About this file

This solicitation is for a Construction Manager as Constructor (CMc) contract to modernize outdated systems and expand laboratory spaces for the FDA Forensic Chemistry Center and Peck Federal Building located in Cincinnati, OH. The General Services Administration (GSA) intends to award a Guaranteed Maximum Price (GMP) contract. The solicitation document provides additional details on the repair and alteration project requirements. Interested parties should review attachments for product and service specifications, response deadlines, and other salient information.

View the file

Other files

File Type Posted
EpsteinCombinedPart-4.pdf PDF
EpsteinCombinedPart-3Part-2.pdf PDF
EpsteinCombined Part 1.pdf PDF
EpsteinCombinedPart-2Part-1.pdf PDF
EpsteinCombinedPart-3Part-1.pdf PDF
EpsteinCombinedPart-2Part-2.pdf PDF
Appendix A.pdf PDF
Appendix H.pdf PDF
Appendix B.pdf PDF
Amendment 02_47PF0020R0057S.pdf PDF
Drawings Amendment 02.pdf PDF
Appendix I.pdf PDF
Appendix E.pdf PDF
Concept Design Report.pdf PDF
Appendix F.pdf PDF
Pre Alteration Assessment Survey.pdf PDF
Appendix D.pdf PDF
Appendix C.pdf PDF
Amendment 01_RFP 47PF0020R0057S.pdf PDF
02_08_60_Lead_Mitigation.doc DOC document
Wage Determnation.pdf PDF
R5_Asbestos_Pre-Alteration_Assessment_Guidance.pdf PDF
Appendix-F_GPC_Checklist.pdf PDF
GSA 013200 Construction Progress Documentation FY15 Update Oct. 1, 2014.docx DOCX document
FDA CMc Solicitation_SOW.pdf PDF
Appendix-E_LEED-CI_Scorecard.pdf PDF
GSA 016000 Product Requirements FY15 Update Oct. 1, 2014.docx DOCX document
GSA 015930 Security Regulations FY15 Update Oct. 1, 2014.docx DOCX document
GSA 014025 Quality Control Testing for Air Barriers FY15 Update Oct. 1, 2014.docx DOCX document
GSA 011400 Work Restrictions FY15 Update Oct. 1, 2014.docx DOCX document
Appendix-D_InteriorDesign_Concepts.pdf PDF
SSL_TLS_Implementation_Guide_10-17-2016.docx DOCX document
GSA 019113 Commissioning FY15 Update Oct. 1, 2014.docx DOCX document
Appendix-H_ProjectLocation_FIRM_Map.pdf PDF
GSA_ACM_Notification_Form.pdf PDF
FDA-FCC_ConceptNarrative.pdf PDF
GSA 014100 Structural Testing Laboratory Services FY15 Update Oct. 1, 2014.docx DOCX document
GSA 013000 Electronic Project Management FY15 Update Oct. 1, 2014.docx DOCX document
Appendix-A_MeetingMinutes.pdf PDF
GSA 014000 Quality Assurance_Control FY15 Update Oct 1_2014.docx DOCX document
GSA 018111 Sustainable Design Requirements FY15 Update Oct. 1 2014.docx DOCX document
Appendix-C-DepartmentalDrawings.pdf PDF
FDA CMa and CXa SOW.pdf PDF
Peck DID Drawings.pdf PDF
GSA Smart Buildings Program Guide_v11.pdf PDF
SF24.pdf PDF
FDA Equipment_Responsibility_ Matrix.xlsx XLSX spreadsheet
GSA 013220 Photographic Documentation FY15 Update Oct. 1, 2014.docx DOCX document
GSA 015950 Safety_Health FY15 Update Oct 1_2014.doc DOC document
BuildingTechnologiesTechnicalReferenceGuidev11-2514.pdf PDF
Show 40 more

Latest 50 of 95 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HDR

Client: GSA/FDA FCC

Location: Cincinnati, OH

Project: Forensic Chemistry Center - NEW LABS Notes:

Project Number: 0XXX-00X.0X

Calculations: Air Valve & Reheat Coil Calculations June 5, 2020

Entering Air Temp 54 °F NEW LAB OPIOID LAB AIRFLOWS Entering Water Temp 180 °F

Hot Water ΔT 20 F° Minimum 6 ACH in labs at all times, including Unoccupied Setting per DRM

Coil Velocity 700 ft/min

Unoccupied Turndown 30%

Unit Sizing Factor 20% 20% Future Growth Capacity for LAB AHU per DRM Paragraph 6.2.1

Lab 1 3470 10.0 6 3470 1.5 8 10 73 6110 18 18 12.9 160.0 73.3 4200 1600 5800 600 6110 6710 6-5 ft FH (700 cfm/ea) (CAV), 16 snork Exh (100 cfm/.ea)

Lab 2 2705 10.0 6 2705 1.5 8 10 73 4625 18 18 9.8 160.0 73.5 2800 800 3600 200 4625 4825 4-5 ft FH (700 cfm/ea) (CAV), 8 snork exh (100 cfm/ea)

Lab Corridor North 210 10.0 6 210 1.0 0 0 75 405 9 9 1.0 161.5 75.0 200 405 205

Lab Corridor East 790 10.0 4 525 1.0 0 0 75 465 12 9 1.4 160.0 75.0 - - 600 600 - -

Lab Corridor South 435 10.0 4 290 1.0 0 0 75 290 9 9 1.0 161.7 75.0 - - 400 400 - -

Lab Equipment Storage 310 10.0 6 310 1.5 8 1 73 1090 15 15 2.3 160.0 73.0 - - 200 1090 1290

Evidence Destruction 330 10.0 6 330 1.5 8 1 73 600 12 9 1.2 160.0 73.0 700 700 200 600 800 1-5 ft FH (700 cfm/ea)

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

- - - - - - - - - - - - 0 - -

- - - - - - - - - - - - 0 - -

- - - - - - - - - - 0 0

8250 7,840 13585 GPM 1200 Supply Exhaust

29.6 13830 13830

35.5 16596 16596

** Room data sheet calls for exhausted Type A2 BSC in Room 066A but DRM paragraph 6.1.16.3 indicates BSC should not be ducted or thimble connected.

Room Name Room Number

Air

Change

Heat

Load

Reheat

Coil

Eqpm

Exhaust Offset Occupied

People (#)

RemarksFloor

Area

(sf)

Ceiling

Height (ft) ACH CFM/sf

Air

Change (cfm)

Lights

(w/sf) Power (w)

Skin

Gain

(MBH)

Design

Temp (°F)

Heat Load

(cfm) Width Height Out (cfm)

General

Supply

(cfm)

Total

Exhaust

(cfm)

GPM

Exit

Water

Temp

Exit

Air

Temp

Fume

Hood

(cfm)

BSC (cfm)

Animal

Racks

(cfm)

System Totals (with sizing factor)

System Sub-Totals

Misc (cfm) Total

(cfm)

In

(cfm)

Location: Cincinnati, OH

Project: Forensic Chemistry Center - NEW LABS Notes:

Project Number: 0XXX-00X.0X

Calculations: Air Valve & Reheat Coil Calculations June 5, 2020

Entering Air Temp 54 °F EXISTING AC-2 AIRFLOWS Entering Water Temp 180 °F

Hot Water ΔT 20 F° Minimum 6 ACH in labs at all times, including Unoccupied Setting per DRM

Coil Velocity 700 ft/min

Unoccupied Turndown 30%

Unit Sizing Factor 20% 20% Future Growth Capacity for LAB AHU per DRM Paragraph 6.2.1

Investigation Sample Prep 051 161 10.0 6 160 280 9 6 1.0 208.4 7.5 380 380 100 280 380 GE

Office / Storage 052 137 10.0 6 135 233 9 6 1.0 202.8 9.1 333 333 100 233 333 GE

Drug Storage 055 74 10.0 6 75 125 6 6 1.0 194.7 0.0 225 225 100 125 225 GE

Evidence Room 061 390 10.0 6 390 710 12 12 1.0 263.6 0.0 810 810 100 710 810 GE

Analyzed and Un-Analyzed Surplus 062 803 10.0 6 805 1402 18 15 1.0 345.0 0.0 1502 1502 100 1402 1502 GE

Security Corridor 056 143 10.0 6 145 400 9 9 1.0 227.1 0.0 - - 400 400 - - no GE

Supply Clerk 057 130 10.0 6 130 150 6 6 1.0 197.7 0.0 250 250 100 150 250 GE

Vault 058 74 10.0 6 75 130 - - - - 1.0 195.3 0.0 230 230 100 130 230 GE

General Chemistry Lab 063 1170 10.0 6 1170 3905 - - - - 1.0 639.7 0.0 3100 1290 4390 485 3905 4390 2 6ft FH's at 1550 cfm ea, 1290 cfm GE

Data Room 064 210 10.0 6 210 241 - - - - 1.0 208.4 0.0 241 241 0 241 241 GE

Data Room 065 146 10.0 6 145 241 - - - - 1.0 208.4 0.0 241 241 0 241 241 GE

Corridor 054 485 10.0 6 485 850 - - - - 1.0 280.1 0.0 275 275 575 850 275 GE

Corridor 053 195 10.0 6 195 500 - - - - 1.0 238.9 0.0 200 200 300 500 200 GE

Washing Autoclave 066 580 10.0 6 580 3000 - - - - 1.0 533.2 0.0 3350 3350 350 3000 3350 GE'1 3200 cfm CH and 150 CFM vent

Lab Equipment Storage 067 330 10.0 6 330 259 - - - - 1.0 210.5 0.0 650 650 400 259 659 GE

Shipping Receiving 068 416 10.0 6 415 880 - - - - 1.0 283.6 0.0 330 330 550 880 330 GE

Shipping Clerk 072 80 10.0 6 80 150 - - - - 1.0 197.7 0.0 0 - - 0 150 150 GE

Chemical Storage 069 192 10.0 6 190 200 - - - - 1.0 203.5 0.0 300 300 100 200 300 no GE

Volatile Solvents 070 250 10.0 6 250 1100 - - - - 1.0 309.5 0.0 1195 1195 95 1100 1195 GE

Cylinder Storage 071 192 10.0 6 190 266 - - - - 1.0 211.3 0.0 366 366 100 266 366 GE

Micro Molecular Biology 075 1205 10.0 6 1205 3500 - - - - 1.0 592.0 0.0 3600 100 3700 200 3500 3700 2 6ft FH at 1550 cfm ea, 1 6 ft FH at 1200 cfm

Corridor 074 405 10.0 6 405 600 - - - - 1.0 250.6 0.0 0 - - 600 600 - - no GE

Corridor 169 975 16.0 6 1560 2000 - - - - 1.0 415.4 0.0 500 500 1500 2000 500 GE

Electrical Repair 165 420 10.0 6 420 1300 - - - - 1.0 333.0 0.0 1000 385 1385 85 1300 1385 1 hood at 1000 cfm

Fingerprint Lab 080 265 10.0 6 265 1800 - - - - 1.0 391.9 0.0 1550 400 1950 150 1800 1950 1 6 ft FH and 2 cabinet exhaust at 200 cfm ea

Data Room 081 84 10.0 6 85 190 - - - - 1.0 202.4 0.0 190 190 0 190 190 GE

Dark Room 082 232 10.0 6 230 652 - - - - 1.0 256.8 0.0 652 652 0 652 652 GE

Telecom 084 102 10.0 6 100 260 9 6 1.0 210.6 0.0 260 260 0 260 260 GE

Electric Room 085 102 10.0 6 100 260 9 6 1.0 210.6 0.0 260 260 0 260 260 GE

Electron Microscope 086 383 10.0 6 385 1360 18 15 1.0 340.1 0.0 1460 1460 100 1360 1460 GE

Microscopy/Photography 087 600 10.0 6 600 1709 18 18 1.0 381.2 0.0 1550 250 1800 100 1709 1809 1 6 ft FH at 1550 cfm & 1 GE

Data Room 088 100 10.0 6 100 270 9 6 1.0 211.8 0.0 270 270 0 270 270 GE

Data Room 089 95 10.0 6 95 270 9 6 1.0 211.8 0.0 288 288 18 270 288 GE

Data Room 090 134 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288 GE

FTIR 091 1050 10.0 6 1050 3422 18 18 1.0 582.8 0.0 1550 1500 3050 200 3422 3622 1 6 ft FH and 1 3312 cfm GE

Data Room 092 133 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288 GE

Data Room 093 138 10.0 6 140 288 9 6 1.0 213.9 0.0 288 288 0 288 288 GE

Corridor 095 420 10.0 6 420 700 12 12 1.0 262.4 0.0 225 225 475 700 225 GE

Analytical Sample Prep 096 471 10.0 6 470 3300 18 18 1.0 568.5 0.0 3400 3400 100 3300 3400 1 Canopy Hood

Separation III 097 1684 10.0 6 1685 7324 18 18 1.0 1042.2 0.0 5924 1800 7724 400 7324 7724 4 6 ft FH at 1550 cfm, 6 snorkel at 300 cfm, 2 GE

Data Room 098 136 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288

Data Room 099 133 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288

Data Room 100 133 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288

Data Room 101 133 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288

Data Room 102 136 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288

Corridor 103 480 10.0 6 480 800 15 12 1.0 274.2 0.0 0 - - 800 800 - -

Standards Separation 104 471 10.0 6 470 1851 18 18 1.0 397.9 0.0 1550 500 2050 199 1851 2050 1 6 ft FH and 1641 cfm GE

Corridor 168 1060 16.0 6 1695 2000 18 18 1.0 415.4 0.0 500 500 1500 2000 500 GE

17838 19,060 50894 GPM 3782 Supply Exhaust

48.0 35400 30405

57.6 42480 36486System Totals (with sizing factor)

System Sub-Totals Existing AC-2 sized for 50,475 cfm

Misc (cfm) Total

(cfm)

In

(cfm) Out (cfm)

General

Supply

(cfm)

Total

Exhaust

(cfm)

GPM

Exit

Water

Temp

Exit

Air

Temp

Fume

Hood

(cfm)

BSC (cfm)

Animal

Racks

(cfm)

Skin

Gain

(MBH)

Design

Temp (°F)

Heat Load

(cfm) Width Height

RemarksFloor

Area

(sf)

Ceiling

Height (ft) ACH CFM/sf

Air

Change (cfm)

Lights

(w/sf) Power (w)

** Room data sheet calls for exhausted Type A2 BSC in Room 066A but DRM paragraph 6.1.16.3 indicates BSC should not be ducted or thimble connected.

Room Name Room Number

Air

Change

Heat

Load

Reheat

Coil

Eqpm

Exhaust Offset Occupied

People (#)

Location: Cincinnati, OH

Project: Forensic Chemistry Center - NEW LABS Notes:

Project Number: 0XXX-00X.0X

Calculations: Air Valve & Reheat Coil Calculations June 5, 2020

Entering Air Temp 54 °F EXISTING AC-3 AIRFLOWS Entering Water Temp 180 °F

Hot Water ΔT 20 F° Minimum 6 ACH in labs at all times, including Unoccupied Setting per DRM

Coil Velocity 700 ft/min

Unoccupied Turndown 30%

Unit Sizing Factor 20% 20% Future Growth Capacity for LAB AHU per DRM Paragraph 6.2.1

Mass Spectrometry 110 1552 10.0 6 1550 4524 18 18 1.0 708.0 0.5 4300 400 4700 176 4524 4700 2 6 ft FH at 2150 CFM each

Data Room 111 136 10.0 6 135 288 9 6 1.0 209.3 7.3 400 400 112 288 400 GE

Data Room 112 133 10.0 6 135 288 9 6 1.0 213.9 0.0 400 400 112 288 400 GE

Clean Room 106 167 10.0 6 165 1354 18 15 1.0 339.4 0.0 1000 1000 354 1354 1000 GE

Change Room 105 128 10.0 6 130 500 12 9 1.0 238.9 0.0 500 500 354 500 854 GE

Clean Room 107 114 10.0 6 115 1192 15 15 1.0 320.3 0.0 880 880 312 1192 880 1-6 ft FH at 880 cfm

108 127 10.0 6 125 1192 15 15 1.0 320.3 0.0 880 880 312 1192 880 1-6 ft FH at 880 cfm

Photograph Document Lab 109 225 10.0 6 225 1058 - - - - 1.0 304.5 0.0 1150 1150 92 1058 1150 GE

Ion Chromotography 113 505 10.0 6 505 2173 - - - - 1.0 435.8 0.0 350 1913 2263 200 2173 2373 1 6ft FH at 1550 Cfm

Data Room 114 165 10.0 6 165 296 - - - - 1.0 214.8 0.0 296 296 0 296 296 GE

Corridor 116 490 10.0 2 165 700 - - - - 1.0 262.4 0.0 530 530 170 700 530 GE

Corridor 103 480 10.0 6 480 800 - - - - 1.0 274.2 0.0 0 - - 800 800 - - no GE

Atomic Absorption 117 1575 10.0 6 1575 5152 - - - - 1.0 786.5 0.0 3100 3000 6100 948 5152 6100 2 6ft FH's at 1550 cfm each, 3000 cfm snorkels

Data Room 118 150 10.0 6 150 400 - - - - 1.0 227.1 0.0 400 400 0 400 400 GE

Data Room 119 150 10.0 6 150 400 - - - - 1.0 227.1 0.0 400 400 0 400 400 GE

Inorganic Sample 120 710 10.0 6 710 7904 - - - - 1.0 1110.5 0.0 6200 2420 8620 716 7904 8620 4 FH's, 2 LF Hoods, 100 cfm furnace

ICP Mass Spectrometry 121 537 10.0 6 535 3961 - - - - 1.0 646.3 0.0 950 1200 2150 1799 3961 2162 1 6ft FH at 950 cfm, 1200 CFM point of use exh

Data Room 122 163 10.0 6 165 295 - - - - 1.0 214.7 0.0 295 295 0 295 295 GE

Corridor 167 960 16.0 6 1535 2000 - - - - 1.0 415.4 0.0 - - 2000 2000 - - no GE

Separation II 132 1681 10.0 6 1680 7040 - - - - 1.0 1008.7 0.0 4000 2900 6900 160 7040 7200 4 6ft FH's at 1550 cfm EA, 1 CH at 1300 cfm, 6 snorkels

Separation 1 124 1695 10.0 6 1695 5940 - - - - 1.0 879.3 0.0 4400 1800 6200 260 5940 6200 4 6ft FH's at 1550 cfm ea, 6 snorkels at 300 cfm

Corridor 131 314 10.0 6 315 556 - - - - 1.0 245.5 0.0 656 656 100 556 656 GE

Data Room 125 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 126 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 127 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 128 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 129 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 133 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 134 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 135 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 136 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE

Data Room 137 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE

13487 13,755 50823 GPM 3230 Supply Exhaust

32.0 38820 33820

38.4 46584 40584System Totals (with sizing factor)

System Sub-Totals Existing AC-3 sized for 49,714 cfm

Misc (cfm) Total

(cfm)

In

(cfm) Out (cfm)

General

Supply

(cfm)

Total

Exhaust

(cfm)

GPM

Exit

Water

Temp

Exit

Air

Temp

Fume

Hood

(cfm)

BSC (cfm)

Animal

Racks

(cfm)

Skin

Gain

(MBH)

Design

Temp (°F)

Heat Load

(cfm) Width Height

RemarksFloor

Area

(sf)

Ceiling

Height (ft) ACH CFM/sf

Air

Change (cfm)

Lights

(w/sf) Power (w)

** Room data sheet calls for exhausted Type A2 BSC in Room 066A but DRM paragraph 6.1.16.3 indicates BSC should not be ducted or thimble connected.

Room Name Room Number

Air

Change

Heat

Load

Reheat

Coil

Eqpm

Exhaust Offset Occupied

People (#)

Location: Cincinnati, OH

Project: Forensic Chemistry Center - NEW LABS

Project Number: 0XXX-00X.0X

Calculations: CHILLED WATER LOADS (New Lab Offices on Office AHU with Return Air)

June 5, 2020

Net to Gross Ceiling Maximum Coil Lvg Coil Lvg Entering Coil Lvg Total Coil Chilled

AHU # area Efficiency Height ACH CFM % OA OA DB OA WB MA DB MA WB air temp air temp Enthalpy Enthalpy load tons Water dt Flow

(ft^2) % (ft) (F) (F) (F) (F) (F - db) (F - wb) (mbh) (F) (gpm)

NEW LAB AHU CAPACITY 9,150 -- -- -- 16,596 100% 92.7 75.1 92.7 75.1 51.0 50.5 38.5 20.5 1,345.77 112.15 14 192.25

AC-2 17,838 -- -- -- 42,480 100% 92.7 75.1 92.7 75.1 51.0 50.5 38.5 20.5 3,444.70 287.06 14 492.10

AC-3 13,487 -- -- -- 46,584 100% 92.7 75.1 92.7 75.1 51.0 50.5 38.5 20.5 3,777.50 314.79 14 539.64

AH-4 (existing office AHU) -- -- -- 51,780 20% 92.7 75.1 82.0 67.0 54.3 54.3 31.0 22.8 1,903.69 158.64 14 271.96

NEW OFFICE AHU 29,700 20% 92.7 75.1 78.5 65.0 52.3 50.5 30.0 20.6 1,256.31 104.69 14 179.47

TOTALS 40,475 135,360 9,824.28 818.69 1,403.47

Total Lab CFM 105660 cfm

New LAB AHUs' 52830 cfm Fan Heat Delta T 3 deg F

(assume 2 Lab AHU's for load plus 1 redundant unit) Unit Leaving Air Temp 54

Office AHU CHW reduction 54 tons

New AHU's BLS3 Peak CHW Load 40 tons

Labs (N+1 and 20% Future) 3 @ 52830 CFM (N+1)

Office (10% Future) 1 @ 29700 CFM Total Cooling Load 819 safety 0% 0

Sub-Total 819

Process Cooling Load

0% 0

Humidification Sub-Total 0

0 30 grains/lb 70 / 30% Total Cooling Load 819

-10/50% 2 grains/lb

AHU Humidifiers 53/80% 50 grains/lb 70 / 45%

Trim Humidifiers 75/55% grains/lb

LAB AHU Humdification Hum per AHU 3 hum per AHU

23,012,748 grains/hr 3288 lbs/hr 1644 548

OFFICE AHU Humidification

2,673,000 grains/hr 382 lbs/hr

TOTAL Humidification

25685748 grains/hr 3669 lb/hr

HDR Atlanta, Georgia

Location: Cincinnati, OH

Project: Forensic Chemistry Center - NEW LABS

Project Number: 0XXX-00X.0X June 5, 2020

Calculations: HEATING LOADS (New Lab Offices on Office AHU with Return Air)

Outside Leaving Total Coil 15 psi steam 50 psi steam 125 psi steam area CFM % OA Air OA DB air temp load Load Load Load

(ft^2) (cfm) (F) (F - db) (mbh) (#/hr) (#/hr) (#/hr)

Preheat

New Lab AHU Capacity 9,150 16,596 100% 16,596 -10.0 55 1,186.61 1,254.35 1,300.83 1,365.02

AH-2 17,838 42,480 100% 42,480 -10.0 55 3,037.32 3,210.70 3,329.66 3,493.98

AH-3 13,487 46,584 100% 46,584 -10.0 55 3,330.76 3,520.88 3,651.34 3,831.54

AH-4 (existing) 0 51,780 20% 10,356 -10.0 55 740.45 782.72 811.72 851.78

NEW OFFICE AHU 29,700 20% 5,940 40.0 85 294.03 310.81 322.33 338.24

Total Preheat 7,848.72

Reheat

New Lab AHU Capacity 9,150 16,596 100% 16,596 55.0 85 547.67 578.93 600.38 630.01

AH-2 17,838 42,480 100% 42,480 55.0 85 1,401.84 1,481.86 1,536.77 1,612.61

AH-3 13,487 46,584 100% 46,584 55.0 85 1,537.27 1,625.02 1,685.24 1,768.40

AH-4 (existing) 0 51,780 20% 10,356 55.0 85 341.75 361.26 374.64 393.13

NEW OFFICE AHU 29,700 20% 5,940 55.0 85 196.02 207.21 214.89 225.49

Total reheat 3683

Total preheat/reheat 40,475 187,140 121956.0 11,531.52 13,126.53 13,612.92 14,284.71

Safety 0% 0.00 0.00 0.00

TOTAL 11,531.52 13,126.53 13,612.92 14,284.71

HDR Atlanta, Georgia

Entered Values

TRACE® 700 version 6.3.4

By HDR

Project Name: FDA FCC Cincinnati

Dataset Name: C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

Location: Cincinnati, OH

Building Owner: GSA

Program User: FDA

Company: FDA

Comments:

Cooling Design Period: January thru December

Peak Hour Override: 0

Cincinnati, OhioLocation:

Daylight Savings Period:

Summer Period:

°F 92.90Summer Design Dry Bulb:

°F 74.90Summer Design Wet Bulb:

Cooling Methodology:

°F 5.10Winter Design Dry Bulb:

TETD-TA1

Heating Methodology: UATD 0.97Summer Clearness Number:

0.97Winter Clearness Number:

Room Circ Rate:

0.20Summer Ground Reflectance:

Medium

0.20Winter Ground Reflectance:

Wall Load To Plenum: YES

Building Orientation:

Infiltration Methodology:

Outside Film Methodology:

Terrain Methodology:

Vary with wind speed

Vary with wind speed

Center of a large city

Force VAV Min => Nominal Ventilation at Design:

Allow Energy Recovery/Transfer at Design:

Retest Design Peaks:

Calculate Building Block Loads:

No

Yes

No

0 degrees from north No

Energy Simulation Period: January thru December

Reduced yearSimulation Hours:

Standard (1978)Calendar Code:

400Carbon Dioxide Level: ppm

Close ventilation dampers during unoccupied hours: Yes

Project Name: TRACE® 700 v6.3.4FDA FCC Cincinnati

Dataset Name: Entered Values - Project InformationC:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

ENTERED VALUES

ROOM BY ROOM

By HDR

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Analytical Sample Prep - 096Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

472 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

73.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None472 ft² 0.90Roof - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Analyzed and Un-Analyzed SurplusRoom Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

802 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

73.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None802 ft² 0.90Roof - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

Project Name: TRACE® 700 v6.3.4 calculated at 09:42 AM on 06/05/2020FDA FCC Cincinnati

Dataset Name: Alternative - 1 Entered Values - Rooms Page 1 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Chemical Storage - 069Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

169 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

73.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None169 ft² 0.90Roof - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

GENERAL INFORMATION

Floor Area: People Type: None # of People:Plenum Height:

Flr-Flr Height:

Corridor - 053Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 0 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

195 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

0 People

0.800 W/sq ft

0 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

0.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

Dataset Name: Alternative - 1 Entered Values - Rooms Page 2 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: None # of People:Plenum Height:

Flr-Flr Height:

Corridor - 054Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 0 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

480 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

0 People

0.800 W/sq ft

0 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

0.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None480 ft² 0.90Roof - 1

GENERAL INFORMATION

Floor Area: People Type: None # of People:Plenum Height:

Flr-Flr Height:

Corridor - 074Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 0 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

405 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

0 People

0.800 W/sq ft

0 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

0.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None405 ft² 0.90Roof - 1

Dataset Name: Alternative - 1 Entered Values - Rooms Page 3 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: None # of People:Plenum Height:

Flr-Flr Height:

Corridor - 095Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 0 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

420 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

0 People

0.800 W/sq ft

0 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

0.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None420 ft² 0.90Roof - 1

0 0 0.06164* LW Block, 4* Ins60 ft² 0.90East Wall

Window None42 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1

GENERAL INFORMATION

Floor Area: People Type: None # of People:Plenum Height:

Flr-Flr Height:

Corridor - 103Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 0 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

420 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

0 People

0.800 W/sq ft

0 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

0.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None420 ft² 0.90Roof - 1

90 0 0.06164* LW Block, 4* Ins60 ft² 0.90East Wall

Window None42 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1

Dataset Name: Alternative - 1 Entered Values - Rooms Page 4 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: None # of People:Plenum Height:

Flr-Flr Height:

Corridor - 168Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 0 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

1,060 ft² 20.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

0 People

0.800 W/sq ft

0 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

0.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None1,060 ft² 0.90Roof - 1

270 0 0.06164* LW Block, 4* Ins1,000 ft² 0.90West Wall

Window None500 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1

GENERAL INFORMATION

Floor Area: People Type: None # of People:Plenum Height:

Flr-Flr Height:

Corridor - 169Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 0 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

975 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

0 People

0.800 W/sq ft

0 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

0.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None975 ft² 0.90Roof - 1

Dataset Name: Alternative - 1 Entered Values - Rooms Page 5 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Cylinder Storage - 071Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

192 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None192 ft² 0.90Roof - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Data Room - 064Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

209 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

Dataset Name: Alternative - 1 Entered Values - Rooms Page 6 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Data Room - 065Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

145 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None145 ft² 0.90Roof - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Data Room - 081Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

84 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None84 ft² 0.90Roof - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

Dataset Name: Alternative - 1 Entered Values - Rooms Page 7 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Data Room - 082Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

232 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None232 ft² 0.90Roof - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Data Room - 088Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

102 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None102 ft² 0.90Roof - 1

90 0 0.06164* LW Block, 4* Ins102 ft² 0.90East Wall

Window None22 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

Dataset Name: Alternative - 1 Entered Values - Rooms Page 8 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Data Room - 089Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

95 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp

Glass

U Value ShadingBtu/h·ft²·°F

Type /

Energy Type

Area Grnd Refl

Temp/

Alpha ft²

0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None95 ft² 0.90Roof - 1

90 0 0.06164* LW Block, 4* Ins100 ft² 0.90East Wall

Window None30 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1

Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1

Dataset Name: Alternative - 1 Entered Values - Rooms Page 9 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc

By HDR

GENERAL INFORMATION

Floor Area: People Type: Laboratory # of People:Plenum Height:

Flr-Flr Height:

Data Room - 090Room Description:

Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass

Ceiling R-Value:

Is There Carpet?: YES

Design Clg DB / Drift Point:

50 %

Floor Multiplier: 1

PEOPLE

People Sensible: 250 Btu/h

People Schedule: Cooling Only (Design)

Lighting Type: LED Lighting 100% load to space

Fixture Type: LED Lighting % Load to RA: 0 %

Lighting Schedule: Cooling Only (Design) Lighting Amount:

1.0

AIRFLOW INFORMATION

No ZoneZone Description:

Vent Type:

Infil Type:

None Vent Value:

Available (100%)Vent Schedule:

None

Infil Value:

Infil Schedule: Available (100%)

None

None

Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:

Supply:

Aux Supply:

Room Exhaust: 100.00 % Clg Airflow

Ballast Factor:

People Latent :

Design Htg DB / Drift Point:

Design Relative Humidity:

Room Multiplier:

100.00 % Clg Airflow 100.00 % Htg Airflow

0.00 air changes/hr 0.00 air changes/hr

To be calculated To be calculated To be calculated To be calculated

134 ft² 14.0 ft

4.0 ft

1.786 hr·ft²·°F/Btu

75.0 °F / 81.0 °F

70.0 °F / 64.0 °F

System Description: AC-2 Existing

250 sq ft/person

1.500 W/sq ft

250 Btu/h

Height Above Flr:

Moisture Capacitance:

Humidistat Location:

Medium

Room NoneCO2 Sensor Location:

RoomThermostat Location:

CstatClg Tstat:

HstatHtg Tstat:

Available (100%)Rm Exh Sched:

LIGHTS

Cooling Heating

1.0 workstation/personWorkstation:

ConditionedRoom Type:

Max: 50.00 % Clg Airflow

Description

Pct Pct Pct Rad

Shade Ret/Rm/Sen/ Frc/

Adj

Const Type /Area/ ExternalU Value Coef

LossPermHeat…

This is the start of the file's text. The full file is on GovTribe.