451524-1-38-01_07_MECHANICAL_S&S_.pdf

PDF 7 MB Posted

Attached to
LAP - Regional Traffic Management Center Facility Construction Federal Funded Project FPID: D324-034B
Solicitation number
PD 24-25.086
Issued by
Escambia County, Florida

About this file

This file contains the mechanical system design and specifications for the Florida-Alabama Transportation Planning Organization (FL-AL TPO) Regional Traffic Management Center facility construction project in Escambia County, Florida. The documents are comprehensive mechanical engineering drawings prepared by WGI, Inc., detailing the Heating, Ventilation, and Air Conditioning (HVAC) systems for a new 19,940 square foot transportation management center located at 6575 North W Street in Pensacola. The technical drawings include detailed schematics for air handling units, chillers, variable air volume terminal boxes, ductwork, piping, control sequences, and equipment schedules covering multiple building zones such as offices, conference rooms, mechanical spaces, and support areas.

The mechanical system design incorporates energy-efficient components including two air-cooled chillers (CH1 and CH2) with a total cooling capacity of approximately 77 tons, a primary air handling unit (AH1) with an energy recovery wheel and total supply air volume of 21,825 CFM, and multiple variable air volume (VAV) terminal units serving different building zones. The system is designed to meet the Florida Building Code 8th Edition requirements, with specific attention to mechanical, electrical, and energy conservation standards. The control systems feature sophisticated building automation capabilities, including demand-controlled ventilation, CO2 monitoring, temperature and humidity management, and comprehensive digital control sequences for optimizing system performance and energy efficiency.

View the file

Other files

File Type Posted
LAP_-_Regional_Traffic_Management_Center_Facility_Construction_Federal_Funded_Project_FPID:_D324-034B.pdf PDF
FDOT_Form_575-060-13_v001_Non_Collusion.pdf PDF
Agreement.ModifiedA_LAPwith_FPID_no_pg_num.pdf PDF
Agreement.ModifiedA_LAPwith_FPID.docx DOCX document
451524-1-38-01_10_TELECOMMUNICATIONS_S&S_.pdf PDF
451524-1-38-01_00_ARCHITECTURE_S&S.pdf PDF
Trench_Safety_Act_(1)_(1).pdf PDF
451524-1-38-01_11_SECURITY_S&S.pdf PDF
2025DavidBaconWages.pdf PDF
U_-_Cert_Debarment_Susupension_Ineligibilty_w37503032_v001_(1)_(1).pdf PDF
LAP_Cert_of_Capacity_w52501046_v001_(1).pdf PDF
451524-1-38-01_04_STUCTURAL_S&S_.pdf PDF
451524-1-38-01_02_CIVIL_S&S_.pdf PDF
451524-1-38-01_03_LANDSCAPE_S&S_.pdf PDF
451524-1-38-01_08___ELECTRICAL_S&S.pdf PDF
Technical_Specifications_April_1_2025.pdf PDF
American_with_Disabilities_Act_Affidavit_(2).pdf PDF
DBE_Bid_Pkg_Info_w27503011_(1).pdf PDF
Federal_Contract_Provisions_(CFR_200)_With_Sign_11-1-2024_(5)_(1).pdf PDF
Cert_Disclosure_of_Lobbying_Activities_w37503033_(2).pdf PDF
451524-1-38-01_09_ITS_S&S.pdf PDF
451524-1-38-01_05_FIRE_PROTECTION_S&S_.pdf PDF
451524-1-38-01_06_PLUMBING_S&S_.pdf PDF
451524-1-38-01_01__GEOTECHNICAL_S&S.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL MECHANICAL NOTES

1. ALL MECHANICAL WORK SHALL MEET ALL OF THE REQUIREMENTS OF THE FOLLOWING:

A. FLORIDA BUILDING CODE (FBC) 8TH EDITION (2023) (EFFECTIVE DECEMBER 31, 2023): THIS CODE INCLUDES THE 2023 FBC BUILDING, MECHANICAL, PLUMBING, ENERGY CONSERVATION, FUEL GAS, ACCESSIBILITY, AND TEST PROTOCOLS VOLUMES. FURTHER, SEE "REFERENCED STANDARDS" IN THE FBC BUILDING CHAPTER 35;

FBC MECHANICAL CHAPTER 15; FBC PLUMBING CHAPTER 15; FBC ENERGY CONSERVATION CHAPTER 6; AND

FBC FUEL GAS CHAPTER 8).

B. 8TH EDITION OF THE FLORIDA FIRE PREVENTION CODE (FFPC): THIS CODE ALSO INCLUDES THE FLORIDA

VERSIONS OF NFPA 1 AND NFPA 101. (EFFECTIVE DECEMBER 31, 2023).

C. 2020 NATIONAL ELECTRIC CODE.

D. STATE OF FLORIDA, DEPARTMENT OF ENVIRONMENTAL REGULATION RULES.

E. FDOT BUILDING FACILITIES DESIGN MANUAL 625-202-016-F – REVISED MAY 2020.

2. VERIFY, BY VISITING THE SITE, THE LOCATION OF UTILITIES IN ALL AREAS BEFORE COMMENCING WORK.

3. COORDINATE ALL WORK WITH OTHER AFFECTED TRADES. THE MECHANICAL CONTRACTOR SHALL FORWARD TO THE ELECTRICAL CONTRACTOR AN APPROVED COPY OF ALL EQUIPMENT SHOP DRAWINGS FOR ELECTRICAL

POWER/CONTROL INTERFACE.

4. COVER ALL ELECTRICAL AND MECHANICAL EQUIPMENT TO PROTECT THEM FROM DUST AND DAMAGE DURING CONSTRUCTION. RESTORE ALL FACTORY PAINTED SURFACES TO NEW CONDITION, REPAIR ALL SCRATCHES, DENTS AND ABRASIONS. THOROUGHLY CLEAN ALL SURFACES OF DUST DEBRIS, AND FOREIGN MATTER. THE EQUIPMENT, WHEN TURNED OVER TO THE OWNER, SHALL BE CLEAN AND FREE OF DEFECTS.

5. THE CONDENSATE DRAIN LINE SHALL HAVE A TRAP AT THE AIR HANDLING UNIT. TRAP SHALL BE FULL SIZE OF UNIT CONNECTION AND SHALL BE AS DETAILED. PROVIDE CLEAN OUTS IN ALL CHANGES OF DIRECTION. MINIMUM PITCH 1/8" PER FOOT. CONDENSATE DRAIN LINE SHALL RUN TO A FLOOR DRAIN. INSULATE ALL INTERIOR CONDENSATE PIPING WITH FLEXIBLE UNICELLULAR FOAM (ARMAFLEX OR EQUIVALENT) INSULATION TO PREVENT SWEATING. CONDENSATE DRAIN LINES AND TRAPS IN MECHANICAL ROOMS SHALL BE INSULATED COPPER AND

SHALL BE RIGIDLY SUPPORTED.

6. FLEXIBLE UNICELLULAR FOAM (ARMAFLEX OR EQUIVALENT) INSULATION SHALL BE 25/50 FLAME SPREAD/SMOKE DEVELOPED. REFRIGERANT PIPING SHALL BE INSULATED WITH FLEXIBLE UNICELLULAR FOAM INSULATION COMPLYING WITH ASTM C534, TYPE 1. PROVIDE ALUMINUM CLADDING FOR ALL INSULATION EXPOSED TO THE SUN

AND WEATHER.

7. REFRIGERANT LINES SHALL BE SIZED AND REFRIGERANT SPECIALTIES SHALL BE PROVIDED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS FOR STATIC LIFTS AND TOTAL LENGTHS REQUIRED. INSTALL IN

ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

8. AIR HANDLING UNITS SHALL HAVE AN AUXILIARY DRAIN PAN 3" LARGER THAN UNIT EACH WAY. DRAIN PAN SHALL HAVE A FLOAT SWITCH TO DE-ENERGIZE THE AHU IN EVENT OF A CONDENSATE OVERFLOW CONDITION.

9. AIR HANDLING UNITS SHALL BE PLACED ON A 1/4" NEOPRENE PAD WITHIN THE AUXILIARY DRAIN PAN.

10. AIR HANDLING UNITS SHALL BE PLACED A MINIMUM OF 30" AWAY FROM WALLS.

11. HOUSEKEEPING PADS SHALL BE A MINIMUM OF 4" HIGH AND SHALL EXTEND AT LEAST 6" BEYOND THE EQUIPMENT IT SUPPORTS. AIR HANDLER AND CHILLER PADS SHALL BE A MINIMUM OF 6" THICK, AND PUMP PADS SHALL BE A

MINIMUM OF 8" THICK. ALL HOUSEKEEPING PADS SHALL HAVE 3/4" CHAMFERED EDGES.

12. IN GENERAL, PLANS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED.

13. ALL DUCTWORK SHALL MEET THE STANDARDS SET FORTH BY THE LATEST EDITION OF SMACNA "HVAC DUCT CONSTRUCTION STANDARDS". SUPPLY, RETURN, AND EXHAUST DUCTWORK SHALL BE FABRICATED FROM SHEET METAL. ALL ROUND DUCT SHALL BE SHEET METAL UNLESS OTHERWISE NOTED. PROVIDE TURNING VANES IN ALL

90° DUCT ELBOWS.

14. SUPPLY AIR DUCT FULL SIZE OF UNIT DISCHARGE. TRANSITION TO SIZE INDICATED ON DRAWINGS. RETURN AIR DUCT IS TO TRANSITION FROM SIZE INDICATED ON DRAWINGS TO FULL SIZE OF UNIT INLET.

15. ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS (FREE AREA).

16. VERIFY ALL CLEARANCES AND DIMENSIONS BEFORE FABRICATION OF DUCTWORK AND PROVIDE ADDITIONAL OFFSETS TO MEET FIELD CONDITIONS. ADJUST LOCATIONS OF ALL EQUIPMENT AND DUCTWORK, AS NECESSARY TO

AVOID INTERFERENCES WITH STRUCTURAL AND OTHER BUILDING COMPONENTS.

17. UNLESS NOTED OTHERWISE, INSTALL DUCTWORK AS HIGH AS POSSIBLE, TIGHT TO UNDERSIDE OF STRUCTURE.

COORDINATE DUCT ELEVATION WITH RAIN LEADERS, WATER PIPING, DRAINS, AND MAJOR ELECTRICAL CONDUITS AND LIGHTS. PROVIDE OFFSETS AND TRANSITIONS AS REQUIRED TO KEEP DUCTWORK TIGHT TO THE STRUCTURE AND MAINTAIN CEILING ELEVATIONS AS INDICATED IN THE ARCHITECTURAL DRAWINGS. DUCTWORK MAY BE FLATTENED TO A 4:1 HEIGHT RATIO MAINTAINING THE DUCT FREE AREA SIZE AS INDICATED IN THE DRAWINGS.

DUCTWORK SHAPE MAY HAVE TO BE ADJUSTED (I.E. ROUND TO RECTANGULAR) AS SPACE DICTATES. MULTIPLE SMALLER RUNS MAY BE REQUIRED IN PLACE OF A SINGLE RUN. DUCT RECONFIGURATION SHALL BE INDICATED IN THE DUCT FABRICATION DRAWINGS AND FIELD VERIFIED PRIOR TO SUBMITTAL FOR ENGINEER'S REVIEW.

(SEE AM-002 FOR CONTINUATION)

DESIGN CRITERIA

PENSACOLA, FL

Space Setpoint - cooling

Space Setpoint - humidity

Space Setpoint - heating

DESIGN TEMPERATURES:

Ambient Winter Design Dry Bulb:

Ambient Summer Design Wet Bulb:

Ambient Summer Design Dry Bulb:

Barometric Pressure:

Elevation:

Longitude:

Location (Weather Data):

Latitude:

75°F

55% RH (±5%)

68°F

30 ft.

29.9 in. Hg

28°F

78°F

93°F

87.3°

30.4°

NOTE: 75°F SPACE SETPOINT FOR COOLING IS THE

MINIMUM ALLOWED AND 72°F IS THE MAXIMUM FOR

HEATING PER FBC ENERGY CONSERVATION SECTION

C302.1.

County:

Climate Zone:

ESCAMBIA

2A

UC

HVAC LEGEND

EXPOSED DUCTWORK (PAINTED)

DOUBLE WALL STEEL DUCTWORK

FIRE DAMPER - REFER TO DETAIL

WALL MTD THERMOSTAT OR TEMPERATURE

SENSOR

BELLMOUTH "SPIN-IN" FITTING WITH

LOCKING QUADRANT DAMPER

VOLUME DAMPER

SIDEWALL GRILLE

SUPPLY AIR DUCT (UP & DOWN)

RETURN AIR DUCT (UP & DOWN)

EXHAUST AIR DUCT (UP & DOWN)

DUCT MOUNTED SMOKE DETECTOR

BOTTOM OF SIDEWALL GRILLE ELEVATION

TOP OF SIDEWALL GRILLE ELEVATION

AIR DEVICE MARK. TOP LINE INDICATES

TYPE, REFER TO SCHEDULE. SECOND

LINE INDICATES AIR QUANTITY CFM.

THIRD LINE INDICATES NECK SIZE AND

DUCT CONNECTION SIZE.

UNDERCUT DOOR BY 3/4" AFF UNLESS

OTHERWISE INDICATED COORDINATE WITH

ARCHITECTURAL DRAWINGS.

BOG

TOG

CD1

12x12/8"∅

FLEX DUCT

DOWN

VD

UP

DOWN

DOWN

UP

UP

IJS DUCT IS LOCATED BETWEEN JOIST OR

THROUGH JOIST WEB.

BACKDRAFT DAMPER EQUIVALENT TO RUSKIN

BD2A1. DAMPER SHALL START TO OPEN AT

0.03" W.G. PRESSURE

ELEVATION

CO2 SENSOR

MOTORIZED DAMPER (24 VOLT UNLESS NOTED

OTHERWISE)

OPPOSED BLADE MOTORIZED DAMPER (24 VOLT

UNLESS NOTED OTHERWISE)

CO2

M

SD

T

VD

M

B

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T H

IS

S

E E T

E

E L E C T R O N

IC

F

IL

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

IN

G

C O D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

Y

A

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :5 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-001HVAC DESIGN CRITERIA, LEGEND,

AND GENERAL NOTES

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

MECHANICAL DRAWING INDEX

SHEET

NUMBER

SHEET NAME

AM-001 HVAC DESIGN CRITERIA, LEGEND, AND GENERAL NOTES

AM-002 HVAC GENERAL NOTES (CONTINUED)

AM-003 HVAC BUILDING AIR BALANCE AND VENILATION TABULATION

AM-100 HVAC SITE PLAN

AM-101 OVERALL HVAC PLAN

AM-111 HVAC PLAN QUAD A

AM-112 HVAC PLAN QUAD B

AM-113 HVAC PLAN QUAD C

AM-114 HVAC PLAN QUAD D

AM-401 ENLARGED HVAC PLANS

AM-402 ENLARGED HVAC PLANS

AM-501 HVAC DETAILS

AM-502 HVAC DETAILS

AM-503 HVAC DETAILS

AM-601 HVAC SCHEDULES

AM-602 HVAC SCHEDULES

AM-603 HVAC SCHEDULES

AM-604 HVAC SCHEDULES

AM-605 HVAC SCHEDULES

AM-606 HVAC SCHEDULES

AM-701 HVAC CONTROLS - CHILLED WATER PLANT SEQUENCES

AM-702 HVAC CONTROLS - CHILLED WATER PLANT SCHEMATIC

AM-703 HVAC CONTROLS - AIRSIDE SEQUENCES

AM-704 HVAC CONTROLS - AIRSIDE FLOW SCHEMATIC

AM-705 HVAC CONTROLS - POINT SCHEDULE

SHEETS: 25

No. Date Issue / Revision

36. ALL EXTERIOR FASTENERS, ANCHORS, SUPPORTS, AND MOUNTING HARDWARE SHALL BE HOT DIPPED GALVANIZED

OR STAINLESS STEEL.

37. PROVIDE COMMISSIONING SERVICES THROUGH A REGISTERED DESIGN PROFESSIONAL OR APPROVED AGENCY IN ACCORDANCE WITH THE PROVISIONS OF FLORIDA BUILDING CODE/ ENERGY CONSERVATION SECTION C408 ON BUILDINGS WITH TOTAL MECHANICAL EQUIPMENT CAPACITY GREATER THAN 480,000 BTUH (40 TONS). THE SECTION STATES THAT PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, EVIDENCE OF THE MECHANICAL SYSTEM'S COMMISSIONING AND COMPLETION SHALL BE PROVIDED. COPIES OF COMMISSIONING DOCUMENT SHALL BE GIVEN

TO THE OWNER AND MADE AVAILABLE TO THE CODE OFFICIAL UPON REQUEST.

38. PRIOR TO SUBSTANTIAL COMPLETION, A COMPLETE CERTIFIED TEST AND BALANCE REPORT SHALL BE SUBMITTED

TO THE ENGINEER FOR REVIEW. REFER TO THE SPECIFICATIONS FOR REQUIREMENTS.

39. DUCTS SHOWN PENETRATING SMOKE PARTITIONS SHALL BE SEALED AIR TIGHT BETWEEN THE DUCT OR ITS

INSULATION AND THE WALL IT PENETRATES.

40. ALL THERMOSTAT/WALL SENSORS SHALL BE LABELED WITH THE UNIT MARK OF THE ITEM BEING CONTROLLED.

41. ALL EQUIPMENT, PIPING, DUCTWORK, ETC. SHALL HAVE VIBRATION ISOLATION. ALL MECHANICAL SYSTEM COMPONENTS SHALL BE INSTALLED IN A VIBRATION FREE MANNER. ALL DUCT AND PIPES WILL HAVE FLEX

CONNECTORS INSTALLED.

42. PIPE INSULATION AND VAPOR BARRIERS SHALL BE INSTALLED CONTINUOUS THROUGH HANGERS.

43. ALL DUCT AND PIPE PENETRATIONS THROUGH ANY WALL, REGARDLESS OF FIRE RATING, SHALL BE SEALED

AIRTIGHT.

44. ALL EXPOSED CONTROL WIRING IN MECHANICAL AND ELECTRICAL ROOMS SHALL BE INSTALLED IN CONDUIT. ALL CONTROL WIRING SHALL BE PLENUM RATED CABLE. CONDUITS SHALL CONFORM TO ALL REQUIREMENTS FOR

DIVISION 26 CONDUITS. REFER TO DIVISION 26 SPECIFICATIONS AND DRAWINGS.

45. SEE TSP FOR ADDITIONAL REQUIREMENTS.

GENERAL MECHANICAL NOTES (CONTINUED FROM AM-001)

18. DUCTWORK, DIFFUSERS, REGISTERS, GRILLES, AND OTHER ITEMS OF THE AIR HANDLING SYSTEM SHALL NOT BE

SUPPORTED BY THE CEILING OR CEILING SUSPENSION SYSTEM.

19. ALL SUPPLY DUCTWORK BETWEEN THE DISCHARGE OF THE PRIMARY AIR HANDLER AND THE INLETS TO THE VAV BOXES SHALL BE 3" W.G. PRESSURE CLASS. ALL OTHER DUCTWORK SHALL BE 1" W.G. ALL SHEET METAL DUCTWORK

SHALL HAVE A CLASS C SEAL.

20. PROVIDE SUPPLEMENTARY STEEL AS REQUIRED TO INSTALL MECHANICAL EQUIPMENT AND MATERIALS.

21. PROVIDE ADDITIONAL VOLUME DAMPERS AS REQUIRED BY THE TEST AND BALANCE CONTRACTOR TO ACHIEVE AIRFLOWS INDICATED ON THE DRAWINGS. MAINTAIN NEGATIVE PRESSURE IN ALL DESIGNATED CONSTRUCTION

AREAS.

22. IN ADDITION TO THE REQUIREMENTS OF THE SPECIFICATIONS, THE AIR HANDLERS MAY ONLY BE STARTED IF

THE FOLLOWING CONDITIONS ARE MET:

A. ALL OPENINGS FROM THE CONDITIONED SPACE DIRECTLY TO THE OUTSIDE MUST BE CLOSED. TEMPORARY CLOSURE METHODS MAY BE USED SUCH AS THE UTILIZATION OF PLASTIC SHEETS AND DUCT TAPE.

B. MOP CLEAN ALL CONSTRUCTION DEBRIS AND DUST FROM THE FLOOR. PROVIDE DOOR MATS AT ALL

ENTRANCES INTO THE BUILDING.

C. TEMPORARY BARRIERS ARE TO BE PROVIDED AROUND AREAS THAT WILL HAVE ANY CONCRETE GRINDING OPERATION, DRYWALL WORK, PAINTING OR ANY OTHER PARTICULATE PRODUCING PROCESSES. ALL AIR DISTRIBUTION DEVICES IN THESE AREAS OF CONTAINMENT ARE TO BE COVERED AND SEALED AIR TIGHT.

D. ALL RETURN GRILLES SHALL HAVE MERV-8 FILTER MEDIA TAPED OVER THEM PRIOR TO AIR HANDLER STARTUP AND SHALL REMAIN IN PLACE UNTIL ALL DUST PRODUCING OPERATIONS HAVE BEEN COMPLETED

AND PRIOR TO TEST AND BALANCE. CLEAN ALL TAPE RESIDUE FROM THE GRILLES.

E. ONCE THE UNIT IS STARTED, FILTERS IN THE AIR HANDLERS ARE TO BE SHAKEN CLEAN DAILY.

23. ALL REQUIRED FIRE DAMPERS MAY NOT BE INDICATED HEREIN. PROVIDE FIRE DAMPERS AS REQUIRED AT RATED WALLS AND FLOORS PER FLORIDA BUILDING - MECHANICAL CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

RATED PARTITION LOCATIONS.

24. OMIT INSULATION ON TRANSFER DUCT SYSTEM. TRANSFER DUCT SYSTEMS ARE CONNECTED TO "XG#" TYPE AIR

DISTRIBUTION DEVICES.

25. RUST COAT ALL CHILLED WATER PIPING AND FITTINGS PER SPECIFICATION (SPECIFICALLY SMALL FITTINGS)

INSTALL AIR BLEED IN APPROPRIATE LOCATIONS.

26. SUBMIT DUCT FABRICATION DRAWINGS AND MECHANICAL ROOM LAYOUTS PER SPECIFICATIONS PRIOR TO ANY FRAMING WORK. ALL CHASE SIZES, FLOOR DRAINS IN MECHANICAL ROOMS/CLOSETS, AND ELECTRICAL PANEL

LOCATIONS SHALL BE FIELD VERIFIED, COORDINATED, AND INDICATED IN THE SUBMITTAL.

27. ALL DUCT MOUNTED MANUAL BALANCING DAMPERS SHALL HAVE A TWO FOOT LONG, YELLOW STRIP OF MATERIAL

ATTACHED TO THE DAMPER HANDLE FOR EASY VISUAL IDENTIFICATION.

28. ALL FIRE STOPPING SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S U.L. DETAILS OF THE PRODUCTS USED SPECIFICALLY ON THIS PROJECT. APPLICABLE U.L. DETAILS SHALL BE SUBMITTED FOR THE ENGINEER'S REVIEW AND A COPY SHALL BE AVAILABLE ON SITE FOR USE BY THE AUTHORITY HAVING

JURISDICTION.

29. CONCRETE SLAB/PAD IS TO HAVE NO CONTACT WITH ANY METAL PORTION OF THE EQUIPMENT OR THAT EQUIPMENT'S SUPPORT. PROVIDE 1/4" THICK RED, OR BLACK, RUBBER PAD UNDER THE ENTIRE METAL SURFACE

INTENDED TO REST ON THE CONCRETE PAD.

30. THE TEMPERATURE CONTROLS (INCLUDING GRAPHICS) SHALL BE IN OPERATION AND EXERCISED IN THE PRESENCE OF THE ENGINEER OF RECORD AT TIME OF SUBSTANTIAL COMPLETION. THE CONSTRUCTION MANAGER SHALL SCHEDULE A MEETING BETWEEN THE CONTROL'S CONTRACTOR AND THE ENGINEER ONE WEEK PRIOR. THIS

SHALL OCCUR PRIOR TO OWNER TRAINING.

31. PROVIDE DIELECTRIC UNIONS/PROTECTION AT ALL POINTS OF CONNECTION BETWEEN DISSIMILAR METALS; PIPE, PIPE HANGERS, CONNECTIONS TO STRUCTURAL STEEL, ETC.

32. ROUND FLEX DUCT SHALL BE A MAXIMUM LENGTH OF 6 FEET. ALL RUNS OF FLEX DUCT ARE TO BE SUPPORTED

WITH THE APPROPRIATE HANGERS. FLEX DUCT SHALL NOT SAG OR BE CRIMPED.

33. AIR CONDITIONING FILTERS ARE TO BE PROVIDED AND CHANGED BY THE CONTRACTOR UP TO AND ON THE DATE OF FINAL COMPLETION ACCEPTANCE. FROM THAT TIME ON, THE OWNER WILL RETAIN ALL RESPONSIBILITY FOR FILTER MAINTENANCE. FILTERS SHALL BE CLEAN AT THE TIME OF SUBSTANTIAL COMPLETION.

34. VAV TERMINAL BOXES SHALL BE MOUNTED WITH THE BOTTOM AT 8" ABOVE THE CEILING. THE CONTROL PANEL AND THE HEATER SERVICE PANEL SHALL BE UNOBSTRUCTED AS REQUIRED BY NEC AND AS RECOMMENDED BY THE TERMINAL MANUFACTURER. VAV BOXES ARE TO BE INSTALLED WITH A 4 FT. LONG STRAIGHT SECTION OF ROUND DUCT AT THE INLET AND SHALL BE THE SAME SIZE AS THE BOX CONNECTION. ALL DUCTWORK BETWEEN

THE VAV INLET AND THE AIR HANDLER IS TO BE RIGID (NO FLEX).

35. LOCATE ALL AIR DISTRIBUTION DEVICES AND CEILING MOUNTED EQUIPMENT IN CONFORMANCE WITH THE REFLECTED CEILING PLANS INCLUDED IN THE ARCHITECTURAL DRAWINGS FOR THIS PROJECT. COORDINATE DUCTWORK TO ALLOW FOR LOCATIONS OF THESE ITEMS. PROVIDE REVISED DUCTWORK LAYOUT WHERE REQUIRED.

ANY MECHANICAL ITEMS EXPOSED TO VIEW SHALL BE PLACED PER THE ARCHITECTURAL DRAWINGS.

DUCTWORK MATERIALS

1. ALL EXPOSED DUCTWORK SHALL HAVE A "PAINT GRIP" GALVANIZED STEEL FINISH AND SHALL

BE FIELD PAINTED. PAINTED AS DIRECTED BY THE ARCHITECT. COORDINATE COLOR WITH

ARCHITECT.

2. UNLESS NOTED OTHERWISE, ALL EXPOSED SUPPLY AND RETURN AIR DUCTWORK SHALL BE

DOUBLE WALL CONSTRUCTION WITH 1-1/2" (1.5 PCF DENSITY) INSULATION AND SOLID LINER.

EXPOSED DUCTWORK SHALL BE SEALED WITHIN THE LAP (MASTIC SHALL NOT BE VISIBLE).

3. FLEX DUCT SHALL BE EQUIVALENT TO FLEXMASTER 1M WITH A POLYETHYLENE FABRIC (PE) CORE AND SHALL HAVE PRESSURE RATINGS OF 10" W.G. POSITIVE, 5" W.G. NEGATIVE THROUGH

16" DIA., AND 1" W.G. NEGATIVE FOR 18" AND 20" DUCTS.

4. ALL TRANSFER DUCT SHALL BE UNINSULATED SHEET METAL DUCTWORK.

5. FLEXIBLE DUCT RUNOUTS SHALL NOT EXCEED 6 FEET.

6. THE USE OF SNAP LOCK DUCT IS NOT PERMITTED.

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :5 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-002

HVAC GENERAL NOTES (CONTINUED)

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

101 Office

102 Office

103 Office

104 Office

105 Exec Dir Office

106 File Sto

107 Media Rm

108 Auto Conf

109 Nexus Conf

111 Mail / Supplies

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Retail stores; Storage

Offices; Conference rooms

Offices; Conference rooms

Offices; Conference rooms

Retail stores; Storage

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0 x x x x x x x x x x

0.06

0.06

0.06

0.06

0.06

0.12

0.06

0.06

0.06

0.12

8.9

8.7

8.7

11.7

12.9

37.2

19.0

35.5

25.5

18.7

AH01

x x x x x x x x x x

OUTDOOR AIR VENTILATION RATES (based on FBC table 403.3.1.1)

FBC TABLE 403.3.1.1 CLASSIFICATIONDESCRIPTION OF AREA

OCC

DENSITY (#

/ 1000 SF)

PEOPLE OUTDOOR

AIRFLOW RATE IN

BREATHING ZONE

(CFM/PERSON)

x =

OCCUPANTS

EACH

PEOPLE

OA

AIRFLOW

(CFM)

AREA OUTDOOR

AIRFLOW RATE IN

BREATHING ZONE

(CFM / SF)

x

TOTAL

SF

AREA

OA

AIRFLOW

(CFM)

REQUIRED

OUTSIDE

AIR

(CFM)

113 Supplies / Tech

115.1 Immersive Space

115.2 Immersive Support

118 Digital Recpt

119 Vestibule

120 Open Off

120.2,3,4,5 CORR

121 Collab Office

122 Collab Office

123 Collab Office

124 Food Sto

125 Coffee bar

Retail stores; Storage

Offices; Office spaces

Offices; Office spaces

Offices; Reception areas

Public spaces; Corridors

Offices; Office spaces

Public spaces; Corridors

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Retail stores; Storage

Food & beverage service; Kitchens (cooking)

5.0

5.0

5.0

5.0

5.0

5.0

5.0

7.5 x x x x x x x x x x x x

0.12

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.12

0.12

1,808

5.2

14.2

6.1

3.4

46.0

108.5

38.3

5.2

5.2

5.2

10.4

34.6 x x x x x x x x x x x x

130 Corridor

132(1) TPO Board Rm

132(2) TPO Board Rm

134 Furniture Sto

135 Break Rm

137 Food Sto

138 Corridor

139 Media Coverage

140 Office

141 Office

142 Office

143 Office

144 Office

145 Office

146 Office

148(1) Control

148(2) Control

148(3) Control

148(4) Control

148(5) Control

Public spaces; Corridors

Offices; Conference rooms

Offices; Conference rooms

Public spaces; Corridors

Food & beverage service; Kitchens (cooking)

Retail stores; Storage

Public spaces; Corridors

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Offices; Office spaces

Offices; Telephone/data entry

Offices; Telephone/data entry

Offices; Telephone/data entry

Offices; Telephone/data entry

Offices; Telephone/data entry

5.0

5.0

7.5

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0

5.0 x x x x x x x x x x x x x x x x x x x x

0.06

0.06

0.06

0.06

0.12

0.12

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

0.06

1,059

1,059

19.3

63.5

63.5

31.6

47.3

7.3

6.9

12.1

9.2

8.8

8.8

9.0

8.9

9.2

8.8

39.1

31.6

33.2

29.1

19.1 x x x x x x x x x x x x x x x x x x x x

Required Outside Air:

Outside Air Provided:

2,855

2,980

BUILDING AIR BALANCE

CFM

NETCFMCFM SOURCE

EXHAUST AIR OUT OF BUILDINGOUTSIDE AIR INTO BUILDING

SOURCE

2,980 EF11 & EF12AH1 (AT MAXIMUM DEMAND LOAD VENTILATION)

ZONE PRESSURIZATION ((2,980 OA - 2,760 EXH) / 21,835 SA) x 100 = 1.01%

2,980

EXFILTRATION **

ERU RELIEF 1,740

2,760 220

1,300 EF11 & EF12AH1 (AT MINIMUM DEMAND LOAD VENTILATION)

ZONE PRESSURIZATION ((1,300 OA - 1,080 EXH) / 21,825 SA) x 100 = 1.01%

1,300

EXFILTRATION **

ERU RELIEF 60

1,080 220

** EXFILTRATION ASSUMED TO BE A MAXIMUM OF 0.05 CFM / SF FOR EXTERIOR WALL ENVELOPE.

HVAC LOAD CALCULATIONS

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :5 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-003HVAC BUILDING AIR BALANCE AND

VENILATION TABULATION

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

M

M

M

M

M

M

M

M

M

M

CU11

CU12

4"

4"

AM-401

CU2

CH1

CH2

BT1

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :0 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-100

HVAC SITE PLAN

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

HVAC SITE PLAN

10'0' 40'20'

MM

M

M M M

M

M

M

ELEC

FIRE

SUPPRESSION

CONTROL

ROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

MEDIA

COVERAGE

ROOM

MECHANICAL

BREAK

ROOM

FOOD

STORAGE

WOMEN

FURNITURE

STORAGE

FAMILY

RTMC

TRAINING/MEETING

ROOM

CORRIDOR

CU11

CHWP1

VAV30

VAV27

V A V

VAV19 VAV20

VAV21 VAV22

VAV25

VAV15

VAV16

VAV17

VAV18

VAV26

V A V

MECHANICAL

CU12

LV1

2,240

54Hx36W

BOT@10'-0"AFF

LV1

2,980

54Hx36W

BOT@10'-0"AFF

V A V

V A V

AM-402

TMC

STORAGE

VAV24

MS12MS11

4" CHWS&R TO

CHILLER YARD

1 2

CU2

NEXUS

CONFERENCE

RESTROOM

RESTROOM

DIGITAL

RECEPTION

FILE

STORAGE

MEDIA

ROOM

AUTO

COLLABORATION

DATA

VISUALIZATION

SPACE

115.1

DATA

VISUALIZATION

SUPPORT

115.2

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

COLLAB

OFFICE

COLLAB

OFFICE

COLLAB

OFFICE

BREAK

ROOM

FOOD

STORAGE

MEN

CHASE

FAMILY

CORRIDOR

VESTIBULE

CORRIDOR

133 CORRIDOR

EF12

EF11

CORRIDOR

120.3

V A V

VAV08

V A V

VAV09

V A V

V A V

V A V

VAV13

V A V

VAV11

VAV03

AS1

VAV07

VAV02

AM-402 2

AM-402

CH2

AH1

JANITORIAL

UTILITY

MAIL /

SUPPLIES

RESTROOM

CH1

BT1

ET1

CHWP2

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :1 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-101

OVERALL HVAC PLAN

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

4'0' 16'8'

HVAC PLAN

KEYNOTES

1 SECURE MINISPLIT OUTDOOR UNIT TO STAINLESS STEEL FLORIDA PRODUCT APPROVAL NOA HIGH VELOCITY WIND RATED WALL

BRACKET. BRACKET TO BE ANCHORED TO WALL WITH HOT DIPPED GALVANIZED OR STAINLESS STEEL ANCHORS. PROVIDE VINYL

LINE SET COVERS WHERE VISIBLE PER SCHEDULE.

2 ROUTE REFRIGERANT LINES THROUGH WALL AND SEAL WALL PENETRATION WEATHERTIGHT.

3 FABRICATE 10" DEEP PLENUM ON BACKSIDE OF LOUVER. ALL CORNERS OF PLENUM TO BE CONTINUOUSLY WELDED AND ENTIRE FABRICATION IS TO BE HOT DIPPED GALVANIZED. BOTTOM PANEL SHALL SLOPE 1" / FOOT BACK TO LOUVER SO COLLECTED WATER

DRAINS BACK INTO LOUVER. PROVIDE WEATHERPROOF SEAL AT LOUVER/PLENUM CONNECTION.

4 SECURE DUCTLESS AIR HANDLER TO WALL WITH TOP 10" BELOW CEILING. ROUTE REFRIGERANT LINES FROM MINI-SPLIT SYSTEM UNITS TO INSIDE FACE OF EXTERIOR WALL AND TURN DOWN TO 20" AFF AND THEN TURN THROUGH EXTERIOR WALL. SEAL WALL

PENETRATIONS WEATHER-TIGHT.

5 SUPPORT REFRIGERANT LINES FROM ABOVE. LINES SHALL BE SIZED AS DIRECTED BY THE MANUFACTURER'S REPRESENTATIVE.

REFER TO SCHEDULE AND SPECIFICATIONS.

VAV17

CD1

6x6/6"Ø

RR1

18x18

"ø

/1

AUTO

COLLABORATION

OFFICE

COLLAB

OFFICE

COLLAB

OFFICE

COLLAB

OFFICE

BREAK

ROOM

FOOD

STORAGE

VAV10

T

VAV02

T

T

VAV13a

VAV13c

T

VAV07

T

"ø

V A V

VAV13

CD1

8x8/8"Ø

RR1

8x8

CD1

6x6/6"Ø

CD1

6x6/6"Ø

CD1

6x6/6"Ø

10/88/84/8

VDVD

VD

"ø

"ø

/1

0VD

30"ø

"ø

10/10

VAV07

SR1

36x18 2,245

VD

VD

8"ø

8"ø

/8

LD1

LD1

CR1

12''

CR1

12''

CR1

12''

CR1

12''

350CR1

6''

65 CR1

6''

VAV02

10"ø

XG1

8x8

XG1

8x8

XG1

8x8

12/8 8/8

18/10

SR1

18x10

VD

10"ø

18"ø 16"ø

"ø

28/28

18"ø

VD

VD

VDVD

VD

VD

VD VD VD

Q U A D

A

Q U A D

B

QUAD A

QUAD D

CORRIDOR

120.1

VD

VD

T

CD1

6x6/6"Ø

VD

/8

/8

VAV13b

T

CO2

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :1 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-111

HVAC PLAN QUAD A

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

8'0' 16' 32'

HVAC PLAN QUAD A

KEYNOTES#

M

M

M

ELEC

FIRE

SUPPRESSION

UPS

MECHANICAL

BREAK

ROOM

FOOD

STORAGE

WOMEN

FURNITURE

STORAGE

FAMILY

CORRIDOR

SERVER/BENCH

TEST

CU11

CHWP1

T

T

T

T

VAV15

V A V

VAV30

VAV27

T VAV18

VAV30

VAV27

V A V

VAV25

VAV15

VAV17

VAV18

VAV26

MECHANICAL

CU12

"ø

"ø

SS2

22x10 1,020

8"ø

SS2

6x6

SS2

10x6

"ø

SR1

36x20 2,790

CD2

8x6

CD1

6x6/6"Ø

CD1

6x6/6"Ø

TV

A V

8EG1

8x8

EG1

8x8

EG1

6x6

EG1

6x6

EG1

6x6

SR1

12x12

/1

"ø2 /1

LV1

2,190

54Hx36W

BOT@10'-0"AFF

10/10

10/10

/1

/6

/6

VD

VD

LV1

2,980

54Hx36W

BOT@10'-0"AFF

28/28

VD

VD

/3

34/34

CD1

10x10/10"Ø

CD1

8x8/8"Ø

CD1

6x6/6"Ø

RR1

12x12

V A V

28/40

34/20

/2

"ø6 "ø

"ø

8"ø

"ø

SS1

6x6

SS2

22x12 1,480

TMC

STORAGE

VD

CD2

8x6

8/10

/1

40/28

92/26

VAV24

34/20

34/20

16"ø

SD

A F M

A F M

/2

/2

SR1

12x6

SR1

36x12 1,430

MS12MS11

4" CHWS&R TO

CHILLER YARD

1 2

MEN

CHASE

FAMILY

CORRIDOR

EF12

"ø

AS1

SD

VD

"ø

/1

/1

VD

VD VD

6/8

/1

/3

28/28

AM-402

AM-402

CHWP2

DDC

Q U A D

A

Q U A D

B

QUAD B

QUAD C

AM-401

AH1

CH1CH2

5' - 0"

9' - 5"

BT1

VD

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :1 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-112

HVAC PLAN QUAD B

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

8'0' 16' 32'

HVAC PLAN QUAD B

KEYNOTES

1 SECURE MINISPLIT OUTDOOR UNIT TO STAINLESS STEEL FLORIDA PRODUCT APPROVAL NOA HIGH VELOCITY WIND RATED WALL

BRACKET. BRACKET TO BE ANCHORED TO WALL WITH HOT DIPPED GALVANIZED OR STAINLESS STEEL ANCHORS. PROVIDE VINYL

LINE SET COVERS WHERE VISIBLE PER SCHEDULE.

2 ROUTE REFRIGERANT LINES THROUGH WALL AND SEAL WALL PENETRATION WEATHERTIGHT.

3 FABRICATE 10" DEEP PLENUM ON BACKSIDE OF LOUVER. ALL CORNERS OF PLENUM TO BE CONTINUOUSLY WELDED AND ENTIRE FABRICATION IS TO BE HOT DIPPED GALVANIZED. BOTTOM PANEL SHALL SLOPE 1" / FOOT BACK TO LOUVER SO COLLECTED WATER DRAINS BACK INTO LOUVER. PROVIDE WEATHERPROOF SEAL AT LOUVER/PLENUM CONNECTION.

4 SECURE DUCTLESS AIR HANDLER TO WALL WITH TOP 10" BELOW CEILING. ROUTE REFRIGERANT LINES FROM MINI-SPLIT SYSTEM UNITS TO INSIDE FACE OF EXTERIOR WALL AND TURN DOWN TO 20" AFF AND THEN TURN THROUGH EXTERIOR WALL. SEAL WALL

PENETRATIONS WEATHER-TIGHT.

5 SUPPORT REFRIGERANT LINES FROM ABOVE. LINES SHALL BE SIZED AS DIRECTED BY THE MANUFACTURER'S REPRESENTATIVE.

REFER TO SCHEDULE AND SPECIFICATIONS.

6 DRIP CONDENSATE ONTO 12" LONG CONCRETE SPLASH BLOCK.

7 MOTORIZED DAMPER INTERLOCKED TO FIRE SUPPRESSION PRE-ACTION SYSTEM.

CONTROL

ROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

145OFFICE

MEDIA

COVERAGE

ROOM

SERVER/BENCH

TEST

T

T

T

T

TTTTT

T

T

T

T

T

VAV24

V A V

VAV23

VAV22

VAV21cVAV21b

V A V a

V A V b

V A V a

VAV19

VAV16

V A V

VAV15

VAV17

VAV19

VAV20

VAV21

VAV22

VAV15

VAV16

VAV18

VAV26

V A V

CD1

6x6/6"Ø

CD1

10x10/10"Ø

RR1

12x12

RR1

10x10

RR1

10x10

CD1

8x8/8"Ø

CD1

10x10/10"Ø

RR1

10x10

CD1

10x10/10"Ø

RR1

10x10

RR1

10x10

CD1

8x8/8"Ø

RR1

10x10

CD1

8x8/8"Ø

RR1

8x8

CD1

8x8/8"Ø

CD1

10x10/10"Ø

CD1

16x16/14"Ø 1,075

CD1

16x16/14"Ø 1,075

SR1

36x18

RR1

18x18

RR1

18x18

RR1

18x18

RR1

18x18

/1

"ø

20/12

/1

/1

20/12 20/12

20/12

(4)LD1

(4)LD1

(1)LD1

(5)LD1

VD

6/10

12/10

"ø

VD

8/10

"ø

10"ø

6/10

10/12

12/12

V A V

VDVDVDVDVD

VDVD

24/14 22/12 18/12 16/12 14/12 12/10

60/30 36/36

/1

/1

/1

/1

/2

16"ø

/2

16/16 14/14

"ø

/2

16"ø

RR1

22x22 2,070

/3

SS2

10x6

SS2

10x6

SS2

10x6

SS2

10x6

VD

SS2

10x6

SS2

10x6

SS2

10x6

SS2

10x6

12/18

18/18

"ø

"ø

SS2

10x6

SS2

10x6

SS2

10x6

SS2

10x6

VD

SS2

10x6

SS2

10x6

SS2

10x6

SS2

10x6

"ø1 "ø

12/18

18/18

VD

VD VD VD VD VD VD

V D

V D

CD1

8x8/8"Ø

/2

28/20 42/20

/1

V

DSR1

36x20 2,605

(4)LD1

42/20

/2

36/36

MS12MS11

VDVDVDVDVDVDVDVD

VD

VD

VD

VD

VD

VD VD VDVD VD VD VD VD VDVD

CORRIDOR

CORRIDOR

V A V

T

"ø

VD

VD

SR1

36x20 2,605

VD

VD

VD

CR1

8''

/1

/1

/3

"ø

"ø

/2

42/20

/1

8"ø

/1

VD

VD

/1

30"ø

/1

RTMC

TRAINING/MEETING

ROOM

VD

QUAD B

QUAD C

VD

Q U A D

D

Q U A D

C

VD

CO2

CO2

CO2

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :2 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-113

HVAC PLAN QUAD C

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

8'0' 16' 32'

KEYNOTES

1 SECURE DUCTLESS AIR HANDLER TO WALL WITH TOP 10" BELOW CEILING. ROUTE REFRIGERANT LINES FROM MINI-SPLIT SYSTEM

UNITS TO INSIDE FACE OF EXTERIOR WALL AND TURN DOWN TO 20" AFF AND THEN TURN THROUGH EXTERIOR WALL. SEAL WALL

PENETRATIONS WEATHER-TIGHT.

2 SUPPORT REFRIGERANT LINES FROM ABOVE. LINES SHALL BE SIZED AS DIRECTED BY THE MANUFACTURER'S REPRESENTATIVE.

REFER TO SCHEDULE AND SPECIFICATIONS.

3 DRIP CONDENSATE ONTO 12" LONG CONCRETE SPLASH BLOCK.

4 MOTORIZED DAMPER INTERLOCKED TO FIRE SUPPRESSION PRE-ACTION SYSTEM.

HVAC PLAN QUAD C

M

M

M

T

VAV03

V A V

RR1

18x18

RR1

18x18

RR1

18x18

RR1

18x18

/1

/1

/1

36/36

VD

VD

CU2

NEXUS

CONFERENCE

RESTROOM

RESTROOM

DIGITAL

RECEPTION

FILE

STORAGE

MEDIA

ROOM

DATA

VISUALIZATION

SUPPORT

115.2

OFFICE

OFFICE

OFFICE

OFFICE

VESTIBULE

EF11

/6

CORRIDOR

120.3

T

V A V

T

VAV09

T

VAV08b T

VAV10

T

V A V

T

VAV06 T

VAV04

T

V A V

T

VAV08c T

VAV08a T

VAV11b T

V A V

T

VAV07

T

VAV08

V A V

VAV09

V A V

V A V

V A V

V A V

VAV11

VAV03

RR1

8x8

CD1

8x8/8"Ø

CD1

8x8/8"Ø

RR1

8x8

CD1

8x8/8"Ø

RR1

8x8

CD1

8x8/8"Ø

RR1

8x8

RR1

6x6

CD1

6x6/6"Ø

CD1

6x6/6"Ø

CD1

8x8/8"Ø

CD1

8x8/8"Ø

RR1

8x8

CD1

16x16/14"Ø

CD1

16x16/14"Ø

RR1

16x16

RR1

16x16

RR1

8x8

CD1

8x8/8"Ø

RR3

8x6

EG1

6x6

EG1

6x6

/1

/1

"ø

"ø

"ø

"ø

/1

/8

"ø

"ø

"ø

14"ø

/1

/1

VD

VD

VD

VDVD

VD

VD

VD

CD1

16x16/14"Ø

RR1

14x14

12"ø

"ø

"ø

10"ø

20"ø 22"ø

26"ø

"ø

/1

"ø

"ø

10/10

8/10

VD

VD

CD1

6x6/6"Ø

SR1

36x18 2,245

30/26

16/16

14/12

/1

/1

SR1

24x6

VD

VD

LD1

LD1

VD

8"ø 8"ø

10/10

VD

VD

VDVDVD

VD

VD

VD

VD

VD

SR1

22x6

30"ø

CR1

12''

CR1

12''

VD

VD

VD

CR1

6''

CR1

6''

CR1

6''

VAV02

10"ø

"ø

26"ø

VD VD

VD

VD

VDVD

VD

/1

30"ø

/1

DATA

VISUALIZATION

SPACE

115.1

QUAD A

QUAD D

"ø

/1

/1

/1

/6

6/6

ELEC.

MAIL /

SUPPLIES

MS2

T

V A V a

RESTROOM

SUPPLIES

/ TECH

JANITORIAL

UTILITY

EG1

6x6

EG1

6x6

VD

VD

VD

VD

CD1

6x6/6"Ø

VD

/6

VD

CD1

6x6/6"Ø

CD2

6x6

/1

VD

26/24

/8

/8

VD

/1

CD1

8x8/8"Ø

CD1

8x8/8"Ø

/1

Q U A D

D

Q U A D

C

VD

VD

LV1

12WX12H

24'-0"AFF

VD

VD

VD

VD

"ø

CO2

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :2 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-114

HVAC PLAN QUAD D

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

8'0' 16' 32'

HVAC PLAN QUAD D

KEYNOTES

1 FABRICATE 10" DEEP PLENUM ON BACKSIDE OF LOUVER. ALL CORNERS OF PLENUM TO BE CONTINUOUSLY WELDED AND ENTIRE

FABRICATION IS TO BE HOT DIPPED GALVANIZED. BOTTOM PANEL SHALL SLOPE 1" / FOOT BACK TO LOUVER SO COLLECTED WATER DRAINS BACK INTO LOUVER. PROVIDE WEATHERPROOF SEAL AT LOUVER/PLENUM CONNECTION.

2 SECURE MINISPLIT OUTDOOR UNIT TO STAINLESS STEEL FLORIDA PRODUCT APPROVAL NOA HIGH VELOCITY WIND RATED WALL BRACKET. BRACKET TO BE ANCHORED TO WALL WITH HOT DIPPED GALVANIZED OR STAINLESS STEEL ANCHORS. PROVIDE VINYL

LINE SET COVERS WHERE VISIBLE PER SCHEDULE.

3 ROUTE REFRIGERANT LINES THROUGH WALL AND SEAL WALL PENETRATION WEATHERTIGHT.

4 SUPPORT REFRIGERANT LINES FROM ABOVE. LINES SHALL BE SIZED AS DIRECTED BY THE MANUFACTURER'S REPRESENTATIVE.

REFER TO SCHEDULE AND SPECIFICATIONS.

5 DRIP CONDENSATE ONTO 12" LONG CONCRETE SPLASH BLOCK.

6 SECURE DUCTLESS AIR HANDLER TO WALL WITH TOP 10" BELOW CEILING. ROUTE REFRIGERANT LINES FROM MINI-SPLIT SYSTEM UNITS TO INSIDE FACE OF EXTERIOR WALL AND TURN DOWN TO 20" AFF AND THEN TURN THROUGH EXTERIOR WALL. SEAL WALL

PENETRATIONS WEATHER-TIGHT.

7 MOTORIZED DAMPER INTERLOCKED TO FIRE SUPPRESSION PRE-ACTION SYSTEM.

AM-401

CH1CH2

7' - 0"

7' - 0"

1' - 2"

2' - 6"

2' - 6"

1' - 2"

4"

BT1

CH1

CH2

STRAINER

STRAINER

BT1

CH2 CH1

4"

C.5C.3

BT1

-4' - 0"

7' - 0"

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :2 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-401

ENLARGED HVAC PLANS

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

2'0' 8'4'

2'0' 8'4'

2'0' 8'4'

KEYNOTES

1 PROVIDE 4" HIGH HOUSEKEEPING PAD, 6" LARGER THAN EQUIPMENT EACH WAY.

PAD SHALL HAVE 3/4" CHAMFERED EDGES.

2 PLACE CHILLER ON 6" THICK CONCRETE HOUSEKEEPING PAD 6" LARGER THAN

UNIT EACH WAY (TYPICAL). CONCRETE PAD SHALL HAVE 3/4" CHAMFERED EDGES.

PROVIDE NEOPRENE PADS BETWEEN CONCRETE AND CHILLER BASE.

HVAC CHILLER YARD PLAN

CHILLER YARD ORTHOGRAPHIC

ELEVATION AT CHILLER YARD

NOTE: REFER TO CHILLER PIPING DETAIL

ON DRAWING AM-503 AND THE CHILLED

WATER PIPING SCHEMATIC ON DRAWING

AM-702 FOR PLACEMENT OF CONTROLS

DEVICES AND OTHER HYDRONIC

SPECIALITY COMPONENTS.

4"CHWS&R

CU11 CU12

CHWP1

AS1

24/24

/3

/4

34/20

SS2

10x6

VAV28

VAV25

SR1

12x12

SD

34/20

MECHANICAL

4"CHWR

4"CHWS

AFM AFM

4"CHWR

ET1

CF1

24/20

10/10

1 1

/2

3"BYPASS

SA

RELIEF

OA

VFDA1S

VFDP1

VFDP2

1 1/2"COND

VFDA1R

AM-402

AM-402

DDC

CHWP2

80/28

"ø

ET1

VAV28

AH1

SD

SD

/2

26/92

28/802 /2

EWH1

C.7

7 8

ET1

AS1

20/24

24/24

10/10

CF1

CHWP2 CHWP1

C.7

6 65 5

4"CHWR

11' - 0"

9' - 4 9/32"

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :3 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-402

ENLARGED HVAC PLANS

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

PE 80532

2'0' 8'4'

MECHANICAL ROOM 148

KEYNOTES

1 FABRICATE 10" DEEP PLENUM ON BACKSIDE OF LOUVER. ALL CORNERS OF PLENUM TO BE CONTINUOUSLY WELDED AND ENTIRE

FABRICATION IS TO BE HOT DIPPED GALVANIZED. BOTTOM PANEL SHALL SLOPE 1" / FOOT BACK TO LOUVER SO COLLECTED WATER

DRAINS BACK INTO LOUVER. PROVIDE WEATHERPROOF SEAL AT LOUVER/PLENUM CONNECTION.

2 SECURE MINISPLIT OUTDOOR UNIT TO STAINLESS STEEL FLORIDA PRODUCT APPROVAL NOA HIGH VELOCITY WIND RATED WALL BRACKET. BRACKET TO BE ANCHORED TO WALL WITH HOT DIPPED GALVANIZED OR STAINLESS STEEL ANCHORS. PROVIDE VINYL LINE

SET COVERS WHERE VISIBLE PER SCHEDULE.

3 LOCAL DDC CONTROL PANEL WITH CONTROLS TRANSFORMER. CONTROLS CONTRACTOR TO EXTEND 120V FROM THE NEARBY DEDICATED

CIRCUIT AT J-BOX TO PANEL. REFER TO ELECTRICAL DRAWINGS.

4 LOCATE AIRFLOW MONITOR CONTROLLER ON WALL AT 60"AFF. COORDINATE CABLE LENGTH BETWEEN CONTROLLER AND AIR FLOW

MEASURING SENSOR WITH AFM VENDOR.

5 PROVIDE 4" HIGH HOUSEKEEPING PAD, 6" LARGER THAN EQUIPMENT EACH WAY. PAD SHALL HAVE 3/4" CHAMFERED EDGES.

6 PUMP ON CONCRETE PAD (8" MIN.). REFER TO DETAIL ON DRAWING AM-502. PAD SHALL HAVE 3/4" CHAMFERED EDGES.

7 THE AIR HANDLER SHALL BE PLACED ON A 6" THICK, REINFORCED CONCRETE PAD (6" LARGER EACH WAY THAN THE UNIT) AND AUXILIARY DRAIN PAN WITH FLOAT SWITCH. PROVIDE CONDENSATE TRAP AS DETAILED AND ROUTE INSULATED COPPER CONDENSATE DRAIN LINE TO CONDENSATE HUB DRAIN. SUPPORT DRAIN LINE FROM FLOOR. COORDINATE EQUIPMENT SUPPORT RAIL HEIGHT OF AIR HANDLER TO ALLOW FOR PROPER TRAP DEPTH. PROVIDE CLEANING/OPERATION VALVES ON CONDENSATE LINE (REFER TO THE

CONDENSATE CLEANING AND OPERATION VALVE DETAIL).

8 ROUTE INSULATED COPPER CONDENSATE DRAIN LINE TO CONDENSATE DRAIN. SUPPORT DRAIN LINE FROM FLOOR. COORDINATE EQUIPMENT SUPPORT RAIL HEIGHT OF AIR HANDLER TO ALLOW FOR PROPER TRAP DEPTH. COORDINATE DRAIN LOCATION WITH PLUMBING CONTRACTOR AND SHOW IN THE MECHANICAL ROOM DUCT FABRICATION SHOP DRAWING SUBMITTAL.

SECTION AT AHU

2'0' 8'4'

SECTION AT CHILLER PUMPS

2'0' 8'4'

NOTE: REFER TO CHILLER PIPING DETAIL

ON DRAWING AM-503 AND THE CHILLED

WATER PIPING SCHEMATIC ON DRAWING

AM-702 FOR PLACEMENT OF CONTROLS

DEVICES AND OTHER HYDRONIC

SPECIALITY COMPONENTS.

BRANCH DUCT TAKE-OFF DETAIL

NOT TO SCALE

BRANCH DUCT-SEE

FLOOR PLAN FOR SIZE

AND ROUTING

MANUAL LOCKING

QUADRANT VOLUME

DAMPER

ATTACH WITH SHEET METAL

SCREWS AND SEAL WITH

MEDIUM PRESSURE DUCT

SEALER

USE THIS FITTING WHERE

SPIN-IN FITTING IS LARGER

THAN DUCT OR PLENUM

PLENUM OR DUCT

HEIGHT MINUS 2"

LID

RECTANGULAR TO

ROUND LOW-LOSS

FITTING

PLENUM OR DUCT

R"X W.(4"M1/2n)

TAPERED TAP-IN

FITTING

AIR

FLOW

CONICAL SHAPED

SPIN-IN TYPE

FITTING.

BRANCH DUCT-SEE

FLOOR PLAN FOR

SIZE AND ROUTING

NYLON GROMMETS AT

SHAFT PENETRATIONS

MIN 3/8" CONTINUOUS

SQUARE SHAFT

OC

LOCKING QUADRANT

2" STANDOFF

WINGNUT

MANUAL LOCKING QUADRANT VOLUME DAMPER

NOTES:

1. WINGNUT ON SHAFT IS UNACCEPTABLE.

WINGNUT MUST RIDE IN LOCKING

QUADRANT.

NOTES:

1. PROVIDE FITTING WITH 1" WIDE FLANGE WITH GASKET.

2. MUST MEET SMACNA GUAGE STANDARDS AND 2" W.G.

STATIC PRESSURE.

3. CONTINUOUS WELD LONGITUDINAL SEAM FOR NO LEAKAGE

AT 2" W.G. STATIC PRESSURE.

CONDENSATE DRAIN TRAP

NOT TO SCALE

UNDER NEG. STATIC PRESS.

SLOPE DN

PROVIDE TEE AND SCREW

IN PLUG FOR MAINTENANCE

AHU

X

H

WHERE:

X = H x 0.5

H = TOTAL STATIC PRESSURE + ONE INCH

DOUBLE WALL DUCTWORK HANGER

NOT TO SCALE

NOTE:

PAINT DUCTWORK &

HANGER ASSEMBLY AS

DIRECTED BY THE

ARCHITECT.

ROUND DOUBLE DUCTWORK

GALVANIZED ALL

THREAD ROD SIZED

PER SMACNA

GUIDELINES.

ROUND DUCT

STRAP BRACKET

EQUIVALENT TO

DUCTMATE TYPE

BA.

PAINTED GALVANIZED

STEEL ANGLE TO SPAN

BETWEEN EXISTING

TRUSSES.

DUCT MOUNTED

TEMPERATURE TRANSMITTER

NOT TO SCALE

TRANSMITTER LEAD IN 1/2

INCH CONDUIT

TEMPERATURE TRANSMITTER

WITH SENSING PROBE

SECURE THE TT THROUGH

THE RIGID INSULATION SPACER

USING SM SCREWS

1 INCH THICK RIGID

INSULATION SPACER

SENSING PROBE

DUCT

DUCT INSULATION

EXPOSED DUCTWORK HANGER

NOT TO SCALE

NOTE:

PAINT

DUCTWORK &

HANGER

ASSEMBLY AS

DIRECTED BY

THE ARCHITECT.

ROUND

DUCTWORK

GALVANIZED ALL

THREAD ROD

SIZED PER

SMACNA

GUIDELINES.

ESCUTCHEON

ROUND DUCT STRAP

BRACKET

EQUIVALENT TO

DUCTMATE TYPE

BA.

LAY IN CEILING

FIRE DAMPER DETAILS

VERTICAL FIRE DAMPER

NOT TO SCALE

RATED WALL

10 GAUGE COLLAR

DUCT

DUCT ACCESS

PANEL

STEEL SLEEVE. SEE

TABLE FOR THICKNESS

BREAKAWAY DUCT

CONNECTION

FUSIBLE LINK

WITH LOCK

FIRE DAMPER OUT

OF AIRSTREAM

DUCT

DIMENSION

12" DOWN

13"-30"

31"-54"

1885" UP

55"-84" 20

1-1/2" x 1-1/2" x 1/8"

FULL PERIMETER

RETAINING ANGLE AT

BOTH SIDE OF

ASSEMBLY

NOTE: PROVIDE DYNAMIC TYPE FIRE DAMPERS

ON AIR SYSTEMS THAT DO NOT SHUT DOWN ON

CALL FROM FIRE ALARM OR FIRESTAT.

SLEEVE

GAUGE

FLEXIBLE DUCT RUN-OUTS TO AIR DEVICE

NOT TO SCALE

CEILING

AIR DISTRIBUTION DEVICE

INSULATED GALV.

STEEL LONG RADIUS

ELBOW

INSULATION

DUCT CLAMP

INSULATED SUPPLY AIR DUCT

SUSPENDED FROM ROOF

STRUCTURE

DUCT CLAMP

TAKE OFF WITH DAMPER (UNLESS

PROVIDED WITH AIR DEVICE)

NOTES:

1. REFER TO THE AIR DISTRIBUTION DEVICE SCHEDULE FOR ADDITIONAL REQUIREMENTS.

2. REFER TO SPECIFICATIONS FOR MAXIMUM FLEXIBLE DUCT LENGTH.

3. SUSPEND AIR DEVICE FROM ABOVE, DO NOT SUPPORT FROM CEILING.

4. INTERIOR OF DEVICE TO BE PAINTED FLAT BLACK.

INTERIOR PAINTED

FLAT BLACK.

ROUND FLEX DUCT SHALL BE A MAXIMUM

LENGTH PER SPECIFICATIONS OR 105%

OF THE DISTANCE BETWEEN THE TWO

SHEET METAL DUCT/GRILLE

CONNECTIONS, WHICHEVER IS LESS. ALL

RUNS OF FLEX DUCT ARE TO BE

SUPPORTED WITH THE APPROPRIATE

HANGERS. FLEX DUCT SHALL NOT SAG OR

BE CRIMPED.

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :3 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-501

HVAC DETAILS

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

INLINE FAN DETAIL

DUCT SIZE AS SHOWN

DUCT SIZE AS SHOWN

STEEL CHANNEL (TYP.)

SPRING ISOLATORS (TYP.)

30° MAX. (ANY SIDE)

OR ROOF MOUNT

RELIEF VENT

TO OUTSIDE

AIR LOUVER

TRANSITION TO FULL

SIZE OF INLET AND

OUTLET

DIRECT

DRIVE

INLINE FAN

WITH SPEED

CONTROLLER

BACKDRAFT DAMPER

FROM EXHAUST

GRILLE(S)

30° MAX. (ANY SIDE)

THREADED RODS FASTENED

TO BUILDING STRUCTURE

FLEX CONNECTOR

FLEX CONNECTOR

TRANSITION TO FULL SIZE

OF INLET AND OUTLET

RETURN, EXHAUST AND

TRANSFER DUCT CONNECTIONS

NOT TO SCALE

HORIZONTAL RUN-OUT SHALL BE THE

SIZE INDICATED ON THE PLAN

OR AIR DEVICE NECK SIZE IF SIZE IS

NOT SHOWN ON PLAN.

VERTICAL DROP SHALL BE THE SAME

SIZE AS THE AIR DEVICE NECK SIZE

AS SHOWN IN THE AIR DISTRIBUTION

DEVICE MARKER.

AIR DISTRIBUTION DEVICE (RETURN,

EXHAUST, OR TRANSFER GRILLE)

CHILLED WATER PIPING TRENCH DETAIL

NOT TO SCALE

PATCH AND REPLACE SURFACE

COVER TO MATCH EXISTING

TRACER TAPE INDICATING

TYPE OF SERVICE

PRE-INSULATED PIPING SYSTEM

OR CELLULAR GLASS INSULATION

ON WELDED SCHED. 40 STEEL

PIPE WITH PITTWRAP

6" MIN. SAND ON ALL

SIDES OF PIPE

12" MIN. ROCK

FREE BACKFILL

6" MIN. SAND ON

ALL SIDES OF PIPE

CHILLED WATER END SUCTION PUMP DETAIL

NOT TO SCALE

FLOW VENTURI PIPE INSULATION (TYP.)

BUTTERFLY VALVE (TYP.)

FLEXIBLE CONNECTION (TYP.)

SILENT CHECK VALVE

CHILLED WATER PUMP NOT TO BE INSULATED.

THE CHILLED WATER PUMP TO BE FIELD

PAINTED WITH 2 COATS OF RUSTOLEUM

PAINT, SAFETY RED MODEL 202192

CHILLED WATER PUMP ONLY,

PROVIDE FACTORY INSTALLED

STAINLESS STEEL DRAIN PAN. FIELD

PAINT WITH 2 COATS OF

RUSTOLEUM PAINT, SAFETY RED

MODEL 202192

PUMP FRAME IS NOT TO SET

DIRECTLY ON THE CONCRETE.

INSTALL A 1/8" THICK RED

NEOPRENE PAD BETWEEN THE

FRAME AND THE CONCRETE.

SUCTION DIFFUSER

DRAIN

x

D

IA

A P P R O X

A P P R O X x

D

IA

REFER TO PUMP

BASE DETAIL

25 40

VACUUM PRESS.

3530 25 40

COIL PRESSURE GAGE DETAIL

NEGATIVE PRESSURE POSITIVE PRESSURE

NOT TO SCALE

4 1/2" DIAL

0-60 P.S.I.

GAGE

PULSATION

DAMPENER

COIL PIPE SIPHON

CONNECT AS

SHOWN FOR

SUCTION GAGE

CONNECT TO

SUCTION

PIPE

1/4" I.P.S.

1/4" COCK

COIL PIPE

SIPHON

PULSATION

DAMPENER

4 1/2" DIAL

0-30" HG 0-60

P.S.I.

COMPOUND

GAGE

PUMP BASE

SECTION A-A (BASE POURED ON TOP OF SLAB)

PLAN

SECTION B-B

NOT TO SCALE

PROVIDE #3 BARS, 12" O.C. EACH WAY, IN

THE BASE AND DOWEL BASE TO FLOOR.

CONCRETE BASE TO WEIGH 2.5 TIMES MORE THAN THE WEIGHT OF

THE PUMP ASSEMBLY. TO CALCULATE, APPLY THE MANUFACTURER'S

LISTED PUMP WEIGHT WT.), BASE LENGTH(L) AND BASE WIDTH(W):

THICKNESS = (((PUMP WT. x 2.5) / 150) x 1,728) / (L"+12) x (W"+ 12).

EQUIPMENT BASE PLATE

TYPICAL ANCHOR BOLT,

NUT AND WASHER

A

A

CONCRETE

BASE

ANCHOR

BOLT

(TYPICAL)

B B

WELD HEAD TO PLATE OR

BEND OVER END 5D.

PIPE SLEEVE

(5D, 3" MIN.)

PAD

W

L

M

IN

'3

D

2D

D

5D

NOTE:

1. L AND W DIMENSIONS SHALL BE 6 INCHES

GREATER THAN THE EQUIPMENT BASE PLATE.

25 40

PUMP PRESSURE GAGE DETAIL

NOT TO SCALE

CONNECT TO

SUCTION PIPE

1/4" I.P.S.

1/4" COCK

COIL PIPE SIPHON

PULSATION

DAMPENER

4 1/2" DIAL 0-30"

HG 0-60 P.S.I.

COMPOUND GAGE

CONNECT TO

DISCHARGE PIPE

WATER TREATMENT

CHEMICAL SHOT FEEDER DETAIL

NOT TO SCALE

1-1/4" TO PUMP SUCTION

3" x 3" x 1/4" STEEL PAD

BOLTED TO CONCRETE PAD

1-1/4" TO 1/2" BUSHING

WITH NIPPLE

1-1/4" TEE

10 GALLON MINIMUM 10 GAUGE

TANK SHELL AND HEADS

1-1/2" x 1-1/2" x 1/4"

ANGLE IRON STAND

1-1/4" N.P.T.

REMOVABLE CAP WITH SELF

ALIGNING O-RING SEAL

UNION (TYP.)

1-1/4" BALL VALVE

1-1/4" CHECK VALVE

1-1/4" FROM PUMP

DISCHARGE

1/2" GLOBE VALVE

WITH HOSE COUPLING

6" CONCRETE PAD

1/4" MANUAL AIR

VENT WITH 1/4" N.P.T.

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :3 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-502

HVAC DETAILS

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

AIR HANDLER COIL PIPING (2-WAY VALVE)

MANUAL AIR VENT

THERMOMETER

PRESSURE GAUGE

ARMSTRONG OR GRISWOLD

BALANCING GLOBE VALVE

2-WAY MODULATING

CONTROL VALVE

UNION

BUTTERFLY OR

BALL VALVE

SUPPLY

RETURN

AIRFLOW

DRAIN

T&P PORT

STRAINER

2 WAY MODULATING CONTROL VALVE ON AH1.

CHILLER PIPING DETAIL

NOT TO SCALE

TEST PLUG

FLOW SWITCH

FLEX CONNECTIONS AS

RECOMMENDED BY THE

CHILLER MANUFACTURER

CHILLED WATER

SUPPLY AND

RETURN

CHILLED WATER

DDC TEMP. SENSOR

DRAIN WITH HOSE

CONNECTION NEOPRENE PADS OR

VIBRATION ISOLATORS AS

RECOMMENDED BY THE

CHILLER MANUFACTURER

HOUSEKEEPING PAD

FLANGED BUTTERFLY

ISOLATION VALVE

PRESSURE

GAUGE

THERMOMETER

AIR VENT

Y-STRAINER

TS

CHILLER

HANGER TO STRUCTURE

ATTACHMENT

NOT TO SCALE

HANGER ROD

EYE SOCKET

HEAVY DUTY BEAM CLAMP

STRUCTURAL STEEL BEAM

HANGER

AT STEEL

BEAM

MANUAL AIR VENT

NOT TO SCALE

TYPE "L" COPPER TUBING

DIELECTRIC UNION

PIPE CAP

6" NIPPLE

SYSTEM PIPE

FULL SIZE TEE

GLOBE VALVE MANUAL AIR

VENT. EXTEND VENT LINE

TO WITH IN 6" ABOVE

CEILING WHERE PIPING IS

CONCEALED ABOVE CEILING.

THERMOMETER WELL

NOT TO SCALE

.0

NOTES:

1. LOCATE A TEST WELL AT EACH POINT OF

TEMPERATURE SENSING AND TEMPERATURE CONTROL.

2. THERMOMETER WELLS MUST BE MOUNTED AT 45

DEGREES FROM HORIZONTAL OR VERTICAL WHERE

POSSIBLE, FILL WELLS WITH OIL.

STANCHION SCHEDULE

PIPE SUPPORT STANCHION

NOT TO SCALE

2"

4"

3'-1" TO

6'-0"

1"

2"

1'-0" TO

3'-0"

SUPPORTED

LENGTHPIPE

SUPPORTED

5" & ABOVE

4" & BELOW

GRINNELL FIG. 259 PIPE

STANCHION SADDLE (OR EQUAL)

TACK WELD STANCHION INTO PIPE

AFTER HEIGHT IS ADJUSTED

STEEL PLATE 10"x10"

PIPE SUPPORTED

WELD ALL AROUND

THREAD-O-LET

SCHEDULE 40 STEEL

PIPE SUPPORT

PIPE STANCHION, ADJUST &

ALIGN SUPPORT BEFORE

ANCHORING TO FLOOR

NOTES:

INSULATE STANCHION AND PIPE SUPPORT

ON COLD WATER APPLICATIONS.

SPACING BETWEEN SUPPORTS

SHALL CONFORM TO MSS-SP58.

THREADED STEEL COUPLING

FOR HEIGHT ADJUSTMENT

WELD TO STEEL PLATE

ANCHOR BOLTS

STEEL PIPE THREADED

INTO COUPLING FOR

ADJUSTMENT

L E N G T H

S U P P O R T E D

INSULATED PIPE HANGER SUPPORT

NOT TO SCALE

HANGER ROD

CLEVIS HANGER

INSULATION BARRIER (VAPOR BARRIER

TYPE IS REQUIRED FOR LOW

TEMPERATURE PIPE)

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION INSERT

UNDER INSULATION SHIELD

INSULATION SHIELD AT HANGER

FINANCIAL PROJECT IDCOUNTYROAD NO.

WGI, INC.

3111 W. DR. MARTIN LUTHER KING JR. BLVD.

SUITE 375

TAMPA, FL 33607

DWG NO.

SHEET NO.

FLORIDA-ALABAMA TPO

T H E

O F F

IC

IA

L

R E C O R D

O F

T

E E

E

E L E C T R O

E

D

IG

IT

A L L Y

S

IG

N E D

A N D

S E A L E D

U N D E R

R U L E

G .0 F .A .C

ENGINEERING BUSINESS LICENSE NO.: 33574

G E N E R A L

D

IS

C L A

IM

E R T O

T H E

B E S T

O F

T H E

A R C H

IT

E C T 'S

O R

E N G

IN

E E R 'S

K N O W L E D G E T H E

P L A N S

A N D

S P E C

IF

IC

A T

IO

N S

C O M P L Y

W

IT

H

T H E

A P P L

IC

A B L E

M

IN

IM

U M

B U

IL

D

D E S

A N D

T H E

A P P L

IC

A B L E

F

IR

E

S A F E T Y

S T A N D A R D S

A S

D E T E R M

IN

E D

B Y

T H E

L O C A L

A U T H O R

IT

C O R D A N C E

W

IT

H

F B C

.8 .4 .4

A N D

C H A P T E R

F L O R

ID

A

S T A T U E S

:0 :3 P

M A u to d e s k D o c s .0 E

C R C .0 E s c a m b ia E

C R C W

G

IM

E P F P R

.r v t

AM-503

HVAC DETAILS

ESCAMBIA 451524-1-38-01

NORTH W

STREET

STEPHEN R. FORKNER, PE

AIR DISTRIBUTION DEVICE SCHEDULE

MODULE/FACE SIZE

CONSTRUCTION

NOTES

NECK SIZE

MANUFACTURER **

MARK

- ALUMINUM

1, 2, 4

INCH

INCH

CD1

24x24/-

NOTES:

1. NECK SIZE OF DEVICE IS EQUAL TO THE DUCT SIZE INDICATED ON THE DRAWING.

2. PROVIDE WITH SQUARE TO ROUND ADAPTER. REFER TO PLANS FOR SIZE.

3. THIS AIR DEVICE HAS A CURVED FACE. REFER TO CONNECTING DUCT SIZED FOR FACE DIAMETER.