This solicitation is for a Construction Manager as Constructor (CMc) contract to modernize outdated systems and expand laboratory spaces for the FDA Forensic Chemistry Center and Peck Federal Building located in Cincinnati, OH. The General Services Administration (GSA) intends to award a Guaranteed Maximum Price (GMP) contract. The solicitation document provides additional details on the repair and alteration project requirements. Interested parties should review attachments for product and service specifications, response deadlines, and other salient information.
View the file
Other files
Show 40 more
Latest 50 of 95 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HDR
Client: GSA/FDA FCC
Location: Cincinnati, OH
Project: Forensic Chemistry Center - NEW LABS Notes:
Project Number: 0XXX-00X.0X
Calculations: Air Valve & Reheat Coil Calculations June 5, 2020
Entering Air Temp 54 °F NEW LAB OPIOID LAB AIRFLOWS Entering Water Temp 180 °F
Hot Water ΔT 20 F° Minimum 6 ACH in labs at all times, including Unoccupied Setting per DRM
Coil Velocity 700 ft/min
Unoccupied Turndown 30%
Unit Sizing Factor 20% 20% Future Growth Capacity for LAB AHU per DRM Paragraph 6.2.1
Lab 1 3470 10.0 6 3470 1.5 8 10 73 6110 18 18 12.9 160.0 73.3 4200 1600 5800 600 6110 6710 6-5 ft FH (700 cfm/ea) (CAV), 16 snork Exh (100 cfm/.ea)
Lab 2 2705 10.0 6 2705 1.5 8 10 73 4625 18 18 9.8 160.0 73.5 2800 800 3600 200 4625 4825 4-5 ft FH (700 cfm/ea) (CAV), 8 snork exh (100 cfm/ea)
Lab Corridor North 210 10.0 6 210 1.0 0 0 75 405 9 9 1.0 161.5 75.0 200 405 205
Lab Corridor East 790 10.0 4 525 1.0 0 0 75 465 12 9 1.4 160.0 75.0 - - 600 600 - -
Lab Corridor South 435 10.0 4 290 1.0 0 0 75 290 9 9 1.0 161.7 75.0 - - 400 400 - -
Lab Equipment Storage 310 10.0 6 310 1.5 8 1 73 1090 15 15 2.3 160.0 73.0 - - 200 1090 1290
Evidence Destruction 330 10.0 6 330 1.5 8 1 73 600 12 9 1.2 160.0 73.0 700 700 200 600 800 1-5 ft FH (700 cfm/ea)
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
- - - - - - - - - - - - 0 - -
- - - - - - - - - - - - 0 - -
- - - - - - - - - - 0 0
8250 7,840 13585 GPM 1200 Supply Exhaust
29.6 13830 13830
35.5 16596 16596
** Room data sheet calls for exhausted Type A2 BSC in Room 066A but DRM paragraph 6.1.16.3 indicates BSC should not be ducted or thimble connected.
Room Name Room Number
Air
Change
Heat
Load
Reheat
Coil
Eqpm
Exhaust Offset Occupied
People (#)
RemarksFloor
Area
(sf)
Ceiling
Height (ft) ACH CFM/sf
Air
Change (cfm)
Lights
(w/sf) Power (w)
Skin
Gain
(MBH)
Design
Temp (°F)
Heat Load
(cfm) Width Height Out (cfm)
General
Supply
(cfm)
Total
Exhaust
(cfm)
GPM
Exit
Water
Temp
Exit
Air
Temp
Fume
Hood
(cfm)
BSC (cfm)
Animal
Racks
(cfm)
System Totals (with sizing factor)
System Sub-Totals
Misc (cfm) Total
(cfm)
In
(cfm)
Location: Cincinnati, OH
Project: Forensic Chemistry Center - NEW LABS Notes:
Project Number: 0XXX-00X.0X
Calculations: Air Valve & Reheat Coil Calculations June 5, 2020
Entering Air Temp 54 °F EXISTING AC-2 AIRFLOWS Entering Water Temp 180 °F
Hot Water ΔT 20 F° Minimum 6 ACH in labs at all times, including Unoccupied Setting per DRM
Coil Velocity 700 ft/min
Unoccupied Turndown 30%
Unit Sizing Factor 20% 20% Future Growth Capacity for LAB AHU per DRM Paragraph 6.2.1
Investigation Sample Prep 051 161 10.0 6 160 280 9 6 1.0 208.4 7.5 380 380 100 280 380 GE
Office / Storage 052 137 10.0 6 135 233 9 6 1.0 202.8 9.1 333 333 100 233 333 GE
Drug Storage 055 74 10.0 6 75 125 6 6 1.0 194.7 0.0 225 225 100 125 225 GE
Evidence Room 061 390 10.0 6 390 710 12 12 1.0 263.6 0.0 810 810 100 710 810 GE
Analyzed and Un-Analyzed Surplus 062 803 10.0 6 805 1402 18 15 1.0 345.0 0.0 1502 1502 100 1402 1502 GE
Security Corridor 056 143 10.0 6 145 400 9 9 1.0 227.1 0.0 - - 400 400 - - no GE
Supply Clerk 057 130 10.0 6 130 150 6 6 1.0 197.7 0.0 250 250 100 150 250 GE
Vault 058 74 10.0 6 75 130 - - - - 1.0 195.3 0.0 230 230 100 130 230 GE
General Chemistry Lab 063 1170 10.0 6 1170 3905 - - - - 1.0 639.7 0.0 3100 1290 4390 485 3905 4390 2 6ft FH's at 1550 cfm ea, 1290 cfm GE
Data Room 064 210 10.0 6 210 241 - - - - 1.0 208.4 0.0 241 241 0 241 241 GE
Data Room 065 146 10.0 6 145 241 - - - - 1.0 208.4 0.0 241 241 0 241 241 GE
Corridor 054 485 10.0 6 485 850 - - - - 1.0 280.1 0.0 275 275 575 850 275 GE
Corridor 053 195 10.0 6 195 500 - - - - 1.0 238.9 0.0 200 200 300 500 200 GE
Washing Autoclave 066 580 10.0 6 580 3000 - - - - 1.0 533.2 0.0 3350 3350 350 3000 3350 GE'1 3200 cfm CH and 150 CFM vent
Lab Equipment Storage 067 330 10.0 6 330 259 - - - - 1.0 210.5 0.0 650 650 400 259 659 GE
Shipping Receiving 068 416 10.0 6 415 880 - - - - 1.0 283.6 0.0 330 330 550 880 330 GE
Shipping Clerk 072 80 10.0 6 80 150 - - - - 1.0 197.7 0.0 0 - - 0 150 150 GE
Chemical Storage 069 192 10.0 6 190 200 - - - - 1.0 203.5 0.0 300 300 100 200 300 no GE
Volatile Solvents 070 250 10.0 6 250 1100 - - - - 1.0 309.5 0.0 1195 1195 95 1100 1195 GE
Cylinder Storage 071 192 10.0 6 190 266 - - - - 1.0 211.3 0.0 366 366 100 266 366 GE
Micro Molecular Biology 075 1205 10.0 6 1205 3500 - - - - 1.0 592.0 0.0 3600 100 3700 200 3500 3700 2 6ft FH at 1550 cfm ea, 1 6 ft FH at 1200 cfm
Corridor 074 405 10.0 6 405 600 - - - - 1.0 250.6 0.0 0 - - 600 600 - - no GE
Corridor 169 975 16.0 6 1560 2000 - - - - 1.0 415.4 0.0 500 500 1500 2000 500 GE
Electrical Repair 165 420 10.0 6 420 1300 - - - - 1.0 333.0 0.0 1000 385 1385 85 1300 1385 1 hood at 1000 cfm
Fingerprint Lab 080 265 10.0 6 265 1800 - - - - 1.0 391.9 0.0 1550 400 1950 150 1800 1950 1 6 ft FH and 2 cabinet exhaust at 200 cfm ea
Data Room 081 84 10.0 6 85 190 - - - - 1.0 202.4 0.0 190 190 0 190 190 GE
Dark Room 082 232 10.0 6 230 652 - - - - 1.0 256.8 0.0 652 652 0 652 652 GE
Telecom 084 102 10.0 6 100 260 9 6 1.0 210.6 0.0 260 260 0 260 260 GE
Electric Room 085 102 10.0 6 100 260 9 6 1.0 210.6 0.0 260 260 0 260 260 GE
Electron Microscope 086 383 10.0 6 385 1360 18 15 1.0 340.1 0.0 1460 1460 100 1360 1460 GE
Microscopy/Photography 087 600 10.0 6 600 1709 18 18 1.0 381.2 0.0 1550 250 1800 100 1709 1809 1 6 ft FH at 1550 cfm & 1 GE
Data Room 088 100 10.0 6 100 270 9 6 1.0 211.8 0.0 270 270 0 270 270 GE
Data Room 089 95 10.0 6 95 270 9 6 1.0 211.8 0.0 288 288 18 270 288 GE
Data Room 090 134 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288 GE
FTIR 091 1050 10.0 6 1050 3422 18 18 1.0 582.8 0.0 1550 1500 3050 200 3422 3622 1 6 ft FH and 1 3312 cfm GE
Data Room 092 133 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288 GE
Data Room 093 138 10.0 6 140 288 9 6 1.0 213.9 0.0 288 288 0 288 288 GE
Corridor 095 420 10.0 6 420 700 12 12 1.0 262.4 0.0 225 225 475 700 225 GE
Analytical Sample Prep 096 471 10.0 6 470 3300 18 18 1.0 568.5 0.0 3400 3400 100 3300 3400 1 Canopy Hood
Separation III 097 1684 10.0 6 1685 7324 18 18 1.0 1042.2 0.0 5924 1800 7724 400 7324 7724 4 6 ft FH at 1550 cfm, 6 snorkel at 300 cfm, 2 GE
Data Room 098 136 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288
Data Room 099 133 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288
Data Room 100 133 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288
Data Room 101 133 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288
Data Room 102 136 10.0 6 135 288 9 6 1.0 213.9 0.0 288 288 0 288 288
Corridor 103 480 10.0 6 480 800 15 12 1.0 274.2 0.0 0 - - 800 800 - -
Standards Separation 104 471 10.0 6 470 1851 18 18 1.0 397.9 0.0 1550 500 2050 199 1851 2050 1 6 ft FH and 1641 cfm GE
Corridor 168 1060 16.0 6 1695 2000 18 18 1.0 415.4 0.0 500 500 1500 2000 500 GE
17838 19,060 50894 GPM 3782 Supply Exhaust
48.0 35400 30405
57.6 42480 36486System Totals (with sizing factor)
System Sub-Totals Existing AC-2 sized for 50,475 cfm
Misc (cfm) Total
(cfm)
In
(cfm) Out (cfm)
General
Supply
(cfm)
Total
Exhaust
(cfm)
GPM
Exit
Water
Temp
Exit
Air
Temp
Fume
Hood
(cfm)
BSC (cfm)
Animal
Racks
(cfm)
Skin
Gain
(MBH)
Design
Temp (°F)
Heat Load
(cfm) Width Height
RemarksFloor
Area
(sf)
Ceiling
Height (ft) ACH CFM/sf
Air
Change (cfm)
Lights
(w/sf) Power (w)
** Room data sheet calls for exhausted Type A2 BSC in Room 066A but DRM paragraph 6.1.16.3 indicates BSC should not be ducted or thimble connected.
Room Name Room Number
Air
Change
Heat
Load
Reheat
Coil
Eqpm
Exhaust Offset Occupied
People (#)
Location: Cincinnati, OH
Project: Forensic Chemistry Center - NEW LABS Notes:
Project Number: 0XXX-00X.0X
Calculations: Air Valve & Reheat Coil Calculations June 5, 2020
Entering Air Temp 54 °F EXISTING AC-3 AIRFLOWS Entering Water Temp 180 °F
Hot Water ΔT 20 F° Minimum 6 ACH in labs at all times, including Unoccupied Setting per DRM
Coil Velocity 700 ft/min
Unoccupied Turndown 30%
Unit Sizing Factor 20% 20% Future Growth Capacity for LAB AHU per DRM Paragraph 6.2.1
Mass Spectrometry 110 1552 10.0 6 1550 4524 18 18 1.0 708.0 0.5 4300 400 4700 176 4524 4700 2 6 ft FH at 2150 CFM each
Data Room 111 136 10.0 6 135 288 9 6 1.0 209.3 7.3 400 400 112 288 400 GE
Data Room 112 133 10.0 6 135 288 9 6 1.0 213.9 0.0 400 400 112 288 400 GE
Clean Room 106 167 10.0 6 165 1354 18 15 1.0 339.4 0.0 1000 1000 354 1354 1000 GE
Change Room 105 128 10.0 6 130 500 12 9 1.0 238.9 0.0 500 500 354 500 854 GE
Clean Room 107 114 10.0 6 115 1192 15 15 1.0 320.3 0.0 880 880 312 1192 880 1-6 ft FH at 880 cfm
108 127 10.0 6 125 1192 15 15 1.0 320.3 0.0 880 880 312 1192 880 1-6 ft FH at 880 cfm
Photograph Document Lab 109 225 10.0 6 225 1058 - - - - 1.0 304.5 0.0 1150 1150 92 1058 1150 GE
Ion Chromotography 113 505 10.0 6 505 2173 - - - - 1.0 435.8 0.0 350 1913 2263 200 2173 2373 1 6ft FH at 1550 Cfm
Data Room 114 165 10.0 6 165 296 - - - - 1.0 214.8 0.0 296 296 0 296 296 GE
Corridor 116 490 10.0 2 165 700 - - - - 1.0 262.4 0.0 530 530 170 700 530 GE
Corridor 103 480 10.0 6 480 800 - - - - 1.0 274.2 0.0 0 - - 800 800 - - no GE
Atomic Absorption 117 1575 10.0 6 1575 5152 - - - - 1.0 786.5 0.0 3100 3000 6100 948 5152 6100 2 6ft FH's at 1550 cfm each, 3000 cfm snorkels
Data Room 118 150 10.0 6 150 400 - - - - 1.0 227.1 0.0 400 400 0 400 400 GE
Data Room 119 150 10.0 6 150 400 - - - - 1.0 227.1 0.0 400 400 0 400 400 GE
Inorganic Sample 120 710 10.0 6 710 7904 - - - - 1.0 1110.5 0.0 6200 2420 8620 716 7904 8620 4 FH's, 2 LF Hoods, 100 cfm furnace
ICP Mass Spectrometry 121 537 10.0 6 535 3961 - - - - 1.0 646.3 0.0 950 1200 2150 1799 3961 2162 1 6ft FH at 950 cfm, 1200 CFM point of use exh
Data Room 122 163 10.0 6 165 295 - - - - 1.0 214.7 0.0 295 295 0 295 295 GE
Corridor 167 960 16.0 6 1535 2000 - - - - 1.0 415.4 0.0 - - 2000 2000 - - no GE
Separation II 132 1681 10.0 6 1680 7040 - - - - 1.0 1008.7 0.0 4000 2900 6900 160 7040 7200 4 6ft FH's at 1550 cfm EA, 1 CH at 1300 cfm, 6 snorkels
Separation 1 124 1695 10.0 6 1695 5940 - - - - 1.0 879.3 0.0 4400 1800 6200 260 5940 6200 4 6ft FH's at 1550 cfm ea, 6 snorkels at 300 cfm
Corridor 131 314 10.0 6 315 556 - - - - 1.0 245.5 0.0 656 656 100 556 656 GE
Data Room 125 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 126 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 127 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 128 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 129 133 10.0 6 135 281 - - - - 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 133 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 134 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 135 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 136 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE
Data Room 137 133 10.0 6 135 281 9 6 1.0 213.1 0.0 281 281 0 281 281 GE
13487 13,755 50823 GPM 3230 Supply Exhaust
32.0 38820 33820
38.4 46584 40584System Totals (with sizing factor)
System Sub-Totals Existing AC-3 sized for 49,714 cfm
Misc (cfm) Total
(cfm)
In
(cfm) Out (cfm)
General
Supply
(cfm)
Total
Exhaust
(cfm)
GPM
Exit
Water
Temp
Exit
Air
Temp
Fume
Hood
(cfm)
BSC (cfm)
Animal
Racks
(cfm)
Skin
Gain
(MBH)
Design
Temp (°F)
Heat Load
(cfm) Width Height
RemarksFloor
Area
(sf)
Ceiling
Height (ft) ACH CFM/sf
Air
Change (cfm)
Lights
(w/sf) Power (w)
** Room data sheet calls for exhausted Type A2 BSC in Room 066A but DRM paragraph 6.1.16.3 indicates BSC should not be ducted or thimble connected.
Room Name Room Number
Air
Change
Heat
Load
Reheat
Coil
Eqpm
Exhaust Offset Occupied
People (#)
Location: Cincinnati, OH
Project: Forensic Chemistry Center - NEW LABS
Project Number: 0XXX-00X.0X
Calculations: CHILLED WATER LOADS (New Lab Offices on Office AHU with Return Air)
June 5, 2020
Net to Gross Ceiling Maximum Coil Lvg Coil Lvg Entering Coil Lvg Total Coil Chilled
AHU # area Efficiency Height ACH CFM % OA OA DB OA WB MA DB MA WB air temp air temp Enthalpy Enthalpy load tons Water dt Flow
(ft^2) % (ft) (F) (F) (F) (F) (F - db) (F - wb) (mbh) (F) (gpm)
NEW LAB AHU CAPACITY 9,150 -- -- -- 16,596 100% 92.7 75.1 92.7 75.1 51.0 50.5 38.5 20.5 1,345.77 112.15 14 192.25
AC-2 17,838 -- -- -- 42,480 100% 92.7 75.1 92.7 75.1 51.0 50.5 38.5 20.5 3,444.70 287.06 14 492.10
AC-3 13,487 -- -- -- 46,584 100% 92.7 75.1 92.7 75.1 51.0 50.5 38.5 20.5 3,777.50 314.79 14 539.64
AH-4 (existing office AHU) -- -- -- 51,780 20% 92.7 75.1 82.0 67.0 54.3 54.3 31.0 22.8 1,903.69 158.64 14 271.96
NEW OFFICE AHU 29,700 20% 92.7 75.1 78.5 65.0 52.3 50.5 30.0 20.6 1,256.31 104.69 14 179.47
TOTALS 40,475 135,360 9,824.28 818.69 1,403.47
Total Lab CFM 105660 cfm
New LAB AHUs' 52830 cfm Fan Heat Delta T 3 deg F
(assume 2 Lab AHU's for load plus 1 redundant unit) Unit Leaving Air Temp 54
Office AHU CHW reduction 54 tons
New AHU's BLS3 Peak CHW Load 40 tons
Labs (N+1 and 20% Future) 3 @ 52830 CFM (N+1)
Office (10% Future) 1 @ 29700 CFM Total Cooling Load 819 safety 0% 0
Sub-Total 819
Process Cooling Load
0% 0
Humidification Sub-Total 0
0 30 grains/lb 70 / 30% Total Cooling Load 819
-10/50% 2 grains/lb
AHU Humidifiers 53/80% 50 grains/lb 70 / 45%
Trim Humidifiers 75/55% grains/lb
LAB AHU Humdification Hum per AHU 3 hum per AHU
23,012,748 grains/hr 3288 lbs/hr 1644 548
OFFICE AHU Humidification
2,673,000 grains/hr 382 lbs/hr
TOTAL Humidification
25685748 grains/hr 3669 lb/hr
HDR Atlanta, Georgia
Location: Cincinnati, OH
Project: Forensic Chemistry Center - NEW LABS
Project Number: 0XXX-00X.0X June 5, 2020
Calculations: HEATING LOADS (New Lab Offices on Office AHU with Return Air)
Outside Leaving Total Coil 15 psi steam 50 psi steam 125 psi steam area CFM % OA Air OA DB air temp load Load Load Load
(ft^2) (cfm) (F) (F - db) (mbh) (#/hr) (#/hr) (#/hr)
Preheat
New Lab AHU Capacity 9,150 16,596 100% 16,596 -10.0 55 1,186.61 1,254.35 1,300.83 1,365.02
AH-2 17,838 42,480 100% 42,480 -10.0 55 3,037.32 3,210.70 3,329.66 3,493.98
AH-3 13,487 46,584 100% 46,584 -10.0 55 3,330.76 3,520.88 3,651.34 3,831.54
AH-4 (existing) 0 51,780 20% 10,356 -10.0 55 740.45 782.72 811.72 851.78
NEW OFFICE AHU 29,700 20% 5,940 40.0 85 294.03 310.81 322.33 338.24
Total Preheat 7,848.72
Reheat
New Lab AHU Capacity 9,150 16,596 100% 16,596 55.0 85 547.67 578.93 600.38 630.01
AH-2 17,838 42,480 100% 42,480 55.0 85 1,401.84 1,481.86 1,536.77 1,612.61
AH-3 13,487 46,584 100% 46,584 55.0 85 1,537.27 1,625.02 1,685.24 1,768.40
AH-4 (existing) 0 51,780 20% 10,356 55.0 85 341.75 361.26 374.64 393.13
NEW OFFICE AHU 29,700 20% 5,940 55.0 85 196.02 207.21 214.89 225.49
Total reheat 3683
Total preheat/reheat 40,475 187,140 121956.0 11,531.52 13,126.53 13,612.92 14,284.71
Safety 0% 0.00 0.00 0.00
TOTAL 11,531.52 13,126.53 13,612.92 14,284.71
HDR Atlanta, Georgia
Entered Values
TRACE® 700 version 6.3.4
By HDR
Project Name: FDA FCC Cincinnati
Dataset Name: C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
Location: Cincinnati, OH
Building Owner: GSA
Program User: FDA
Company: FDA
Comments:
Cooling Design Period: January thru December
Peak Hour Override: 0
Cincinnati, OhioLocation:
Daylight Savings Period:
Summer Period:
°F 92.90Summer Design Dry Bulb:
°F 74.90Summer Design Wet Bulb:
Cooling Methodology:
°F 5.10Winter Design Dry Bulb:
TETD-TA1
Heating Methodology: UATD 0.97Summer Clearness Number:
0.97Winter Clearness Number:
Room Circ Rate:
0.20Summer Ground Reflectance:
Medium
0.20Winter Ground Reflectance:
Wall Load To Plenum: YES
Building Orientation:
Infiltration Methodology:
Outside Film Methodology:
Terrain Methodology:
Vary with wind speed
Vary with wind speed
Center of a large city
Force VAV Min => Nominal Ventilation at Design:
Allow Energy Recovery/Transfer at Design:
Retest Design Peaks:
Calculate Building Block Loads:
No
Yes
No
0 degrees from north No
Energy Simulation Period: January thru December
Reduced yearSimulation Hours:
Standard (1978)Calendar Code:
400Carbon Dioxide Level: ppm
Close ventilation dampers during unoccupied hours: Yes
Project Name: TRACE® 700 v6.3.4FDA FCC Cincinnati
Dataset Name: Entered Values - Project InformationC:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
ENTERED VALUES
ROOM BY ROOM
By HDR
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Analytical Sample Prep - 096Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
472 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
73.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None472 ft² 0.90Roof - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Analyzed and Un-Analyzed SurplusRoom Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
802 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
73.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None802 ft² 0.90Roof - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
Project Name: TRACE® 700 v6.3.4 calculated at 09:42 AM on 06/05/2020FDA FCC Cincinnati
Dataset Name: Alternative - 1 Entered Values - Rooms Page 1 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Chemical Storage - 069Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
169 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
73.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None169 ft² 0.90Roof - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
GENERAL INFORMATION
Floor Area: People Type: None # of People:Plenum Height:
Flr-Flr Height:
Corridor - 053Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 0 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
195 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
0 People
0.800 W/sq ft
0 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
0.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
Dataset Name: Alternative - 1 Entered Values - Rooms Page 2 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: None # of People:Plenum Height:
Flr-Flr Height:
Corridor - 054Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 0 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
480 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
0 People
0.800 W/sq ft
0 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
0.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None480 ft² 0.90Roof - 1
GENERAL INFORMATION
Floor Area: People Type: None # of People:Plenum Height:
Flr-Flr Height:
Corridor - 074Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 0 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
405 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
0 People
0.800 W/sq ft
0 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
0.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None405 ft² 0.90Roof - 1
Dataset Name: Alternative - 1 Entered Values - Rooms Page 3 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: None # of People:Plenum Height:
Flr-Flr Height:
Corridor - 095Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 0 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
420 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
0 People
0.800 W/sq ft
0 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
0.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None420 ft² 0.90Roof - 1
0 0 0.06164* LW Block, 4* Ins60 ft² 0.90East Wall
Window None42 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1
GENERAL INFORMATION
Floor Area: People Type: None # of People:Plenum Height:
Flr-Flr Height:
Corridor - 103Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 0 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
420 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
0 People
0.800 W/sq ft
0 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
0.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None420 ft² 0.90Roof - 1
90 0 0.06164* LW Block, 4* Ins60 ft² 0.90East Wall
Window None42 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1
Dataset Name: Alternative - 1 Entered Values - Rooms Page 4 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: None # of People:Plenum Height:
Flr-Flr Height:
Corridor - 168Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 0 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
1,060 ft² 20.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
0 People
0.800 W/sq ft
0 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
0.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None1,060 ft² 0.90Roof - 1
270 0 0.06164* LW Block, 4* Ins1,000 ft² 0.90West Wall
Window None500 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1
GENERAL INFORMATION
Floor Area: People Type: None # of People:Plenum Height:
Flr-Flr Height:
Corridor - 169Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 0 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
975 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
0 People
0.800 W/sq ft
0 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
0.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None975 ft² 0.90Roof - 1
Dataset Name: Alternative - 1 Entered Values - Rooms Page 5 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Cylinder Storage - 071Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
192 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None192 ft² 0.90Roof - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Data Room - 064Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
209 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
Dataset Name: Alternative - 1 Entered Values - Rooms Page 6 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Data Room - 065Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
145 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None145 ft² 0.90Roof - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Data Room - 081Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
84 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None84 ft² 0.90Roof - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
Dataset Name: Alternative - 1 Entered Values - Rooms Page 7 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Data Room - 082Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
232 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None232 ft² 0.90Roof - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Data Room - 088Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
102 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None102 ft² 0.90Roof - 1
90 0 0.06164* LW Block, 4* Ins102 ft² 0.90East Wall
Window None22 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
Dataset Name: Alternative - 1 Entered Values - Rooms Page 8 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Data Room - 089Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
95 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeatCoolInternal Amount ScheduleDir Tilt ShadingBtu/h·ft²·°F CoefLenTmpTmp
Glass
U Value ShadingBtu/h·ft²·°F
Type /
Energy Type
Area Grnd Refl
Temp/
Alpha ft²
0 90 0.06814* LW Conc, 3* Ins None0 Overhang - None95 ft² 0.90Roof - 1
90 0 0.06164* LW Block, 4* Ins100 ft² 0.90East Wall
Window None30 Overhang - None0.55 0.50Double Coated 1/4* 0.00 Opening - 1
Cooling Only (Design) 100 60.0001008.00 W/sq ft NoneMisc Load 1
Dataset Name: Alternative - 1 Entered Values - Rooms Page 9 of 97C:\Users\wzavatkay\Documents\TRACE 700 Projects\FDA FCC CINCINNATI OPTION 1A.trc
By HDR
GENERAL INFORMATION
Floor Area: People Type: Laboratory # of People:Plenum Height:
Flr-Flr Height:
Data Room - 090Room Description:
Slab Cnstr Type: 4* LW Concrete Room Mass: Time delay based on actual mass
Ceiling R-Value:
Is There Carpet?: YES
Design Clg DB / Drift Point:
50 %
Floor Multiplier: 1
PEOPLE
People Sensible: 250 Btu/h
People Schedule: Cooling Only (Design)
Lighting Type: LED Lighting 100% load to space
Fixture Type: LED Lighting % Load to RA: 0 %
Lighting Schedule: Cooling Only (Design) Lighting Amount:
1.0
AIRFLOW INFORMATION
No ZoneZone Description:
Vent Type:
Infil Type:
None Vent Value:
Available (100%)Vent Schedule:
None
Infil Value:
Infil Schedule: Available (100%)
None
None
Vav Airflow: Min: 50.00 % Clg Airflow Available (100%)Vav Sched:
Supply:
Aux Supply:
Room Exhaust: 100.00 % Clg Airflow
Ballast Factor:
People Latent :
Design Htg DB / Drift Point:
Design Relative Humidity:
Room Multiplier:
100.00 % Clg Airflow 100.00 % Htg Airflow
0.00 air changes/hr 0.00 air changes/hr
To be calculated To be calculated To be calculated To be calculated
134 ft² 14.0 ft
4.0 ft
1.786 hr·ft²·°F/Btu
75.0 °F / 81.0 °F
70.0 °F / 64.0 °F
System Description: AC-2 Existing
250 sq ft/person
1.500 W/sq ft
250 Btu/h
Height Above Flr:
Moisture Capacitance:
Humidistat Location:
Medium
Room NoneCO2 Sensor Location:
RoomThermostat Location:
CstatClg Tstat:
HstatHtg Tstat:
Available (100%)Rm Exh Sched:
LIGHTS
Cooling Heating
1.0 workstation/personWorkstation:
ConditionedRoom Type:
Max: 50.00 % Clg Airflow
Description
Pct Pct Pct Rad
Shade Ret/Rm/Sen/ Frc/
Adj
Const Type /Area/ ExternalU Value Coef
LossPermHeat…