J.30 Reagan Building Annual FA Report 3.1.21 - Complete (1).xlsx

XLSX spreadsheet 321 KB Posted

Attached to
Ronald Reagan Building International Trade Center Manager
Solicitation number
47PM0820R0009
Issued by

View the file

Other files

File Type Posted
47PM0820R0009 AM0007 SF30 - 28 September 2022.pdf PDF
47PM0820R0009 AM0006 SF30 - 27 September 2022.pdf PDF
47PM0820R0009 AM0005 SF30 - 29 April 2022.pdf PDF
47PM0820R0009 AM0004 SF30.pdf PDF
J.37 Elevator and Vertical Transportation SOW .pdf PDF
J.45 Centerra and Local 99-99A CBA.pdf PDF
J.19 Wage Rate Determination 2015-4281 Rev 21.pdf PDF
J.40 Reagan Bldg Service Call Work Orders Jan 2020 - Dec 2021.xlsx XLSX spreadsheet
Section A rev 25 Feb 2022.pdf PDF
J.36 RFI Responses revised.pdf PDF
J.44 Event Reports.pdf PDF
J.43 Deliverable #44 Cleaning Plan Option Year 1 2019-20.pdf PDF
J.28 Award Fee Performance Evaluation Plan 16 Feb 2022.pdf PDF
J.42 Landscaping and Snow Removal.pdf PDF
J.41 Water Reports.PDF PDF
J.39 R11 Reagan Complex List of Assets 12-10-2021.xlsx XLSX spreadsheet
Section C - 25 Feb 2022.pdf PDF
Section J - Table of Contents - 25 Feb 2022.pdf PDF
J.34 Food Court Tenant Monthly Sales 2018-21.xlsx XLSX spreadsheet
J.34 MRG-FY18.xlsx XLSX spreadsheet
J.34 Food Court Sales and Breakpoints 2011-2017 -thru Sept 17(1).xlsx XLSX spreadsheet
47PM0820R0009 AM0003 SF30.pdf PDF
J.34 MRG-FY17.xlsx XLSX spreadsheet
J.30 Reagan Building Annual FA Report 3.1.21 - Complete (1)(1).xlsx XLSX spreadsheet
J.34 ITC Event revenue.xlsx XLSX spreadsheet
J.30 Reagan Building Annual Fire Alarm Report 3.1.21 - Complete (1).xlsx XLSX spreadsheet
Section J 27 Jan 2022.pdf PDF
J.34 MRG-FY20.xlsx XLSX spreadsheet
J.31 RRB Parking Equipment Inventory 211207.xlsx XLSX spreadsheet
J.34 MRG-FY19.xlsx XLSX spreadsheet
47PM0820R0009 AM0002 SF30.pdf PDF
47PM0820R0009 AM0001 SF30x.pdf PDF
47PM0820R0009 AM0001 SF30.pdf PDF
Section M.pdf PDF
Section G.pdf PDF
Section E.pdf PDF
Section H.pdf PDF
Section J.pdf PDF
Section F.pdf PDF
Section I.pdf PDF
Section L.pdf PDF
Section K.pdf PDF
Section D.pdf PDF
Section C.pdf PDF
Section B.pdf PDF
Section A.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

General Information

Submitted to: Tyrone Dorsey

Project Name:Ronald Reagan Building Annual FA ITM 2020-2021
Site:Ronald Reagan Building
Location or Building:1300 Pennsylvania Avenue, NW, Washington, DC 20004
Lead Inspector:Kevin Combs/Joe Woodring
Date Inspection Completed:3/1/2021-4/30/21
Fire Alarm Inspection Reports
Panel Inspection Report

Batteries Inspection Report

Alarm & Supervisory Functions Report

Alarm Devices Report

Fire Phones

A/V's

Deficiencies Report

Recommendations Report

Report Prepared by:

11685 Crossroad Circle, Suite L Baltimore, MD 21220 P: 410-628-1155 F: 410-828-1148

Device Quantities

Project:Ronald Reagan Building Annual FA ITM 2020-2021
Site:Ronald Reagan Building
Location:1300 Pennsylvania Avenue, NW, Washington, DC 20004
Inspector:Kevin Combs/Joe Woodring
Date:3/1/2021-4/30/21
Device Quantites By Building
<<
Device TypeQuantity
Manual Pull Stations499
Smoke Detectors1176
Heat Detectors129
Duct Detectors453
Beam Detectors15
Fire Phones356

Panel Inspection Node 1

Project:Ronald Reagan Building Annual FA ITM 2020-2021
Site:Ronald Reagan Building
Location:1300 Pennsylvania Avenue, NW, Washington, DC 20004
Inspector:Kevin Combs/Joe Woodring
Date:3/1/2021-4/30/21
Panel Inspection Report Node 1
<<
Panel Information

Siemens MXL Panel Manufacturer/Model

Fire Command Center Panel Location

Addressable Panel Type

Panel Inspection

Yes x No NA System was normal and clear in operation upon arrival?

xYesNoNAPanel and surrounding equipment, conduit and wiring well
secured and in good condition?

x Yes No NA Are all lamps and displays operating correctly?

x Yes No NA Primary power supply operates properly under full load?

x Yes No NA Transient suppressors visually inspected?

x Yes No NA Have all fuses been checked for rating and supervision?

x Yes No NA Are drawings and wiring diagrams available at the panel?

x Yes No NA Are operating instructions posted or available at the panel?

x Yes No NA Are zones labeled and identified?

Central Station Test

Networked Type Transmission

YesNoxNAAlarm, Trouble and Supervisory indication tested and verified
with the central station?

Self Monitored Operator Called

Printer x Yes No NA Is the type legible?

x Yes No NA Did the printer work?

Panel Inspection Node 2

Project:Ronald Reagan Building Annual FA ITM 2020-2021
Site:Ronald Reagan Building
Location:1300 Pennsylvania Avenue, NW, Washington, DC 20004
Inspector:Kevin Combs/Joe Woodring
Date:3/1/2021-4/30/21
Panel Inspection Report Node 2
<<
Panel Information

Siemens MXL Panel Manufacturer/Model

Fire Command Center Panel Location

Addressable Panel Type

Panel Inspection

Yes x No NA System was normal and clear in operation upon arrival?

xYesNoNAPanel and surrounding equipment, conduit and wiring well
secured and in good condition?

x Yes No NA Are all lamps and displays operating correctly?

x Yes No NA Primary power supply operates properly under full load?

x Yes No NA Transient suppressors visually inspected?

x Yes No NA Have all fuses been checked for rating and supervision?

x Yes No NA Are drawings and wiring diagrams available at the panel?

x Yes No NA Are operating instructions posted or available at the panel?

x Yes No NA Are zones labeled and identified?

Central Station Test

Networked Type Transmission

YesNoxNAAlarm, Trouble and Supervisory indication tested and verified
with the central station?

Self Monitored Operator Called

Printer x Yes No NA Is the type legible?

x Yes No NA Did the printer work?

Panel Inspection Node 3

Project:Ronald Reagan Building Annual FA ITM 2020-2021
Site:Ronald Reagan Building
Location:1300 Pennsylvania Avenue, NW, Washington, DC 20004
Inspector:Kevin Combs/Joe Woodring
Date:3/1/2021-4/30/21
Panel Inspection Report Node 3
<<
Panel Information

Siemens MXL Panel Manufacturer/Model

Fire Command Center Panel Location

Addressable Panel Type

Panel Inspection x Yes No NA System was normal and clear in operation upon arrival?

xYesNoNAPanel and surrounding equipment, conduit and wiring well
secured and in good condition?

x Yes No NA Are all lamps and displays operating correctly?

x Yes No NA Primary power supply operates properly under full load?

x Yes No NA Transient suppressors visually inspected?

x Yes No NA Have all fuses been checked for rating and supervision?

x Yes No NA Are drawings and wiring diagrams available at the panel?

x Yes No NA Are operating instructions posted or available at the panel?

x Yes No NA Are zones labeled and identified?

Central Station Test

Networked Type Transmission

YesNoxNAAlarm, Trouble and Supervisory indication tested and verified
with the central station?

Self Monitored Operator Called

Printer x Yes No NA Is the type legible?

x Yes No NA Did the printer work?

Batteries Inspection

Project:Ronald Reagan Building Annual FA ITM 2020-2021
Site:Tyrone Dorsey
Location:1300 Pennsylvania Avenue, NW, Washington, DC 20004
Inspector:Kevin Combs/Joe Woodring
Date:3/1/2021-4/30/21
Batteries Inspection Report
<<
Battery TypeQtySize

Volts

AmpsBattery YearReadingsLocation/DescriptionEquipment
CoveredPhysical
ConditionFunctional
TestConnection TypeDate InspectedComments
Battery 1 AH/TempBattery 2 AH/Temp
SLA212V 26AH2019100%/ 78.6F100%/ 79.3FFCC Node 3FACP NODE 3PassPassF24/8/21
SLA212V 18AH2020100%/ 79.5F100%/ 78.5FFCC Node 2FACP NODE 2PassPassF24/8/21
SLA212V 18AH2020100%/ 79.3F100%/ 79.5FFCC Node 1FACP NODE 1PassPassF24/8/21
SLA212V 40AH2020100%/ 77.2F100%/ 77.4FSouth Room M.5B EPAPWR Panel 1:32-29PassPassNB4/8/21
SLA212V 18AH2019100% 77.3F100%/ 77.3FSouth Room M.5B EPAPSR 3:80PassPassF24/8/21
SLA212V 7AH2018100%/ 78.6F100%/ 78.6FMezz. CLDPSilent Knight NACPassPassF23/24/21
SLA212V 40AH2020100%/ 78.6F100%/ 77.7FMezz. CLDPPWR PanelPassPassNB3/24/21
SLA212V 18AH2017100%/ 78.4F100%/ 79.7FMezz. CLDPPSR 3:70PassPassF23/24/21
SLA212V 38AH2020100%/ 98F100%/ 80FRoom G.7BStrobe PWR PNL RPassPassNB3/15/21
SLA212V 40AH2017100%/ 98F100%/ 80FRoom G.7BStrobe PWR PNL LPassPassNB3/15/21
SLA212V 18AH202080%/ 79.5F70%/ 80.4FRoom G.7BMXLRV-5.5PassPassF23/15/21
SLA212V 18AH2019100%/ 80.9F100%/ 80.7FRoom G.7BPSR 2-21PassPassF23/15/21
SLA212V 18AH2019100%/ 84.9F100%/ 85.2FRoom G.5BMXLRA-1PassPassF23/15/21
SLA212V 40AH2019100%/ 81.9F100%/ 80.4FRoom G.5BMXLRV-6PassPassNB3/15/21BATTERY 1 IS STARTING TO SHOW SIGNS OF CORROSION
SLA212V 75AH2019100%/ 66.3F100%/ 66.5FRoom C.7BAMP PanelPassPassNB3/15/21
SLA212V 18AH2020100%/ 67.6F100%/ 69.4FRoom C.7BPSR 3-47PassPassF23/15/21
SLA212V 7AH2018100%/ 64.9F100%/ 66.3FRoom C.7BPAD-3PassPassF23/15/21
SLA212V 75AH2019100%/ 59.8F100%/ 61.3FRoom C.4BAMP PanelPassPassNB3/15/21
SLA212V 18AH2019100%/ 66.7F100%/ 68FRoom C.4BPSR 2-65PassPassNB3/15/21
SLA212V 7AH2020100%/ 65.3F100%/ 65.1FRoom C.4BBooster Con 66:6PassPassF23/15/21
SLA212V 12AH2020100%/ 63.1F100%/63.5FRoom C.4BBooster Con 66:5PassPassF23/15/21
SLA212V 18AH2019100%/ 77.1F100%/ 78.4FRoom B1.11PSR 2:230PassPassF23/24/21
SLA212V 18AH2019100%/ 76.4F100%/ 77.1Room B1.11PSR 3:35PassPassF23/24/21
SLA212V 18AH201780%/ 80.1F80%/ 81.1FRoom B1.5PSR 2:240PassPassF23/15/21
SLA212V 35AH2020100%/ 79.8F100%/ 80.2FRoom B2.1PWR PNL 2:244-32PassPassNB3/15/21
SLA212V 75AH2019100%/ 79.8F100%/ 80FRoom B2.1PSR/AMP Panel 3:40PassPassNB3/15/21
SLA212V 18AH2020100%/ 76.1F100%/ 76.5FRoom B3.5-SEPSR 2:220PassPassF23/15/21
SLA212V 55AH2020100%/ 80.7F100%/ 82.4FRoom B4-SE12PWR Panel 2:221-14PassPassNB3/24/21
SLA212V 18AH2017100%/ 78.4F100%/ 78.4FRoom B4-SE12PSR 3:20PassPassF23/24/21
SLA212V 40AH2020100%/ 68.1F100%/ 68.0FRoom B.4-NE11PWR Panel 2:212-32PassPassNB3/15/21
SLA212V 18AH2018100%/ 68.9F100%/ 69.0FRoom B.4-NE11Panel 3-10PassPassF23/15/21
SLA212V 18AH2017100% 78.6F100%/ 78.9FRoom B2.6PSR 3:34PassPassF23/15/21
SLA212V 55AH201880%/ 78.4F80%/ 77FRoom B2.6PWR Panel 2:236-38PassPassNB3/15/21
SLA212V 75AH2019100%/ 78.4F100%/ 78.8FRoom B2.6AMP PanelPassPassNB3/15/21
SLA212V 18AH2017100%/ 73.7F100%/ 75.7FRoom B2.6PWR PNL 2:236-32PassPassF23/15/21
SLA212V 7AH2018100%/ 81.5F100%/ 81.3FRoom B3-NE09SK NAC 2:216-60PassPassF23/24/21
SLA212V 18AH2020100%/ 78.9F100%/ 79.8FRoom B3-NE09PSR 2:210PassPassF23/24/21
SLA212V 18AH201890%/ 71.4F100%/ 72.6FUSAID Telcom 8.10PSRPassPassF24//12/21
SLA212V 18AH2017100%/ 71.5F100%/ 71.8FUSAID Telcom 7.10PSRPassPassF24//12/21
SLA212V 75AH2020100%/ 78.2F100%/ 78.1FUSAID Telcom 7.10AMP Panel 3:130PassPassNB4//12/21
SLA212V 26AH2019100%/ 69.8F100%/ 69FUSAID Telcom 7.10Bottom PWR PNLPassPass4//12/21
SLA212V 38AH201770%/ 69.5F70%/ 68.9USAID Telcom 7.10Top PWR PNLPassPass4//12/21
SLA212v 7AH2019100%/ 70.5100%/ 72.6USAID Telecom 7.10PAD 3 topPassPassF24//12/21
SLA212V 7AH2020100%/ 71.6100%/ 72.6USAID Telecom 7.10PAD 3 Left 3:131-52PassPassF24//12/21
SLA212V 7AH2016100%/ 72.6100%/ 71.6USAID Telecom 7.10PAD 3 RightPassPassF24//12/21
SLA212V 18AH2017USAID Telcom 6.10PSRF24//12/21Couldn’t get access to room. Card reader not working.
SLA212V 35AH2018100%/ 72.6F100%/ 73.4FUSAID Telcom 5.10Strobe PWR PNL 1:72-1PassPassNB4//12/21
SLA212V 18AH201780%/ 74.6F80%/ 75.3FUSAID Telcom 5.10PSRPassPassF24//12/21
SLA212V 18AH2019USAID Telcom 4.10PSRF24//12/21Couldn't get access. Floor under constructon.
SLA212V 38AH202090%/ 73.5F90%/ 73.5FUSAID Telcom 3.10Bottom PWR PNLPassPassNB4//12/21
SLA212V 26AH2019100%/ 74.1F100%/ 74.4FUSAID Telcom 3.10Top PWR PNLPassPassF24//12/21
SLA212V 18AH2019100%/ 73.7F100%/ 74.6FUSAID Telcom 3.10PSRPassPassF24//12/21
SLA212V 75AH2017100%/ 73.5F100%/ 73.5USAID telcom 3.10AMP Panel 3:90PassPassNB4//12/21
SLA212V 12AH2020100%/ 74.5F100%/ 74.5FUSAID Elec Rm 2.09EANac PanelPassPassF24//12/21
SLA212V 12AH2020100%/ 75.9F100%/ 75.8USAID Elec RmNac PanelPassPassF24//12/21
SLA212V 18AH2016100%/ 70.3F80%/ 71.7USAID telcom 2.10PSR 1:30PassPassF24//12/21
SLA212V 18AH201870%/ 75.7F70%/ 76.2FCustoms telcom 2.5PSR-20PassPassF24/15/21
SLA212V 75AH2020100%/ 69.4F100%/ 68.9FCustoms telcom 3.5AMP PanelPassPassNB4/15/21
SLA212V 35AH202070%/ 69.4F70%/ 69.2FCustoms telcom 3.5PWR PNLPassPassNB4/15/21
SLA212V 7AH2019100%/ 76.1F100%/ 68.9FCustoms telcom 4.5PAD 3PassPassF24/15/21
SLA212V 18AH2020FAILFAILCustoms telcom 4.5PSRFailFailF24/15/21Corrossion
SLA212V 7AH2017100%/ 78.2F100%/ 77.7FCustoms telcom 5.5SK BPSPassPassF24/15/21
SLA212V 7AH2020100%/ 77.5F100%/ 76.8FCustoms telcom 5.5PAD-4PassPassF24/15/21
SLA212V 18AH2020100%/ 73.5F100%/ 78.6FCustoms telcom 5.5PSR-120PassPassF24/15/21
SLA212V 55AH2020100%/ 76.2F100%/ 76.4FCustoms telcom 5.5PWR PNLPassPassNB4/15/21
SLA212V 18AH2020100%/ 78.8F100%/ 79.8FCustoms telcom 6.5PSRPassPassF24/15/21
SLA212V 75AH2019100%/ 80.6F100%/ 80FCustoms telcom 7.5AMP PanelPassPassNB4/15/21
SLA212V 40AH2019100%/ 79.5F100%/ 79.2FCustoms telcom 7.5PWR PNLPassPassNB4/15/21
SLA212V 18AH201790%/ 77.3F90%/ 77.7FCustoms telcom 8.5PSRPassPassF24/15/21
SLA212V18AH201790%/ 84.3F90%/ 85.6FCustoms telecom 9.1PSR 3:165PassPassF24/15/21
SLA212V18AH2018100%/ 81.8F100%/ 80.6FCustoms telecom 9.1Pwr PNL 1:88-51PassPassF24/15/21
SLA212V 18AH2017100%/ 85.2F100%/ 86.3FCustoms telcom 9.1PSR 3:160PassPassF24/15/21
SLA212V 18AH201790%/ 78.2F90%/ 78.3FCustoms telcom 9.5AMP PanelPassPassF24/15/21
SLA212V18AH2020100%/ 78.5F100%/ 78.5FCustoms telcom 9.5PSRPassPassF24/15/21
SLA212V 18AH2019100%/ 78.9F100%/ 78.9F9th Flr 9.6 Mech Rm ZCPSR 3:155PassPassF24/8/21
SLA212V 18AH201310%/ 78.5F10%/ 78.5F9th Flr 9.6 Mech Rm ZCPSR 3:150PassFailF24/8/21Expired
SLA212V 18AH201870%/ 78F80%/ 78F9th Flr 9.6 Mech Rm ZCPWR PNL 1:96-1PassPassF24/8/21
SLA212V 7AH2020100%/ 71F100%/ 71F8th Flr Telcom Rm NTWRNac Panel PAD3PassPassF23/24/21
SLA212V 7AH2020100%/ 71F100%/ 72.1F8th Flr Telcom Rm NTWRNac Panel PAD2PassPassF23/24/21
SLA212V 7AH2020100%/ 83.1F100%/ 83.4F7th Flr Telcom Rm NTWRNac PanelPassPassF23/24/21
SLA212V 7AH2020100%/ 85.1F100%/ 84.3F6th Flr Telcom Rm NTWRNac PanelPassPassF23/24/21
SLA212V 7AH2020100%/ 80.2F100%/ 80.9F5th Flr Telcom Rm NTWRNac PanelPassPassF23/24/21
SLA212V 7AH2020100%/ 78.1F100%/ 78.4F4th Flr Telcom Rm NTWRNac PanelPassPassF23/24/21
SLA212V 7AH2017100%/ 81.8F100%/ 81.8F3rd Flr Telcom Rm NTWRNac Panel TopPassPassF23/24/21
SLA212V 7AH2020100%/ 80.4F100%/ 78.9F3rd Flr Telcom Rm NTWRNac Panel BottomPassPassF23/24/21
SLA212V7AH2020100%/ 77.9F100%/ 77.3FMarket to MarketNac PanelPassPassF23/24/21

Alarm & Supervisory Functions

Project:Ronald Reagan Building Annual FA ITM 2020-2021
Site:Ronald Reagan Building
Location:1300 Pennsylvania Avenue, NW, Washington, DC 20004
Inspector:Kevin Combs/Joe Woodring
Date:3/1/2021-4/30/21
Alarm & Supervisory Functions Report
<<
FunctionDescriptionTest Result
Alarm Functions
Alarm Bells/Horns/StrobesEvacuation Alarm functions including Bells/Horns/Strobes actuaute properlyNo A/V testing done per GSA
Alarm Panel Supervisory Functions
Panel AC Power LossLoss of AC power to the alarm panel is detected by the alarm systemPass
Panel Sec Power LossLoss of Secondary power to the alarm panel is detected by the alarm systemPass
Open Alarm CircuitsElectrical opens in initiating and indicating circuits are detectedPass
Short Alarm CircuitsElectrical shorts in initiating and indicating circuits are detectedPass
Ground Faults DetectedGround faults in alarm circuits are detectedPass
Auxiliary Functions
Remote AnnunciatorRemote annunciator shows properlyPass
Stair PressurizationStairwell is pressurized for smoke control by roof fanPass
Elevator RecallElevators are recalled to primary floor except for primary floor alarm initiationNot tested yet.
Elevator Recall Primary FlElevators are recalled to Secondary floor for Primary floor alarm initiationNot tested yet.
HVAC ShutdownHVAC shutdown upon an alarm conditionPass
High/Low AirHigh or low air pressure switch actuation indicating conditions in the dry sprinkler system is detected by the alarm systemN/A
Building TempTemperatures below 40 degress in wet sprinkler areas is detected by the alarm systemPass
Site Water Temp.Water Temperature below 40 degrees in a water tank is supervised by the alarm systemN/A
Site Water LevelSite Water Level too high or low in a water tank is supervised by the alarm systemN/A
Fire Pump Supervisory Functions
Fire Pump PowerFire Pump Power not connected or off is supervised by the alarm systemPass
Fire Pump RunningFire Pump Running is detected by the alarm systemPass
Fire Pump Phase ReversalFire Pump Phase Reversal is detected by the alarm systemPass
Fire Pump Auto PositionFire Pump Controller in the Automatic Position is supervised by the alarm systemPass
Fir Pump or Pump Controller TroubleFire Pump or Pump Controller Trouble is supervised by the alarm systemPass
Generator Supervisory Functions
Generator in Auto PositionGenerator Controller in Auto Position is supervised by the alarm systemPass
Generator or Controller TroubleGenerator or Controller Trouble is supervised by the alarm systemPass
Switch TransferSwitch Transfer between power sources is supervised by the alarm systemPass

Alarm Devices

Project:Ronald Reagan Building Annual FA ITM 2020-2021
Site:Ronald Reagan Building
Location:1300 Pennsylvania Ave, NW, Washington, DC 20004
Inspector:Kevin Combs/Joe WoodringTesting Counts
Date:3/1/2021-4/30/21Total DevicesDevices TestedDevices Not TestedPercentage Done
Alarm Devices Report227222720100
<<Need to update descriptions as tested
Device TypeLocation/DescriptionAddressPhysical
ConditionFunctional
TestCommentsDate Inspected
Duct DetectorMezz Level ZE0404 RF-60S1:21:08PassPassRemote LED did not activate4/29/21
Duct DetectorMezz Level ZE ME-04161:21:09DNTDNTDid not test inaccessable4/29/21
Smoke DetectorMezz Level ZF Elev Lobby SWG1-31:21:10PassPass4/26/21
Smoke DetectorGround Floor Elev Lobby SWP1-61:21:11PassPass4/26/21
Smoke DetectorMezz Level Elev Lobby SEG1-31:21:12PassPass4/23/21
Smoke DetectorMezz Level Elev Lobby SEF1-21:21:13PassPass4/29/21
Smoke DetectorGround Floor Elev Lobby SEP1-61:21:14Passpass4/23/21
Smoke DetectorGround Floor Elev Lobby SEP7-91:21:15PassPass4/23/21
Smoke DetectorMezz Level ME-04221:21:16PassPass3/4/21
Smoke DetectorMezz Level ME-04221:21:17PassPass3/4/21
Smoke DetectorMezz Level ME-04221:21:18PassPass3/4/21
Smoke DetectorMezz Level ME-04181:21:19FailPassSmoke is painted3/4/21
Smoke DetectorMezz Level ME-04181:21:20PassPass3/4/21
Smoke DetectorMezz Level ME-04181:21:21PassPass3/4/21
Smoke DetectorMezz Level ME-04181:21:22PassPass3/4/21
Smoke DetectorMezz Level ME-04181:21:23PassPass3/4/21
Smoke DetectorGround Floor GR-04201:21:24PassPass3/4/21
Smoke DetectorGround Floor GR-04201:21:25PassPass3/4/21
Smoke DetectorGround Floor GR-04201:21:26PassPass3/4/21
Smoke DetectorMezz Level ME-04011:21:27PassPass3/4/21
Smoke DetectorMezz Level ME-04011:21:28PassPass3/4/21
Smoke DetectorMezz 14th St Bridge1:21:29PassPass3/4/21
Smoke DetectorMezz Level ME-04081:21:30PassPass3/4/21
Smoke DetectorMezz Level ME-04061:21:31PassPass3/4/21
Smoke DetectorMezz Level ME-07021:21:32PassPass4/2/21
Smoke DetectorMezz Level ME-SE02A1:21:33PassPass4/2/21
Smoke DetectorMezz Level ME-07081:21:34PassPass4/2/21
Smoke DetectorMezz Level ME-07121:21:35PassPass4/2/21
Smoke DetectorMezz Level ME-0701A1:21:36PassPass4/2/21
Smoke DetectorMezz Level Tele Com Rm EPA1:21:37PassPass4/8/21
Smoke DetectorMezz Level Tele Rm EPA1:21:38PassPass4/8/21
Smoke DetectorMezz Level Elec Closet EPA1:21:39PassPass4/8/21
Manual StationMezz Level ME-04041:21:40PassPass3/4/21
Manual StationMezz Level ME-SE02A1:21:42PassPass4/2/21
Manual StationMezz Level ZE Stair 6B EPA1:21:43PassPass4/8/21
Manual StationMezz Level ZE Stair 6B EPA1:21:44PassPass4/8/21
Manual StationMezz Level ZF ME-07021:21:55PassPass3/4/21
Manual StationMezz Level EPA1:21:58PassPass4/8/21
Manual StationMezz Level EPA1:21:59PassPass4/8/21
Smoke DetectorMezz Level USAID1:22:01PassPass4/2/21
Smoke DetectorMezz Level Electric Closet EPA1:22:02PassPass4/8/21
Manual StationMezz Level USAID Stair 7C1:22:04PassPassNo point on NCC4/2/21
Duct DetectorMezz Level ME-0605 RF35 EPA1:22:05PassPass4/8/21
Smoke DetectorMezz Level Tele Com Room EPA1:22:06PassPass4/8/21
Smoke DetectorMezz Level Jan Closet1:22:08PassPass3/4/21
Manual StationMezz Level Stair 6C EPA1:22:09PassPass4/8/21
Smoke DetectorMezz Level ZF ME-04221:22:16PassPass3/4/21
Smoke DetectorGround Floor GR-05131:22:17PassPass3/4/21
Smoke DetectorMezz Level ME-05061:22:18PassPass3/4/21
Smoke DetectorMezz Level ME-05041:22:19PassPass3/4/21
Smoke DetectorGround Floor East Atrium1:22:20PassPass3/4/21
Smoke DetectorGround Floor East Atrium1:22:21PassPass3/4/21
Smoke DetectorGround Floor East Atrium High Ceiling1:22:22DNTDNTneed boom lift to test3/1/21
Smoke DetectorGround Floor ZF GR-05181:22:25PassPass3/4/21
Smoke DetectorGround Floor ZF GR-05181:22:26PassPass3/4/21
Smoke DetectorGround Floor ZF GR-05181:22:27PassPass3/4/21
Duct DetectorMezz Level USAID RF-401:22:32PassPass3/25/21
Duct DetectorMezz Level USAID RF-401:22:33PassPass3/25/21
Duct DetectorMezz Level USAID RF-761:22:35PassPass3/25/21
Smoke DetectorMezz Level ZG Tele Com Room1:22:36PassPassNeed Access USAID4/2/21
Smoke DetectorMezz Level ZG Elec Closet1:22:37PassPass4/2/21
Smoke DetectorMezz Level Elev Lobby EP 1-31:22:38DNTDNTDid not test inaccessable4/22/21
Manual StationMezz Level USAID Stair 7C1:22:39PassPass4/2/21
Duct DetectorMezz Level Child Care RF-711:22:49PassPass3/4/21
Smoke DetectorMezz Level Elev Lobby CCP-11:22:50PassPass4/22/21
Smoke DetectorMezz Level Mech Rm 0722 Child Care1:22:51PassPass3/4/21
Smoke DetectorMezz Level Elec Room 0714 Child Care1:22:52PassPass3/4/21
Manual StationMezz Level Child Care1:22:53PassPass3/4/21
Manual StationMezz Level ZE Child Care1:22:54PassPass3/4/21
Manual StationMezz Level ZE EPA1:22:55PassPass4/8/21
Duct Detector2nd Floor ZE RF52 CBP1:23:05PassPass4/16/21
Duct Detector2nd Floor ZE RF55 CBP1:23:06PassPass4/16/21
Duct Detector2nd Floor ZE RF60S CBP1:23:07PassPass4/16/21
Duct Detector2nd Floor RF52 CBP1:23:08DNTDNTDid not test inaccessable4/16/21
Duct Detector2nd Floor ZE RF53 CBP1:23:09PassPass4/16/21
Duct Detector2nd Floor ZE RF54 CBP1:23:10PassPass4/16/21
Smoke Detector2nd Floor Elev Lobby SWP1-61:23:11PassPass4/26/21
Smoke Detector2nd Floor ZE 02-SW17 Telecom Rm CBP1:23:12PassPass4/7/21
Smoke Detector2nd Floor ZE 02-SW14 CBP1:23:13PassPass4/8/21
Smoke Detector2nd Floor ZE 02-SW12 CBP1:23:14PassPass4/8/21
Smoke Detector2nd Floor ZE 02-SW11 Telecom Rm CBP1:23:15PassPassNo point on NCC4/7/21
Smoke Detector2nd Floor ZE 02-SW08 CBP1:23:16PassPass4/8/21
Smoke Detector2nd Floor ZE 02-SW09 Telecom Rm 2 CBP1:23:17PassPass4/7/21
Smoke Detector2nd Floor ZE 02-SW10 CBP1:23:18PassPass4/8/21
Manual Station2nd Floor ZE CBP1:23:19PassPass4/8/21
Manual Station2nd Floor ZE CBP1:23:20PassPass4/7/21
Smoke Detector2nd Floor ZG USCS Tel Room1:23:34PassPass4/28/21
Duct Detector2nd Floor ZG 02-0000 RF77 CBP1:23:35PassPass4/16/21
Duct Detector2nd Floor ZG 02-0701 RF42 CBP1:23:36DNTDNTDid not test inaccessable4/16/21
Smoke Detector2nd Floor ZG Elev Lobby EP 1-31:23:37DNTDNTDid not test inaccessable4/22/21
Smoke Detector2nd Floor ZG 02-07011:23:38PassPass4/7/21
Smoke Detector2nd Floor ZG 02-07011:23:39PassPass4/7/21
Smoke Detector2nd Floor ZG 02-07021:23:40PassPass4/7/21
Smoke DetectorGround Floor ZG High Ceiling1:23:41DNTDNTneed boom lift to test3/1/21
Smoke DetectorGround Floor ZG High Ceiling1:23:42DNTDNTneed boom lift to test3/1/21
Smoke DetectorGround Floor ZG High Ceiling1:23:43DNTDNTneed boom lift to test3/1/21
Smoke DetectorGround Floor ZG High Ceiling1:23:44DNTDNTneed boom lift to test3/1/21
Smoke Detector2nd Floor ZG 02-SE18 Telecom Rm CBP1:23:45PassPass4/7/21
Smoke Detector2nd Floor ZG 02-SE19 CBP1:23:46PassPass4/7/21
Manual Station2nd Floor ZG 02-0000 CBP1:23:47PassPass4/7/21
Manual Station2nd Floor ZG 02-00001:23:48PassPass4/7/21
Manual Station2nd Floor ZG 02-07011:23:49PassPass4/7/21
Duct Detector2nd Floor ZF 02-000 RF44 USAID1:24:05PassPassWrong Label Should be Zone C4/5/21
Duct Detector2nd Floor ZF 02-000 RF47 USAID1:24:06PassPassWrong Label Should be Zone C4/5/21
Duct Detector2nd Floor ZF 02-000 RF561:24:07DNTDNTDid not test inaccessable4/5/21
Duct Detector2nd Floor ZF 02-000 RF53 CBP1:24:08PassPass4/16/21
Duct Detector2nd Floor ZF 02-000 RF57 CBP Mens Rm 2.51:24:09PassPass4/16/21
Smoke Detector2nd Floor ZF Elev Lobby Sep1-61:24:10PassPass4/23/21
Smoke Detector2nd Floor ZF Elev Lobby SEF1-21:24:11PassPass4/23/21
Smoke Detector2nd Floor ZF 02-SE08 CBP1:24:12PassPass4/8/21
Smoke Detector2nd Floor ZF 02-SE09 Telecom Rm 3 CBP1:24:13PassPass4/7/21
Smoke Detector2nd Floor ZF 02-SE10 CBP1:24:14PassPass4/8/21
Smoke Detector2nd Floor ZF 02-SE11 Telecom Rm CBP1:24:15PassPass4/7/21
Smoke Detector2nd Floor ZF 02-SE14 CBP1:24:17PassPass4/8/21
Smoke Detector2nd Floor ZF 02-SE12 CBP1:24:19PassPass4/8/21
Smoke Detector2nd Floor ZF 02-0503 Telecom Rm 4 CBP1:24:20PassPass4/7/21
Smoke Detector2nd Floor ZF 02-0502 CBP1:24:21PassPass4/16/21
Smoke Detector2nd Floor ZF 02-0501 CBP1:24:22PassPass4/16/21
Smoke DetectorGround Floor ZF East Atrium1:24:23DNTDNTneed boom lift to test3/1/21
Smoke DetectorGround Floor ZF East Atrium1:24:24DNTDNTneed boom lift to test3/1/21
Smoke Detector2nd Floor ZF Bridge East Atrium1:24:25DNTDNTneed boom lift to test3/1/21
Smoke Detector2nd Floor ZF Bridge East Atrium1:24:26DNTDNTneed boom lift to test3/1/21
Smoke DetectorGround Floor ZF East Atrium1:24:27DNTDNTneed boom lift to test3/1/21
Smoke DetectorGround Floor ZF East Atrium1:24:28DNTDNTneed boom lift to test3/1/21
Smoke DetectorGround Floor ZF East Atrium1:24:29DNTDNTneed boom lift to test3/1/21
Manual Station2nd Floor ZF 02-0000 CBP1:24:30PassPass4/7/21
Manual Station2nd Floor ZG 02-SE01 CBP1:24:31PassPass4/8/21
Smoke Detector2nd Floor ZG EMR SEP 7-91:24:46PassPass4/23/21
Duct Detector2nd Floor ZF EMR SEP 7-9 SF-94 CBP1:24:49PassPass4/16/21
Heat Detector2nd Floor ZF EMR SEP 7-9 SF-941:24:50PassPass4/23/21
Smoke Detector2nd Floor ZG TOS SEP-71:24:51PassPass4/23/21
Smoke Detector2nd Floor ZG TOS SEP-81:24:52PassPass4/23/21
Smoke Detector2nd Floor ZG TOS SEP-91:24:53PassPass4/23/21
Smoke Detector2nd Floor ZG EMR Sep 7-91:24:54PassPass4/23/21
Manual Station2nd Floor ZG EMR 07051:24:55PassPass4/23/21
Smoke DetectorMezz Level ZB Elev Lobby NG 1-31:31:11PassPass4/19/21
Smoke DetectorGround Floor ZB Elev Lobby NP 1-61:31:12PassPass4/19/21
Smoke DetectorMezz Level ZB ME-01011:31:15PassPass4/28/21
Manual StationMezz Level ZB Stair 1A1:31:16PassPass4/28/21
Smoke DetectorGround Floor ZB GR-01001:31:23PassPass3/4/21
Duct DetectorMezz Level ZB Mens Rm RF141:31:30PassPass4/29/21
Smoke DetectorMezz Level ZB Elec Closet1:31:31PassPass3/24/21
Smoke DetectorMezz Level ZB Tele Com Room1:31:32PassPass3/24/21
Smoke DetectorCon Level ZB CO-03251:31:33DNTDNTneed boom lift to test3/12/21
Smoke DetectorCon Level ZB CO-03251:31:34PassPass3/12/21
Smoke DetectorGround Floor ZB GR-03251:31:34PassPass3/4/21
Smoke DetectorGround Floor ZB GR-03071:31:35PassPass3/4/21
Smoke DetectorCon Level ZB CO-03071:31:36PassPass3/12/21
Smoke DetectorGround Floor ZB GR-03071:31:36PassPass3/4/21
Smoke DetectorGround Floor ZB GR-03251:31:37DNTDNTinaccessible through grate.3/1/21
Smoke DetectorGround Floor ZB GR-03251:31:38DNTDNTinaccessible through grate.3/1/21
Smoke DetectorGround Floor ZB GR-03251:31:39DNTDNTinaccessible through grate.3/1/21
Smoke DetectorGround Floor ZB GR-01001:31:40DNTDNTinaccessible through grate.3/1/21
Smoke DetectorGround Floor ZB GR-01001:31:41DNTDNTinaccessible through grate.3/1/21
Smoke DetectorGround Floor ZB GR-01441:31:42PassPass3/4/21
Smoke DetectorGround Floor ZB GR-01441:31:43PassPass3/4/21
Smoke DetectorGround Floor ZB GR-01441:31:44PassPass3/4/21
Smoke DetectorGround Floor ZB GR-01441:31:45PassPass3/4/21
Smoke DetectorGround Floor ZB GR-01441:31:46PassPass3/4/21
Manual StationMezz Level ZB ME-NM011:31:47PassPass3/24/21
Manual StationMezz Level ZB ME-03021:31:48PassPass3/24/21
Duct DetectorMezz Level ZD ME-0206 RF311:32:05PassPass3/25/21
Duct DetectorMezz Level ZD ME-0203 RF361:32:06PassPass3/25/21
Duct DetectorMezz Level ZD ME-0208 RF361:32:07PassPass3/25/21
Duct DetectorMezz Level ZD ME-0200 RF731:32:08PassPass3/25/21
Duct DetectorMezz Level ZD ME-0200 RF731:32:09PassPass3/25/21
Smoke DetectorMezz Level ZD ME-0201 Telecom Rm1:32:12PassPass3/24/21
Smoke DetectorMezz Level ZD ME-0202 Elec Rm1:32:13PassPass3/24/21
Smoke DetectorMezz Level ZD Elec Closet1:32:14PassPass3/24/21
Smoke DetectorMezz Level ZD Tele Com Room1:32:15PassPass3/24/21
Smoke DetectorMezz Level ZD ME-03071:32:16PassPass3/24/21
Manual StationMezz Level ZD ME-02061:32:17PassPass3/24/21
Manual StationMezz Level ZD ME-02061:32:18PassPass3/24/21
Manual StationMezz Level ZD Commerce Dept1:32:19PassPassNo point on NCC3/24/21
Manual StationMezz Level ZD ME-11011:32:20PassPassNo point on NCC3/24/21
Manual StationMezz Level ZD ME-11131:32:21PassPassNo point on NCC3/24/21
Duct DetectorMezz Level ZF 0405 RF-60N1:32:30PassPass4/29/21
Smoke DetectorMezz Level ZF Elev Lobby NWG1-31:32:31PassPass4/22/21
Smoke DetectorMezz Level ZF ME-04211:32:32PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04211:32:33PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04191:32:34PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04191:32:35PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04191:32:36PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04191:32:37PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04191:32:38PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04191:32:39PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04191:32:40PassPass3/4/21
Smoke DetectorMezz Level ZF ME-04211:32:41PassPass3/4/21
Smoke DetectorGround Floor ZF GR-04211:32:42PassPass3/4/21
Smoke DetectorGround Floor ZF GR-04211:32:43PassPass3/4/21
Smoke DetectorGround Floor ZF GR-04071:32:44PassPass3/4/21
Smoke DetectorMezz Level ZF Tele Com Room1:32:45PassPass3/4/21
Smoke DetectorMezz Level ZF Electric Room1:32:46PassPass3/4/21
Manual StationMezz Level ZF ME-0405 Stair 4A1:32:47PassPass3/4/21
Smoke DetectorMezz Level ZF Tele Com Room1:33:05PassPass4/9/21
Smoke DetectorGround Floor ZD NWP1-6 Elev Lobby1:33:06PassPass4/21/21
Manual StationMezz Level ZD Stair 2B1:33:07PassPass3/24/21
Manual StationMezz Level ZD Stair 2B1:33:08PassPass3/24/21
Smoke DetectorMezz ZF Elev Lobby NEG 1-31:33:18PassPass4/22/21
Smoke DetectorMezz Level ZF Elev Lobby NEF1-21:33:19PassPass4/21/21
Smoke DetectorGround Floor Elev Lobby NEP 11-161:33:20PassPass4/21/21
Smoke DetectorGround Floor ZF Elev Lobby NEP 1-61:33:21PassPass4/21/21
Smoke DetectorMezz Level ZF Elev Lobby FS 1-21:33:22PassPass4/19/21
Smoke DetectorGround Floor ZF Elev Lobby NEP 7-101:33:23PassPass4/21/21
Smoke DetectorMezz Level ZF Elev Lobby PFP1-21:33:24PassPass4/19/21
Smoke DetectorGround Floor ZF East Atrium1:33:25PassPass3/4/21
Smoke DetectorMezz Level ZF ME-05031:33:26PassPass3/4/21
Smoke DetectorMezz Level ZF ME-05051:33:27PassPass3/4/21
Smoke DetectorGround Floor ZF GR-05121:33:28PassPass3/4/21
Duct DetectorMezz Level ZC ME-0507 RF301:33:29PassPass3/25/21
Smoke DetectorGround Floor ZF GR-03271:33:30PassPass3/4/21
Smoke DetectorGround Floor ZF GR-03271:33:31PassPass3/4/21
Smoke DetectorGround Floor ZF GR-03261:33:32PassPass3/4/21
Smoke DetectorGround Floor ZF GR-03261:33:33PassPass3/4/21
Smoke DetectorGround Floor ZF GR-03261:33:34PassPass3/4/21
Smoke DetectorGround Floor ZF GR-03261:33:35PassPass3/4/21
Smoke DetectorMezz Level ZF Sec Room 03231:33:36PassPass4/29/21
Smoke DetectorMezz Level ZF Elec Room 03251:33:37PassPass4/28/21
Smoke DetectorMezz Level ZF over Stair 8A1:33:38PassPass3/4/21
Smoke DetectorMezz Level ZF over Stair 8A1:33:39PassPass3/4/21
Manual StationMezz Level ZF Atrium1:33:40PassPass3/4/21
Manual StationMezz Level ZD ME-NE021:33:41PassPass3/4/21
Manual StationMezz Level ZF ME-NE02A1:33:42PassPass4/29/21
Manual StationMezz Level ZF ME-0309A1:33:43PassPass4/28/21
Manual StationMezz Level ZC Stair 3D EPA1:33:44PassPass4/8/21
Manual Station2nd Floor ZA Stair 1A NTWR1:35:01PassPass3/19/21
Duct Detector2nd Floor ZA 02-1000 RF-2 NTWR1:35:07PassPass4/14/21
Duct Detector2nd Floor ZA 02-0000 RF-1 NTWR1:35:08PassPass4/14/21
Smoke Detector2nd Floor ZA Elev Lobby NP 1-61:35:09PassPass4/19/21
Smoke Detector2nd Floor ZA 02-NA08 NTWR1:35:10PassPass3/19/21
Smoke Detector2nd Floor ZA 02-NA13 NTWR1:35:11PassPass3/19/21
Smoke Detector2nd Floor ZA 02-NA16 NTWR1:35:12PassPass3/19/21
Smoke Detector2nd Floor ZA 02-NA15 NTWR1:35:13PassPass3/19/21
Smoke Detector2nd Floor ZA Sister Cities NTWR1:35:14PassPass3/19/21
Smoke DetectorCon Level ZB Elev Lobby AP-11:35:15PassPass4/19/21
Smoke DetectorCon Level ZA C0-10001:35:16DNTDNTneed boom lift to test3/12/21
Smoke DetectorCon Level ZA C0-10001:35:17DNTDNTneed boom lift to test3/12/21
Smoke DetectorCon Level ZA C0-10001:35:18DNTDNTneed boom lift to test3/12/21
Smoke DetectorCon Level ZA C0-10001:35:19DNTDNTneed boom lift to test3/12/21
Manual Station2nd Floor ZA 02-0000 USAID1:35:20PassPass4/5/21
Manual Station2nd Floor ZA 02-0000 NTWR1:35:21PassPass3/19/21
Manual Station2nd Floor ZA 02-NA09 NTWR1:35:22PassPass3/19/21
Manual Station2nd Floor ZA 02-0000 USAID1:35:25PassPass4/5/21
Duct Detector2nd Floor ZD 02-0000 RF60N USAID1:35:37DNTDNTDid not test inaccessable4/5/21
Duct Detector2nd Floor ZD 02-0000 RF46 USAID1:35:38DNTDNTDid not test inaccessable4/5/21
Duct Detector2nd Floor ZD 02-0000 RF47 USAID1:35:39PassPass4/5/21
Duct Detector2nd Floor ZD 02-0000 RF46 USAID1:35:40PassPass4/5/21
Duct Detector2nd Floor ZD 02-0000 RF49 USAID1:35:41DNTDNTDid not test inaccessable4/5/21
Duct Detector2nd Floor ZD 02-0000 RF48 USAID1:35:42PassPass4/5/21
Smoke Detector2nd Floor ZD NWP 1-6 ELEV Lobby1:35:43PassPass4/21/21
Smoke Detector2nd Floor ZD 02-NW-17 USAID Telcom Rm1:35:44PassPass4/5/21
Smoke Detector2nd Floor ZD 02-NW12 USAID Elec Rm1:35:45PassPass4/5/21
Smoke Detector2nd Floor ZD 02-NW14 USAID Elec Rm1:35:46PassPass4/5/21
Smoke Detector2nd Floor ZD 02-NW-11 USAID Telcom Rm1:35:47PassPass4/5/21
Smoke Detector2nd Floor ZD 02-NW10 USAID Elec Rm1:35:48PassPass4/5/21
Smoke Detector2nd Floor ZD 02-NW09 USAID Telcom Rm1:35:49PassPass4/5/21
Smoke Detector2nd Floor ZD 02-NW08 USAID Elec Rm1:35:50PassPass4/5/21
Manual Station2nd Floor ZD 02-0000 USAID Stair 2B1:35:51PassPass4/5/21
Manual Station2nd Floor ZD 02-0000 USAID1:35:52PassPass4/5/21
Smoke Detector2nd Floor ZB 02-NM14 Tele Rm USAID1:36:04PassPassNeed access4/15/21
Duct Detector2nd Floor ZB 02-0000 RF-3 USAID1:36:05PassPass4/5/21
Duct Detector2nd Floor ZB 02-0000 RF-4 USAID1:36:06PassPass4/5/21
Smoke Detector2nd Floor ZB 02-NM12 USAID Elec Rm1:36:07PassPass4/5/21
Smoke Detector2nd Floor ZB 02-NM13 USAID Elec Rm1:36:08PassPass4/5/21
Smoke Detector2nd Floor ZB 02-NM09 USAID Tele Rm1:36:09PassPass4/5/21
Smoke Detector2nd Floor ZB 02-NM08 USAID Elec Rm1:36:10PassPass4/5/21
Manual Station2nd Floor ZB 02-NM01 USAID1:36:11PassPass4/5/21
Duct Detector2nd Floor ZC 02-0000 RF-50 USAID1:36:25PassPass4/5/21
Duct Detector2nd Floor ZC 02-0000 RF-51 USAID1:36:26DNTDNTDid not test inaccessable4/5/21
Duct Detector2nd Floor ZC 02-0306 RF39 USAID1:36:27DNTDNTDid not test inaccessable4/5/21
Duct Detector2nd Floor ZC 02-0000 RF45 USAID1:36:28DNTDNTDid not test inaccessable4/5/21
Smoke Detector2nd Floor ZC Elev Lobby PFP1-21:36:29PassPass4/19/21
Smoke Detector2nd Floor ZC Elev Lobby FS 1-21:36:30PassPass4/19/21
Smoke Detector2nd Floor ZC Elev Lobby NEP1-61:36:31PassPass4/21/21
Smoke Detector2nd Floor ZC Elev Lobby NEP9-101:36:32PassPass4/21/21
Smoke Detector2nd Floor ZC Elev Lobby NEP11-161:36:33PassPass4/21/21
Smoke Detector2nd Floor ZC Elev Lobby NEF1-21:36:34PassPass4/21/21
Smoke Detector2nd Floor ZC 02-0305 USAID Telcom Rm1:36:35PassPass4/5/21
Smoke Detector2nd Floor ZC 02-NE09 USAID Telcom Rm1:36:36PassPass4/5/21
Smoke Detector2nd Floor ZC 02-NE08 USAID Elec Rm1:36:37PassPass4/5/21
Smoke Detector2nd Floor ZC 02-NE11 USAID Telcom Rm1:36:38PassPass4/5/21
Smoke Detector2nd Floor ZC 02-NE14 USAID Elec Rm1:36:39PassPassNo point on NCC4/5/21
Smoke Detector2nd Floor ZC 02-NE12 USAID Elec Rm1:36:40PassPassNo point on NCC4/5/21
Manual Station2nd Floor ZC 02-0000 USAID Stair 3A1:36:41PassPass4/5/21
Manual Station2nd Floor ZC 02-0000 USAID Stair 3A1:36:42PassPass4/5/21
Manual Station2nd Floor ZC 02-0305 USAID Telcom Rm1:36:43PassPass4/5/21
Smoke Detector2nd Floor ZC Pavillion1:36:53PassPassNo point on NCC4/5/21
Beam DetectorMain Atrium ZF1:41:01DNTDNTTo high up to access need lift3/1/21
Beam DetectorMain Atrium ZF1:41:02DNTDNTTo high up to access need lift3/1/21
Beam DetectorMain Atrium ZF1:41:03DNTDNTTo high up to access need lift3/1/21
Beam DetectorMain Atrium ZF1:41:04DNTDNTTo high up to access need lift3/1/21
Duct Detector3rd Floor ZE 03-0000 RF52 CBP1:41:11PassPass4/16/21
Duct Detector3rd Floor ZE 03-0000 RF55 CBP1:41:12PassPass4/16/21
Duct Detector3rd Floor ZE 03-0000 RF541:41:13DNTDNTDid not test inaccessable4/28/21
Duct Detector3rd Floor ZE 03-0000 RF52 CBP1:41:14PassPass4/16/21
Duct Detector3rd Floor ZE 03-0000 RF53 CBP1:41:15PassPassNo point on NCC4/7/21
Duct Detector3rd Floor ZE EMR SWG 1-3 SF98 CBP1:41:16PassPass4/16/21
Smoke Detector3rd Floor ZE TOS SWG-11:41:17PassPass4/26/21
Smoke Detector3rd Floor ZE TOS SWG-21:41:18PassPass4/26/21
Smoke Detector3rd Floor ZE TOS SWG-31:41:19PassPass4/26/21
Smoke Detector3rd Floor ZE EMR SWG 1-31:41:20PassPass4/26/21
Heat Detector3rd Floor ZE EMR SWG 1-31:41:21PassPass4/26/21
Smoke Detector3rd Floor ZE Elev Lobby SWP1-61:41:22PassPass4/26/21
Smoke Detector3rd Floor ZE 03-SW17 Telecom Rm 1 CBP1:41:23PassPass4/7/21
Smoke Detector3rd Floor ZE 03-SW14 CBP1:41:24PassPass4/8/21
Smoke Detector3rd Floor ZE 03-SW12 CBP1:41:25PassPass4/8/21
Smoke Detector3rd Floor ZE 03-SW08 CBP1:41:26PassPass4/16/21
Smoke Detector3rd Floor ZE 03-SW09 Telecom Rm 2 CBP1:41:27PassPass4/7/21
Smoke Detector3rd Floor ZE 03-SW10 CBP1:41:28PassPass4/8/21
Smoke Detector3rd Floor ZE 03-SW11 Telecom Rm CBP1:41:29PassPass4/7/21
Manual Station3rd Floor ZE 03-0000 CBP1:41:30PassPass4/8/21
Manual Station3rd Floor ZE 03-0000 CBP1:41:31PassPass4/7/21
Beam Detector3rd Floor Main Atrium ZF1:41:37DNTDNTTo high up to access need lift3/1/21
Beam Detector3rd Floor Main Atrium ZF1:41:38DNTDNTTo high up to access need lift3/1/21
Beam Detector3rd Floor Main Atrium ZF1:41:39DNTDNTTo high up to access need lift3/1/21
Beam Detector3rd Floor Main Atrium ZF1:41:40DNTDNTTo high up to access need lift3/1/21
Beam Detector3rd Floor Atrium1:41:41DNTDNTTo high up to access need lift3/1/21
Beam Detector3rd Floor Main Atrium ZF1:41:43DNTDNTTo high up to access need lift3/1/21
Beam Detector3rd Floor Main Atrium ZF1:41:44DNTDNTTo high up to access need lift3/1/21
Duct Detector3rd Floor ZF 03-0000 RF53 CBP1:41:54PassPass4/16/21
Smoke Detector3rd Floor ZF 03-0503 Telecom Rm 4 CBP1:41:55PassPass4/7/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:01PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:04PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:05PassPass3/17/21
Smoke Detector3rd Floor ZF EMR SEG 1-31:42:08PassPass4/23/21
Duct Detector3rd Floor ZF 03-0000 RF56 CBP1:42:11PassPass4/16/21
Duct Detector3rd Floor ZF 03-SE06 RF57 CBP Mens Rm 3.51:42:12PassPass4/16/21
Duct Detector3rd Floor ZF EMR SEG1-3 SF100 CBP1:42:13PassPass4/16/21
Heat Detector3rd Floor ZF EMR SEG 1-31:42:14PassPass4/23/21
Smoke Detector3rd Floor ZF EMR SEG 1-31:42:15PassPass4/23/21
Smoke Detector3rd Floor ZF TOS SEG 11:42:16PassPass4/23/21
Smoke Detector3rd Floor ZF TOS SEG 21:42:17PassPass4/23/21
Smoke Detector3rd Floor ZF TOS SEG 31:42:18PassPass4/23/21
Smoke Detector3rd Floor ZF Elev Lobby SEF 1-21:42:19PassPass4/23/21
Smoke Detector3rd Floor ZF Elev Lobby SEP 1-61:42:20PassPass4/23/21
Smoke Detector3rd Floor ZF 03-SE08 CBP1:42:21PassPass4/8/21
Smoke Detector3rd Floor ZF 03-SE09 Telecom Rm 3 CBP1:42:22PassPass4/7/21
Smoke Detector3rd Floor ZF 03-SE11 CBP1:42:23PassPass4/16/21
Smoke Detector3rd Floor ZF 03-SE11 Telecom Rm CBP1:42:24PassPass4/7/21
Smoke Detector3rd Floor ZF 03-SE14 CBP1:42:25PassPass4/8/21
Smoke Detector3rd Floor ZF 03-SE12 CBP1:42:26PassPass4/8/21
Manual Station3rd Floor ZF 03-0000 CBP1:42:28PassPass4/8/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:31PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:32PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:33PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:34PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:35PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:36PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:37PassPass3/17/21
Smoke Detector3rd Floor ZG 03-0701 (WW)1:42:38PassPass3/17/21
Duct Detector3rd Floor ZG Customs RF43 CBP1:42:41PassPass4/16/21
Manual Station3rd Floor ZG 03-0000 (WW)1:42:42PassPass3/17/21
Duct Detector3rd Floor ZG 03-0701 RF42 in Rm 3.1-02 WW1:42:43PassPass4/2/21
Duct Detector3rd Floor ZG 03-0701 in Rm 3.1-28 RF42 WW1:42:44PassPass4/2/21
Smoke Detector3rd Floor ZG 03-SE16 Tele Closet (WW)1:42:45PassPass4/2/21
Smoke Detector3rd Floor ZG 03-SE17 Elec Closet (WW)1:42:46PassPass3/17/21
Smoke Detector3rd Floor ZG Elevator Lobby EP 1-31:42:48PassPass4/22/21
Manual Station3rd Floor ZG 03-0701 (WW)1:42:49PassPass3/17/21
Manual Station3rd Floor ZG 03-0701 (WW)1:42:50PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:01PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:02PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:03PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:04PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:05PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:06PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:07PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:08PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:09PassPass3/17/21
Smoke Detector4th Floor ZG 04-0701 (WW)1:43:10PassPass3/17/21
Duct Detector4th Floor ZG 04-0701 RF42 In Rm 4.1-02 WW1:43:11PassPass4/2/21
Duct Detector4th Floor ZF Customs RF43 CBP1:43:12PassPass4/16/21
Duct Detector4th Floor ZG 04-0701 Personal File RM RF42 WW1:43:13DNTDNTNo access4/2/21
Smoke Detector4th Floor ZG Elevator Lobby EP 1-31:43:14PassPass4/22/21
Smoke Detector4th Floor ZG 04-0701 Tele Closet (WW)1:43:15PassPass4/2/21
Smoke Detector4th Floor ZG 04-0701 Elec Closet (WW)1:43:16PassPass3/17/21
Smoke Detector4th Floor ZG 04-SE191:43:16PassPass4/28/21
Manual Station4th Floor ZG 04-0000 (WW)1:43:18PassPass3/17/21
Manual Station4th Floor ZG 04-0701 (WW)1:43:19PassPass3/17/21
Manual Station4th Floor ZG 04-0701 (WW)1:43:20PassPass3/17/21
Smoke Detector4th Floor ZG Rear Lobby EP 11:43:31DNTDNTNo access4/22/21
Duct Detector4th Floor ZF 04-0000 RF57 CBP Men Rm 4.51:43:41PassPass4/16/21
Duct Detector4th Floor ZF 04-000 RF56 CBP1:43:42PassPass4/16/21
Smoke Detector4th Floor ZF Elevator Lobby SEF1-21:43:43PassPass4/23/21
Smoke Detector4th Floor ZF Elevator Lobby SEP1-61:43:44PassPass4/23/21
Smoke Detector4th Floor ZF 04-SE08 Elec Rm CBP1:43:45PassPass4/8/21
Smoke Detector4th Floor ZF 04-SE09 Telecom Rm 3 CBP1:43:46PassPass4/7/21
Smoke Detector4th Floor ZF 04-SE10 Elec Rm CBP1:43:47PassPass4/8/21
Smoke Detector4th Floor ZF 04-SE11 Telecom Rm CBP1:43:48PassPass4/7/21
Smoke Detector4th Floor ZF 04-SE14 Elec Rm CBP1:43:49PassPass4/8/21
Smoke Detector4th Floor ZF 04-SE12 Elec Rm CBP1:43:50PassPass4/8/21
Manual Station4th Floor ZF 04-0000 CBP1:43:51PassPass4/8/21
Duct Detector4th Floor ZE 04-000 RF52 CBP1:44:11PassPass4/16/21
Duct Detector4th Floor ZE 04-000 RF53 CBP1:44:12PassPass4/7/21
Duct Detector4th Floor ZE 04-000 RF521:44:13DNTDNTDid not test inaccessable4/28/21
Duct Detector4th Floor ZE 04-000 RF55 CBP1:44:14PassPass4/16/21
Duct Detector4th Floor ZE 04-000 RF54 CBP1:44:15PassPass4/16/21
Smoke Detector4th Floor ZE Elevator Lobby SWP1-61:44:16PassPass4/26/21
Smoke Detector4th Floor ZE 04-SW17 Telecom Rm 1 CBP1:44:17PassPass4/7/21
Smoke Detector4th Floor ZE 04-SW14 Elec Rm CBP1:44:18PassPass4/8/21
Smoke Detector4th Floor ZE 04-SW12 Elec Rm CBP1:44:19PassPass4/8/21
Smoke Detector4th Floor ZE 04-SW08 Elec Rm CBP1:44:20PassPass4/8/21
Smoke Detector4th Floor ZE 04-SW09 Telecom Rm CBP1:44:21PassPass4/7/21
Smoke Detector4th Floor ZE 04-SW10 Elec Rm CBP1:44:22PassPass4/8/21
Smoke Detector4th Floor ZE 04-SW11 Telecom Rm CBP1:44:23PassPass4/7/21
Manual Station4th Floor ZE 04-0000 CBP1:44:24PassPass4/7/21
Manual Station4th Floor ZE 04-0000 CBP1:44:25PassPass4/8/21
Duct Detector4th Floor ZF 04-000 RF53 CBP1:44:54PassPass4/16/21
Smoke Detector4th Floor ZF 04-0503 Telecom Rm CBP1:44:55PassPass4/7/21
Duct Detector3rd Floor ZA EMR NG 1-3 SF95 NTWR1:51:04PassPass4/14/21
Duct Detector3rd Floor ZA 03-000 RF2 NTWR1:51:05PassPass4/14/21
Duct Detector3rd Floor ZA 03-000 RF1 NTWR1:51:06PassPass4/14/21
Heat Detector3rd Floor ZA EMR NG 1-31:51:07PassPass4/19/21
Smoke Detector3rd Floor ZA TOS NG-31:51:08PassPass4/19/21
Smoke Detector3rd Floor ZA TOS NG-21:51:09PassPass4/19/21
Smoke Detector3rd Floor ZA TOS NG-11:51:10PassPass4/19/21
Smoke Detector3rd Floor ZA EMR NG 1-31:51:11PassPass4/19/21
Smoke Detector3rd Floor ZA Elev Lobby NP1-61:51:12PassPass4/19/21
Smoke Detector3rd Floor ZA Rear Elev Lobby NP-41:51:13PassPass4/19/21
Smoke Detector3rd Floor ZA 03-NA08 NTWR1:51:14PassPass3/19/21
Smoke Detector3rd Floor ZA 03-NA13 NTWR1:51:15PassPass3/19/21
Smoke Detector3rd Floor ZA 03-NA15 NTWR1:51:16PassPass3/19/21
Smoke Detector3rd Floor ZA 03-NA16 NTWR1:51:17PassPass3/19/21
Manual Station3rd Floor ZA 03-NA09 NTWR1:51:18PassPass3/19/21
Manual Station3rd Floor ZA 03-0000 NTWR1:51:19PassPass3/19/21
Smoke Detector3rd Floor ZC Tele Com Rm USAID Telcom Rm1:51:24PassPass4/5/21
Smoke Detector3rd Floor ZC Electric Room USAID Telcom Rm1:51:25PassPass4/5/21
Duct Detector3rd Floor ZC 03-0000 RF44 USAID1:51:26PassPass4/5/21
Duct Detector3rd Floor ZC 03-0000 RF47 USAID1:51:27PassPass4/5/21
Duct Detector3rd Floor ZB 03-0000 RF31:51:28DNTDNTDid not test inaccessable4/28/21
Duct Detector3rd Floor ZB 03-0000 RF4 NTWR1:51:29PassPass4/14/21
Smoke Detector3rd Floor ZB 03-NM14 Tele Rm EPA1:51:30PassPassNeed access4/28/21
Smoke Detector3rd Floor ZB 03-NM12 Elec Rm C EPA1:51:31PassPass4/15/21
Smoke Detector3rd Floor ZB 03-NM08 Elec Rm A EPA1:51:32PassPass4/15/21
Smoke Detector3rd Floor ZB 03-NM09 Tele Rm EPA1:51:33PassPassNeed access4/28/21
Smoke Detector3rd Floor ZB 03-NM10 Elec Rm B EPA1:51:34PassPass4/15/21
Manual Station3rd Floor ZB 03-NM01 EPA1:51:35PassPass4/15/21
Manual Station3rd Floor ZB 03-NM01 EPA1:51:36PassPass4/15/21
Smoke Detector3rd Floor ZA EMR NG1-31:51:39PassPass4/19/21
Smoke Detector3rd Floor ZB EMR NEP 7&81:51:40PassPass4/19/21
Smoke Detector3rd Floor ZB TOS NEP 81:51:43PassPass4/19/21
Smoke Detector3rd Floor ZB TOS NEP 71:51:44PassPass4/19/21
Duct Detector3rd Floor ZB EMR 301 RF45 NTWR1:51:45PassPass4/14/21