This document is a sources sought notice from the Department of the Navy Naval Facilities Engineering Command for a design-build contract at the Philadelphia Navy Yard Annex. The notice seeks to determine if there are commercially available and interested suppliers capable of providing various products and services, including:

Card readers, power supply enclosures, access control system dual reader interface (DRI) modules, request to exit devices, electric strikes, translucent wall panels, roof enclosures for cable, fire alarm control panels, flood doors, thermal breaks, fire alarm radio transmitters, fuel oil system equipment, and balanced magnetic switches. The government is requesting a capabilities statement package of no more than 5 pages from interested vendors by May 10, 2024. This is a market research tool, and the government is not obligated to pay for any information received. The notice includes detailed product specifications and requirements for the requested items.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Access Hardware

LNL-1320

Series 3 Dual Reader Interface Module

Overview LenelS2TM offers a Dual Reader Interface (DRI) module for access control solutions. Most access control card readers, keypads, or readers with keypads that use standard Wiegand Data1/Data0 or Clock/Data communication are supported, as are those that support the bidirectional RS-485 Open Supervised Device Protocol (OSDP™). Lock, unlock, and facility code offline access modes are supported on all readers connected to the DRI. Each DRI supports up to 16 different card formats as well as issue codes for both magnetic and Wiegand card formats.

The DRI provides a vital link between the Intelligent System Controller (ISC) and the card reader attached to the interface.

As many as 32 DRI modules can be multidropped using RS- 485 2-wire communication up to 4,000 feet per port away from the ISC. Each DRI module is individually addressed for increased reporting capabilities with OnGuard® access control software applications. The DRI includes eight inputs that support normally open, normally closed, supervised, and non-supervised circuits. In addition, six output relays support fail-safe or fail-secure operation.

Features & Functionality

• 12 or 24 VDC power supply

• Supports Data1/Data0, Clock/Data, Supervised and Unsupervised

F2F and OSDP-compatible RS-485 readers and keypads

• Supports Open Supervised Device Protocol (OSDP) readers, including biometric template transfer and Secure Channel encryption

• Downloadable firmware

• Six Form-C 5 A at 28 VDC relay outputs

• Up to 16 different formats

• Issue code support for magnetic and Wiegand formats

• Door contact supervision (open/closed)

• REX push-button monitor

• Strike control output

• Bicolor reader status LED support and 2-wire LED support

• Beeper control

• Dedicated tamper and power failure circuits

• Support for offline reader access mode

• On-board jumpers for termination

• On-board regulator allows 12 VDC reader support from 24 VDC power source

• DIP switch-selectable addressing

• Advanced Encryption Standard (AES) 128-bit algorithm for communications to ISC

• Compatible with current and previous versions of OnGuard Extended Functionality

• Connect FIPS-201 readers for embedded authentication (when used with LNL-4420 or LNL-X4420 and appropriate HID® and OnGuard software and licenses)

Specifications

Primary Power 12 to 24Vdc ±10%, 550mA maximum (plus reader current) 12Vdc @ 550mA (plus reader current) maximum, 22.5 BTUs 24Vdc @ 330mA (plus reader current) maximum, 27.0 BTUs

Outputs 6 outputs, Form-C contacts: Normally Open (NO) Contact: 5A @ 30 Vdc, Normally Closed (NC) Contact: 3A @ 30 Vdc

Inputs 8 unsupervised/supervised, standard EOL: 1k/1k ohm, 1% 1/4 watt 2 unsupervised, dedicated for cabinet tamper and UPS fault monitoring

Reader Interface Reader power: 12Vdc ±10% regulated, 300mA maximum each reader (jumper selectable and input voltage (VIN) must be 20Vdc minimum) or 12 to 24Vdc ±10% (input voltage passed through) 300mA maximum each reader

Reader Port Compatibility

Wiegand Data 1/Data 0 Magnetic Clock/Data Supervised and Unsupervised F2F Open Supervised Device Protocol

Mechanical Dimension: 6” (152mm)W x 8” (203mm)L x 1” (25mm)H Weight: 11 oz. (312g) nominal

Environmental Temperature

Operating: 32°F to 158°F (0°C to +70°C) Storage: -67°F to 185°F (-55°C to +85°C)

Humidity 5% to 95% RHNC

Compliance Approvals FCC Part 15, CE, RoHS, UL 294, UL 2610

LenelS2.com

(866) 788-5095

Specifications subject to change without notice.

©2023 Carrier. All Rights Reserved. All trademarks and service marks referred herein are property of their respective owners. 2023/06

LNL-1320 Series 3

Intelligent System Controller (ISC) Capacity varies per ISC model*

LNL-1320

Dual Reader Interface Module

LNL-1300

Single Reader Interface Module

LNL-1100

Input Control Module Up to 16 Inputs per

LNL-1100

Motion Sensor Alarm

LNL-1200

Output Control Module Up to 16 Outputs per

LNL-1200

RS-485 Multi-drop up to 4000 ft.

Option 1

TC

P

/I P

N E

TW

O

R K

Reader Reader Reader

Option 2

OnGuard®

Security Server

-OR-

* See ISC datasheets for speci�c capacities.