B&M B.S.
SSG PREVENTIVE MAINTENANCE SCHEDULE
| BUILDING: B&M BORDER STATION (TX0000BM) | W - Weekly I - Inventory Only | ||||||||||||||
| M - Monthly O - Omit | |||||||||||||||
| LOCATION: Brownsville, TX | Q - Quarterly once every X years | ||||||||||||||
| SA - Semi Annually | |||||||||||||||
| A - Annually | |||||||||||||||
| (Revised 2017) | Z - Zero PM | ||||||||||||||
| PM GUIDE NO. | ITEM | QTY | FREQ | JAN | FEB | MAR | APRIL | MAY | JUNE | JULY | AUG | SEPT | OCT | NOV | DEC |
| A-02A | UNITARY HEATING & COOLING UNIT | 2 | A | X | |||||||||||
| A-05A | A/C MACHINE; MINI-SPLIT SYSTEM (COMFORT) | 5 | A | X | |||||||||||
| A-05C | A/C MACHINE; MINI-SPLIT SYSTEM (SPECIAL) | 4 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| A-07A | AIR CONDITIONER PACKAGE | 1 | M / A | X | X | X | X | X | X | X | X | X | X | X | X/X |
| A-10A | HEAT PUMPS | 1 | A | X | |||||||||||
| B-03 | BURNERS, GAS (not in use IMP PRIM) | 1 | I | ||||||||||||
| C-04A | CENTRAL MINI-COMPUTER HVAC SYSTEM | 1 | A | X | X | X | X | ||||||||
| C-04C | BAS CONTROLLER | 1 | A | X | |||||||||||
| C-04J | BAS, JACE | 1 | A | X | |||||||||||
| C-24A | CONDENSING UNIT, REFRIGERATION | 17 | A | X | X | X | |||||||||
| D-03A | DRAINS, ROOF, GUTTER | 5 | A | X | |||||||||||
| D-05A | DOOR, MAIN ENTRANCE | 27 | SA | X | X | ||||||||||
| D-10A | DOOR, MANUAL OVERHEAD | 2 | A | X | |||||||||||
| E-19A | EMERGENCY LIGHTS (CLOSED SYSTEMS) | 21 | Q | X | X | X | X | ||||||||
| E-26A | LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER | 6 | A | X | |||||||||||
| E-34B | DISCONNECT, LOW VOLTAGE | 1 | A | X | |||||||||||
| E-36A | AUTOMATIC TRANSFER SWITCH | 1 | SA | X | X | ||||||||||
| E-40A | EMERGENCY GENERATOR, GAS/NATURAL GAS | 1 | A | X | |||||||||||
| E-42A | EMERGENCY GENERATOR | 1 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| E-51A | MOTOR STARTER | 1 | A | X | |||||||||||
| E-57A | LOW VALTAGE DRY TYPE TRANSFORMERS | 2 | A | X | |||||||||||
| E-60A | LIGHTING, CONTACTOR | 2 | A | X | |||||||||||
| F-13A | FIRE SUPERVISORY SIGNAL, TESTING | 2 | Q | X | X | X | X | ||||||||
| F-14A | AUTO. FIRE DETECTION/SMOKE DETECTOR/ALARM DEVICE, DUCT DETECTOR | 30 | SA | X | X | ||||||||||
| F-14B | AUTOMATIC FIRE DETECT. WATERFLOW ALARMS | 2 | Q | X | X | X | X | ||||||||
| F-15A | FIRE ALARM CONTROL PANEL | 3 | Q | X | X | X | X | ||||||||
| F-15B | CENTRAL STATION TRANSMITTER | 3 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-17A | FIRE ALARM BOX, MANUAL -UNCODED | 12 | A | X | |||||||||||
| F-20A | FIRE SPRINKLER HEADS- SPRINKLERED AREAS | 3 | A | X | |||||||||||
| F-22A | FIRE EXTINGUISER, STORED PRESSURE W/GAUGE | 24 | 6 yrs | X | |||||||||||
| F-23A | FIRE EXTINGUISER, GAS CARTRIDGE | 24 | A | X | |||||||||||
| F-24A | FIRE EXTINGUISHER, INSPECTIONS | 24 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-25A | FIRE EXTINGUISER, HYDROSTATIC TESTING | 24 | 5 yrs | X | |||||||||||
| F-27A | FAN, CENTRIFUGAL | 8 | A | X | |||||||||||
| F-30A | FILTER, VISCOUS TYPE | 7 | Z | ||||||||||||
| F-32A | FILTER, THROWAWAY | 26 | Z | ||||||||||||
| F-36A | FANS, PROPELLER | 8 | A | X | |||||||||||
| G-26A | WATER COOLER, STAND ALONE | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| G-26B | WATER COOLER, STAND ALONE | 2 | SA | X | X | ||||||||||
| H-02A | HOT WATER HEATER, GAS | 1 | A | X | |||||||||||
| H-03A | HOT WATER HEATER- ELECTRIC | 1 | A | X | |||||||||||
| H-06A | HOT AIR FURNACE | 4 | A | X | |||||||||||
| I-04A | FAN COIL UNIT-CEILING HUNG | 12 | A | X | |||||||||||
| L-02A | LOADING RAMPS, ADJUSTABLE | 2 | Q | X | X | X | X | ||||||||
| L-05A | LOAN SPRINKLER NOZZLES | 40 | I | ||||||||||||
| M-03A | MOTORS 1 HP TO 7.5 HP | 6 | A | X | |||||||||||
| R-02A | ROOF, ASSEMBLY INSPECTION | 8 | SA | X | X | ||||||||||
| V-05A | VALVE, MANUALLY OPERABLE | 5 | A | X | |||||||||||
| V-09A | BACKFLOW PREVENTER (Irrigation) | 4 | A | X | |||||||||||
| V-09A | BACKFLOW PREVENTER (Fireline) | 1 | A | X | |||||||||||
| W-02A | WASH, EMERGENCY | 3 | W | X | X | X | X | X | X | X | X | X | X | X | X |
| X-26A | PV SOLAR PANELS BANK 1 | 215 | I | ||||||||||||
| X-32A | PARKING LOT GATES | 3 | A | X | |||||||||||
| ACT | AIR CURTAINS | 4 | Q | X | X | X | X |
GATEWAY B.S.
SSG PREVENTIVE MAINTENANCE SCHEDULE
| BUILDING: GATEWAY BORDER STATION | W - Weekly I - Inventory Only | ||||||||||||||
| M - Monthly O - Omit | |||||||||||||||
| LOCATION: Brownsville, TX | Q - Quarterly once every X years | ||||||||||||||
| SA - Semi- Annually | |||||||||||||||
| A - Annually | |||||||||||||||
| (Revised 2017) | Z - Zero PM | ||||||||||||||
| PM GUIDE NO. | ITEM | QTY | FREQ | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEPT | OCT | NOV | DEC |
| A-02A | UNITARY HEATING & COOLING UNIT | 6 | A | X | |||||||||||
| A-05A | A/C MACHINE; SPLIT SYSTEM (COMFORT) | 5 | A | X | |||||||||||
| A-05C | A/C MACHINE; SPLIT SYSTEM (SPECIAL) | 1 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| A-07A | A/C MACHINE, PACKAGE UNIT | 1 | M | X | X | X | X | X | X | X | X | X | X | X | |
| A-11A | AIR HANDLER UNIT | 18 | A | X | |||||||||||
| A-11B | AIR HANDLER UNIT | 1 | A | X | |||||||||||
| B-02A | BOILER, GAS | 2 | A | X | |||||||||||
| B-03A | BURNERS, GAS | 4 | A | X | |||||||||||
| B-07A | BOILER, SCHEDULE LICENSED INSPECTION | 4 | A | X | |||||||||||
| B-08A | BOILER, FLUE GAS TEST | 4 | A | X | |||||||||||
| C-03A | COILS, REHEAT | 5 | A | X | |||||||||||
| C-04A | CENTRAL MINI-COMPUTER HVAC SYSTEM | 2 | A | X | X | X | X | ||||||||
| C-04C | BAS CONTROLLER | 1 | A | X | |||||||||||
| C-04J | BAS, JACE | 1 | A | X | |||||||||||
| C-24A | CONDENSING UNIT, REFRIGERATION | 10 | A | X | |||||||||||
| D-01A | DOOR, POWER OPERATED | 2 | SA | X | X | ||||||||||
| D-03A | DRAINS, ROOF, GUTTER | 9 | A | X | |||||||||||
| D-05A | DOOR, MAIN ENTRANCE | 32 | SA | X | X | ||||||||||
| D-07A | SEDIMENT BASIN | 1 | SA | X | X | ||||||||||
| D-10A | DOOR, MANUAL OVERHEAD | 1 | A | X | |||||||||||
| E-19A | EMERGENCY LIGHTS (CLOSED SYSTEM) | 30 | Q | X | X | X | X | ||||||||
| E-25A | GROUND FAULT TYPE, RELAY | 2 | A | X | |||||||||||
| E-26A | LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER | 8 | A | X | |||||||||||
| E-30A | SWITCHBOARD (LOW VOLTAGE) | 1 | A | X | |||||||||||
| E-34A | DISCONNECT, LOW VOLTAGE | 4 | A | X | |||||||||||
| E35A | MOTOR CONTROL CENTER | 1 | SA | X | X | ||||||||||
| E-36A | AUTOMATIC TRANSFER SWITCH | 3 | SA | X | X | ||||||||||
| E-40A | EMERGENCY GENERATOR, GAS/NATURAL GAS | 2 | A | X | |||||||||||
| E-42A | EMERGENCY GENERATOR | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| E-49A | EMERGENCY PUMP | 1 | A | X | |||||||||||
| E-50A | EMERGENCY PUMP | 1 | Q | X | X | X | X | ||||||||
| E-57A | LOW VALTAGE DRY TYPE TRANSFORMERS | 9 | A | X | |||||||||||
| E-60A | LIGHTING, CONTACTOR | 3 | A | X | |||||||||||
| F-11A | FIRE DOORS-STAIRWELLS AND EXITWAYS | 11 | A | X | |||||||||||
| F-13A | FIRE SUPERVISORY SIGNAL, TESTING | 1 | Q | X | X | X | X | ||||||||
| F-14A | AUTO. FIRE DETECTION/SMOKE DETECTOR/ALARM DEVICE, DUCT DETECTOR, AUDIBLE STROBE | 15 | SA | X | X | ||||||||||
| F-14B | AUTOMATIC FIRE & HEAT DETECT. WATERFLOW ALARMS | 1 | Q | X | X | X | X | ||||||||
| F-15A | FIRE ALARM CONTROL PANEL | 2 | Q | X | X | X | X | ||||||||
| F-15B | CENTRAL STATION TRANSMITTER | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-17A | FIRE ALARM BOX, MANUAL | 17 | A | X | |||||||||||
| F-20A | FIRE SPRINKLER HEADS- SPRINKLERED AREAS | 11 | A | X | |||||||||||
| F-22A | FIRE EXTINGUISHER, PRESSURE W/GAUGE | 30 | 6 yrs | X | |||||||||||
| F-23A | FIRE EXTINGUISER, GAS CARTRIDGE OR -CYLINDER | 30 | A | X | |||||||||||
| F-24A | FIRE EXTINGUISHER, INSPECTIONS | 30 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-27A | FAN, CENTRIFUGAL | 22 | A | X | |||||||||||
| F-32A | FILTER, THROWAWAY | 66 | Z | ||||||||||||
| F-36A | FANS, PROPELLER | 11 | A | X | |||||||||||
| G-03A | FENCES, SECURITY/ACCESS | 2998LF | I | ||||||||||||
| G-26A | WATER COOLER, STAND ALONE | 16 | M | M | M | M | M | M | M | M | M | M | M | M | M |
| G-26B | WATER COOLER, STAND ALONE | 16 | SA | X | X | ||||||||||
| H-02A | HOT WATER HEATER, GAS | 3 | A | X | |||||||||||
| H-03A | HOT WATER HEATER- ELECTRIC | 1 | A | X | |||||||||||
| I-04A | FAN COIL UNIT, CEILING HUNG | 8 | A | X | |||||||||||
| L-02A | LOADING RAMPS, ADJUSTABLE | 4 | Q | X | X | X | X | ||||||||
| M-03A | MOTORS 1 HP TO 7.5 HP | 36 | A | X | X | X | X | ||||||||
| P-04A | PUMP, CENTRIFUGAL | 7 | A | X | |||||||||||
| R-02A | ROOF, ASSEMBLY INSPECTION | 10 | SA | X | X | ||||||||||
| R-04B | CENTRAL PACKAGE CHILLED WATER UNIT | 1 | A | X | |||||||||||
| R-04D | CENTRAL PACKAGE CHILLED WATER UNIT | 2 | A | X | |||||||||||
| S-06A | SEWAGE EJECTOR, SUMP TYPE | 2 | A | X | |||||||||||
| S-07A | SUMP PUMP | 1 | A | X | |||||||||||
| S-08A | STRAINER, Y-TYPE | 4 | A | X | |||||||||||
| S-09A | STRAINER, BOLTER FLANGE | 4 | A | X | |||||||||||
| T-01A | TANK, WATER | 4 | 3yrs | X | |||||||||||
| U-01 | UNIT HEATERS-HOT WATER | 4 | A | X | |||||||||||
| V-02A | VALVES, SAFETY RELIEF | 3 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| V-05A | VALVE, MANUEL OPERABLE | 17 | A | X | |||||||||||
| V-06A | VALVE, MOTOR OPERATED | 2 | A | X | |||||||||||
| V-07A | VALVE, PNEUMATIC | 1 | A | X | |||||||||||
| V-08A | CHECK VALVE, CRITICAL | 6 | A | X | |||||||||||
| V-09A | VALVE, BACKFLOW PREVENTER | 7 | A | X | |||||||||||
| W-02A | WASH, EMERGENCY | 7 | W | X | X | X | X | X | X | X | X | X | X | X | X |
| W-08A | WATER TREATMENT FOR COOLING TOWERS | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| W-09 | WATER TREATMENT FOR HEATING SYSTEMS | 3 | W | X | X | X | X | X | X | X | X | X | X | X | X |
| X-32A | PARKING LOT GATES | 4 | A | X | |||||||||||
| X-50A | FREQUENCY DRIVE | 2 | SA | X | X |
U.S. COURTHOUSE
SSG PREVENTIVE MAINTENANCE SCHEDULE
| BUILDING: US COURTHOUSE | W - Weekly I - Inventory Only | ||||||||||||||
| M - Monthly O - Omit | |||||||||||||||
| LOCATION: Brownsville, TX | Q - Quarterly once every X years | ||||||||||||||
| SA - Semi Annually | |||||||||||||||
| A - Annually | |||||||||||||||
| (Revised 2017) | Z - Zero PM | ||||||||||||||
| PM GUIDE NO. | ITEM | QTY | FREQ | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | OCT | NOV | DEC |
| A-05C | A/C MACHINE; SPLIT SYSTEM | 5 | M | X | X | X | X | X | X | X | X | X | X | X | X/ X |
| A-11A | AIR HANDLER UNITS | 3 | A | X | |||||||||||
| A-11B | AIR HANDLER UNITS | 16 | A | X | X | X | |||||||||
| A-11C | AIR HANDLER UNITS | 1 | A | X | |||||||||||
| C-04A | CENT. MINI-COMPUTER, HAVAC SYSTEM | 1 | Q | X | X | X | X | ||||||||
| C-04C | BAS CONTROLLER | 1 | X | ||||||||||||
| C-04J | BAS, JACE | 1 | X | ||||||||||||
| C-05A | AUTOMATIC MIXING BOX, ELECTRIC, | 69 | Z | ||||||||||||
| C-06A | BAS CONTROLS, CENTRAL SYSTEM, HVAC | 146 | A | X | |||||||||||
| C-09B | COOLING TOWER | 2 | A | X | |||||||||||
| C-10B | COOLING TOWER, MAINTENANCE | 2 | Q | X | X | X | X | ||||||||
| C-24A | CONDENSING UNIT, REFRIGERATION | 4 | A | X | |||||||||||
| D-01A | DOOR, POWER OPERATED | 4 | SA | X | X | ||||||||||
| D-05A | DOOR, MAIN ENTRANCE | 8 | SA | X | X | ||||||||||
| E-19A | EMERGENCY LIGHTS, (CLOSED SYSTEMS) | 98 | Q | X | X | X | X | ||||||||
| E-26A | LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER | 8 | A | X | |||||||||||
| E-35A | MOTOR CONTROL CENTER | 3 | SA | X | X | ||||||||||
| E-36A | AUTOMATIC TRANSFER SWITCH | 1 | SA | X | X | ||||||||||
| E-19A | EMERGENCY LIGHTS, (CLOSED SYSTEMS) | 98 | Q | X | X | X | X | ||||||||
| E-41A | EMERGENCY GENERATOR, DIESEL | 1 | A | X | |||||||||||
| E-42A | EMERGENCY GENERATOR | 1 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| E-57A | LOW VOLTAGE DRY TYPE TRANSFORMER | 13 | A | X | |||||||||||
| F-02A | DRY PIPE, DELUGE AND PREACTION VALVES | 2 | A | X | |||||||||||
| F-02B | DRY PIPE, DELUGE AND PREACTION VALVES | 1 | A | X | |||||||||||
| F-04A | FIRE CONTROL VALVES | 20 | Q | X | X | X | X | ||||||||
| F-04B | FIRE CONTROL VALVES | 20 | A | X | |||||||||||
| F-06A | FIRE PUMP | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F06B | FIRE PUMP | 2 | A | X | |||||||||||
| F-07A | FIRE PUMP | 2 | A | X | |||||||||||
| F-07J | FIRE PUMP | 2 | A | X | |||||||||||
| F-09A | FIRE DEPARTMENT HOSE CONNECTIONS | 17 | 5yrs | X | |||||||||||
| F-10A | FIRE DEPARTMENT HOSE CONNECTIONS (ROOF) | 1 | A | X | |||||||||||
| F-10A | FIRE DEPARTMENT HOSE CONNECTIONS | 16 | A | X | |||||||||||
| F-13A | FIRE SUPERVISORY SIGNAL, TESTING | 1 | Q | X | X | X | X | ||||||||
| F-14A | AUTO. FIRE DETECTION/SMOKE DETECTOR/ALARM DEVICE, DUCT DETECTOR | 82 | SA | X | X | ||||||||||
| F-14A | AUTOMATIC FIRE DETECT. WATERFLOW ALARMS | 21 | Q | X | X | X | X | ||||||||
| F-14B | AUTOMATIC FIRE DETECT. HEAT DETECTORS | 17 | A | X | |||||||||||
| F-15A | FIRE ALARM CONTROL PANEL | 1 | Q | X | X | X | X | ||||||||
| F-15B | CENTRAL STATION TRANSMITTER | 1 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-17 | MANUAL FIRE ALARM STATIONS-CODED & UNCODED | 20 | A | X | |||||||||||
| F-18 | FIRE AND SMOKE DAMPERS | 48 | 2yrs | X | |||||||||||
| F-20A | FIRE SPRINKLER HEADS- SPRINKLERTED AREAS | 1690 | A | X | |||||||||||
| F-22A | FIRE EXTINGUISER, STORED PRESSURE W/GAUGE | 36 | 6 yrs | X | |||||||||||
| F-23A | FIRE EXTINGUISER, GAS CARTRIDGE | 36 | A | X | |||||||||||
| F-24A | FIRE EXTINGUISHER, INSPECTIONS | 36 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-25A | FIRE EXTINGUISHER HYDROSTATIC TESTING | 36 | 5 yrs | X | |||||||||||
| F-26A | FIRE EXTINGUISHING SYSTEM, C02 | 1 | SA | X | X | ||||||||||
| F-27A | FAN, CENTRIFUGAL | 20 | A | X | |||||||||||
| F-32A | FILTER, THROWAWAY (AHU'S) | 117 | Z | ||||||||||||
| F-32A | FILTER, THROWAWAY (VAB'S) | 93 | Z | ||||||||||||
| F-32A | FILTER, THROWAWAY (ROOFTOP UNITS) | 24 | Z | ||||||||||||
| F-36A | FANS, PROPELLER | 2 | A | X | |||||||||||
| F-38A | LIGHTING PROTECTION SYSTEM | 1 | A | X | |||||||||||
| F-39A | FAN, CENTRIFUGAL | 3 | SA | X | |||||||||||
| F-40A | FILTER, THROWAWAY, BAG TYPE | 117 | Z | ||||||||||||
| F-44A | FOUNTAIN, MEMORIAL/DECORATIVE | 2 | SA | X | X | ||||||||||
| G-02A | GREASE TRAP | 1 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| G-26A | WATER COOLER, STAND ALONE | 3 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| G-26B | WATER COOLER, STAND ALONE | 3 | SA | X | X | ||||||||||
| H-03A | HOT WATER HEATER- ELECTRIC | 2 | A | X | |||||||||||
| I-04A | FAN COIL UNIT, CEILING HUNG (SEE SCHED TAB.) | 109 | A | X | X | X | X | X | X | X | X | X | X | X | X |
| L-02A | LOADING RAMPS, ADJUSTABLE | 1 | Q | X | X | X | X | ||||||||
| L-05A | LAWN SPRINKLER NOZZLES | 80 | I | ||||||||||||
| M-03A | MOTORS, 1 HP TO 7.5 HP | 16 | A | X | |||||||||||
| M-03B | MOTORS, 7.5 TO 50 HP | 17 | A | X | |||||||||||
| M11-B | MOTOR, HIGH VOLTAGE | 3 | A | X | |||||||||||
| P-04A | PUMPS | 10 | A | X | |||||||||||
| P-04B | PUMPS | 3 | A | X | |||||||||||
| Q-55M | ALTERNATE -MONTHS (BOLLARDS) | 13 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| R-02A | ROOF, ASSEMBLY INSPECTION | 1 | SA | X | X | ||||||||||
| R-15A | REFRIGERATION MONITOR | 4 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| R-13A | NON-DESTRUCTIVE CHILLER TUBE ANALYSIS | 3 | 3yrs | x | 2 | 0 | 2 | 0 | |||||||
| R-17B | MAGNETIC BEARING CHILLER | 3 | A | X | |||||||||||
| S-07A | SUMP PUMP | 2 | A | X | |||||||||||
| S-08A | STRAINER, Y-TYPE | 20 | A | X | |||||||||||
| S-09A | STRAINER, BOLTED FLANGE | 8 | A | X | |||||||||||
| T-03A | TANK, FUEL OIL, STORAGE | 1 | 4yrs | X | |||||||||||
| V-02A | VALVE, SAFETY RELIEF | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| V-08A | CHECK VALVE, CRITICAL | 5 | A | X | |||||||||||
| V-09A | VALVE, BACKFLOW PREVENTER (Irrigation) | 5 | A | X | |||||||||||
| V-09A | VALVE, BACKFLOW PREVENTER (Fireline) | 1 | A | X | |||||||||||
| W-02A | WASH, EMERGENCY | 1 | W | X | X | X | X | X | X | X | X | X | X | X | X |
| W-07A | WHEELCHAIR LIFT | 6 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| W-08A | WATER TREATMENT FOR COOLING TOWERS | 1 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| X-32H | PARKING LOT, BARRIER SYSTEM | 13 | A | X | |||||||||||
| X-50B | FREQUENCY DRIVE | 22 | SA | X | X |
LOS TOMATES B.S.
SSG PREVENTIVE MAINTENANCE SCHEDULE
| BUILDING: LOS TOMATES B. S. | W - Weekly I - Inventory Only | ||||||||||||||
| M - Monthly O - Omit | |||||||||||||||
| LOCATION: Brownsville, TX | Q - Quarterly once every X years | ||||||||||||||
| SA - Semi Annually | |||||||||||||||
| A - Annually | |||||||||||||||
| (Revised 2017) | Z - Zero PM | ||||||||||||||
| PM GUIDE NO. | ITEM | QTY | FREQ | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEPT | OCT | NOV | DEC |
| A-02A | UNITARY HEATING/COOLING UNIT | 4 | A | X | |||||||||||
| A-05A | A/C MACHINE; SPLIT SYSTEM | 14 | A | X | |||||||||||
| A-05C | A/C MACHINE; SPLIT SYSTEM (Special) | 9 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| A-11A | AIR HANDLER UNITS | 6 | Y | X | |||||||||||
| A-13A | A/C UNIT, CEILING WALL MOUNTED, COMFORT COOLING | 1 | A | X | |||||||||||
| C-03A | COIL, REHEAT/PREHEAT, ELECT | 4 | Y | X | |||||||||||
| C-04A | CENT. MINI-COMPUTER HAVAC SYSTEM | 1 | Q | X | X | X | X | ||||||||
| C-04C | BAS CONTROLLER | 1 | X | ||||||||||||
| C-04J | BAS, JACE | 1 | X | ||||||||||||
| C-05A | AUTOMATIC MIXING BOX, ELECTRIC, | 53 | Z | ||||||||||||
| C-06A | BAS CONTROLS, CENTRAL SYSTEM, HVAC | 57 | A | X | |||||||||||
| C-24A | CONDENSING UNIT, REFRIGERATION | 13 | A | X | X | ||||||||||
| C-24B | CONDENSING UNIT, REFRIGERATION | 6 | A | X | X | ||||||||||
| D-03A | DRAIN - GUTTER W/DOWNSPOUT | 5 | A | X | |||||||||||
| D-05A | DOOR, MAIN ENTRANCE | 37 | SA | X | X | X | |||||||||
| D-10A | DOOR, MANUAL OVERHEAD | 3 | A | X | |||||||||||
| E-19A | EMERGENCY LIGHTS, (CLOSED SYSTEMS) | 7 | Q | X | X | X | X | ||||||||
| E-25A | GROUND FAULT TRANSFORMER/DIFFERENTIAL RELAY | 1 | A | X | |||||||||||
| E-26A | LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER | 11 | A | X | |||||||||||
| E-34A | DISCONNECT, LOW VOLTAGE | 2 | A | X | |||||||||||
| E-36A | AUTOMATIC TRANSFER SWITCH | 1 | SA | X | X | ||||||||||
| E-40A | EMERGENCY GENERATOR, DIESEL | 2 | A | X | |||||||||||
| E-42A | EMERGENCY GENERATOR | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| E-57A | LOW VOLTAGE DRY TYPE TRANSFORMER | 10 | A | X | |||||||||||
| E-60 | LIGHTING CONTACTOR | 10 | A | X | |||||||||||
| F-04A | FIRE CONTROL VALVES | 4 | Q | X | X | X | X | ||||||||
| F-04B | FIRE CONTROL VALVES | 4 | A | X | |||||||||||
| F-13A | FIRE SUPERVISORY SIGNAL, TESTING | 4 | Q | X | X | X | X | ||||||||
| F-14A | AUTO. FIRE DETECTION/SMOKE DETECTOR/ALARM DEVICE, DUCT DETECTOR | 66 | SA | X | X | ||||||||||
| F-14B | AUTOMATIC FIRE DETECT. WATERFLOW ALARMS | 3 | Q | X | X | X | X | ||||||||
| F-15A | FIRE ALARM CONTROL PANEL | 2 | Q | X | X | X | X | ||||||||
| F-15B | CENTRAL STATION TRANSMITTER | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-17 | MANUAL FIRE ALARM STATIONS-CODED & UNCODED | 19 | A | X | |||||||||||
| F-20A | FIRE SPRINKLER HEADS- SPRINKLERTED AREAS | 213 | A | X | |||||||||||
| F-22A | FIRE EXTINGUISER, STORED PRESSURE, W/GAUGE, NON STAINLESS STEEL | 45 | 6yrs | X | |||||||||||
| F-23A | FIRE EXTINGUISER | 45 | A | X | |||||||||||
| F-24A | FIRE EXTINGUISHER, INSPECTIONS | 45 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-25A | FIRE EXTINGUISHER, HYDROSTATIC TEST GAS CYLINDER | 45 | 5yrs | X | |||||||||||
| F-27A | FAN, CENTRIFUGAL | 13 | A | X | |||||||||||
| F-32A | FILTER, THROWAWAY | 127 | Z | ||||||||||||
| F-36A | FANS, PROPELLER | 15 | A | X | |||||||||||
| F-40A | FILTER, THROWAWAY, BAG TYPE | 20 | Z | ||||||||||||
| G-26A | WATER COOLER, STAND ALONE | 4 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| G-26B | WATER COOLER, STAND ALONE | 4 | SA | X | X | ||||||||||
| H-02A | HOT WATER HEATER, GAS | 1 | A | X | |||||||||||
| H-03A | HOT WATER HEATER- ELECTRIC | 7 | A | X | |||||||||||
| H06A | HOT AIR FURNACE | 1 | A | X | |||||||||||
| L-02A | LOADING RAMPS, ADJUSTABLE | 4 | Q | X | X | X | X | ||||||||
| L-05A | LAWN SPRINKLER NOZZLES | 125 | I | ||||||||||||
| M-03A | MOTORS 1 HP TO 7.5 HP | 2 | A | X | |||||||||||
| M-03B | MOTORS 7.5 TO 50 HP | 2 | A | X | |||||||||||
| R-02A | ROOF, ASSEMBLY INSPECTION | 18 | SA | X | X | ||||||||||
| T-01A | TANK, WATER | 1 | 3yrs | X | |||||||||||
| V-02A | VALVE, SAFETY RELIEF | 1 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| V-05A | VALVE, MANUEL OPERABLE | 2 | A | X | |||||||||||
| V-09A | BACKFLOW PREVENTER | 1 | X | ||||||||||||
| W-02A | WASH, EMERGENCY | 4 | W | X | X | X | X | X | X | X | X | X | X | X | X |
| X-32A | PARKING ARM GATES | 6 | A | X | |||||||||||
| X-50B | FREQUENCY DRIVE | 4 | SA | X | X |
LOS INDIOS B.S.
SSG PREVENTIVE MAINTENANCE SCHEDULE
| BUILDING: LOS INDIOS B. S. | W - Weekly I - Inventory Only | ||||||||||||||
| M - Monthly O - Omit | |||||||||||||||
| LOCATION: Brownsville, TX | Q - Quarterly once every X years | ||||||||||||||
| SA - Semi Annually | |||||||||||||||
| A - Annually | |||||||||||||||
| (Revised 2017) | Z - Zero PM | ||||||||||||||
| PM GUIDE NO. | ITEM | QTY | FREQ | JAN | FEB | MAR | APR | MAY | JUN | JUL | AUG | SEP | OCT | NOV | DEC |
| A-01A | AIR DRYER, REFRIGERATED | 2 | SA | X | X | ||||||||||
| A-02A | UNITARY HEATING & COOLING UNIT | 3 | A | X | |||||||||||
| A-04A | AIR COMPRESSOR | 4 | SA | X | X | ||||||||||
| A-05A | A/C MACHINE; SPLIT SYSTEM | 12 | A | X | |||||||||||
| A-05C | A/C MACHINE; SPLIT SYSTEM | 8 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| A-08W | A/C UNIT WITH HEAT, WINDOW | 1 | I | ||||||||||||
| A-09A | AIR COOLED CONDENSER | 3 | A | X | |||||||||||
| A-10A | HEAT PUMPS | 3 | A | X | |||||||||||
| A-11A | AIR HANDLER UNIT | 1 | A | X | |||||||||||
| A-11B | AIR HANDLER UNIT | 2 | A | X | |||||||||||
| A-13A | A/C UNIT-CEILING MOUNT | 4 | A | X | |||||||||||
| B-02A | BOILER, GAS | 2 | A | X | |||||||||||
| B-03A | BURNERS, GAS | 15 | A | X | |||||||||||
| B-07A | BOILER, SCHEDULE LICENSED INSPECTION | 2 | A | X | |||||||||||
| B-08A | BOILER, FLUE GAS TEST | 2 | A | X | |||||||||||
| C-03A | COILS, REHEAT | 1 | A | x | |||||||||||
| C-04A | CENTRAL MINI-COMPUTER HVAC SYSTEM | 1 | Q | X | X | X | X | ||||||||
| C-04C | BAS CONTROLLER | 1 | X | ||||||||||||
| C-04J | BAS, JACE | 1 | X | ||||||||||||
| C-05A | AUTOMATIC MIXING BOX, PNEUMATIC | 1 | Z | ||||||||||||
| C-06A | BAS CONTROLS, CENTRAL SYSTEM, HVAC | 132 | A | X | |||||||||||
| C-09B | COOLING TOWER, MAINTENANCE | 1 | A | X | |||||||||||
| C-10B | COOLING TOWER, MAINTENANCE | 1 | Q | X | X | X | X | ||||||||
| C-24A | CONDENSING UNIT, REFRIGERATION | 11 | A | X | |||||||||||
| D-01A | DOOR, POWER, OPERATED | 3 | SA | X | X | ||||||||||
| D-03A | DRAINS, ROOF, GUTTER | 6 | A | X | |||||||||||
| D-03B | DRAINS, ROOF, BUCKET | 29 | SA | X | X | ||||||||||
| D-05A | DOOR, MAIN ENTRANCE | 38 | SA | X | X | ||||||||||
| D-10A | DOOR, MANUAL OVERHEAD | 4 | A | X | |||||||||||
| E-19A | EMERGENCY LIGHTS (CLOSED SYSTEM) | 31 | Q | X | X | X | X | ||||||||
| E-21A | OVER/UNDER VOLTAGE RELAY | 2 | A | X | |||||||||||
| E-25A | GROUND FAULT TYPE RELAY | 1 | A | X | |||||||||||
| E-26A | LOW VOLTAGE MOLDED CASE CIRCUIT BREAKER | 9 | A | X | |||||||||||
| E-30A | SWITCHBOARD (LOW VOLTAGE) | 1 | A | X | |||||||||||
| E-34A | DISCONNECT, LOW VOLTAGE | 6 | A | X | |||||||||||
| E-34B | DISCONNECT, LOW VOLTAGE (OVER 500 AMP) | 2 | A | X | |||||||||||
| E-36A | AUTOMATIC TRANSFER SWITCH | 2 | SA | X | X | ||||||||||
| E-40A | EMERGENCY GENERATOR, GAS/NATURAL GAS | 3 | A | X | |||||||||||
| E-42A | EMERGENCY GENERATOR | 3 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| E-49A | EMERGENCY PUMP | 1 | A | X | |||||||||||
| E-51A | MOTOR, STARTER | 2 | A | X | |||||||||||
| E-57A | LOW VALTAGE DRY TYPE TRANSFORMERS | 8 | A | X | |||||||||||
| E-60A | LIGHTING, CONTACTOR | 6 | A | X | |||||||||||
| F-01A | ALARM CHECK VALVES & ACCESSORIES | 2 | SA | X | X | ||||||||||
| F-04A | FIRE CONTROL VALVES | 1 | Q | X | X | X | X | ||||||||
| F-04B | FIRE CONTROL VALVES | 1 | A | X | |||||||||||
| F-09A | FIRE DEPT. HOSE CONNECTIONS | 4 | A | X | |||||||||||
| F-11A | FIRE DOORS-STAIRWELLS AND EXITWAYS | 2 | A | X | |||||||||||
| F-13A | FIRE SUPERVISORY SIGNAL, TESTING | 3 | Q | X | X | X | X | ||||||||
| F-14A | AUTOMATIC FIRE/SMOKE DETECTORS | 29 | A | X | |||||||||||
| F-14B | AUTOMATIC FIRE DETECT. WATERFLOW ALARMS | 4 | Q | X | X | X | X | ||||||||
| F-15A | FIRE ALARM CONTROL PANEL | 3 | Q | X | X | X | X | ||||||||
| F-15B | CENTRAL STATION TRANSMITTER | 3 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-17A | FIRE ALARM BOX, MANUAL | 14 | A | X | |||||||||||
| F-18A | FIRE & SMOKE DAMPERS | 11 | 2 yrs | x | |||||||||||
| F-19A | FIRE HYDRANTS | 13 | A | X | |||||||||||
| F-20A | FIRE SPRINKLER HEADS | 108 | A | X | |||||||||||
| F-22A | FIRE EXTINGUISER, STORED PRESSURE W/GAUGE | 37 | 6 YRS | X | |||||||||||
| F-23A | FIRE EXTINGUISER,-GAS CARTRIDGE | 37 | A | X | |||||||||||
| F-24A | FIRE EXTINGUISHER, INSPECTIONS | 37 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| F-27A | FAN, CENTRIFUGAL | 41 | A | X | |||||||||||
| F-30A | FILTER, VISCOUS TYPE, WIRE MESH | 16 | Z | ||||||||||||
| F-32A | FILTER, THROWAWAY | 104 | Z | ||||||||||||
| F-36A | FANS, PROPELLER | 19 | A | X | |||||||||||
| G-26A | WATER COOLER, STAND ALONE | 9 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| G-26B | WATER COOLER, STAND ALONE | 9 | SA | X | X | ||||||||||
| H-02A | HOT WATER HEATER, GAS | 4 | A | X | |||||||||||
| H-03A | HOT WATER HEATER- ELECTRIC | 5 | A | X | |||||||||||
| H-06A | HOT AIR FURNACE | 13 | A | X | |||||||||||
| I-04A | FAN COIL UNIT-CEILING HUNG | 3 | A | X | |||||||||||
| I-06A | FAN COIL UNIT VAV, W/HOT WATER HTNG. | 26 | A | X | X | X | |||||||||
| L-02 | LOADING RAMPS, ADJUSTABLE | 12 | Q | X | X | X | X | ||||||||
| M-03A | MOTORS 1 TO 7.5 | 29 | A | X | X | X | X | X | |||||||
| M-03B | MOTORS 7.5 TO 50 | 2 | A | X | |||||||||||
| M-11B | MOTORS, HIGH VOLTAGE | 2 | A | X | |||||||||||
| P-04A | PUMP, CENTRIFUGAL | 10 | A | X | |||||||||||
| R-02A | ROOF, ASSEMBLY INSPECTION | 15 | SA | X | X | ||||||||||
| R-13A | NON-DESTRUCTIVE CHILLER TUBE ANALYSIS | 2 | 3yrs | X | 2 | 0 | 2 | 0 | |||||||
| R-17A | MAGNETIC BEARING CHILLER | 2 | A | X | |||||||||||
| S-06A | SEWAGE EJECTOR, SUMP TYPE | 2 | A | X | |||||||||||
| S-08A | STRAINER, Y TYPE | 8 | A | X | |||||||||||
| S-09A | STRAINER, BOLTED FLANGE TYPE | 4 | A | X | |||||||||||
| T-01A | TANK, WATER | 2 | 3YR | X | |||||||||||
| U-01A | UNIT HEATERS | 10 | A | X | |||||||||||
| V-02A | VALVE, SAFETY RELIEF | 4 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| V-05A | VALVE, MANUEL OPERABLE | 52 | A | X | X | X | X | ||||||||
| V-07A | VALVE, ELECTRIC | 3 | A | X | |||||||||||
| V-08A | CHECK VALVE, CRITICAL | 3 | A | X | |||||||||||
| V-09A | VALVE, BACKFLOW PREVENTER (Irrigation) | 4 | A | X | |||||||||||
| V-09A | VALVE, BACKFLOW PREVENTER (Fireline) | 2 | A | X | |||||||||||
| W-02A | WASH, EMERGENCY | 11 | W | X | X | X | X | X | X | X | X | X | X | X | X |
| W-08A | WATER TREATMENT FOR COOLING SYSTEMS | 1 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| W-09A | WATER TREATMENT FOR HEATING SYSTEMS | 2 | M | X | X | X | X | X | X | X | X | X | X | X | X |
| X-32A | PARKING LOT GATES | 6 | A | X | |||||||||||
| X-39A | SEPTIC TANK, DRAIN FIELD | 8 | A | X | |||||||||||
| X-50B | FREQUENCY DRIVE | 4 | SA | X | X |