-SW08 CBP | 1:41:26 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 3rd Floor ZE 03-SW09 Telecom Rm 2 CBP | 1:41:27 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 3rd Floor ZE 03-SW10 CBP | 1:41:28 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 3rd Floor ZE 03-SW11 Telecom Rm CBP | 1:41:29 | Pass | Pass | 4/7/21 | ||||||
| Manual Station | 3rd Floor ZE 03-0000 CBP | 1:41:30 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | 3rd Floor ZE 03-0000 CBP | 1:41:31 | Pass | Pass | 4/7/21 | ||||||
| Beam Detector | 3rd Floor Main Atrium ZF | 1:41:37 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | 3rd Floor Main Atrium ZF | 1:41:38 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | 3rd Floor Main Atrium ZF | 1:41:39 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | 3rd Floor Main Atrium ZF | 1:41:40 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | 3rd Floor Atrium | 1:41:41 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | 3rd Floor Main Atrium ZF | 1:41:43 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Beam Detector | 3rd Floor Main Atrium ZF | 1:41:44 | DNT | DNT | To high up to access need lift | 3/1/21 | |||||
| Duct Detector | 3rd Floor ZF 03-0000 RF53 CBP | 1:41:54 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 3rd Floor ZF 03-0503 Telecom Rm 4 CBP | 1:41:55 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:01 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:04 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:05 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZF EMR SEG 1-3 | 1:42:08 | Pass | Pass | 4/23/21 | ||||||
| Duct Detector | 3rd Floor ZF 03-0000 RF56 CBP | 1:42:11 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 3rd Floor ZF 03-SE06 RF57 CBP Mens Rm 3.5 | 1:42:12 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 3rd Floor ZF EMR SEG1-3 SF100 CBP | 1:42:13 | Pass | Pass | 4/16/21 | ||||||
| Heat Detector | 3rd Floor ZF EMR SEG 1-3 | 1:42:14 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 3rd Floor ZF EMR SEG 1-3 | 1:42:15 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 3rd Floor ZF TOS SEG 1 | 1:42:16 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 3rd Floor ZF TOS SEG 2 | 1:42:17 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 3rd Floor ZF TOS SEG 3 | 1:42:18 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 3rd Floor ZF Elev Lobby SEF 1-2 | 1:42:19 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 3rd Floor ZF Elev Lobby SEP 1-6 | 1:42:20 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 3rd Floor ZF 03-SE08 CBP | 1:42:21 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 3rd Floor ZF 03-SE09 Telecom Rm 3 CBP | 1:42:22 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 3rd Floor ZF 03-SE11 CBP | 1:42:23 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 3rd Floor ZF 03-SE11 Telecom Rm CBP | 1:42:24 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 3rd Floor ZF 03-SE14 CBP | 1:42:25 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 3rd Floor ZF 03-SE12 CBP | 1:42:26 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | 3rd Floor ZF 03-0000 CBP | 1:42:28 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:31 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:32 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:33 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:34 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:35 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:36 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:37 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-0701 (WW) | 1:42:38 | Pass | Pass | 3/17/21 | ||||||
| Duct Detector | 3rd Floor ZG Customs RF43 CBP | 1:42:41 | Pass | Pass | 4/16/21 | ||||||
| Manual Station | 3rd Floor ZG 03-0000 (WW) | 1:42:42 | Pass | Pass | 3/17/21 | ||||||
| Duct Detector | 3rd Floor ZG 03-0701 RF42 in Rm 3.1-02 WW | 1:42:43 | Pass | Pass | 4/2/21 | ||||||
| Duct Detector | 3rd Floor ZG 03-0701 in Rm 3.1-28 RF42 WW | 1:42:44 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-SE16 Tele Closet (WW) | 1:42:45 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | 3rd Floor ZG 03-SE17 Elec Closet (WW) | 1:42:46 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 3rd Floor ZG Elevator Lobby EP 1-3 | 1:42:48 | Pass | Pass | 4/22/21 | ||||||
| Manual Station | 3rd Floor ZG 03-0701 (WW) | 1:42:49 | Pass | Pass | 3/17/21 | ||||||
| Manual Station | 3rd Floor ZG 03-0701 (WW) | 1:42:50 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:01 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:02 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:03 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:04 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:05 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:06 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:07 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:08 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:09 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 (WW) | 1:43:10 | Pass | Pass | 3/17/21 | ||||||
| Duct Detector | 4th Floor ZG 04-0701 RF42 In Rm 4.1-02 WW | 1:43:11 | Pass | Pass | 4/2/21 | ||||||
| Duct Detector | 4th Floor ZF Customs RF43 CBP | 1:43:12 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 4th Floor ZG 04-0701 Personal File RM RF42 WW | 1:43:13 | DNT | DNT | No access | 4/2/21 | |||||
| Smoke Detector | 4th Floor ZG Elevator Lobby EP 1-3 | 1:43:14 | Pass | Pass | 4/22/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 Tele Closet (WW) | 1:43:15 | Pass | Pass | 4/2/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-0701 Elec Closet (WW) | 1:43:16 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG 04-SE19 | 1:43:16 | Pass | Pass | 4/28/21 | ||||||
| Manual Station | 4th Floor ZG 04-0000 (WW) | 1:43:18 | Pass | Pass | 3/17/21 | ||||||
| Manual Station | 4th Floor ZG 04-0701 (WW) | 1:43:19 | Pass | Pass | 3/17/21 | ||||||
| Manual Station | 4th Floor ZG 04-0701 (WW) | 1:43:20 | Pass | Pass | 3/17/21 | ||||||
| Smoke Detector | 4th Floor ZG Rear Lobby EP 1 | 1:43:31 | DNT | DNT | No access | 4/22/21 | |||||
| Duct Detector | 4th Floor ZF 04-0000 RF57 CBP Men Rm 4.5 | 1:43:41 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 4th Floor ZF 04-000 RF56 CBP | 1:43:42 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 4th Floor ZF Elevator Lobby SEF1-2 | 1:43:43 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 4th Floor ZF Elevator Lobby SEP1-6 | 1:43:44 | Pass | Pass | 4/23/21 | ||||||
| Smoke Detector | 4th Floor ZF 04-SE08 Elec Rm CBP | 1:43:45 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 4th Floor ZF 04-SE09 Telecom Rm 3 CBP | 1:43:46 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 4th Floor ZF 04-SE10 Elec Rm CBP | 1:43:47 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 4th Floor ZF 04-SE11 Telecom Rm CBP | 1:43:48 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 4th Floor ZF 04-SE14 Elec Rm CBP | 1:43:49 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 4th Floor ZF 04-SE12 Elec Rm CBP | 1:43:50 | Pass | Pass | 4/8/21 | ||||||
| Manual Station | 4th Floor ZF 04-0000 CBP | 1:43:51 | Pass | Pass | 4/8/21 | ||||||
| Duct Detector | 4th Floor ZE 04-000 RF52 CBP | 1:44:11 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 4th Floor ZE 04-000 RF53 CBP | 1:44:12 | Pass | Pass | 4/7/21 | ||||||
| Duct Detector | 4th Floor ZE 04-000 RF52 | 1:44:13 | DNT | DNT | Did not test inaccessable | 4/28/21 | |||||
| Duct Detector | 4th Floor ZE 04-000 RF55 CBP | 1:44:14 | Pass | Pass | 4/16/21 | ||||||
| Duct Detector | 4th Floor ZE 04-000 RF54 CBP | 1:44:15 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 4th Floor ZE Elevator Lobby SWP1-6 | 1:44:16 | Pass | Pass | 4/26/21 | ||||||
| Smoke Detector | 4th Floor ZE 04-SW17 Telecom Rm 1 CBP | 1:44:17 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 4th Floor ZE 04-SW14 Elec Rm CBP | 1:44:18 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 4th Floor ZE 04-SW12 Elec Rm CBP | 1:44:19 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 4th Floor ZE 04-SW08 Elec Rm CBP | 1:44:20 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 4th Floor ZE 04-SW09 Telecom Rm CBP | 1:44:21 | Pass | Pass | 4/7/21 | ||||||
| Smoke Detector | 4th Floor ZE 04-SW10 Elec Rm CBP | 1:44:22 | Pass | Pass | 4/8/21 | ||||||
| Smoke Detector | 4th Floor ZE 04-SW11 Telecom Rm CBP | 1:44:23 | Pass | Pass | 4/7/21 | ||||||
| Manual Station | 4th Floor ZE 04-0000 CBP | 1:44:24 | Pass | Pass | 4/7/21 | ||||||
| Manual Station | 4th Floor ZE 04-0000 CBP | 1:44:25 | Pass | Pass | 4/8/21 | ||||||
| Duct Detector | 4th Floor ZF 04-000 RF53 CBP | 1:44:54 | Pass | Pass | 4/16/21 | ||||||
| Smoke Detector | 4th Floor ZF 04-0503 Telecom Rm CBP | 1:44:55 | Pass | Pass | 4/7/21 | ||||||
| Duct Detector | 3rd Floor ZA EMR NG 1-3 SF95 NTWR | 1:51:04 | Pass | Pass | 4/14/21 | ||||||
| Duct Detector | 3rd Floor ZA 03-000 RF2 NTWR | 1:51:05 | Pass | Pass | 4/14/21 | ||||||
| Duct Detector | 3rd Floor ZA 03-000 RF1 NTWR | 1:51:06 | Pass | Pass | 4/14/21 | ||||||
| Heat Detector | 3rd Floor ZA EMR NG 1-3 | 1:51:07 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA TOS NG-3 | 1:51:08 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA TOS NG-2 | 1:51:09 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA TOS NG-1 | 1:51:10 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA EMR NG 1-3 | 1:51:11 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA Elev Lobby NP1-6 | 1:51:12 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA Rear Elev Lobby NP-4 | 1:51:13 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA 03-NA08 NTWR | 1:51:14 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA 03-NA13 NTWR | 1:51:15 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA 03-NA15 NTWR | 1:51:16 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | 3rd Floor ZA 03-NA16 NTWR | 1:51:17 | Pass | Pass | 3/19/21 | ||||||
| Manual Station | 3rd Floor ZA 03-NA09 NTWR | 1:51:18 | Pass | Pass | 3/19/21 | ||||||
| Manual Station | 3rd Floor ZA 03-0000 NTWR | 1:51:19 | Pass | Pass | 3/19/21 | ||||||
| Smoke Detector | 3rd Floor ZC Tele Com Rm USAID Telcom Rm | 1:51:24 | Pass | Pass | 4/5/21 | ||||||
| Smoke Detector | 3rd Floor ZC Electric Room USAID Telcom Rm | 1:51:25 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 3rd Floor ZC 03-0000 RF44 USAID | 1:51:26 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 3rd Floor ZC 03-0000 RF47 USAID | 1:51:27 | Pass | Pass | 4/5/21 | ||||||
| Duct Detector | 3rd Floor ZB 03-0000 RF3 | 1:51:28 | DNT | DNT | Did not test inaccessable | 4/28/21 | |||||
| Duct Detector | 3rd Floor ZB 03-0000 RF4 NTWR | 1:51:29 | Pass | Pass | 4/14/21 | ||||||
| Smoke Detector | 3rd Floor ZB 03-NM14 Tele Rm EPA | 1:51:30 | Pass | Pass | Need access | 4/28/21 | |||||
| Smoke Detector | 3rd Floor ZB 03-NM12 Elec Rm C EPA | 1:51:31 | Pass | Pass | 4/15/21 | ||||||
| Smoke Detector | 3rd Floor ZB 03-NM08 Elec Rm A EPA | 1:51:32 | Pass | Pass | 4/15/21 | ||||||
| Smoke Detector | 3rd Floor ZB 03-NM09 Tele Rm EPA | 1:51:33 | Pass | Pass | Need access | 4/28/21 | |||||
| Smoke Detector | 3rd Floor ZB 03-NM10 Elec Rm B EPA | 1:51:34 | Pass | Pass | 4/15/21 | ||||||
| Manual Station | 3rd Floor ZB 03-NM01 EPA | 1:51:35 | Pass | Pass | 4/15/21 | ||||||
| Manual Station | 3rd Floor ZB 03-NM01 EPA | 1:51:36 | Pass | Pass | 4/15/21 | ||||||
| Smoke Detector | 3rd Floor ZA EMR NG1-3 | 1:51:39 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZB EMR NEP 7&8 | 1:51:40 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZB TOS NEP 8 | 1:51:43 | Pass | Pass | 4/19/21 | ||||||
| Smoke Detector | 3rd Floor ZB TOS NEP 7 | 1:51:44 | Pass | Pass | 4/19/21 | ||||||
| Duct Detector | 3rd Floor ZB EMR 301 RF45 NTWR | 1:51:45 | Pass | Pass | 4/14/21 |