472_22426 - CTS Full Set Drawings_Stamped_Part2.pdf
PDF 5 MB Posted
- Attached to
- 472/22426. CTS; CMCF - Various Security Upgrades
- Solicitation number
- RFQ 171 240000000205 2
- Issued by
- Gogebic County, Sterling Heights City, Michigan
About this file
This document is a set of stamped construction drawings prepared for the State of Michigan Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division, for a maintenance project identified as file number 472/22426. The drawings were issued for bids on January 19, 2024, and include mechanical and electrical specifications for multiple buildings including a Transportation Building, Housing Units J+K, L+M, and N+P. The project scope encompasses HVAC system installations, including new dehumidifiers, supply and return air ductwork, condensate piping, and associated controls, along with electrical work including lighting fixtures, power systems, and receptacle relocations. The drawings specify that all work must be performed by licensed contractors and subcontractors in compliance with the Michigan Mechanical Code and applicable National Electric Code standards. Key requirements include field verification of existing conditions, coordination with other trades, maintenance of equipment in new condition, and post-construction meetings at six and eleven months to address warranty issues.
The technical specifications detail material requirements such as galvanized sheet metal ductwork with minimum 26-gauge thickness, low-pressure loss duct fittings complying with SMACNA standards, condensate drain piping with minimum one percent slope, and tamperproof fasteners in areas accessible to inmates. All wall and floor penetrations must be sealed to maintain original ratings, and all exposed wiring must be installed in conduit. Electrical work includes relocation of existing condensate pumps and piping to accommodate new doorways, with any electrical outage not to exceed two hours; portable generators must provide service for longer interruptions. The contractor is required to track and provide documentation of recycled materials throughout the project and attend post-construction meetings with the engineer and owner during the warranty period.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL HVAC NOTES
1. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
2. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT
MAY AFFECT THE WORK.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
4. ALL WORK SHALL BE PERFORMED BY LICENSED CONTRACTORS
AND SUBCONTRACTORS AS REQUIRED BY LAW.
5. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
6. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT FITTINGS
IN ACCORDANCE WITH SMACNA. (WYES, RADIUSED OR VANED
TEES, ETC.) DUCTWORK SHALL BE GALVANIZED SHEET METAL,
MIN. 26 GA.
7. ALL EXPOSED ROUND DUCTWORK SHALL BE SPIRAL.
8. ALL EXTERNALLY ISOLATED HVAC EQUIPMENT SHALL HAVE
FLEXIBLE DUCT CONNECTORS.
9. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.
10. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA AIR
GAP.
11. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR
SPECIFICATIONS THE MORE STRINGENT AND GREATER COST
ITEM SHALL BE USED.
12. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.
IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL NECESSARY
OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO
STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE HEADROOM AND
KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE
FROM DRAWINGS.
13. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL
USE TAMPERPROOF SCREWS.
14. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST
CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER TO
REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.
15. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO OWNER
OF THE AMOUNT OF MATERIAL BEING RECYCLED THROUGHOUT
THE PROJECT.
16. CONTRACTOR TO ROUTE CONDENSATE PIPING AS HIGH AS
POSSIBLE.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLSHVAC PIPING
HVAC DUCTWORK
SD
F/S F/S s s
TEMPERATURE CONTROL SYMBOLS
M
P
M
H
S
T P T N
T
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
FLOAT & THERMOSTATIC STEAM TRAP
INVERTED BUCKET STEAM TRAP
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
BT
FT
SD-1 250
8"ø ---
472/22426.CTS
file no.
checked by drawn by consultant issue date sheet no.
index no.
contract order no.
472STFMAINTPROJ
consultant job no.
23140.00 sheet title
M a tr ix
Y23249
ISSUED FOR BIDS 01-19-24
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M-1.0
CAT
MECH. SYMBOLS,
NOTES, ABBREV.,
AND SCHEDULES
DBP
SD-1 150
6x6 ---
RG-1 150
6x6 ---
DEH-1
3/4" CD
3/4" CD
H
DEH-1
8" RA2
8" SA2
3/4" CD DN
TO X-FD
HVAC KEY NOTES
INSTALL NEW DEHUMIDIFIER, CONTROLS, HUMIDISTAT,
AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION
SHOWN PER THE MANUFACTURES INSTALLATION
INSTRUCTIONS. MOUNT NEW HUMIDIFIER ON UNISTRUT
FRAME FASTENED TO THE TOP OF THE NEW ARSENAL
STRUCTURE. INSTALL NEW HUMIDISTAT INSIDE THE
ARSENAL STRUCTURE IN THE LOCATION SHOWN.
INSTALL NEW SUPPLY AIR DUCTWORK, SUPPLY
DIFFUSER, RETURN AIR DUCTWORK, RETURN GRILLE,
AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION
SHOWN.
INSTALL NEW CONDENSATE PIPING AND ALL
ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN.
ROUTE NEW CONDENSATE PIPING AS HIGH AS
POSSIBLE. ROUTE NEW CONDENSATE PIPING TO
NEAREST EXISTING FLOOR DRAIN AS SHOWN.
472/22426.CTS
file no.
checked by drawn by consultant issue date sheet no.
index no.
contract order no.
472STFMAINTPROJ
consultant job no.
23140.00 sheet title
M a tr ix
Y23249
ISSUED FOR BIDS 01-19-24
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M-4.0
DBP
CAT
TRANSPORT. BLDG
FLOOR PLAN -
MECHANICAL NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
N TRANSPORTATION BUILDING FLOOR PLAN - MECHANICAL NEW
FCPS
V
M C
VI
AV
B
C
DC
M
B
KP
SSCP
CR
SS
AS
TS
G
NCC
M P
E
A L B1 B2
S
SRS
X
X
X
CB
EMERGENCY PUSH STATION
CODE BLUE STATION
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVE
GLASS BREAK
DS
DUPLEX RECEPTACLE
TEACHER STATION
ADMINISTRATION STATION
STUDENT STATION
CARD READER
CARBON MONOXIDE DETECTOR
H
DOCK LIGHT FIXTURE
CONTROL MODULE
S
TELEPHONE / DATA OUTLET
DUTY STATION
STAFF STATION
STAFF REGISTER STATION
DOME LIGHT
DUAL BED STATION
SINGLE BED STATION
BED / LIGHT INTERFACE
PENDENT INTERFACE
EMERGENCY PULL STATION
MASTER STATION
NURSE CALL CONTROLLER
NURSE CALL
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
BELL
AUDIO / VIDEO INPUT
VIDEO INPUT
WALL MOUNTED SPEAKER / CLOCK COMBO
WALL MOUNTED SPEAKERS
DUAL FACE CLOCK
CCTV CONTROL PANELCCTV
SECURITY SYSTEM CONTROL PANEL
KEY PAD
BEAM DETECTOR
MOTION DETECTOR
DOOR CONTACT
CAMERA
MONITOR MODULE
FIRE CONTROL POWER SUPPLY
VISUAL ONLY UNIT
ELECTRICAL SYMBOLS LEGEND
DH
V
S
C
M
I
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SINGLE FACE CLOCK
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SOUND and SIGNAL
INTERCOM OUTLET
MICROPHONE OUTLET
TELEVISION OUTLET
CHIME
BUZZER
VOLUME CONTROL
SPEAKER
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER (BY x/C U.O.N.)
MAGNETIC STARTER (BY x/C U.O.N.)
DISCONNECT SWITCH (fuse size shown)
TRANSFORMER
CONTROL
xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
FIRE ALARM
TAMPER SWITCH (furnished by FP/C) FLOW SWITCH (furnished by FP/C)
FIREFIGHTER COMMUNICATION JACK
MAGNETIC DOOR HOLDER
REMOTE INDICATING LIGHT, CLG. MTD.
REMOTE INDICATING LIGHT, WALL MTD.
END OF LINE DEVICE
ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
PULL STATION
SPEAKER & LIGHT
SPEAKER
HORN
DUCT SMOKE DETECTOR
HEAT DETECTOR
SMOKE DETECTOR
HORN & LIGHT
DESIGNATIONS
(by E.C.)
(by others)
TT
FACP
ANN
EOL
G
WW
PC
CT
TS
T
H
TC
IC
F
FC
F
T
1,3
OR
PM
WM
BD
UFD
B
F S
J
J
D
WH
PP
J
SENSOR SWITCH WSD-PDT SERIES
SWITCH STYLE OCCUPANCY SENSOR
OC
WATT STOPPER TS-400
DIGITAL TIME SWITCH
SENSOR SWITCH MP20 SERIES
POWER PACK
SENSOR SWITCH CMR-PDT SERIES
ULTRASONIC SENSOR - 360° - 500 SQ FT
SENSOR SWITCH CMR-PDT-10
ULTRASONIC SENSOR - 360° - 1000 SQ FT
SENSOR SWITCH CMR-PDT-10-2P
ULTRASONIC SENSOR - 360° - 2 CIRCUIT
SENSOR SWITCH CMR-PC-ADC SERIES
OCCUPANCY SENSOR / PHOTOCELL
SENSOR SWITCH WV-PDT-16 SERIES
WALL MOUNT DUAL TECHNOLOGY SENSOR
OS5
OS4
T
OS2
OS3
OS1
PP
DUCT SMOKE DETECTORF/S
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST (E)
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
LU LUMENS
M
LED - LED - 1X4 WRAPAROUND LIGHT FIXTURE.
FIXTURE
MOUNTING
HEIGHT
LAMPSDESCRIPTION AND COMMENTSTYPE MANUFACTURER CATALOG NO.
LIGHTING FIXTURE SCHEDULE
COOPER LIGHTING OR
EQUAL 4NWS3C3-UNVLA CEILING
BALLAST INFO
0-10V
LED - EXIT SIGN.SURE-LITES OR EQUAL APX6-RXA - --
5272 LUMENS
39W, 4000K
LED
LED - 1X4 WRAPAROUND LIGHT FIXTURE. CONTRACTOR TO PROVIDE A BLTC DEVICE.LAEM CEILING0-10VCOOPER LIGHTING OR
EQUAL
LED - 1X4 LIGHT FIXTURE. CONTRACTOR TO PROVIDE A BLTC DEVICE.4SLSTP4040DD-UNVLBEM CEILING0-10V
5210 LUMENS
39W, 4000K
LED
COOPER LIGHTING OR
EQUAL
4NWS3C3-UNV
5272 LUMENS
39W, 4000K
LED
GENERAL ELECTRICAL NOTES
1. ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED TO MAINTAIN ORIGINAL RATING.
2. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL STEEL.
3. CONTRACTORS SHALL VISIT THE PROJECT SITE AND DETERMINE THE EXACT EXTENT OF THE DEMOLITION WORK REQUIRED
BEFORE BIDDING THE PROJECT.
4. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT WHERE WORK IS BEING DONE EXCEPT
ITEMS NOTED OTHERWISE.
5. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK, SURFACES SHALL BE PATCHED TO MATCH
ADJACENT.
6. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND
THEN PATCHED TO MATCH, OR AS NOTED.
7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED TO SUIT THE NEW SYSTEMS AS REQUIRED.
PROVIDE ALL REQUIRED CUTTING AND PATCHING.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO MATCH THE ADJACENT SURFACES BEHIND ALL
SURFACE MOUNTED EQUIPMENT.
9. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING SERVICE TO EQUIPMENT.
10. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD OBSERVATION. REPORT ANY DISCREPANCIES TO
ENGINEER FOR CLARIFICATION.
11. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIRMENTS:
11.1. STRAP DISTANCE: 5 FEET.
11.2. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.
11.3. FITTINGS: COMPRESSION.
11.4. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.
12. ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
12.1. STRAP DISTANCE: 3 FEET.
12.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
12.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.
12.4. FITTINGS: COMPRESSION.
12.5. BELL BOXES: FS TYPE.
12.6. NO KNOCKOUTS.
12.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES
13. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE CEILINGS IS ACCEPTABLE. REFER TO TC
DRAWINGS FOR SUPPORT DETAILS.
14. CONDUITS SHALL BE INSTALLED STRAIGHT AND LEVEL AND SHALL BE PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.
15. CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.
16. ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED CONDUIT FOLLOWING NOTES 11 AND 12
ABOVE.
17. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.
18. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE EPC-40-PVC
19. ANY ELECTRICAL OUTAGE SHALL NOT LAST OVER 2-HOURS. FOR OUTAGES OVER PORTABLE GENERATORS SHALL BE USED TO
REPLACE ANY ELECTRICAL SERVICE EXCEEDING THIS TIME PERIOD.
E-1.0
JFS
MMG
SYMBOLS, NOTES,
ABBREVIATIONS, AND
SCHEDULES
472/22426.CTS
file no.
checked by drawn by consultant issue date sheet no.
index no.
contract order no.
472STFMAINTPROJ
consultant job no.
23140.00 sheet title
M a tr ix
Y23249
ISSUED FOR BIDS 01-19-24
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
PNL KB
208/120
EX FAN
CONTROLS
EX FAN
GRILL
AC
PNL KB
208/120
AC
MINI SPLIT
FACP
GRILL
TC
EX FAN
CONTROLS
EX FAN
TC
FACP
MINI SPLIT
112 2
PNL KB
208/120
EX FAN
CONTROLS
EX FAN
GRILL
AC
PNL KB
208/120
AC
MINI SPLIT
FACP
GRILL
TC
EX FAN
CONTROLS
EX FAN
TC
FACP
MINI SPLIT
RELOCATED
RECEPTACLE 1RELOCATED
RECEPTACLE1
GENERAL ELECTRICAL NOTES
1. ALL DEVICES EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
DISCONNECT & REMOVE EXISTING DEVICE. EXTEND ASSOCIATED CONDUIT &
WIRE AS REQUIRED.
CONTRACTOR TO RELOCATE EXISTING CONDENSATE PUMPS, PIPING, AND
ALL ASSOCIATED ACCESSORIES CLOSER TO THE EXISTING CEILING AS
REQUIRED TO INSTALL NEW DOORWAYS IN LOCATION SHOWN.
DEMOLITION NOTES
ELECTRICAL KEY NOTES
CONTRACTOR SHALL EXTEND EXISTING CONDUIT AS REQUIRED
TO RELOCATE EXISTING RECEPTACLE INCLUDING BUT NOT
LIMITED TO JUNCTION BOX, DEVICE, AND COVER PLATE.
CONTRACTOR SHALL RELOCATE EXISTING CONDENSATE PUMPS,
PIPING, AND ALL ASSOCIATED ACCESSORIES CLOSER TO THE
EXISTING CEILING AS REQUIRED TO INSTALL NEW DOORWAYS IN
LOCATION SHOWN.
GENERAL ELECTRICAL NOTES
1. ALL DEVICES AND LIGHT FIXTURES EXISTING TO REMAIN.
E-3.0
JFS
MMG
HOUSING UNIT
J + K
472/22426.CTS
file no.
checked by drawn by consultant issue date sheet no.
index no.
contract order no.
472STFMAINTPROJ
consultant job no.
23140.00 sheet title
M a tr ix
Y23249
ISSUED FOR BIDS 01-19-24
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
SCALE: 1/4" = 1'-0"
0 1 5 10
N HOUSING UNIT J + K - POWER - NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
N HOUSING UNIT J + K - LIGHTING - NEW
SCALE: 1/4" = 1'-0"
N HOUSING UNIT J + K - LIGHTING AND POWER - DEMO
208/120
EX FAN
GRILL
MINI SPLIT
EX FAN
CONTROLS PNL KB
208/120
EX FAN
CONTROLS
FACP
EX FAN
GRILL
MINI SPLIT
AC
TCTC
FACP
AC
12 2
PNL KB
208/120
EX FAN
GRILL
MINI SPLIT
EX FAN
CONTROLS PNL KB
208/120
EX FAN
CONTROLS
FACP
EX FAN
GRILL
MINI SPLIT
AC
TCTC
FACP
AC
RELOCATED
RECEPTACLE 1RELOCATED
RECEPTACLE1
GENERAL ELECTRICAL NOTES
1. ALL DEVICES EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
DISCONNECT & REMOVE EXISTING DEVICE. EXTEND ASSOCIATED CONDUIT &
WIRE AS REQUIRED.
CONTRACTOR TO RELOCATE EXISTING CONDENSATE PUMPS, PIPING, AND
ALL ASSOCIATED ACCESSORIES CLOSER TO THE EXISTING CEILING AS
REQUIRED TO INSTALL NEW DOORWAYS IN LOCATION SHOWN.
DEMOLITION NOTES
ELECTRICAL KEY NOTES
CONTRACTOR SHALL EXTEND EXISTING CONDUIT AS REQUIRED
TO RELOCATE EXISTING RECEPTACLE INCLUDING BUT NOT
LIMITED TO JUNCTION BOX, DEVICE, AND COVER PLATE.
CONTRACTOR SHALL RELOCATE EXISTING CONDENSATE PUMPS,
PIPING, AND ALL ASSOCIATED ACCESSORIES CLOSER TO THE
EXISTING CEILING AS REQUIRED TO INSTALL NEW DOORWAYS IN
GENERAL ELECTRICAL NOTES
1. ALL DEVICES AND LIGHT FIXTURES EXISTING TO REMAIN.
E-3.1
JFS
MMG
HOUSING UNIT
L + M
472/22426.CTS
file no.
checked by drawn by consultant issue date sheet no.
index no.
contract order no.
472STFMAINTPROJ
consultant job no.
23140.00 sheet title
M a tr ix
Y23249
ISSUED FOR BIDS 01-19-24
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
SCALE: 1/4" = 1'-0"
0 1 5 10
N HOUSING UNIT L + M - POWER - NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
N HOUSING UNIT L + M - LIGHTING - NEW
SCALE: 1/4" = 1'-0"
N HOUSING UNIT L + M - LIGHTING AND POWER - DEMO
208/120 PNL KB
208/120
EX FAN
CONTROLS
FACPFACP
EX FAN EX FAN
GRILL
GRILL
MINI SPLIT MINI SPLIT
EX FAN
CONTROLS
TC
1 1
TC
2 2
PNL KB
208/120 PNL KB
208/120
EX FAN
CONTROLS
FACPFACP
EX FAN EX FAN
GRILL
GRILL
MINI SPLIT MINI SPLIT
EX FAN
CONTROLS
TC TC
RELOCATED
RECEPTACLE 1RELOCATED
RECEPTACLE1
GENERAL ELECTRICAL NOTES
1. ALL DEVICES EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
DISCONNECT & REMOVE EXISTING DEVICE. EXTEND ASSOCIATED CONDUIT &
WIRE AS REQUIRED.
CONTRACTOR TO RELOCATE EXISTING CONDENSATE PUMPS, PIPING, AND
ALL ASSOCIATED ACCESSORIES CLOSER TO THE EXISTING CEILING AS
REQUIRED TO INSTALL NEW DOORWAYS IN LOCATION SHOWN.
DEMOLITION NOTES
ELECTRICAL KEY NOTES
CONTRACTOR SHALL EXTEND EXISTING CONDUIT AS REQUIRED
TO RELOCATE EXISTING RECEPTACLE INCLUDING BUT NOT
LIMITED TO JUNCTION BOX, DEVICE, AND COVER PLATE.
CONTRACTOR SHALL RELOCATE EXISTING CONDENSATE PUMPS,
PIPING, AND ALL ASSOCIATED ACCESSORIES CLOSER TO THE
EXISTING CEILING AS REQUIRED TO INSTALL NEW DOORWAYS IN
GENERAL ELECTRICAL NOTES
1. ALL DEVICES AND LIGHT FIXTURES EXISTING TO REMAIN.
E-3.2
JFS
MMG
HOUSING UNIT
N + P
472/22426.CTS
file no.
checked by drawn by consultant issue date sheet no.
index no.
contract order no.
472STFMAINTPROJ
consultant job no.
23140.00 sheet title
M a tr ix
Y23249
ISSUED FOR BIDS 01-19-24
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
SCALE: 1/4" = 1'-0"
0 1 5 10
N HOUSING UNIT N + P - POWER - NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
N HOUSING UNIT N + P - LIGHTING - NEW
SCALE: 1/4" = 1'-0"
N HOUSING UNIT N + P - LIGHTING AND POWER - DEMO
| Sheets and Views |
| E1.0-2314000-30x42 |
| 472_22426 - CTS Mechanical Drawings.pdf |
| Sheets and Views |
| M1.0-2314000-M-1.0 |
| M4.0-2314000-M-4.0 |
File details come from the government source that posted it. Updated .